Sie sind auf Seite 1von 22

Voltage Influence on Typical Protection and Controls for Motors, Power Electronics, and Other Common Loads

Presentation to: WECC Modeling and Validation Work Group November 18, 2010 John Kueck

Many Well Known Standards:

The Study Examines a Range of Standards for Both Equipment Protection and Voltage Tolerance
Buff Book IEEE Std 242-2001 Protection and Coordination of Industrial and Commercial Power Systems Gray Book IEEE Std 241-1990 Electric Power Systems in Commercial Buildings Red Book IEEE Std 141-1993 Electric Power Distribution for Industrial Plants Gold Book IEEE Std 493-2007 Design of Reliable Industrial and Commercial Power Systems Blue Book IEEE Std 1015-2006 Applying Low Voltage Circuit Breakers Used in Industrial and Commercial Power Systems The National Electrical Code (NEC, 2008)

These standards provide guidance on the suggested setpoint for undervoltage trip for various equipment, there is significant latitude allowed to the designer, and really no requirement that the designer rigorously follow the standard. Also, few equipment types for which under voltage protection is recommended. Biggest problem may be the ice cube relay.

Voltage Tolerance of Programmable Logic Controllers, A Wide Range


PLC Power Supply Voltage Sag Tolerance (CIGRE 412)
100

% V

80 60 40 20 0 200 400 600 Duration of Sag (milliseconds) Average 800

Upper Range

Lower Range

Adjustable Speed Drive Tolerance and Protection


ASD Voltage Sag Tolerance (Djokic Paper)

100

% V

80 60 40 20 0 Overcurrent Protection Undervoltage Protection 200 400 600 Duration of Sag (milliseconds) Average 800

Upper Range

Lower Range

Motor Torque
Induction motor torque is a function of the terminal voltage squared. During a rapid dip, the motor goes into regeneration and will be slowed.
A stiff system slows the motor faster Low inertia in the driven equipment means even faster deceleration Tests by SCE show air conditioning compressors can stall in 1 to 18 cycles

The IEEE Buff Book (242, 2001) Section 10.3.2.1 Motor Protection, Undervoltage
To prevent a motor from automatically restarting when voltage returns. To avoid excessive inrush to the total motor load on the power system. To avoid reaccelerating motors before their fields collapse. Time delay undervoltage protection will often not be satisfactory because magnetically held contactors may drop out before the undervoltage protection.

Very Few Other Standards Mention Undervoltage Protection for Motors


For large motors, the IEEE Red Book (IEEE_Standard_141, 1993) states in Section 5.6.3.1 motor protection may include:
Internal fault protection - either overcurrent relays or percentage differential relays; sometimes ground fault protection is provided using a zero sequence approach. Sustained overloads and locked rotor - Conventional over current relays may provide too much margin between the motor thermal capability curve and the relay operating time characteristic. Overcurrent relays do, however, provide excellent locked rotor and short circuit protection. Thermal relays will give adequate protection for light and medium overloads. Under voltage - Large motors and medium voltage motors should have separate undervoltage protection.

For small motors, the Red Book and the NEC do not require undervoltage protection.

What Percentage Are Large Motors?


Industrial motor systems account for approximately twenty three per cent of all electricity consumed. Large motors, i.e. those over 200 horsepower, account for only one percent of the motors in the entire manufacturing inventory, but use 45 percent of the energy use. Approximately 70% of motors which are >200 horsepower, fall into the 250-500 hp size How many of these are equipped with undervoltage protection? A growing number.

Emerson Secure Start and ComfortAlert for Air Conditioning Compressors


ComfortAlert will flash an alert if the voltage is below 71% Secure Start
Monitors supply voltage in air conditioning compressors and protects against low voltage or locked rotor. Also provides a reduced voltage soft start. Can be used in areas with problems in voltage variation.

Ice Cube Relay, the Achilles Heel


These relays are ubiquitous in 120 volt control circuitry, for example:
Emergency stop circuits Door interlock circuits Air compressor starter controls Chiller controls Conveyor controls Oven controls PLC - Motor interface circuit ASD start circuit Vending machines

Ice Cube Relay Voltage Sag Tolerance (EPRI)

100

% V

80 60 40 20

200

400

600

800

Duration of Sag (milliseconds) Upper Range Lower Range

Contactors
Large Motor Starter Contactors Motor starter contactors may open at 65 to 75% voltage in the case of 2300 or 4600 Volt motors and 55 to 65% in the case of 460 Volts and below. The contactor dropping out or control relays dropping out is really the only fast undervoltage protection that motors under 600 volts typically have. Motors over 600 volts represent a very small percentage of the population. Large Air Conditioners Large three phase air conditioning in industrial or commercial applications typically have undervoltage relays which trip in perhaps six cycles after the voltage drops below 0.6 pu.

Contactors Voltage Sag Tolerance (CIGRE 412)

100

% V

80 60 40 20

AC Upper Range

AC Lower Range DC 0 200 400 600 800

Duration of Sag (milliseconds) Upper Range Lower Range

DC

Lamps
Incandescent filament lamps are quite tolerant to voltage sags, but the light output and lifetime are dramatically impacted by sustained voltage deviations. Fluorescent lamps may stop working anywhere between 80 and 40% voltage and in as little as 10 milliseconds. Some electronic ballasts may keep the light working at 40% indefinitely.

ANSI Voltage Tolerance Limits for Low Voltage Regulated Power Distribution System, 120 V Base
Maximum allowable voltage Voltage drop allowance for primary distribution line Minimum primary service voltage Voltage drop allowance for distribution transformer Minimum secondary service voltage Voltage drop allowance for plant wiring Minimum Utilization Voltage Range A 126 9 Range B 127 13

117 3

114 4

114 6 (See Concern Below) 108

110 6 104

NEC FPN4 states that conductors for branch circuits should be sized to prevent a voltage drop exceeding 3 percent at the farthest outlet of power, heating and lighting loads, and where the maximum total voltage drop on both feeders and branch circuits to the farthest outlet does not exceed 5%, yielding 108 at the motor. But, the code requirement is only for ampacity, not for voltage. As houses get larger, is the FPN note met? Also, what is the voltage drop across the meter? It is assumed by all of the above to be zero.

Possible Concern

Japanese Study
The load drop does not occur if the lowest voltage is higher than 0.85 pu. The load drop occurs if the lowest voltage becomes lower than 0.85 pu, and rapidly increases when the lowest voltage is around 0.6 pu. The load drop, however, saturates after that and does not increase over 30% ..."

Other Parameters Are Probably More Important than the Dip Magnitude
More recent studies have shown that there are a number of parameters which have a major impact the capability of a device to ride through an interruption than just the dip magnitude and duration. (CIGRE, 2010) These parameters include: Pre dip voltage magnitude and distortion of sine wave. Unbalance during dip for three phase devices, dip shape, and point on the sine wave where the dip starts. Speed of recovery of dip. Source impedance (distribution transformer). Other equipment connected close by.

Conclusions
Point on wave may have a greater impact than magnitude and duration. High efficiency motors are more prone to stall. Ice cube relays are used everywhere and will drop at 70% V in one cycle. Voltage drop in branch circuits and other parasitic drop in low voltage systems may be a growing problem. Motors at 600 volts and below usually do not have undervoltage protection unless supplied by manufacturer (air conditioning compressor). Motor contactors will typically provide the undervoltage protection by dropping out.

Das könnte Ihnen auch gefallen