Beruflich Dokumente
Kultur Dokumente
Mechanical Specification
General
Unit shall be assembled on heavy gauge steel mounting/lifting rails and shall be weatherproof, Units shall include a hermetic scroll compressor (s), fin and tube condenser coil, fans and motors, controls and fully charge of R-22. Units rated in accordance with ARI Standard 590-92.
Controls
The chiller shall be completely factory-wired with necessary safety control or terminal block for power wiring in a weather-tight enclosure. Control shall control up to maximum of 4 compressors, automatically balanced for their loading. Water temperature display can be interchangeable between degree C and F. Additional digital wired display can be connected to PCB as remote display in control room. Safety control shall include high and low pressure switches with manual reset, compressor timer delay, water temperature error sensor, and display for error codes.
Chilled Water Air Handling Unit BDHA/CB Model 2,000 - 8,000 CFM
Casing
Unit casing shall be constructed of 18 gauge zinc coated heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized and finished with a polyester powder painting and weather-resistant baked enamel finish. Units surface shall be tested 500 hours in salt spray test. Units shall have removable end panels which allow access to all major components and controls.
Besides CGAT chillers, Trane offers a complete range of chilled water terminals to be integrated in any type of installation
Evaporator
The evaporator shall have independent refrigerant circuit. The evaporator shall be brazed plate heat exchanger. For units with two evaporators, the connecting water manifold shall be provided. Evaporator shall be insulated with a 1" closed-cell insulation.
CFEB Convertible Chilled Water Fan Coil 400-2,000 CFM Tall Floor: Yukon HFWB 1,500-4,000 cfm
CGAT065-105 model shall have a single refrigeration circuit with an intergral subcooling circuit. CGAT065-105 shall have both a liquid line and suction gas line access valve with gauge port and one direct drive hermetic scroll compressor with centrifugal oil pump providing positive lubrication to moving parts. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Internal temperature and current-sensitive motor overloads shall be included for maximum protection. Scroll type compressor shall provide inherently low vibration and noise by having no suction and discharge valves. External high, low pressure cutout devices and filter drier shall be provided.
New PCB
Condenser Coil
Coil shall be internally finned of smooth bore 3/8 copper tubes mechanically bonded to configured aluminum plate fin as standard. Factory pressure and leak tested to 375 psig air pressure. New Digital Wired Display
Accessories (Optional)
Copper fin/Blue fin or Aeris coating shall protect corrosion on sea coast application. Wire Guard : Protect coil from delivery damage Digital Room Thermostat for fan coil unit : fully communicates with CGAT PCB to provide optimum comfort to room occupations
10.00
5-18 TONS 50 Hz
Trane optimizes the performance of home and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable, and energy efficient environments, Trane offers a broad portfolio of advance controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.tranethailand.com
1.00 10.0
CGAT-SLB001
100.0
General Data Model Unit Performance Cooling Capacity (1) MBH Main Power supply V/Ph/Hz Min.Brch.Cir.Ampacity A No.of Refrigerant circuits Compressor Type Number Used Rated Amps (2) A Locked rotor Amps (2) A Evaporator Type Water flowrate GPM Water Connections Type Diameter Outdoor Coil Type Tube size inch Rows # Fins per inch (fpf) # Outdoor Fan Type Number Used Diameter inch Drive type Air flow CFM Fan Motor Number Used Motor Output (1) Watt Rated Amps (1) A Locked rotor Amps (1) A Dimensions Height mm Width mm Depth mm Weight uncrated kg R-22 Refrigerant Charge (2) kg CGAT065 CGAT085 CGAT105 CGAT135 CGAT175 CGAT215
Performance Data -Cooling capacity Entering air temperature on condensing coil 75 deg.F Model LWT deg.F 42 44 45 46 48 50 42 44 45 46 48 50 42 44 45 46 48 50 42 44 45 46 48 50 42 44 45 46 48 50 42 44 45 46 48 50 85 deg.F 95 deg.F 105 deg.F
65.2 86.3 104.4 133.1 175.4 214.9 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 18.1 27.3 29.9 32.7 49.4 54.2 1 1 1 2 2 2 Hermetic Scroll 1 2 22.9 13.6 145.0 98.0
Cooling Water flow Cooling Water flow Cooling Water flow Cooling Water flow Capacity rate Capacity rate Capacity rate Capacity rate MBH US gpm MBH US gpm MBH US gpm MBH US gpm 68.2 70.5 72.4 74.3 75.1 78.5 90.6 94.4 96.3 98.2 98.9 102.4 111.1 114.9 116.0 116.0 119.0 122.8 140.3 145.6 147.5 149.4 153.2 157.0 186.1 192.2 195.2 197.1 204.0 208.1 223.7 229.7 233.5 237.3 241.9 249.1 13.6 14.1 14.5 14.9 15.0 15.7 18.1 18.9 19.3 19.6 19.8 20.5 22.2 23.0 23.2 23.2 23.8 24.6 28.1 29.1 29.5 29.9 30.6 31.4 37.2 38.4 39.0 39.4 40.8 41.6 44.7 45.9 46.7 47.5 48.4 49.8 66.7 68.2 69.0 70.9 71.7 75.1 87.2 91.0 92.1 92.1 95.2 98.9 104.3 108.0 109.9 111.8 115.6 119.4 135.0 138.8 140.7 142.5 146.3 150.1 177.8 183.1 185.8 189.6 194.1 197.9 213.4 219.5 223.3 227.1 231.6 238.8 13.3 13.6 13.8 14.2 14.3 15.0 17.4 18.2 18.4 18.4 19.0 19.8 20.9 21.6 22.0 22.4 23.1 23.9 27.0 27.8 28.1 28.5 29.3 30.0 35.6 36.6 37.2 37.9 38.8 39.6 42.7 43.9 44.7 45.4 46.3 47.8 63.3 64.8 65.2 67.5 68.2 71.7 83.8 85.3 86.3 88.0 91.7 92.1 100.8 103.5 104.4 105.8 108.8 112.6 128.1 131.9 133.1 135.7 139.5 146.7 169.1 172.9 175.4 179.3 183.9 187.7 203.2 209.3 214.9 216.0 221.0 225.2 12.7 13.0 13.0 13.5 13.6 14.3 16.8 17.1 17.3 17.6 18.3 18.4 20.2 20.9 20.9 21.2 21.8 22.5 25.6 26.4 26.6 27.1 27.9 29.3 33.8 34.6 35.1 35.9 36.8 37.5 40.6 41.9 43.0 43.2 44.2 45.0 59.9 61.4 62.2 64.1 64.8 68.2 78.5 80.8 82.6 84.5 85.3 88.7 94.0 97.8 99.7 101.6 105.4 105.8 121.3 125.1 127.0 128.9 132.7 136.5 158.8 164.9 167.9 169.8 173.6 177.4 191.5 196.8 199.4 203.2 207.8 215.0 12.0 12.3 12.4 12.8 13.0 13.6 15.7 16.2 16.5 16.9 17.1 17.7 18.8 19.6 19.9 20.3 21.1 21.2 24.3 25.0 25.4 25.8 26.5 27.3 31.8 33.0 33.6 34.0 34.7 35.5 38.3 39.4 39.9 40.6 41.6 43.0
2 20.7 130.0
2 22.9 145.0
CGAT065
With CGAT chillers, you will find an answer to fit all your applications, whether it is comfort or process cooling.
Brazed-plate Brazed-plate Brazed-plate Brazed-plate 20.9 26.6 35.1 43.0 Male 1 1/2" Male 1 1/2" Male 1 1/2" Male 1 1/2" CGAT085
Installation
All chillers are completely factory-wired with necessary capacity and safety controls, enclosed in a weather-tight control panel with knockouts for jobsites fully assembled, tested, charged and ready to provide chilled water. No messy field assembly or refrigerant charging is required. Further, the unit has been designed for a single power and water connection.
Easy Service
Our design allows you to remove any or all panels for service. We have paid careful attention to service details, and all units feature coded wiring, hinged control boxes, and mechanical controls for easy service.
Corrugate Fin Corrugate Fin Corrugate Fin Corrugate Fin Corrugate Fin Corrugate Fin 3/8 3/8 3/8 3/8 3/8 3/8 2 2 2 2 2 2 16 (192) 16 (192) 16 (192) 16 (192) 16 (192) 16 (192) Propeller 1 28 Direct 4900 1 290 1.06 2.27 1050 950 1060 181 4.0 Propeller 1 28 Direct 5800 1 420 1.41 3.53 1050 950 1060 204 4.3 Propeller 1 28 Direct 6800 1 300 1.32 2.80 1050 950 1060 250 6.0 Propeller 2 28 Direct 9800 2 290 1.06 2.27 1050 2200 1050 406 4.0 Propeller 2 28 Direct 11600 2 420 1.41 3.53 1050 2200 1050 452 5.0 Propeller 2 28 Direct 13600 2 300 1.32 2.80
CGAT105
CGAT135
Notes: (1) per motor (2) per circuit (3) Product design and specification are subject to change without notice.
Notes : 1. Ratings based on ARI Standard 590-92 2. Data based on 10 deg.F water temperature rise 3. LWT - Leaving Water Temperature 4. Product design and specification are subject to change without notice.
CGAT-SLB001 CGAT-SLB001