Code No: NR310203 NR

III B.Tech I Semester Supplementary Examinations, February 2007


POWER SYSTEMS-II
(Electrical & Electronic Engineering)
Time: 3 hours Max Marks: 80
Answer any FIVE Questions
All Questions carry equal marks
?????

1. (a) Discuss the concept of geometric mean distance. How this concept used to
find the inductance of composite conductor line.
(b) A 3-phase single circuit 132 KV overhead line has conductors of diameter 1.8
cm each. The spacing between conductors is 4 m, 6 m, and 9 m. Find the
inductance per phase per km. [6+10]

2. What is method of images? Derive an expression for the capacitance per unit length
of a 3-phase transposed line. What is the effect of earth on the capacitance of the
line? [4+8+4]

3. (a) Discuss why equivalent π circuit of a long line is preferred over the equivalent
T circuit.
(b) A three phase 50 Hz transmission line is 150 km long and delivers 25 MW at
0.85 power factor lagging and at 110 KV. The resistance and reactance of the
line per conductor per km are 0.3 ohms and 0.9 ohms respectively. The line
charging admittance is 0.3×10−6 mho per km per phase. Compute by applying
the nominal π method the voltage regulation and transmission efficiency.
[4+12]

4. (a) Each conductor of a 33 KV, 3-phase system is suspended by a string of three


similar insulators, the capacitance of each disc is nine times the capacitance
to ground. Calculate the voltage across each insulator. Determine the string
efficiency.
(b) A string of eight suspension insulators is to be graded to obtain uniform dis-
tribution of voltage across the string. If the capacitance of the top unit is 10
times the capacitance to ground of each unit, determine the capacitance of
the remaining seven units. [8+8]

5. An overhead line has a conductor of cross-section 2.5 cm2 hard drawn copper and a
span length of 150 metres. Determine the sag which must be allowed if the tension
is not to exceed one-fifth of the ultimate strength of 4,175 Kg/Cm2 .

(a) in still air and


(b) with a wind pressure of 1.3 kg/metre and an ice coating of 1.25 cms.

Determine also the vertical sag in the latter case. [8+6+2]

6. (a) Derive an expression for the capacitance of a single core cable.

1 of 2
Code No: NR310203 NR
(b) The insulation resistance of a single core cable is 495 MΩ/km. If the core
diameter is 2.5cm and resistivity of insulation is 4.5 × 1014 Ω − cm. Find the
insulation thickness. [8+8]

7. (a) Explain the concept of power factor.


(b) Explain any three causes of low power factor of supply system.
(c) Discuss the disadvantages of low power factor and list methods to improve
power factor. [4+4+8]

8. (a) What is the symmetrical components? Why they are necessary?


(b) A 3-phase unbalanced system currents are read as IR =150A, IY =130A and
IB =10A. the phase sequence is RYB. Find all the three symmetrical compo-
nents for the case. [6+10]

?????