Automated Logic Corporation - WebCTRL

ZN220; ZN253; ZN551


Primary Control Unit ZN Line Last Saved: Mar 29, 2004 4:18:18 PM Description

Product Name(s): Product Description: Product Application(s):

ZN220 ZN253 ZN551

Stand-alone Zone Controllers The ZN253 and ZN551 are zone controllers for VAV, heat pump, unit ventilator and other packaged HVAC applications. The ZN220 is suitable for a variety of applications including fan coil units, lighting, and exhaust fan control.

Automated Logics line of RS room sensors and provides local access to the system. Control Unit Model #: ZN551 ZN253 ZN220 AI DI UI 5 5 2 DO 5 2 2 AO 1 3 0 X UO Other

A/D Converter Resolution

8 bit 10 bit 12 bit 16 bit Other

D/A Converter Resolution

- 6 bit X 8 bit - 10 bit - No Analog Output - Other


X No

HOA switches provided on each output?

Note: These are also available as an add-on from 3rd party vendors. - Both AO and DO
- DO Only - Other X No AO and DO AO Only DO Only Other

Indicating status LED on each output?

Additional Features

VAV Controllers No Integral Flow Sensor? No Integral Damper Actuator? Can controller accept occupant override from thermostat? Yes Yes (dry contact or 0-5Vdc) Can controller accept occupancy sensor input?

I/O Expansion ZN551 and ZN253 are compatible with U Line Single air Flow sensor (USF) or U Expander Line Dual air Flow sensor (UDF) for pressure independent VAV applications. Boards Connects directly with cable/connector provided with USF and UDF. Expansion Device Model # USF UDF AI 1 1 DI UI DO AO UO Other

Network and External Communication Ports Network Ports, Protocol(s), and (1) EIA-485 BACnet port to primary BACnet network Speed(s) Supported (ARCNET at 156 kbps or MS/TP at 9.6, 19.2, 38.4, or (Note: See 'Architecture' for network 76.8 kbps) details) (1) Local access port for system start-up and External Communication Ports, troubleshooting Speeds and Access Devices (1) Rnet port for RS room sensors Additional Information (Optional)

Operator Interfaces (via Controller) * no Access controller only no Access controller plus additional controllers on network segment / LAN Network Accessing Capabilities via yes Access all controllers on system Controller no No access available on this controller no Other yes Laptop/PC no Local Display Panel (controller-mounted) no Local Display Panel (zone-mounted) no Handheld Interface Device (proprietary device) no PDA (3rd-Party HID) yes Zone-Based port (details below) no Other

Controller Access Devices

Functions Available Through Field Interface** : Laptop/PC Zone-Based port (details below)

View Params X X

Change Params X X

Change Programs/Logi c X X

O&M Support X X

TAB/Cx Support X X

Zone-Based Interface Access

Laptop can be connected to the RSPro and RSBasic sensor for full system access. yes Zone-Mounted touchpad (thermostat or stand-alone display) no HID (proprietary device) no PDA (3rd party HID, with software) yes Laptop/PC no none no Other

Zone Interface Hardware

*Note: This section covers the capabilities for accessing the controller or other parts of the network from the controller (i.e. 'bottom-up'). Standard access functionality is covered in the Architecture and Software sections. **Does NOT include front-end OI functions. See vendor for specific functions available.

Microprocessor(s)

Processor, Memory, and Battery 16-bit microprocessor with ARCNET communication coprocessor. no no yes no no Powered, battery-backed Battery powered Powered, no battery backing None Other

Clock Type

Clock Synchronization Volatile Memory (RAM) Capacity

Time synchronization occurs periodically through broadcasts from the WebCTRL server, and from the BACnet Router on each network segment. Module only contains non-volatile and flash memory. - RAM use unrestricted - RAM use restricted as shown below - Information Not Provided

Volatile Memory (RAM) Uses

no no no no yes N.A. N.A. N.A. N.A.

Program Execution / Calculation storage Data / Trends / Alarms storage Configuration / Parameter storage Control Programming storage Others (N.A.)

Is Volatile Memory Supported By Battery? Battery Type(s) Battery Life Backup Battery Operating Time Non-Volatile Memory Capacity (EEPROM/Flash) *

512 KByte non-volatile battery-backed RAM, 1 MByte Flash memory, 16-bit memory bus yes yes yes yes no Data / Trends / Alarms / Calculation Storage Configuration / Parameter Storage Control Programming Storage Controller Operating System Other

Non Volatile Memory Uses

Additional Information * Items in NV memory are not lost upon power or battery failure. Other types of NV memory such as EPROM, NOVROM, etc. do not directly impact system performance.

Trend Data Storage Can trend data be stored in this controller? Yes

The user has complete control over how trend memory is used, including how many points are trended, how often the trend How many total trend values samples are taken, how many samples are stored in the module, can be stored? and whether or not the trend data will be backed up to a historical database on the server. What is the controllers role in Controller samples data either at time intervals or based on change of value trending? Can controller be programmed to 'push' data to Controller can be programmed to push data to archive, or data archive or are trends 'pulled' can be dynamically pulled from the controller for display from controller? When full, does controller automatically send up trend User defines whether controller should stop when full or begin data; overwrite data, or stop overwriting oldest data logging data?

Programming Method(s) (See Also 'Software' Form) Resident vs. Non-Resident Program Execution

Programming ZN Line controllers are fully graphically programmable using the Eikon graphical programming software. All graphical programs reside in the controller. no Resident/Supervisory. This controller supervises the scheduling of other controllers. yes Resident/Stand Alone. This controller contains its own schedule. no Non-Resident. This controller is dependent upon another controller for its schedule. no None. This controller has no scheduling features. no Other

Scheduling (See Also 'Software' Form)

no Energy management algorithms for this controller can be custom programmed yes Pre-programmed/built-in algorithms (Controller-resident energy management available, and are fully editable using functions/algorithms calculated and performed custom programming by this controller. These typically require pointsharing and can involve calculations and no Pre-Programmed/built-in with limited multiple-loop functions. One or more of these editing via template-based programming Resident Energy Management

choices may be selected.)

no Controller is not typically used for energy management functions no Others no None (custom programming only) no None (not applicable) yes Optimal Start/Optimal Stop yes Peak Demand Limiting/Load Shedding no Economizer (enthalpy, dry-bulb, CO2, modulating/2-position, etc.) no Other no Additional Energy Management functions are resident at SI A library of pre-engineered control routines provides solutions for most zone control applications. Custom programs can be easily written in EIKON using ALCs graphic programming language.

Specific Pre-Programmed Algorithms Available

Additional Programming Functions

DDC Loops (P, PI, PID) Automatic PID Tuning Feature Automatic-Dial Alarm Support

Controller Features Available through custom Eikon graphical programming No

Yes (See 'Software' for further information) Does controller perform multiple retires and Yes buffer/store alarm until connection is made? Yes Are multiple destinations possible? Upon controller power loss or hardware failure: No Are network communications affected? Is loss recognized on/by the network and Yes alarm reported? - Outputs fail to a user pre-specified position X Outputs fail to a normal (unpowered) position - Outputs fail to last position - Other - Lost X Retained for life of backup battery (shelf life

DO and AO response?

Volatile memory functions?

(See 'Memory' section)

10 years with 10,000 hours of continuous operation) - Other

Upon restoration of power does the controller: Auto-reboot without operator intervention? Yes Automatically reset/synchronize the clock? Yes Yes Update all monitored functions? Generate an alarm if backup battery is Yes dead? Upon network or communications failure: Does controller: Yes Continue to operate standalone? Operate with last global settings or userUser-specified default values specified value? Do broken network segments continue to communicate within the remaining segment? Yes. (Note: may depend on proper termination of segments for higher speed networks.) Does network automatically reconfigure Yes upon restoration? Does network store 'loss of communications' Yes alarm with time of event? Additional Information (optional) Self Test Diagnostics Does controller have internal self-test diagnostics to check: Processor failure? Internal hardware failure? Open/shortened sensor? Others? Control Enclosure Yes Yes

Rugged GE C2950 Cycoloy plastic

Power Supply Power Supply Required 24 Vac 10%, 26 Vdc (25 V min, 30 V max), 50 to 60Hz, Voltage 20 VA VA Surge Protection

Listing, Labeling, and Compliance Underwriters Laboratories UL 916(Canadian STD C 22.2 No.205-M1983) Part 15-Subpart B-Class A FCC Yes CE X X Yes No No - but LonWorks compatible Information not provided Yes No Not submitted for testing Information not provided

LonMark Certified

BACnet (BTL) Certified

Other

LGR Line Last Saved: Feb 27, 2004 10:10:04 AM Description

Product Name(s): Product Description: Product Application(s):

LGR-25 LGR-1000

The LGR is a router/gateway that can connect to a BACnet/IP backbone. Support for BACnet/IP, BACnet-over-Ethernet, ARCNET 156 kbps, MS/TP, and BACnet PTP communications are standard. A wide range of open and proprietary protocol translator drivers allow the LGR to also serve as a gateway to other manufacturers equipment. Fully programmable, the LGR can also execute control strategies for system integration. Supported by the Iowa Energy Center.