Beruflich Dokumente
Kultur Dokumente
Number:
3481-8531-CA-0002
Revision
No:
D1
FEED
Date:
12/2008
Page:
1 of 16
Earthing Calculation
QPCC
MESAIEED, QATAR
D1
12/2008
For information
PWR
DR
DR
01
07/07/08
PWR
RS
DR
Rev
Date
Description
Orig by
Chkd by
App By
Client
App
This document is issued by Foster Wheeler Energy Limited, for and on behalf of QPCC, Doha, Qatar. The information contained in this
document is the confidential property of QPCC. It cannot be disclosed, copied or used for any purpose without the approval of QPCC. If
you are not authorised to possess this document, please destroy it immediately.
File:
DSN: 1027
CALCULATION
FEED
Number:
3481-8531-CA-0002
Revision
No:
D1
Date:
12/2008
Page:
2 of 16
CONTENTS
1. SUMMARY.................................................................................................................................. 3
2. METHOD.................................................................................................................................... 4
3. RESULTS.................................................................................................................................... 9
4. RECOMMENDATIONS.............................................................................................................. 10
APPENDIX 1 ................................................................................................................................ 11
File:
DSN: 1027
CALCULATION
FEED
1.
Number:
3481-8531-CA-0002
Revision
No:
D1
Date:
12/2008
Page:
3 of 16
SUMMARY.
This grounding study is performed to ANSI/IEEE Std. 80 2000. The findings are as follows
1.1
Touch Voltages
The results show that the calculated actual touch voltage is less than the allowable touch
voltage. This is the case when the calculations use the 0.4kV equipment fault current rating
and the smaller calculated fault current.
1.2
Step Voltages
The calculated step voltage is less than the allowable step voltage.
1.3
1.4
File:
DSN: 1027
CALCULATION
Number:
3481-8531-CA-0002
Revision
No:
D1
FEED
2.
Date:
12/2008
Page:
4 of 16
METHOD
This study is based on ANSI/IEEE Std. 80-2000 IEEE Guide for Safety in AC Substation
Grounding.
The main object of this study is to design the substation grounding arrangement and
substation above grade down conductor sizes. The calculation is performed for the worst
case fault level rating of switchgear. To avoid excessive construction costs, the design
should be optimised at the EPC stage for each substation switchgear rating.
2.1
Tm
Ta
= ambient temperature in 0C
= 50oC (refer to 3481-8531-SP-0002)
tc.
File:
DSN: 1027
CALCULATION
FEED
2.2
Number:
3481-8531-CA-0002
Revision
No:
D1
Date:
12/2008
Page:
5 of 16
2.2.1
Step Voltages.
The following assumptions are made for data required by IEEE-80:
a) A body weight of 50Kg is used
b) the earth fault will last for a maximum duration of 0.5 sec. (backup clearance time)
c) Ground fault current shall be the higher of the line to line to ground or the symmetrical
line to ground fault current
d) In calculations of the grid current, the current division factor is assumed to be 1.0
e) For calculations of allowable step and touch potentials, the resistivity of the surface
material (rhos) shall be assumed to be 2,000 ohm-meters for a minimum 75mm thick pad of
clean crushed rock, 10,000 ohm-meters for a minimum 50 mm layer of asphalt, and 200
ohm-meters for a minimum 75 mm layer of concrete. For all other surface materials, the
lower of 100 ohm-meters or the actual measured top layer (minimum 0.3 m layer thickness)
soil resistivity is used.
The tolerable step voltage is given by;
Estep50 = (1000 + 6CSS)0.116/tS
eq.1
where:
CS = reduction factor for derating the nominal value of surface layer resistivity determined
from Equation 27 of IEEE- 80 substituting for K using;
K = ( - S) / ( + S)
eq.2
File:
DSN: 1027
CALCULATION
Number:
3481-8531-CA-0002
Revision
No:
D1
FEED
Date:
12/2008
Page:
6 of 16
Touch Voltages
The tolerable touch voltage is given by;
Etouch50 = (1000 + 1.5CSS)0.116/tS
eq.3
2.3.1
eq. 4
where :
Sf = current division factor relating the magnitude of fault current to that portion flowing
between the grounding grid and surrounding earth.
If
File:
DSN: 1027
CALCULATION
FEED
Number:
3481-8531-CA-0002
Revision
No:
D1
Date:
12/2008
Page:
7 of 16
The supply to the QPCC plant is via underground cable. Therefore it is considered that
there will be no diversion of ground current from the ground grid, as might be the case if
overhead lines were used (see IEEE-80, Sect 15.6). This approach is considered
conservative, as ignoring this effect results in a more onerous ground grid requirement.
Similarly the effects of any below grade cable armour and pipes in the switchyard are
ignored.
Therefore Ig is assumed equal to If.
Thus giving Ig = 100kA
2.3.2
eq. 5
where:
IG
Cp
= corrective projection factor accounting for the relative increase of fault currents
during the station life span; the rating of the switchgear is 100kA, so no increase in
fault current during the life-span is considered. Hence, C p = 1.0
Df
Ig
and
tf,
= 0.5 s
= 100kA
Therefore IG = Ig x 1.052
= 105.2kA
2.4
File:
DSN: 1027
CALCULATION
FEED
Number:
3481-8531-CA-0002
Revision
No:
D1
Date:
12/2008
Page:
8 of 16
grid is direct buried at a depth of 0.5m. The perimeter loop is connected to ground rods at
10m intervals
The ground soil characteristics are given in Fugro report PQ/1001/04/02
Using the computer model representation of the ground grid (Appendix 1), the ground grid
resistance is calculated as:
Rg = 0.08 .
This satisfies the requirement for substation grid resistance to be 1.
2.5
2.5.1
2.5.2
Mesh Voltage.
The mesh voltage is given by (IEEE-80 eq.80);
EM = IG Km Ki / LM
eq. 6
where:
Km = 1/2 [ln (D2 /16hd + (D+2h)2 / 8dD h/4d) + (Kii / kh) ln 8/(2n-1)
eq. 7
Kii = 1
Kh = (1 + h / ho)
eq. 8
eq. 9
File:
DSN: 1027
CALCULATION
FEED
Number:
3481-8531-CA-0002
Revision
No:
D1
Date:
12/2008
Page:
9 of 16
D = 5m
h = 0.45m
n = 73
D = 0.0095m
ho = 0.5m (reference depth of ground grid)
Ki = 13.212 + 0.172 x 73
LM = LC+[1.55+1.22(Lr/{ Lx2+Ly2})]LR
From Appendix 1,
EM = 547V @ 105.2kA.
2.5.3
Step Voltage
Using Es = IG Ks Ki / LS
eq. 10
where:
Ks = 1/ [1 / 2h + 1 / (D+h) + (1-0.5n-2 )/ D
eq. 11
eq. 12
From Appendix 1,
Es = 650V
3.
RESULTS
3.1
3.2
File:
DSN: 1027
CALCULATION
FEED
4.
Number:
3481-8531-CA-0002
Revision
No:
D1
Date:
12/2008
Page:
10 of 16
RECOMMENDATIONS
With the geological structure as used in these studies, the results are acceptable. However,
EPC is advised that the actual geological structure and water table depth is to be
determined by site investigation. The calculation should then be revised to reflect the
findings of the site survey.
Wet organic soil has been taken as an equivalent to the local water table. Depending on the
actual water table depth, EPC may have to increase the ground rod lengths as required to
reach the water table and achieve the required grounding resistance, step and touch
voltages.
The calculation has been carried out for the anticipated worst case substation. During EPC,
calculations should be carried out for each substation to determine the optimum ground grid
design.
File:
DSN: 1027
CALCULATION
Number:
3481-8531-CA-0002
Revision
No:
D1
FEED
Date:
12/2008
Page:
11 of 16
APPENDIX 1
Computer Programme Results
File:
DSN: 1027
CALCULATION
FEED
File:
Number:
3481-8531-CA-0002
Revision
No:
D1
Date:
12/2008
Page:
12 of 16
DSN: 1027
CALCULATION
FEED
File:
Number:
3481-8531-CA-0002
Revision
No:
D1
Date:
12/2008
Page:
13 of 16
DSN: 1027
CALCULATION
FEED
File:
Number:
3481-8531-CA-0002
Revision
No:
D1
Date:
12/2008
Page:
14 of 16
DSN: 1027
CALCULATION
FEED
File:
Number:
3481-8531-CA-0002
Revision
No:
D1
Date:
12/2008
Page:
15 of 16
DSN: 1027
CALCULATION
FEED
File:
Number:
3481-8531-CA-0002
Revision
No:
D1
Date:
12/2008
Page:
16 of 16
DSN: 1027