Presented by:
Performance Testing
Performance Testing
Pre Pre-construction mock mock-up
Purpose: testing is performed to attempt to simulate asasbuilt field conditions for the evaluation of the performance and constructability of an exterior wall system Standards:
ASTM E 283 Standard Test Method for Determining Rate of Air Leakage ASTM E 331: Standard Test Method for Water Penetration... (Static Pressure) Structural Uniform Loading by Static Pressure (ASTM E330) AAMA 501.1: Standard Test Method for Water Penetration... (Dynamic Pressure) AAMA 1503: Voluntary Test Method for Thermal Transmittance and Condensation Resistance
Size:
Typically at least 2 stories high by two units wide
Scope:
Incorporate largest spans/openings which exceed published test data Incorporate adjacent finishes/conditions to ensure construction and configuration Include insets, corners, parapets, sunshades, etc. where possible
QA/QC Testing
Field Testing
Purpose: Testing of installed assemblies to evaluate the performance and quality of the work ki installed. ll d (I (It i is d desirable i bl to perform f throughout construction so that quality at each stage is evaluated evaluated.) ) Standards:
AAMA 502 502-08: Voluntary Voluntary Specification for Field Testing of Newly Installed Fenestration Products. ASTM E1105: Standard Test Method for Field Determination of Water Penetration of Installed (Static Pressure)
Chamber:
Water Penetration: ASTM E1105 Air Infiltration: ASTM E 283
Location: Typically selected by A/E or Consultant Size: Typically one floor level by two units high Frequency:
Recommended: 10%, 25%, 50%, 75% and 90%. Typical targets targets: : 10%, 50%, and 75%
Diagnostic Testing
Diagnostic Testing
Purpose: Testing of installed assemblies to determine
the source of known water infiltration. infiltration Standard Guidelines:
AAMA 511: Voluntary y Guideline for Forensic Water Penetration Testing ASTM E 2128: Standard Guide for Evaluating Water Leakage of Building g Walls
Standards:
AAMA 501.2 QA and Diagnostic Water Leakage Field Check of Installed Installed AAMA 502 502-08: Voluntary Specification for Field Testing of Newly Installed Fenestration Products. ASTM E1105: E1105 Standard St d d Test T t Method M th d for f Field Fi ld Determination D t i ti of f Water Penetration of Installed (Static Pressure)
Determine actual wind velocities and rate of rainfall for testing g Isolate specimen p so p perimeter excluded Then test specimen including perimeter condition
Variations to testing
Diagnostic Testing
Summary
Summary
Pre Pre-Construction Performance Testing
Air: ASTM E 783 Static Water: ASTM E 1105 Structural: ASTM E 331 Nozzle: AAMA 501.2 (field check, not performance)
Diagnostic Testing
AAMA 501.2 supplemented with ASTM E 1105