RELAY COORDINATION BETWEEN INCOMER & OUTGOING FEEDERS OF MV SWITCHGEAR

CTR 2500/1

I/C

CTR 700/1

CTR 250/1

CTR 2500/1

CTR 1250/1

4500KW

2500KVA

2500 A

1250 A

I]

Between Incomer and Motor Feeder FAULT TYPE: SHORT CIRCUIT Motor Rating Motor rated voltage Motor full load current CT Ratio (CTR) CT Secondary current

4500 KW 6.6 KV 454.2 700/1 0.65

Calculation of Operating time of over current protection of Motor Feeder Current Setting in % (PS) Current Setting (I>) (CTR X PS) Fault Current considered (Amps) (I) Operating time calculated as follows

2.0 1400.00 25000

1 >

+ K
IEC Very inverse (A) (B) 13.5 0

1 >

Selected Characteristic Time/current curve group Very inverse C K (TMS)

1 0.7

Operating time of Over current protection,t (sec)


II Calculation of required TMS for Incomer Feeder Fault current considered (A) Current Setting in % (PS) Current Setting (I>)

0.5606
25000 100% 2500

Operating time calculated as follows

1 >

+ K
IEC Very inverse (A) (B) 13.5 0

1 >

#REF!

Selected Characteristic Time/current curve group Very inverse C K (TMS)

1 0.92

Operating time of Over current protection,t (sec)

1.38
0.529 0.92

Minimum TMS for discrimination Selected TMS considering that TIE between unit boards are closed

I]

Between Incomer and Transformer Feeder FAULT TYPE: SHORT CIRCUIT Transformer Rating Transformer rated voltage Transformer full load current CT Ratio (CTR) CT Secondary current

2500KVA 6.6 KV / 433V 218.69 250/1 0.87

Calculation of Operating time of over current protection of Transformer Feeder Current Setting in % (PS) Current Setting (I>) (CTR X PS) Fault Current considered (Amps) (I) Operating time calculated as follows

0.9 225.00 25000

1 >

+ K
IEC Very inverse (A) (B) 13.5 0

1 >

Selected Characteristic Time/current curve group Very inverse C K (TMS)

1 1

Operating time of Over current protection,t (sec)


II Calculation of required TMS for Incomer Feeder Fault current considered (A) Current Setting in % (PS) Current Setting (I>) Operating time calculated as follows

0.1226
25000 100% 2500

1 >

+ K
IEC Very inverse (A) (B) 13.5 0

1 >

Selected Characteristic Time/current curve group Very inverse C K (TMS)

1 1

Operating time of Over current protection,t (sec)

1.5
0.529 0.92

Minimum TMS for discrimination Selected TMS considering that TIE between unit boards are closed