SECTION 15300 FIRE PROTECTION SYSTEM
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

ENGG

CERT

PMT

SUBSECTION INDEX Part 1 - General

DESCRIPTION

1.01 1.02 1.03 1.04

Description of System Quality Assurance Submittals Product Delivery and Handling

Part 2 - Products
DATE JOB/EWO

2.01

Materials

Part 3 - Execution 3.01 Installation

REV. NO.

PART 1 - GENERAL
DISCIPLINE ENGINEER

__ ________ _ DATE: ________

1.01 Description Of System A. This Section covers providing the fire protection system as shown on the Drawings and specified herein, including fittings and accessories required to complete the Work acceptable to Saudi Aramco Representative.

PROJECT ENGINEER
____________ DATE

CERTIFIED _ __________
DATE: ________

1.02 Quality Assurance A. Reference Codes and Standards: Comply with Section 15001 - Industry Codes and Standards. Test: The entire piping system shall be tested to 13.5 Bar (200 psig) and checked for completely functional operation and water distribution. Approvals: Contractor shall prepare detailed shop drawing locating and identifying valves and accessories, and showing exact routing, size and type of pipe, including spooling. Shop drawings shall be approved by Saudi Aramco Representative prior the Work is started. Completed installation is to be inspected and approved by Saudi Aramco Representative.

CONSTRUCTION AGENCY
________________ DATE:

B.

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By:

C.

Date:

SECTION 15300

CONSTRUCTION SPECIFICATIONS
KAUST TOWN CENTER RESIDENTIAL &

DWG. TYPE PLANT NO. INDEX

DRAWING NO.

SHT. NO. REV. NO.

DOC

COMMUNITY SUPPORT BUILDINGS RABIGH SAUDI ARABIA

K55
JOB/EWO#

VE-417361 BI-25-00002

14-Sep-07

1 OF 5

00

Saudi Aramco 2616-ENG (3/99)


OPERNS.


SAUDI ARAMCO OIL COMPANY
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

PMT

1.03

Submittals A. Submit three (3) copies to Saudi Aramco Representative for approval, manufacturers data and a complete and independent set of shop drawings showing layout, installation details, valve locations and other accessories.

ENGG

CERT

1.04
DESCRIPTION

Product Delivery and Handling A. Refer to Section 15050 Basic Mechanical Material and Methods.

PART 2 - PRODUCTS 2.01 Materials A. Piping: Unless otherwise noted on the Drawings, the following shall apply. 1. Aboveground firewater pipes inside buildings shall be galvanized carbon steel as per ASTM A-53, Grade B, Sch 40, ERW. B. Fittings: 1. Flanged pipe fittings shall conform to ANSI B16.5. 2. Screwed pipe fittings conforming to ANSI B16.3 or to ANSI B16.4. C. Valves 50mm (2) and Smaller: 1. Gate Valve: bronze gate valve as per ASTM B62, screwed ends, solid wedge, OS & Y, rising stem, UL and FM approved, 200 psi non-shock cold water. Check valves: bronze check valve as per ASTM B62, screwed ends, swing check, regrinding type, renewable composition disc, 200 psi non-shock cold water. UL and FM approved. Strainer: Y type, Bronze screwed type with blow off connection. Furnished with 20 mesh self- aligning stainless steel screen 400 psi WOG.

REV. NO.

DATE JOB/EWO

DISCIPLINE ENGINEER

__ ________ _ DATE: ________

PROJECT ENGINEER
____________ DATE

CERTIFIED _ __________
DATE: ________

CONSTRUCTION AGENCY
________________ DATE:

2.

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By:

3.

D. Valves 75 mm (3) and larger:


Date:

1.

Gate Valve: 150 lb., ANSI B16.34, cast steel body ASTM A216 Class B, solid wedge type gate valve ,Bronze B62 trim, bolted bonnet, outside screw and yoke, rising stem, renewable seat rings, UL and FM approved.
SECTION 15300

CONSTRUCTION SPECIFICATIONS
KAUST TOWN CENTER RESIDENTIAL &

DWG. TYPE PLANT NO. INDEX

DRAWING NO.

SHT. NO. REV. NO.

DOC

COMMUNITY SUPPORT BUILDINGS RABIGH SAUDI ARABIA

K55
JOB/EWO#

VE-417361 BI-25-00002

14-Sep-07

2 OF 5

00

Saudi Aramco 2616-ENG (3/99)


OPERNS.


SAUDI ARAMCO OIL COMPANY
2. Check Valve: 150 lb., ANSI B16.34. Cast steel body, swing type disk with bolted cap and flanged ends. Strainer: Y type, cast iron flanged conforming to ASTM A-126 with blow off connection. Furnished with self-aligning perforated cylindrical screens 125 lb.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

CERT

PMT

ENGG

3.

E.
DESCRIPTION

Special Valves 1. Alarm Check Valve : Iron body, bronze mounted, variable pressure type with retarding chamber. Provide basic trimmings for alarm test by pass, gages, drain connections, mounting supports for retarding chamber, and drip funnel. Provide pressure sensitive alarm switch to actuate the fire alarm system. UL and FM approved. Drain Valves: Threaded bronze angle, globe, ball or butterfly, 150 lb. WOG equipped with reducer and hose connection with cap or connected to a drain line. Self-contained Test and Drain Valve: a. Ductile iron body with bronze Drain and Test bonnets. Acrylic sight glass for viewing test flow. Various sized orifice inserts to simulate flow through the last sprinkler on the branch it is attached, 25 mm (1 in.) female threaded outlets or 25 mm (1 in.) onequarter turn locking lug outlets for plain end pipe (end preparation to be in accordance with manufacturers recommend-ation). Bronze body, with chrome plated bronze ball, brass stem, steel handle, teflon seat and sight glasses. Provide valve with three position indicator plate (off, test, and drain), 6 mm (1/4 in.) tapping for pressure gage and various other orifice inserts to simulate flow through the last sprinkler on the branch it is attached.

DATE JOB/EWO

2.

REV. NO.

3.

DISCIPLINE ENGINEER

__ ________ _ DATE: ________

PROJECT ENGINEER
____________ DATE

CERTIFIED _ __________
DATE: ________

b.

CONSTRUCTION AGENCY
________________ DATE:

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By:

F.

Water Flow Alarm Switch: 1. Water pressure activated to operate electric circuit to local and remote alarms; 4 to 11 psi operational setting; automatic reset, two separate circuits. Weatherproof construction; F.M. approved, U.L. listed

Date:

2. G.

Sprinklers shall be fully recessed type with pop off dish with a POP that is compatible with the ceiling finish. Sprinklers shall be fast response, standard coverage, K=5.6, NPT, 93oC (200oF).
DWG. TYPE PLANT NO. INDEX DRAWING NO.

SECTION 15300
SHT. NO. REV. NO.

CONSTRUCTION SPECIFICATIONS
KAUST TOWN CENTER RESIDENTIAL &

DOC

COMMUNITY SUPPORT BUILDINGS RABIGH SAUDI ARABIA

K55
JOB/EWO#

VE-417361 BI-25-00002

14-Sep-07

3 OF 5

00

Saudi Aramco 2616-ENG (3/99)


OPERNS.


SAUDI ARAMCO OIL COMPANY
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

PMT

ENGG

CERT

H.

Fire Department Connection: Wall type or free-standing connection with cap and chains, escutcheon lettered to indicate that is a connection to the building standpipe system, equipped with NST male threads, polished brass finish. 2x2-1/2 NPT Female type. Portable Fire Extinguishers:

I.
DESCRIPTION

1. FE-1

REV. NO.

DATE JOB/EWO

Fire Extinguisher: Refer to SAMS 21-102-223 Carbon Dioxide, for Class B,C fire, 4.5 kg. (10 lb.), 10-BC UL, potable, 1.8 m. (6 ft.) range, 9.5 mm (3/8 in.) mono valve outlet, ANSI/UL 711 and ANSI/UL 154, hand-carried, lever operated complete with alum cylinder 838.2 mm (33 in.) long hose, nozzle horn, metal hanging bracket and an inspection tag to record date and weight at the time of inspection, tested to comply with standards. Box painted to SAES-H-101 APCS 6-Red, Language: English and Arabic. Accessories: 1. For surface mounted: Use all-purpose bracket as specified by manufacturer. Fire Extinguisher: Refer to SAMS 21-102-775 Dry Chemical, for Class A,B,C fire, 11.4 kg. (25 lb.), 20-A, 80-BC UL, portable, 6.1 m. (20 ft) range, 15.9 mm (5/8 in.) dia. Hose outlet, ANSI/UL-154, UL-711, mono-ammonium phosphate foray hand-carried, gas pressure cartridge puncture pin operated, expanding round stream nozzle, 905 mm (35-5/8 in.) long chemical hose. Body painted to SAES-H-101 APCS-6-RED, Language: English and Arabic. Accessories: 1. For surface mounted: Use all-purpose bracket as specified by manufacturer. 2. For semi-recessed type: Use fire extinguisher cabinet, Larsen Model #MSS3216-R (FS) or approved equal. Semi-recessed 5/16 Flat Trim, fire rated, solid door with a vertical glass panel similar to Larsen Vertical Duo type, stainless steel, 18 Ga. construction; stainless steel satin finish, cabinet size to fit the selected fire extinguisher. Fire Extinguisher: Refer to SAMS 21-104-550 Water, for Class A fire, 9.5 L (2.5 gal.), 2A UL, portable, 13.7 m (45 ft.) range, 7.9 mm (5/16 in. dia.) hose outlet, ANSI/UL-54, UL711, air pressurized type, SS cylinder with straight stream nozzle, 7.9 mm (5/167 in.) dia. X 610 mm (24 in.) long hose, without corrosion inhibitor pills. Body painted to SAES-H-101 APCS Red. Language: English and Arabic. Accessories: 1. For surface mounted: Use all-purpose bracket as
DWG. TYPE PLANT NO. INDEX DRAWING NO.

2. FE-2

DISCIPLINE ENGINEER

__ ________ _ DATE: ________

PROJECT ENGINEER
____________ DATE

CERTIFIED _ __________
DATE: ________

CONSTRUCTION AGENCY
________________ DATE:

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By:

3. FE-3
Date:

SECTION 15300
SHT. NO. REV. NO.

CONSTRUCTION SPECIFICATIONS
KAUST TOWN CENTER RESIDENTIAL &

DOC

COMMUNITY SUPPORT BUILDINGS RABIGH SAUDI ARABIA

K55
JOB/EWO#

VE-417361 BI-25-00002

14-Sep-07

4 OF 5

00

Saudi Aramco 2616-ENG (3/99)


OPERNS.


SAUDI ARAMCO OIL COMPANY
specified by manufacturer. 2. For semi-recessed type: Use fire extinguisher cabinet, Larsen Model #MSS3216-R (FS) or approved equal. Semirecessed 5/16 Flat Trim, fire rated, solid door with a vertical glass panel similar to Larsen Vertical Duo type, stainless steel, 18 Ga. construction; stainless steel satin finish, cabinet size to fit the selected fire extinguisher. 4. FE-4 Refer to SAMS 21-102-820 Dry chemical suitable for class B&C 12.2 kg. (27lbs).
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

DESCRIPTION

ENGG

CERT

PMT

PART 3 - EXECUTION 3.01 Installation A. Install per applicable Saudi Aramco Engineering and Drawings Standards, IBC, IPC and NFPA requirements. Install dielectric flange kits or unions between dissimilar metals in the fire piping system. Replace or repair damage materials, equipment and defective Work as directed by Saudi Aramco Representative at no additional cost to Saudi Aramco.

DATE JOB/EWO

REV. NO.

B.

DISCIPLINE ENGINEER

C.

__ ________ _ DATE: ________

PROJECT ENGINEER
____________ DATE

- END OF SECTION -

CERTIFIED _ __________
DATE: ________

CONSTRUCTION AGENCY
________________ DATE:

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By:

Date:

SECTION 15300

CONSTRUCTION SPECIFICATIONS
KAUST TOWN CENTER RESIDENTIAL &

DWG. TYPE PLANT NO. INDEX

DRAWING NO.

SHT. NO. REV. NO.

DOC

COMMUNITY SUPPORT BUILDINGS RABIGH SAUDI ARABIA

K55
JOB/EWO#

VE-417361 BI-25-00002

14-Sep-07

5 OF 5