Sie sind auf Seite 1von 4

DOCUMENT No PCPL-0532-4-407-04-11-1

BATTERY DATA SHEET

SECTION - 4 PAGE: 1 of 4

Sl. NO. 1 2

DESCRIPTION Type of Battery Quantity/Application

DATA SHEET A1

3 4 5 6 7 8

Number of battery banks required Number of cells in each bank in series (Approximate) Ambient conditions Type of Nickel-Cadmium battery Cell container (Ni-Cd) i)D.C. System voltage for engine starter system ii)Control supply for AMF Panel Ampere-hour capacity of battery at 27O C. 10 hours rate to give final cell voltage of 1.75 volts/cell sealed lead acid. Momentary load/duration Emergency load/duration Continuous load/duration Sketch NO.(If any) showing load on battery Cell voltage-initial /final Calculated ampere hour for above duty Specified ampere hour Tentative size of cables to connect battery to external circuit Available area in battery room L X B Layout drawing No.(if any) Mounting arrangement High discharge test requires Yes/ No Charging method proposed

REQUIREMENT Sealed Lead Acid Plante / Tubular i) Two Nos. of 24 V Supply for engine starter system ( One Battery charger system for each DG set) ii) One no. of 30V supply for AMF panel for both DG sets. One 12V, 2 Nos for 24 V system 15 V , 2 Nos. for 30V system. 45OC (ref Section-2) NA 24 V 30 V * * * * NA 2.15V / 1.75V * * * NA NIL Rack No Float and Boost

9 10 11 12 13 14 15 16 17 18 19 20 21 22

* Data by bidder.

DATE:22-06-2006 ISSUE No: P0

DOCUMENT No PCPL-0532-4-407-04-11-1

BATTERY DATA SHEET

SECTION - 4 PAGE: 2 of 4

DATA SHEET A2 APPLICABLE STANDARD Sl. NO. DESCRIPTION 1 Sealed lead acid Nickel Cadmium 2 Water for storage battery 3 Sulfuric acid 4 Sealing compound for lead acid batteries 5 Synthetic separator for lead acid batteries STANDARD IS-8320, 1652 IS-12956

IS-6071

DATE:22-06-2006 ISSUE No: P0

DOCUMENT No PCPL-0532-4-407-04-11-1

BATTERY DATA SHEET

SECTION - 4 PAGE: 3 of 4

DATA SHEET B Sl. NO. DESCRIPTION 1.0 a) Manufacturers Name b) Type of battery 2.0 Standards to which battery is manufactured 3.0 Capacity 3.1 At 27 Deg. C 3.1.1 Initial 3.1.2 Rated 3.1.3 End of life 3.2 Rated capacity at minimum Ambient temperature 3.3 Rated capacity at maximum ambient temp. 3.4 Capacity at high discharge rate 27Deg. C 3.4.1 5 minutes 3.4.2 30 minutes 3.4.3 45 minutes 3.4.4 1 hour 3.4.5 2 hour 3.4.6 3 hour 3.4.7 4 hour 3.4.8 5 hour 3.4.9 6 hour 3.4.10 7 hour 3.4.11 8 hour 3.4.12 9 hour 3.5 Maximum Momentary current 1 minute 3.6 Expected life of battery 4.0 Recommended charging rate 4.1 Float charging Voltage/ current 4.2 Trickle charging Voltage/ Current 4.3 Boost charging Voltage/ Current 4.4 Equalizing charge a) Voltage/current b) Duration c) Interval between successive equalising charges

UNIT

DETAILS

Ah Ah Ah Ah Ah Ah Ah Ah Ah Ah Ah Ah Ah Ah Ah Ah Ah Ah Amps Years V A V A

V/A Min. Hrs.

DATE:22-06-2006 ISSUE No: P0

DOCUMENT No PCPL-0532-4-407-04-11-1

BATTERY DATA SHEET

SECTION - 4 PAGE: 4 of 4

DATA SHEET B Sl. NO. DESCRIPTION 5.0 Expected fault level at bus due to battery 6.1 Total resistance of battery 6.2 Resistance of inter cell Connectors 7.1 AH efficiency at rated load 7.2 Watthour efficiency 8.1 Type of positive plate 8.2 8.3 8.4 8.5 8.6 8.7 8.8 9.0 9.1 9.2 10.0 10.1 10.2 11.0 12.0 12.1 12.2 13.0 NO. of positive plates/ cell No. of cells required to give rate D.C. voltage NO. of spare cells Whether positive plates of individual cells are inter changeable Whether negative plates are interchangeable Type of containers Type of cell Overall dimensions Each cell L x W x H Complete battery L x W x H Weight Each cell Complete battery Whether explosion vents are offered Ventilation requirements Cubic content of battery room Exhaust fans a) Number b) Rating of each Whether there would be any harmful effect on the life of battery if discharged as per load cycle specified above, after being maintained in float charging condition List of spare/accessories enclosed Kist of deviations enclosed

UNIT kVA Ohms Ohms Pocket / Sintered

DETAILS

YES/NO YES/NO

mm mm Kg Kg Yes/no M3 kW Yes/no

14.0 15.0

Yes/no Yes/no

Note: Bidder to submit separate data sheets for 24 V and 30 V battery systems.

DATE:22-06-2006 ISSUE No: P0