SECTION - 4 PAGE: 1 of 7
1.1 1.2
Designation
Quantity/Application
1.3 1.4 1. GENERAL PARTICULARS 1.5 1.6 1.7 1.8 1.9 1.10
Type Boost / Float / Composite DC System voltage Location Design Ambient Temperature Type of mounting (floor/Pedestal/ column/wall) Cable Entry- Top/Bottom Glands/Conduits Purchaser's Earthing conductor Material Size Painting: Colour Outside Inside Control scheme & Bill of Material, enclosed Yes Ref No. Degree of enclosure protection and grade of the cubicle. IP class as per IS Thickness of Sheet Steel Cold Rolled Hot rolled Earthing Bus Material Size Momentary Emergency
Composite i)24 V for engine starter ii)30 V AMF panel control supply Indoor 45OC FLOOR Top Glands Cu Flat 40 x 6 mm RAL 7032 Glossy White No, to be furnished by Vendor IP 52
i) Two Nos. battery chargers for 24 V Supply for engine starter system ( One Battery charger system for each DG set) ii) One no. battery charger for 30V battery for AMF panel for both DG sets.
Frame, 2mm Doors 1.6 mm, Covers 1.6 mm Frame, Doors, Covers 2.5 mm Copper 40 x 6 * *
2. DC BUS LOAD
DOCUMENT No PCPL-0532-4-407-04-12-1
2.3 Continuous
SECTION - 4 PAGE: 2 of 7
Supply:
3.2 3.3 3.4 3.5 3.6 3.7 4.1 4.2 4.3 4.4
Voltage + /- 10% Frequency + /- 5% Short circuit level 37.5 MVA Type of earthing Effectively earthed Auxiliary supply if available Yes Control Transformer Required Space Heater/Lighting Supply Voltage 240V Automatic voltage regulator Yes Regulation with AVR + /- 2% Permissible harmonics at rated continuous load + /- 3% Minimum permissible power factor at rated continuous load 0.9
Variation in supply
* Data by bidder Note: Bidder to submit separate data sheets for 24 V and 30 V battery systems.
4. PERFOR MANCE
DOCUMENT No PCPL-0532-4-407-04-12-1
SECTION - 4 PAGE: 3 of 7
01 02 03 04 05 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
APPLICABLE STANDARDS Switchgear general requirements IS : 4237 AC circuit breakers IS : 2516 Factory built assemblies of SW. Gear and control gear IS : 8623 for voltages up to and including 1000V AC & 1200V DC. Air break switches IS : 4064 Miniature circuit breakers IS : 8828 Contactors IS : 2959 Starters IS : 8544 Control switches / push buttons IS : 6875 Current transformers IS : 2705 Voltage transformers IS : 3156 Relays IS : 3231 Indicating instruments IS : 1248 Arrangement for busbars main connections and IS : 5578 accessories IS: 11353 AC electricity meters IS : 8530 Degree of protection IS : 2147 The performance of AC control gear equipment rated up to 600V for use on high prospective fault current -system Code of practice for installation and maintenance of IS : 10118 switchgear Climate proofing of electrical equipment -Code of practice for phosphating iron & steel IS : 6005 BS : 3189 Wrought aluminium & aluminium alloys for electrical IS : 5082 purposes Control transformer for switchgear and control gear IS : 12021 for voltage not exceeding 1000V AC
DATA SHEET A2
DOCUMENT No PCPL-0532-4-407-04-12-1
SECTION - 4 PAGE: 4 of 7
mm
Yes/no
(Insulated/Bare)
DOCUMENT No PCPL-0532-4-407-04-12-1
SECTION - 4 PAGE: 5 of 7
17.2
18
19 20
21
Length Width Height Weight Typical GA drawings enclosed Yes / No List of routine tests to be done on charger a) b) c) List of type test carried on charger a) b) c)
mm mm mm Kgs.
DOCUMENT No PCPL-0532-4-407-04-12-1
SECTION - 4 PAGE: 6 of 7
1.13 1.14 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11
DESCRIPTION GENERAL Switchgear designation Single front or double front Module construction Fully drawout/semi drawout/fixed Dimensions of the board L X W X D Width of each vertical section Sheet metal thickness Front a) Rear b) Side panels c) Module partitions d) Door Has the sheet metal been treated in accordance with the specification Have all the feeders specified in Data Sheets A-3 been provided Bus bar continuous rating Short time rating (1-sec.) Clearances in airi) Between poles ii) Between pole and earth for unearthed system Degree of protection provided by the enclosure (as per IS:2147 or equivalent
UNIT
BIDDER
Earth bus bar size MCCB Makers Name Makers type designation Applicable standards Circuit breaker type Services voltage No. of poles and breaks per pole Rated operating duty Rated current Derating factor for operation under site conditions Rated breaking current at V DC Rated short time current (for 1 sec.)
mm2
V-DC A kA DC kA DC
DOCUMENT No PCPL-0532-4-407-04-12-1
SECTION - 4 PAGE: 7 of 7
SL # 2.12 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10 3.11 3.12 3.13 3.14
DESCRIPTION Rated making current BUSBARS Material of bus bars Size Type of insulation Whether have been taped Maximum continuous current Rating Temperature rise over the specified ambient when carrying rated current Material of bus bar supports Spacing between supports Spacing between bus bars Clearance in air i) between poles Max. fault withstand current rating (one sec.) Max. fault withstand current momentary rating (peak) Dielectric strength One min. power frequency withstand voltage
BIDDER