DESCRIPTION
The Model SRPM Room Pressure Monitor provides a system for monitoring differential pressures in critical low pressure applications. A backlit LCD provides an intuitive graphic user interface for ease of unit, security and alarm setup. Installation costs and on going calibration costs of ownership are signicantly reduced. A red LED, green LED, backlit LCD, local audible alarm and optional remote annunciator alert personnel of the status of the system. A SPDT relay output is also available for additional status indication. Three analog outputs are available in the same unit to interface with BAS system. The Model SRPM is housed in a tough re resistant plastic housing designed for surface mounting. The attractive case ts into Hospital and Pharamceutical applications. Models are available for 120/240 VAC or 24 VAC. The optional SRAN remote annunciator provides a visual and audible warning of room conditions at a remote location. BACNET VERSIONS
FEATURES
Easy, menu-driven programming Large 2" x 2" LCD touch screen display 0.5% accuracy Visual and audible local alarms w/ alarm silence Built in alarm horn with local alarm silence Optional remote annunciator available Selectable analog voltage and milli-amp outputs SPDT alarm relay Red and green room status LEDs Display resolution of 0.001" Door status monitor Variable alarm delay NIST certication included Optional BACnet MSTP
APPLICATION Typical applications include positive-pressure clean rooms such as pharmaceutical processing areas and negative-pressure isolation rooms such as hospital rooms housing contagious patients.
PRESSURE
19
SPECIFICATIONS
Supply Voltage Supply Watts Signal Output 24 VAC 50/60 Hz, 120 VAC 50/60 Hz 5W 0-5 VDC (2.5 V @ 0 pressure) 0-10 VDC (5 V @ 0 pressure) 4-20 mA sourcing (12 mA @ 0 pressure) SPDT, 5A @ 30 VDC, 120 VAC 0.5% FS LCD, 128x128 RGB backlit 0.001" WC Inches of Water ("WC), Pascals (Pa) BACnet
Optional Remote Annunciator Setras SRAN annunciator allows remote indication of room status at monitoring or nurses station. A GREEN LED indicates a normal room condition, a RED LED and audible alarm signal a breach in room pressure status.
Operating Humidity Operating Temperature Enclosure Rating Mounting Process Connection Dimensions Approvals Weight Warranty
Alarm Relay Output Accuracy Display Display Resolution Display Units Protocol
5 to 95% (non-condensing) 32 to 120F (0 to 50C) NEMA 1, Fire retardant plastic Mounts to a 4" x 4" electrical box Barbed ttings for 1/4" OD tubing 8.0"H x 5.4"W x 1.6"D (20.3 x 13.7 x 4.1 cm) CSA C22.2 No. 1010 Safety 1.5 lb (0.69 kg) 1 year
886
2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc.
January 2012
PRESSURE
ROOM PRESSURE MONITOR SRPM
WIRING
PSI
PRESSURE
ORDERING INFORMATION
Model Description SRPM Setra Room Pressure Monitor R05WB 0R1WB R25WB 0R5WB 001WB 2R5WB 005WB 0.05" WC 0.1" WC 0.25" WC 0.5" WC 1.0" WC 2.5" WC 5.0" WC A1 V1 A2 V2 24 VAC Supply voltage 120 VAC Supply voltage 24 VAC Supply, BACnet 120 VAC Supply, BACnet V 0.25% Accuracy 0.5% Accuracy E
19
Example: SRPM-001WB-A1-E SRPM pressure monitor measuring 1.0" W.C. pressure 24VAC supply voltage at 0.5% accuracy.
RELATED PRODUCTS 4" square steel box 1-1/2" deep, 1/2" and 3/4" KO Stainless steel room pressure sensor, 1/4" barb Ivory plastic room pressure sensor, 1/4" barb White plastic room pressure sensor, 1/4" barb Remote annunciator with red and green status LEDs, audible alarm and acknowledge switch 1/4" OD black poly tubing, 1 coil, 250 ft (76 m)
January 2012
2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc.
kele.com
888-397-5353 USA
001-901-382-6084 International
887
PRESSURE
PSI
DESCRIPTION
The PCM Series Pressure Controller is a low air pressure transducer combined with a microprocessor-based proportional or Proportional plus Integral (PI) controller. The compact size and ease of installation and setup makes this unit ideal for standard HVAC applications. Ranges are available from 0-2, 3, or 5 "W.C. The setpoint adjustment knob is clearly marked with the appropriate scale for ease of use. All setup and tuning is easily accomplished by DIP switches and bottle plug jumpers. Mounting is a snap with the convenient mounting tabs or with the DIN rail mounting option. Remote setpoint is also possible with voltage or milliamp signals. The PCM Series can be congured for direct or reverse acting control.
FEATURES
Proportional or PI control Easy setup DIP switch/jumper setup and tuning Selectable proportional band Selectable integral reset rate Direct or reverse acting Optional DIN rail mounting Compact size Position insensitive
DIMENSIONS
in (cm)
0.7 (1.78)
PRESSURE
APPLICATION
Controlling duct pressures Isolation rooms VAV systems Inlet guide vanes and VFDs Paint booths Relief damper control Pressure bypass damper control
Mounting Slots for optional DIN Rail Adapter High Pressure Port Low Pressure Port 2.9 (7.37) 1.5 (3.81)
4.6 (11.68)
19
2.75 (6.99)
SPECIFICATIONS
Supply Voltage Supply Current Signal Output Maximum Output Impedance Local Setpoint Input Remote Setpoint Input Accuracy 24 VDC +15%, -10% 75 mA max 4-20 mA sourcing 650 max Built-in three-wire potentiometer 4-20 mA, 1-5 VDC 2% of range including non-linearity and hysteresis Maximum Overpressure800% of the pressure range Resolution 255 steps Operating Humidity 0% to 90% non-condensing Operating Temperature 32 to 125F (0 to 52C) Process Connection 3/16" dia suitable for 1/4" OD polyethylene tubing Weight 1.3 lb (0.61 kg) Warranty 18 months
890
2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc.
January 2012
PRESSURE
PRESSURE CONTROLLER PCM SERIES
WIRING
PCM DIP SWITCH SETTINGS 1=ON 0=OFF
A1 A2 A3
Local Setpoint 0 1 Remote Setpoint 1 0
1 2 3 4 5 6 7 8
PSI
ON
A
1 2 3 4 5 6 7 8
Direct Acting 1 This Units Reset Per Minute Rate Range Is: Off 0.5 1.0 2.0 0-2" W.C. A4 0 0 1 1 0-3" W.C. A5 0 1 0 1 0-5" W.C. Proportional Throttling Range Settings
10% 20% 35% 50% 65% 80% 90% 100%
Reverse Acting 0
ON
Common
1 2 3 4 5 6 7 8 9 10 11 12
PWM INPUT PWM INPUT REM SPT INPUT LOC SPT POT + LOC SPT INPUT LOC SPT POT FEEDBK INPUT 24 PWR COMMON MA SIG OUTPUT
A6 A7 A8
0 0 0
0 0 1
0 1 0
0 1 1
1 0 0
1 0 1
1 1 0
1 1 1
Local Setpoint Jumper Positions 1, 8, 11 For Remote Setpoint: Voltage Input Jumper Positions 2, 8, 11 Current Input Jumper Positions 1, 8, 11
PRESSURE
ORDERING INFORMATION
MODEL PCM DESCRIPTION Pressure setpoint controller PRESSURE RANGE 020 0-2" W.C. 030 0-3" W.C. 050 0-5" W.C. OPTIONS 47 DIN rail mounting (must be factory installed) 020
19
PCM
47
Example: PCM-020-47 Pressure controller for a 0-2" W.C. range with DIN rail mounting
PAGE 925 925 925 925 925 925 925 925 759
RELATED PRODUCTS Duct static pressure tip, 1/4" compression Duct static pressure tip, 1/4" barb Duct static pressure fitting, 1/4" barb Flange mounting kit (1 required for each A-301-K or A-302-K) Stainless steel room pressure sensor, 1/4" barb Ivory plastic room pressure sensor, 1/4" barb White plastic room pressure sensor, 1/4" barb Surge dampener 1/4" OD black poly tubing, 1 coil, 250 ft (76 m)
January 2012
2012 Kele, Inc. All rights reserved. The Kele name and logo are registered trademarks of Kele, Inc.
kele.com
888-397-5353 USA
001-901-382-6084 International
891
28
159 Swanson Road, Boxborough, MA 01719, Tel: 800-257-3872; Fax: 978-264-0292; Email: sales@setra.com; Web: www.setra.com SS-SRPM Rev. A 5/1/2008
Contents
1.0 Introduction .........................................................................................................5
1.1 Intended Use......................................................................................................................................... 5 1.2 SRPM Function ..................................................................................................................................... 5
12.0 Electrical Power 1) Model SRPM-XXXXX-V1-X For the high voltage model the input voltage range is from 85 VAC to 265 VAC, 50 Hz or 60 Hz All the internal supply voltages are generated using the Switching Mode Power Supply (SMPS). All the internal supply voltages and their ratings as follows: Internal Supply Voltage +5 V +3.3 V +15 V Max. Current Consumption 800 mA 200 mA 200 mA
2.) Model SRPM-XXXXX-A1-X For the lower voltage model the input voltage range is from 18 to 32 VAC, 50 Hz or 60 Hz All the internal supply voltages and their ratings as follows: Internal Supply Voltage +5 V +3.3 V +15 V Door Status Switch Current Consumption 800 mA 200 mA 200 mA SPDT or SPST NO
27
Contents (contd)
7.5 SETUP ALARM SCREEN .............................................................. 21
7.5.1 Alarm Setup Operation ......................................................................................................21 7.5.2 Entering Data.........................................................................................................................21 7.5.2.1 Mute Time Out/Alarm Delay ..................................................................................21 7.5.3 Data Entry Screen.................................................................................................................21
Thermal Effects**
Compensated Range F (C) 0.03% FS (0.05% FS) Overpressure 1 psi * RSS of Non-Linearity, Non-Repeatability and Hysteresis **Units calibrated at nominal 70F. Maximum thermal error computed from this datum.
Environment Data
Temperature Operating* F (C) Storage F (C) Operating Humidity *Operating temperature limits of the electronics only. +32 to 120 (0 to +50 -20 to +160 (-30 to 70) 5 to 95% RH (Non-condensing)
Physical Description
Case Dimensions Electrical Connection Pressure ttings Weight (approx.) Mounting Display LCD Status Indicators Fire Retardant Plastic (NEMA 1 Rated for Indoor Applications) 8H x 5.4W x 1/8D (20.3H x 13.7W x 4.1D cm) Removable Terminal Block Barbed Fittings for 1/4 Tubing 1.5 lbs (680g) (Mounts to double gang electrical box.) 128 x 128, RGB Backlit Green LED, Normal; Red LED, Alarm; Backlit LCD 3-Wire (Exc., Out, Com) 0 to 5 VDC 0 to 10 VDC 85-265 VAC, 50-60 Hz 18- 32 VAC, 50-60 HZ 5W SPDT Relay 1A @24 VDC 1A @ 120 VAC
8.8 Pressure Monitoring Screens ................................................................23 9.0 Maintenance ...........................................................................................25 9.1 Cleaning ..................................................................................................25 10.0 Agency Electrical Standards ................................................................25 11.0 SRPM Specications ...........................................................................26 12.0 Electrical ................................................................................................27 13.0 RETURNING PRODUCTS FOR REPAIR ..................................................28 14.0 Warranty and Limitations of Liability .................................................28
*Calibrated into a 50K ohm load, operable into a 5000 ohm load or greater.
2-Wire 4 to 20 mA 0 to 510 ohms 85-265 VAC, 50-60 Hz 18- 32 VAC, 50-60 HZ Air or Nonconductive, Nonexplosive Gases.
26
9.0 Maintenance The SRPM is designed to operate in an indoor environment, monitoring clean, dry (see humidity specications) air. 9.1 Cleaning Important
Do not blow into the pressure tubing or ttings with mouth. Compressed air, or canned air. Such actions may permanently damage the pressure sensor. Cleaning your SRPM Do not clean or wash-down the SRPM with industrial cleaners or solvents. The housing may be wiped down with soap and water or isopropyl alcohol; and, the LCD display with isopropyl alcohol only. Do not immerse unit.
For 120/240 VAC Version, only CAUTION: Do not open or remove SRPM cover (tool required) with input power applied unless performed by a licensed electrician. Hazardous Live voltage is present at connector J3 when power is applied. Please observe the warning symbol ( ! ) near the J3 power connector.
25
7.0 Model SRAN Remote Annunciator Setras Remote Annunciator (SRAN) provides remote indication of room status.
1.0 Introduction
Congratulations, and thank you for purchasing Setras Room Pressure Monitor (Model SRPM). Its ease of operation and durable construction will provide years of reliable service. While the SRPM is easy to operate, it is advisable to read this guide carefully before use. It is designed to help you take full advantage of the function and performance of the SRPM. 1.1 Intended Use The SRPM is designed to monitor critical air environments, providing room static pressure indication, alarming, and communication functions. The applications include: 1.) hospitals - patient isolation and protection rooms, operating suites, intensive care and emergency rooms. 2.) pharmaceutical, semiconductor, and precision manufacturing and clean rooms. 3.) laboratories - medical research and BSLs (Bio-Safety Labs), radiation, toxic metals and chemicals.
Audible Alarm
Green LED
Visual indication of normal room condition Visual Indication of a breach in room pressure protection. Buzzer sounds to indicate a breach in room pressure protection Press to Silence the buzzer.
Red LED
1.2 SRPM Function The SRPM senses very low differential pressure using Setras patented, high accuracy capacitive sensor technology. The pressure difference for these application is the difference in static pressure between a critical environment room and its surrounding reference area ( usually a hallway or another room) see Figure 1. Maintaining and monitoring a static room pressure difference insures that the critical environment room is either protected or isolated from a surrounding environment. Protection strategy requires a net positive room static pressure difference, while isolation requires a net negative static pressure difference. The SRPM can be programmed to monitor either positive or negative room static pressure. The SRPM low pressure sensing technology is coupled with multifunctional alarming and simple, intuitive touch-screen user interface with selectable security protection.
Audible Alarm
Under normal conditions the Green LED remains on. When an alarmed condition occurs (i.e., room pressure falls outside preset range), a signal is triggered by the SRPM, the Green LED shuts off, the Red LED ashes and the Audible Alarm sounds. The acknowledge button can be pressed to momentarily turn-off the Audible Alarm and the Red LED will continue to ash until the alarmed condition is corrected. When the alarmed condition is corrected the annunciator will reset itself. The Green LED will turn-on, the Red LED and Audible alarm will shut-off.
24
Qty
(1) (2) (2) (4) Setra SRPM assembly Barbed Coupling, Brass 1/4 inch Tube, Silicone, Inter-Connect 6-32 x 1/2 Mounting Screws for SRPM Base
Not Included: Supplied by User (2) Single Gang Electrical Box for RPS Plates (1) Double Gang Metal Electrical Box with Grounding Stud (1) 4 x 4 inch Metal Plaster Ring (1) Door Switch SPDT or SPST, N.O., as needed 1.2 Model SRAN (Option) Parts List Qty (1)
Normal room pressure condition within limits turns screen to yellow when door is open, indicating Pre-alarm.
Annunciator Assembly
Not Included: Supplied by User (1) Single Gang Electrical Box 1.3 Accessories (Option) Parts List Qty (2)
Part # RPS, Static Pressure Fitting Plate Room static pressure outside preset limits is indicated by a Red screen after expiration of alarm time delay.
Not Included, Supplied by User (2) Single Gang Electrical box for RPS Plates
23
Installation Instructions
7.6.1 Self Test Operation
This screen identies the Product Model and Software Version. User can also perform a Self Test of the SRPM to verify that the data in memory hasnt been corrupted and also test the alarm to verify the sound level and alarm setup. Press Power On Self Test button to initiate test sequence. Press Test Alarm to test buzzer and visual Red LED Alarm. Press Exit to return to Main Menu.
22
Enter numbers by pressing each key in sequence until the desired character is displayed in the data entry box above the keypad. (Note: The cursor will blink for one to two seconds then stop and display the character.) Erase any mistakes by using the Back Space key. When nished entering data, Press Enter key and return to SETUP UNIT screen, press Save and Exit to return to MAIN MENU, then press Back to return to PRESSURE MONITORING SCREEN. Example: Enter number 3, press (or tap) 3/DEF key once Enter the letter T, press (or tap) the 8/STU key three times in succession.
Note: Use the eraser end of a pencil or back-end of a pen to press (or tap) box on screen to increase accuracy of inputs.
21
CAUTION: Do not open or remove SRPM cover (tool required) with input power applied unless performed by a licensed electrician. Hazardous Live voltage is present at connector J3 when power is applied. Please observe the warning symbol ( ! ) near the J3 power connector.
7.4.1 Setup Room Operation Monitor either protective positive room static pressure or isolating negative room static pressure. 7.4.2 Entering Data Press lightly or tap Positive Room or Negative Room button. Background of selection will change from clear to black, then enter high and low limits as follows:. Simply press lightly (or tap) either the Positive Room or Negative Room box to activate the Data Entry Screen (see 7.4.3.), then proceed to enter the low and high limits of the room pressure to be monitored. Save and Exit. 7.4.3 Data Entry Screen
Enter numbers by pressing each key in sequence until the desired character is displayed in the data entry box above the keypad. (Note: The cursor will blink for one to two seconds then stop and display the character.) Erase any mistakes by using the Back Space key. When nished entering data, Press Enter key to return to SETUP UNIT screen, press Save and Exit to return to MAIN MENU, then press Back to return to PRESSURE MONITORING SCREEN. Example: Enter number 3, press (or tap) 3/DEF key once Enter the letter T, press (or tap) the 8/STU key three times in succession.
Note: Use the eraser end of a pencil or back-end of a pen to press (or tap) box on screen to increase accuracy of inputs.
The Setra Room Pressure Monitor is designed to be mounted on a standard double gang metal electrical box using a 4 x 4 inch plaster ring adaptor. Remove the SRPM cover and mount the baseplate to the plaster ring adaptor using (4) 6-32 1/2 inch long mounting screws, see Figure 2. Note: The plaster ring external mounting face needs to be positioned ush to recessed, relative to the surface of the wall. Also note the orientation of the 4 mounting screws in the plaster ring, the plaster ring is rotated 90 from conventional mounting.
Electrical Box 4 x 4 inch Plaster Ring (Rotated 90) SRPM Metal Base SRPM Cover Figure 3: Mounting the SRPM 3.2 Wiring Electrical box (rough in) Pre-wire electrical box with power (24 VAC or 120/240 VAC depending on SRPM model ), and provide grounding to the electrical box and plaster ring adaptor. Note: For CSA Safety Certication it is necessary to ground the metal electrical box to building earth ground. The safety ground path consists of the (4) 6-32 x 1/2 metal screws that connect the RPM metal base to the 4 x 4 metal plaster ring. The plaster ring is grounded to the 4 x 4 electrical box Mounting Screws (x2) by 2 mounting screws. Figure 4: 4 x 4 Electrical Box Power leads and wiring should be 14 to 22 AWG braided wire. 18 AWG braided wire is recommended for wiring J3 power connector to SRPM (see J3, Figure 2). For 120/240 VAC the hot wire connects to H and neutral to L.
20
Figure 6: Silicone & RPS Tubing connected by barbed Male to Male Tubing Adaptor Electrical Box
Silicone Tubing RPS Tubing SRPM Header H1 Figure 7: Example of Completed Tube Installation
Example:
10
19
4.0 Model SRAN Room Annunciator Installation 4.1 Alarm Relay Output
The Single Pole Double Throw (SPDT) relay output can be used for remote signaling of alarm condition. A form C contact rated at 1A is available. Connect to J4, Pins 1 and 4. 4.1.1 Model SRAN Remote Annunciator Wiring (see Figure 8 below or Figure 2, pg. 8) Remote Annunciator Connector (J1), SRPM Connector J4: Connect pins 1 & 2 (short) and then connect pin 2 (+15 V Exc.), pin 3 (Ground, pin 4 (Annunciator Trigger).
J1: SRAN
+15 VDC Excitation A1 Ground A2 +15 VDC Trigger A3 Jumper
J4: SRPM
P4 (Annunciator Trigger P3 (Ground) P2 (+15 VDC Excitation) P1 (Relay N.O.)
Button
Setup Unit
Description
Setup password, output, engineering units, and display averaging Setup high and low pressure limits to monitor positive or negative room Setup latch alarm, audible alarm, door alarm input, mute time out, alarm delay, and volume Identies product model and software version. Veries SRPM operation and alarm sound level and setup Perform zero and span calibration Returns to monitoring screen
Figure 8: Model SRAN Wiring 4.1.2 Non-Setra Remote Annunciator The SRPM can drive other annunciators that are powered by a 15V supply, 50 mA max., and accept a 15V trigger. If purchased separately, the SRAN can also be driven as shown in Figure 9. Power Supply 15 VDC
Setup Room
Setup Alarm
J1
+15 VDC Excitation A1 Ground A2 +15 VDC Trigger A3
Self Test
Calibration Back
18
11
4.2 Audible Alarm Alarm potentiometer adjusts from 0 to 85 dBA. Using a screwdriver, rotate potentiometer clockwise to increase volume and counterclockwise to decrease volume.
Figure 10: Model SRAN PC Board View 5.0 Door Status Switch Wiring ( see Figure 2, J6) 5.1 Wiring
Use normally open (N.O.) side of contact switch. The RPM will indicate status of door position. A contact closure indicates that the door is closed. This is a low voltage circuit (5 VDC).
Welcome Screen
Monitoring Screen
The actual room static pressure is shown as a number on the LCD and visually as a Moving Bar indicator operating between the preset alarm units. The Vertical Bar is an indicator of the pressure.
Button
Silence Menu Reset
Description
Shuts off Alarm Access to setup functions Resets the unit in Latched mode. See Alarm Setup Screen.
12
17
WelcomeScreen
LOGIN
Enter Password Usr! OK Wrong Password Entered, Re-enter the Password Cancel
16
Menu Button Pressed
LOGIN
Enter Password
MENU
Setup Unit
Setup Room
Setup Alarm
Self Test
Calibration
Back
OK
Cancel
OK
Cancel
Login Sreen
CALIBRATION MENU
Negative Room
-0.026 WC
Apply Zero ZERO Pressure Apply Full Scale SPAN Pressure Restore Exit Factory Setting
Cancel
Door Open
-0.04
Reset
Silence
Pressure falls outside of preset limits (alarmed state), the screen is Red
3 Common
2 C Out 4 to 20 mA
1 V Out 0 to 5, 0 to 10 VDC
6.1 Analog Output (J5) SRPM can be congured as current (4 to 20 mA) or voltage (0 to 5 or 0 to 10 VDC). Voltage output pin 1, Current output pin 2, Common pin 3. Note. No external excitation is required.
13
14
15