Dry pre-assembled cable termination, outdoor TD 145 kV

Use For installations in which the cable termination is to be used as a fixed connection point and in installations where there is a risk of very high continuous creepage currents. Standard Meets the requirements of: IEC 60840 Design TD 145 contains of: a pre-assembled cable termination, top bolt and bolt clamp in the top fitting and also cable clamp and earth clamp.

top bolt bolt clamp

The cable termination consists of a composite insulator with integrated base part, stress cone, support pipe and dry electrical insulating silicone compound. Both the support pipe and the cable clamp are made of fiberglass reinforced polyester that provides an insulated installation. The field control component is a premolded stress cone. The termination has a minimum creepage distance of 4650 mm, which means it fulfills Pollution class IV according to IEC 60815-3. A bolt clamp for the cable conductor and a top bolt is included in the kit. For the maximum permitted diameter across the oversheath of the cable and the diameter across prepared insulation, see the table below. Installation The termination comes pre-assembled from the factory which remarkably reduces installation time after cable preparation. Installation can be made horizontally or vertically. No filling of insulating medium at site. When ordering, please state the following data: Diameter across prepared insulation Conductor cross section Screen, cross section and type Outer diameter of cable If optical fibres in screen Diameter and material of the top bolt, Cu or Al for connecting to overhead power line
Insulation diameter min mm 53 102 max
Base part

Outer sheath max mm 150

Max conductor cross section mm 2500

Voltage kV 145

Insulator

Designation

Creepage distance min mm 4650

Prefabricated cable termination cable clamp earth clamp

Net weight kg/item 100

Composite

TD 145

6/13 | Kabeldon cable accessories 1420 kV | Cable accessories for XLPE-insulated cables 52420 kV

Technical specification, applications and accessories TD 145 kV

40/50/54/60

~ 130 mm

Max. permissible forces acting on the top bolt, horizontally and vertically: 2000 N.

18.5

Dimensions in mm

140

345-350

Creepage distance min 4650 mm

345-350 min 280

Fixing to bracket Insulated or non-insulated: four 18.5 mm holes for M16 bolts.

1630 mm

45

380 mm

325 mm

Accessories, to be ordered separately

Inclination up to 45.

Selection table for installation cone


Inner diameter
RKM 145 Installation tool. Opto kit

Outer diameter mm 53 55 58 61 64 67 70 73 78 84 93 102 105

Installation cone Article number 4209.2384 4209.2385 4209.2386 4209.2387 4209.2388 4209.2331 4209.2332 4209.2333 4209.2334 4209.2335 4209.2336 4209.2337 4209.2400

Optical fiber kit for cables with


integrated optical fibers in the earth screen.

Installation cone.

Designation RKM 145 Installation cone Opto kit

Description Installation tool Installation cone, see table. Optical fiber kit for optical fibers in the screen of the cable

kV 20 22 22 29 38 28 32 36 43 48 51 57 57

Designation JSA SCK

Description Earthing kit for cable with metallic sheath, e.g. lead. Not needed if cable has only Cu-wire screen. Screen connection for Al-foil radial waterproof cable. Not needed if cable has only Cu-wire screen.

See page 6/21 6/21

Cable accessories for XLPE-insulated cables 52420 kV | Kabeldon cable accessories 1420 kV |

6/14