Sie sind auf Seite 1von 115

Navigation directions for Catalog 2013/2014

Dear Madam/Sir, all index entries and cross-references in this catalog have been laid out as hyperlinks to help you get to the required product or information as quickly as possible. There is a grey button labelled Table of Contents on top of each page which takes you back to the Table of Contents immediately. We offer you the following search options: - Applications Overview (page 4/5) - Table of Contents (page 6) - Type Index (page 111) Enjoy browsing through our new GOSSEN METRAWATT catalog 2013/2014!

go to T&M Catalog

Measuring Instruments

and Testers

20

13

/2

01

2 SAFEtY thRoUgh CompEtENcE

E DITORIAL
Dear reader, Thank you for your interest in our products and services covering all aspects of measuring and test technology. Our product range is distinguished by values such as quality, reliability, safety and advanced technology, as well as dynamic design, extremely easy operation and a unique innovative spirit. After all, our measuring and test technology expertise is built into each of our products and has been for more than 100 years. Again and again, users tell us that measuring and test systems from Gossen-Metrawatt are safe, reliable and economic, and were very pleased to hear it because this is precisely what we strive to accomplish, and thats what differentiates us from the competition. And were self-assured enough to go one step further as well: Gossen-Metrawatt stands for reliability and competence in measuring and test technology. Were ready to meet the challenges of future market developments with attractive new products, as well as services, consultation, project engineering, training and on-site assistance. You get support and competent, personalized advice. This is your guarantee of a customer-oriented sales network with highly qualied sales engineers. Weve grown together with you over a period of many decades, and have always striven to align ourselves to you requirements You can count on us!

Ma

de

in G er m

an

GOSSEN METRAWATT

SaFEtY StaNdaRd: IEC 61010-1

MEasURING CatEGORIEs

IEC 61010-1

CAT II

CAT IV

CAT I
CAT CAT I (0)* CAT II CAT III CAT IV
* Per DIN EN 61010-2-030

CAT III
Description Measurements in electrical circuits which are not directly connected to the mains Measurements in electrical circuits which are directly connected to the low-voltage mains Measurements in building installations Measurements at power sources for low-voltage installations e.g. batteries etc. via plug, e.g. in household, office and laboratory applications Stationary consumers, distributor terminals, devices connected permanently to the distributor Meters, mains terminals, primary overvoltage protection devices Applications

With regard to multimeters and test instruments, the CE declaration of conformity conrms that European regulations (low-voltage directive and EMC directive) are adhered to.The CE declaration is a prerequisite for putting products into circulation within the European Community. Adherence is substantiated by fullling the following standards: IEC61010-1 (international), EN61010-1 (German version) and VDE classication VDE0411-1.

Safety requirements for electrical equipment for measurement, control and laboratory use are described in this standard. Currently valid safety regulations include: IEC 61010-1:2010 + Cor.:2011 DIN EN 61010-1:2010 VDE 0411-1:2011

in de

Ma

Germ a
ny

GOSSEN METRAWATT

APPLIcatIONs: Overview

Medical Technology
n SEcULiFE (+accEssORiEs)............ 77
n SEcUtEst n SECULIFE

Electrical Engineering /Semiconductors:


n KONstaNtERSSP 32/62/64N........98 n KONstaNtERMSP 64D................100 n METRAHIT 30M................................12 n METRAHIT ULTRA.............................13 n MavOWatt/MavOsYs*.................. 38 n MavOLOg........................................... *

(+accessories).............. 75 SB................................... 78 n SECULIFE HIT.................................. 23 Welding and Soldering Technology:

n SEcUTEST S2N+W...........................75 n SEcUstaR FM+................................78 n SEcULOad....................................... 84 n 3-Phase adapters............................ 84 n METRAHIT ENERGY...........................13 n METRAHIT ISO..................................14

Communications Engineering / Telecommunications:


n KONstaNtERSYSKON P series...... 96 n KONstaNtERSSP 32/62/64N....... 98 n METRAHIT T-COM plus (KMM2009)..14 n Rotation angle measurement technology

Service (Instrument Repairs)


n MEtRatEstER 5...............................79 n SEcUtEst (+accessories).............. 75 n METRAHIT 27M/I/AS........................20

Events Technology, Stage Construction and Lighting Technology:


n SEcUtEst (+accessories).............. 75 n MavOLUX 5032B/C USB................108 n MavO-MONITOR USB.....................109 n MavO-SPOT 2 USB.........................110 n PROFitEst Master...........................46 n MavOWatt...................................... 38

Mining Engineering: n PROFitEst Master.......................... 46 n METRAHIT World IS (South Africa)...15 n Rotation angle measurement technology

Chemicals and Pharmaceuticals Industry:


n Controllers and control systems........ * n METRACAL MC.................................18 n METRAHIT ULTRA.............................13 n PROFitEst Master.......................... 46 n Energy management systems............ * n Process measuring technology.......... * n Heavy-current engineering................ *

Electrical Safety Service Providers, Maintenance Departments:


n SEcUtEst (+accessories).............. 75 n SEcUstaR FM+ (+accessories).......78 n MiNitEst..........................................80 n PROFitEst Master.......................... 46 n MULtimEtERs................................... 7

Education (Vocational Training Schools and Universities):


n KONstaNtERSSP 32N...............98 n KONstaNtERLSP series..............101 n KONstaNtERSYSKON P series......96 n PROFitEst Master.......................... 46 n METRAHIT 2 plus..............................15 n SEcUtEst (+accessories).............. 75 n MEtRatEstER 5............................... 79 n Test panels...................................... 81 n MavOWatt...................................... 38 n Electronic Loads.............................102 n Heavy-current engineering ............... *

Automotive/eMobility R&D, Test&Production Departments: n Laboratory power supplies..............95 n METRAport 40S (VAG1526)...............16 n METRAHIT H+ E CAR........................21 n Current clamps............................... 28 n PROFitEst Master.......................... 46 n SEcUtEst (+accessories).............. 75 n Energy management systems............ *
in de

Ma

Germ a
ny

GOSSEN METRAWATT

APPLIcatIONs: Overview

Tooling Expenditures
n MiNitEst..........................................80 n SEcUtEst (+accessories)...............75

Utility Companies, Renewable Energy Technology (solar, photovoltaic, wind power):


n MavOWatt...................................... 38 n PROFitEst Master.......................... 46 n Raytech........................................... 71 n Earth testers................................... 56 n PROFITEST PV / PV SUN.................. 62 n Current clamps............................... 28 n Load optimizing, U1500..................... * n METRAHIT ISO (Suntech)..................14 n METRAHIT OUTDOOR (offshore)........12 n Electronic Loads.............................102 n A series (210, 230, Aplus).................. * n Energy management systems............ * n Heavy-current engineering ............... * n Rotation angle measurement technology n MavOsYs*/MavOLOg....................... *

Aviation /Railway Technology (VDE 0115)/Shipbuilding:


n METRAHIT ISO@Aero.......................14 n MavOWatt...................................... 38 n Earth testers................................... 56 n PROFitEst Master........................... 46 n Insulation measuring instruments.. 51 n Charging concepts, SYSKON P series.96 n Electronic Loads.............................102 n Rotation angle measurement

technology......................................... *

Machinery Manufacturing:
n PROFitEst 204................................ 60 n MEtRisO 5000 (A, D-PI).................. 54 n Phase sequence indicators............. 66 n Controllers and control systems........ * n METRAHIT 1ASI................................19 n METRAHIT ENERGY...........................13 n MavOWatt/MavOLOg*.................. 38 n Process measuring technology......... * n Rotation angle measurement technology

Electrical Trades: n MavOWatt.......................................38 n PROFitEst Master...........................46 n Voltage testers................................ 66 n Insulation measuring instruments.. 51 n Earth testers....................................56 n PV module measuring instruments. 62 n Current clamps................................28 n SEcUtEst (+accessories)...............75 n METRAHIT PRO.................................10 n MiNitEst..........................................80 n MEtRatEstER 5...............................79 n Test panels...................................... 81

*Camille Bauer
Further information regarding products for the elds of heavy-current engineering, rotation angle measurement and process metrology can be found in the catalogs issued by Camille Bauer AG, or at: www.camillebauer.com and www.gossenmetrawatt.com
in de

Textiles
n OEM KONSTANTER.........................106

Ma

Germ a
ny

GOSSEN METRAWATT

TaBLE OF CONtENts

MULtImEtERs. .................................................. 7 Multimeters 7


HandheldDigital digital Multimeters: multimeters: Handheld A series..and ................................................................................... 8 Symbols Their Meanings...................................................... 8 ESeries.................................................................................. series..................................................................................... 9 A 10 seriesspecial instruments...................................................11 10 ESSeries. .................................................................................. Handheld multimeters.................................................... 12 S Series digital Special Devices....................................................... 12 Handheld analog multimeters................................................... 13 Multimeters Insulation Measuring Instruments........................ 14 Process calibrator and multimeters........................................... 14 Handheld Digital/Analog Multimeters......................................... 15 Calibrator and diagnostics unit..................................................16 15 Folding Digital/Analog Multimeters............................................ InsulationAnalog measuring instruments. .............................................17 16 Handheld Multimeters .................................................. Milliohmmeters and insulation measuring instruments................18 17 Process Calibrator / Multimeters............................................... Overview................................................................................. 18 Calibrator / Diagnostics Unit...................................................... 19 Accessories: / Insulation Measuring Instruments.................... 20 Milliohmmeters Adapters/charger.................................................................... 22 Handheld Digital Multimeters: Overview..................................... 22 Power packs / eld measuring adapters.................................... 23 Accessories: Current sensors....................................................................... 24 Adapters / Charger................................................................... 26 Current clamp sensors.............................................................27 25 Power Packs ........................................................................... CurrentSensors. transformers / probes...................................................28 26 Current ...................................................................... Temperature sensors. ...............................................................29 27 Current Clamp Sensors............................................................ Probe /cable sets .................................................................... 28 Current Transformers / Probes.................................................. 30 Cable sets /fuses. ....................................................................31 29 Temperature Sensors............................................................... Software. ................................................................................. 30 Probe /Cable Sets ................................................................... 32 Pouches / cases......................................................................33 32 Fuses...................................................................................... Software.................................................................................. 34 Pouches /Cases...................................................................... 36 Power quality 33

DIN VDE 0113/EN 60204........................................................ 60 Testers electrical equipment 63 Accessories............................................................................. 61 DIN VDE 0701-0702IEC62353 (VDE 0751)............................ 64 Photovoltaics .............................................................. 62 Medical technology and production........................................... 65 METRALINE............................................................................. 64 Facility management solution modular test system. . ................ 66 METRATHERM......................................................................... 65 Overview................................................................................. 67 Phase Sequence Indicators /Voltage Testers.............................. 66 DIN VDE 0701-0702. . .............................................................. 68 Current Clamp Meters.............................................................. 68 DIN VDE 0701-07023-phase testers. . .................................... 69 Overview of Accessories........................................................... 70 Accessories. . ........................................................................... 71 High-Voltage Transformers........................................................ 71 Accessories DIN VDE 0701-0702........................................... 72

TEstERs.......................................................... 73

MaINs QUaLItY............................................... 37 3-phase energy and power disturbance analyzers...................... 35


Software.................................................................................. 39 Power Meters /Voltage Quality.................................................. 38 3-Phase Energy and Power Disturbance Analyzers..................... 39 Test instruments Accessories. ............................................................................41 43 Software. . ................................................................................ DIN VDE 0100600/IEC 60364-6...........................................44 42

Power meters /voltage quality................................................... 34

TEstERs. ........................................................ 45 Ohmmeters./insulation measuring instruments.......................... 46


Insulation measuring instruments.............................................. 48 DIN VDE 0100600/IEC 60364-6........................................... 46 Earth testers. ........................................................................... 50 Accessories............................................................................ Accessories.............................................................................50 51 Ohmmeters Insulation Measuring Instruments........................... 51 DIN VDE 0113/EN 60204........................................................ 54 Low-Resistance / Insulation Measuring Instruments................... 52 Accessories............................................................................. 55 Insulation Measuring Instruments /Accessories......................... testers...............................53 56 Phase sequence indicators /voltage Insulation Measuring Instrument / ISO Calibrator........................ 54 Current clamp meters.............................................................. 58 Insulation Measuring Instruments.............................................. 55 Clamp meters. ......................................................................... 59 Earth Testers........................................................................... Overview of accessories...........................................................56 60 Accessories. ............................................................................ High-voltage transformers........................................................57 61

Accessories............................................................................. 45

Software Equipment. test instruments Electrical Safety of .................................................. 77 74 Test Cases, Workshop Test Panels. ............................................ 81 Software for test instruments. ................................................... 78 Accessories:............................................................................ 82 Adapters, Cables..................................................................... 83 Laboratory power supplies 83 Sensors. .................................................................................. 86 Pouches, Cases....................................................................... 87 Computer controlled laboratory power supplies: Identification Accessories......................................................... 88 SYSKONP series...................................................................... 84 SYSKON 1500W...4500W........................................................ 85 SOFtwaRETEstERs..................................... 89 SSP 120W...320W.................................................................. 86 SSP 500W...3000W................................................................ 87 LaBORatORY POwER SUPPLIEs.95 KONSTANTER MSP 2x24W...120W.............................................................. 88 Analog laboratory power supplies: Programmable Laboratory Power Supplies: SLP 120W...320W and LSP 25W+25W+35W........................ 89 1500Wto4500W. ................................................................... 96 LSP 33K, LSP 32K and SSL 32EL............................................. 90 120Wto320W. ....................................................................... 98 Remote software. ..................................................................... 91 500Wto3000W. ..................................................................... 99 Overview of all KONSTANTERs. .................................................. 92 24W/49W/120W, up to 8 Channels. .................................... 100 Overview of laboratory power supplies and accessories.............. 93 90Wto108W. ....................................................................... 101 Laboratory power supplies: OEM product overview..................... 94 Analog Controlled Laboratory Power Supplies: 120W to 320W.101 Programmable Electronic Loads: 150Wto400W..................... 102 Software ............................................................................... 103 Photometry and temperature measurement 95 Laboratory Power Supplies: Overview and Accessories............. 104 Illuminance meters. .................................................................. 96 Power Supplies: OEM Product Overview.................................. 106 Luminance meters................................................................... 97 Infrared thermometers.............................................................. 98
Illuminance Meters................................................................. 108 Luminance Meter Contact Measurement.............................. 109 Luminance Meter Distance Measurement............................. 110

PHOtOmEtRY................................................ 107

TYPE INdEX................................................... 111


Recommended Workshop Equipment...................................... 112

Our New Products


METRAHIT H+E CAR.......................21 METRAHIT ULTRA............................13

METRISO G1000+...........................52 PROFITEST PV SUN.........................63

New! GMC-I app: VDE testing made easy! Terminology, standards, publications Product overview and much more The latest news from GMC-I? Visit us at Facebook.

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

MULTImETERS

MULTIMETERS
A multimeter is an electronic measuring instrument that combines several measurement functions into a single unit, and is used primarily to measure electrical quantities. To measure means to compare a known quantity with an unknown quantity. The standards of measure of the PTB in Brunswick (German Federal Institute of Physics and Metrology) are used as comparative quantities for our multimeters This is conrmed by means of a DAkkS calibration certicate. Multimeters included in the MEtRaHit series are rugged, reliable digital multimeters with housings made of impact resistant plastic, and are equipped with unique, patented automatic blocking sockets (ABS). The devices feature a new design and are equipped with state-ofthe-art technology and safety.

GOSSEN METRAWATT

HANDhELD DIGITAL MULTImETERS: Symbols and Their Meanings

Table of Contents

Selecting the Right Digital Multimeter (DMM)


The icons help provide the user with quick, condensed information regarding the range of applications and the functions of the respective DMM, thus assuring correct selection. Important selection criteria include: Number of displayed digits in digits  Integrated data memory and the interface for data Range of application, e.g. CATIII, transfer for analysis at a PC and max. permissible voltage, e.g. 1000V  Special device functions such as milliohm measurement by means of 4-wire measurement, as Measuring accuracy well as insulation, power and energy measure Bandwidth or frequency range for TRMS measurement ment, calibration functions, intrinsic safety etc.  The current measurement function either direct, or via current transformers or current sensors

Symbol

Meaning VDE approval mark Tested safety

Symbol Rubber holster

Meaning

ABS RANGE
AUTO/MAN

Automatic blocking sockets Measuring range selection, automatic/manual Connector jack for external power pack Battery display Battery charge level indicator

TRMS
AC

True root mean square (TRMS) for alternating quantities TRMS for alternating and pulsating quantities TRMS for alternating quantities up to 100 kHz Measuring category / overvoltage category Storage of min./max. measured values Data logger function Infrared data interface Bluetooth data interface

TRMS
AC+DC

100 kHz

TRMS

300 V
CAT IV

Battery operation Measurement of alternating, direct and pulsating voltage Measurement of alternating, direct and pulsating current Activatible low-pass lter AC voltage measurement with low input impedance (prevents measurement of phantom voltage) Temperature measurement by means of thermocouples and resistance temperature detectors

DATA
Min-Max

AC, DC, AC+DC

DATA LOGGER

AC, DC, AC+DC

IR

FIL
1 kHz

60,000

1 M

LoV

Digits

Display range (resolution)


TC/ RTD

0000 0000

00000

Triple digital display

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

HANDhELD DIGITAL MULTImETERS: Symbols and Their Meanings

Symbol

Meaning Continuity test with acoustic signal CLIP factor (adjustable transformation ratio for interconnected current clips) Highest resistance measuring range Frequency measurement up into the MHz range Duty cycle Voltage level measurement in decibels RPM measurement Capacitance measurement Diode test IP 65 protection Additional, virtual analog display Automatic circuit breaker USB Port

Symbol
RS 232

Meaning Serial port LED display LCD panel Mains operation Acoustic signals Kelvin connection (4-wire)

CLIP 40 M

LED LCD

MHz % dB

Power Pack

RPM

Ri

Internal resistance Earth resistance measurement Diode signal

IP 65

Clip

Factor

Transformation ratio for current clamp measurement For avionics service

Bar Graph

AUTO Fuse

Ri

Internal resistor Additional display illumination

dB

Voltage level measurement in decibels Acoustic signals

xdB 0dB xdB

Differential level measurement Measurement data acquisition software Data storage Power quality measurement Active power measurement Accuracy class (e.g. 20% of MR)
in de

Software

TouchScreen

Touch-screen Loop impedance measurement Low-resistance measurement Optical indicators

Memory

Rs
Low

PQ W
Class

2.5

Ma

Germ a
ny

GOSSEN METRAWATT

10

HANDhELD DIGITAL MULTImETERS: A Series

Table of Contents

A
A Series TRMS TRMS
AC
AC+DC

4 Digit TRMS Digital Multimeter for Professional Use with a Resolution of 12,000 Counts
n DAkkS calibration certicate Scope of delivery, A series: n KS17-2 measurement cable set n R  ubber holster n Two 1.5V AA batteries (XTRA only) nS  et MEtRaHITIPro (M242D):

in HC20 case with WZ12A AC current clamp

600 V 1000 V
CAT IV CAT III
D-K1508001-01

RANGE

AUTO/MAN

40 M

AC, DC, AC+DC

ABS

Our Top Model

DATA
Bar Graph Min-Max

METRAHITIBASE
Article: M241A Multimeter with high-impedance measuring inputs without direct measurement of current, e.g. for use in the eld of energy technology at power utilities

METRAHITIPRO
Article: M242A Multimeter with low-pass lter and low-impedance voltage input, e.g. for measurements at frequency converters

METRAHITITECH
Article: M243A Multimeter with optimized current ranges, e.g. for measurements at measuring transducers in the process industry

METRAHITIXTRA
Article: M240A System multimeter with data logger, IR interface and power pack socket for use in combination with PCs

Function
Clip function Frequency measurement Duty cycle Temperature Power pack connector socket IR interface Data logger LO voltage with low-pass lter Rubber holster HC 20 case TRMS bandwidth (VAC) TRMS current measurement Capacitance measurement Resolution
in de

BASE
n

PRO

TECH
n

XTRA

100 kHz TC Optional 1kHz 12,000

100kHz TC
n

100kHz TC
n

1MHz
n

TC/RTD
n n n n n

Optional 10kHz 1A/10A 12,000

Optional 10kHz 10mA/100mA/1A/10A


n

20kHz 100A...10A
n

12,000

12,000

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

HANDhELD DIGITAL MULTImETERS: E Series

11

E
E Series TRMS
AC
AC+DC

4 Digit High-End TRMS Digital Multimeter, System Compatible with IR Interface Resolution: 60,000 Counts Scope of delivery, E series:
n KS17-2 measurement cable set n Two 1.5 V AA batteries n DAkkS calibration certicate n Rubber holster n Set with HC20 hard case

TRMS 600 V 1000 V


CAT IV

CAT III RANGE


CLIP

AUTO/MAN

60 M

AC, DC, AC+DC AC, DC, AC+DC

ABS
D-K1508001-01

Our Top Model

DATA
Bar Graph Min-Max

IR

METRAHITIEBASE
Article: M251A Same applications as BASE but with higher resolution and system interface

METRAHITIESPECIAL
Article: M252A Special multimeter for connection to current transformers without fuses, in order to eliminate danger resulting from interruption of the transformer circuits

METRAHITIETECH
Article: M253A Same applications as TECH but with higher resolution and system compatible thanks to IR interface

METRAHITIEXTRA
Article: M250A Same as XTRA with larger data memory, higher resolution and VAC bandwidth up to 100kHz

EBase
n

ESPECIAL
n

ETECH
n

EXTRA
n

Function
Clip function Frequency measurement Duty cycle Temperature Power pack connector socket IR Interface Data logger LO voltage with low-pass lter Rubber holster HC 20 case TRMS bandwidth (VAC) TRMS current measurement Capacitance measurement Resolution
in de

300kHz TC
n

300kHz TC
n

300kHz TC/RTD
n

1MHz
n

TC/RTD
n n n n n n


n n

n n n

n n n

1kHz 60,000

20kHz 6A/10A 60,000

20kHz 60mA/600mA/6A /10A


n

100 kHz 600A...10A


n

60,000

60,000

Ma

Germ a
ny

GOSSEN METRAWATT

12

HANDhELD DIGITAL MULTImETERS: S Series Special Devices

Table of Contents

METRAHITIOUTDOOR
Article: M2400 The OUTDOOR multimeter has been specially designed and manufactured to meet the challenges faced by engineers and technicians in adverse environments. Its extremely rugged, impact-resistant, water-proof and dust-proof, and is resistant to extreme temperatures. Technology and scope of functions are the same as with the MetraHITIXtra
nS  pecial rugged design with shock and impact nA  dditional rubber holster nS  pecial sand color nD  ust-proof /water jets per IP 65 nP  atented, sealed blocking sockets nP  lus additional functions as included with the MEtRaHITIXtra

resistant housing

Scope of delivery: nK  S17-2 measurement cable set nR  ubber holster n Two 1.5V AA batteries n DAkkS calibration certicate

TRMS TRMS TRMS 600 V 1000 V DATA


AC
AC+DC 20 kHz

CAT IV

CAT III

Min-Max AUTO/MAN

DATA LOGGER

IR

IP 65 MHz

12,000

Counts
AC, DC, AC+DC

Bar Graph

ABS FIL
1 kHz 1 M

RANGE TC/ RTD


40 M

AC, DC, AC+DC

LoV

METRAHITI30M

Article: M230B

6 Digit Precision TRMS Multimeter, Temperature Measuring Instrument and Data Logger for Demanding, Universal Applications in the Lab and for Service Calls
nD  isplay: 1,200,000 counts nI ntrinsic error: (35ppm

nP  TC fuse, max. 250V nI ntegrated 128kB measurement

data memory, sampling interval: 0.1 s to 10min. n Mains power pack (optional) nC  AT II at 600V per IEC 61010-1 Scope of delivery: KS17-2 measurement cable set n nR  ubber holster n Two 1.5V AA batteries n DAkkS calibration certicate

of the measured value +70ppm) nR  esistance and temperature measurement with 4-wire Kelvin connection nM  in-Max measured value storage nA  utomatic range selection and battery cutoff TRMS TRMS
AC+DC DC, AC+DC

100 kHz D-K1508001-01

DC, AC+DC

12 M

kHz RANGE
AUTO/MAN

TC/ RTD DATA


Min-Max

IR

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

HANDhELD DIGITAL MULTImETERS: S Series Special Devices

13

METRAHITIENERGY
Article: M249A Multimeter with power and energy measurement, e.g. for ascertaining energy consumption in standby mode for consumer electronics, communications and IT devices, as well as household appliances such as refrigerators etc., plus a single-phase mains quality measuring instrument (power quality tool). Scope of delivery:
nK  S29 measurement cable set nR  ubber holster n Two 1.5V AA batteries n DAkkS calibration certicate

TRMS TRMS TRMS 300 V 600 V


AC
AC+DC 100 kHz

CAT IV

CAT III

DATA
Min-Max AUTO/MAN

DATA LOGGER

IR

60,000

0000 0000

Digits 00000
AC, DC, AC+DC

ABS FIL
1kHz 1 M

RANGE TC/ RTD


60 M CLIP

AC, DC, AC+DC

LoV

MHz

dB

RPM

PQ

METRAHITIULTRA
Article: M248A / M248B (Bluetooth) Handheld digital multimeter with TRMS measurement with, amongst other measuring functions: V AC TRMS, V AC+DC TRMS, V DC, A AC TRMS, A AC+DC TRMS, A DC dB, Hz(V), Hz(A), V , C / F (TC/RTD)
nR  esolution of 310,000 digits, triple display,

Scope of delivery:
nK  S17-2 cable set in nR  ubber holster nC  ondensed operating instructions,

NEW our product range

English/German
nC  D ROM with operating instructions in

display illumination can be activated under difficult lighting conditions nM  easurement data memory for up to 300,000 measured values nI nstrument can be remote controlled via Bluetooth interface (device variant M248B only) TRMS TRMS TRMS 300 V 600 V
AC
AC+DC 100 kHz

English and German, as well as other available languages n Two 1.5V AA batteries n DAkkS calibration certicate Freeware App for smartphone or tablet with AndroidTM for the Bluetooth variant DATA
Min-Max

CAT IV

CAT III CLIP

DATA LOGGER

310,000

0000 0000

Digits 00000
AC, DC, AC+DC

ABS FIL
1kHz

RANGE
30 M

AUTO/MAN

AC, DC, AC+DC

TC/ RTD IR

D-K1508001-01

MHz

dB

Ma

in de

Germ a
ny

GOSSEN METRAWATT

14

MULTImETERS Insulation Measuring Instruments

Table of Contents

METRAHITIISo

Article: M246B

4 Digit Multimeter and Insulation Tester for Service Applications for Measuring and Testing Industrial Trucks, Household Appliances and other Applications Resolution: 30,000 Digits 26Multimeter Functions
n1  kHz low-pass lter can be activated for nD  ata logger function with 512kB data memory

measurement of V AC nC  urrent measurement: bandwidth up to 2kHz nV  oltage measurement: bandwidth up to 10kHz n I nsulation resistance measurement with adjustable test voltage (50,100,250, 500 or 1000V) and detection of interference voltage TRMS TRMS 600V
AC
AC+DC

for up to 15,400 measured values Scope of delivery: n KS17-2 measurement cable set n Two 1.5 V AA batteries n DAkkS calibration certicate

CAT III

1000V
CAT II
DATA LOGGER

IR TC/ RTD FIL


1 kHz 3 G

AC, DC, AC+DC

AC, DC, AC+DC

300 k

METRAHITIISo@AERO and AERO Master Test Kit


Article: M246M/M246N/Z246A Special version for avionics services with special low-voltage insulation measurement and data hold function. Avionics service case with special test and measuring accessories for aviation technology, consisting of measurement cables, terminals, adapters and sockets for MIL plug connectors in a waterproof, pressure-tight hard case. Scope of delivery, ISO@AERO (M246M)same as ISO n Additionally includes power pack with broad range input: 90 to 250V, 50/60Hz Scope of delivery, AERO Master Test Kit I (Z246A) n 68 piece set of special measuring and test accessories for avionics Scope of delivery, AERO Master Test Kit II (M246N) n Avionics service case including METRAHIT ISO@AERO

METRAHITIT-Com/T-COM PLUS

Article: M246A /M246S

3 Digit Telecommunications Multimeter for Measurements in Symmetrical Copper Cable Networks System Compatible with Data Memory and IR Interface 22 or 25 Multimeter Functions
n Insulation resistance measurement n Measurement of cable length with adjustable

(T-COM test voltage: 100V, T-COM plus: 10 V/100V) n Detection of interference voltage and polarity reversal n Cable symmetry testing by means of rapid terminal switching: a b E n 200Hz low-pass lter can be activated for measurement of V AC n Analog display, linear or logarithmic for insulation measurement TRMS TRMS 600 V 300 V
AC
AC+DC
AC, DC, AC+DC

cable parameters
nL  ow-resistance measurement (cable loops) RSL

with a test current of 2mA

n T-COM plus: signature measurement

Scope of delivery: n KS21-T measurement cable set n Two 1.5V AA batteries n DAkkS calibration certicate

CAT II

CAT III

DATA LOGGER

IR TC/ RTD FIL


200 Hz 30 M

AC, DC, AC+DC


in de

30 kH

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

HANDhELD DIGITAL/ANALOG MULTImETERS

15

METRAHITI2+

Article: M205A

36/7 Digit Universal TRMS Digital Multimeter with Analog Scale for Use in All Areas of Electrical Engineering TRMS
AC
D-K1508001-01

TRMS 600 V TC
1 kHz

CAT III

DATA
Min-Max

6..000

Counts

Bar Graph

ABS

RANGE

AUTO/MAN

AC, DC

AC, DC

40 M

Scope of delivery: n KS17-ONE measurement cable set n Two 1.5V AA batteries n Rubber holster n DAkkS calibration certicate

METRAHITIWORLD

Article: M206A

36/7 Digit Universal Digital Multimeter with Analog Scale for Use in All Areas of Electrical Engineering, especially at the International Level

TRMS
AC
40 M

Digits

6000

TRMS 600 V 1000 V TC


1 kHz

CAT IV

CAT III

RANGE
AC, DC,

AUTO/MAN

Hz DATA
Bar Graph Min-Max

%
D-K1508001-01

RPM

AC, DC,

IR

Scope of delivery: n KS17-2 measurement cable set n Two 1.5V AA batteries n Rubber holster n DAkkS calibration certicate

ABS

METRAMAXI12 Article: M212A / M212D (set)


Inexpensive Handheld Digital-Analog Multimeter for Use in the Fields of General Electronics and Electrical Engineering
nS  witchable input resistance:

Scope of delivery: n KS17-2 measurement cable set n Two 1.5V AA batteries n Rubber holster METRAMAXI12 Set (article: M212D): n With HC20 case and WZ12A current clamp

10M/400k nC  ase with tilt stand and take-up reel nD  imensions (WxHxD): 92 x 154 x 25mm nW  eight: approx. 0.2 kg with batteries nM  anufacturers guarantee: 3 year material and workmanship

300 V 600 V
CAT III CAT II

DATA
Min-Max

RANGE Digits Hz

AUTO/MAN

4000

Bar Graph

AC, DC

AC, DC

40 M

METRAMAX 12 Set

400 k

LoV

Ma

in de

Germ a
ny

GOSSEN METRAWATT

16

ADDITIONAL MEASURING INSTRUmENTS: Folding Digital/Analog Multimeters

Table of Contents

METRAportI40S

Article: M234D

4 Digit Folding Digital Multimeter for Universal Use in General Electrical and Electronics Applications, as well as for Automotive Service Ideal reading angle adjustment is made possible by the tilt stand, and when suspended from the neck strap both hands are free for performing measurements. The instrument is switched off automatically when folded closed, and the display and the control panel are protected against damage. User-friendly thanks to resettable auto-fuses for the current measuring ranges Scope of delivery: KS17-2 measurement cable set n n Two 1.5V AA batteries Carrying strap n n DAkkS calibration certicate TRMS TRMS TRMS 300 V
AC
AC+DC 20 kHz

CAT II

D-K1508001-01

Min-Max

DATA

30,000

Digits
AC, DC

Bar Graph

RANGE
30 M

AUTO/MAN

AUTO Fuse

CLIP

AC, DC

TC/ RTD

kHz

RPM

METRAportI3A

Article: M113A

Folding analog multimeter for demanding applications with analog display and 46 measuring ranges for universal use in process engineering, electronics and electrical applications, testing, R&D, service and training in accordance with EN 61010-1/DIN VDE 0411, part 1
nF  or measurement of voltage, current,

n9  level measuring ranges n7  current measuring ranges: 10mAto 10A

1to20M nS  cale can be tilted with folding lid which also provides protection during transport Scope of delivery: n KS17-2 measurement cable set n 9V at cell battery per IEC 6LR61 n Carrying strap
Class
Analog

n5  resistance measuring ranges:

resistance and level nW  ith reective scale nH  igh input resistance of 10M for no-load voltage measurement nA  utomatic battery cutoff when instrument is folded closed nO  verload protection in all 250V~ ranges (except 10A range) n9  voltage measuring ranges: 100mVto600V

2.5

500 V
CAT II
20 M

AC, DC

AC, DC

dB

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

HANDhELD ANALOG MULTImETERS

17

METRAmax 2

Article: M102A

METRAmax 3

Article: M103A

METRAmax6
Article: GTM3060000R001 Resistance Measuring Instrument with Analog Display for Use in the Plant, on Service Calls and for Installation Work
nM  easuring method: current measure-

The analog multimeter was developed in cooperation with a renowned German training systems manufacturer and fullls requirements for instruction and vocational education. Its suitable for balancing, and inspection work as well.
nV  oltage measurement: 100mV to 300V nC  urrent measurement: 100mAto 3A nZ  ero point can be set to left or center nO  utstanding overload capacity nA  utomatic battery cutoff nD  imensions (WxHxD):

Analog Multimeter for Training Applications, and for Use in the Electrical Trades. Overload protection with integrated auto-fuse and high performance PTC thermistors.
nV  oltage measurement: 30V to 600V nC  urrent measurement: 300mAto 15A nP  rotective conductor nD  imensions (WxHxD):

ment
nR  ugged, moving-coil mechanism with

100 x 140 x 35mm nW  eight: approx. 0.3kg with batteries Scope of delivery: n Multimeter n One 1.5V AA battery

spring loaded bearings


nI ntegrated buzzer for continuity testing nA  llows for use under adverse operating

conditions
nD  imensions: 100 x 140 x 35mm nW  eight: approx. 0.3kg without battery

100 x 140 x 35mm


nW  eight: approx. 0.3kg with batteries

Scope of delivery: Multimeter n

Scope of delivery: n Multimeter n One 1.5V AA battery

Class
Analog

2.5

600 V
CAT II
300 k

300 V
CAT III
AUTO FUSE

Analog

2=/3~

Class

300 V
CAT II

AC, DC

AC, DC

AC, DC

AC, DC

dB

Class
Analog

1.5

300 k

METRAHITI1A / 2A

Article: M100A / M101A

Compact, Basic Analog Multimeter for Training and Hobby, and for Electrical Applications
nD  imensions (WxHxD): 92 x 126 x 45mm nW  eight: approx. 0.25kg without battery nB  attery: 1.5V, IEC LR 6 (AA) nM  anufacturers guarantee: 1 year material and workmanship

Scope of delivery: n 9V at cell battery per IEC 6LR61


Analog

Class

2.5

500 V
CAT II

dB

AC, DC

AC, DC

1 M

Ma

in de

Germ a
ny

GOSSEN METRAWATT

18

ADDITIONAL MEASURING INSTRUmENTS: Process Calibrator / Multimeters

Table of Contents

METRACALIMC

Article: M245A

Our Top Model


The instrument is equipped with a bidirectional infrared interface for subsequent documentation of test results at a PC, and for the transmission of stored measured values. The measuring, simulation and calibrating functions are very comprehensive and include current (mA), voltage (mV, V), resistance (0 to 2000 ), pulse count and frequency (Hz), as well as temperature measurement and simulation of resistance temperature detectors (Pt100, Pt1000, Ni100, Ni 1000) and thermocouples (J, K, T, L, R, B, S, E, U, N), which can be displayed as desired in C or F. The calibration and measuring functions can be scaled as electrical quantities, or as percentage values of an adjustable measuring span. In this way, error can be elegantly indicated as a percentage at the high contrast LCD without any additional tools.

Calibration and Measurement: Efficient and Time-Saving thanks to Simulation The new, extremely cost-effective METRACAL MC multi-functional process calibrator is distinguished by its ruggedness, easy handling, outstanding functionality, accuracy and PC systems compatibility. The METRACAL MC streamlines measuring, calibration and inspection work for chemical processes, in the lab and in R&D, for the production of electronic measuring transducers and when balancing and calibrating metrology components. The integrated multimeter and calibrator make it possible for measuring technicians to simulate sensor conditions at the inputs of transducers, transmitters and buffer ampliers, and at the same time to accurately measure the electrically isolated signal output, and to save results to memory on-site.

Display illumination and multiple display, e.g. functions and output value or measurement and simulation values etc.
nU  niversal calibrator, simulator and

Separate battery and fuse compartments

Connection for external power pack and continuous, battery-free power supply Scope of delivery: n KS29 measurement cable set n Rubber holster with carrying strap n Two 1.5V AA batteries n DAkkS calibration certicate

nF  requency and pulse run generators:

multimeter for mA/mV ... V/C (Pt100/1000, Ni100/1000, thermocouples: J, L, T, U, K, E, S, R, B, N)/ 30to2000 nD  ual mode simultaneous calibration and measurement (U/I) nT  RMS AC measurement to 1kHz nM  easurement and simulation in absolute terms and as percentages (scaled) nM  emory for measurement results: 2MB TRMS 300 V
AC CAT II

1Hz to 2kHz nR  amp and staircase functions n METRAwin 90-2 calibration software (optional) nT  ransmitter simulator (sink: 0 to 24 mA) nD  AkkS calibration certicate included nR  ugged, EMC compliant design

Digits 00000

60,000

0000 0000

IP 65

IR

AC, DC

AC, DC

mA

30 M

TC/ RTD

Hz

D-K1508001-01

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

ADDITIONAL MEASURING INSTRUmENTS: Calibrator / Diagnostics Unit

19

METRAHITICAL / CAL Pack

Article: M244A / M244B


nI nfrared interface for data exchange and

Multifunctional Calibrator for Process Engineering 18 Calibrator Functions. The newly developed calibrator can be used for generating and simulating a broad range of electronic quantities, and also covers 10 different thermocouples and 4 resistance temperature sensors. Its outstanding accuracy and rugged design make the METRAHIT CAL a high performance tool for use in the workshop and the lab.
nS  imulation function for voltage, resistance

parameters conguration with a PC (optionally available IR-USB adapter and software) nH  andheld, battery powered instrument for use directly on-site with additional mains connection for continuous operation

Scope of delivery: n KS17-2 measurement cable set n Rubber holster with carrying strap n Two 1.5V AA batteries n DAkkS calibration certicate Scope of delivery, METRAHITICAL Pack: n Handheld calibrator with rubber holster n METRAHIT X-TRA with rubber holster n Measurement cable sets and batteries n HC30 hard case n DAkkS calibration certicate

and frequency
nS  ource and sink functions for current, in

particular for process quantities, e.g. 0 to 20 mA nT  emperature simulation for resistance thermometers and thermocouples nS  imple adjustment of values with function keys and entry eld nI nterval functions, ramp functions and procedures. Automated sequences with adjustable time quantities can be generated for all simulation quantities.

www.gossenmetrawatt.

More information at

com

METRAHITI1ASi

Article: M235H
nD  ata transmission and management, as well as

The handy, rugged addressing and diagnostics tool for initial start-up, maintenance and service of ASi systems offers the following functions:
nR  ead-out of slave addresses 0 through 31,

documentation of system parameters with optional software Scope of delivery: n ASi addressing device and tester n Rubber holster with carrying strap n Connector cable set, M12 to jack plug n Z236A addressing cable n Z231G module base with addressing socket n 4 batteries per IEC LR6

and A and B, without scrolling including clear-cut, complete LCD nR  ead-out of slave IO and ID codes (including extended ID codes 1 and 2) nS  tandard addressing mode and extended addressing mode per ASi version 2.1 nP  rogrammable ID code 1 nF  unction test for slaves, including analog slaves with prole 7.2 (7.3 in preparation) nR  ecognition of complete arrays of system components nS  torage, diagnostics and PC gateway functions nC  onnection with jack plugs

Type
METRAHIT 1ASi Module base HC20

Article Number
M235H Z231G Z113A

Ma

in de

Germ a
ny

GOSSEN METRAWATT

20

ADDITIONAL MULTImETERS: Milliohmmeters / Insulation Measuring Instruments Table of Contents

METRAHITI27M

Article: M227A

Milliohmmeter, 4 Digit Multimeter and Data Logger, Temperature Measuring Instrument for On-Site Service and for Laboratory Tasks: General low-resistance measurements  Measurement of low value contact resistances at welding seams and riveted joints  Determination of low value contact resistances on aircraft outer skins (lightning protection and wick test)
nM  illiohmmeter: 3000mto300.00m with1A

measuring current and 30.00mto30.00 with 200mA measuring current, and 1 A pulsed nK  elvin connection (4-wire measurement) nV  oltage measurement: 3V to 600 and 3V to 600 V AC with 30,000 digits nR  esistance measurement: 300to30M nF  requency measurement: 300Hzto3kHz nD  ATA hold memory for up to 1200 measured values nC  ontinuity and diode testing, overload protection

Scope of delivery: nK  S17-S measurement cable set n Rubber holster with carrying strap n Three AA rechargeable NiMH batteries n DAkkS calibration certicate

METRAHITI27I / 27AS

Article: M227B/M227C/M227S

Insulation Resistance Tester, Milliohmmeter, 4 Digit Multimeter and Data Logger. In addition to a milliohmmeter, an insulation tester has been integrated for measurements up into the gigaohm range. Where service and repairs in the eld of aviation technology are involved, the instrument can be used in a broad range of applications.
nI nsulation resistance measurement: 30.00Mto3.000G with selectable test

voltages of 50, 100, 250 and 500V nM  illiohmmeter: 3.000m to 300.00m with 1A measuring current and 30.00mto30.00 with 200mA measuring current nK  elvin connection (4-wire measurement) nV  oltage measurement: 3V to 600 V DC and 3V to 600 V AC with 30,000 digits n Continuity and diode testing n Overload protection nL  CD panel with background illumination Scope of delivery, METRAHIT 27 I (article: M227B): n Metrahit 27 I n KS17-S measurement cable set n Three AA rechargeable NiMH batteries n NA HIT 27 charger n KC4 set of Kelvin clips (2 pieces) n DAkkS calibration certicate
in de

Additionally included in Avionic-Set (Article: M227C) nK  C27 set of Kelvin probes (2 pieces) nH  C30 hard case nU  SB pack (USB cable, CD ROM with drivers, METRA-win 10/METRAHIT software) Additionally included in METRAHIT 27 I Set (article: M227S) nH  C30 hard case nK  S17-2 measurement cable set

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

ADDITIONAL MULTImETERS: Milliohmmeters / Insulation Measuring Instruments

21

METRAHITIH+E CAR Article: M227T


The new METRA HIT H+E CAR (hybrid and e-car) is a measuring instrument for testing the electrical safety of electric and hybrid vehicles, and can be used for, amongst others, the following measurements and tests:

n Protection against direct contact during


charging and discharging n Protection against indirect contact during discharging (battery in the vehicle) and charging of the drive battery Insulation and absence of voltage (insulation n resistance between all electrical components of the high-voltage system and the chassis) n Battery insulation (insulation resistance between the high-voltage battery poles and the metallic chassis) n Voltage at capacitors n Testing of the charge controller n Testing of the electric motor (nominal voltage, power, speed) Scope of delivery: n Rubber holster, orange n Three AA rechargeable NiMH batteries n NA HIT 27 charger n Operating instructions (D/GB/F) n DAkkS calibration certicate

Additionally included in METRAHIT H+E CAR-Set (article: M227U) Hybrid test case kit, orange, n with test probes, measurement cables and Kelvin clips Options: n Hybrid test case kit(Z227U) n ADK automotive diagnostics case (Z227T) See data sheet for included equipment.

Z227U

Z227T

METRAHITI27EX

Article: M227F

4 Digit Milliohmmeter for Potentially Explosive Atmospheres for measuring low-value contact resistance in explosive atmospheres, e.g. at contacts inside aircraft fuel tanks (bonding test), as well as for general low-value resistance measurements inside and outside of potentially explosive atmospheres, for example on aircraft outer skins (lightning protection and wick test)
nM  easuring ranges: 30m, 300m, 3, 30 n Resolution: 10 n DATA hold memory: 1200 measured values nP  roduct type test certicate:

INERIS 05ATEX0040 n Ex designation: Ex II 2 G EEx ia IIA T4 Scope of delivery: n 8 Ex approved rechargeable NiMH batteries n KC27 Kelvin probe (1 piece) n KC4 Kelvin clip (1 piece)

n HC30 hard case n DAkkS calibration certicate n Ex certicate: INERIS 05ATEX00401 n  Special variant for AIRBUS: M227G with AIRBUS logo; ID no. 97F92003500 per AMM

Ma

in de

Germ a
ny

GOSSEN METRAWATT

22

HANDhELD DIGITAL MULTImETERS: Overview

Table of Contents

METRAHIT

BASE

EBASE

PRO

ESPECIAL

TECH

ETECH

DC voltage measurement Intrinsic error for V DC AC voltage measurement Intrinsic error for V AC TRMS V DC current measurement Intrinsic error, DC AC current measurement Intrinsic error, AC TRMS A Resistance measurement Intrinsic error, resistance 4-wire milliohm measurement Power and energy measurement Mains quality Capacitance measurement Intrinsic error, capacitance Temperature measurement, Pt100/1000 Thermocouple (type) Continuity testing Diode test Frequency measurement Level measurement (dB) DATA / Min-Max storage Data storage (measured values) Analog display, 35/36 scale graduations Digital display (digits/digits) Display illumination Measurements per second Bandwidth, V AC / V DC Interface Automatic blocking sockets Measuring category Calibration certicate Weight with batteries Batteries / operating hours Dimensions in mm (W x H x D) Protection Approvals and certicates Accessories / included Software option Article number
in de

10mV...1000 V 0.05% rdg.+3d 10mV...1000V 0.5% rdg.+9d AC, AC+DC With clamp With clamp AC, AC+DC 0.01W...40MW -250...+1372(K) n 5.1 V 0.01 Hz...100kHz n n 4=12,000 d n 40 analog/10 digital 1kHz n CAT III/1000V CAT IV/600V DAkkS 395g 2 ea. 1.5V / 200 89 x 199 x 43 IP 52 CE, VDE-GS Cable set M241A CE CS, HC20, RH METRAwin10 M251A IR 10kHz
6 7

10mV...1000V 0.05% rdg. + 3d 10mV...1000V 0.5% rdg. + 9d AC, AC+DC 0.1mAto10A 0.9% rdg. + 5d 0.1mAto10A 1.5% rdg.+30d AC, AC+DC 0.01W...40MW -250...+1372(K) n 5.1V 0.01Hz...100kHz n n n 4=12,000d n 40 analog/10 digital 20kHz IR n CAT III/1000V CAT IV/600V DAkkS 395g 2 ea. 1.5V / 200 89 x 199 x 43 IP 52 CE, VDE-GS Cable set M242A CE CS, HC20, RH METRAwin10 M252A CAT II/600V
6 7

10mV...1000V 0.05% rdg.+3d 10mV...1000V 0.5% rdg.+9d AC, AC+DC 1mA...10A 0.5% rdg.+5d 1mA...10A (16A) 1.5% rdg.+30d AC, AC+DC 0.01W...40MW 10pF ... 1000F n 5.1V 0.01Hz...100kHz 0.01 Hz...300kHz n n n 4=12,000d n 40 analog/10 digital 10kHz n CAT III/1000V CAT IV/600V DAkkS 395g 2 ea. 1.5V / 200 89 x 199 x 43 IP 52 CE, VDE-GS Cable set M243A CE CS, HC20, RH METRAwin10 M253A 20kHz IR
6 7

0.01W...60MW

0.01W...60MW

0.01W...60MW

0.2% rdg.+5d

0.2% rdg.+5d

0.2% rdg.+5d

10pF ... 600F -200 ... +850

1% rdg.+6d -250...+1372(K)

0.01 Hz...300kHz n

0.01 Hz...300kHz n

n 4 / =60,000d

4 / =60,000d

4 / =60,000d

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

HANDhELD DIGITAL MULTImETERS: Overview

23

X-TRA

EXTRA

30M

ENERGY

ULTRA

OUTDOOR

SECULIFE

METRAHIT

10mV...1000V 0.05% rdg.+3d 10mV...1000V 0.5% rdg.+9d AC, AC+DC 10nA...10A 0.5% rdg.+5d 10nA...10A 1.5% rdg.+30d AC, AC+DC 0.01W...40MW 0.01W...60MW 0.2% rdg.+5d 10pF ... 1000F 10pF ... 600 F 1% rdg.+6d -200to+850 -250...+1372(K) n 5.1V 0.001Hz...1MHz n 540kB (15400) 2048kB (61600) n 4=12,000d n 40 analog/10 digital 20kHz IR n CAT III/1000V CAT IV/600V DAkkS 395 g 2 ea. 1.5V / 200 89 x 199 x 43 IP 52 CE, VDE-GS Cable set, RH METRAwin10 M240A M250A CE CS, HC20, RH 100 kHz n 46/7=60,000d n

0.1mV...600V 1mV...600V 0.08% rdg.+5d AC+DC 100pA...120mA 0.02% rdg.+5d 1nA...120mA 0.1% rdg.+5d AC+DC 0.1mW...12MW 0.005% rdg.+5d 0.1mW...30W n 5.1V 0.01Hz...100kHz n 30,000 n 6=1,200,000d n 1 digital 10kHz IR CAT II/600V DAkkS 350g 2 ea. 1.5V / 200 84 x 195 x 35 IP 42 CE Cable set, RH METRAwin10 M230B

1mV...600V 10mV...600V 0.2% rdg.+30d AC, AC+DC 10nA...10A 0.05% rdg.+20d 10nA...10A 0.5% rdg.+25d AC, AC+DC 10mW...60MW 0.1% rdg.+5d n n 10pF ... 600F 1% rdg.+6d -200to+850 n 6.0V 0.01Hz...1MHz n n 300,000 Triple digital 60,000d n 10 digital 100kHz IR n CAT III/600V CAT IV/300V DAkkS 400g 2 ea. 1.5V / 200 89 x 199 x 43 IP 52 CE Cable set, RH METRAwin10 M249A

1mV...600V 10mV...600V 0.2% rdg.+30d AC, AC+DC 1nA...10(16)A 0.02% rdg.+5 10nA...10(16)A 0.5% rdg.+30d AC, AC+DC 1mW...30MW 0.05% rdg.+8d 1 pF ... 3 mF 1% rdg.+6d -200to+850 n 4.5V 0.001Hz...1MHz n n 300,000 Triple digital 310,000 d n 10 digital 100kHz IR/Bluetooth n CAT III/600V CAT IV/300V DAkkS 400g 2 ea. 1.5V / 200 89 x 199 x 43 IP 52 CE Cable set, RH METRAwin10 M248A/B

10mV...1000V 0.05% rdg.+3d 10mV...1000V 0.5% rdg.+9d AC, AC+DC 10nA...10A 0.5% rdg.+8d 10nA...10A 1.5% rdg.+30d AC, AC+DC 0.01W...40MW 0.2% rdg.+5d 10pF ... 1000F 1% rdg.+6d -200to+850 -250...+1372(K) n 5.1V 0.001Hz...1MHz n 540kB (15400) n 4=12,000d n 40 analog/10 digital 20kHz IR n CAT III/1000V CAT IV/600V DAkkS 395 g 2 ea. 1.5V / 200 89 x 199 x 43 IP 65 / IP 52 CE Cable set, RH CS, HC20, RH METRAwin10 M240O M687A

DC voltage measurement Intrinsic error for V DC AC voltage measurement Intrinsic error for V AC TRMS V DC current measurement Intrinsic error, DC AC current measurement Intrinsic error, AC TRMS A Resistance measurement Intrinsic error, resistance 4-wire milliohm measurement
Power and energy measurement

0.003% rdg.+3d 0.02% rdg.+15d 0.02% rdg.+20d

Power quality Capacitance measurement Intrinsic error, capacitance


Temp. measurement, Pt100/1000

-270to+1372(J,K) -260to+1372(J,K) -270to+1372C (K)

Thermocouple (type) Continuity testing Diode test Frequency measurement Level measurement (dB) DATA / Min-Max storage
Data storage (measured values)

Analog display, 35/36 scale graduations Digital display (digits/digits) Display illumination Measurements per second Bandwidth, V AC / V DC Interface Automatic blocking sockets Measuring category Calibration certicate Weight with batteries Batteries / operating hours Dimensions in mm (W x H x D) Protection Approvals and certicates Accessories / included Software option Article number
in de

Ma

Germ a
ny

GOSSEN METRAWATT

24

HANDhELD DIGITAL MULTImETERS: Overview

Table of Contents

METRAHIT

2plus

WORLD

METRAmax12

METRAport 40S

DC voltage measurement Intrinsic error for V DC AC voltage measurement Intrinsic error for V AC TRMS V DC current measurement Intrinsic error, DC AC current measurement Intrinsic error, AC TRMS A Resistance measurement Intrinsic error, resistance 4-wire milliohm measurement Power and energy measurement Power quality Capacitance measurement Intrinsic error, capacitance Temp. measurement, Pt100/1000 Thermocouple (type) Continuity testing Diode test Frequency measurement Level measurement (dB) DATA / Min-Max storage Data storage (measured values) Analog display, 35/36 scale graduations Digital display (digits/counts) Illuminated display Measurements per second Bandwidth Interface Automatic blocking sockets Measuring category Calibration certicate Weight with batteries in g Batteries / operating hours Dimensions in mm (W x H x D) Protection Approvals and certicates Accessories / included Software option Article number
in de

100mV...600V 0.5% rdg. +3d 100mVto600V 1% rdg.+3d AC 10mA...10(16) A 1% rdg.+5d 10mA...10(16) A 1.5% rdg.+2d AC 0.1W...40MW 0.7% rdg.+3d -50...+400(K) n 2V 0.1 ... 1kHz n n 3 /7=6000d
6

100mV...1000V 0.5% rdg.+3d 100mV...1000V 1% rdg.+3d AC 10mA...10(16) A 1% rdg.+5d 10mA...10(16) A 1.5% rdg.+2d AC 0.1W...40MW 0.7% rdg.+3d 10pF...400mF 1% rdg.+6d -50...800(K) n 2V 0.1Hz...1kHz n n 3 /7=6000d
6

100mV...600V 0.5% rdg. +2d 100mV...600V 1% rdg. +5d 10mA...10A 0.8% rdg.+2d 10mA...10A 1.0% rdg.+5d 0.1W...40MW 0.8% rdg.+2d 1.0pF...40mF 3% rdg.+40d n 3V 0.01Hz...400kHz n n 3=4000d n 20 analog/2 digital 500Hz CAT III/300 V CAT II/600V 200g 2ea.1.5V/600 92 x 154 x 25 IP 52 CE Cable set M212A

10mV...600V 0.2% rdg. +3d 10mV...600V 0.5% rdg. +30d AC 10nA...10A 0.5% rdg.+5d 10nA...10A 1.0% rdg.+30d AC 10...30M 0.2% rdg.+5d 10pF...300mF 1% rdg.+6d -200...+850 -250...+1372(K) n 5.1V 0.01Hz...1MHz n n 4=30,000d n 20 analog/2 digital 10kHz USB CAT II/300 V DAkkS 450g 2ea.1.5V/200 146 x 118 x 44 IP 42 CE Cable set METRAwin10 M234D

n 20 analog/2 digital 1kHz n CAT III/600 V DAkkS 350g 2ea.1.5V/up to 750 84 x 195 x 35 IP 40 CE Cable set, RH M205A

n 20 analog/2 digital 1kHz IR n CAT IV/600 V CAT III/1000V DAkkS 350g 2ea.1.5V/up to 750 84 x 195 x 35 IP 40 CE Cable set, RH METRAwin10 M206A

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

HANDhELD DIGITAL MULTImETERS: Overview

25

T-COM

T-COM plus

ISO

ISO Aero

27M

27I(AS)

27H+E CAR

METRAHIT

100mV...600V 0.5% rdg.+1d 100mV...600V 1.5% rdg.+3d AC, AC+DC 100mA...1A 0.5% rdg.+5d 100mA...1A 1.5% rdg.+5d AC, AC+DC 100mW...30MW 0.5% rdg.+1d 5kW...300MW 5kW...300MW 100V 10V/100V 30nF...300mF 1% rdg.+6d -200...+850 -250...+1372(K) n 13V 300Hz...300kHz n n 540kB (15,400) n 3=3100d n 40 analog/10 digital 10kHz IR n CAT II/600V CAT III/300V DAkkS 420g 2 ea. 1.5V / 200 89 x 199 x 43 IP 54 CE Cable set, pouch, RH METRAwin10 M246A M246S

300mVto600V 0.5% rdg.+1d 300mV...600V 1.5% rdg.+3d AC, AC+DC 300mA...1A 0.5% rdg.+5d 300mA...1A 1.5% rdg.+5d AC, AC+DC 300W...30MW 0.5% rdg.+1d 5kW...3GW 50V ... 1000V 5kW...3GW 10V ... 500V

100mV...600V 0.1% rdg.+5d 100mV...600V 0.2% rdg.+10d With clamp 10mW...30MW 0.1% rdg.+5d 0.001mW...30W 10kW...3GW 50V ... 500V -200...600 n 3V 0.01Hz...3kHz n 32kB (1000) 4=31,000d n 10 analog/2 digital 1kHz IR CAT II/600V DAkkS 420g 3 ea. 1.5V / 20 84 x 195 x 35 IP 54 CE Cable set, RH METRAwin10 M227A Cable set, RH (case) METRAwin10 M227B /C/S M227T/U

DC voltage measurement Intrinsic error for V DC AC voltage measurement Intrinsic error for V AC TRMS V DC current measurement Intrinsic error, DC AC current measurement Intrinsic error, AC TRMS A Resistance measurement Intrinsic error, resistance 4-wire milliohm measurement Insulation measurement / measuring voltage Capacitance measurement Intrinsic error, capacitance
Temp. measurement, Pt100/1000

30nF...300mF 1% rdg.+6d -200...+850 -250...+1372(K) n 13V 0.1Hz...300kHz n 540kB (15,400) n 4=30,000d n 40 analog/10 digital 10kHz IR n CAT II/1000V CAT III/600V DAkkS 420g 2 ea. 1.5V / 200 89 x 199 x 43 IP 54 CE Cable set, pouch, RH METRAwin10 M246B M246M

Thermocouple (type) Continuity testing Diode test Frequency measurement Level measurement DATA / Min-Max storage Data storage (measured values) Analog display, 35/36 scale graduations Digital display (digits/counts) Display illumination Measurements per second Bandwidth Interface Automatic blocking sockets Measuring category Calibration certicate Weight with batteries Batteries / operating hours Dimensions in mm (W x H x D) Protection Approvals and certicates Accessories / included Software option Article number
in de

Ma

Germ a
ny

GOSSEN METRAWATT

26

MULTImETER ACCESSORIES: Adapters / Charger

Table of Contents

Shunts

Article: see description


nN  W300mA (Z205C): 300mA1 nN  W3A (Z205B): 3A 0.1

Shunt Resistors for Multimeters Without Current Measuring Function The shunt resistors serve as adapters for multimeters without their own current measuring function, or are used to extend the current range (NW10A).

class 0.5 1mV/mA

class 0.5 600VCAT IV100mV/A

PMA16

Article: Z228A

SM16

Article: GTM9070190E0002

USB-HIT

Z216A/Pack: Z216B

PMA16 Power Measuring Adapter The power measuring adapter is an intermediate plug for the measurement of power consumption at single-phase consumers with an additional cable for connection to the multimeters voltage path.

SM16 Current Measuring Adapter For safe, trouble-free measurement of current consumption via the mains plug of connected power consumers. The cable with contact-protected connectors is connected directly to the current measurement sockets at the multimeter.

IR RS 232 Bidirectional Snap-On Interface Adapter Data are transmitted from the multimeter to the adapter in an electrically isolated, bidirectional fashion, and to the USB interface for PCs and laptops. nU  SB-Pack: including METRAwin10/METRAHit software.

In

cl. Softwar

BD232

Article: GTZ3242100R0001 /BD

Pack 1

Article: Z215A

IR RS 232 Snap-On Interface Adapter The infrared interface allows for electrically isolated data transmission between PC and multimeter. Data transmission is indicated visually by means of two LEDs. The BD232 interface adapter is above all recommended for multimeters with integrated memory. It can also be used for online data transmission with multimeters which do not have integrated memory. The BD-Pack is available as a complete package for

single-channel operation. In order to expand to 2, 3 or 4-channel operation, an additional BD232 is required for each channel, as well as the additionally required multimeters.
n BD Pack 1: including METRAwin10/ METRAHit software, RS 232 interface cable Z3241 and installation instructions

In

cl. Softwar

USBIXTRA

Article: Z216C

Z206D
Article: Z206D Quick Charger for NiMH / NiCd Batteries (AA, AAA)
ncl
. Driver

Bidirectional Infrared-USB Interface Adapter for Starline Multimeters with Serial IR Interface for Connection to a USB Port at a PC Adapter for data transmission between the multimeter and the PC.

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

MULTImETER ACCESSORIES: Power Packs

27

NA X-TRA

Article: Z218G

NA Hit 2x

Article: Z218H

Mains Power Pack: 90 ... 250 V AC / 5 V DC Power pack for battery-saving mains operation, for continuous measurement using multimeters with internal memory
nB  road range input: 50 / 60Hz nM  easuring category: CAT IV at 600V

Mains Power Pack: 90 ... 250 V AC / 5 V DC The power pack allows for battery-saving mains operation, in particular for continuous measurement with internal memory.
nM  odied plug connectors

for below mentioned instruments manufactured as of 2004 nB  road range input: 50 / 60Hz measuring category: CAT IV at 600V

Overview

Multimeter Accessories

com www.gossenmetrawatt.
METRAHIT METRAmax METRAport

More information at:

PRO/ESPECIAL

ISO/ISO@Aero

X-TRA/EXTRA

TECH/ETECH

SECULIFE HIT

BASE/EBASE

T-COM/plus

OUTDOOR

27H+E CAR

Type

METRACAL MC

23/24/25S

ONEPlus

ENERGY

WORLD

32S/XS

16I/T/U

22S/M

26S/M

ULTRA

2 plus

1A/2A

27M/I

30M

29S

40S n n n n
Ma

CAL

Shunts NW300mA NW3A NW10A Adapter USB X-TRA BD232 BD-Pack1 USB-Hit USB-Pack SM16 PMA16 EMA1 n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

n n

n n n n n n n n n n n

n n n n

n n n

n n

n n n

Power Packs / Chargers NA HIT 2x NA HIT 27 NA X-TRA Z206D


1

n n n

n n n n
in de

n n n n

n n n n n

n n

n n

n n

n n

n n

n n n n n n n n n n n n

For dates of manufacture through 2004 only

3A
Germ a
ny

GOSSEN METRAWATT

12

28

MULTImETER ACCESSORIES: Current Sensors

Table of Contents

AC/DC Current Sensor

Article: see table Advantages: nE  lectrical circuits need not be interrupted no electrical connection to the conductor nM  easurement of current up to 2000A no multimeter overloading as a result of current surges

AC-DC Current Sensors with Voltage Output, mV / A Current within conductors can be conveniently and safely measured with current clamp sensors and multimeters. Scope of delivery:
nC  urrent sensor with connector cable n9  V at cell battery

Type Z13B

Article

Measuring Measuring Conductor Dia. Range DC, ~AC Category 0.5...60/600A CAT IV/300V 50 Z213B 0.2...40/400A~

Trans. Ratio mV/A 10 / 1

Uncertainty Frequency Range Intrinsic (% rdg. + A) DC...65Hz/...10kHz CP30


CP330

1.5%/2%
CP1100

AC/DC Current Sensors

Article: see table


nA  C and DC current measurement

The CP30, CP330 and CP1100 current clamp sensors have been developed for precise contactless measurement of alternating and direct current. Theyre well suited for precision current measurement thanks to the use of the latest Hall effect technology.

for TRMS multimeters


nH  ighly accurate: 1% nA  utomatic shutdown for extended

battery service life


nT  ransformation ratios can be set directly

at many METRAHIT multimeters.


nE  asy zero balancing by simply pressing

a key
nM  easuring category: CAT III/ 300V

Type CP30

Article

Measuring Range, AC

Resolution 1mA 50mA / 100mA 100mA / 500mA

Conductor Dia., mm

Overcurrent Frequency Capacity Range (DC) 500A (60 s) 600A (60 s) Up to 20kHz (-1dB) Up to 20kHz (-3dB)

Intrinsic Gain Drift /C Trans. Ratio Uncertainty mV/A (% rdg.+A) 1% + 2mA 1%+50/100mA 1%+100/500mA 0.01 0.1 0.1 100 10/1 10/1

Z201B 0...30A

25 25 32

CP330 Z202B 0...450A CP1100 Z203B 0...1400A

to 20kHz 2000A (60 s) Up (-1dB)

Flexible Current Sensors

Article: see table

Flexible current sensors with voltage output for measuring alternating current at difficult to access places; highly insulated and with range selector switch (selectable transformation ratio). Maximum phase error is 2.5 at a frequency of up to 1 kHz. Scope of delivery, METRAFLEX: n Two 1.5V AA batteries Type Article Measuring Range DC, AC 30/300/3000A 3/30/300A Measuring Category CAT III/1000V CAT IV/600V CAT III/1000V CAT IV/600V

METRAFLEX 300M
METRAFLEX 3000

Loop Trans. Ratio Circumf., mm mV/A

Frequency Range 10Hz...10kHz

Intrinsic Uncertainty (%rdg.+mA) 1%100 1%200

METRAFLEX Z207E 3000 METRAFLEX Z207M 300M

610 160

100/10/1

1000/100/10 20Hz...100kHz

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

MULTImETER ACCESSORIES: Current Clamp Sensors

29

AC Current Sensors

Article: see description

AC Current Sensors with Voltage Output, mV / A Current within conductors can be conveniently and safely measured with current clamp sensors and multimeters. Scope of delivery: nC  urrent sensor with connector cable Advantages:
nE  lectrical circuits need not be interrupted

WZ11B
Z3512A

No electrical connection to the conductor


nM  easurement of current up to 2000 A

no multimeter overloading as a result of current surges

WZ12C Type WZ12B WZ12C WZ11B Z3512A Article Z219B Z219C Z208B Z225A Measuring Range, AC Measuring Cable Category Dia. mm 15 15 20 52 Trans. Ratio mV/A 100 1000/1 100/10 1000/100/10/1 Frequency Range 45...65...500Hz 45...65...500Hz Intrinsic Uncertainty (% rdg. + A) 1.5%+0.1m 3%+0.15 m/2%+0.1

0.01 ... 100A CAT III/300V 0.001...15A / CAT III/300V 1...150 A 0.5...20A / CAT III/600V 5...20A 0 ... 1000A CAT III/600V

30...48...65/...500Hz 1 ... 3% 10...48...65Hz/...3kHz 0.2%...0.7%

Overview

Multimeter Accessories
METRAHIT PRO/ESPECIAL ISO/ISO@Aero TECH/ETECH 27H+E CAR METRAmax METRAport

23/24/25S

OUTDOOR

ONEPlus

Type

METRACAL MC

BASE /EBASE

X-TRA/EXTRA

SECULIFE HIT

T-COM/plus

ENERGY

WORLD

32S/XS n n n n n

16I/T/U

22S/M

26S/M

ULTRA

2 plus

1A/2A

27M/I

30M

29S

40S n n n n n n
Ma

CAL

Current Sensors CP30 CP330 CP1100 Z13B WZ11B WZ12B WZ12C Z3512A n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

n n n n n n n n

Flexible Current Sensors METRAFLEX 3000 METRAFLEX 300M n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n


in de

3A
Germ a
ny

GOSSEN METRAWATT

12

30

MULTImETER ACCESSORIES: Current Transformers / Probes

Table of Contents

AC Current Transformers

Article: see table

Z3512

Z3514

AC Current Transformers with Current Output, mV / A Scope of delivery:


nC  urrent sensor with connector cable

Advantages:
nE  lectrical circuits need not be interrupted

no electrical connection to the conductor


nM  easurement of current up to 2000A

no multimeter overloading as a result of current surges Type WZ12A WZ12D WZ11A Z3511 Z3512 Z3514 Article Z219A Z219D Z208A Measuring Range, AC 15 ... 180A 0.03 ... 150A 1 ... 200A Measuring Category CAT III/300V CAT III/300V CAT III/600V CAT III/600V CAT III/600V Conductor Dia. mm 15mm 15mm 20mm 30 x 63mm 52mm
Trans. Ratio mA/A

WZ12A/D

Frequency Range 45...65...400Hz 45...65...500Hz 48...65...400Hz 45... 65 Hz...1kHz 3045...65Hz...5kHz 30...45...65 Hz...5kHz

Intrinsic Uncertainty 3% rdg. (2.5% rdg. +0.1mA) 1 ... 3% rdg. (3% rdg. +0.4A) 0.5 ... 0.7% rdg. 0.5% rdg.

1 1 1 1 1 1

GTZ3511000 4 ... 500A R0001 GTZ3512000 0.5 ... 1000A R0001 GTZ3514000 1 ... 2000A R0001

CAT III/600V 64 x 150mm

Temperature Probes

Article: see table Scope of delivery: nZ  3431-3: temperature probe with a permanently mounted, standard immersion sensor nZ  3431-4 and Z3431-9: temperature probe without plug-in sensor
Intrinsic Uncertainty

AC Current Transformers with Current Output, mV/A Suitable for temperature measurement from -25to+1150 C. The measurement output is connected to the mV/V measurement input at the multimeter. Type Article
Measuring Range

Sensor Type NiCr-NiAl, type K thermocouple NiCr-NiAl, type K thermocouple NiCr-NiAl, type K thermocouple NiCr-NiAl, type K thermocouple NiCr-NiAl, type K thermocouple NiCr-NiAl, type K thermocouple NiCr-NiAl, type K thermocouple

Output Operating Output V Multimeter Temperature

Power Supply

-20 C... Z3431-3 GTZ3431003 R0001 +350 C -25 C... Z3431-4 GTZ3431004 R0001 +1150 C -20 C... Z3431-9 GTZ3431009 R0001 +350 C Z3431-5 GTZ3431005 ... +1100 C R0001 Z3431-6 GTZ3431006 ... +850 C R0001 Z3431-7 GTZ3431007 ... +450 C R0001 Z3431-8 GTZ3431008 ... +250 C R0001
in de

(0.5% baby cell, 250 >10k 1 mV/C 5 C...45 C 1.5V rdg.+0.5 C) hrs. Service life (1% baby cell, 250 >10k 1 mV/C 5 C...45 C 1.5V rdg.+1 C) hrs. Service life (0.5% baby cell, 250 >10k 1 mV/C 5 C...45 C 1.5V rdg.+0.5 C) hrs. Service life Standard immersion sensor, can be plugged into temperature probes Z343-4 and Z343-9 Surface sensor, can be plugged into temperature probes Z343-4 and Z343-9 High temperature sensor tape, can be plugged into temperature probes Z343-4 and Z343-9 Flexible, insulated sensor, can be plugged into temperature probes Z343-4 and Z343-9

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

MULTImETER ACCESSORIES: Temperature Sensors

31

Temperature Sensors
Scope of delivery:

Article: see table

TF400CAR

Z3409

nT  F400CAR: PT1000 temperature sensor for oil

nZ  3409: PT 100 temperature sensor for surface

temperature measurement and immersion measurements nT  F400SURFACE: fast reacting surface temperanT  F220:PT1000 immersion sensor for measureture sensor, type K thermocouple ments in gases and liquids nT  S-Chipset: PT100 miniature temperature nT  F550: PT100 immersion sensor for measuresensor (10 pieces, adhesive) for spot measurements in ovens and freezers ments at small measuring points Intrinsic Transient Accuracy Error K at 0 Recovery, T90 Water/Air C/...C GTZ3409000 130/1000 -40...+600 Class A 0.15/ Z3409 Pt100 5s/30s R0001 mm 600:1.35 39/1500 -50 ...+ 220 Class B 0.3/ TF220 Z102A Pt1000 8s/33s mm 220:1.4 GTZ3408000 Pt100 40/1500 -50 ...+ 550 Class B 0.3/ TF550 8s/33s R0001 mm 550:3.1 TF400 Z102C Pt1000 810/2310 -50 ...+ 500 Class B / / CAR mm TF400 K 280/130 -50 ...+ 400 / 2s SURFACE Z102E (NiCr-Ni) mm 2.3/10 -50 ...+ 550 Class B 0.4/ TSGTZ3406000 Pt100 0.3 s/15s mm 550: 3.1 Chipset R0001 Type Article Length of Sensor Element / Element Sensor Temp. Range

TF220/TF550

Lead in mm Strand, 2 ea. 0.35 Strand, 2 ea. 0.35 Strand, 2 ea. 0.35 Strand, 2 ea. 0.35 Strand, 2 ea. 0.35 0.25 dia./NiPt

Outer Jacket / Insulation PVC/PVC Teon / Teon V4A / glass PVC/PVC PVC/PVC /

Overview

Multimeter Accessories
METRAHIT PRO/ESPECIAL ISO/ISO@Aero METRACAL MC SECULIFE HIT BASE/EBASE T-COM/plus X-TRA/EXTRA/ETECH

www.gossenmetrawatt.

More information at:

com
METRAmax METRAport

23/24/25S

OUTDOOR

ONEPlus

ENERGY

WORLD

Type

27H+E CAR

TECH/

32S/XS n n n n

16I/T/U

22S/M

26S/M

ULTRA

2 plus

1A/2A

27M/I

30M

29S

40S n n n n n n n n n n n n
in de

CAL

Current Transformers WZ11A WZ12A WZ12D Z3511 Z3512 n Z3514

n n n n n n

n n n n n n

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

n n n n

n n n n

n n n n n n n n n n n n n n n n n n n n n

n n n n

n n n n

Temperature Sensors and Probes TF400CAR TF400SURF. TF220 TF550 TS Chipset Z3409 Z3431-3 Z3431-4 Z3431-9 n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

Ma

Germ a
ny

GOSSEN METRAWATT

3A n n n n n n

12

32

MULTImETER ACCESSORIES: Probe /Cable Sets

Table of Contents

High Frequency Probe

Article: GTZ3431002R0001 within a frequency range of 100 kHz to 750 MHz. The probe recties alternating voltages at a ratio of 1:1. The measuring instrument must have an input impedance of 10 M.

Z3431-2 High Frequency Probe: 100 kHzto750 MHz, 0.25to 50 VAC. In combination with a multimeter, the Z3431-2 high frequency probe allows for measurement of alternating voltages with an amplitude of 0.25 V to 50 V

Cable Sets

Article: see table

Cable Sets with Permanently Mounted Test Probes and Contact-Protected Angle Plugs for Safe Measuring Hook clips, alligator clips or push-on lugs can be attached to the test probes for special measuring tasks.
nK  S17-ONE cable set (Z110K):

KS17-ONE KS17-2 KS29

600 V/CATIII, 1A, 120cm long 600 V/CATII, 16 A


nK  S17-2 cable set (GTY3620034P0002):

1000 V/CATIII, 1A, 600 V/CATIV, 1A 1000 V/CATII, 16A, 120cm long
nK  S17-S cable set (Z110H):

KS17-S

1000 V/CATII, 120cm long, 2 mm diameter steel tips


nK  S-AP cable set (Z110S):

1000V/CATII, 32A, 1000V/CATIV, 1A, with adjustable test probes, 150 cm long, 4 mm angle plug
nK  S-NTS cable set (Z110W):

1000V/CAT II/III, 20A, double insulated silicon measurement cables, 120 cm long, with one pair each small test probes, alligator clips, clip hooks and North American test probes
nK  S21-T cable set (Z11OU):

(adjustable test probe, CATII/CATIV)

KS-AP

KS-NTS

1000 V/CATII, 16A, 200cm long for cable multimeter


nK  S29 cable set (Z229A):

KS21-T

1000 V/CATIII, 1A, safety cable set for power meters


nK  Y95-3 alligator clip (Z110J):

1000 V/CATIII, 16A,


n2  magnetic test probes

KY95-3

with 4 mm plug (Z502U): 1000 V/CATIII, 4A

Z502U
in de

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

MULTImETER ACCESSORIES: Cable Sets / Fuses

33

Interface Cable RS 232


Article: GTZ3241000R0001 Interface Cable for Connecting the Measuring Instrument / Adapter to a PC 2 meters long, 9-pin subminiature plug/socket connector, 1:1 uncrossed

Kelvin Clips

Article: Z227A

Kelvin Probes

Article: Z227B

Kelvin clips/probes are used for connecting low impedance resistors (e.g.contact resistors, shunts etc.) to an ohmmeter with 4-wire connection. This allows for compensation of cable resistance.
nK  C4: Kelvin clips (1 set = 2 pieces) for 4-pole

nK  C27: Kelvin probes (1 set=2 pieces)

with 2 stainless steel tips for 4-pole connection of low-resistance DUTs, cable length: 120cm

connection of low-resistance DUTs, cable length: 120cm, clip for connection to DUTs with diameters of up to 30mm

KC27

KC4

Overview
Type

Multimeter Accessories
METRAHIT PRO/ESPECIAL ISO/ISO@Aero X-TRA/EXTRA TECH/ETECH SECULIFE HIT BASE/EBASE T-COM/plus METRACAL MC 27H+E CAR 23/24/25S METRAmax METRAport

OUTDOOR

ONEPlus

ENERGY

WORLD

32S/XS n n n n n n n

16I/T/U

22S/M

26S/M

ULTRA

2 plus

1A/2A

27M/I

30M

29S

40S n n n n n n n

CAL

High-Frequency Probe Z3431-2 n Measuring Accessories KS17-ONE n n KS17-2 n n KS17-S n n KS-AP n n KS-NTS KS21-T KS29 n n KY95-3 Z3241 Kelvin Clips KC4 KC27 n n n n n

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

n n n n n n n n

n n n n n n n n

n n n n n n n n

n n n n n n n n

n n n n n n n n

n n n n n n n n n

n n n n n n n n

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

n n n n

n n

Fuses for Multimeters


Type FF (UR) 16 A/1 kV AC/DC FF (UR) 10 A/1kV AC/DC FF (UR) 1.6 A/1kV AC/DC FF 1.6 A/700V AC FF (UR) 16 A/600V AC FF 630 mA/700V FF 6.3 A/400V FF 16 A/600V AC FF 1 A/380V (5 x 20) T 16 A/500V (6.3 x 32) FF 0.63 A/400V Designation Fuse link Fuse link Fuse link Fuse link Fuse link Fuse link Fuse link Fuse link Fuse link Fuse link Fuse link Article Z109B Z109L Z109C Z109E Z109D Z109J Z109K Z109A Z109H Z109I Z109M For following devices: METRAHIT 24S ... 26S METRAHIT PRO, TECH, X-TRA, ETECH, EXTRA, 2, WORLD, ULTRA, 29S METRAHIT 23S ... 26S, 27M/I, 27H+E CAR, 29S METRAHIT ONE Plus/2/WORLD/2A, METRAmax 12, METRAport 3A METRAHIT ONE Plus METRAHIT 1A METRAHIT 1A METRAmax 12, METRAport 3A, METRAHIT 2A METRAport 32S/32XS METRAport 32S/32XS METRACAL MC

Ma

in de

Germ a
ny

GOSSEN METRAWATT

3A n n n n n n n

12

34

MULTImETER ACCESSORIES: Software

Table of Contents

METRAwin 90-2

Article: Z211A (update: Z211E) Calibration procedures are created with METRAwin software. Specied analog values are transmitted via the IR adapter from the PC to the calibrator and are fed to the device to be calibrated from the analog output at the calibrator. The analog output value from the device to be calibrated is then measured by the multimeter, and is returned to the PC for evaluation via the interface. If the measurement results remain within the specied tolerances, each consecutive calibration step is initialized automatically until the entire procedure has been run. Calibration data can be imported into other Windows applications (e.g. WoRd or ExcEl).

Calibration Software for Controlling Process Calibrators The handheld calibrator with multimeter is transformed into a professional, PC-based calibration system for measuring transducers, indicators, recording instruments etc. with the help of METRAwin 90-2 and an interface cable.

METRAwin 90-F

Article: Z211C/-FJ Article: Z211F transmission of measurement results from the METRAHIT multimeter to the computer. In the case of measuring transducers, the analog output value from the device to be calibrated is measured by a multimeter, and is returned to the PC for evaluation via the interface. If the measurement results remain within the specied tolerances, each consecutive calibration step is initialized automatically until the entire procedure has been run. nA  utomated calibration of multimeters with IR interface nA  djustment of the METRAHIT 22-29S/M via IR interface nG  eneration, testing and documentation of calibration procedures
nO  utstanding applications exibility with

A universal, professional, automated closed-loop calibration system for METRAHIT multimeters can be set up with METRAwin 90-F / FJ, an IEEE 488 interface at the PC and a Fluke 5500A, 5520A or 5700A calibrator. Also suitable for universal use for the calibration of analog and digital multimeters, recorders and power meters, power measuring transducers, amplier modules, transducers etc. Calibration procedures are generated with METRAwin 90-F. Specied analog values are transmitted via the IEEE 488 interface from the PC to the calibrator and are fed to the device to be calibrated from the analog output at the calibrator. A BD232 adapter is coupled to the computer via an RS 232 cable for automatic

calibration signal correction by means of key entry or via the interface nD  ocumentation is printed out as a standard calibration report, or as a user-specic certicate nD  ynamic data exchange with Microsoft Excel and Word nD  ocumentation with all entries required for certicates in accordance with ENISO9000 n  Determination of measuring uncertainty in accordance with DKD-3 after a specied number of measurements nS  pecication of calculated measuring uncertainty in accordance with DKD-3 or TUR (test uncertainty ratio) included in the report

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

MULTImETER ACCESSORIES: Software

35

METRAwin 10/METRAHit
Article: GTZ3240000R0001 Parameters Conguring and Analysis Software for METRAHIT Multimeters METRAwin 10/METRAHIT is a measurement data logging program for recording, visualizing, evaluating and documenting measured values from METRAHIT multimeters with reference to time. METRAwin 10/METRAHit supports the following multimeters (see complete list below): n METRAHIT Starline series (X-TRA, E and S series) in combination with USB-X-TRA interface adapter (max. 6 channels, max. 1 measurement/s, memory: 10 measurement/s). n METRAHIT 30M in combination with USB-Hit interface adapter (single-channel only, max. 10 measurements/s) or BD232 (max. 4 channels). n METRAHIT 22S-29S/M/C/I in combination with USB-Hit (singlechannel only, max. 20 measurements/s) or BD232 interface adapter, or SI232-II or SI232 memory adapter (max. 6 channels, max. 20 measurements/s). n METRAHIT 12S-18S/I/T/U/ONE Plus in combination with RS232 interface adapter (single-channel only) or SI232-II or SI232 memory adapter (max. 6 channels, max. 20 measurements/s). German, English, French, Spanish, Italian or Slovak can be selected as the user interface language. The software runs under Windows XP, Vista and 7 (branch office license). A test version can be downloaded from our website Depending upon device type, one or several of the following operating modes are possible:
nD  evice conguration n Online recording of measurement data n Read-in and display of offline data

recorded to device memory

Measurement data can be displayed and analyzed in various formats:


n Analog/digital instrument (online) n Yt diagram

Analog/Digital Instrument

max. 4 channels, with limit monitor

max. 6 channels, scroll and zoom function, absolute/relative time axis, automatic/manual Y scale, 2 cursors n XY diagram max. 4 channels. automatic/manual Y scale, 2 cursors n Data logger table max. 12 channels, data export to ASCII le or via the clipboard to other Windows programs e.g. MS Excel Amongst other possibilities, a continuous line recorder printing option is available for documenting measurements. Up to 10 channels can be printed out continuously as a Yt line graph at a color printer with this function.
n Math functions

Yt Diagram

XY Diagram

Measurement data from different channels can be linked and processed with high performance arithmetic functions.
Data Logger Table

Overview

Software
ISO/ISO@Aero

com www.gossenmetrawatt.
MULTIMETER METRAHIT 12-18 S/I/T/U METRAport 27H+E CAR 23/24/25S Calibrator METRACAL MC 28C/28C Light n SECULIFE HIT

More information at:

X-TRA/EXTRA

OUTDOOR

ESPECIAL

ONEPlus

ENERGY

Type ETECH EBASE

T-COM/plus

WORLD

32S/XS

ULTRA

22S/M

2 plus

26S/M

27M/I

30M

29S

40S

Software METRAwin10/Hit n METRAwin 90 F n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n METRAwin 90-2 n n n n n n

METRAwin 90 FJ n

n
in de

18C

CAL

3A

Ma

Germ a
ny

GOSSEN METRAWATT

36

MULTImETER ACCESSORIES: Pouches /Cases

Table of Contents

Pouches / Hard Cases / Covers / Hangers for Multimeters


Type HitBag Designation Article Z115A Z117A GTY3172083P01 GTY3172095P01 GTY3172097P01 GTY3172100P01 GTZ3301000R0003 GTZ3302000R0001 GTZ3302001R0001 Z104A Z104C GTZ3212000R0001 Z104B Z113A Z113A
METRAHIT STARLINE ONE...30M n n n n n n n n n n n n n n n n

com www.gossenmetrawatt.
METRAmax 1A / 2A n n n n 2/3/6 n n n n n n n 12 n n n METRAport 40S / 3A n n n

More information at:

Cordura belt pouch Magnetic hanger and strap HIT-Clip for METRAHIT with rubber holster F809 Ever-ready case with cable compartment F822 Ever-ready case with cable compartment F823 Ever-ready case with cable compartment F825 Ever-ready case with cable compartment F829 Carrying pouch F836 Ever-ready case with cable compartment Ever-ready case for 2 instruments, F840 2 adapters and accessories F841 Carrying pouch GH X-TRA Rubber holster GH18 Rubber holster with carrying strap GH19 Rubber holster HC20 Hard case for 1 device, accessories HC30 Hard case for 2 devices, accessories

HitBag

F809

F822

F823

Our Top Model

F840

F825

F829

F836

F841

HC30 GH X-TRA
in de

HIT-Clip

GH18

GH19

HC20

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

MAINS QUALITY

37

MAINS QUALITY
Mains Quality Always on the Safe Side with Clean Electrical Networks Industry, commerce, health care services, banks and other service providers are extremely dependent upon electrical and electronic systems. These systems inuence mains quality themselves in many ways, but they react extremely sensitively to disturbances as well. Theres only one convincing response to the challenges faced by users in the area of electrical power supply: highly versatile MAVOWATT mains quality analyzers for mains quality testing and assurance. With the help of these innovative class A (2008) products, all relevant measured quantities can be acquired which are decisive for the quality of electrical supply power the perfect foundation for sustainable optimization.

GOSSEN METRAWATT

38

MAINS QUALITY: Power Meters /Voltage Quality

Table of Contents

MAVOWATTI4
Article: GTM3033000R0001 The multiple power meter for direct measurement of DC power, as well as RMS power measurement for single-phase alternating current and balanced load three-wire, threephase current.
n Determination of reactive power nM  easurement of phase-to-phase

voltage(s)
nI deal instrument for training facilities n Phase sequence indicator n cos j measurement

Scope of delivery: n Batteries Optional accessories n Factory calibration certicate

MAVOWATTI20

Article: see description

In

cl. Softwar

3-Phase Energy and Power Analyzer Advantages:


A  cquisition of energy consumption and

costs
D  etermination of CO2 footprint D  etermination of inverter efficiency U  ninterrupted recording of all mains-

earth. Recording of energy exported to and imported from the grid has proven especially advantageous within a setting of alternative energy concepts. Energy Platform Report Writer Software (EPRW) License-free EPRW software records parameters including curves for voltage, current, active, reactive, and apparent power, power factor, harmonics, import, energy and much more in a user congured report. An energy audit report summarizes the energy measurement which consists of basic billing parameters such as tariff periods (peak, standard and off-peak), peak loads, energy costs and CO2 balance. Scope of Delivery Energy and power analyzer including a complete set of measurement cables, rechargeable battery, charger, 4 GB CF memory card, factory calibration certicate, operating instructions, EPRW software and carrying pouch

relevant parameters
M  easurement possible at 2 systems:

AC/DC
M  onitoring of energy ow direction License-free EPRW software P  rint-out of comprehensive, customer-spe-

cic reports
Compatible with DranView6

Applications The MAVOWATT 20 mains and power analyzer acquires power, demand and energy, and it calculates consumption costs as well as CO2 footprint. Harmonics and RMS voltage dips can also be recorded for the purpose of mains evaluation. DC coupled measurement inputs make it possible to determine the efficiency of photovoltaic inverters. Channel D is laid out as a differential input for measuring voltage between the neutral conductor and protective

An overview of the softwares performance features is available on the Internet (see order information for web address). Please refer the data sheets for further technical specications.
in de

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

MAINS QUALITY: 3-Phase Energy and Power Disturbance Analyzers

39

 DRANFLEX 3000XL/24 AC current sensor

(30/300/3000 A)  ISOFLEX-MHXL mains power pack R  R/PS/4A adapter cable for 4 DRANFLEX  AC/DC current clamp sensor MAVOWATT 20 Set 6 (M817V)  MW 20 and accessories (see above)  DRANFLEX 3003XL/24 three-phase AC current sensor (30/300/3000 A)  DRANFLEX 3000XL/24 AC current sensor (30/300/3000 A)  ISOFLEX-MHXL mains power pack  RR/PS/4A adapter cable for 4 DRANFLEX MAVOWATT 20 Set 7 (M817Z)  MW 20 and accessories (see above)  Additionally with exible current sensors: 4 ea. DRANFLEX 300MH (3/30/300A) with ISOFLEX-MHXL

Measured Quantities
 U, I, P, S, Q, TPF, DPF, f, demand  THD / harmonic spectrum (U, I, P),  TID sub-harmonic spectrum (U, I)  Crest factor, K factor, transformer

and energy

up to 63rd harmonic up to 63rd harmonic

derating factor, telephone interference factor, asymmetry (deviation from RMS values and sequence components)  W, VA, VAR, TPF, DPF, consumption, energy etc. Available Menu Languages
 European version includes:

in Our Product Range

New

English, French, Finnish, German, Italian, Polish, Spanish and Swedish  Asian version includes: English, Chinese (simplified and traditional), Japanese, Korean and Thai General Technical Data
 Dimensions:  Weight: 1.8 kg  Operating temperature: 0 to +50 C  Storage temperature: -20 to +50 C  Atmospheric humidity:  System time:

MAVOWATT 20 Sets MAVOWATT 20 Set 1 (M817Q)  MW 20 and accessories (see above)  4 TR-2500A AC current clamps (10 ... 500 A) MAVOWATT 20 Set 2 (M817R)  MW 20 and accessories (see above)  4 TR-2510A AC current clamps (1 ... 10A) MAVOWATT 20 Set 3 (M817S)  MW 20 and accessories (see above)  DRANFLEX 3003XL/24 three-phase AC current sensor (30/300/3000 A)  DRANFLEX 3000XL/24 AC current sensor (30/300/3000 A)  ISOFLEX-MHXL mains power pack  RR/PS/4A adapter cable for 4 DRANFLEX MAVOWATT 20 Set 4 (M817T)  MW 20 and accessories (see above)  4 TR-2550A AC current clamps (1 ... 100 A) MAVOWATT 20 Set 5 (M817U)  MW 20 and accessories (see above)  DRANFLEX 3003XL/24 three-phase AC current sensor (30/300/3000 A)

Measured Parameters
 4 voltage inputs for 1 to 600 VTRMS,

CAT III, AC/DC, 0.1% rdg., 256 samples per period, 16 bit ADC  4 current inputs for current sensors, 1 to 600 ATRMS, AC/DC, 256 samples per period, 16 bit ADC  Frequency range: 16/2/3, 45 to 65 Hz  Phase lock loop standard PQ mode Functions and Conformity
 IEC/EN 61000-4-7, harmonic analysis  EN 16001, energy management  EEE 1159 PQ guideline, events

203 x 300 x 64 mm

10 to 90%, no condensation system clock with quartz movement 90 to 264 V AC, 47 to 63 Hz

 Resolution: 1 second  Power pack / charger:

systems

 Battery operation time: 3 hours  Display:  Data storage:

identification C  ontinuous data logging of all measured


quantities with min., max. and mean values  Acquisition and recording of voltage

color LCD touch-screen, 12x9.5 cm high-speed compact flash 4 GB

within specified intervals

dips/swells with time stamp and characteristic values

Measured Quantities

www.gossenmetrawatt.

More information at:

com

Ma

in de

Germ a
ny

GOSSEN METRAWATT

40

MAINS QUALITY: 3-Phase Energy and Power Disturbance Analyzers

Table of Contents

+
MAVOWATTI30I40I70
3-Phase Energy and Power Analyzer Advantages: nS  imple control per EN50160, EN 61000-4-7 and EN61000-4-15 nS  imple handling, automatic detection of electrical system types nA  utomatic analysis/evaluation of measurement results in a matter of just seconds nA  utomatic report generation with ultramodern PC software nA  utomatic setup assistant Applications: The class A device (2008) simultaneously monitors TRMS values, harmonics, icker and transients down to a time range of approximately 80 s. The measuring conguration and the type of electrical circuit is selected automatically based upon detected measured quantities. Acquired data are stored to a CF memory card and can be transferred to DranView for further processing. Technical Data:
n8  measurement outputs, 4 voltage (differential) n4  current (current transformer), for measurement with line nS  torage of data to compact ash card nM  emory card with up to 32GB nP  ower supply:  Via charger: 90to 264V/47to63Hz Installed rechargeable battery for up to 3 hours operating time

MAVOWATT 70-400
nF  requency range: 50/60 Hz and 400Hz nT  esting per military standard 1399

Scope of delivery: Each set includes the mains analyzer of your choice plus a complete set of measurement cables, rechargeable battery and charger, compact ash memory card 4GB, factory calibration certicate, condensed operating instructions, DranView 6 Pro software and carrying pouch. Set 1 Energy and mains analyzer with accessories (see above) + three TR-2500A AC current clamps (10 to 500A) Set 2 Energy and mains analyzer with accessories (see above) + three TR-2510A AC current clamps (1 to 10A) Set 3 Energy and mains analyzer with accessories (see above) + DRANFLEX 3003XL/24 3-phase AC current sensor (30/300/3000A ) + DRANFLEX 3000XL/24 AC current sensor (30 / 300 / 3000A) + ISOFLEX-MHXL mains power pack Set 4 Energy and mains analyzer with accessories (see above) + 4xDRANFLEX 300MH (3/30/300A) with Isoex-MHXL + DranView6 Pro Software + Carrying pouch Article
M817E M817I M817M M817X M817B M817F M817J M817N M817Y

frequencies of 45to65Hz and 162/3Hz

MAVOWATT 40same as MW 30, plus:


n Acquisition of making-operations and error recording  Analysis module for voltage dip direction, switching peaks for

power factor correction and motor quality MAVOWATT 70same as MW 40, plus: nE  xpanded mains analysis functions nC  haracterization of transients nR  apid transient measurement as of 1 s sampling rate with storage of waveform parameters for distorted and asymmetrical systems per IEE1459 nV  ector / arithmetic parameters Type
MAVOWATT 30 Set 1 MAVOWATT 30 Set 2 MAVOWATT 30 Set 3 MAVOWATT 30 Set 4 MAVOWATT 40 MAVOWATT 40 Set 1 MAVOWATT 40 Set 2 MAVOWATT 40 Set 3 MAVOWATT 40 Set 4

Type
MAVOWATT 70 MAVOWATT 70 Set 1 MAVOWATT 70 Set 2 MAVOWATT 70 Set 3 MAVOWATT 70 Set 4 MAVOWATT 70-400 MAVOWATT 70-400 Set 1 MAVOWATT 70-400 Set 2 MAVOWATT 70-400 Set 3

Article
M817C M817G M817K M817O M817W M817D M817H M817L M817P

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

MAINS QUALITY: 3-Phase Energy and Power Disturbance Analyzers

41

MAVOWATTI50
Advantages:

Article: M816A

Type
MAVOWATT 50 MAVOWATT 50 Set 1 MAVOWATT 50 Set 2

Article
M816A M816B M816C

3-Phase Energy and Power Disturbance Analyzer


nM  easurement is possible in DC systems,

as well as in single and 3-phase AC systems. nC  omplete power disturbance analysis with simultaneous measurement of all relevant mains quantities nP  ower and energy analysis in power supply systems, as well as at the outputs of frequency converters nM  ains power monitoring per EN 50160, EN 61000-4-7, /-4-15, /-4-30 nL  arge frequency measuring range of up to 1kHz nW  orldwide use thanks to broad range variable power pack: 85to250V AC/DC nM  easurement and analysis of voltage transients of up to 1.3kV is possible as of a duration of 10s.

logging and analysis of energy consumption, right on up to calculation and static analysis of characteristic voltage quality from power supply systems in accordance with EN50160. It also functions as a test instrument and compares harmonic current generated by electrical equipment, as well as voltage uctuation, with specied limit values. Broadband measurement is laid out for line frequencies of up to 1 kHz, and covers everything from railway power at 162/3 Hz through mains power with 50/60Hz, right on up to onboard electrical systems with 400Hz.
n 8  isolated measuring circuits (4

nE  thernet TCP/IP with web server for

remote control and read-out


nS  torage of bulk data to plug-in CF memory

card or USB stick


nI ntegrated rechargeable battery for power

failures
nR  elay output for generating alarms in the

event that selected limit values are violated

Technical Data:

voltage and 4 current, 100kHz sampling rate) Applications: n4  digital status inputs indicate The spectrum of consumer operating states possible applications n 4  digital control inputs for synchronizranges from ing the measuring interval and the acquisition, display meter input and recording of nC  olor touch-screen: 1/4" VGA mains quantities to n U  SB ports (PC), external memory MAVOWATTI20 MAVOWATTI30 MAVOWATTI40 n n

Applications/Functions Mains analysis per EN 50160 Voltage quality measuring method Energy / load tests / examinations Extended load disturbance and asymmetry

MAVOWATTI70

MAVOWATTI50

n n n IEC 61000-4-30, IEEE 1159 IEC 61000-4-30 n n n n n 2 16 / 3, 50to60Hz 2 2 2 1000Hz Frequency measuring range 16 /3, 50to60Hz 16 /3, 50to60Hz 16 /3, 50to60Hz MW 70-400 up to 400 Hz n n Errors recording / in-rush n n Motor testing n n n n n Data logging Up to the 50th Harmonic analysis up to the 63rd harmonic n n n n (IEC61000-4-7, IEEE519) harmonic n n n n Flicker per IEC 61000-4-15, IEEE1453 Acquisition of fast transients 80s 80s 1s 10s AnswerModule (motor state, n n capacitance switching, voltage dip) Common Measurement inputs Differential Differential Differential Differential reference n Demand and energy reports Monitoring modes 2 4 7 7 8 Pre, error and post cycles 0 100 10,000 10,000 300 to 3500 Languages 11 11 11 11 3 n Interfaces (USB port, Ethernet) Optional Optional Optional Optional n Frequency converter measurement n Remote control of the instrument
Ma
in de

Germ a
ny

GOSSEN METRAWATT

42

MAINS QUALITY: 3-Phase Energy and Power Disturbance Analyzers

Table of Contents

Accessories: MAVOWATTI20I30I40I70
Type TR-2510B TR-2500B TR-2520B PR150/SP2B PR1500/SP8B PR150/SP1B PR1500/SP7B COMM-RS232 COMM-OEA COMM-OUA 4 mm adapter CFDATA-DB BP-PX5 SCC-4300 DRANFLEX 3000XL DRANFLEX 6000XL METRAFLEX 3001XL METRAFLEX 3003XL Description Current clamp sensor: 1...10 A AC RMS, 40 Hz...5kHz, 15mm dia. Current clamp sensor: 10...500 A AC RMS, 40Hz...5kHz, 50mm dia. Current clamp sensor: 100...3000A AC RMS, 40Hz...5kHz, 72mm dia. Current clamp sensor: 150AAC/DC, 9 V battery operation Current clamp sensor: 1500AAC/DC, 9 V battery operation Current clamp sensor: 150 A AC / DC, operation with power pack (included) Current clamp sensor: 1500A AC / DC, operation with power pack (included) RS 232 adapter including NodeLink software Ethernet adapter including NodeLink software USB adapter including NodeLink software Adapter for current clamps with 4 mm safety plugs Selected compact ash memory card, 4 GB Rechargeable battery pack Carrying pouch for measuring instrument, current clamps and manuals 30/300/3000A, various sensor lengths (e.g. 60cm) 60/600/6000A, various sensor lengths (e.g. 90cm) 30/300/3000A, 60 cm sensor length, without power pack 3-phase, 30/300/3000A, 60cm sensor length, without power pack Article Z817A Z817B Z817C Z817N Z817O Z817P Z817Q Z818A Z818B Z818C Z817T Z818F Z818G Z818H Z817V Z816B Z207H Z207I

Accessories: MAVOWATTI50

www.gossenmetrawatt.

More information at:

com

Z821B

Z3512A

WZ11B Max. Conductor Dia.

Z13B

CP30

CP330

CP1100

Type

Description

Applica- Measuring tions Category a, b a, b a, b a, b a, b a, b, (c) a, b, c 600V CAT III 600V CAT IIl 600V CAT III 600V CAT III 600V CAT III

Usable Range 50A20mA 1mA1.2A 0.026A 0.1 16A Low-pass lter f3dB

Output Signal Article 50mV/mA 1000mV/A 50mV/A 10mV/A ~900kHz 0.33 mV/A 1000mV/A 100mV/A 10mV/A 1mV/A Z860A Z861A Z862A Z863A Z865B Z821B Z225A

Plug-in Shunt Resistors Z860A 50W, 0.2%, 1.5W Z861A 1W, 0.2%, 1.5W Z862A 0.05W, 0.2%, 1.5W Z863A 0.01W, 0.2%, 1.5W STP 100K Set (3 pieces) 100kW, 0,2% Current Clamp Sensors Z821B AC, 30Hz5kHz Z3512A AC, switchable: 10Hz 3kHz

64mm 52mm

600 V/CAT II 3...3000 A~ 0.001...1.2A~ 600 V / 0.01...120A~ CAT III 0.1...120A~ 1...1200A~

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

MAINS QUALITY: Accessories

43

Type WZ11B Z13B CP30 CP330 CP1100

Description AC, switchable: 30 ... 500Hz AC/DC, switchable: DC ... 10kHz, with 9V battery (operating hours: approx. 50) AC/DC, switchable: DC ... 20kHz, with 9 V battery (operating hours: approx. 30) AC-/DC, DC...20kHz, with 9 V battery (operating hours: approx. 30) AC/DC, switchable: DC ... 20kHz, with 9V battery (operating hours: approx. 30)

Max. Conductor Dia.

Applica- Measuring tions Category a, (c) b, c b, c b, c b, c 600 V / CAT III 300V / CAT IV 300V / CAT III 300V / CAT III 300V / CAT III

Usable Range 0.5...20A~ 5...200A~ 0.2...40A~/60A ...0.5... 400A~/600A 5 mA ... 30 A 0.5 ... 30 A 5 300 A 0.5 100 A 5 1000 A

Output Signal Article 100mV/A 10mV/A 10mV/A 1mV/A 100mV/A 10mV/A 1mV/A 10mV/A 1 mV/A Z208B Z213B Z201B Z202B Z203B

20mm 50 mm 25mm 25mm 32mm

Flexible AC Current Sensors 10Hz ... 20kHz, METRAFLEX Switchable: with batteries or external 3001 power supply METRAFLEX 3-phase set, switchable: 10Hz ... 20kHz, with batteries 3003 or external power supply

61cm 3x61cm

a, b, c a, b, c

AC, 1000V/CAT III 30A AC, 600V/CAT IV 300A 3000A AC 1000 V/CAT III 30A AC, 300A AC, 600 V/CAT IV 3000A AC

100mV/10 mV/1mV per A Z207F (AC coupled) 100 mV/ 10mV/1mV pro Z207G A (AC coupled)

a = long-term measurement, b = harmonic measurement, c = frequency converter measurement

Metraex 3003 for MW 50

TR-2500A for MW 20/30/40/70

Metraex 3003 XL for MW 20/30/40/70

Accessories: MAVOWATTI20I30I40I70 and 50


Flexible Current Measuring Sensors with Voltage Output, mV / A
n Compact

Absolutely New

n Rugged n  Small The METRAFLEX 3000M or the DRANFLEX 300MH assures safe, accurate and exible measurement at bus bars and current distributors. The coil is above all highly suitable for difficult to access, tight spaces.

Feature
Measuring ranges Scaling factor Output sensitivity Accuracy (45to65 Hz) Noise Output connection Power Supply Battery Battery service life External Connection

Metraex 300M (Z207M)


3A 30A 300A 1 10 100 1000mV/A 100mV/A 10mV/A 1% rdg. 0.2A 1% rdg. 1A 3mV TRMS 1mV TRMS 0.1mV TRMS 1 pair 4mm safety plugs

Dranex 300MH (Z207N)


3A 30A 300A 2 20 200 500mV/A 50mV/A 5mV/A 1% rdg. 0.1A 1% rdg. 0.5A 1.5mV TRMS 4-pin Hypertronics plug

Metraex 300M for MW 50 and Multimeters

2ea. AA, MN1500 LR6 alkaline batteries 150hours (MFLEX 3000 M) 80hours (MFLEX 3000MXL) 3.512V DC/max. 100mA 2 3V DC/max. 100mA Barrel connector, 5.5/2.1mm, minus pole inside

Dranex 300MH for MW 20/30/40/70

Ma

in de

Germ a
ny

GOSSEN METRAWATT

44

MAINS QUALITY: Software

Table of Contents

DranView 6 Software

Article: see table

DranView makes it possible for power grid specialists to easily and quickly view and analyze monitored data from the mains. Its very easy to use, includes automated functionality and unites powerful analytical capabilities and adaptable options, in order to fulll the requirements of each and every user. DranView supports more than 12 languages and is being used successfully by thousands of customers all over the world. DranView is available in two different versions, namely Pro and Enterprise. Data collected by MAVOWATT 20, 30, 40, 50 and 70 power disturbance and power analyzers can be evaluated and documented with this extremely versatile and convenient PC software.
nI ntuitive, easy to handle user interface nR  otatable axes in graphics, simple dragging and zooming of diagrams nT  ime, waveform, amplitude duration and DFT diagrams nR  escue kit (data repair) nA  utomatic or user-specic report generator dependent upon measurement type nS  eparate scaling of harmonics for voltage, current and power nD  ata can be exported to ASCII,XLSandXLSX formats

Type
DVP-PX DVE-PX DVP-MW20 DVP-MW20TOPX

Article
Z818D Z818E Z818Q

Scope of delivery:
nD  ranView Professional (DVP-PX) including USB hardware dongle nD  ranView Enterprise (DVE-PX) including USB hardware dongle

METRAWin/MAVOWATTI20
Data Transmission and Analysis Software for MAVOWATT 50 Saved measurement data from the MAVOWATT 50 energy and power disturbance analyzer can be visualized in various views, analyzed and documented with METRAwin10 / MAVOWATT50 software. Recorded measurement data are transferred from the instrument to a PC with the help of a CF card or a memory stick, and are displayed at a browser. MAVOWATT 50 permits execution of the following functions via the browser:
nR  etrieve and display current LCD content nD  ownloading of recorded measurement

(e.g. live measured values) per mouse click or cyclically nR  emote control of all functions which can be executed via the instruments touch-screen per mouse click in the LCD panel shown in the browser (exceptions: touch-screen settings, network parameters and administrator functions) nD  ownloading of measurement and memory proles stored at the instrument for subsequent reuse or transfer to another instrument

data stored at the instrument for subsequent analysis with METRAwin10.

The browser can be started from METRAwin10 with the instruments URL address. However, direct communication between the software and the MAVOWATT 50 only takes place via the instruments integrated web server. Recording of live measurement data at the PC is thus not possible.

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS

45

TEStERS
Protective measures in electrical systems are intended to prevent bodily injury due to accidents involving electrical current. Of course they also prevent property damage caused by electrical power as well. And thus every electrical system should be checked with our test instruments before initial start-up, and at regular intervals thereafter, in order to assure the effectiveness of installed protective measures. For the most part, this involves testing in accordance with VDE 0100 (IEC 60364), VDE 0105 (EN 50110) and VDE 0113 (EN 60204) regulations. The tests themselves are executed by the instruments strictly in accordance with stipulations set forth in particular by VDE 0413 (EN 61557).

transfer

GOSSEN METRAWATT

46

TEStERS: DIN VDE 0100600/IEC 60364-6

Table of Contents

PROFITESTIMaster
For testing the effectiveness of safety measures in electrical systems in accordance with DIN VDE 0100600/DIN VDE 0105100 For use in all alternating and 3-phase electrical systems with voltages from 65 to 500V and frequencies of 15.4 to 420Hz

Testers: PROFITESTIMaster
Type
PROFITEST MBASE PROFITEST MTECH PROFITEST MPRO PROFITEST MXTRA

Article
M520M M520O M520N M520P

Advantages: Low-resistance, insulation, earth resistance, standing-surface insulation, loop and line impedance measurements, as well as testing of residual current devices (RCDs)
nC  AT IV n DAkkS calibration certicate n Bidirectional data exchange via USB n AMC automatic measurement cable

compensation using 4-wire method


n 2-pole measurements with plug insert or

interchangeable 2/3-pole adapter n Help menu with wiring diagrams n Connection of an RFID reader or barcode scanner n Including ETC software (Electrical Testing Center) n Bidirectional data exchange with DDS-CAD planning software n Free rmware updates with the master updater. Advantage: adaptation to changing standards and expanded functions n Registration at myGMC (www.gossenmetrawatt.com) Advantages (amongst others): u Protection against theft after registering your serial number u Free download of current rmware u Information regarding amendments to standards

Applications: nL  oop measurement without tripping the RCD n RCD test with continuously rising ramp n Voltage drop measurement n1  mA varistor response test with insulation measuring voltage up to 1000V nD  isplay of approved fuse types for electrical systems nE  nergy meter start-up testing n Calculation of cable lengths for common copper wire cross-section nL  eakage and equalizing current of up to 1A, as well as working current of up to 150A can be measured with the W Z12C current clamp sensor n Phase sequence measurement (including highest line-to-line voltage) nT  esting of special RCCBs with PROFITEST MTECH/MXTRA: selective S, SRCDs, PRCDs (Schukomat, Sidos and others), types A, AC, B, B+, F, G/R nT  esting of RCD protection in IT systems nI nsulation measurement with rising voltage n Current measurement with Metraex (option)

PROFITEST MXTRA Functions n Intelligent ramp, simultaneous measurement of breaking current IN and breaking time tA n Testing of IMDs and RCMs n Creation of test sequences (ETC) nB  luetooth interface n Earth resistance measurements, amongst others: u Selective earth resistance (4-wire measuring method) u Earth loop resistance (2-clamp method) u Soil resistivity Rho n Leakage current measurement with PRO-AB n Ascertainment of residual voltage per EN 60204 Scope of delivery: n Earthing contact plug insert (PRO-Schuko) n 2-pole measuring adapter and cable for expansion into a 3-pole adapter (PRO-A3-II) nA  lligator clips  n Set of rechargeable batteries and charger n DAkkS calibration certicate nE  TC software  nU  SB cable 

Incl. DAkkS rat Calib ion Certicate

In

cl. Softwar

An overview of the softwares performance features is available on Page 89 of the catalog and on the Internet (see order information for web address). Please refer to the data sheet for further technical specications.

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: DIN VDE 0100600/IEC 60364-6

47

PROFITEST MBASE MTECH MXTRA MPRO Overview Characteristics /Features RCD measurements UB measurement without tripping the RCCB Tripping time measurement Tripping current measurement Selective, SRCDs, PRCDs, types A, AC, G/R and F AC/DC sensitive RCDs, type B, type B+ Testing of insulation monitoring devices (IMDs) Testing of residual current monitoring devices (RCMs) Testing for N-PE reversal Loop impedance ZL-PE/ZL-N Fuse table for systems without RCDs Without tripping the RCD, fuse table With 15mA test current* without tripping the RCD Earth resistance RE I-U measuring method, mains operation (2/3-wire measuring method via measuring adapter: 2-wire/2-wire + probe) Earth resistance RE (battery operation) 3 or 4-wire measuring method via PRO-RE adapter Soil resistivity rE (battery operation) 4-wire measuring method via PRO-RE adapter Selective earth resistance RE (mains operation) with 2-pole adapter, probe, earth electrode and current clamp sensor (3-wire measuring method) Selective earth resistance RE (battery operation) with probe, earth electrode and current clamp sensor (4-wire measuring method via PRO-RE adapter and current clamp sensor) Earth loop resistance RELOOP (battery operation) with 2 clamps (current clamp sensor direct and current clamp transformer via PRO-RE/2 adapter) Measurement of equipotential bonding RLO Automatic polarity reversal Insulation resistance RISO Variable or rising test voltage (ramp) Voltage measurement UL-N/UL-PE / UN-PE/f Special measurements Leakage current (clamp measurement) IL, IAMP Meter start-up Phase sequence Voltage drop Standing-surface insulation ZST Earth leakage resistance RE(ISO) Leakage current with PRO-AB adapter Residual voltage test Intelligent ramp Features Selectable user interface language Memory (database for up to 50,000 objects) Automatic test sequence function RS 232 port for RFID/scanner USB port for data transmission Bluetooth interface ETC user software for PC Measuring category: CAT III 600V / CAT IV 300V DAkkS calibration n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

Working Efficiently
The PROFITEST MASTER product range allows for data entry via the RS232 port with the help of a barcode or RFID reader. This unique function assures maximum operating convenience for creating and expanding tree structures (customers, buildings, distributors etc.), searching for designations or IDs, navigating through various modes, creating test texts, inspection and trial tests, creating defects lists and much more. Data processing, measurement and visual inspection can be executed immediately without reconguring plugs or switches the basis for meaningful documentation.

Automated Test Sequences


Automated test sequences can be generated from manually created individual measurements with the help of the test sequence function. A test sequence consists of individual steps, measurements, visual inspections etc., which are executed one after the other. Measurement results obtained in this way are saved correctly to the freely selectable tree structure and can be subsequently documented by means of appropriate software. Test sequences are created with the help of ETC software and are transferred to the respective test instrument (PROFITEST MXTRA und MPRO).

* The so-called live measurement is only advisable if there is no bias current within the system. Only suitable for motor protection switches with small nominal current.
in de

Ma

Germ a
ny

GOSSEN METRAWATT

48

TEStERS: DIN VDE 0100600/IEC 60364-6

Table of Contents

Testing Packages
Article Accessories PROFITEST MBASE PROFITEST MTECH PROFITEST MXTRA Earth spike SP350 TR50 drum VARIO plug adapter set PRO-RLO II adapter PRO-AB leakage current measuring adapter E-Clip 2 generator clamp for earthing measurements Z3512A clamp for earthing measurements PRO-RE 2 measuring adapter for 2-clamp measuring method F2000 universal carrying pouch Professional case E-CHECK case Rechargeable battery pack Charger Charger M520M M520O M520P GTZ3304000R0001 GTY1040014E34 Z500A Z501P Z502S Z591B Z225A Z502T Z700D Z502W Z502M Z502H Z502P Z502R

M500M n n n n n

M500N n n n n n

M500P n n n n n n n n

M500U n n n n n

M500V n n n n n

M500W n n n n n n

M500X M500Y n n n n n n n n n n n n n n n

PRO-AB Leakage Current Measuring Adapter

TR50 Drum

PRO-RLO II Adapter VARIO Plug Adapter Set

E-Clip 2 Clamp Generator

PRO-RE 2 Measuring Adapter

F2000 Universal Carrying Pouch

SP350 Earth Spike Professional Case Z3512A Clamp Meter

PROFITESTIS1

Article: GTM5101000R0001
nI nsulation resistance measurements nL  ow-resistance measurements at

Simulation Model for Testing the Effectiveness of Safety Measures in Low-Voltage Systems per DIN VDE 0100 This model can be used to simulate TT and TN systems with overcurrent protective devices, as well as with RCDs (systems with overcurrent protective devices can be equipped with normal and selective RCCBs). In combination with the appropriate measuring and test instruments, all measurements and tests can be executed which are stipulated for safety testing of electrical systems of up to 500 V with various system types and protective measures.

equipotential bonding conductors


nM  easurements for testing RCDs nL  oop impedance measurements nE  arthing resistance measurements nL  ine voltage measurements

Optional accessories:
n S1A-4/10 contact protected jumper

(package of 10): GTZ3216000R0001 PROFITEST 0100S-II+, PROFITEST 2, PROFITEST ONE, C devices

nC  an be used with: PROFITEST MASTER,

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Pro-Package XTRA

Starter Package XTRA

Master Package TECH

Master Package XTRA

TECH Starter Package

MEDpackage XTRA

BaSE Starter Package

E-CHECK Set

Table of Contents

TEStERS: DIN VDE 0100-600/IEC 60364-6 49

PROFITESTIC
Article: M521A Test Instrument for DIN VDE 0100 / IEC 60364-6 Protective measures test instrument for loop resistance measurement, calculation of short-circuit current and display of suitable fuse ratings. In addition to complete testing for the effectiveness of RCCBs, the instrument is also capable of phase sequence analysis, as well as the measurement of voltage and frequency.
nR  ugged 2-component housing with nG  o / No-Go indication via LEDs, and

Incl. Factory Calibration Certicate

integral impact guard perfect for use by on-site installation teams and an ideal supplement to the PROFITEST 204 in accordance with the new EN 60204 standard. nL  arge, illuminated, anti-glare graphic display allows for clear, intuitive, menu-driven operation nQ  uick, easy operation with the help of just 5 keys nI ntegrated measured value memory can be read out via the IrDa interface which is included as a standard feature. nT  he instrument can always be kept current thanks to the update option. nS  torage of measured values with accurate assignment to their respective electrical circuits, distributors and buildings with the alphanumeric keypad

instructions in the display


nI ntegrated phase tester nS  tand, holders for test probes and

cables, and a recharging socket for NiCd/NiMH batteries Please refer to the data sheet for further technical specications.

YouR 2nd InStRumEnt

PROFITESTI2
Inexpensive, Universal Protective Measure Test Instrument for DIN VDE 0100600/IEC 603646 The PROFITEST 2 provides users with a test instrument for testing the effectiveness of protective measures in electrical systems per DIN VDE 0100600.
nE  asy operation n Fast test sequences n AMC automatic measurement cable nC  omplete RCD testing (RCD types A and AC) nE  arth measurement nP  hase sequence indicator nT  esting via earthing contact plug or

2-pole adapter Scope of delivery:


n Earthing contact plug insert

(PRO-Schuko)
n Cable for expansion into a

3-pole adapter
n 2 alligator clips /

compensation using 4-wire method nL  ow-resistance measurement nI nsulation measurement nZ  LOOP + IK + fuse type

2-pole measuring adapter


n Shoulder strap

Incl. Factory Calibration Certicate


Article M520W Please refer to the data sheet for further technical specications.

Type PROFITEST 2a D, GB, F, I, E, NL

Languages

Ma

in de

Germ a
ny

GOSSEN METRAWATT

50

TEStERS: Accessories

Table of Contents

Please refer to the data sheets for further technical specications.

SCANBase/SCANWriteIRFID
RFID Reader / Scanner The RFID identication system is used to mark and identify tools and equipment.

Barcode Scanner
Article: Z502F Barcode Scanner with Laser and Coil Cable Laid Out Especially for the Profitest Master Series For identifying system components and equipment. Devices and system components can be logged by the Profitest, and acquired measured values can be allocated to them with the scanner.
nS  canning of barcodes from considerable

PROFISCAN ETC
Article: Z502G List with Barcodes, CODE 128, for Use with the Z502F Barcode Scanner and Profitest Master Series Testers
nC  reation of system structures and

n RFID reader/scanner, RS 232 (Z751G)

See Page 88 for details.

distributors
nA  cquisition of room designations nF  unctions for navigating within the

database for the Profitest Master series distances


nV  ariable barcode lengths nI mproved reading accuracy nG  reen Spot technology nC  onguration of EAN13, CODE 39 and nN  ew entry and expansion of test texts n  Go/No-Go acknowledgment of report

texts, inspections and much more


nA  cquisition of defects / defects lists nS  pace for self-generated barcodes in

ETC software

CODE 128 barcodes

METRAFLEX P300

Article: Z502E

Flexible AC current sensor for PROFITEST MASTER nB  road range of applications, 3 measuring nH  igh levels of safety for the operator, ranges: 3 A,30A,300A AC measuring category: 1000 V @ CAT III, nB  road bandwidth of 20Hzto4kHz for 600 V @ CAT IV and unlimited overload harmonic analysis capacity nE  asy to use in tight spaces thanks to nA  ccurate measurement, even with low small sensor cross-section current values, thanks to large dynamic n9  .9 mm and narrow end-cap (13.6 mm) range and high sensor sensitivity nC  urrent sensor with IP 65 protection See Page 28 and Page 43 in the catalog for more exible AC current sensors.

PRO-AB
Article: Z502S PRO-AB Leakage Current Measuring Adapter for PROFITEST MXTRA
nI nput current: 0 to 10 mA nI nput impedance: 1 k 0.5% n Output voltage:

Plug Inserts: PRO-

www.gossenmetrawatt.

More information at:

com

PRO-SCHUKO Article: GTZ3228000R001 Plug insert for Germany and other countries with corresponding plug systems PRO-CH Article: GTZ3225000R001 Plug insert for Switzerland in accordance with SEV PRO-RLO II Article: Z501P Plug inserts for PE and other similar measurements PRO-UNI II Article: Z501R Plug inserts with 3 connector cables for any connection standards

10:1: 0 to 1 V (0.1 V/mA) 1:1: 0 to 10 V (1 V/mA) n  Output impedance: 10 k

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: /Ohmmeters Insulation Measuring Instruments

51

METRAOHM 413

Article: M630A
nC  ompact and rugged for service calls and

Digital Low-Resistance Measuring Instrument for Measuring Protective Conductors, Equipotential Bonding and Much More
nT  wo measuring ranges from 0.01 to 1999k,

laboratory use
nO  vervoltage protection protects the instrument

zero balancing for measurement cables


nI ndication of interference voltage

in the event of inadvertent connection to mains power nM  easuring category: CAT lll 300V/CAT ll 600V nI P 65 protection Scope of delivery: nP  lug-in measurement cable n9  V Battery

com www.gossenmetrawatt.

More information at:

METRISO C

Article: M541A

Battery Powered Insulation Resistance Tester for Measurements in Systems with Nominal Voltages of up to 1000V
nM  easurement of insulation resistance

Scope of delivery:
nM  easurement cables

and high value ohmic resistance with display of the measured value and the actual measuring voltage nM  easurements at bonding and protective conductors with low-resistance measurement nM  easurement of touch current nV  oltage and frequency measurement nO  ptional temperature measurement, measurement of relative humidity nA  ll measurements are in compliance with the following regulations: DIN VDE 0100, part 600, DIN VDE 0701-0702, EN 344, EN 1081 - insulation measurement only! nU  nambiguous limit value and Go/No-Go indication by means of LEDs, and display of useful information nA  ll measurement values are stored to memory with reference to their respective electrical circuit designations nR  ugged 2-component housing for everyday use Function Insulation resistance RISO Resistance RLO Voltage UISO/U~ Touch current IB

Please refer to the data sheet for further technical specications.

Incl. Factory lib Ca ration Certicate


Measuring Voltage Nominal Current 1mA (R =1k/V) 200mA (R <10)

Measuring Range

0.00k...99.9G 50V...1000V 0.00...99.9 0 V...1200V 0.00mA...9.99mA 4.5V (U0)


Ma

in de

Germ a
ny

GOSSEN METRAWATT

52

TEStERS: Low-Resistance / Insulation Measuring Instruments

Table of Contents

METRISO 1000A
Insulation Measuring Instrument for Electrical Systems with Warning in Case of Dangerous Touch Voltage Metriso 1000 A Display Insulation measuring voltage Insulation measuring range RLO measuring ranges Limit value signals Article Analog 501002505001000V 400 M 4 Indicator lamp M540C

METRISO 1000A

Please refer to the data sheet for further technical specications.

METRISO G500MM/G500/G1000/G1000+
Insulation and Low Resistance Measuring Instruments

METRISO G500MM

Please refer to the data sheets for further technical specications.

METRISO G1000A

METRISO G500

METRISO G1000+

METRISO G1000 Type Display Measuring voltage Measuring range Polarization index, PI/DAR Low-resistance measurement Voltage measurement Article number
in de

Metriso G500MM LCD 50 to 500V (50, 100, 250, 500) 10k ... 100G

Metriso G500 LCD 50 to 500V (50, 100, 250, 500) 10k ... 100G

Metriso G1000 LCD 50 to 1000V (50, 100, 250, 500, 1000) 10k ... 200G 0.17 10 10V 1000 V M550C

Metriso G1000+

Metriso G1000A

LCD Analog 50 to 1000V 50 to 1000V (50, 100, 250, 500, (50, 100, 250, 500, 1000) 1000) 10k ... 1T 10k ... 1T
n

10V 500V
M550E

0.17 10 10V 500V


M550D

0.17 10 10 V 1000V M550B

0.20 5 10 V 1000V M542A

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: Insulation Measuring Instruments /Accessories

53

Set Article
Accessories

Metriso G500MM Set M550J

Metriso G500 Set M550H

Metriso G1000 Set M550G

Metriso G1000+ Set M550F

Metriso G1000A Set M542B

Test probe for remote triggering METRISO G Ever-ready case METRISO G

Z550A Z550C

n n

n n

n n

n n

n n

Test probe for remote triggering METRISO G ever-ready case

METRISO 5024

Article: M540E
nL  ow-resistance measurements for

www.gossenmetrawatt.
protective conductor and equipotential bonding conductor resistance, and continuity nB  uzzer and blinking LED indicate alarm status for erroneous and implausible measurements nF  luttering pointer as last-resort warning function Measuring Current Short-Circuit Current

More information at:

com

Analog Insulation Measuring Instrument, Low-Resistance Measuring Instrument and Voltmeter with Buzzer for Quick, Two-Hand Operation
nE  rgonomic handling nI lluminated scale nI nsulation measurement with 100, 250

Scope of delivery: nI nsulation measuring instrument, ohmmeter and voltmeter nC  arrying pouch

and 500V measuring voltages Measuring Range Intrinsic Uncertainty

Overload

Insulation measurement, measuring voltage: 100 / 250 / 500 V 0.1...400M 2.5% 600V AC >1mA <10mA Measuring error under reference conditions relative to scale length (l = 84.6mm) Low resistance measurement, measuring voltage: 4.5 V 0...4 2.5% 250V DC >200mA Measuring error under reference conditions relative to upper range value (l = 74.9mm) Voltage measurement, DC / AC (40 ... 200 Hz) 0 ... 500V 2.5% 600V AC 450k Measuring error under reference conditions relative to scale length (l = 73.3mm)

Please refer to the data sheet for further technical specications.

Ma

in de

Germ a
ny

GOSSEN METRAWATT

54

TEStERS: Insulation Measuring Instrument / ISO Calibrator

Table of Contents

ME

METRISO 5000A

Article: M580A

TR

ISO

High-Voltage Insulation Measuring Instruments with Test Voltage of up to 5000V DC For non-destructive measure ment of insulation resistance in electrical systems, as well as at machines, transformers, cables and electrical equipment utilized in, for example, locomotives, street cars and ocean going vessels, with selectable test voltages of up to 5kV.

50

00 A /

Analog High-Voltage Insulation Measuring Instrument with Permanently Connected Measurement Cables and Test Probes METRISO 5000AK: The battery powered METRISO 5000 A is converted into the muscle powered METRISO 5000AK by replacing the battery module with a crank generator.
nE  xtensive measuring range: 10k...1T nM  easuring range: 100k...100M (1000V) nM  easuring voltages:100V, 250V, 500V,

M E

TR

ISO

50

00 D-

PI

nM  easurements to 1000V per DIN VDE 0413 n Voltage measurement to 1000V nC  oncise logarithmic display nG  uard terminal for the elimination of surface current

1000V, 1500V, 2000V, 2500V, 5000V

Scope of delivery: METRISO 5000A (580A) nW  ith battery module: METRISO 5000AK (580C) nW  ith crank generator Both with 5 KV alligator clips KY 5000A METRISO 5000A-Set (M580S)/ METRISO 5000AK-Set (M580T) nK  Y 5000A nG  UARD 5000A nU  niversal carrying pouch F2000

Please refer to the data sheet for further technical specications.

ISO KALIBRATOR 1

Article: M662A Please refer to the data sheet for further technical specications.

Test Adapter for Insulation Measuring Instruments and Ohmmeters Adapter for rapid, efficient testing of the accuracy of measuring instruments for insulation resistance and low-value resistors. Insulation measuring instruments with nominal voltages of up to 1000 V can be tested with the ISO Calibrator 1.
nT  est range: 100k to 100M nP  rotection: n Usable  with following instruments:

Housing: IP 50, sockets: IP 20

Metriso Series, Protest Master Series

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: Insulation Measuring Instruments

55

METRISO 5000D-PI

Article: M5810

Digital High-Voltage Insulation Measuring Instrument with Test Voltage of up to 5000V DC Voltage measurement to 1000V Testing for absence of voltage at the device under test in systems of up to 1kV can be performed with the voltage measuring range. Discharging Capacitive Devices Under Test Capacitive devices under test such as cables and coils, which may be charged with test voltage, are discharged by the measuring instrument. The falling voltage value can be observed at the display. Measurements in Accordance with EN61557, DIN VDE 0413 Nominal current amounts to 1mA at a test voltage of 100, 250, 500 or 1000V. Highly Insulated Measuring Cables The highly insulated measuring cables are permanently connected for safety reasons in order to avoid danger resulting from an inadvertently disconnected cable. Polarization Index PI Polarization index testing is recommended for electrical machines. This procedure involves expanded testing of insulation resistance. DC measuring voltage from the METRISO 5000D-PI is applied to the insulation for a duration of 10 minutes. The measured value is documented after one minute, and after ten minutes. If the insulation is defective, the value measured after ten minutes is higher than the value measured after one minute. The relationship between the two measurement values is the polarization index. Charged material within the insulation is aligned due to the application of measuring voltage over a long period of time, resulting in polarization. The polarization index indicates whether or not the charged material contained in the insulation can still be moved, thus allowing for polarization. This, in turn, is an indication of the condition of the insulation.
nE  xtensive measuring range:

Scope of delivery: nB  asic instrument with permanently connected measurement cables and test probes nA  lligator clips (5kV version) nR  echargeable battery (for M5810-0001 only) /mains power cable n5m extension cable/interface cable Please refer to the data sheet for further technical specications.

0.4M ...1T

nV  ariable test voltage, or in xed steps:

100V, 250V, 500V, 1kV, 1.5kV, 2kV, 2.5kV, 5kV nP  olarization index and absorption ratio nV  oltage measurement to 1000V nF  requency measurement: 15Hzto1kHz nC  apacitance measurement: 0.1...5F nM  easurement of electrical discharge nG  uard terminal for the elimination of surface current nS  upply power from mains, battery pack or external 12V power supply nB  acklit dot matrix display nD  igital display of measured values and limit values nT  imer function: 1s...100min. Incl. DAkkS

Calibration Certicate

Guard 5000A, Leadex 5000


Guard 5000A (Z580C) (for the elimination of surface current): guard cable and 1 alligator clip  Leadex 5000 (Z580D): 5m extension cable

Generator 5000A
Article: Z580A Crank Generator for Metriso 5000 A The battery powered METRISO 5000A is converted into the muscle powered METRISO 5000 AK by replacing the battery pack with a crank generator.

KY 5000A
Article: Z580B Alligator clips, 5 kV version

www.gossenmetrawatt.

More information at:

com
in de

Ma

Germ a
ny

GOSSEN METRAWATT

56

TEStERS: Earth Testers

Table of Contents

GEOHM C

Article: M590A
nM  easurement of earth resistance in 5

Battery Powered Earth Tester also for Measurement of Soil Resistivity


nC  ompact, menu-driven instrument for the

ranges to 50kW

measurement of earth resistance for 3 or 4-wire connection nC  ontinuous monitoring of interference voltage, as well as auxiliary earth electrode and probe resistance with indication if allowable limit values are violated nC  omplete display of all required values at a large dot matrix display, or warning with 4 LEDs. Easy concise operation with only 4 keys.

nV  oltage measurement: 10to 250V nF  requency measurement: 45to200Hz nB  attery monitoring and self-test nI ntegrated memory with IrDA interface nE  arth tester per DIN VDE 0413 nE  xtremely rugged 2-component housing

Please refer to the data sheet for further technical specications.

GEOHM 5

Article: M591B

Earth Tester for All Known Measuring Methods This battery powered measuring instrument can also be used to ascertain or measure soil resistivity and ohmic resistance in accordance with the current-voltage measuring method. Easy concise operation with only 4 keys.
nM  easurement of: u Earth resistance  u Selective earth resistance u Soil resistivity uC  urrent (TRMS) via clamp meter

com www.gossenmetrawatt.
Please refer to the data sheet for further technical specications.

More information at:

Scope of delivery: nB  lack test cable, 4.5 meters nG  reen test cable, 4.5 meters nR  ed test cable, 15 meters nB  lue test cable, 20 meters n4  earth spikes n4  batteries per LR14 nC  arrying strap nS  tackable system case Optional accessories:
nB  attery charger with 4 batteries n LINK-G software Z591D

(optional) nC  onventional 3 and 4-pole measurement nS  elective single-clamp measurement (optional) n2  -clamp measurement (optional) nB  attery operation is possible (optional) nD  igital display nR  ugged housing nN  o balancing required nC  ontinuous monitoring of interference voltage and auxiliary earth electrode resistance with indication when allowable limit values are exceeded nD  ata storage for 250 measurements (1000 measured values) nD  ata interface for transmission of measured values to a PC

Z591C

Incl. Test report

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: Accessories

57

E-Set 3
Article: GTZ3301005R0001 Set of measuring accessories for measurements with earth spikes. Measuring accessories set consisting of: n2  reels n2  measurement cables, 25m each n1  measurement cable, 40m long n2  measurement cables, 3m each n4  earth spikes (zinc plated) n 2 spike pullers n1  hammer

E-Set 4
Article: Z590A Set of measuring accessories for earth measurements, same as E-Set 3 but with earth drills instead of spikes. Measuring accessories set consisting of: n2  reels n2  measurement cables, 25m each n1  measurement cable, 40m long n2  measurement cables, 3m each n4  earth drills Usable with following instruments: GEOHM C, GEOHM 5, PROFITEST MXTRA/MPRO*

E-Set 5
Article: Z590B Extensively equipped earth measurement case for device and accessories. Earth measurement case consisting of: n 1 imitation leather case n 1 drum with 25 m measurement cable n 2 drums with 50 m measurement cable each n 3 measurement cables, 0.5 m each n 1 measurement cable, 2 m long n 1 test clamp n 4 earth drills, 350 mm long n1  dust cloth n 2 pads with forms Usable with following instruments: GEOHM C, GEOHM 5, PROFITEST MXTRA/MPRO*

Usable with following instruments: GEOHM C, GEOHM 5, PROFITEST MXTRA/MPRO*

* Only in combination with PRO-RE adapter (Z501S)

E-ClipI1/E-ClipI2
E-Clip 1 Clamp Meter: 1mAto1200A, 1mA/A, 40Hz5kHz, 52mmdia. n Measuring range: 1mAto1200A (Z591A) n Measuring category: 600V CATIII n Cable diameter: 52 mm n Transformation ratio: 1000A/1A n Frequency range: 40Hzto5kHz n Output signal: 1Ato1.2A nS  cope of delivery: clamp meter with connector cable (1.5m) and laboratory safety plug E-Clip 2 Generator Clamp: 0.2to1200A, 1mA/A, 40Hz 5kHz, 52mmdia. Same as E-Clip 1, but: (Z591B)  n Measuring range: 0.2 Ato 1200A n Output signal: 0.2mAto1.2A nS  cope of delivery: Generator clamp with laboratory safety plug inputs

E-Clip

SP350 Article: GTZ3304000R0001


Earth spike, 35cm long, with connector for 4 mm banana plug. Can also be used as a probe or auxiliary earth electrode for earth measurements, testing RCCBs etc.
in de

Ma

Germ a
ny

GOSSEN METRAWATT

58

TEStERS: Accessories

Table of Contents

A3-1663 3-Phase Adapters


3-Phase Current Adapter for Connecting Test Instruments to 5-Pole CEE Outlets
nT  he adapter corresponds to the 5-pole

PRO-A3 II Measuring Adapter


Article: Z501O Measuring Adapter for Systems, 3-Phase Current, Phase Sequence Scope of Delivery n 2 alligator clips

CEE outlet with appropriate nominal current nF  or 16 A nominal current: A3-16, 32A: A3-32, 63 A: A3-63 nP  hase sequence testing with signal lamps nT  esting the effectiveness of safety measures with ve 4mm contact protected sockets
nA  3-16 (GTZ3602000R0001) nA  3-32 (GTZ3603000R0001) nA  3-63 (GTZ3604000R0001)

Magnetic Test Probes AC Current Clamp Sensors


nZ  3512A (Z225A): WZ12C nM  agnetic test probes

with 4 mm sockets

Z3512A

current clamp sensor, 0.1/1/10/100/1000A AC, switchable nW  Z12C (Z219C): Current clamp sensor,1mAto15A AC, 1mV/mA, 1Ato150A AC, 1mV/A, switchable

Measurement cable
TR25  (GTZ3303000R0001) Reel with 25m measurement cable. Cable ends are equipped with banana plugs. TR50  (GTY1040014E34) Metal drum with 50m measurement cable. One end of the cable is integrated into the drum as a socket, and the other is equipped with a banana plug. The drum axle can be inserted with a single action.
TR50 TR25

Z502Z

Rechargeable Battery Set


nB  attery set for PROFITEST Master

KS24 Cable Set


Article: GTZ3201000R0001 Cable Set for Test Instruments The KS24 cable set includes a 4m long extension cable with a permanently attached test probe at one end and a contact protected socket at the other end, as well as an alligator clip which can be plugged onto the test probe.
in de

series (Z502H): 8 rechargeableNiMH eneloop batteries nC  hargers for Z502H battery set (Z502P) for PROFITEST MTECH/ MBASE Z502R for PROFITEST MXTRA/MPRO/ METRISO G1000+

Z502H

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: Accessories

59

Please refer to the data sheets for further technical specications.

T/F Sensor

Article: Z541A

VARIO Plug Adapter Set

Adapter for temperature and atmospheric humidity measurement with infrared interface to the measuring instrument. For determining ambient temperature and  atmospheric humidity during oor measurements including:
n Leakage, insulation and

Article: Z500A Three self-retaining, contact protected test probes for the connection of measurement cables with 4mm banana plugs, or with contact protected plugs for sockets with an opening of 3.5mm to 12mm, e.g. CEE, Perilex sockets. For example, the test probes also t the square PE jacks on Perilex sockets. Maximum allowable operating voltage: 600V per IEC 61010.

surface resistance n Temperature range: -10to+50C n Relative humidity measuring range: 10to90%

Article: GTZ3196000R0001 Floor Probe This metallic tripod-type measurement electrode is used for: nD  etermination of electrical resistance at elastic oor coverings in accordance with EN 1081 nR  esistance measurement for insulating oors and walls in accordance with DINVDE 0100600

1081 Probe

Telearm 1

Article: GTZ3232000R0001

E-CHECK-Set

Article: M500U

Telescoping rod with test probe, and with a socket in the handle for quick and safe testing of, for example, lamps installed at excessive heights for the measurement of protective conductor resistance. The rod is 53cm long and can be telescoped to a working length of 120cm and locked into place. Max. allowable voltage to earth: 1000V. Carrying pouches F2000 HC30-C HC40
Ever-Ready Case

nP  rotest MTECH (M520O) nV  ARIO plug adapter set (Z500A) nW  riting pad

Included with E-CKECK case.

E-CHECK case (Z502M): Printed with contents layout. Optional: trolley (Z502N): Suitable for E-CHECK case

Description Universal carrying pouch for measuring and test instruments, as well as accessories, dimensions: 380 x 310 x 200mm Hard case for series C testers and accessories,  dimensions: 394 x 294 x 106mm Hard case for 2 series C testers and accessories,  dimensions: 450 x 361 x 140mm Ever-ready case for PROFITEST MASTER with external pockets for accessories
HC30-C/ HC40
in o

Article Z700D Z541C Z541D Z502X

NEW in our product range

F2000

ur p New rodu ct

EverReady Case
rang e

IrDa-USB Converter
Article: Z501J Interface Adapter for Connecting a Test Instrument to a PC (IrDA-USB) Electrically isolated infrared interface for data transmission between the test instrument and a PC (USB).
nS  cope of delivery: CD ROM with

RS 232 USB Converter


Article: Z501L Interface Converter The interface converter is used to connect any desired device with RS 232 ports to PCs which are equipped with USB ports only.
nS  cope of delivery: CD ROM with

interface drivers

interface drivers

com www.gossenmetrawatt.
Ma
in de

More information at:

Germ a
ny

GOSSEN METRAWATT

60

TEStERS: DIN VDE 0113/EN 60204

Table of Contents

PROFITEST I204+/204L+

Article: GTM5027000R0001/M505C

Tester for DIN VDE 0113, EN 60204-1 Portable test instrument for measurements per EN 60204, DIN VDE 0113 and similar regulations for machines and their electrical systems, with measured value storage and report generation. Measuring instrument for:
nP  rotective conductor measurement nI nsulation measurement nR  esidual voltage measurement nT  ouch current

Scope of delivery for PROFITEST 204+: n 1 test probe with integrated control unit for remote control of functions for protective conductor and insulation resistance measurement with permanently connected Please refer to the data sheet for measurement cable further technical specications. n 1 test probe with integrated fuse and permanently connected measurement cable Incl. Factory n 1 cable lug Calibration Certicate n Mains power cable with earthing contact plug n 1 factory calibration certicate

n 1 RS 232 bus cable for connection to the COM port PROFITEST 204L+: Same as PROFiTEST 204, but: n With permanently connected 12 meter measurement cable n With Start/Store function activation in the test plug

MetraMachineI204/2.5+ (M504D), MetraMachineI439/5.4+ (M504F)


MetraMachine 204/2.5+: for DIN VDE 0113, EN 60204-1 Portable test instrument for measurements per EN 60204, VDE 0113 and similar regulations for machines and their electrical systems, and report generation. MetraMachine 439/5.4+: for DIN VDE 0660500, EN 60439-1 Portable test system for testing low-voltage switchgear combinations per DIN VDE 0660500, EN 60439-1. Scope of delivery: MetraMachine 204/2.5+ n PROFITEST 204+ n PROFITEST 204HP n Signal 204 n Leadex 204 n Caddy 204 n Test report MetraMachine 439/5.4+ n PROFITEST 204+ n PROFITEST 204HV n Signal 204 n Leadex 204 n Caddy 204 n Test report

Incl. Factory Calibration Certicate

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: Accessories

61

Accessories for PROFITESTI204+


nS  ignal 204 (Z504D): nC  addy 204 (Z504A): nR  S 232 USB Converter (Z501L):

Combination signal lamp on a magnetic base plate for high-voltage tests in accordance with DIN VDE 0104
nC  able lug 204 (Z504E):

Trolley for basic instrument combined with high-voltage module, includes cover with side pockets
nC  laim 204 (Z504G):  et of various items used to warn S

Adapter for PE and ISO tests plug-on cable lug for secure attachment of the test probe to terminals
nL  eadex 204 (Z504C):

Interface adapter cable for connecting the RS 232 port at the test instrument to the USB port of a PC for transferring data between the PC and the test instrument, e.g. for software updates
nF  2000 (Z700D):

12 meter extension for the measurement cable with test probe to which the measuring circuit fuse is installed

unauthorized persons and for securing large areas, machines or machine components during the performance of high-voltage testing.

Universal carrying pouch For the test instrument and accessories

Signal 204

F2000

RS 232 USB Claim 204

Caddy 204

ProfiTestI204HP/2,5kV, ProfiTestI204HV/5,4kV
High-Voltage Module for Connection to the PROFITEST 204+ PROFITEST 204 HP-2.5 (M505A) 2kV high-voltage module for connection to the PROFITEST 204+ and expanded measuring options for high-voltage testing with 2 x UN or 1000V, from 500 VA transformer (max. 700VA). Adjustable high-voltage: 1000to 2000V. PROFITEST 204 HV-5.4 (M505B) 5kV high-voltage module for connection to the PROFITEST 204+ and expanded measuring options for high-voltage testing for EN 60439 and similar regulations. Adjustable high-voltage: 1000to 5000V (max. 100VA).

Incl. Test report

Article:M702G Article:GTM5016000R0001 for PROFITEST I204+/204L+ and METRISO 5000D-PI The SECUTEST SI / SECUTEST PSI serves strictly as an input device for the PROFITEST 204+ and the METRISO 5000D-PI. With the help of the SECUTEST PSI, test results can be printed out in the form of documented reports with date and time.
Ma
in de

SECUTestISI+ SECUTestIPSI

Germ a
ny

GOSSEN METRAWATT

62

PhotovoltaicS

Table of Contents

PROFITEST IPV

Article: M360A Peak Power Measuring Instrument and Curve Tracer for PV Modules and Strings

The PROFITEST PV allows for the measurement of characteristic IU curves, as well as individual photovoltaic modules and strings.
Generator voltage up to 1000 V DC, current up to 20 A DC Measurement of short-circuit current ISC, open-circuit voltage UOC, Separate measurement of temperatures at the irradiation sensor

and the back of the module for increased measuring accuracy


High level of intrinsic safety thanks to included load disconnector

instantaneous peak power of a solar cell Pmax, internal series resistance RS, measurement of internal parallel resistance RP Automatic conversion of momentary measured values to STC Patented calculation process for evaluating PV generators without knowledge of the manufacturers specications Patented calculation process for determining the generators internal series resistance based solely on a single characteristic IUcurve

(1000V / 32 A DC) for all-pole disconnection of the measuring instrument from the PV generator Calibrated irradiation sensor in accordance with IEC/EN 60904-2 with integrated Pt1000 temperature sensor Integrated customer/module database with bidirectional data exchange Software for Graphic Representation, Evaluation and Documentation with Integrated Database / PV Analyzer Scope of delivery for PROFITEST PV n Irradiation sensor with integrated Pt1000 temperature sensor, 10 m n External safety disconnector, 1000 V / 32 A n 4-wire measurement cable set, 10 m n Pt100 PV surface sensor n External power pack

External Load Disconnector

Calibrated Irradiation Sensor

Case System for the Protest PV and Accessories

External 4-Wire Measurement Cable, Pt100 Temperature Sensor 10 m, Set

External Power Pack

PV Analyzer
The database software offers effective support for testing and documentation. Its been specially developed for use in the eld of photovoltaics and allows for graphic representation and analysis of measurement results. PV Analyzer includes the following functions and more: n Read-in measured characteristic curve values from the PROFiTEST-PV n Export of measured values or results (e.g. as XLS le) n Generation of a test report (e.g. as a PDF le) n Online measurement graphic representation of the characteristics curve and measured values (also suitable for continuous measurement) n Online access to the database / data management in the PROFiTEST-PV n Representation of measured and calculated values under STCs n Overview of characteristic IU curves for a given test series in browser window n Module database (approx. 40,000 modules) n Analysis function: evaluation of measured values acquired under STCs (error interpretation).

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

PhotovoltaicS

63

Accessories for PROFITEST IPV


nT  rolley (502V): for case system nM  agnetic test probes (Z502Y): nP  V adapter set (Z360K):

MC3-MC4
nP  V adapter set (Z360J):

nP  V adapter set (Z360H):  UNCLIX-MC4 S n4  -wire measurement cable (Z360L):

with MC4 plug

TYCO-MC4

25 meter connection

PV Adapter Set MC3-MC4 (Z360K) Trolley (502V) for Case System

PV Adapter Set SUNCLIX-MC4 (Z360H)

Magnetic Test Probes with MC4 Plug (Z502Y)

PV Adapter Set TYCO-MC4 (Z360J)

4 Wire Measurement Cable Set, 25 m Connection (Z360L)

PROFITEST IPVSUN

Article: M360C

Test Instrument for Testing PV Modules and Strings per DIN EN 62446 (VDE 0126-23)
 Voltage measurement: 0...1.000VDC  Current measurement (direct):  Ground fault measurement:  Compact and rugged Weight: just 500 g  Extensive accessories

0...20ADC Insulation resistance measurement Measuring range: 0...20M  Test voltages: 250V,500V,1.000VDC

0...1.000VDC  Testing for protective conductor continuity: 0...10/>200mA Polarity test Backlit LCD panel

for service calls under harsh conditions

Scope of Delivery
n n n n n n n n

1 PROFITEST PVsun tester 4 batteries, 1.5 V IEC LR6 (AA) 3 safety measurement cables, 1.5m, red, blue and yellow 1 Solar plug adapter to MC3 and MC4 1 plug-on safety test probe with socket 1 plug-on safety alligator clip with socket 1 carrying case with foam insert 1 set of operating instructions

Accessories for PROFITEST IPVSUN


nP  ROFITEST PV SUN-SOR (Z360N):

Sensor for irradiation, temperature and inclination

Ma

in de

Germ a
ny

GOSSEN METRAWATT

64

TEStERS: METRALINE

Table of Contents

METRALINE IZCHECK

Article: M507A Loop Resistance Measuring Instrument

The test instrument is used to measure earth-fault loop impedances and line impedance. The measuring range of 0 to 200 (0.27 to 200 per VDE0413 /EN61557) allows for calculation of short-circuit current from 0 to 23 kA. The METRALINE Zcheck allows for the evaluation of measured impedance in consideration of type, nominal current and disconnection time. A table with the parameters of various protective devices is included in device memory. The following measurements can be performed with the METRALINE Zcheck: Fault loop impedance with short-circuit current Measurement Results Fault loop impedance with short-circuit current without tripping the RCD Line impedance with short-circuit current Line voltage Phase detection Phase Detection (L) Features Table of common protective devices can be displayed Digital display, backlit color OLED display, switching between brief and detailed representation LED for measurement point illumination Table Display Patented means of securing test probes Compact and rugged

For service calls under harsh conditions and laboratory use


Article: M507B Testing of Residual Current Devices (RCCBs) As indicated by the designation, this is a measuring instrument which tests the characteristics of an RCD. In particular, this involves the measurement of touch voltage, disconnection time and breaking current for type A, AC (impermissible in Germany), and S RCDs, as well as type F mixed frequency RCDs as of recently.
Measurement of touch voltage without tripping the RCCB. Touch voltage is measured with reference to nominal residual current using

METRALINE IRCDCHECK

www.gossenmetrawatt.

More information at:

com

Touch voltage

1/3 of the nominal residual current value.


Tripping test with nominal residual current, measurement of time to trip Special tests for systems and RCDs Testing systems and RCDs with rising residual current including indication of

Time to trip

tripping current
Testing of RCDs, IDN = 10, 30, 100, 300 und 500 mA Testing of RCDs with IN, 1 IN, 2 IN,

Testing RCDs with half-waves (pulsating direct current)

(5 IN to 100 mA nominal current)

Tripping current

for determining time to trip and tripping current Testing of special RCDs, selective S , type AC, type A, type F Measurement of line voltage and fault loop impedance

OLED = light emitting diode (LED) made of organic semiconductive materials. The great advantage of this component is its high contrast, which makes it especially suitable for measuring instruments.
in de

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: METRALINE / METRATHERM

65

Article: M507C Insulation Resistance Measurement The test instrument allows for the measurement of insulation resistance with test voltages between 50 and 1000 V in accordance with VDE0413-1,-2 (EN 61557-1,-2). The measuring range is 100 k to 1 G.
Measurement of insulation resistance at voltage-free

METRALINE IISOCHECK

Ramp Function

devices and systems, up to 1000 V depending upon variant


Measurement of surge protection devices, up to 1000 V depending upon

Measurement Results

variant
Checking of test objects for absence of voltage Insulation resistance measurement with test voltage from 50 to 1000 V Voltage measurement to 600 V Table Display Measurement of surge protection devices with test voltage from 50 to 1000 V Table of common varistors can be displayed Digital display, backlit color OLED display Indication of dangerous touch voltage Type Description LED for measurement point illumination Loop Resistance Measuring Patented means of securing test probes Metraline Zcheck Instrument Compact and rugged check Metraline RCD T  esting of RCCBs For service calls under harsh conditions and laboratory use

Article M507A M507B M507C Article Z507A Z507B

Metraline ISOcheck Scope of delivery: n 1 test instrument with mobile test probe n 4 batteries (AAA) n 1 carrying pouch n 1 set of condensed operating instructions n 1 CD-ROM with operating instructions in available languages n 1 factory calibration certicate

Insulation Resistance Measurement 

Optional Accessories Broad-range charger for charging batteries Input: 90 to 265 V AC Output: 9.5 V DC, 180 mA 4 rechargeable batteries (AAA)

METRATHERM|1

com www.gossenmetrawatt.
Article: M680A

More information at:

Contactless Infrared Thermometer with Laser Pointer and Data Logger Software for Temperature Measurement at a Safe Distance from the Danger Zone For repairs and maintenance work in the automotive industry and in air conditioners, scientic experiments, manufacturing processes in the eld of semiconductor technology, contacts in electrical control cabinets, food monitoring and processing
nI nfrared temperature measuring range: nS  torage of currently measured tempera-

-50to1000 C (-58to1832F) nE  xact positioning with activatable laser beam nH  igh distance-to-spot size ratio (D:S) of 50:1 nE  missivity adjustable from 0.1 to 1.00 in steps of 0.01 nA  dditional contact measurements with type K thermocouple nI ndividual/continuous measurement, 10memory locations for individual measurements

ture, lowest and highest temperature or maximum temperature difference T nU  SB port for data transmission to a PC nS  oftware for displaying and recording measured values (data logger) Scope of delivery:
nC  arrying strap nT  ype K thermocouple nU  SB adapter cable n9  V battery per 6LR61 nC  D ROM with installation program for PC

display and recording program


in de

Ma

Germ a
ny

GOSSEN METRAWATT

66

TEStERS: Phase Sequence Indicators /Voltage Testers

Table of Contents

PhaseCopI2

Article: GTM5202000R0001
nN  ominal range of use:

Phase Sequence Indicator with LEDs and Contact Protected Plugs Instrument for determining direction of rotation and phase sequence in three-phase systems Phase sequence is acquired by means of an electronic circuit. The direction of rotation is indicated by one of two directional arrows, each of which is equipped with an LED. An LED is provided for each phase which indicates whether or not the phase conductor is live. The device can be used in all low-voltage systems.
nC  omplies with DIN VDE 0413-7 /

90to660V/45to1000Hz Scope of delivery:


n Phase sequence indicator n 3 permanently connected measurement

cables with contact-protected plugs


n 3 plug-on test probes n 1 alligator clip

n F801 ever-ready case (GTY3172070P01)

Optional accessories:

EN61557-7, indicates direction of rotation and phase

Please refer to the data sheet for further technical specications.

DUSPOL
EN 61243-3 (DIN VDE 0682-401) DUSPOL Voltage and Continuity Tester nD  ata Hold/measuring point illumination nD  irect display without key activation high impedance testing nI mpact resistant housing with IP 64 protection against dust and water

DUSPOL digital LC

DUSPOL analog plus

DUSPOL expert

EN 61243-3 Display Measuring category Display levels Continuity test Phase sequence test Single-pole phase test Polarity test Load switched via pushbutton 30 mA RCCB tripping via pushbutton Vibration alarm Measuring point illumination Protection Article
in de

DUSPOL digital LC LED/LCD CAT IV 6 to 750V Buzzer +LCD, 200k LCD LCD LCD Is=200mA (750VDC)
n n

DUSPOL analog plus Moving coil / LED CAT IV 12 to 690V LCD LCD LED Is=250mA (750VDC)
n n

DUSPOL expert LED / LCD CAT IV 12 to 690V Buzzer +LED, 108k LCD LCD LED Is=200mA (750VDC)
n n

LED IP 64 M611A

IP 64 M611B

LED IP 64 M611C

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: Phase Sequence Indicators /Voltage Testers

67

MetraPhaseI1

Article: M620A in accordance with the regulations, as is nominal line voltage. The phase sequence indicator can be used as a 3-pole or a 2-pole indicator.
nC  omplies with DIN VDE 0413-7/EN

Phase Sequence Indicator with Electronic Rotary Dial, Frequency Display and Nominal Line Voltage Display Complies with Safety Regulations The mechanical rotary dial based upon the Ferraris principle preferred by many users necessitates a large housing for the respective clearances and creepage distances. Our phase sequence indicator has an electronic rotary dial. LEDs arranged in a circular array not only indicate the direction of rotation, but rather line frequency as well by means of LEDs which light up in various colors. The presence of voltage at each phase is indicated with additional LEDs

61557-7

nI ndicates direction of rotation and phase,

as well as nominal line frequency and voltage nN  ominal range of use: 100to690V/50to400Hz nP  ower supply: 4 ea. mignon cell per IECLR 6

Scope of delivery: n3  plug-in measurement cables with contactprotected plugs n3  plug-on test probes n1  alligator clip n4  batteries n Carrying case Optional accessories: n GH18 (GTZ3212000R0001): Rubber holster n Vario plug adapter set (Z500A): 3.5to12mm diameter

Please refer to the data sheet for further technical specications.

ProfiSafe 400/690
EN 61243-3 (DIN VDE 0682-401) Rugged Voltage, Phase, Continuity, Polarity Tester and Phase Sequence Indicator for up to 400 or 690 V in accordance with EN 61243-3 (VDE0682401)
nD  ouble indication reliability nI ndividually tested for dielectric strength

METRAVOLT 7A
EN 61243-3 (DIN VDE 0682-401) Voltage Tester with Indication of Phase, Polarity and Direction of Rotation

METRAVOLT 12D+L
EN 61243-3 (DIN VDE 0682-401) Voltage Tester with Indication of Phase, Polarity and Direction of Rotation
nL  arge backlit display

EN 61243-3 Nominal voltage Measuring category Protection Dielectric strength Display levels Input impedance Continuity test Frequency Range Current Display Power supply Functions Article

ProSafe 400 12400V CAT IV IP 65

ProSafe 690 24690V CAT IV IP 65

Metravolt 7A 24740V CAT IV IP 65

Metravolt 12D+L

New range roduct p r u in o

> 5kV, test voltage: 5kV (1.2/50ms pulse wave) 12/24/50/ 12/24/50/ 120/230/ 400V 120/230/400/690V 117k 202k 1M/57k 311k 0500k 0500k 010k 02000Hz 02000Hz 0100Hz 1510,000Hz 3.4mA 3.4mA 0.6 ... 13mA 3.2mA Measuring movement LEDs LEDs LCD (backlit)+LEDs +LCD+LED Rechargeable Li battery Rechargeable Li battery None 9 V block battery with solar cell with solar cell Voltage testing and measurement plus phase, continuity, polarity and phase sequence indicator M630E M630F M630D M630G
Ma
in de

81000V AC/1500V DC CAT IV IP 65 10kV, test voltage: 6kV (1.2/50ms pulse wave)

Germ a
ny

GOSSEN METRAWATT

68

TEStERS: Current Clamp Meters

Table of Contents

com www.gossenmetrawatt.

More information at:

Technical Data

METRACLIP 41

METRACLIP 410

METRACLIP 61

METRACLIP 62

Article

M320A

M320B

M311D Digital leakage current clamp, DATA HOLD and maximum/minimum display.

M311F Current clamp for measuring leakage and charging current. Leakage current clamp meter with specially shielded clamp opening for protection against external inuences. 18 III/300 digital 200m AC TRMS/DC 2000m AC TRMS/DC 10AC TRMS/DC 100 A / 1 mA / 0.01 A 50 to 60 2kHz cut-off frequency Min/Max; DATA HOLD 1% 3/5 /10 digits 2ea. LR6 (AA) 76 x 194 x 30 0.35kg

Description

Electrical safety per IEC Electrical safety per IEC 61010. 61010. HOLD function. HOLD function Suitable for measuring 4 to 20 mA process signals

Clamp opening (mm) CAT/Vmax (V) Display, digits Current (A) Resolution Voltage (V) Frequency range for U / I (Hz) Peak memory Frequency measurement (Hz) Continuity Resistance (Ohms) Active power (W) Power factor Accuracy Power supply Dimensions (mm) Weight with battery

25 III/300 digital 5mAto40A TRMS (AC+DC) 1 mA / 10 mA 15 to 400 DATA HOLD 1% rdg. 5 digits 9V block 75 x 190 x 30 0.235kg

25 III/300 digital 100mAto400A TRMS (AC+DC) 10 mA / 100 mA 15 to 400 DATA HOLD 1% rdg. 5 digits 9V block 75 x 190 x 30 0.235kg

40 III/300 digital+bar 00.3/0300AC 0.01 mA / 0.01 A 50 to 60 DATA HOLD (1.2%+5d) (-5%5d) 2 ea. LR44/SR44 64 x 176 x 23 0.125 kg

Included Accessories

2 button-cell batteries, imitation leather pouch

Batteries, imitation leather pouch

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: Current Clamp Meters

69

METRACLIP 63

METRACLIP 64

METRACLIP 70

METRACLIP 72

METRACLIP 75

M311G

M311H

M312A Clamp meter with 4-place digital display. Automatic or manual measuring range selection, DATA HOLD and maximum/minimum display.

M312E

M312H

Milliampere current clamps for measuring leakage current and process signal current (4 to 20 mA). The milliampere current clamp is extremely well suited for measuring small DC and AC current values beginning with 1mA. Its equipped with a power saving circuit, an analog interface, indication of exceeded measuring ranges and a exible current sensor, and can even be used under very unfavorable mechanical conditions. 5 II/600III/300 30 II/600III/300

Digital clamp multimeter with multimeter functions: Direct and alternating voltage measurement, continuity test, buzzer, resistance, overvoltage category: CATIII@600V, IP 40 protection, Frequency measurement, Temperature measurement phase sequence 26 26 III/600 ... IV/300 4000 0.2to400 DC/AC RMS 600 A pk III/600 ... IV/300 4000 0.1to200 AC RMS, 0.2to600 DC/AC RMS

42 III/600 digital 0.2 to 1400 DC 0.2to1000 AC RMS 100 mA / 1 A 0.2 to 600 DC 0.4to600 AC 45 to 450 Min/Max; DATA HOLD ...4k Acoustic 0.5to6M 2%10 digits 9 V, IEC 6 LR61 97x254x46mm 0.6kg Battery, carrying pouch, 2 measurement cables with test probes

digital digital 100m/1000m DC 100 m/1000m DC 100 m/1000m AC 100 m/1000m AC 10AC 10AC 0.01 mA / 0.1 mA / 0.001 mA 50 to 60 DATA HOLD 1%10 digits 4ea. LR6 (AA) 19 x 113 x 28 0.28kg 50 to 60 DATA HOLD 1%10 digits 4ea. LR6 (AA) 33 x 170 x 24 0.28kg

10 mA / 100 mA / 1 A 0.2to600 DC/AC RMS 0.2to600 DC/AC RMS 900 V pk 900 V pk 45 to 65 Min/Max; DATA HOLD Peak 0.01Hz...20kHz Acoustic ...400 0.040k 240kW 0.2 ... 1.00 1%+2 digits 9 V, IEC 6 LF22 70x193x37mm 0.26kg 45 to 65 Min/Max; DATA HOLD; PEAK Acoustic ...400 0.54k 1%+2 digits 9 V, IEC 6 LF22 70x193x37mm 0.26kg

IEC LR6 batteries (AA), carrying pouch, data recording cable

Battery, 2 measurement Battery, 2 measurement cables with contactcables with contactprotected plugs and test protected plugs and test probe, probe, 1 adapter for type K 1 alligator clip, pouch with thermocouple, pouch with carrying strap carrying strap
in de

Ma

Germ a
ny

GOSSEN METRAWATT

70

TEStERS: Overview of Accessories

Table of Contents

5000D-PI

GEOHM C

MXTRA

Modules, Adapters, Plugs, Plug Inserts, Cable Sets S1 SECUTEST SI+/PSI A3-16 A3-32 A3-63 3-pole adapter Vario plug Telearm1 TR25 TR50 SP350 KS24 KS-C Z502Z PRO-Schuko PRO-CH PRO-RSA PRO-A3 II PRO-RE PRO-RE 2 PRO-RLO II PRO-UNI II Z550A IrDa-USB RS 232 USB Z580A KY 5000A Guard 5000A Leadex 5000 Simulation model per DIN VDE 0100 Module (printer, memory, RS 232 interface) 3-phase adapter 5-pole for 32A n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n GTM5101000R0001 M702G/ GTM5016000R0001 n GTZ3602000R001 n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n GTZ3603000R001 GTZ3604000R001 Z521A, B, C Z500A GTZ3303000R0001 GTY1040014E34 GTZ3304000R0001 Z541F Z502Z

CEE outlets CEE outlets 3-phase adapter 5-pole for 63A CEE outlets
3-phase adapter 5-pole for 16A 3-phase measuring adapter for Schuko plug or CH, UK Plug set, 3.5...12mm dia. (3 pcs.) Telescoping rod for PE measurement Reel with 25m measurement cable Drum with 50m measurement cable Earth drill, 35cm long Extension cable, 4m Cable set: measurement and high-resistance measurement cable for G range Magnetic test probes Plug insert for PRO-A3 adapter (Germany) Plug insert for PRO-A3 adapter (Switzerland)

n n GTZ3232000R0001

n n

n n

n n n GTZ3201000R0001

n n n n n n n n n n n n n n n n n n n n n

n GTZ3228000R0001 n GTZ3225000R0002 n n Z501A Z501O Z501S Z502T Z501P Z501R Z550A Z501J Z501L Z580A Z580B Z580C Z580D

Plug insert for PRO-A3 adapter (South Africa)

Measuring adapter for systems, 3-phase current, phase sequence n Adapter for connecting clamp meters, 2-clamp method Plug inserts for PE and other similar measurements Test probe for remote triggering the Metriso G IR to USB interface Adapter cable, RS 232 to USB port Crank generator Alligator clips, 2 ea. Guard cable, 1 ea. with 1 alligator clip Extension cable, 5m

3/4-wire measurement, selective earth resistance measurement n n n n n n n

n n n n n n n n n

Plug inserts: 3 connector cables for any connection standards n

n n n n n n n n n n n

Current Clamps, Temperature Sensors Current clamp sensor: 1mA...15 A/1A...150A AC, WZ12C switchable Current sensor clamp, 0.1/1/10/100/1000A AC, Z3512A switchable Generator clamp: 0.2...1200A, 1mA/A, 40Hz5kHz, E-CLIP 2 52mm dia. T/H sensor Sensor for temperature and relative humidity Probes 1081 Probe Z502F Z721D Z751G Z591C NA101 NA102 Z502H Pouches, Cases F2000 HC30-C HC40 F837 Z502X Z550C Universal pouch Hard case for series C testers and accessories Hard case for 2 series C testers and accessories Ever-ready case for Metriso Ever-ready case for Protest Ever-ready case for Metriso G Triangular probe for oor measurements Barcode reader/scanner, infrared with RS 232 port Barcode printer RFID reader/scanner, (13.56 MHz) with RS 232 port Charger with 4 NiMH rechargeable batteries Charger for 0100S battery set Charger for battery sets for C series instruments Battery set: 8xNiMH rechargeable

n n n

n n n

n n n

n n n n

Geohm5

G1000+

G1000A

Type

Designation MBASE MTECH 204L+ MPRO 204+

METRAOHM 413

PROFITEST

METRISO Article

1000A

5000A

G1000

G500

5024

Z219C Z225A Z591B Z541A

n n n n n n n n n n n

n n GTZ3196000R0001 Z502F Z721D Z751G Z591C Z501M Z501N Z502H Z700D Z541C Z541D Z502X Z550C

Barcode Scanners / Printers n n n n n n n n n n n n n n n

Chargers, Battery Sets n n n n n n n n n n n n n n

n n n n n n n n n n n n n

n GTZ3312000R0001 n

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: High-Voltage Transformers

71

For sale in Germany only

WR50-12/13/12R/13R Article: see below


50 A Winding Resistance Meter, 2-Channel (WR5012) or 3-Channel (WR50-13) The revolutionary charging and discharging circuit in the WR50 allows for extremely quick resistance measurement of highly inductive loads, at the same time assuring maximum safety. channels/direct temperature correction of the resistors n  Heat-run test can be implemented (optional) nC  olor LCD panel, backlit touch-screen nI ntegrated printer (interval controlled print-outs) nI nterfaces: two USB and nC  harges inductive loads up one RS 232 to 1500 Henry nS  tores up to 10,000 nH  igh power supply: 50A / complete measurement 50V DC results nS  electable current for nV  isual and acoustic resistance measurement: indication of charge and from 0.05 to 100k discharge statuses nF  astest discharge unit on nE  asy operation with the market (more than 10 touch-screen/water-proof housing times as fast) nF  ully automatic degaussing n U  nsurpassed safety and circuit (internationally protection circuitry unique)
n3  temperature measuring nS  electable test current:

50 to 0.01A DC/output voltage: 0 to 50V DC n Input power: 90to250V AC (max. 1.5kW) 50/60 Hz automatic nO  perating temperature: -10 to 60 C; storage temperature -20 to 70 C
n WR50-12: n WR50-12R: n WR50-13: n WR50-13R:

M681M M681T M681N M681P

Micro Junior 2

Article: M681A

10 A Micro-Ohmmeter, Portable and Fully Automated For testing and documenting connection and contact resistance
n Extremely  accurate resistance measure-

ment in the eld nS  uitable for eld use thanks to battery operation nF  ully graphics compatible display; self-calibration nI nternal memory for measurement results nI ntegrated reports printer n Can  be expanded for turns resistance measurement (50A, 50V) with WR50-1A

nC  urrent ranges: 1mA DC ... 10A DC,

safety/protection circuit nS  ingle pushbutton operation; emergency stop nR  ugged, lightweight, water-proof carrying case Resistance measurement nT  est current: 10 mAto10 ADC, resolution: 4 places, accuracy: 0.1%

n Battery:  14.8 V / 6 Ah, external charger: n Serial  port: 9-pin RS 232 n Internal  memory for 2000 measurement nO  perating temperature: -10to60 C,

100 to 240V AC 50 / 60Hz results

storage temperature -40to 70 C

Scope of delivery: 3m measurement cable set, alligator clips

Micro Centurion 2

Article: M681E

200 A Micro-Ohmmeter for measurement of contact resistance at circuit breakers and connections nE  xtremely accurate n Large  input voltage range nI nternal memory: up to 2000 measureresistance measurement results Resistance measurement ment in the eld n Graphics  compatible LCD with background nT  est current: 10 to 200 A DC, resolution: 4 nS  ingle pushbutton illumination places, accuracy: 0.1% operation / continuous n Interfaces:  9-pin RS 232 serial / 25-pin nI nput voltage range: 100 to 205V AC, 45 current Centronics parallel to 65Hz, max. 1kW n Graphics  compatible display/self-calibration nO  perating temperature: -10to60 C, nT  emperature measurement (optional): n Internal  memory for measurement results storage temperature -40to 70 C -20to140 C, resolution: 0.1 C, nS  afety and protection circuitry; emergency off Scope of delivery: 5m measurement cable accuracy: 0.7% nR  ugged, water-proof carrying case set, alligator clips
in de

Ma

Germ a
ny

GOSSEN METRAWATT

72
For sale in Germany only

TEStERS: High-Voltage Transformers

Table of Contents

TR-1/TR-1P

Article: see below


nT  R-1P with integrated printer nT  urns ratio:

Portable, Single-Phase Ratio Meter for Rough Use in the Field The TR-1 is a fully automated, single-phase transformer-turns ratio meter which is suitable for precise laboratory applications, as well as for use in the eld. Its a rugged, lightweight instrument which automatically measures turns ratio, excitation current and phase displacement. Furthermore, the TR-1 measures the highest ratios with the greatest accuracy in its class in the CT mode down to very low power ratings. Its is easy to operate, and can be used for all single and multiphase transformers. Specications nR  ugged, lightweight, water-proof carrying case nO  peration with rechargeable battery nR  echargeable with mains power or 12V automotive adapter nG  raphic LCD panel with background illumination nI nternal memory for the last 100 measurements nU  p to 1000 measurements with fully charged battery nM  emory for up to 16 transformers for comparisons nC  ontinuity test/polarity test nF  ully automated measurement nF  unction for comparison with nominal values nT  est current of up to 1 A for current transformer test (CT) nR  echargeable lithium ion battery, 16.4V / 1.6Ah n2  -year standard guarantee

Measuring Parameters

u Range: 0.8to100, resolution: 5 digits u PT accuracy (40V): 0.08% rdg. 1 LSD u CT Accuracy (1 to 5V): 0.08% rdg. 1 LSD u Range: 101to4000, resolution: 5 digits u PT accuracy (40V): 0.08% rdg. 1 LSD nT  est current, PT mode: 0to0.1 A, CT mode: 0to1 A, accuracy: 1mA, resolution: 0.1mA nO  utput voltage, PT mode: 40V AC, CT mode: 1to5V, automotive mains input: 100 to 250V AC 50/60Hz automatic, 12V DC (optional) nI nterface: RS 232 nF  ront panel: anodized aluminum nO  perating temperature: -10 to 60C/ storage temperature: -40 to 70C
n TR-1 (M681R): 5m measurement cable set nT  R-1P (M681K): 5m measurement cable

Scope of delivery:

set, printer module

T-Rex/T-Rex R

Article: M681D/Z681G
nS  elf-calibration; 3-phase voltage vector measurement nO  ne-time only hook-up to the transformer nL  oad on device under test: < 0.05 VA nS  afety and protection circuitry, Centronics (parallel) interface nR  ugged, lightweight, water-proof carrying case n2  -year guarantee nL  ine voltage: 100 to 240V AC 50/60Hz, auto-ranging nT  est voltage: 40V AC/0.5A max. nO  perating temperature: -10to60 C,

Voltage Vector Measuring Option for the TR-Spy Mark II, 3-Phase, Fully Automated The T-Rex allows the operator to test the phase relationships of transformer windings while applying three phase voltage. This system is thus capable of precisely measuring the angular relationships of 3-phase transformers. This option is intended for transformers with phase relationships of other than 30 degrees or multiples thereof.

storage temperature -40to 70 C

Type TRO201

Description

Micro TR-Mark Micro Centurion WR WR 50-12 Article IIR Junior 2 50-1A WR 50-13 II

10m measurement cable extension (also in various other lengths) TP02 Temperature probe TP01 Temperature probe TRO203 Trigger switch, length: 10m MJO201 Kelvin clips, length: 3m RaytechFree PC software for all Raytech devices. Toolbox.net Always the most up-to-date version via free download. for checking ratio measurements and current TR-Checkbox Checkbox measurements
Ma
in de


n n

n n

n n n

Z681D Z681B Z681E Z681C Z681A


n n

M681L

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS

73 73

TEStERS Electrical Equipment


Test Instruments for Testing the Electrical Safety of Electrical Equipment at the Workplace and in Production The fulllment of legal requirements such as occupational safety legislation, medical device regulations and product safety law necessitates comprehensive measurements and testing in accordance with stipulations set forth in DIN VDE, as well as EN and IEC standards, for example:
n As

an equipment manufacturer per IEC/EN61010, 60601, 60950, 60335 n For service work or as the operating company u For electric equipment per IEC 62638 E, (DIN VDE 0701-0702) u For medical devices IEC 62353 (VDE 0751) u For welding equipment per IEC 60974-4 (VDE 0544-4)

GOSSEN METRAWATT

74

TEStERS: Electrical Safety of Equipment Overview: Testers


Type MINITEST BASE METRATESTER 5+ PRO MASTER SECUTEST S2 N+/+10 S2 N+W SECUTEST SIII+/ SECULIFE ST

Table of Contents

SECUSTAR FM+/ SECULIFE SB

SECULIFE SR

Article number Applications, Target Groups BGV A3, VDE 0701-0702, BetrSichV For trained persons Repairs and service Production Tooling expenditures Medical technology, VDE 0751, IEC 62353 Medical technology, IEC 60601 (SFC conditions) Welding technology, IEC 60974-4 (VDE 0544-4) Interfaces USB (m = master, s = slave) Ethernet CF connection RS 232C Test sequences Data storage (devices under test) Software (optional) Functions / Measurements Visual inspection
Protective conductor resistance

M712C M712D M712U n n n n n s n n s n 2000

M700D M7010-V031/32 n n n n n n

M7010-V033 n n n n n n

Congurable n n n n n n n

M761A/M691A n n n n n 4m n n Programmable Approx. 3000*

M692A n n n s

n n Fixed, per standard

meas. values

125 (PSI option: approx. 400; SECUSTORE: 1000) Comprehensive information is available on Page 89.

Insulation resistance

200 mA n

n 200mA/10A

n Programmable 200mA 10/25A 200mA Adjustable voltage d (RMS) E, (AC) d (AC, DC, RMS) E, (AC) d (AC, DC, RMS) E (AC) d (RMS) E, (AC)

200mA

Leakage Current Test Methods d = direct, E = equivalent, = differential Protective conductor (AC) (AC) (AC) E, (AC) E, (AC) current Touch current Patient leakage current Leakage current from the application part Device leakage current d (AC) d (AC) d (AC) d (AC)

d (AC, DC, RMS) E, (AC) d DC, RMS) d (AC, DC, RMS) d (AC, DC, RMS) E (AC, (AC) (AC, DC, RMS) d (AC, DC, RMS) d (AC, DC, RMS) d E (AC) d (AC) E (AC) E (AC) E (AC) d (AC, DC, RMS) d (AC, DC, RMS) d (AC, DC, RMS) E, (AC) E, (AC) E, (AC) E, (AC) U, I, P, PF n n n n n

Function Test U = line voltage, I = current consumption, P = power; PF = power factor U, I Other Measurements High-voltage test
RCD test (time)

Customer specic Rotary switch 230V / 50Hz

n n

Expandable as desired n

Voltage measurement Temperature: Pt 100 / Pt 1000 (optional) Miscellaneous Display Operation Mains power
in de

LED

2-line LCD Rotary switch, save key 230V/50Hz

Black and white dot matrix Rotary switch, scroll keys 230V/50Hz 230V/50Hz 115V/60Hz

Color Black and white touch-screen dot matrix Touch-screen, Keys keys Battery 90Vto250V 90Vto250V 40Hzto400Hz 40Hzto400Hz
*> 3000 performance reduction

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: Electrical Safety of Equipment

75

SECUTEST S2N+/+10/SECUTEST S2N+W


DAkkS Calibration Certicate

Test Instrument for BGV A3 and MPG Universal Test Instrument for Testing the Electrical Safety of Electrical Devices in Accordance with Safety Legislation, Medical Device Regulations and BGV A3 Automatic test sequences per:
n IEC 62638 E (VDE 0701-0702) u Testing of extension cables u Passive test sequence (device is not started up) u Active test sequence (device is started up) u Testing of computer equipment nI EC 62353 (VDE 0751),

testing of electrical medical devices or


nI EC 60974-4 (VDE 0544-4),

testing of arc welding equipment Expanded functionality:


nS  afety for the user thanks to integrated safety switch Photo shows optional SI+module.

suitable for persons with basic electro-technical instruction nM  enu driven test sequences in compliance with the standards including automatic detection of protection classes I + II nV  oltage measurement at SELV PELV circuits included in the test sequence nC  onvenient memory and report generating functions (optional with S2N+) nE  xpanded data storage and reports generating via optional, external memory nE  xpandable with optional accessories for 3-phase devices Scope of delivery:
nP  robe cable with test probe nA  lligator clip nD  AkkS calibration certicate nC  arrying strap

Optional accessories beginning on Page 82


SECUTEST S2N+w with optional SI+ module

Ma

in de

Germ a
ny

GOSSEN METRAWATT

76

TEStERS: Electrical Safety of Devices

Table of Contents

Standard Models SECUTEST S2N+ Article: M7010-V031


n IEC 62638 E (VDE 0701-0702) u Testing of extension cables u Passive test sequence (device is not started up) u Active test sequence (device is started up) u Testing of computer equipment nI EC 62353 (VDE 0751),

testing of electrical medical devices

SECUTEST S2N+10 Article: M7010-V032


same as M7010-V031 plus:
n2  00 mA/10 A test current

SECUTEST S2N+w Article: M7010-V033


nI EC 60974-4 (VDE 0544-4),

) accessories (package eXample: M702P

beginning on Page 82

same as M7010-V032, but instead of IEC 62353 (VDE 0751): testing of arc welding equipment

www.gossenmetrawatt.

More information at:

com

SOFTWARE SECU-UP

Article: Z713C/Z713D

Firmware Update for all SECUTEST SIII..., SIII+... and -SII+... Not for SECUTEST SII, DC, med, SECUTEST 0701 or SECUTEST 0701/0702S. Software for reading out data from the SECUTEST and generating simple reports. The software includes:
nD  evice software update resulting from

further development free of chargewithin a given primary version. Simply download and install the software, or send your instrument to GMC-I Service GmbH.

For a fee for instruments with older versions. Just ask our service department for an update appointment, and the instrument can be recalibrated at the same time if required. nL  anguage selection for operating and help menus included languages: D, GB, F, I, E, NL, CZ nU  pdating of optional device functions if enabled nE  nabling of options after purchasing an enabling code

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: Electrical Safety of Devices 77

SECUTEST|SIII+

Article: M7010/SECULIFE|ST Article: M693A

Calib DAkkS ratio n Cer ti


Universal Test Instrument for Testing the Electrical Safety of Electrical Devices in Accordance with Safety Legislation, Medical Device Regulations and BGV A3, as well as Final Inspection Testing in Production Automatic test sequences per: n IEC 62638 E (VDE 0701-0702), testing of electrical devices nI EC 62353 (VDE 0751), testing of electrical medical devices nI EC 60601, routine testing of electrical medical devices (optional/congurable) nI EC 60335, routine testing of household appliances nI EC 61010, routine testing of laboratory equipment nI EC 60950, routine testing of IT equipment Expanded functionality: nM  enu driven test sequences in compliance with the standards including automatic detection of protection classes I + II nA  utomatic adaptation to either 110V / 60Hz or 230V / 50Hz mains power nC  onvenient memory and report generating functions nE  xpanded data storage and reports generating via optional, external memory nE  xpandable with optional accessories for 3-phase devices nA  pplication-specic conguration Plus the following with Seculife ST: nU  p to 10 application parts can be connected nT  est sequence per IEC 60601 with SFC conditions Standard models available from stock: Secutest SIII+H Seculife ST (M693A) n Internal  memory for 125 test results (entry of ID number and designation via barcode/RFID) nD  irect printing nD  etection of probe at protective conductor n IEC  60601, routine testing of electrical medical devices (optional/ congurable) Seculife ST HV (M693C)
nI ncluding high-voltage test up to 6000V DC (at SC II devices) nA  C test current for 25 A protective conductor measurement

cate

Designation

Basic Instrument = All 00 Features

M7010 M693O
Standard Model M7010V013 M693A
n B00

Scope of delivery: nP  robe cable with test probe/alligator clip nD  AkkS calibration certicate Optional accessories: see SECUTEST S2N+/S2N+I10

SECULIFE|ST with option for connecting up to 10 application parts

n B00 Germany Germany, additionally with B01 service socket Connectors and UK B02 plugs for mains France / Czech Republic B03 power and socket for Denmark B05 device under test B06 B07 China / Australia B08 Other countries upon Switzerland B09 request Adapter set for international use (equipped with B11 feature B01) n C00 German English C01 French C02 Language Italian C03 for user prompting Spanish C04 Czech C05 Dutch C06 None F00 With HV test, setpoint: HV test max. 4kV AC test n F02 voltage output: max. 6.126kV DC G00 AC test current for 10A n G01 protective conductor 25A measurement Without AC test current G02 None KA00 Test sequence for IEC 60601 With (recommended with J01) KA01 KB00 Data memory for up None n KB01 to 125 tests With None KD00 Detection of probe at protective conductor With (including SK5 probe, 5m) n KD01 None KE00 Direct printing after each Direct printing n KE01 measurement for automatic test sequences

B01 B02 B03 B05 B06 B07 B08 B09 B11


n C00

C01 C02 C03 C04 C05 C06 n F00 F02


n G00

G01 G02
n n n

Ma

in de

Germ a
ny

GOSSEN METRAWATT

78

TEStERS: Electrical Safety of Devices

Table of Contents

SECUSTAR|FM+ Article: M761A SECULIFE|SB Article: M691A


Modular Measuring and Test System for User-Controlled Execution of Legally Required or Company Specied Work Procedures and Directives, e.g. Occupational Safety Legislation and Medical Device Regulations
nS  uitable for use by trained persons n Predened test sequences for u Electrical devices (IEC 62353/DIN VDE 0701-0702) u Electrical medical devices (IEC 62353/DIN VDE 0751) u Arc welding equipment (IEC 60974-4) nC  an be easily supplemented with freely programmable test steps n SECUSTAR FM+ n Bagstar carrying pouch n Barcode scanner (Z751A) n PC.doc-ACCESS for testing in accordance with

Starter set (M702W)

DINVDE07010702 Optional accessories beginning on Page 82 n Package of 3 wands (Z753A): for data entry via the LCD touch-screen n Package of 2 retaining clips (Z753B) n DAkkS calibration certicate(Z752A)

and test sequences


nO  peration via color touch-screen nM  ains-independent operation with rechargeable batteries nD  ata storage and data management for more than 2000 objects nI ntegrated deadlines management nD  ata interfaces: 4-socket USB hub for connecting PC,

printer or sensor
nU  SB, CF connection for data exchange; Ethernet

connection for hook-up within the LAN Scope of delivery: n Mains connection at the test instrument: via 16A inlet plug country-specic at the mains end n Probe cable with test probe/alligator clip n Compact ash card type II

SECULIFE|SR

Article: M692A
nP  rogrammable test sequences nC  reates tree structure for devices under test

Universal, PC Controlled Measuring Instrument Used for testing the electrical safety of electrical medical devices after repair or modication, and for conducting periodic tests at regular intervals.
nS  treamlined, time-saving tests thanks to direct measurement

(customer, building, room, oor, type etc.) nT  ree structure interchangeable via e-mail

start-up by pressing a key


n USB data interface nC  onnection of 10 application parts (via 4 mm sockets) nS  upports all measuring methods for leakage current (direct,

differential, equivalent)
nC  onnection option for 10A test probe (PGS10 Z745Y)

ETC data management software (included)


nT  ests can be remote controlled with ETC software nC  onvenient reports generation (as PDF le, export to Word or

EXcel)
nT  est results displayed as a list by simply pressing a key
Ma
in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: Electrical Safety of Devices

79

METRATesterI5+

Article: M700D
n Panel  mount variant:

Instrument for Testing the Electrical Safety of Electrical Equipment per DINVDE 0701-0702
nL  arge, digital LCD panel nM  ains connection testing with nger

METRATESTER 5-F-E (M700T)

Scope of delivery:
nF  actory calibration certicate

contact and indicator lamp


nD  ifferential current measurement per

Test

Measuring Range

DINVDE 0701-0702 nA  ll measured values appear clearly at a large digital display nE  xceeded limit values are indicated optically and acoustically nD  imensions (W x H x D): 190 x 140 x 95mm, weight: approx. 1.3kg

Protective conductor resistance 0...19.99 Insulation resistance 0...19.99M Equivalent leakage current 0...19.99mA~ Absence of voltage 0...1.999mA~ Differential current 0.01...19.99mA~ Line voltage 207V...253V~ Load current 0...16.00A~

METRATESTERI5+3P

Article: M700K

Test Case with M700D for Testing Devices in Accordance with DIN VDE 0701-0702, can also be used as a Workshop Test Panel per DINVDE0104. For testing the electrical safety of single and 3-phase electrical equipment in accordance with the regulations: The test case complies with guidelines for equipment required for electrical installation operations issued by the Federal Committee for Electrical Installations, ZVEH, WFE and electrical power utilities.
nM  ains connection: The

in phases L1, L2 and L3. Protective conductor measurement is performed correctly in accordance with DINVDE0104.
nC  onvenient testing: All

Scope of delivery:
nT  est case including test

instrument
nM  ains cable with earthing

Our Top Model

test case can be connected either to an earthing contact outlet with the two included power cables, or to a 16 A CEE mains outlet.
nT  est types: DIN VDE tests

safety and function tests are executed in a practical fashion by switching mains voltage or the individual phases to the device under test with selector switches.
nR  ugged case design:

contact plug and coupling socket nM  ains cable with CEE 16 A, 5-pole mains plug and coupling socket nO  ptional accessories beginning on Page 82

without mains operation: protective conductor resistance, insulation resistance, equivalent leakage current; DIN VDE tests with mains operation at all single and 3-phase devices: differential current, touch current. Function tests with measurement of current consumption and voltage

Test case consisting of an aluminum shell and a removable, lockable lid; ample space is provided for connection adapters and operating instructions.
nD  imensions:

Approx. 380 x 300 x 220mm, weight: approx. 8kg

Ma

in de

Germ a
ny

GOSSEN METRAWATT

80

TEStERS: Electrical Safety of Devices

Table of Contents

MINITESTIBase MINITESTIPro
Article: see description MINITEST BASE (M712C) Test instrument for DIN VDE 0701-0702, for testing and measurement of repaired or modied devices by measuring: n Protective conductor resistance n Insulation resistance nP  rotective conductor current differential current method nT  ouch current direct measurement method nI ndication of limit value violations by means of color LEDs nT  he probe cable is protected by means of a fuse link. MINITEST PRO (M712D) Test instrument for DIN VDE 0701-0702, for testing and measuring repaired or modied devices. Same as MINITEST BASE plus: nM  easured values appear at a large digital display. nU  SB interface for report generation with data nM  INITEST software included on CD ROM nE  xtensive safety features nR  CCB in the plug on the mains cable

MINITESTI3P Master MINITESTIMaster


MINITEST 3P MASTER (M712X) Same as MINITEST MASTER plus:
nC  EE 16A test socket and mains outlet,

single and 3-phase


nC  EE 32A test socket and mains outlet,

single and 3-phase MINITEST MASTER (M712U) Same as MINITEST PRO plus:
nM  emory for 2000 tests with up to

MINITEST 3P MASTER

10 measured values each

Scope of delivery: MINITEST BASE n Test instrument n Probe cable Additional features for MINITEST PRO/ MASTER: n USB connector cable n CD ROM with software Additional features for MINITEST 3P MASTER: n Adapter: CEE 32 to Schuko n Adapter: CEE 32 to 16 x 3 n Adapter: CEE 32 to 16 x 1 n Adapter: CEE 32 to 32 x 1 Optional accessories beginning on  nP  C.doc-WORD/EXCEL analysis software beginning on Page 91 

MINITEST BASE
in de

MINITEST PRO

MINITEST MASTER

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: Test Cases, Workshop Test Panels

81

SECUTest|3PL

Article: M704B
n Function test with power analysis

Test Case for Tests per BGV A3/GUV A2 at Single and 3-Phase Devices and Extension Cables per DIN VDE 0701-0702 The test instrument is used for fast, safe periodic testing of electrical devices. Measurements per DIN VDE 0701-0702: nP  rotective conductor resistance nP  rotective conductor current nT  ouch current Measuring methods:
nD  irect measurement, equivalent leakage

for single phase DUTs: The following are measured or calculated: nL  ine voltage /differential current nC  urrent consumption /electrical energy nA  ctive and apparent power/power factor nO  n-time Report Generating Functions All of the values required for approval reports or device logbooks for electrical equipment (e.g. per ZVEH) can be measured. All measurement data can be documented and archived thanks to the measurement and test report which can be printed from, or stored to a PC.

Scope of delivery: nP  robe cable with test probeand plug-on alligator clip nA  dapter cable for connection to 16A, 3-phase systems/16A lighting networks (Schuko) nT  est report  ptional accessories: beginning on Page O 82 PC analysis software: PC.doc-WORD/ EXCEL beginning on Page 91

current, differential current Testing the electrical safety of extension cables nP  rotective conductor resistance n Insulation  resistance nC  ontinuity, short-circuiting, polarity reversal

Applications for all SECUTEST Instruments

SECUTEST|21F

Article: M601A

SECUTEST|WP

Article: M704C Schematic diagrams which illustrate proper connection of devices under test to the SECUTEST WP can be displayed as well. Depending upon the device under test and usage, the following must be tested in accordance with these regulations: nP  rotective conductor resistance n Insulation resistance

Workshop Test Panel for Testing Devices in Accordance with DIN VDE 0701-0702 The SECUTEST 21F test panel has been designed for the setup of test stations at shops specialized in electrical work. Its used for measurement and testing of electrical devices after repair or modication, as well as for periodic testing, in accordance with DIN VDE 0701-0702. The test panel is designed for wall mounting. Its equipped with a mains switch with undervoltage trigger and lock. Load currents of up to 25 A and line voltages of up to 500 V can be measured. Compliance with DIN VDE 0104 also assures awless protective conductor measurements.
n Dimensions: 532 x 792 x 179mm n Weight: approx. 24kg

In accordance with the guidelines for workshop equipment for electrical installation operations issued by the ZVEH / VDEW Optional accessories: nV  L2E test adapter: testing of protective conductor and insulation resistance at devices and extension cables beginning on Page 84

The workshop test panel for periodic testing is intended for measuring and testing single and 3-phase electrical devices and extension cables. The test panel is mounted to the wall and connected to the mains by means of a permanently laid cable and pre-fusing with 3 x 32 A. Performance of measurements and tests is quick and easy. Integrated online instructions inform the user regarding all required connections, necessary work steps, operator errors, measurement results and more in all measuring modes. Information and test results appear at the dot matrix LCD in plain text. Online help can be queried and displayed at the LCD for all measuring and test functions, and for almost all settings.

Ma

in de

Germ a
ny

GOSSEN METRAWATT

82

TEStERS: Accessories

Table of Contents

SECUTEST|SI+/SECUTEST|PSI
Article: see table SECUTEST SI Memory or Input Module Test results from the test instruments are transmitted to the SI+ module directly via the interface. Test results are saved on-site as clear-cut, reliably documented measurement and test reports with date and time. Stored data can be transferred to a PC at a later point in time independent of the test instrument. SECUTEST PSI Printer-Memory and Input Module Test results are transmitted to the PSI module, which is integrated into the instruments lid, via a ribbon cable and are stored automatically. All measured values for 400 test reports can be stored to memory. Test results can be printed out on-site in the form of documented reports which can be furnished with date, time and text entered at the keypad.
nD  imensions: 240x81x40mm,

SECUSTORE

Article: Z745U

SECUTEST PSI consumable materials: n PS-10P=pack of 10 six meter recording charts n Z3210=10 ribbon cartridges Scope of delivery: SECUTEST SI n SI+ module SECUTEST PSI n PSI module n 2 recording charts /1 ribbon cartridge n Interface description

Memory Adapter for Use with SECUTEST... Testers


nD  ata storage: measured values for approx.

1000 test reports. The ash memory module allows for battery-independent data storage.
nY  -plug: simultaneous connection of a barcode/

RFID scanner or a keyboard adapter


n Compatible: SECUTEST S2N+ or S2N+10 and

SECUTEST SIII+ or SECULIFE ST

weight: approx. 0.8kg


nB  atteries: 4ea.1.5V IEC LR 6 (AA)

RS 232 USB Converter


Article: Z501L Type SECUTEST SI+ SECUTEST PSI PS-10P Z3210 Article M702G GTM5016000R0001 GTZ3229000R0001 GTZ3210000R0001 Interface Converter The interface converter is used to connect test instruments and multimeters with appropriate adapters including an RS 232 port to PCs which are equipped with USB ports only.

Overview

Tester Accessories
METRATESTER 5+3P METRATESTER 5+ MINITEST SECUTEST

3P Master

Type Master BASE PRO

S2N+10

S2N+W

S2N+

SIII+

SII+

General Accessories

SECUTEST SI+ SECUTEST PSI RS 232 USB converter SECULOAD CEE Adapter SECUSTORE
in de

n n n n n n

n n n n n n

n n n n n n

n n n n n n

n n n n n n

Ma

Germ a
ny

GOSSEN METRAWATT

3PL
n n

Table of Contents

TEStERS: Accessory Adapters

83

AT3-III-E

Article: Z745S
nA  utomatic adaptation to the program

Adapter for Active and Passive Testing of 3-Phase Current Consumers and Extension Cables in Combination with Safety Testers nT  esting of single and 3-phase consumers, and extension cables in combination with external test instruments nA  dditional protection during testing of defective devices with integrated residual current monitoring and shutdown nF  unction test for automatic shutdown by pressing a self-test button nP  revention of short-circuits and blown mains fuses during testing thanks to pre-testing stage

selected at the test instrument with transfer of measured values nI n combination with SECUTEST: testing of protective conductor resistance, insulation resistance, equivalent leakage current, dielectric strength, differential current, touch current nD  imensions: 405x300x220mm (with lid), weight: approx. 6.7kg

AT3-IIS/AT3-IIS32

Article Equipment: 5-pole CEE 32 A (max. 20 A) and CEE 16 A Dimensions*: 290x120x105mm, weight: 2.4kg n AT3-IIS32  : Article: Z745X Equipment: 5-pole CEE 32 A (max. 40 A) and Test types: CEE 16 A, DIN VDE tests with mains operation single-phase earthing (active) nD  ifferential current, touch current contact outlet DIN VDE tests without mains operation Dimensions*: (passive) 285x220x128mm, nP  rotective conductor resistance, Weight: 4.15kg AT3-IIS insulation resistance, equivalent *Dimensions (LxWxH) without leakage current cables and grommets It allows for fully automated or manual testing in accordance with the menu-driven test sequences included with the test instruments, with transmission of test results to, and analysis at, SECUTEST test instruments.
nA  T3-IIS: Article: Z745T

AT3-IIS32

Adapter for Active and Passive Testing of 3-Phase Current Consumers in Combination with SECUTEST Safety Testers The safety tester is used in combination with SECUTEST test instruments for testing 3-phase devices after repair, as well as for periodic testing (DIN VDE 0701-0702).

AT16-DI/AT32-DI

Article: Z750A/Z750B The following tests can be performed on devices with CEE plugs with the help of the adapter:
nT  esting of protective conductor continuity n Insulation test n Equivalent leakage current measurement nD  ifferential current measurement,

16 or 32A 3-Phase Current Adapter for Secustar FM, Seculife SB and Secutest S2N+W CEE adapter for quick, efficient testing of devices which are equipped with 5-pole 16A/6h or 32 A / 6h CEE plugs. The adapter is connected to a test instrument designed for testing portable devices in accordance with DIN VDE 0701-0702 or DIN VDE 0750/IEC 601, which is only equipped with an earthing contact outlet for connecting the device under test, and is capable of directly measuring protective conductor current.

L1-L2-L3-N
n Function test

Ma

in de

Germ a
ny

GOSSEN METRAWATT

84

TEStERS: Accessory Adapters

Table of Contents

VL2E

Article: Z745W

Adapter for Passive Testing of Protective Conductor and Insulation Resistance at Devices and Extension Cables nE  quivalent leakage current The test adapter is intended for the performance of measurements and tests at electrical devices and extension cables with Plus the following at extension cables:  asy function test for single and 3-phase CEE plug connectors in combination with test n E extension cables including testing for instruments in accordance with the following conductor continuity, short-circuiting and standards: testing after repairs or periodic polarity reversal (clockwise rotation) with testing per DIN VDE 0701-0702. rotary selector switch using an insulation The following quantities can be tested with resistance measurement the adapter in combination with test nW  hen performing tests, the adapters instruments which are intended for the connector cable is plugged into the test performance of the respective tests: socket at the test instrument. The test At electrical devices: instruments probe cable is additionally nP  rotective conductor resistance plugged into the connector socket at the nI nsulation resistance (measurement of L1, adapter when testing extension cables. L2, L3 and N short-circuited to PE)

CEE Adapter Z745A

Article: Z745A

Adapter for 3-Phase Consumers nS  afety outlets for 3-phase devices The Z745A CEE adapter allows for quick without permanently attached plug and efficient testing of devices equipped nP  rotective conductor continuity test and with a CEE plug in accordance with DINVDE insulation test for each phase, and 0701-0702. combined phases, with rotary switch
nC  EE attachment outlets:

16 A, 3-pole / 16 A, 5-pole, 32 A/5 pole

SECU-cal 10 Article: Z715A


Calibration Adapter for All Device Testing Instruments The following measured values can be calibrated with the adapter:
nI nsulation resistance nE  quivalent leakage current nD  ifferential current nT  ouch current nP  rotective conductor resistance

(max. test current: 1A)

SECULOAD
Article: Z745V Test Adapter for Testing Open-Circuit Voltage at Welding Units per EN 60974-4 In combination with a multimeter, the test adapter is used for testing welding units in accordance with the EN 60974-4:2007 standard. This standard stipulates that peak values for open-circuit voltage may not exceed the limit values, regardless of the utilized settings.
Germ a
ny

www.gossenmetrawatt.

More information at:

com

Ma

in de

GOSSEN METRAWATT

Table of Contents

TEStERS: Accessory Adapters, Cables

85

EL1
Article: Z723A Adapter for Testing Single-Phase Extension Cables
nC  onnector cable to the test PRO-CH

instrument with handle / socket PRO-CH plug insert (GTZ3225000R0001): for plug inserts Plug insert for using the EL1 n Pro-Schuko plug insert adapter in Switzerland nP  lug insert for non-heating devices
nE  N60320 C14 to EN60320 C6

plug adapter (non-heating devices, 10A to 2.5A IBM plug)


nA  dditional country-specic

inserts available as well. Not usable for high-voltage test!

EL1

KS13

Article: GTY3624065P01

Cable Set for Connecting Test Instruments to the Mains Cable set for connecting test instruments to the mains without earthing contact sockets, and for connecting DUTs consisting of:
nC  oupling socket with 3 permanently n3  measurement cables, 3 plug-on

pick-up clips
n2  plug-on test probes

connected cables

SK2/SK5

Article: see description

Probe Cable for Protective Conductor Measurement SK2  (Z745D): Probe cable with test probe and 2m probe cable (not coiled), suitable for high-voltage testing SK2W (Z745N): Probe cable with test probe and 2m probe cable (coiled), suitable for high-voltage testing SK5  (Z745O): 5 meter probe cable for protective conductor measurement SK5  (Z745K): 5 meter probe cable for protective conductor measurement (cable plus software)
nA  utomatic recognition of changing

measuring points as software upgrade


nG  o/No-Go indication display

Ma

in de

Germ a
ny

GOSSEN METRAWATT

86

TEStERS: Accessory Sensors

Table of Contents

Current Clamp Sensor


n1  mA...15A AC, 1mV/mA n1  mA...150A AC, 1mV/A

Article: Z219C
WZ12C

Current clamp sensor: 1mA...15 / ... 150A AC, switchable

Scope of delivery:
nC  urrent clamp sensor including permanently attached safety cable with connector plug

Measuring Range

CAT at V Diameter

Conductor

Transformation Ratio 1mV/mA/ 1mV/A

Frequency Intrinsic Accuracy Range (% rdg. + mA) 45...65... 500Hz 3%+0.15mA/ 2% + 0.1A

1mA...15AAC/ IIIat300 15mm dia. 1A...150AAC

Brush Probe Article: Z745G


The brush probe is suitable for contacting exposed conductive parts which rotate or vibrate etc. during operation. The brush is plugged onto the test probe.
nL  eakage current measurement (touch current) nP  rotective conductor resistance measurement

PA4

Article: Z745L

Patient Connector Cable Adapter cable for SECUTEST, SECULIFE ST for adapting the 2 mm connector sockets at the SECUTEST / SECULIFE ST to 4 mm sockets and plugs, 1.5m long with 12 cables, each with 4mm plug

Temperature Sensor Z3409

Article: GTZ3409000R0001

Standard PT 100 Temperature Sensor for Surface and Immersion Measurements Technical Data Sensor element Length of sensor element / sensor Temperature range, C Accuracy per DIN EN 60751/IEC 751 Intrinsic accuracy at 0 C/600C Transient recovery, T90 water/air Lead/insulation Pt100 130 / 1000mm -40 ... + 600 Class A 0.15K 5s/30s Strands: 2 ea. 0.35 sq. mm / PVC

Z701C

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

TEStERS: Accessory Pouches, Cases

87

Pouches, Cases
F2000 (Z700D): Universal Carrying Pouch nD  imensions: 380 x 310 x 200mm F2020 (Z700F): Large Universal Carrying Pouch nD  imensions: 430 x 310 x 300mm K2010 (Z504L): Aluminum Case nD  imensions: 645 x 535 x 160mm Z740B (Z740B): Hard Case for Testers and Accessories nD  imensions: 394 x 294 x 106mm BAGSTAR (Z700E): Ever-Ready Case

K2010

BAGSTAR F2000

Overview Tester Accessories


METRATESTER 5+ METRATESTER 5+3P MINITEST SECUTEST SEcuStaR FM+

General Accessories AT3-IIIE AT3-IIS AT3-IIS32 AT16-DI AT32-DI SECU-cal 10 Temperature / humidity sensor VL2E EL1 KS13 SECULOAD CEE adapter SK2 SK5 Current clamp sensors Brush probe PA4 Temperature sensor Carrying pouches F2000 F2020 K2010 Z740B BAGSTAR

n n n n n n n

n n n n n n n

n n n n n n n

n n n n n

n n n n n n

n n n n n

n n n n n n n n n n n n n n n n n n

n n n n n n n n n n n n n n n n n

n n n n n n n n n n n n n n n n

n n n n n n n n n n n n n n n n

n n n n n n n

n n n n n n n n n n n n n n

n n n n n n n n n n n n n n

com www.gossenmetrawatt.
Ma

More information at:

in de

Germ a
ny

GOSSEN METRAWATT

SEcuLIFE SR
n n n n n n n n n n n n n n

SIII+ SECULIFE ST

SEcuLIFE ST

3P MaStER

Type MaStER BASE PRO

S2N+10

S2N+W

S2N+

3PL

88

TEStERS: Identification Accessories

Table of Contents

SCANBASE/SCANWrite|RFID
Article: see table RFID reader/writer, for test instruments with USB or RS 232 port The RFID identication system is used to mark and identify tools and equipment. ID numbers can be written to RFID tags via a PC with the SCANWRITE. SCANWRITE, as well as other SCANBASE RFID reading devices, read out the code and forward it to our test instruments, in order to be able to allocate measured values and test results to the device under test in an unequivocal fashion. Type RFID reader/scanner, USB, 125kHz RFID reader/writer, USB, 13.56MHz RFID reader/writer, RS 232 Article Frequency Standard Z751D Z751E Z751G 125 kHz 13.56 MHz 13.56 MHz USB Connection

Barcode Reader, Scanner


Article: Z720A/Z751A/GTZ3261000R0001 Barcode Scanner Z720A with Laser for Test Instruments with RS 232 Port For identifying devices and system components. Devices and system components can be logged by our test instruments, and acquired measured values can be allocated to them with the scanner. See our barcode and label printers for water-insoluble labels as well. nS  canning of barcodes from considerable distances nV  ariable barcode lengths nI mproved reading accuracy nT  he barcode scanner is congured for use with the following barcodes: EAN13, CODE 39 and CODE 128 (other codes upon request). Barcode Reader Z502F same as Z720A but with coil cable Barcode Reader Z751A with Laser for Test Instruments with RS 232 Port For identifying devices and system components. Devices and system components can be logged by our test instruments, and acquired measured values can be allocated to them with the scanner. B3261 Barcode Scanner GTZ3261000R0001 with RS232 port for direct connection to SECUTEST PSI and PROFITEST PSI-BC nT  rouble-free scanning of all common barcode types nI nsertion of decoded characters to any desired cursor position B3261

ISO 15693 USB ISO 15693 RS 232

Z751D, E and G RFID readers are preprogrammed to read the Accessories:  following RFID tags: Type Article Frequency Standard 13.56 MHz 13.56 MHz 13.56 MHz 125 kHz ISO 15693 ISO 15693 ISO 15693 Type 22mm wide self-adhesive 30mm with 3mm hole Pigeon ring, 10mm 20mm Qty. 500 500 250 100 RFID tag, ISO15693, Z751R 24x18mm RFID tag, ISO15693, Z751S 30mm/3mm RFID tag, ISO15693, Z751T pigeon ring RFID tag (125kHz), Z751U shape as requested

Overview

Tester Accessories
SECUTEST

Type

Barcode Printer

Article: Z721D

Barcode and Label Printer for Connection to a PC, Including Software


nF  or identifying equipment with barcode labels nP  rints smudge-proof, scratch resistant labels in all common sizes nI deal in combination with the following barcode scanners: B3261, Z720A, Z751A n MS Windows software

SCANBASE/SCANWRITER|RFID Z751D Z751E Z751G n n n n n n n n n n n

Label set nZ  722D:  quantity x width: 3 ea. 24mm, 1 ea. 18mm, 1 ea. 9mm, 8m long n Z722E:  quantity x width: 5 ea. 18mm, 8m long Scope of delivery: barcode printer /label set
in de

Barcode readers / scanners Z720A Z502F Z751A B3261 n n n n n n n n n n n n n n n n n n n n n n n n n n n n

Ma

Germ a
ny

GOSSEN METRAWATT

BASE PRO MaStER 3P MaStER METRATESTER 5+ METRATESTER 5+3P SII+ SIII+ S2N+ S2N+10 S2N+W 3PL SEcuStaR FM PROFITEST MASTER

MINITEST

Table of Contents

SOFtWARETEStERS TEStERS

89

SOFTWAREElectrical Equipment
Data transfer, display, management and documentation our software does it all. Standards and regulations apply to all electrical systems and equipment. Time required for well-organized safety tests is minimized through the use of ultramodern test software. GOSSEN METRAWATT can provide you with a complete spectrum of software: beginning with a free report generating program right on up to comprehensive patManager for commercial, infrastructural and technical administration of properties, buildings, building technology and systems.

GOSSEN METRAWATT

90

SOFtWARE: Testers

Table of Contents

Overview

Instruments
SECUTEST Master Series SECUSTAR MINITEST METRISO G1000+ SECUSTAR FM+ METRA Machine 439/5.4 n n Machine 204/2.5 n n

SECUSTORE

3P MASTER

PSI, SI, SI+

METRISO C

Type

SECULIFE ST

SECULIFE SB

Software ETC PC.doc-Word/Excel PC.doc-Access pat Manager * With SECUTEST SI+ n n n* n* n* n* n n* n n n n n n n n n n n n n n n n n n n n n n n n n n* n n n n n n n n n n n

n* n* n* n* n n*

ETC
Report Software for Following Testers: PROFITEST MASTER, MINITEST, SECULIFE SR, SECUTEST SI, METRISO G1000+ ETC offers a wide variety of support options for data acquisition and management, reports generating and the control of test sequences. PROFITEST MASTER
n The software acquires all important data for reports in accordance with DIN VDE 0100, part 600. n Test reports (ZVEH) can be generated automatically.

Distribution structures with electrical circuit and RCD data can be individually dened.
n Created structures can be saved to memory and loaded to the test instrument as required. n The test instrument and the PC can exchange data bidirectionally via USB. n Data can be exported to Excel, CSV and XML formats. n Multilingual user interface

MINITEST PRO/MASTER, SECULIFE SR and METRISO G1000+


n The software copies measured values from the test instruments. n Report data can be supplemented. n Limit values can be set. n Test reports can be saved as PDF les. n Data can be exported to Excel, CSV and XML formats. n Multilingual user interface

PRO

204

n n n

GEOHM C

MASTER

S2N+10

PSI-BC

SI-BC

S2N+

SIII+

SII+

3PL

Free Download

SecuStore memory adapter for the SECUTEST range and the SECULIFE ST The software copies test reports from the memory adapter and saves them automatically as PDF les.

Download from: www.gossenmetrawatt.com/english/ugruppe/softwarefortesters.htm


Ma
in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

SOFtWARE: Testers

91

PC.doc-WORD PC.doc-EXCEL PC.doc-ACCESS

Can be used with nd Wi ows as of 2000/XP

Report software as supplement to Microsoft Office Word and Excel. PC.doc-WORD/EXCEL inserts test results and data entered at the test instrument input module into report or list forms. These can then be supplemented and printed out with Word/Excel. System requirements: nW  ord 97, 2000, 7.0 if reports are generated with Word nE  xcel 2000 or higher if reports are generated with Excel nU  ser interface: D, GB, F, FI, PL nP  C with at least 500MHz and 256MB RAM n1  available serial or USB port and a USB RS232 adapter PC.doc-ACCESS: PC.doc-ACCESS is used for generating reports and managing test data as a supplement to Microsoft Access. System requirements:
nA  ccess 2000, 7.0 nE  xcel 2000 or higher

if reports are generated with Excel


nU  ser interface: D, GB nP  C with 486 CPU or higher and at least 8MB

RAM
n1  available serial or USB port

Type PC.doc WORD/EXCEL PC.doc ACCESS PC.doc-update

Article Z714A Z714B Z714C

Download from: www.gossenmetrawatt.com/english/ugruppe/softwarefortesters.htm


Ma
in de

Germ a
ny

GOSSEN METRAWATT

92

SOFtWARE: Testers

Table of Contents

pat Manager
DataBase and test report software for SECUTEST / SECULIFE ST and tHe (P)SI module
nE  asy, clear-cut archiving/substantiation of tested devices

within the company/departments


nC  reation of test history for each device nP  rintouts (paper or PDF le) of test reports,

inspection cards, stickers nA  utomatic scheduling and verication of the validity of tests n e-mail notication of past-due and upcoming tests nM  odern, user-friendly interface

Test our free trial version! *


* Limited to 5 devices

http://www.gossenmetrawatt.com/english/produkte/ patmanager.htm

Runs under Windows XP, Vista and 7

Generation of test reports in PDF format

Automatic data import from tester memory or (P)SI

Download Download from: from: www.gossenmetrawatt.com/english/ugruppe/softwarefortesters.htm www.gossenmetrawatt.com/english/ugruppe/softwarefortesters.htm


Ma
in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

SOFtWARE: Testers

93

Overview

Reports and Database Software


ETC PC.doc-Word/Excel Z714A
D, GB, F, FIN, PL (Excel section: D, GB)

pat Manager Z712A D, GB, PL, R Autonomous Always complete n n n n n n n

PC.doc-Access Z714B D, GB Requires MS Access or Access Runtime Always complete n n With Access query functions n Using Access functions n n n n
Error statistics, defects statistics

Article User interface User Interface Autonomous Layout Firmware update (tester software) Generation of test reports Generation of lists List generator Forms generator Management of objects/tests Document management / image viewer Database management / navigator / search functions Database management / automatic deadline follow-up Common functions as icons
Data saved back to tester if set up accordingly

Free Download

D, GB, NL, I, F, CZ n Always complete n n n n SECULIFE SR n

Requires MS Word/Excel Always complete n n


Error statistics, defects statistics

Remote control Hazard analysis XML / Excel / ASCII import and export Catalog function Cost management Network compatible Barcode generation Client options / outdoor function Inventory management / error message module / maintenance / re safety Statistics

Special features

Tree structure

Download from: www.gossenmetrawatt.com/english/ugruppe/softwarefortesters.htm


Ma
in de

Germ a
ny

GOSSEN METRAWATT

94

NOtES

Table of Contents

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

KONSTANTER LaBoratorY PoWer SUpplIes

95

LABORATORY POWER SUpplIEs


Laboratory power supplies from GMC-I Messtechnik, known as GOSSEN KONSTANTERs, combine modern circuit technology with a broad range of functions and absolute reliability. Our KONSTANTERs can be ideally incorporated into demanding applications in the eld of research and development, as well as into production and (continuous) test systems. Depending upon power, linear regulators and switching controllers are used with a high degree of efficiency. Due to their exceptionally short response times, type SLP, SSP and ultramodern SYSKON KONSTANTERs are especially well suited for generating complex test signals, or for superimposing low-frequency signals to the output via analog control inputs. Data storage provided by SSP and SYSKON models makes it possible to save UI time proles, and to run the respective sequences automatically. Depending upon the device, available interfaces include analog, RS 232, IEEE 488 (GPIB) or USB.
SHort Response TIMes ACCUrate / MeasUreD ValUes SettInGs HIGHlY RelIaBle EXtensIve SaFetY FUnCtIons InterFaCe VarIants Free OperatInG SoFtWare (FroM WeBsIte)

GOSSEN METRAWATT

96

ProGraMMaBle LaBoratorY PoWer SUpplIes: 1500Wto4500W

Table of Contents

Sensational Response Times Highly Precise Setting and Measured Values High Output power

SYSKONP Series

Article: see table

SYSKONP series KONSTANTERs (SYSTEM KONSTANTER, programable) are single output, computer controlled laboratory power supplies for demanding professional use in R&D, production and test systems.

Extensive power-factor control (PFC), Safety Functions these models deliver RVP , OTP , OVP, OCP

Equipped with active

1500, 3000 or 4500 W of power, depending upon Interfaces: device type, at up to 60 V AN IF, RS232, and max. 60, 120 or USB or GPIB 180A with characteristic UIP curve. Special Deactivatable switching controller n ctio Sink Fun technology and matching status controllers provide Free Operating Software for high dynamics and (from website) sensationally short response times of less e Programmabl than 2 ms. The setting Test Signal range for output voltage Generator

and output current can be restricted by specifying setting limits. The analog interface is equipped with two programmable trigger inputs and three signal outputs, which can be linked to various device functions for indication, or for controlling external devices and an auxiliary power output. Monitor outputs and control inputs for voltage and current setpoints are also available. Sensing leads allow for auto-sensing operation at the power consumer. Strict menu-driven operation simplies the use of highly diverse programming functions. The devices are transformed into freely programmable test-signal generators by means of an expanded sequence memory.
nA  uto-ranging output with 1500, 3000 or

nS  equence functions with sequence control

for creating voltage and current sequences


nC  omprehensive calibration report

Scope of delivery:
nS  YSKON KONSTANTER nM  ains power cable

(for SYSKON P1500 only)


nU  SB cable (90 angle) nI nstallation set for rack mounting nD  AkkS calibration certicate nC  D with drivers and operating software

(D, GB), plus data sheet


nO  perating instructions (printed)

Optional accessories:
nI EEE 488 interface n3  -phase mains cable for

4500 W
nV  ery short response times (rise and fall

SYSKON P3000 and P4500 Software:


nG  M-SYSKON-SFP operating software

times)
nE  xcellent dynamic control parameters nO  utput: voltage, current and power

(free download
nD  rivers for LabVIEW, LabWindows/CVI,

regulated nM  inimal residual ripple nM  ains input with power-factor control nH  ighly efficient, low power loss nO  utput on/off function nS  ink mode operation (can be deactivated) nL  ockable controls nM  aster-slave operation for parallel and series connection nO  vervoltage, overcurrent and overtemperature protection

Agilent VEE
Starter Motor Curve Test Signal

SYSKON Test Sequence nS  etup memory: 15 memory locations for complete congurations Sequence 1 Sequence 2 Sequence X

n Sequence memory:

1700 locations for sequence functions


nS  equence stringing Sequence 1 Sequence R2 Sequence R3

n Invocation of sub-sequences from primary sequences Sequence 1

Sequence S2

Sequence S3

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents ProGraMMaBle LaBoratorY PoWer SUpplIes: 1500Wto4500W

97

Outputs Working Range


Characteristic Power Curve

com www.gossenmetrawatt.
SYSKONP1500

More information at:

1500W Output Power

Characteristic Power Curve

SYSKONP3000

3000W Output Power

Characteristic Power Curve

SYSKONP4500

4500W Output Power

Type SYSKON P1500 (1500W) SYSKON P3000 (3000W) SYSKON P4500 (4500W) IEEE 488 interface 3-phase mains cable, 3m

Power Pnom [W] 1500 3000 4500

Voltage USet [V] 0 ... 60 0 ... 60 0 ... 60

Current ISet [A] 0 ... 60 0 ... 120 0 ... 180

Dimensions (W x H x D in mm) Benchtop Instrument 447 x 102 x 541 447 x 191 x 541 447 x 191 x 541 19" Rack 2 standard height units x 501 4 standard height units x 501 4 standard height units x 501

Weight (approx. Article kg) 10 16 20 K353A K363A K364A K384A K991B


in de

Ma

Germ a
ny

GOSSEN METRAWATT

98

ProGraMMaBle LaBoratorY PoWer SUpplIes: 120Wto320W

Table of Contents

Extremely Short Response Times Programmable Test Signal Generator

SSP 32N-KONSTANTER 120 to 320

Article:see table

SSP32N KONSTANTER 120, 240 and 320 devices (single output system power supplies) are single output computer controlled laboratory power supplies for universal use in R&D, production and testing.

nM  inimal residual ripple nO  utput on/off function nM  aster-slave operation for parallel and

Scope of delivery:
n SSP-KONSTANTER n Mains power cable with earthing contact

series connection
n Bridging of two instruments for the

plug
n Test report n Operating instructions

generation of bipolar voltages


nO  vervoltage, overcurrent, polarity reversal

BET circuit technology (bidirectional energy transformation) allows for rise and decay times of less than 1 ms almost entirely independent of load (< 4 ms with 80V device). The analog interface includes monitor, auxiliary power and programmable signal outputs, as well as setpoint and programmable trigger inputs. This also makes it possible to adjust internal output impedance for the simulation of weak batteries. nA  uto-ranging output with 120 W, 240 W or 320 W nI ncreased output power for brief intermittent periods nM  inimal power loss n Constant voltage and constant current operating modes nS  ink mode (static/dynamic) nS  equence functions with sequence control for creating voltage and current sequences nE  xtremely short response times thanks to BET technology

and overtemperature protection


nL  ockable controls nC  alibrating procedure for menu-driven

balancing
nC  omprehensive test report nF  loating output terminals at front and rear

Optional accessories: nI EEE 488 interface n IEEE 488 and RS 232 cable n Installation sets for rack mounting n Mains jumper cable Software: (beginning on Page 103) n Drivers for LabVIEW, LabWindows/CVI, Agilent VEE n GM SSP-SFP operating software

panels
nC  an be electrically and mechanically

combined into multi-output devices


nA  nalog interface (standard equipment) nR  S 232 port (standard equipment) nI EEE 488 interface (optional) 120W/240W

320W

n Sequence memory: 245 locations for sequence functions Sequence 1 Sequence 2

Sequence X

Type

Power Pmax Pnom [W] [W] 120 120 120 240 240 240 320 200 240 240 320 360 360 430

Voltage Current Dimensions (WxHxD in mm) Weight Unom Inom Benchtop 19" Rack (approx. Article kg) [V] [A] Instrument 0 ... 20 0 ... 40 0 ... 80 0 ... 20 0 ... 40 0 ... 80 0 ... 32 0 ... 10 0 ... 6 0 ... 3 0 ... 20 0 ... 12 0 ... 6 0 ... 18 221.5x 102.0x 397.5 221.5x 102.0x 397.5 221.5x 102.0x 397.5 19"x2 standard height unitsx400 19"x2 standard height unitsx400 19"x2 standard height unitsx400 2.9 K320A K321A K322A K330A K331A K332A K334A K380A

120W
Outputs Working Range

Unom

Short-Term Working Range (max.90s)

Pmax Pnom

240W

2.9

320W
Inom

3.4 0.1

IEEE 488 interface

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

ProGraMMaBle LaBoratorY PoWer SUpplIes: 500Wto3000W

99

SSP 62N/64N-KONSTANTER 500 to 3000Article:see table


SSP KONSTANTER 500, 1000, 2000 and 3000 devices (single output system power supplies) are single output computer controlled laboratory power supplies for universal use in R&D, production and testing.

Special circuitry allows for jumping from 0 V to nominal voltage (0V UNom) and from UNom 0V under nominal load conditions within very short response times of less than 10 ms. The analog interface includes monitor and auxiliary power outputs, as well as programmable trigger and setpoint inputs.
nA  uto-ranging output with 500W, 1000W,

nL  ockable controls nS  equence functions: sequence control

2000W or 3000W
nV  ery short response times thanks to

special circuit concept


nE  xcellent dynamic control parameters nM  inimal power loss nO  utput: voltage and current regulated nM  inimal residual ripple nR  emote sensing nL  ockable controls nS  ink mode, dynamic nO  utput on/off function SSP 62N Models 500W and 1000W

for creating voltage and current sequences nM  aster-slave operation for parallel and series connection nO  vervoltage, overcurrent, polarity reversal and overtemperature protection nR  ear panel connections: Output: bus bars with holes for M8 screws and 4 mm diameter Analog Interface Mains input, 62N: inlet plug with protective contact L + N + PE Mains input, 64N: screw-terminal block 3 L + N + PE

Scope of delivery:
nS  SP-KONSTANTER nM  ains power cable(SSP 62N) nI nstallation set for rack mounting nO  perating instructions

SSP 64N Models 2000W and 3000W

nI EEE 488+RS 232 interface nR  S 232 interface n3  -phase cable for SSP 64N models with

Optional accessories:

16 A 5-pin CEE plug Software: (beginning on Page 103)


nS  SP Soft Front-Panel nD  rivers for LabVIEW, LabWindows/CVI,

n Sequence memory: 245 locations for sequence functions Sequence 1

Agilent VEE

Sequence 2

Sequence X

Power Type Pnom [W]

Voltage Current USet [V] ISet [A] 0 ... 25 0 ... 12.5 0 ... 50 0 ... 25 0 ... 100 0 ... 50 0 ... 150 0 ... 75

Dimensions (W x H x D in mm) Benchtop Instrument 19" Rack

Weight (approx. Article kg) 12 13 22 28 K344A K341A K345A K343A K352A K351A K362A K361A K382A K383A K991B

500 0 ... 52 500 0 ... 80 1000 0 ... 52 1000W 1000 0 ... 80 2000 0 ... 52 2000W 2000 0 ... 80 3000 0 ... 52 3000W 3000 0 ... 80 IEEE 488+RS 232 interface RS 232 interface 3-phase mains cable, 3 m 500W
*)

449 x 101 x 500 2 s. h. u. x 500 *) 2 s. h. u. x 500 449 x 101 x 500  449 x 190 x 500 4 s. h. u. x 500 449 x 190 x 500 4 s. h. u. x 500

Outputs Working Range

Unom Pnom

Inom
Germ a
ny

s. h. u. = standard height units

GOSSEN METRAWATT

Ma

in de

100

of Contents ProGraMMaBle LaBoratorY PoWer SUpplIes: 24W/49W/120W, Up to 8Table Channels

MSP 64D-KONSTANTER Article: see table


The MSP-KONSTANTER (multi-output system power supply) offers extensive exibility, ease of operation and economy for universal use in R&D, production and testing. The MSP KONSTANTER is a modular, manually operated and computer 8 to Up Output Channels controlled DC power supply. The basic unit with integrated Individualized auxiliary power supply Configuration and cooling fan is equipped with IEEE 488 and RS 232 interfaces, and accepts up to four single or 2-channel plug-in power supply modules, and one control module. The control module allows for manual operation of all 8 channels. The plug-in modules function in accordance with the linear controller principle, and the outputs have a 2 quadrant operating range (source and sink). Source and sink functions are possible for constant voltage as well as constant current operation. Parallel or series connection, as well as bridging for the generation of bipolar voltages, is also possible.
2-Quadrant Working Range (source&sink)
nE  asy, exible device conguration nS  witchable mains input:

Included with Basic Instrument:


n MSP 64D basic instrument n Mains power cable with earthing contact

230V AC/115V AC
nU  p to 8 independent, electrically isolated

plug
n5  blanking plates for unused module slots nI nstallation set for rack mounting nO  perating instructions

outputs nA  ll outputs can be used as electronic loads as well nS  hort response times and minimal residual ripple nO  utput on/off function nO  utputs can be activated and deactivated individually or in groups nM  easuring function for voltage, current and power with threshold memory nH  elp texts available in various languages by simply pressing a key nI EEE 488 and RS 232 interface Standard

Plug-in power supply modules and control module are not included with the basic instrument. Optional accessories (Page 105):
n IEEE 488 and RS 232 bus cable

Software (Page 103): nF  ree driver software for LabVIEW, LabWindows/CVI, Agilent VEE (download from website)

Outputs Working Range


U

Sink < 1.5 V Inom 0

Source I + Inom

Dimensions Weight (W x H x D in mm) Type (approx. Article Benchtop 19" Rack kg) Instrument 448 x 177 x 4 s. h. u. MSP 64 N 42 P basic device 6.6 K370A 390 x 440 MSP control module 0.7 K371A 2x24 2x0...8 2x0...3 3.3 K372A 2x24 2x0...16 2x0...1.5 3.3 K372B ES31 2x24 2x0...40 2x0...0.6 3.3 K372C 1x49 0 ... 7 0 ... 7 3.3 K372D 1x120 0 ... 30 0 ... 4 6.8 K373A ES32 6.8 K373B 1x120 0 ... 80 0 ... 1.5 Power Pnom [W] Voltage USet [V] Current ISet [A]

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

ProGraMMaBle LaBoratorY PoWer SUpplIes: 90Wto108W

101

LSP 32K-KONSTANTER Article: see table


Series LSP 32K KONSTANTERs (laboratory and system power supply) are linear controlled power supplies for use in R&D, production, service and training applications. The devices are distinguished by outstanding ease of operation, excellent regulating accuracy and minimal residual ripple. nP  rocessor controlled Scope of delivery: nS  erial device interface nL  SP-KONSTANTER nO  utput can be switched on and off nM  ains power cable with earthing contact plug nV  oltage and current regulating nO  perating instructions nR  otary encoder for adjusting USET and ISET Optional accessories: (Page 105) nA  djustment is also possible with keys nI nterface adapter for USB, RS 232 nM  ultifunctional LCD panel Software: (Page 103) nM  emory for 10 device congurations n P  ower Management System nP  rotective devices nB  enchtop instrument, suitable for mounting to a 19" rack Type Power Pnom [W] 90 108 108 Voltage USet [V] 0...18 0...36 0...72 Current ISet [A] 0...5 0...3 0...1.5 Dimensions (W x H x D in mm) Benchtop 19" Rack Instrument 215 x 100 x 280
1

Outputs Working Range

Weight (approx. kg) 6.0

Article K110A K111A K112A

LSP 32K

/219"x2 standard height unitsx243 + 45mm

AnaloG ControlleD LaBoratorY PoWer SUpplIes: 120W to 320W SLP 32N-KONSTANTER 120 to 320
Article:see table

Series SLP 32N KONSTANTERs (single-output laboratory power supplies) are analog controlled, single output laboratory power supplies for universal use in R&D, production, training and service applications. SLP 32N KONSTANTERs are equipped with the same nominal output values and outstanding control characteristics as the SSP 32N series. However, in this case the output parameters are not set by means of processor controlled operating elements or via a PC interface, but rather in the traditional manner with ten-turn potentiometer. Measured values and setpoints for output voltage and current can viewed at two Type Power POut [W] 120W 240W 320W 120 120 120 240 240 240 320 Voltage USet [V] 0...20 0...40 0...80 0...20 0...40 0...80 0...32 Current ISet [A] 0...10 0...6 0...3 0...20 0...12 0...6 0...18 4-place digital displays. However, an analog interface for remote control and coupling purposes (also included with series SSP 32N instruments) is included here as well. Scope of delivery: n SLP-KONSTANTER n Mains power cable with earthing contact plug n Operating instructions Dimensions Weight (W x H x D in mm) (approx. Article Benchtop kg) 19" Rack Instrument K220A K221A K222A K230A K231A K232A K234A Optional accessories: (Page 105) nI EEE 488 interface n IEEE 488 and RS 232 cable n Installation sets for rack mounting n Mains jumper cable

Outputs Working Range

Unom

Short-Term Working Range (max.90s)

221.5x 102.0x 397.5

19"x2 standard height unitsx400

Pmax Pnominal

2.7

3.2

Inom
in de

Ma

Germ a
ny

GOSSEN METRAWATT

102

ProGraMMaBle EleCtronIC LoaDs: 150Wto400W

Table of Contents

Load KONSTANTERSSL 32EL Article: see table


SSL 32EL Load KONSTANTERs (single-channel system load) are programmable electronic loads with a maximum sink power of 150W or 300W. Theyre used for loading direct voltage sources with constant current, resistance or power in an adjustable fashion. Their range of applications includes testing power packs, batteries, PV modules, fuel cells etc.
n 3 operating modes: CC, CR and CP n Settings selected by means of rotary encoder and keypad n PC control via optional interface adapter n High resolution measurement of U, I and P nM  ultifunctional, illuminated LCD panel n Memory for 10 setting values with time regulated sequence

Load KONSTANTERSPL Article: see table


SPL Load KONSTANTERs (single-channel programmable load) are programmable electronic loads with a maximum sink power of 250W or 400W and outstanding dynamic control characteristics. Theyre used for loading direct voltage/current sources with constant current, resistance, voltage or power in an adjustable fashion. Their range of applications includes static and dynamic testing of power packs, batteries, PV modules, fuel cells etc.
n 4 operating modes: CC, CV, CR and CP n 17 bit adjusting resolution and 24 bit measuring resolution n Adjustable rate of current rise: 0.1mA to 4A per s n High-speed sequencing and transients function nS  hort-circuit and battery discharging function nM  emory for 7 sequences with up to 50 steps each

control (at least 1 second per step)


nE  xtensive protective functions: OV, OC, OP, OT, RV nL  oad on/off switching function n Controls can be password protected

(at least 10s per step)


nL  ow load voltage: < 0.6V at max. current n Load on/off switching function n Multifunctional, illuminated LCD panel n Extensive protective functions: OV, OC, OP, OT, RV n PC control via RS232 port or optional IEEE488 interface with

Scope of delivery: nL  oad KONSTANTER n Mains power cable with earthing contact plug nO  perating instructions Optional accessories: (Page 105) Interface adapter for USB / RS 232 Software (Page 103):
n Eload Management System

SCPI commands or LabVIEW driver Scope of delivery: nL  oad KONSTANTER n Mains power cable with earthing contact plug nO  perating instructions Optional accessories: IEEE 488 interface Software (Page 103):
n LabVIEW device driver

Power Type SSL 32EL 150 SSL 32EL 300 SPL 250-30 SPL 400-40 IEEE 488 interface
in de

Voltage USet [V]


0.001...360.0 0.001...360.0

Current ISet [A]


0.001...30.00 0.001...30.00

Resistance RSet []
0.01...500.0 0.01...500.0 0.0200...2000 0.0200...2000

Dimensions (W x H x D in mm) Benchtop Instrument 215 x 100 x 280 226 x 110 x 414
1

PSet [W]
0.1...150.0 0.1...300.0

19" Rack /219"x2 s. h. u. x 243 +0 45mm /219"x2 s. h. u. x 350 +0 45mm

Weight (approx. Article kg) 5.0 5.8 0.1 K850A K851A K852A K853A K890A

0.001...250.00 0.001...80.000 0.0001...30.000 0.001...400.00 0.001...80.000 0.0001...40.000

Ma

Germ a
ny

GOSSEN METRAWATT

Table of Contents

SoFtWare For LaBoratorY PoWer SUpplIes anD EleCtronIC LoaDs


KONSTANTER Series SYSKON P
n n n n

103

Software

Free Download

SSP 32N
n n n n

SSP 62N/64N
n n n n

MSP 64D
n n n

LSP 32K
n

SSL 32EL
n

SPL
n n

Device driver for NI LabVIEW Device driver for NI LabWindows/CVI Device driver for NI Agilent VEE SYSKON Soft Front-Panel SSP Soft Front-Panel POWER Management System ELOAD Management System

Device Drivers for NI LabVIEW, NI LabWindows/CVI and Agilent VEE Device drivers for simple integration of our programmable laboratory power supplies and electronic loads into automated measuring and test systems which are controlled by the specified software packages are available for download from our website free of charge. SSP Soft Front-Panel PC User Interface for SSP-KONSTANTER All SSP KONSTANTER functions can be controlled and displayed at a PC with this Windows software. Additional devices can be individually operated by starting the SFP more than once.
n  For the RS 232 and the IEEE 488(GPIB) interface n  Runs under Windows 2000, XP, Vista and 7 n  Automatic search for SSP devices at all available interfaces n  Menu language: English Prerequisite: NI-VISA driver and additional NI-488.2 driver (National Instruments) must be installed for control via GPIB.

SYSKON Soft Front-Panel PC User Interface for SYSKON P Series This Windows software can be used to interactively control and display all SYSKON functions from a PC. Additional devices can be individually operated by starting the SFP more than once.
n  For USB, RS 232 and IEEE 488 (GPIB) interface n  Runs under Windows 2000, XP, Vista and 7 n  Automatic search for SSP devices at all available interfaces n  Menu language: English

Power Management System PC User Interface for LSP-KONSTANTER 32K Series 32K LSP Konstanter functions can be interactively controlled and displayed at a PC with this Windows software.
n  For USB and RS 232 interface n  Runs under Windows 2000, XP, Vista and 7 n  Menu language: English Prerequisite: K910A or K910B interface adapter (see Page 105)

Eload Management System PC User Interface for SSL 32EL Electronic Load Series SSL 32EL electronic load functions can be interactively controlled and displayed at a PC with this Windows software.
n  For USB and RS 232 interface n  Runs under Windows 2000, XP, Vista and 7 n  Menu language: English Prerequisite: K910A or K910B interface adapter (see Page 105)

Ma

GOSSEN METRAWATT

in de

Germ a
ny

104

LaBoratorY PoWer SUpplIes: Overview

Table of Contents

Overview Laboratory Power Supplies


Max. Power Type Article Duration <90s [W] [W] Programmable Laboratory Power Supplies LSP 32 K 18 R 5 LSP 32 K 36 R 3 LSP 32 K 72 R 1.5 K110A 90 0...18 0...36 0...72 0...5 0...3 0...1.5 0.1+20 0.1 + 20 0.1 + 20 0.2+20 0.2 + 20 0.2 + 20 <1 <1 <1 <5 <4 <3 u u u u u u n n n n n n Uset [V] Iset [A] Uset (% + mV) Iset (% + U I mA) [mVTRMS] [mATRMS] Sink Mode Analog RS 232 USB IEEE 488 Setting Range Setting Accuracy Residual Ripple Interfaces Query Measured Values Overvoltage Protection Auto-Ranging Output

K111A 108 K112A 108

SSP 32 N 20 RU 10 P SSP 32 N 40 RU 6 P SSP 32 N 80 RU 3 P SSP 32 N 20 RU 20 P SSP 32 N 40 RU 12 P SSP 32 N 80 RU 6 P SSP 32 N 32 RU 18 P SSP 62 N 52 RU 25 P

K320A 120 (200) K321A 120 (240) K322A 120 (240) K330A 240 (320) K331A 240 (360) K332A 240 (360) K334A 320 (430) K344A 500

0...20 0...40 0...80 0...20 0...40 0...80 0...32 0...52 0...80 0...52 0...80 0...52 0...80 0...52 0...80

0...10 0... 6 0... 3 0...20 0...12 0... 6 0...18 0... 25 0... 12.5 0... 50 0... 25 0...100 0... 50 0...150 0... 75

0.15 + 30 0.4 + 35 0.15 + 40 0.5 + 20 0.15 + 80 0.5 + 10 0.15 + 40 0.5 + 70 0.15 + 45 0.5 + 45 0.15 + 80 0.5 + 25 0.15 + 50 0.5 + 70 0.1 + 17 0.2+25 0.1 + 20 0.2+15 0.1 + 17 0.2+50 0.1 + 20 0.2+25 0.1 + 17 0.25 + 100 0.1 + 20 0.25 + 50 0.1 + 17 0.3 + 150 0.1 + 20 0.3+80

10 10 10 15 15 15 30 10 10 10 15 10 15 10 15

25 20 10 50 25 20 50 15 15 25 20 80 30 120 60

n n u Dyn. n n n n n n n u Dyn. n n n n n n n u Dyn. n n n n n n n u Dyn. n n n n n n n u Dyn. n n n n n n n u Dyn. n n n n n n n u Dyn. n n n n n n u u Dyn. n n n n n n u u Dyn. n n n n n n u u Dyn. n n n n n n u u Dyn. n n n n n n u u Dyn. n n n n n n u u Dyn. n n n n n n u u Dyn. n n n n n n u u Dyn. n n n n n

SSP 62 N 80 RU 12.5 P K341A 500 SSP 62 N 52 RU 50 P SSP 62 N 80 RU 25 P SSP 64 N 52 RU 100 P SSP 64 N 80 RU 50 P SSP 64 N 52 RU 150 P SSP 64 N 80 RU 75 P K345A 1000 K343A 1000 K352A 2000 K351A 2000 K362A 3000 K361A 3000

SYSKON P1500-60-60

K353A 1500

0...60 0...60 0...60

0... 60 0...120 0...180

0.05 + 30 0.05 + 90 0.07 + 48 0.10 + 135 0.10 + 48 0.15 + 180

6 10 15

50 70 100

n n n u Dyn. n n n n n n n n u Dyn. n n n n n n n n u Dyn. n n n n n

SYSKON P3000-60-120 K363A 3000 SYSKON P4500-60-180 K364A 4500 MSP Plug-In Modules ES 31 K 7 R 7 P ES 32 K 30 R 4 P ES 32 K 80 R 1.5 P ES 31 K 2x8 R 3 P ES 31 K 2x16 R 1.5 P ES 31 K 2x40 R 0.6 P K372D 49

0... 7 0...30 0...80 2x0...8

0...7 0...4

0.05 + 4 0.05 + 16

0.1 + 4 0.1 + 2 0.1 + 1 0.1 + 2 0.1 + 1

1 3 3 1 1 3

3 3 2 3 2 2

Via basic instrument

n n n n n n

n n n n n n n n n n n n

K373A 120 K373B 120 K372A 2x24 K372B 2x24 K372C 2x24

0...1.5 0.05 + 40 2x0...3 0.05 + 4

2x0...16 2x0...1.5 0.05 + 8

2x0...40 2x0...0.6 0.05 + 20 0.1 + 0.5

n Standard equipment u Optional


Ma
in de

Germ a
ny

GOSSEN METRAWATT

Sequence Control

Output On/Off

LaBoratorY PoWer SUpplIes anD EleCtronIC LoaDs: Overview and Accessories


Table of Contents

105

Overview Continued Laboratory Power Supplies


Max. Power Type Article Duration <90s [W] [W] SLP 32 N 20 R 10 SLP 32 N 40 R 6 SLP 32 N 80 R 3 SLP 32 N 20 R 20 SLP 32 N 40 R 12 SLP 32 N 80 R 6 SLP 32 N 32 R 18 K220A K221A K222A K230A K231A K232A K234A 120 120 120 240 240 240 320 (200) (240) (240) (320) (360) (360) (430) Uset (% + mV) 20 15 15 30 23 23 40 Iset (% + mA) 28 15 15 38 38 20 50 Setting Range Total System Error SELV (safety extra-low voltage)

Residual Ripple

Auto-Ranging Output

Front Panel Output

Uset [V] 0...20 0...40 0...80 0...20 0...40 0...80 0...32

Iset [A] 0...10 0... 6 0... 3 0...20 0...12 0... 6 0...18

U I [mVTRMS] [mATRMS] 10 10 10 15 15 15 30 25 20 10 50 25 20 50

Analog Controlled Laboratory Power Supplies n n Dyn. n n Dyn. n Dyn. n n Dyn. n n Dyn. n n Dyn. n n Dyn. n n n n n n n n n n n n n n n n n n n n n n n n n n n n Mains Input 50 ... 60Hz

Power
Type Article

Voltage USet [V]

Current ISet [A]

Resistance
RS 232

Interfaces

PSet [W]

RSet []

IEEE 488

USB

[VAC]

Programmable Electronic Loads SSL 32 EL 150 R 30 SSL 32 EL 300 R 30 SPL 25030 SPL 40040 K850A K851A K852A K853A 0.1...150.0 0.1...300.0 0.001...250.00 0.001...400.00 0.001...360.0 0.001...360.0 0.001...80.000 0.001...80.000 0.001...30.00 0.001...30.00 0.0001...30.000 0.0001...40.000 0.01...500.0 0.01...500.0 0.0200...2000 0.0200...2000 u u n n u u u u 115/230 115/230 115/230 115/230

KONSTANTER Accessories
Mounting Kit, 2x32N Mains Jumper Cable RS 232 Interface Cable Interface Adapter

Type K990A K990B K991A K991B K931A

Designation Mounting kit 1x32N Mounting kit 2x32N Mains jumper cable, 0.4m 3-phase mains cable, 3m, with 5-pole 16 A CEE plug IEEE/IEEE bus cable, 2m

Usable for SSP 32N, SLP 32N SSP 32N, SLP 32N SSP 32N SSP 64N, SYSKON P3000/P4500 SSP 32N, SSP 62N/64N, MSP 64D, SYSKON SSP 32N, SSP 62N/64N, MSP 64D, SYSKON LSP 32K, SSL 32EL LSP 32K, SSL 32EL

Article K990A K990B K991A K991B K931A GTZ3241000 R0001 K910A K910B
in de

Z3241 RS 232 interface cable, 2m K910A Interface adapter, RS 232 / LSP, SSL K910B Interface adapter, USB / LSP, SSL

Ma

Germ a
ny

GOSSEN METRAWATT

Rear Panel Output

Surge protection

Analog Interface

Output On/Off

Sink Mode

106

PoWer SUpplIes: OEM Product Overview

Table of Contents

OEM Power Supplies Panel Mount Power Supplies


www.gossenmetrawatt.
OEM power supplies for special applications, or in accordance with customer specications. In addition to our standard power supply ranges (laboratory KONSTANTERs), we also fabricate power supplies for special applications, or in accordance with customer specications, for example:
nF  ixed voltage switched-mode power

More information at:

com

supplies in European plug-in module or cartridge format


n2  4 to 12V DC-DC voltage converters for

commercial vehicles
nC  ustomer-specic power supplies

The photos show examples of our OEM power supplies.

Ma

in de

Germ a
ny

GOSSEN METRAWATT

Table of Contents

Photometry

107

PHOTOMETRY
Reliable measurement results with dened error limits are guaranteed by luminance meters and luxmeters classied in accordance with DIN 5032-7 and DIN EN 13032-1. This ensures that quality inspections, orientation measurements and assessments conducted with these meters deliver accurate statements. Calibration certicates and recalibration at regular intervals are required for use in qualityrelevant applications and for assessments. The GOSSEN Light Lab offers these services, even for products from other manufacturers, and issues factory calibration certicates. The optical table used for this purpose is subject to strict test equipment monitoring, and is traced back to the PTB in Brunswick, Germany (German Federal Institute of Physics and Metrology). Aside from the PTB, our lab is the rst in Germany to be accredited for illuminance by DAkkS (German accreditation authority), and is thus authorized to issue internationally recognized DAkkS calibration certicates. This assures that acquired measured values comply with official regulations, and as a rule stand up to legal argumentation.

GOSSEN METRAWATT

108

Photometry: Illuminance Meters

Table of Contents

MAVOLUX 5032B/C USB

Article: M503N/M502N

This high precision luxmeter is available in class B and class C versions in accordance with DIN 5032-7, appendix B of IEC 13032-1 and CIE 69. Both variants are equipped with V() adaptation as well as cosine correction, and reliably measure the illuminance of daylight and articial sources of light. Even in the case of very bright sunlight or illumination from headlights, no accessories are required. Due to its outstanding accuracy in accordance with class B, the MAVOLUX 5032 B USB is used primarily for certication and inspection applications. An additional measuring range with high initial sensitivity of 0.01lx makes it possible to measure extremely small illumination intensities. This even allows for reliable measurement of emergency lighting. After pressing the HOLD key, the measured value is saved to memory and display illumination included with this version is activated, making it possible to read the display in dark environments. Matching to the spectral brightness sensitivity of the human eye V() is highly precise with minimal deviation of just f1' < 3%. With accuracy according to class C, the MAVOLUX 5032 C USB is used primarily for general applications as an industrial measuring instrument. The smallest of four measuring ranges begins with an initial sensitivity of 0.1lx. V() matching deviation, which amounts to f1' < 7.5%, is considerably better than the permissible error limit for class C. Both variants can be used as unclassied luminance meters with the help of an optional luminance attachment with an acceptance angle of 15. Luminance is measured in candelas per square meter (cd/m) or foot-lamberts (fL), and denes the perceived brightness of a luminous or reecting surface. At GOSSEN, great emphasis is placed upon reliability by means of calibration. For purposes of substantiation, a factory calibration certicate or a DAkkS calibration certicate can be ordered along with either variant. Depending on how the meter is used, we recommend a calibration interval of 12 to 24 months.

DIN 5032-7 classB/C

Optional Accessoires:
nA  rticle: M516G

Luminance attachment, acceptance angle of approx. 15


nA  rticle: M499G

M516G

Adapter disc for the prevention of light leakage from the side during contact measurement
M499G

Specications/Features:
nM  aximum precision Classied measurement of illuminance in

www.gossen-photo.de
nS  imple functions expansion Unclassied measurement of

More information:

lx or fc in accordance with class B or class C per DIN 5032-7, appendix B of IEC 13032-1 and CIE 69. nB  road measuring range High initial sensitivity and a resolution of 0.01lx or 0.001fc for the MAVOLUX 5032 B USB, right on up to large illuminance values of 199,900lx or 19,990fc. nV  () adaptation The spectral sensitivity of the silicon photodiode is color corrected and corresponds to the spectral brightness sensitivity of the human eye V(). The quality of this matching represents a signicant difference between the class B and class C variants. nC  osine correction The luminosity of a at measuring surface is proportional to the cosine of the incident angle of light. This relationship is taken into consideration by the receiver during evaluation.

luminance in cd/m2 or fL is made possible by the optional luminance attachment. An additional adapter disc prevents erroneous measurements due to light leakage at the side. nC  onvenient everyday use Simple operation, easy to read display, compact design, protection during transport in a high quality aluminum case. nN  on-volatile memory 100 measured values can be saved, retrieved or transmitted to a PC via the integrated USB port. Mean illuminance values can also be calculated as a result. nC  omputer-aided measurement The meters continuous operating mode is assured thanks to power supply via the USB port. Meter control, as well as acquisition, display and storage of measured values, is managed with included GLUX 2 software.

Foto- und Lichtmesstechnik GmbH


Ma

Please send RFQs, orders and requests for additional information to:

de

in G er m

an

GOSSEN METRAWATT

Table of Contents

Photometry: Luminance Meter Contact Measurement

109

MAVO-MONITOR USB

Article: M504G

This high precision luminance meter for contact measurement is assigned to class B in accordance with DIN 5032-7, appendix B of IEC 13032-1 and CIE 69, and measures the perceived brightness of luminous surfaces in candelas per square meter (cd/m) or foot-lamberts (fL). Excellent adaptation to the spectral brightness sensitivity of the human eye V() is highly precise with minimal deviation of just f1' < 3%, which is signicantly better than specied in the standard. After pressing the HOLD key, the measured value is saved to memory and display illumination is activated, making it possible to read the display in dark environments. The included adapter disc protects the meter from light leakage at the side during measurement, and the velvety coating prevents scratching of self-luminous and transilluminated surfaces. In industrial, commercial and service applications, luminance can be measured at monitors of any type, TV screens, light tables, trough luminaires, illuminated advertising surfaces, traffic signs and viewing screens. Calibration conducted at regular intervals is substantiated by means of a factory calibration certicate for special tests involving adherence to quality, safety and work safety regulations, monitor workstations in the eld of medical diagnostics and office technology. Depending on how the meter is used, we recommend a calibration interval of 12 to 24 months.

DIN 5032-7 classB

Specications/Features:
appendix B of IEC 13032-1 and CIE 69.

www.gossen-photo.de

More information:

nM  aximum precision Classied measurement of luminance in cd/m or fL in accordance with class B per DIN 5032-7, nB  road measuring range High initial sensitivity and a resolution of 0.01cd/m or 0.001fL, right on up to 19,990cd/m or 1999fL. nV  () adaptation The spectral sensitivity of the silicon photodiode is color corrected and corresponds to the spectral brightness nC  onvenient everyday use Simple operation, easy to read display, compact design, protection during transport in high quality nN  on-volatile memory 100 measured values can be saved, retrieved or transmitted to a PC via the integrated USB port. nC  omputer-aided measurement The meters continuous operating mode is assured thanks to power supply via the USB port.

sensitivity of the human eyeV(). aluminum case.

Mean luminance values can also be calculated as a result.

Meter control, as well as acquisition, display and storage of measured values, is managed with included GLUX 2 software.

Reliable Measured Values through Calibration at Regular Intervals


DIN EN ISO 9001-9004 stipulates test equipment monitoring, if such equipment is relevant for product quality or is used for the preparation of assessments. This test equipment must be calibrated at regular intervals and traced back to national standards. Calibration involves the ascertainment and documentation of meter display deviation, traced back to a specic standard using a specied procedure. Depending upon how the respective device is used, a calibration interval of between 12 and 24 months is recommended. A combination including receiving report, adjustment and nal report is also possible for GOSSEN meters.

Strictest Standards for the GOSSEN Light Lab


The GOSSEN Light Lab is equipped with a tested and monitored optical table, whose traceability to the national standard maintained by the PTB (German Federal Institute of Physics and Metrology) is assured by means of a Wi41G standard lamp. The lab is subject to test equipment monitoring in accordance with DIN EN ISO 9001-9004, and is additionally accredited for illuminance by DAkkS in accordance with DIN EN ISO/IEC 17025 under registration number D-K-15080-01-01. And thus you can count on product quality, the competence of our employees, continuous external monitoring and international recognition of our calibration services.

GOSSEN Foto- und Lichtmesstechnik GmbH Vertrieb Lichtmesstechnik

Lina-Ammon-Str. 22 90471 Nrnberg, Germany Phone: +49 911 / 86 02-170

Fax: +49 911 / 86 02-142 e-mail: info@gossen-photo.de www.gossen-photo.de


in G er m

Ma

de

an

GOSSEN METRAWATT

110 Photometry: Luminance Meter Distance Measurement

Table of Contents

MAVO-SPOT 2 USB

Article: M508G

This high precision luminance meter for distance measurement with an acceptance angle of 1 is assigned to class B in accordance with DIN 5032-7, appendix B of IEC 13032-1 and CIE 69. It measures the perceived brightness of luminous surfaces in candelas per square meter (cd/m) or foot-lamberts (fL) in consideration of ambient light. Excellent adaptation to the spectral brightness sensitivity of the human eye V() is highly precise with minimal deviation of just f1' < 3%, which is signicantly better than specied in the standard. The test object can be homed in on precisely via the reex optics with a 15 eld of view and a sharply marked 1 measuring circle at the center. Focus can be set for distances ranging from 1 meter to innity. Shorter distances as of 34cm are made possible by means of optional close-up lenses. Alternatively, contact measurement can also be performed with an optional, top quality probe. The velvety coating on the adapter disc prevents scratching of self-luminous and transilluminated surfaces. Measurement functions are selected and measurements are started with convenient on-hand operation. The display on the viewnder is activated along with background illumination by simply pressing a key. The comparative and ratio measurements are especially advantageous, by means of which deviation of measured value B from reference value A is evaluated and displayed. The relationship A/B is used for contrast measurement at workstations. Percentage deviation %A allows for an assessment of the uniformity of monitor screens and projection screen illumination, and difference A-B is used to detect deviation during the production process. Calibration conducted at regular intervals is substantiated by means of a factory calibration certicate for special tests for adherence to quality, safety and work safety regulations, for monitor workstations in the eld of medical diagnostics and for office technology. Depending on how the meter is used, we recommend a calibration interval of 12 to 24 months.

DIN 5032-7 classB

Optional Accessoires:
n Article: M496G Close-up lens 1 (measuring distance: 51 to 100cm) n Article: M497G Close-up lens 2 (measuring distance: 34 to 50cm) n Article: M511G Probe for contact measurement M511G including adapter disc and lens cover n Article: M512G Reectance standard for lux measurement n Article: M513G Baffle n Article: M514G Carrying strap

M496G/M497G

M511G

M512G

M513G

M514G

Specications/Features:

www.gossen-photo.de

More information:

nM  aximum precision Classied spot metering of luminance

nS  imple functions expansion Unclassied measurement of

with an acceptance angle of 1 in cd/m or fL in accordance with class B per DIN 5032-7, appendix B of IEC 13032-1 and CIE 69. nP  recision focusing The reex viewnder with a 1 measuring circle and a 15 eld of view is laid out for distance measurements from 1 meter to innity, with optional close-up lenses for focusing as of 34cm. nC  ontact measurement Contact measurement can be performed with an optional probe and adapter disc. nB  road measuring range High initial sensitivity and a resolution of 0.01 to 99,900cd/m or 0.01 to 30,000fL. nC  omparative and ratio measurement Contrast A/B, uniform illumination %A and deviation A-B are calculated and directly displayed. nV  () adaptation The spectral sensitivity of the silicon photodiode is color corrected and corresponds to the spectral brightness sensitivity of the human eye V().
de
in G er m

illuminance in lx or fc is possible with the optional reectance standard. nC  onvenient everyday use Simple operation with one hand, easy to read viewnder display, compact design, " tripod thread, protection during transport in high quality aluminum case. nN  on-volatile memory 1000 measured values or 10 groups of 100 measured values can be saved, retrieved or transmitted to a PC via the integrated USB port. nC  omputer-aided measurement The meters continuous operating mode is assured thanks to power supply via the USB port. Meter control, as well as acquisition, display and storage of measured values, is managed with included GLUX 2 software. nE  IZO RadiCS The meter is integrated into the software and can be used for comprehensive testing and automatic adjustment of RadiForce monitors, in order to assure constant and consistent image reproduction.

Ma

an

GOSSEN METRAWATT

Table of Contents

TYPE INDEX

111

1081 Probe ................................................... 59 A3-1663 3-Phase Adapters....................... 58 Accessories for PROFITESTI204+................... 61 Accessories for PROFITEST PV /PVsUN. ............ 63 Accessories: MAVOWATT ................................ 42 AC Current Clamp Sensors ............................. 58 AC Current Sensors ........................................ 29 AC Current Transformers ................................ 30 AC/DC Current Sensors ................................. 28 AT3-III-E ........................................................ 83 AT3-IIS/AT3-IIS32 ........................................ 83 AT16-DI/AT32-DI .......................................... 83 Barcode Printer, Reader, Scanner..................... 88 Barcode Scanner............................................ 50 BD232 /BD Pack 1 ........................................ 26 Brush Probe ................................................... 86 Cable Sets ..................................................... 32 CEE Adapter Z745A........................................ 84 Current Clamp Sensor .................................... 86 DranView 6 Software....................................... 44 DUSPOL....................................................... 66 E-ClipI1/E-ClipI2 ......................................... 57 EL1................................................................ 85 E-Set 3.......................................................... 57 E-Set 4.......................................................... 57 E-Set 5.......................................................... 57 ETC................................................................ 90 Flexible Current Sensors ................................. 28 Generator 5000A .......................................... 55 GEOHM 5 ...................................................... 56 GEOHM C....................................................... 56 Guard 5000A, Leadex 5000 ........................... 55 High Frequency Probe .................................... 32 Interface Cable RS 232 .................................. 33 IrDa-USB Converter ........................................ 59 ISO KALIBRATOR 1 ......................................... 54 Kelvin Clips .................................................... 33 Kelvin Probes.................................................. 33 KONSTANTER Accessories............................. 105 KS13............................................................. 85 KS24 Cable Set ............................................. 58 KY 5000A ..................................................... 55 Load KONSTANTERSPL .............................. 102 Load KONSTANTERSSL 32EL ..................... 102 LSP 32K-KONSTANTER ................................ 101 Magnetic Test Probes...................................... 58 MAVOLUX 5032B/C USB ............................. 108 MAVO-MONITOR USB ................................... 109 MAVO-SPOT 2 USB ...................................... 110 MAVOWATTI4 ............................................... 38 MAVOWATTI20.............................................. 38 MAVOWATTI30I40I70 .................................. 40 MAVOWATTI50 ............................................. 41 METRACALIMC ............................................. 18 METRACLIP SERIES......................................... 69 METRAFLEX P300.......................................... 50 METRAHITI1A / 2A......................................... 17 METRAHITI1ASi............................................. 19

METRAHITI2+ ............................................... 15 METRAHITI27EX ........................................... 21 METRAHITI27I / 27AS .................................. 20 METRAHITI27M............................................. 20 METRAHITI30M ............................................ 12 METRAHITIBAsE.............................................. 10 METRAHITICAL / CAL Pack ............................ 19 METRAHITIEBAsE. ........................................... 11 METRAHITIENERGY........................................... 13 METRAHITIEsPECIAL......................................... 11 METRAHITIETECH. ........................................... 11 METRAHITIEXTRA. ........................................... 11 METRAHITIH+E CAR...................................... 21 METRAHITIISo@AERO .................................. 14 METRAHITIISo............................................... 14 METRAHITIOUTDOOR. ....................................... 12 METRAHITIPRO............................................... 10 METRAHITIT-Com/T-COM plus ................... 14 METRAHITITECH.............................................. 10 METRAHITIULTRA........................................... 13 METRAHITIWORLD .......................................... 15 METRAHITIXTRA.............................................. 10 METRALINE SERIES ........................................ 64 MetraMachineI204/2.5+ (M504D), MetraMachineI439/5.4+ (M504F).............. 60 METRAmax 2 ................................................. 17 METRAmax 3 ................................................. 17 METRAmax6 ................................................. 17 METRAMAXI12)............................................. 15 METRAOHM 413 ............................................ 51 MetraPhaseI1 ........................................... 67 METRAportI3A .............................................. 16 METRAportI40S ............................................ 16 METRATESTERI5+3P..................................... 79 METRATesterI5+ ........................................ 79 METRATHERM|1 .......................................... 65 METRAVOLT 7A.............................................. 67 METRAVOLT 12D+L....................................... 67 METRAwin 10/METRAHit ............................... 35 METRAwin 90-2............................................. 34 METRAwin 90-F /-FJ...................................... 34 METRAWin/MAVOWATTI20 .......................... 44 METRISO 1000A........................................... 52 METRISO 5000A ......................................... 54 METRISO 5000D-PI...................................... 55 METRISO 5024............................................. 53 METRISO C..................................................... 51 METRISO G500MM/G500/G1000/G1000+.52 Micro Centurion 2........................................... 71 Micro Junior 2 ............................................... 71 MINITESTIBase / 3P Master MINITESTIPro /Master.................................... 80 MSP 64D-KONSTANTER ............................... 100 NA Hit 2x ....................................................... 27 NA X-TRA....................................................... 27 PA4 ............................................................... 86 pat Manager................................................... 92 PC.doc-ACCESS............................................. 91

PC.doc-EXCEL................................................ 91 PC.doc-WORD............................................... 91 PhaseCopI2 ................................................ 66 Plug Inserts: PRO- ..................................... 50 PMA16 .......................................................... 26 Pouches / Hard Cases / Covers / Hangers for Multimeters.................................. 36 Pouches, Cases for Testers............................. 87 PRO-A3 II Measuring Adapter.......................... 58 PRO-AB ......................................................... 50 ProfiSafe 400/690 ..................................... 67 PROFISCAN ETC............................................. 50 PROFITESTI2................................................. 49 PROFITEST I204+/204L+ ............................. 60 ProfiTestI204HP/2,5kV, ProfiTestI204HV/5,4kV.............................. 61 PROFITESTIC ................................................ 49 PROFITESTIMaster ....................................... 46 PROFITEST IPV .............................................. 62 PROFITEST IPVSUN .......................................... 63 PROFITESTIS1 .............................................. 48 Rechargeable Battery Set ............................... 58 RS 232 USB Converter ................................ 59 RS 232 USB Converter ................................ 82 SCANBase/SCANWriteIRFID..................... 50, 88 SECU-cal 10 .................................................. 84 SECULIFE|SR................................................. 78 SECULOAD .................................................... 84 SECUSTAR|FM+ / SECULIFE|SB..................... 78 SECUSTORE ................................................... 82 SECUTest|3PL.............................................. 81 SECUTEST|21F ............................................. 81 SECUTestIPSI .............................................. 61 SECUTestISI+ .............................................. 61 SECUTEST S2N+/+10/SECUTEST S2N+W..... 75 SECUTEST|SIII+ /SECULIFE|ST ..................... 77 SECUTEST|SI+/SECUTEST|PSI...................... 82 SECUTEST|WP............................................... 81 Shunts .......................................................... 26 SK2/SK5 ...................................................... 85 SLP 32N-KONSTANTER 120 to 320 .............. 101 SM16 ............................................................ 26 SECU-UP ....................................................... 76 SP350........................................................... 57 SSP 32N-KONSTANTER 120 to 320 ................ 98 SSP 62N/64N-KONSTANTER 500 to 3000...... 99 SYSKONP Series ........................................... 96 Telearm 1....................................................... 59 Temperature Probes ....................................... 30 Temperature Sensors ............................... 31, 86 T/F Sensor ................................................... 59 TR-1/TR-1P .................................................. 72 T-Rex/T-Rex R ............................................... 72 USB-HIT /Pack............................................... 26 USBIXTRA ...................................................... 26 VARIO Plug Adapter Set ................................. 59 VL2E ............................................................. 84 WR50-12/13/12R/13R ................................ 71 Z206D .......................................................... 26

GOSSEN METRAWATT

112 RECOmmENDED WOrKsHOP EQuiPmENt

Table of Contents

Recommended Workshop Equipment in Accordance with ZVEH and VDEW Guidelines


Required Measuring and Test Instruments Per Standard For First-Time Users Standard For Efficient Work

Test bay with permanently integrated measuring instruments

DIN VDE 0104


METRATESTER 5+3P SECUTEST 21F METRATESTER 5+3P/VL2E

Measuring instruments for electrical devices

DIN VDE 0701-0702


METRATESTER 5+ SECUTEST S2N+ with SI module

Voltmeters to at least 600 V Current meters to at least 15 A (continuity testers)

DIN VDE 0410 DIN VDE 0410 DIN VDE 0403


METRAHIT 2+ with WZ12A current transformer clamp METRAHIT PRO with WZ12D current transformer clamp METRAHIT X-TRA with Z3512 current transformer clamp

Current clamps to at least 300A

METRACLIP 410 METRACLIP 410 METRACLIP 410

Insulation measuring instruments RCCB testers Ohmmeters Loop resistance measuring instruments Phase sequence indicator DIN VDE 0413, part 2 DIN VDE 0413, part 3 DIN VDE 0413, part 4 DIN VDE 0413, part 6 DIN VDE 0413, part 7
PROFITEST 2 PROFITEST MTECH PROFITEST MTECH

Earth testers

DIN VDE 0413, part 5


GEOHM C GEOHM C

Single-pole voltage testers 2-pole voltage testers

DIN VDE 0680, part 5 DIN VDE 0682, part 401


ProSafe 400 Duspol digital LC METRAVOLT 12D+L

Continuity testers

DIN VDE 0403


ProSafe 400 ProSafe 690

Phase sequence indicators

DIN VDE 0413-7


PhaseCop 2 PhaseCop 2 METRAPHASE 1

Ma

in de

Germ a
ny

GOSSEN METRAWATT

PRODUcT SPEcTRUM

113

MEAsURING INsTRUMENTs AND TEsTERs Measuring Systems for Medical Technology Function Testers Safety Testers Light Analyzers Modular Test System Measuring Technology Universal Mains Quality Energy Power Field Measuring Systems, Cable Detection Devices Resistance Thermometers / Clamp-Type Measuring Instruments Digital Multimeters Analog Multimeters Multimeter Accessories Calibrators Temperature Measuring Instruments, Light Meters Testing Technology Electrical Facility Management Solutions Installations and Equipment Testing (permanently installed) Electrical Device Testing (portable) Electrical Machinery Testing Earthing, Insulation, Low-Resistance Workshop Test Panels AS Interface Test Instruments Power Supply Technology Laboratory Power Supplies Electronic Loads Customer-Specic OEM Power Supplies Software for Measuring Instruments Testers Power Supplies

INDUsTRIAL MEAsURING AND CONTROL TEcHNOLOGY Measuring Technology Industrial Meas. Transducers for Temperature and DC Quantities Meas. Transducers for Heavy Current Quantities Measuring Transducers for Angle of Rotation and Position DC Signal Isolators, Isolating Transformers Power Packs, Mounting Racks Isolating Switch Ampliers, Isolating Ampliers Valve Control Modules, Limit Value Indicators Thermocouples, Resistance Thermometers Ex-i Equipment Energy Management Energy Meters, Summators, Additional Components Power Energy Mains Quality Load Optimization ECS Energy Control System Energy Management Engineering Competent Project Management Partner Control Technology Compact Controllers, Multi-Channel Control Systems CoDeSys and PC Worx Software Controllers Controller Modules for the Siemens S7-300 Recording Technology Display Recorders Continuous Line Recorders Point Recorders Software for Energy Control System Measuring Transducers Isolating Ampliers Controllers

Further information about our company is available at www.gossenmetrawatt.com


Ma

de

in G er m

an

GOSSEN METRAWATT

Sdwestpark 15 90449 Nrnberg, Germany Phone: +49 911 8602-111 +49 911 8602-777 Fax: e-mail: info@gossenmetrawatt.com www.gossenmetrawatt.com

GMC-I Messtechnik GmbH

Electromediciones Kainos S.A. Poligon Industrial Est, Energa, 56 E-08940 Cornell de Llobregat, Barcelona Phone: +34 934 742 333 Fax: +34 934 743 470 E-mail: kainos@kainos.es www.kainos.es
Printed in Germany Subject to change without notice 1/11.12 Order no. 3-337-026-03

GMC-Instruments France SAS 3 rue Ren Cassin F-91349 Massy Cedex Phone: +33 1 6920 8949 Fax: +33 1 6920 5492 E-mail: info@gmc-intruments.fr www.gmc-instruments.fr GMC-mic technika s.r.o. Fgnerova 1a CZ-67801 Blansko Phone: +420 516 482 611/-617 Fax: +420 516 410 907 E-mail. gmc@gmc.cz www.gmc-cz GMC-Instruments Austria GmbH Richard-Strauss-Str. 10/2 A-1230 Wien Phone: +43 1 890 2287 Fax: +43 1 890 2287 99 E-mail: office@gmc-instruments.co.at www.gmc-instruments.co.at GMC-Instruments (Tianjin) Co., Ltd. Fon +86 10 84798255 Fax +86 10 84799133 Rm.710, Jin Ji Ye BLD. No.2, Sheng Gu Zhong Rd. P.C.: 100022, Chao Yang District info@gmci-china.cn, www.gmci-china.cn

GMC-Instruments Italia S.r.l. Via Romagna, 4 I-20046 Biassono (MI) Phone: +39 039 2480 51 Fax: +39 039 2480 588 E-mail: info@gmc-i.it www.gmc-instruments.it GMC-Instruments Nederland B.V. Daggeldersweg 18 NL-3449 JD Woerden Phone: +31 348 42 11 55 Fax: +31 348 42 25 28 E-mail: info@gmc-instruments.nl www.gmc-instruments.nl GMC-Instruments Schweiz AG Glattalstr. 63 CH-8052 Zrich Phone: +41 44 308 80 80 Fax: +41 44 308 80 88 E-mail: info@gmc-instruments.ch www.gmc-instruments.ch

Sales Partners ies in Over 40 Countr


Your sales partner:

Das könnte Ihnen auch gefallen