3RT12 65 S10
3RT12 66 S10
General data
Permissible mounting position The contactors have been designed for operation on a vertical mounting surface. Mechanical endurance
NSB01350
Electrical endurance Rated insulation voltage Ui (pollution degree 3) Rated impulse withstand voltage Uimp Safe isolation between coil and main contacts (to DIN VDE 0106 Part 101 and A1 [Draft 2/89]) Positively-driven/mirror contacts Positively-driven operation applies when the NC and NO contact cannot be closed at the same time. Permissible ambient temperature For operation For storage Rectangular pulse Sine pulse C C g/ms g/ms V kV V
1000 8 690 Yes, between main contacts and auxiliary NC contacts as well as within the auxiliary switch blocks to ZH 1/457, IEC 60947-4-1, Appendix F -25 ... +60/+55 with AS-Interface -55 ... +80 IP00/open, coil assembly IP20 8.5/5 and 4.2/10 13.4/5 and 6.5/10
2) 3)
Degree of protection to IEC 60947-1/IEC 60529 Shock resistance Conductor cross-sections Electromagnetic compatibility (EMC)
Short-circuit protection
Main circuit Fuse-links gL/gG NH 3NA, DIAZED 5SB, NEOZED 5SE to IEC 60947-4-1/EN 60947-4-1 Type of coordination "1" Type of coordination "2" Weld-free 4) Auxiliary circuit Fuse-links, gL/gG DIAZED 5SB, NEOZED 5SE (weld-free protection for Ik 1 kA) or miniature circuit-breaker with C characteristic (short-circuit current Ik 400 A) 1) See Page 2/16 2) See Page 2/66 3) See Page 2/9 4) Standard conditions for testing in accordance with IEC 60947-4-1.
A A A A
Control circuit
Operating range of the solenoid AC/DC (UC) Power consumption of the solenoid (when coil is cool and rated range Us min ... Us max) Conventional operating mechanism - AC operation Closing at Us min Closing at Us max Closed at Us min Closed at Us max Closing at Us min Closing at Us max Closed at Us min Closed at Us max W W W W VA/p.f. VA/p.f. VA/p.f. VA/p.f. W W W W DC 24 V/ 30 mA power consumption (operating range DC 17 ... 30 V) 460 630 3.4 4.2 420 /0.8 570 /0.8 4.3 /0.8 5.6 /0.8 580 700 6.8 8.2 Closing at Us min Closing at Us max Closed at Us min Closed at Us max Closing at Us min Closing at Us max Closed at Us min Closed at Us max VA/p.f. VA/p.f. VA/p.f. VA/p.f. 530 /0.9 630 /0.9 6.1 /0.9 7.4 /0.9
- DC operation
- DC operation
PLC control input (EN 61131-2/type 2) Operating times (Total break time = Opening delay + Arcing time) Conventional operating mechanism - 0.8 x Us min ... 1.1 x Us max - for Us min ... Us max Closing delay Opening delay ms ms 35 ... 50 50 ... 80 Solid-state operating mechanism, operation via A1/A2 - 0.8 x Us min ... 1.1 x Us max - for Us min ... Us max Closing delay Opening delay Closing delay Opening delay Closing delay Opening delay ms 10 ... 15 ms ms 50 ... 65 80 ... 100 ms ms 45 ... 80 80 ... 100 ms ms 110 ... 130 80 ... 100 Solid-state operating mechanism, operation via PLC input - 0.8 x Us min ... 1.1 x Us max - for Us min ... Us max Arcing time Closing delay Opening delay ms ms 105 ... 145 80 ... 100 Closing delay Opening delay ms ms 30 ... 95 40 ... 80
Minimum conductor cross-section for loads with Ie Utilization category AC-2 and AC-3 Rated operating currents Ie Rated output power for slipring or squirrel-cage motors at 50 Hz and 60 Hz
Thermal load rating Power loss for each conducting path Utilization category AC-4 (for Ia = 6 x Ie) Rated operating current Ie Rated output power for squirrel-cage motors at 50 Hz and 60 Hz 110 132 The following applies to contact endurances of about 200,000 operating cycles: - Rated operating currents Ie - Rated output power for squirrelcage motors at 50 Hz and 60 Hz 30 55 68 94 95 37 65 81 112 114 for 230 V 400 V 500 V 690 V 1000 V kW kW kW kW kW up to 690 V 1000 V A A 97 68 115 81 140 98 45 79 98 138 140 for 400 V kW 160 up to 690 V A 195 230 280
Utilization category AC-6a, switching of AC transformers Rated operating current Ie For inrush current = 20 For inrush current = 30 Rated output power P For inrush current = 20 for 230 V 400 V 500 V 690 V 1000 V for 230 V 400 V 500 V 690 V 1000 V kVA kVA kVA kVA kVA 74 128 160 221 320 kVA kVA kVA kVA kVA 111 193 241 332 482 up to 690 V up to 690 V A A 278 185
For deviating inrush current factors x, the power must be recalculated as follows: Px = Pn 30 30/x Utilization category AC-6b, switching low-inductance (low-loss, metallized dielectric) AC capacitors Ambient temperature 40 C Rated operating currents Ie Rating of single capacitors or banks of capacitors (minimum inductance between 6 H connected in parallel capacitors) at 50 Hz, 60 Hz and up to 500 V for 230 V 400 V 500 V 690 V A kvar kvar kvar kvar 220 88 152 191 152
Operating frequency
Operating frequency z in operating cycles/hour Contactors without overload relay Dependence of the operating frequency z' on the operating current I' and operating voltage U': z' = z (Ie/I') (400 V/U')1,5 1/h Contactors with overload relay (mean value) 1) Industrial furnaces and electric heaters with resistance heating, for example (increased power consumption on heating up taken into account). No-load operation frequency AC-1 AC-2 AC-3 AC-4 h-1 h-1 h-1 h-1 h-1 h-1 2000 800 300 750 250 60 2000 750 250 750 250 60 2) In accordance with EC 60947-4-1. For rated values for different start-up conditions see Protection devices: Overload relay -> SIRIUS overload relay.
NSB00481
General data
Permissible mounting position The contactors have been designed for operation on a vertical mounting surface. Mechanical endurance
1)
Oper- 10 million ating cycles V kV V 690 Yes, between main contacts and auxiliary NC contacts as well as within the auxiliary switch blocks to ZH 1/457, IEC 60947-4-1, Appendix F C C IP00/open, coil assembly IP20 g/ms g/ms 8.5/5 and 4.2/10 13.4/5 and 6.5/10
2) 3)
Electrical endurance Rated insulation voltage Ui (pollution degree 3) 1000 8 Rated impulse withstand voltage Uimp Safe isolation between coil and main contacts (to DIN VDE 0106 Part 101 and A1 [Draft 2/89]) Positively-driven/mirror contacts Positively-driven operation applies when the NC and NO contact cannot be closed at the same time. Permissible ambient temperature Degree of protection to IEC 60947-1/IEC 60529 Shock resistance Conductor cross-sections Electromagnetic compatibility (EMC) Rectangular pulse Sine pulse For operation For storage -25 ... +60/+55 with AS-Interface -55 ... +80
Short-circuit protection
Main circuit Fuse-links gL/gG NH 3NA, DIAZED 5SB, NEOZED 5SE - to IEC 60947-4-1/EN 60947-4-1 Type of coordination "1" Type of coordination "2" Weld-free 4) A 10 A A A 800 800 500
Auxiliary circuit Fuse-links, gL/gG DIAZED 5SB, NEOZED 5SE (weld-free protection for Ik 1 kA) or miniature circuit-breaker with C characteristic (short-circuit current Ik < 400 A) 1) See Page 2/16 2) See Page 2/49 3) See Page 2/9 4) Standard conditions for testing in accordance with IEC 60947-4-1.
Control circuit
Operating range of the solenoid Power consumption of the solenoid (when coil is cool and rated range Us min ... Us max) Conventional operating mechanism - AC operation Closing at Us min Closing at Us max Closed at Us min Closed at Us max Closing at Us min Closing at Us max Closed at Us min Closed at Us max W W W W VA/p.f. VA/p.f. VA/p.f. VA/p.f. W W W W DC 24 V/ 30 mA power consumption (operating range DC 17 ... 30 V) 600 800 4 5 560 /0.8 750 /0.8 5.4 /0.8 7 /0.8 770 920 8.5 10 Closing at Us min Closing at Us max Closed at Us min Closed at Us max Closing at Us min Closing at Us max Closed Us min Closed Us max VA/p.f. VA/p.f. VA/p.f. VA/p.f. 700 /0.9 830 /0.9 7.6 /0.9 9.2 /0.9
- DC operation
- DC operation
PLC control input (EN 61131-2/type 2) Operating times (Total break time = Opening delay + Arcing time) Conventional operating mechanism - 0.8 x Us min ... 1.1 x Us max - for Us min ... Us max Closing delay Opening delay Closing delay Opening delay Closing delay Opening delay Closing delay Opening delay Closing delay Opening delay ms 10 ... 15 ms ms 65 ... 80 80 ... 100 ms ms 60 ... 90 80 ... 100 ms ms 125 ... 150 80 ... 100 ms ms 120 ... 150 80 ... 100 ms ms 50 ... 70 70 ... 100 Solid-state operating mechanism, operation via A1/A2 - 0.8 x Us min ... 1.1 x Us max - for Us min ... Us max Solid-state operating mechanism, operation via PLC input - 0.8 x Us min ... 1.1 x Us max - for Us min ... Us max Arcing time Closing delay Opening delay ms ms 45 ... 100 60 ... 100
Minimum conductor cross-section for loads with Ie Utilization category AC-2 and AC-3 Rated operating currents Ie Rated output power for slipring or squirrel-cage motors at 50 Hz and 60 Hz
Thermal load rating Power loss for each conducting path Utilization category AC-4 (for Ia = 6 x Ie) Rated operating current Ie Rated output power for squirrel-cage motors at 50 Hz and 60 Hz 200 250 The following applies to contact endurances of about 200,000 operating cycles: - Rated operating currents Ie - Rated output power for squirrelcage motors at 50 Hz and 60 Hz 56 98 124 172 183 for 230 V 400 V 500 V 690 V 1000 V kW kW kW kW kW 70 122 153 212 217 690 V 1000 V A A 175 123 215 151 for 400 V kW up to 690 V A 350 430
Utilization category AC-6a, switching of AC transformers Rated operating current Ie For inrush current = 20 For inrush current = 30 Rated output power P For inrush current = 20 for 230 V 400 V 500 V 690 V 1000 V for 230 V 400 V 500 V 690 V 1000 V kVA kVA kVA kVA kVA 111 193 241 332 482 kVA kVA kVA kVA kVA 167 290 363 501 726 up to 690 V up to 690 V A A 419 279
For deviating inrush current factors x, the power must be recalculated as follows: Px = Pn 30 30/x Utilization category AC-6b, switching low-inductance (low-loss, metallized dielectric) AC capacitors Ambient temperature 40 C Rated operating currents Ie Rated output power of single capacitors or banks of capacitors (minimum inductance between 6 H connected in parallel capacitors) at 50 Hz, 60 Hz and up to 500 V for 230 V 400 V 500 V 690 V A kvar kvar kvar kvar 407 162 282 352 282
Operating frequency
Operating frequency z in operating cycles/hour Contactors without overload relay Dependence of the operating frequency z' on the operating current I' and operating voltage U': z' = z (Ie/I') (400 V/U')1,5 1/h Contactors with overload relay (mean value) 1) Industrial furnaces and electric heaters with resistance heating, for example (increased power consumption on heating up taken into account). No-load operation frequency AC-1 AC-2 AC-3 AC-4 h-1 h-1 h-1 h-1 h-1 h-1 2000 700 250 750 250 60 2) In accordance with EC 60947-4-1. For rated values for different start-up conditions see Protection devices: Overload relay -> SIRIUS overload relay.
Conductor cross-sections
Screw terminals Front terminal connected
NSB00479
Short-circuit protection
NSB00481