Cable cabinet, 250 A HDC-A 1224 kV

Use For jointing or branching XLPE- and EPR-insulated 1-core or 3-core, 1224 kV cables with conductor cross sections 2595 mm, 250 A.

When branching in a cable grid, a branching point may be necessary to enable selected cable runs to be sectionalized during maintenance. With HDC-A, a solution is provided that makes this possible. Up to three cables can be connected in parallel. Standards Enclosure meets the requirements of mechanical impact tests according to: IEC 60439-5 Cable connectors meet the requirements of electrical tests according to CENELEC, HD 629.1 S2 Design The enclosure is made of hot-dip-galvanized sheet steel plates with a foundation base plate and additional corrosion protection on parts that will be buried under ground.
Overall height 1293 mm Height above ground level,993 mm

312 mm 996 mm

The screened separable cable connectors are connected with coupling pieces pre-mounted in the cabinet. The cable cabinet is supplied with: 9 screened separable connectors Standard locks and padlock shackle Note: For 3-core cables, branch seal kit type TSH or screen separation kit type PSSK must be used. To be ordered separately. For foundation kit for floor installation, contact us.

Always select products by Insulation diameter.

Voltage kV 12 24

Insulation diameter Conductor cross section Designation basic configuration mm mm 1322 1725.5 2595* 2595* HDC-A 12250 HDC-A 24250

Weight kg /unit 117 117

* For cables smaller than 25 mm, contact us.

3/41 | Kabeldon cable accessories 1420 kV | Cable accessories for XLPE-insulated cables 12-42 kV

Accessories, to be ordered separately Cable cabinet, HDC 1224 kV, 250 A

3
IP 250 Screened insulating plug for installation in the connector so that the cable can be energized even when the cable connector is disconnected. IH-A 24250 Insulating hood made of flexible rubber with outer conductive layer and an already installed insulating rod. To be mounted on the bushing in HDC-A 250 for insulation when a cable is temporary disconnected and remaining cables are under voltage. MA 250 Measurement adapter used for mega ohm measurements and to perform different measurements up to 5 kV DC, for example determination of phases.

KA 250 Transversal anchor bar. PSSK: for cables with Cu-wire screen, heat-shrink. PSSK E: for Ericssons cables with Al-wire screen, heat-shrink. TSH Branch seal kit

13

35

UKRA 90 Universal clamp.

Designation IP 250 IH-A 24250 MA 250 KA 250 PSSK 1 PSSL 1 L PSSK 1 E* PSSK 2 PSSL 2 L PSSK 2 E* TSH UKRA 90

Description Screened insulating plug Insulating hood Measurement adapter Busbar Screen separation kit, heat-shrink, for 3-core cable 1070 mm / 12 kV, 1035 mm / 24 kV Screen separation kit, heat-shrink, reinforced and extended, for 3-core cable, 1070 mm / 12 kV, 1035 mm / 24 kV Screen separation kit, heat-shrink, for 3-core Ericsson cable 1070 mm / 12 kV, 1035 mm / 24 kV Screen separation kit, heat-shrink, for 3-core cable 95300 mm / 12 kV, 50300 mm / 24 kV Screen separation kit, heat-shrink, reinforced and extended, for 3-core cable, 95300 mm / 12 kV, 50300 mm / 24 kV Screen separation kit, heat-shrink, for 3-core Ericsson cable 95300 mm / 12 kV, 50300 mm / 24 kV Branch seal Clamp for fixing cables

Qty kit 1 3 1 1 1 1 1 1 1 1 1 1

Weight kg/unit 0.8 2.3 0.3 0.5 1.9 3.3 1.9 2.5 3.9 2.5 0.31.0 0.23

See page 3/42 3/42 3/42 3/42 3/45 3/45 3/45 3/45 3/45 3/45 3/46 7/2

* Special screen separation for Ericssons 3-core cable with Al-wire screen.

Cable accessories for XLPE-insulated cables 12-42 kV | Kabeldon cable accessories 1420 kV |

3/42

Cable cabinet, 630 A HDC-A 1236 kV

Use For jointing or branching of XLPE- and EPR-insulated, 1236 kV 1-core or 3-core cables with conductor cross sections 25630 mm, 630 A. Up to four cables can be connected in parallel.

3
When branching in a cable grid, a branching point may be necessary to enable selected cable runs to be sectionalized during maintenance. With HDC-A a solution is provided that makes this possible. Standard The cable cabinet meets the requirements for mechanical impact testing according to IEC 60439-5. The cable connectors meet the electrical requirements according to CENELEC, HD 629.1 S2.
522 mm

The screened separable cable connectors are connected with coupling pieces pre-mounted in the cabinet. The cable cabinet is supplied with: 6 screened separable cable connectors Locks and padlock shackle Required when connecting more cables: 6 screened separable cable connectors type CSE-A. Parallel coupling piece type PC. Note: For 3-core cables, branch seal kit type TSH or screen separation kit type PSSK must be used. To be ordered separately. For foundation kit for floor installation, contact us.
Voltage kV 12 12 12 24 24 24 36 36 36 Insulation diameter mm 1320 18.530.5 30.545 1724 22.535 30.545 24.534 27.542 3855 Conductor cross section mm 2570 95300 400630 2570 95300 400630 5095 95300 400630

Overall height 1293 mm Height above ground level,993 mm

Design The enclosure is made of hot-dip-galvanized sheet steel plates with a foundation base plate and additional corrosion protection on parts that will be buried under ground.

996 mm

The third cable connector is to be ordered separately.

Always select products by Insulation diameter.

Designation basic configuration HDC-A 12630-01 HDC-A 12630-02 HDC-A 12630-03 HDC-A 24630-01 HDC-A 24630-02 HDC-A 24630-03 HDC-A 36630-01 HDC-A 36630-02 HDC-A 36630-03

Weight kg /unit 140 140 140 140 140 140 140 140 140

3/43 | Kabeldon cable accessories 1420 kV | Cable accessories for XLPE-insulated cables 12-42 kV

Accessories, to be ordered separately Cable cabinet, HDC-A 1236 kV, 630 A

PG 630 Bushing for voltage testing of the cable. Adapted to cable connectors 1224 kV.

3
CSE-A IH-A 24630, IH-A 42630 Screened separable connector 630 A Insulating sealing hood of flexible for connection of an external cable. rubber with outer conductive layer and an already installed insulating hood. To be installed in HDC-A 630 instead of cable connector in order to temporarily insulate 630 A switchgear or transformer bushings. PSSK L Screen separation kit for 3-core cables with Cu-wire screen including heat-shrink branch seal and 2 meters long protective hoses.

PG-A 630 Bushing for voltage testing of the cable. Adapted to cable connectors 36 kV.

PC 630-3 Parallel coupling piece. Replaces the plug in CSE-A when making a parallel connection to another CSE-A 1224 kV.

IP 630 Screened insulating plug for installation in the screened separable connector so that the cable can be energized even when the connector is disconnected from the switchgear or transformer.

MA-A 630 Measurement adapter used for mega ohm measurements and to perform different measurements up to 5 kV DC, for determination of phases. 13

TSH Branch seal kit.

35

PC 630-3 L Parallel coupling piece. Replaces the plug in CSE-A when making a parallel connection to another CSE-A 36 kV.

PC 630/250 Connector for connecting a CSE-A 250, in parallel with a previously mounted CSE-A 630. 3 pieces in the kit, tool is included.

UKRA 90 Universal clamp.

KA 630 Transversal anchor bar.

Designation CSE-A KA 630 IH-A 24630 IH-A 42630 PC 630-3 PC 630-3 L PG 630 PG-A 630 IP 630 MA-A 630 PC 630/250 PSSK 2, PSSK 2 L, PSSK 2 E PSSK 3, PSSK 3 L, PSSK 3 E TSH UKRA 90

Description Screened separable connector. Transversal anchor bar, add two when using 1-core cables Insulating sealing hood, 1224 kV Insulating sealing hood, 36 kV Parallel coupling piece, 630, 1224 kV Parallel coupling piece, 630, 36 kV Bushing for voltage testing of the cable, 1224 kV Bushing for voltage testing of the cable, 36 kV Insulating plug, 630 A Measurement adapter, 630 A Parallel coupling piece between CSE-A 630 and CSE-A 250 Screen separation for 3-core cable 95300 mm / 3642 kV Screen separation for 3-core cable 95300 mm / 3642 kV Branch seal Clamp for fixing cables

Qty. per kit 3 1 3 3 3 3 1 1 1 3 3 1 1 1 1

Weight kg/kit Olika 0.8 5.2 5.2 1.1 1.1 1.5 2.0 0.8 0.1 3.0 2.5 / 3.9 / 2.5 3.4 / 4.8 / 3.4 0.31.0 0.23

See page 3/44 3/44 3/44 3/44 3/44 3/44 3/44 3/44 3/44 3/44 3/44 3/45 3/45 3/46 7/2