Reference Documents
Ambient Conditions
1 Max design Temperature
2 Min design Temperature
Battery:
DC Voltage
Nominal - V
Max (+10%)
Min (-15%)
2
3
4
5
6
7
8
9
10
Battery Type
Charging time
Battery back-up time
Cell Nominal voltage
End Cell Voltage
Number of Cells
Selected Battery size
Nominal DC voltage
Cable Voltage Drop
Nos
AH
Volts
Battery Charger:
Type
2 AC Input Voltage
1
Voltage variation
Frequency
5 Frequency variation
3
4
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
40 C
o
10 C
BEDD
110
121 V
93.5V
BEDD
Do
Do
Ni-Cd
8 Hrs
2 Hrs
1.2 V/cell
1.10 V/cell
90
600
110
5V
3481-8531-SP-0024
Do
3481-8532-70-0031
SAFT Catalogue
SAFT Catalogue
Calculated
Calculated
BEDD
Annex 1
Annex 2
Assumed
Charging Method
Constant Voltage
3481-8531-SP-0024
9W
15W
11.6W
9W
11.6W
9W
150W
8W
3W
250W
125W
400W
185W
185W
440W
ABB
Power consumptions
HV closing coil
HV tripping coil
HV spring charging Motor
LV closing coil
LV tripping coil
LV spring charging Motor
LV contactor coils
Attachment
ABB
ABB
GE Power
GE Power
GE Power
Considered to be AC operated.
Annex 4
Annex 3
Annex 5
Annex 4
Annex 5
Annex 4
Annex 6
Annex 7
Annex 8
Period 2 (M2)
2nd min to 118th
0th min to 1st min
min
1min
118min
Period 1 (M1)
(W)
a)
b)
c)
d)
e)
f)
g)
h)
i)
Duration in minutes
HV (33 kV) Switchboard - 3 I/C & 2 B/T
SWB-01-2501A/B/C
Opening Coil (3 I/C and 2 B/T)
Closing Coil - I/C
Spring Charging Motor - HV CB
Relay (IPR) for the Incomers
Relay (IPR) for the Bus Tie
Lock out Relay (86)
Trip Circuit supervision Relay (96)
Auxiliary Relays (6 Nos per CB)
Indication Lamps etc (assumed LS 10W)
j)
k)
l)
m)
(A)
5
5
5
3
2
5
5
5
5
10
5
5
3
2
5
5
30
5
125.00
250.00
400.00
9.00
11.60
150.00
8.00
3.00
10.00
1.14
2.27
3.64
0.08
0.11
1.36
0.07
0.03
0.09
10
3
2
5
5
30
5
0.24
0.22
6.80
0.35
0.90
0.45
24
24
24
48
24
24
125.00
250.00
400.00
250.00
1.14
2.27
3.64
2.27
48
54.72
n)
o)
p)
q)
r)
s)
16
8
24
24
24
24
16
8
24
24
144
24
9.00
15.00
150.00
8.00
3.00
10.00
0.08
0.14
1.36
0.07
0.03
0.09
16
8
24
24
144
24
1.28
1.12
32.64
1.68
4.32
2.16
5
5
5
3
2
5
5
5
5
10
5
5
3
2
5
5
30
5
125.00
250.00
400.00
9.00
11.60
150.00
8.00
3.00
10.00
1.14
2.27
3.64
0.08
0.11
1.36
0.07
0.03
0.09
10
11.40
3
2
5
5
30
5
0.24
0.22
6.80
0.35
0.90
0.45
j)
k)
l)
m)
39
39
39
78
39
39
125.00
250.00
400.00
250.00
1.14
2.27
3.64
2.27
78
88.92
n)
o)
p)
q)
r)
s)
38
1
39
39
39
39
38
1
39
39
234
39
9.00
15.00
150.00
8.00
3.00
10.00
0.08
0.14
1.36
0.07
0.03
0.09
38
1
39
39
234
39
a)
b)
c)
d)
e)
f)
g)
h)
i)
Continuous
Load Current in
Amps
Current drawn
in Amps
No of feeders
Current drawn
in Amps
No of feeders
Current drawn
in Amps
No of Feeders
Rated current
Rated Power
Total Number
Total Operating
breakers
Sl Description
Period 3 (M3)
119th min to
120th min
1min
11.40
3.04
0.14
53.04
2.73
7.02
3.51
3
2
0.24
0.22
5
5
3
2
11.35
18.20
0.24
0.22
0.24
0.22
5
30
5
0.35
0.90
0.45
5
30
5
0.35
0.90
0.45
0.35
0.90
0.45
24
24
54.48
87.36
16
8
1.28
1.12
16
8
1.28
1.12
1.28
1.12
24
144
24
1.68
4.32
2.16
24
144
24
1.68
4.32
2.16
1.68
4.32
2.16
3
2
0.24
0.22
5
5
3
2
11.35
18.20
0.24
0.22
0.24
0.22
5
30
5
0.35
0.90
0.45
5
30
5
0.35
0.90
0.45
0.35
0.90
0.45
39
39
88.53
141.96
38
1
3.04
0.14
38
1
3.04
0.14
3.04
0.14
39
234
39
2.73
7.02
3.51
39
234
39
2.73
7.02
3.51
2.73
7.02
3.51
Period 2 (M2)
2nd min to 118th
0th min to 1st min
min
1min
118min
Period 1 (M1)
(W)
a)
b)
c)
d)
e)
f)
g)
h)
i)
Duration in minutes
LV (400V) Switchboard - 2 I/C & 1 B/T
SWB-01-4501A/B
Opening Coil (2 I/C and 1 B/T)
Closing Coil - LV I/C & B/C
Spring Charging Motor - LV Board
Relay (IPR) for the Incomers
Relay (IPR) for the Bus Tie
Lock out Relay (86)
Trip Circuit supervision Relay (96)
Auxiliary Relays (6 Nos per CB)
Indication Lamps etc (assumed LS 10W)
j)
k)
l)
m)
n)
o)
4
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
k)
l)
m)
n)
o)
TOTAL
(A)
3
3
3
2
1
3
3
3
3
3
3
3
2
1
3
3
18
3
185.00
185.00
440.00
9.00
11.60
150.00
8.00
3.00
10.00
1.68
1.68
4.00
0.08
0.11
1.36
0.07
0.03
0.09
2
1
3
3
18
3
0.16
0.11
4.08
0.21
0.54
0.27
30
2
23
32
55
33
3
26
36
61
9.00
9.00
9.00
150.00
10.00
0.08
0.08
0.08
1.36
0.09
33
3
26
36
61
2.64
0.24
2.08
48.96
5.49
2
2
2
2
2
2
2
2
3.36
2
2
12
2
1.68
1.68
4.00
0.08
0.11
1.36
0.07
0.03
0.09
2
2
2
2
185.00
185.00
440.00
9.00
11.60
150.00
8.00
3.00
10.00
9.00
9.00
9.00
150.00
10.00
0.08
0.08
0.08
1.36
0.09
Continuous
Load Current in
Amps
Current drawn
in Amps
No of feeders
Current drawn
in Amps
No of feeders
Current drawn
in Amps
No of Feeders
Rated current
Rated Power
Total Number
Total Operating
breakers
Sl Description
Period 3 (M3)
119th min to
120th min
1min
5.04
2
1
0.16
0.11
3
3
2
1
5.04
12.00
0.16
0.11
0.16
0.11
3
18
3
0.21
0.54
0.27
3
18
3
0.21
0.54
0.27
0.21
0.54
0.27
33
3
26
2.64
0.24
2.08
33
3
26
2.64
0.24
2.08
2.64
0.24
2.08
61
5.49
61
5.49
5.49
3.36
8.00
0.16
0.16
0.16
0.16
2
2
2
2
2
12
2
2.72
0.14
0.36
0.18
2
12
2
0.14
0.36
0.18
2
12
2
0.14
0.36
0.18
0.14
0.36
0.18
0.64
0.64
0.64
0.64
0.72
0.72
0.72
0.72
505.09
45.26
375.14
45.26
Min Cell
Voltage
83.44
90 Nos
considered
1.094
1.1
considered
1
2
3
Capacity
Removed
(AH)
1
6.252
118
89.011
1
8.418
375.14
45.26
505.09
Total
103.681
138 AH
min
1
118
119
120
min
1
90
90
120
min
0
120
120
0
Amps
235
62.3
62.3
51.8
Amps
0
51.8
51.8
0
Factor
Kt1 for
time t1
0.587
2.215
2.215
2.664
Kt = Kt2 -
(Kt2-Kt1) x (t2-t)
----------------------(t2-t1)
0.000
2.664
2.664
0.000
0.59
2.63
2.65
2.66
Load Cycle
A1
375.14
A3
Amp
A2
45.26
505.09
Amp
1 min
Amp
118 min
1 min
Duration
Sl
(2)
Period
(3)
Load
(Amp)
(4)
(5)
(6)
Change in Duration
Load
of period
(Amp)
(min)
375.14
Time to
end of
section
(min)
(7)
(8)
Capacity
rating
factor at t
min rate
(Kt)
Temp
derating
factor for t
min (Tt)
(9)
(M1)
(T=M1)
(Kt)
(Tt)
0.587
(M1) (T=M1+M2)
(Kt)
(Tt)
Subtotal
2
Second
period
375.14
(A2)
375.14
(A2-A1)
1
(M2)
(T=M2)
119
2.649
(Kt)
1
(Tt)
45.26
-329.88
118
118
2.634
(M1) (T=M1+M2+
(Kt)
(Tt)
Subtotal
3
M3)
Second
period
Third
period
Subtotal
375.14
(A2)
375.14
(A2-A1)
1
120
(M2) (T=M2+M3)
2.664
(Kt)
1
(Tt)
45.26
(A3)
-329.88
(A3-A2)
118
(M3)
(T=M3)
2.649
(Kt)
1
(Tt)
505.09
459.83
0.587
119
Required
section
size
(3)x(6)x(7) =
Rated AH
Kt x T t x
col 4
220.29
220.29
Kt x T t x
col 4
993.79
Kt x T t x
col 4
-868.96
124.83
Kt x T t x
col 4
999.41
Kt x T t x
col 4
-873.89
Kt x T t x
col 4
270.03
395.55
(AH)
(AH)
(AH)
395.55
1.1
1.25
543.88
600
600
8
75
AH
H
A
DC UPS Output
DC UPS output Power (DCW)
=
=
=
=
[45.26 + 75]x121
14551.46 W
16006.61 W
16.01
kW
=
=
16006.606 / 93.5
171.19
A
=
=
=
=
600
90
171.19
16.01
SUMMARY
Battery Capacity
No of Cells
Max DC output current Idc max
DC UPS Output Power
AH
Nos
A
kW
(Considering 10%
design margin)