05.15.00 ILLUMINATION SlNo Descriptionofparameter Thetypeoffixturesalongwiththeaverageluxlevelshallbeasfollows:


1.

Area

Average Illumination Level(LUX) 300

ControlRoom

SwitchgearMCCRoom Battery Room and Battery ChargerRoom Corridor, Passages, Staircases & Toilet Switchyardandalloutdoorarea Approvedmake

100

5 6 7

50 2030 20(general)

LightingfixturesforACType ofLighting Decorative,recessmounting fluorescentfixture.(Energy efficientBEE3starlabelCFL) Industrialtroughtype fluorescentfixture.(Energy efficientBEE3starlabelCFL) Corrosionproof,fluorescent fixtures.(EnergyefficientBEE3 starlabelCFL) (EnergyefficientBEE3star labelCFL) Metalhalidefixture Bajaj/Havells/Phillips/CGL

05.16.00 PLCC SNo 1. 2. 3. 4. 5.

Description PLCCtype FreqRange Coupling Channels1 Channelauxsupply

6. Standards 7. Panel 8. Guaranteedperformance Temperaturerange 9. Bandwidthconfigurationin Speech+DataPLCC 10. AmplifierPoweroutput 11. ReturnLoss 12. CompositeLoss 13. TappingLoss

Particulars ABBETL41 24to500kHzfornominaloutputpower=40W PhasetoPhase 1channelforprotection&Speech. Eachchannelshallhaveitsownpowersupply unit(PSU). IEC60495,IEC608341,IEC6100062, IEC6100064(CISPR22,ClassA); Onlyfrontopening From0degCto50DegCAmbienttemperature Speech+300to1200baudratein 4kHzbandwidth 40W Morethan12dB 2dB Lessthan2dBasperIEC60495

DOC.NO.:WRELW0WEL357TSP0001R0

Page55 of77

T e ch n i c a l Sp e cif i cat ion f o r 1 1 0 kV / 3 3k V S w itch y a rd

K a lgu rk i ( 50 M W) W ind Pow e r p ro j ec t

14. 15. 16. 17. 18. 19.

AGCrangeofreciever Carrierfreqstability Nominaloutputimpedance Coaxialcable Linematchingunit Modems

20. 21. 22. 23.

Plugin(4W)phonesets AuxSupply ProtectionCoupler Frequencyallocation

24. Telephoneset 25. Approvedmake 05.17.00 BUSPOSTINSULATOR S.No Description 1. Codesandstandards 2. OperationalRequirements

40dBminimum +/1ppm 75Ohmunbalanced 75Ohmunbalanced MCD80(AB9S+AB9T) NSK5 Shall be supplied with PLCC. It may be integral part of PLCC. Shall be suitable for interfacing with Gateway having communication protocolofIEC608705101/104,Ifapplicable. Oneperchannel 48VDC+20/15% NSD50(min3codesperchannel.) M/s ABB shall provide assistance in indicating the availablefrequencyrange/valuesforthespecified location of the plant. However, final frequency allocationshallbeprovidedbyWelspun. 4wireexpressphone ABB

3. NominalsystemVoltage 4. HighestsystemVoltage 5. Ratedoneminutepower frequencywithstandsvoltage. 6. Dryoneminutepower frequencywithstandvoltage. 7. LightingImpulsewithstand voltagepeak 8. Minimumnominalcreepage distance 9. Minimumcoronaextension voltage 10. RadioInterferencevoltage( Microvoltat1MHz)atasystem voltageof92kVrms 11. Cantileverstrength(Upright) 12. Torsionalstrength

Particulars IS:2544,IEC168,IEC273&IEC815.ItsGlaze colourmustbeBrown. Thereshallbenoelectricdischargebetweenthe conductorandinsulators,whenoperatingat normalvoltage,whichwouldcausecorrosionor injurytoanyofthematerial. 110kV 145kV 275kVrms 275kVrms 550kV 3625mm 105kV(rms) <200V