Molded-case Circuit Breakers Earth-leakage Circuit Breakers

Mitsubishi Molded-case Circuit Breakers and Earth-leakage Circuit Breakers

INDEX

This document is intended for those having electrical knowledge and expertise, such as those using these products for manufacturing assemblies, carrying out electrical installation, maintenance and inspection, including the operators (end users) of these products.

Introduction ................................................................................................................................ 1 12 1. Detailed Specifications ................................................................................................................. 13


Molded-case Circuit Breakers ........................................................................................................................................ 13 Earth-leakage Circuit Breakers ...................................................................................................................................... 21 Motor-protection Breakers .............................................................................................................................................. 25

2. Special-purpose Breakers ............................................................................................................ 27


Mag Only (Instantaneous tripping circuit breakers) ............................................................................................................ 27 DC MCCBs and DSN Switches ........................................................................................................................................ 27 400Hz MCCBs ................................................................................................................................................................... 28 Low-instantaneous MCCBs ............................................................................................................................................. 28 Generator Protection MCCBs ......................................................................................................................................... 28 Measuring Display Unit (MDU) ........................................................................................................................................ 29

3. Connection Method ...................................................................................................................... 32

Note This document describes the product specifications for selecting an appropriate low-voltage circuit breaker. A separate document Handling and Maintenance describing the operating instructions in detail. Please be sure to request a copy for using the selected product correctly.

4. Accessories ................................................................................................................................... 33
Internal Accessories ......................................................................................................................................................... 33
1. Accessories ............................................................................................................................................................................. 2. Switch Operation and Rating ................................................................................................................................................... 3. Maximum Number of Internally Mounted Accessories ............................................................................................................ 4. Shunt Trip (SHT) ...................................................................................................................................................................... 5. Undervoltage Trip (UVT) .......................................................................................................................................................... 6. Test Button Module (TBM) ....................................................................................................................................................... 7. Lead-wire Specifications .......................................................................................................................................................... 8. Vertical Lead-wire Terminal Block (SLT) .................................................................................................................................. 9. Cassette-type Accessories ...................................................................................................................................................... 10. Pre-alarm Module (PAL) .......................................................................................................................................................... 1. F-type Operating Handle ......................................................................................................................................................... 2. V-type Operating Handle ......................................................................................................................................................... 3. S-type Operating Handle ......................................................................................................................................................... 4. Terminal Cover ........................................................................................................................................................................ 5. Electrical Operation Device ..................................................................................................................................................... 6. Mechanical Interlocks (MI) ...................................................................................................................................................... 7. Handle Lock Devices and Card Holder ................................................................................................................................... 8. IEC 35mm Rail Mounting Adapters ......................................................................................................................................... 9. Insulating Barrier ..................................................................................................................................................................... 33 33 34 35 35 35 35 35 36 36 37 38 39 39 40 40 41 41 41

External Accessories ........................................................................................................................................................ 37

5. Characteristics and Dimensions .................................................................................................. 43


Molded-case Circuit Breakers ........................................................................................................................................ 43 Earth-leakage Circuit Breakers ...................................................................................................................................... 55 Motor-protection Breakers .............................................................................................................................................. 63

6. LOW-VOLTAGE SWITCHGEAR TECHNICAL INFORMATION SERVICE VIA THE INTERNET ....... 67


(http://www.MitsubishiElectric.co.jp/haisei/lvs/)

Molded-case Circuit Breakers Earth-leakage Circuit Breakers

Higher Performance
The new circuit breaking technology Expanded ISTAC upgrades current limiting performance, leading to higher breaking capacity.
With higher breaking capacity, lower class models (e.g. NF-S General-purpose model to NF-C Economy model) can be used, thus leading to cost reduction of panels/machines.

Expanded ISTAC breaking technology

Grid Movable conductor Current C Current Arc

NF250-HV

Increased reaction force of movable conductor

Reaction circuit

Conventional model NF250-HW

50kA/13kA (at 400VAC)

Current B

Fixed conductor

75kA/75kA
New model NF250-HV (at 400VAC)

Extending the conductor (reaction circuit for movable conductor) beneath the fixed conductor makes the movable conductor open faster than the conventional ISTAC mechanism. Significantly improves the current limiting performance.(Reduces the maximum peak current by 10%.)

Visualization
The new electronic circuit breakers (with display) and MDU breakers can display various measurement items. This will enable energy management through visualization, which leads to energy saving.
Electronic circuit breaker (with display)

MDU breakers

The display is on the circuit breaker body and shows circuit information. Detailed setting can be done on the display. The display turns red during alarms.
Display Current in each phase Alarm

Molded-case Circuit Breakers Earth-leakage Circuit Breakers

Compact
The thermal adjustable circuit breakers and electronic circuit breakers are smaller.
These breakers contribute to the reduction of panel size.

Volume ratio
NF250-SGW

(Compared with our conventional models)

74%

NF250-SGV

(Conventional model : 105 165 86mm)

(New model : 105 165 68mm)

250AF circuit breakers fixed types (NF250-CV, NF250-SV, NF250-HV, NV250-CV, NV250-SV, NV250-HV), thermal adjustable types (NF250-SGV, NF250-HGV, NF250RGV), and electronic types (NF250-SEV, NF250-HEV, NV250-SEV, NV250-HEV) are the same size, leading to the standardization of panel design.

Standardization
Types of internal accessories are reduced from 3 types to 1 type.
Standardization of internal accessories contributes to the reduction of stock and delivery time.

Conventional models

Three types

For 32/63AF For 125AF For 250AF

New models

One type

For 32 to 250AF
Applicable accessories AL AX AL+AX SHT UVT

32AF and 63AF circuit breakers can now be used in both AC and DC circuits without specifying when ordering. This will lead to prevention of ordering mistakes. The earth-leakage circuit breakers can now be equipped with a voltage shunt trip device (SHT).

Molded-case Circuit Breakers Earth-leakage Circuit Breakers

Environment
Nonuse of Hazardous Substances
Eco-friendly design is used for all circuit breakers, and they do not use hazardous substances.The circuit breakers comply with RoHS regulation.

Use of Various Recyclable Materials


The circuit breakers are made of thermo-plastic materials that are easy to recycle. (Some models are partially made of thermoset materials.) The major plastic parts bear material identifications so that they can be recycled.

Energy Saving at Fukuyama Works


Mitsubishi Electric Cooperation Fukuyama Works uses energy saving support devices such as MDU breakers and EcoServer to save energy through visualization of energy. Along with visualization, Fukuyama Works also installed high-efficiency equipments to further promote energy saving. Through energy saving activity, Fukuyama Works has successfully reduced its electrical power consumption rate by 27% in 2007 (compared with 1990).

Product Line-up
Molded-case circuit breakers
NF-C economy type NF-S standard type NF-H high-performance type NF-U ultra current-limiting type

Motor protection
Motor circuit breaker

Earth-leakage circuit breakers


NV-C economy type NV-S standard type NV-H high-performance type

MDU breakers
NF-S, NF-H types

Molded-case Circuit Breakers


Types Frame(A)

30 32

50 60 63
NF63-CV

100 125
NF125-CV NF125-SV NF125-SGV NF125-SEV

160

225 250
NF250-CV NF250-SV

400
NF400-CW NF400-SW NF400-SEW

600 630
NF630-CW NF630-SW NF630-SEW

800
NF800-CEW NF800-SDW

1000

1250

1600

NF-C economy type


NF32-SV

NF63-SV

NF-S standard type

NF160-SGV

NF250-SGV NF250-SEV NF250-HV NF250-LGV NF250-HGV NF250-HEV NF250-RGV NF250-UGV

NF1000-SEW NF1250-SEW NF1600-SEW NF800-SEW

NF-H high-performance type

NF63-HV

NF125-HV NF125-LGV NF125-HGV NF125-HEV NF125-RGV

NF160-LGV NF160-HGV

NF400-HEW

NF630-HEW

NF800-HEW

NF400-REW NF400-UEW

NF400-REW

NF800-REW NF800-UEW

NF-U ultra current-limiting type


NF125-UGV

Earth-leakage Circuit Breakers


Types Frame(A)

30 32

50 60 63
NV63-CV

100 125
NV125-CV NV125-SV NV125-SEV

160

225 250
NV250-CV NV250-SV NV250-SEV NV250-HV NV250-HEV

400
NV400-CW NV400-SW NV400-SEW

600 630
NV630-CW

800
NV800-SEW

NV-C economy type


NV32-SV

NV63-SV

NV630-SW

NV-S standard type


NV125-HV NV125-HEV
NV600-HEW NV400-HEW NV800-HEW

NV-H high-performance type

NV63-HV

Motor Protection
Types Frame(A)

30 32
NF32-SV

50 60 63
NF63-CV NF63-SV

100 125
NF125-SV

160

225 250
NF250-SV

400

600 630

800

Motor circuit breaker

MDU Breakers
Types Frame(A)

30 32

50 60 63

100 125

160

225 250
NF250-SEV NF250-HEV

400
NF400-SEP NF400-HEP

600 630
NF600-SEP NF600-HEP

800
NF800-SEP NF800-HEP

NF-S, NF-H types

New models

10

11

Ordering Information
Molded-case Circuit Breakers
Type name
NF C S H U DSN Economy type Standard type High-performance type Ultra current-limiting type DSN-type switches

Earth-leakage Circuit Breakers


Type name
NV C S H U Economy type Standard type High-performance type Ultra current-limiting type

NF250-SV
Number of poles

NV250-SV
Number of poles

2P, 3P, 4P

2P 3P 4P

NV NV NV

12W 12W 13W 33W 34W

3P
Rated current

3P
Rated current

200A
Motor protection

Please specify the rated current even for rated current adjustable types

200A
Motor protection

Please specify the rated current even for rated current adjustable types

MB
Rated voltage

Please specify MB for motor protection types

MB
Rated voltage

Please specify MB for motor protection types

Please specify DC voltage for use in DC circuit

AC

AC
Standard
Please specify applicable marine standard

100-440V 200-440V

Rated sensitivity current

30mA 100 / 200 / 500mA

100 / 200 / 500mA


Connection method
F SL B PM Front connection Solderless (box) terminal Rear connection Plug-in

Connection method

F SL B PM

Front connection Solderless (box) terminal Rear connection Plug-in

B
Built-in accessories

B
Type of residual current protection

PAL

Pre-alarm (contact output)

Blank Specify

High-speed type Time-delay type

PAL
Internal accessories
AL AX SHT UVT SLT MD F/S/V Alarm switch Auxiliary switch Shunt trip (specify rated coil voltage) Under voltage trip (specify rated coil voltage) Lead-wire terminal block Electrical operation device Operating handle Enclosure box Mechanical interlock Terminal cover (TC-L, TC-S, TTC, BTC) Handle lock device Card holder Mag Only (specify AC or DC and rated current) DC-use (specify 400, 440, 500, 550 or 600VDC) 400Hz use Low-inst (specify AC or DC and Inst. %)

Built-in accessories

MG EAL TBM PAL

Insulation switch Earth-leakage circuit alarm switch Test button module Pre-alarm module

AL, SHT (110VAC)


External accessories

MG
Internal accessories

AL AX UVT SLT

Alarm switch Auxiliary switch Under voltage trip (specify rated coil voltage) Lead-wire terminal block

AX, SLT, TBM


Special-purpose breakers
S/I/W MI TC LC / HL HL-S CH

External accessories
MD F/S/V MI Electrical operation device Operating handle Mechanical interlock Terminal cover (TC-L, TC-S, TTC, BTC) Handle lock device Card holder

Quantity

Quantity

TC LC / HL HL-S CH

10
Mag Only

10

DC400V 400Hz Low-inst

12

1. Detailed Specifications
Molded-case Circuit Breakers
NF-C (Economy type)
Frame (A) Type name 63 NF63-CV 125 NF125-CV 250 NF250-CV

Image

Rated current In (A) Number of poles Rated ambient temperature (C) Rated insulation voltage Ui (V) 690V 500V 440V 415V 400V 380V 230V 250V

Rated short-circuit breaking capacities (kA)

IEC 60947-2 (Icu/Ics)

AC

DC Rated impulse withstand voltage Uimp (kV) Current (*1) Suitability for isolation Reverse connection Number of operating Without current cycles With current (440VAC) Utilization category Pollution degree EMC environment condition (environment A or B)
a ca c b

Overall dimensions (mm)

a b c ca

Mass of front-face type (kg) (F) Front Installation (SL) Solderless (BOX) terminal and (B) Rear connections (PM) Plug-in (AL) Alarm switch (AX) Auxiliary switch (SHT) Cassette-type Shunt trip (UVT) accessories Undervoltage trip (SLT) With lead-wire terminal block (PAL) Pre-alarm Closed (S) Enclosure Dustproof (I) Waterproof (W) Electrical operation device (NFM) Mechanical interlock (MI) (*4) Panel mounting LC Handle lock device HL External HL-S accessories (F) External operating (V) handle (S) (*4) Terminal cover (TC-L, TC-S, TTC, BTC, PTC) (B-ST) Rear stud (PM) Plug-in IEC 35mm rail mounting adapters CE marking CCC recognition Automatic tripping device Trip button

3 4 (5) 6 10 (15) 16 20 25 (30) 32 40 50 (60) 63 2 3 40 600 2.5/2.5 2.5/2.5 2.5/2.5 5/5 5/5 7.5/7.5 2.5/2.5 (*5) 8 AC/DC compatible Compatible Possible 10,000 6,000 A 3 N/A 50 75 130 68 90 0.5 0.7 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped

50 (60) 63 (75) 80 100 125 3 40 600 7.5/4 10/5 10/5 10/5 10/5 30/15 7.5/4 (*2) 8 AC/DC compatible Compatible Possible 10,000 6,000 A 3 N/A 60 90 130 68 90 0.6 1.0 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped 2

(100) 125 150 175 200 225 250 2 3 40 600 10/8 15/12 25/19 25/19 25/19 36/27 15/12 (*2) 8 AC/DC compatible Compatible Possible 8,000 4,000 A 3 N/A 105 165 68 92 1.3 1.5 (*3) (*3) (*3) (*3) TV approval Recognized Thermal-magnetic Equipped

Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. *2 Use two poles for three- and four-pole products. If wired as shown on the right, three and four poles can be used for up to 400 and 500VDC, respectively. *3 The cassette-type design makes it easy for customer to install. Available for installation on side (excluding UVT). *4 Not isolation-compatible. *5 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. Not available for use with connection as shown on the right. *6 Use two poles for three- and four-pole products. If wired as shown on the right, three and four poles can be used for up to 500 and 600VDC, respectively.

Line

Line

3-pole

Load

Load 4-pole

13

NF-S (Standard type)


32 NF32-SV 63 NF63-SV 125 NF125-SV 125 NF125-SGV

3 4 (5) 6 10 (15) 16 20 25 (30) 32 3 40 600 2.5/2.5 2.5/2.5 2.5/2.5 5/5 5/5 7.5/7.5 2.5/2.5 (*5) 8 AC/DC compatible Compatible Possible 10,000 6,000 A 3 N/A 50 75 130 68 90 0.45 0.65 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped 2

3 4 (5) 6 10 (15) 16 20 25 (30) 32 40 50 (60) 63 2 3 4 40 600 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 15/15 7.5/7.5 (*5) 8 AC/DC compatible Compatible Possible 15,000 8,000 A 3 N/A 50 75 100 130 68 90 0.55 0.75 1.0 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped

(15) 16 20 (30) 32 40 50 (60) 63 (75) 80 100 125 2 3 4 40 690 8/8 18/18 25/25 30/30 30/30 30/30 50/50 40/40 (*2) 8 AC/DC compatible Compatible Possible 25,000 10,000 A 3 N/A 60 90 120 130 68 90 0.7 0.95 1.3 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped

16-20 20-25 25-32 32-40 35-50 45-63 56-80 70-100 90-125 2 3 4 40 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 20/20 (300V) (*6) 8 AC/DC compatible Compatible Possible 50,000 30,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped

Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Specify P-LT when using a plug-in product with a lead-wire terminal block. 3. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.

14

1. Detailed Specifications
Molded-case Circuit Breakers
NF-S (Standard type)
Frame (A) Type name 125 NF125-SEV 160 NF160-SGV 250 NF250-SV

Image

Available soon Rated current In (A) Number of poles Rated ambient temperature (C) Rated insulation voltage Ui (V) 690V 500V 440V 415V 400V 380V 230V 250V 16-32 32-63 63-125 3 40 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 8 AC Compatible Possible 25,000 10,000 A 3 A 105 165 68 92 1.7 2.2 140 4 2 125-160 3 4 40 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 20/20 (300V) (*2) 8 AC/DC compatible Compatible Possible 40,000 15,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped (100) 125 150 160 175 200 225 250 2 3 4 40 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 20/20 (300V) (*2) 8 AC/DC compatible Compatible Possible 25,000 10,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) TV approval Self-declaration Recognized Thermal-magnetic Equipped

Rated short-circuit breaking capacities (kA)

IEC 60947-2 (Icu/Ics)

AC

DC Rated impulse withstand voltage Uimp (kV) Current (*1) Suitability for isolation Reverse connection Number of operating Without current cycles With current (440VAC) Utilization category Pollution degree EMC environment condition (environment A or B)
a ca c b

Overall dimensions (mm)

a b c ca

Mass of front-face type (kg) (F) Front Installation (SL) Solderless (BOX) terminal and (B) Rear connections (PM) Plug-in (AL) Alarm switch (AX) Auxiliary switch (SHT) Cassette-type Shunt trip (UVT) accessories Undervoltage trip (SLT) With lead-wire terminal block (PAL) Pre-alarm Closed (S) Enclosure Dustproof (I) Waterproof (W) Electrical operation device (NFM) Mechanical interlock (MI) (*4) Panel mounting LC Handle lock device HL External HL-S accessories (F) External operating (V) handle (S) (*4) Terminal cover (TC-L, TC-S, TTC, BTC, PTC) (B-ST) Rear stud (PM) Plug-in IEC 35mm rail mounting adapters CE marking CCC recognition Automatic tripping device Trip button

(*3) (*3) (*3) (*3)

Self-declaration Recognized Electronic (effective value detection) Equipped

Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. *2 Use two poles for three- and four-pole products. If wired as shown on the right, three and four poles can be used for up to 500 and 600VDC, respectively. *3 The cassette-type design makes it easy for customer to install. Available for installation on side (excluding UVT). *4 Not isolation-compatible.

Line

Line

3-pole

Load

Load 4-pole

15

NF-L
250 NF250-SGV 250 NF250-SEV 125 NF125-LGV 160 NF160-LGV 250 NF250-LGV

Available soon 125-160 140-200 175-250 3 4 40 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 20/20 (300V) (*2) 8 AC/DC compatible Compatible Possible 25,000 10,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped 2 80-160 125-250 3 40 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 8 AC Compatible Possible 25,000 10,000 A 3 A 105 165 68 92 1.7 2.2 140 4 16-20 20-25 25-32 32-40 35-50 45-63 56-80 70-100 90-125 2 3 4 40 690 8/8 36/36 50/50 50/50 50/50 50/50 90/90 20/20 (300V) (*2) 8 AC/DC compatible Compatible Possible 50,000 30,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped 125-160 3 4 40 690 8/8 36/36 50/50 50/50 50/50 50/50 90/90 20/20 (300V) (*2) 8 AC/DC compatible Compatible Possible 40,000 15,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped 2 125-160 140-200 175-250 3 4 40 690 8/8 36/36 50/50 50/50 50/50 50/50 90/90 20/20 (300V) (*2) 8 AC/DC compatible Compatible Possible 25,000 10,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped 2

(*3) (*3) (*3) (*3)

Self-declaration Recognized Electronic (effective value detection) Equipped

Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Specify P-LT when using a plug-in product with a lead-wire terminal block. 3. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.

16

1. Detailed Specifications
Molded-case Circuit Breakers
NF-H (High-performance type)
Frame (A) Type name 63 NF63-HV 125 NF125-HV 125 NF125-HGV

Image

Rated current In (A) Number of poles Rated ambient temperature (C) Rated insulation voltage Ui (V) 690V 500V 440V 415V 400V 380V 230V 250V

Rated short-circuit breaking capacities (kA)

IEC 60947-2 (Icu/Ics)

AC

DC Rated impulse withstand voltage Uimp (kV) Current (*1) Suitability for isolation Reverse connection Number of operating Without current cycles With current (440VAC) Utilization category Pollution degree EMC environment condition (environment A or B)
a ca c b

Overall dimensions (mm)

a b c ca

Mass of front-face type (kg) (F) Front Installation (SL) Solderless (BOX) terminal and (B) Rear connections (PM) Plug-in (AL) Alarm switch (AX) Auxiliary switch (SHT) Cassette-type Shunt trip (UVT) accessories Undervoltage trip (SLT) With lead-wire terminal block (PAL) Pre-alarm Closed (S) Enclosure Dustproof (I) Waterproof (W) Electrical operation device (NFM) Mechanical interlock (MI) (*4) Panel mounting LC Handle lock device HL External HL-S accessories (F) External operating (V) handle (S) (*4) Terminal cover (TC-L, TC-S, TTC, BTC, PTC) (B-ST) Rear stud (PM) Plug-in IEC 35mm rail mounting adapters CE marking CCC recognition Automatic tripping device Trip button

10 (15) 16 20 25 (30) 32 40 50 (60) 63 2 3 4 40 690 2.5/2.5 7.5/7.5 10/8 10/8 10/8 10/8 25/19 7.5/7.5 (*5) 8 AC/DC compatible Compatible Possible 15,000 8,000 A 3 N/A 50 75 100 130 68 90 0.55 0.75 1.0 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped

(15) 16 20 (30) 32 40 50 (60) 63 (75) 80 100 125 2 3 4 40 690 10/8 30/23 50/38 50/38 50/38 50/38 100/75 8 AC Compatible Possible 25,000 10,000 A 3 N/A 90 120 130 68 90 0.6 1.0 1.2 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped

16-20 20-25 25-32 32-40 35-50 45-63 56-80 70-100 90-125 2 3 4 40 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 40/40 (300V) (*2) 8 AC/DC compatible Compatible Possible 50,000 30,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped

Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. *2 Use two poles for three- and four-pole products. If wired as shown on the right, three and four poles can be used for up to 500 and 600VDC, respectively. *3 The cassette-type design makes it easy for customer to install. Available for installation on side (excluding UVT). *4 Not isolation-compatible. *5 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. Not available for use with connection as shown on the right.

Line

Line

3-pole

Load

Load 4-pole

17

125 NF125-HEV

160 NF160-HGV

250 NF250-HV

250 NF250-HGV

250 NF250-HEV

Available soon 16-32 32-63 63-125 3 40 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 8 AC Compatible Possible 25,000 10,000 A 3 A 105 165 68 92 1.7 2.2 140 4 2 125-160 3 4 40 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 40/40 (300V) (*2) 8 AC/DC compatible Compatible Possible 40,000 15,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped 125 150 160 175 200 225 250 2 3 4 40 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 40/40 (300V) (*2) 8 AC/DC compatible Compatible Possible 25,000 10,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped 125-160 140-200 175-250 3 4 40 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 40/40 (300V) (*2) 8 AC/DC compatible Compatible Possible 25,000 10,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped 2

Available soon 80-160 125-250 3 40 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 8 AC Compatible Possible 25,000 10,000 A 3 A 105 165 68 92 1.7 2.2 140 4

(*3) (*3) (*3) (*3)

(*3) (*3) (*3) (*3)

Self-declaration Recognized Electronic (effective value detection) Equipped

Self-declaration Recognized Electronic (effective value detection) Equipped

Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Specify P-LT when using a plug-in product with a lead-wire terminal block. 3. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.

18

1. Detailed Specifications
Molded-case Circuit Breakers
NF-U (Current-limiting type ultra breaker)
Frame (A) Type name 125 NF125-RGV 250 NF250-RGV

Image

Available soon Rated current In (A) Number of poles Rated ambient temperature (C) Rated insulation voltage Ui (V) 690V 500V 440V 415V 400V 380V 230V 250V 16-20 20-25 25-32 32-40 40-50 50-63 63-80 80-100 100-125 2 3 40 690 125/125 150/150 150/150 150/150 150/150 8 AC Compatible Possible 50,000 30,000 A 3 N/A 105 165 68 92 1.5 1.8 (*1) (*1) (*1) (*1) Self-declaration Recognition in process Thermal-magnetic Equipped

Available soon 125-160 160-200 200-250 2 40 690 125/125 150/150 150/150 150/150 150/150 8 AC Compatible Possible 25,000 10,000 A 3 N/A 105 165 68 92 1.5 1.8 (*1) (*1) (*1) (*1) Self-declaration Recognition in process Thermal-magnetic Equipped 3

Rated short-circuit breaking capacities (kA)

IEC 60947-2 (Icu/Ics)

AC

DC Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Reverse connection Number of operating Without current cycles With current (440VAC) Utilization category Pollution degree EMC environment condition (environment A or B)
a ca c b

Overall dimensions (mm)

a b c ca

Mass of front-face type (kg) (F) Front Installation (SL) Solderless (BOX) terminal and (B) Rear connections (PM) Plug-in (AL) Alarm switch (AX) Auxiliary switch Cassette-type Shunt trip (SHT) accessories (UVT) Undervoltage trip (SLT) With lead-wire terminal block (PAL) Pre-alarm Closed (S) Enclosure Dustproof (I) (W) Waterproof Electrical operation device (NFM) Mechanical interlock (MI) (*2) Panel mounting LC Handle lock device HL External HL-S accessories (F) External operating (V) handle (S) (*2) Terminal cover (TC-L, TC-S, TTC, BTC, PTC) (B-ST) Rear stud (PM) Plug-in IEC 35mm rail mounting adapters CE marking CCC recognition Automatic tripping device Trip button

Notes: *1 The cassette-type design makes it easy for customer to install. Available for installation on side (excluding UVT, NF125-RGV, NF250-RGV). *2 Not isolation-compatible.

19

125 NF125-UGV

250 NF250-UGV

Available soon 16-20 20-25 25-32 32-40 40-50 50-63 63-80 80-100 100-125 2 3 40 690 15/15 200/200 200/200 200/200 200/200 200/200 200/200 8 AC Compatible Possible 50,000 30,000 A 3 N/A 105 240 68 92 2.7 4 2

Available soon 125-160 160-200 175-225 3 40 690 15/15 200/200 200/200 200/200 200/200 200/200 200/200 8 AC Compatible Possible 25,000 10,000 A 3 N/A 105 240 68 92 2.7 4

140

140

2.5

3.7

2.5

3.7

(*1) (*1) (*1) (*1)

(*1) (*1) (*1) (*1)

Self-declaration Thermal-magnetic Equipped


Remarks: 1. Specify P-LT when using a plug-in product with a lead-wire terminal block. 2. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.

Self-declaration Thermal-magnetic Equipped

20

1. Detailed Specifications
Earth-leakage Circuit Breakers
NV-C (Economy type) Harmonic surge ready
Frame (A) Type name 63 NV63-CV 125 NV125-CV 250 NV250-CV

Image

Rated current In (A) Number of poles Rated ambient temperature (C) Phase line (*1) Rated operational voltage Ue (V) High-speed type Max. operating time Rated current sensitivity Max. operating time Internal non-operating time Earth-leakage indication system Time-delay type Rated short-circuit breaking capacity (kA) (s)

(5) (10) (15) 16 20 25 (30) 32 40 50 (60) 63 2 40 (*2) (mA) at In at 5In AC 33W, 12W 100-440 30,100/200/500 30 selectable 0.1 0.04 Mechanical type (button) 2.5/2.5 2.5/2.5 5/5 7.5/7.5 7.5/7.5 7.5/7.5 6 AC Compatible 10,000 6,000 A 2 A 75 130 68 90 0.7 0.75 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Thermal-magnetic Equipped 12W 100-240 3

(60) 63 (75) 80 100 125 3 40 33W, 12W 100-440 30, 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 10/5 10/5 10/5 30/15 30/15 30/15 6 AC Compatible 10,000 6,000 A 2 A 90 130 68 90 1.0 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Thermal-magnetic Equipped

125 150 175 200 225 250 3 40 33W, 12W 100-440 30, 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 15/12 25/19 25/19 36/27 36/27 36/27 6 AC Compatible 8,000 4,000 A 2 A 105 165 68 92 1.7 (*5) (*5) (*5) (*5) (*6) TV approval Recognized Thermal-magnetic Equipped

Rated current sensitivity

(mA) (s) (*4) (s) (or more) 440V 415V 400V 230V 200V 100V

IEC 60947-2 (Icu/Ics)

AC

Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Number of operating Without current cycles With current Utilization category Pollution degree EMC environment condition (environment A or B)
a ca c b

Overall dimensions (mm)

a b c ca

Mass of front-face type (kg) (F) Front Installation (SL) Solderless (BOX) terminal and (B) Rear connections (PM) Plug-in (AL) Alarm switch (AX) Auxiliary switch Cassette-type Shunt trip (SHT) accessories (UVT) Undervoltage trip (SLT) With lead-wire terminal block (TBM) Test button module Closed (S) Enclosure Dustproof (I) Waterproof (W) Electrical operation device (NFM) Mechanical interlock (MI) (*8) Panel mounting LC Handle lock device HL External HL-S accessories (F) External operating (V) handle (S) (*8) Terminal cover (TC-L, TC-S, TTC, BTC) (B-ST) Rear stud (PM) Plug-in IEC 35mm rail mounting adapters CE marking CCC recognition Automatic tripping device Trip button

Notes: *1 For the 12W supply system, use the right and left pole terminals. Caution is required in this case as the center pole is a live part. *2 Rated operational voltage of time-delay type is for 200-440V. *3 Time-delayed types are produced for current specifications of 20A or more. *4 When operating times are 0.45s, 1.0s and 2.0s, the relay operates between 0.15s and 0.45s, 0.6s and 1.0s, and 1.2s and 2.0s, respectively.

*5 The cassette-type design makes it easy for customer to install. Available for installation on side (excluding UVT). *6 All models have a vertical lead terminal unit (SLT) as standard. *7 For other models, please order in conjunction with the circuit breaker. *8 Not isolation-compatible.

21

NV-S (Standard type) Harmonic surge ready


32 NV32-SV 63 NV63-SV 125 NV125-SV 125 NV125-SEV

Available soon (5) 6 10 (15) 16 20 25 (30) 32 3 40 33W, 12W 100-440 30, 100/200/500 selectable 0.1 0.04 Mechanical type (button) 5/5 5/5 5/5 10/10 10/10 10/10 6 AC Compatible 10,000 6,000 A 2 A 75 130 68 90 0.75 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Thermal-magnetic Equipped (5) (10) (15) 16 20 25 (30) 32 40 50 (60) 63 3 40 33W, 12W 100-440 30, 100/200/500 selectable 0.1 0.04 Mechanical type (button) 7.5/7.5 7.5/7.5 7.5/7.5 15/15 15/15 15/15 6 AC Compatible 15,000 8,000 A 2 A 75 130 68 90 0.8 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Thermal-magnetic Equipped (15) 16 20 (30) 32 40 50 (60) 63 (75) 80 100 125 (*3) 3 40 33W, 12W 100-440 34W 200-440 4 3 40 33W, 12W 100-440 34W 63-125 4

30, 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 25/25 30/30 30/30 50/50 50/50 50/50 6 AC Compatible 25,000 10,000 A 2 A 90 130 68 90 1.1 1.4 120

(*5) (*5) (*5) (*5)

(*6) Self-declaration Recognized Thermal-magnetic Equipped

(30) 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 36/36 36/36 36/36 85/85 85/85 85/85 6 AC Compatible 25,000 10,000 A 2 A 105 140 165 68 92 1.9 2.5 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Electronic (effective value detection) Equipped

Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. The circuit breakers will be delivered with rated current sensitivity set to 500mA and operating time of time-delayed types to 2.0s unless otherwise specified. 3. Specify P-LT when using a plug-in product with a lead-wire terminal block. 4. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.

(5)

Applicable circuit voltage Available voltage range Rated operational voltage 100/110/200/220/230/240V 80~264V 100-240V 100/110/200/220/240/254/265/380/400/415/440V 80~484V 100-440V 200/220/240/254/265/380/400/415/440V 160~484V 200-440V 100/110/200/220/240/254/265/380/400/415/440V 80~484V 100-200-415V 200/220/240/254/265/380/400/415/440V 160~484V 200-415V

22

1. Detailed Specifications
Earth-leakage Circuit Breakers
NV-S (Standard type) Harmonic surge ready
Frame (A) Type name 250 NV250-SV 250 NV250-SEV

NV-H
63 NV63-HV

Image

Available soon Rated current In (A) Number of poles Rated ambient temperature (C) Phase line type (*1) Rated operational voltage Ue (V) High-speed type Max. operating time Rated current sensitivity Max. operating time Internal non-operating time Earth-leakage indication system Time-delay type Rated short-circuit breaking capacity (kA) (s) 125 150 175 200 225 250 3 40 (*2) (mA) at In at 5In AC 33W, 12W 100-440 34W 200-440 4 125-250 3 40 33W, 12W 100-440 (15) 16 20 (30) 32 40 50 (60) 63 3 40 33W, 12W 100-440 30, 100/200/500 selectable 0.1 0.04 Mechanical type (button) 10/8 10/8 10/8 25/19 25/19 25/19 6 AC Compatible 15,000 8,000 A 2 A 75 130 68 90 0.8 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Thermal-magnetic Equipped

Rated current sensitivity

(mA) (s) (*4) (s) (or more) 440V 415V 400V 230V 200V 100V

IEC 60947-2 (Icu/Ics)

AC

Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Number of operating Without current cycles With current Utilization category Pollution degree EMC environment condition (environment A or B)
a ca c b

Overall dimensions (mm)

a b c ca

Mass of front-face type (kg) (F) Front Installation (SL) Solderless (BOX) terminal and (B) Rear connections (PM) Plug-in (AL) Alarm switch (AX) Auxiliary switch (SHT) Cassette-type Shunt trip (UVT) accessories Undervoltage trip (SLT) With lead-wire terminal block (TBM) Test button module Closed (S) Enclosure Dustproof (I) Waterproof (W) Electrical operation device (NFM) Mechanical interlock (MI) (*8) Panel mounting LC Handle lock device HL External HL-S accessories (F) External operating (V) handle (S) (*8) Terminal cover (TC-L, TC-S, TTC, BTC) (B-ST) Rear stud (PM) Plug-in IEC 35mm rail mounting adapters CE marking CCC recognition Automatic tripping device Trip button

(30) 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 36/36 36/36 36/36 85/85 85/85 85/85 6 AC Compatible 25,000 10,000 A 2 A 105 165 68 92 1.9 (*5) (*5) (*5) (*5) (*6) TV approval Self-declaration Self-declaration Recognized Recognized Electronic (effective value detection) Thermal-magnetic Equipped Equipped (30) 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 36/36 36/36 36/36 85/85 85/85 85/85 6 AC Compatible 25,000 10,000 A 2 A 105 140 165 68 92 1.9 2.5 (*5) (*5) (*5) (*5) (*6)

Notes: *1 When wiring a three-pole earth-leakage circuit breaker to 12W, do not use the central pole but connect to the left and right poles. *2 Rated operational voltage of time-delay type is for 200-440V. *3 Time-delayed types are produced for current specifications of 20A or more. *4 When operating times are 0.45s, 1.0s and 2.0s, the relay operates between 0.15s and 0.45s, 0.6s and 1.0s, and 1.2s and 2.0s, respectively.

*5 The cassette-type design makes it easy for customer to install. Available for installation on side (excluding UVT). *6 All models have a vertical lead terminal unit (SLT) as standard. *7 For other models, please order in conjunction with the circuit breaker. *8 Not isolation-compatible.

23

(High-performance type) Harmonic


125 NV125-HV

surge ready
250 NV250-HV 250 NV250-HEV

125 NV125-HEV

Available soon (15) 16 20 (30) 32 40 50 (60) 63 (75) 80 100 125 (*3) 3 40 33W, 12W 100-440 34W 200-440 4 3 40 33W, 12W 100-440 34W 33W, 12W 100-440 63-125 4 125 150 175 200 225 250 3 40 34W 200-440 4

Available soon 125-250 3 40 33W, 12W 100-440 (30) 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 65/65 70/70 75/75 100/100 100/100 100/100 6 AC Compatible 25,000 10,000 A 2 A 105 165 68 92 1.9 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Electronic (effective value detection) Equipped
Applicable circuit voltage 100/110/200/220/230/240V 100/110/200/220/240/254/265/380/400/415/440V 200/220/240/254/265/380/400/415/440V 100/110/200/220/240/254/265/380/400/415/440V 200/220/240/254/265/380/400/415/440V Available voltage range 80~264V 80~484V 160~484V 80~484V 160~484V

30, 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 50/38 50/38 50/38 100/75 100/75 100/75 6 AC Compatible 25,000 10,000 A 2 A 90 120 130 68 90 1.1 1.4 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Thermal-magnetic Equipped

(30) 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 65/65 70/70 75/75 100/100 100/100 100/100 6 AC Compatible 25,000 10,000 A 2 A 105 140 165 68 92 1.9 2.5 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Electronic (effective value detection) Equipped

30, 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 65/65 70/70 75/75 100/100 100/100 100/100 6 AC Compatible 25,000 10,000 A 2 A 105 140 165 68 92 1.8 2.5 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Thermal-magnetic Equipped
(5)
Rated operational voltage 100-240V 100-440V 200-440V 100-200-415V 200-415V

Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. The circuit breakers will be delivered with rated current sensitivity set to 500mA and operating time of time-delayed types to 2.0s unless otherwise specified. 3. Specify P-LT when using a plug-in product with a lead-wire terminal block (excluding 63A frame or smaller). 4. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells. 5. Please contact us for 4 pole of NV250-SEV, NV250-HEV.

24

1. Detailed Specifications
Motor-protection Breakers
NF - MB (Motor breakers)
Frame (A) Type name 32 NF32-SV 50 NF63-CV NF63-SV

A 32 25 16 12 10 8 7.1 5 4

Rated current In (A) Rated motor capacity (kW)

200/220V 400/440V kW kW 7.5 15 11 5.5 7.5 3.7 5.5 2.2 3.7 1.5 2.2 1.5 0.75

A 45 40 32 25 16 12 10 8

200/220V 400/440V kW kW 22 11 18.5 15 7.5 11 5.5 7.5 3.7 5.5 2.2 3.7

A 7.1 5 4

200/220V 400/440V kW kW 1.5 2.2 1.5 0.75

Number of poles Rated ambient temperature (C) Rated insulation voltage Ui (V) Rated short-circuit breaking capacity (kA) IEC 60947-2 (Icu/Ics) 440V 415V 400V 380V 230V

AC

Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Reverse connection Number of operating Without current cycles With current (440VAC) Utilization category Pollution degree EMC environment condition (environment A or B)
a ca c b

Overall dimensions (mm)

a b c ca

Mass of front-face type (kg) Installation (F) Front and (B) Rear connections Plug-in (PM) (AL) Alarm switch (*1) (AX) Auxiliary switch (*1) Cassette-type (SHT) Shunt trip (*1) accessories (UVT) Undervoltage trip (*1) (SLT) With lead-wire terminal block Closed (S) Enclosure Dustproof (I) Waterproof (W) Electrical operation device (NFM) Mechanical interlock (MI) (*2) Panel mounting LC Handle lock device HL External HL-S accessories (F) External operating (V) handle (S) (*2) Terminal cover (TC-L, TC-S, TTC, BTC) (B-ST) Rear stud (PM) Plug-in IEC 35mm rail mounting adapters CE marking CCC recognition Automatic tripping device Trip button

3 40 500 2.5/2.5 2.5/2.5 5/5 5/5 7.5/7.5 8 AC Compatible Possible 10,000 6,000 A 3 N/A 75 130 68 90 0.65 Self-declaration Recognized Thermal-magnetic Equipped

3 40 500 2.5/2.5 2.5/2.5 5/5 5/5 7.5/7.5 8 AC Compatible Possible 10,000 6,000 A 3 N/A 75 130 68 90 0.65 Self-declaration Recognized Thermal-magnetic Equipped

3 500 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 15/15 8 AC Compatible Possible 15,000 8,000 A 3 N/A 75 130 68 90 0.7 Self-declaration Recognized Thermal-magnetic Equipped

Notes: *1 The cassette-type design makes it easy for customer to install. Available for installation on side (excluding UVT). *2 Not isolation-compatible.

25

100 NF125-SV

225 NF250-SV

200/220V 400/440V kW kW 100 55 90 22 45 71 18.5 37 63 15 30 45 11 22 (40) 19 32 7.5 15 (25) 5.5 11 (16) 3.7 7.5 (12.5) 5.5 A

A 225 200 175 150 125

200/220V 400/440V kW kW 110 55 90 45 75 37 30

3 40 500 25/25 30/30 30/30 30/30 50/50 8 AC Compatible Possible 25,000 10,000 A 3 N/A 90 130 68 90 0.95 Self-declaration Recognized Thermal-magnetic Equipped

3 40 500 36/36 36/36 36/36 36/36 85/85 8 AC Compatible Possible 25,000 10,000 A 3 N/A 105 165 68 92 1.6 TV approval Recognized Thermal-magnetic Equipped

Remarks: 1. The motor circuit breakers do not have an applicable rated motor capacity. Select a motor circuit breaker based on the total load current of the motor. 2. Products with rating parenthesized are produced when an order is placed. 3. Specify P-LT when using a plug-in product with a lead-wire terminal block. 4. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.

26

2. Special-purpose Breakers
Mag Only, DC and DSN

Mag Only (Instantaneous tripping circuit breakers)


NF63-CV/SV/HV NF125-CV/SV/HV Fixed NF250-CV/SV/HV NF125-SGV/LGV/HGV NF160-SGV/LGV/HGV NF250-SGV/LGV/HGV AC, DC AC, DC AC, DC AC, DC 10 times rated current (AC) (DC) Remarks: 1. The size, weight, accessories, etc., are all identical to the same-designation C, S and H Series breakers. 2. For more details, please contact your dealer.

DC MCCBs and DSN Switches


Breaking is more difficult with direct currents because the current value never reaches zero. While ordinary DC breakers are suitable for low voltages, special-voltage DC breakers are recommended for voltages in excess of 250VDC. Breakers for 550V are all 4-pole models. The size, shape, drilling plan, accessories, etc., are all identical to the S Series breakers with the same designations.
Type Number of poles Rated voltage (VDC) Rated breaking capacity (kA) IEC 60947-2 (Icu/Ics)

Wiring diagram for DC use.

Wiring diagram for DC use Remark: 1. The tripping characteristics will change if the wiring differs from that shown here.

NF63-SV
3 400 2/2 4 550

NF125-SV
3 440 4 550

NF250-SV
3 500 4 600

10/10

20/20

Remark: 1. Time constant: 10ms or below.

DC side These breakers are designed as thyristor-Leonard system DC-side breakers. They protect the thyristor from short circuiting when there is a power or communication failure (Mag-only breakers can also be used for this purpose). Use these breakers in combination with fast fuses for even greater protection.
Type Number of poles Rated voltage (VDC) Rated breaking capacity (kA) IEC 60947-2 (Icu/Ics) Instantaneous trip current (min.)

NF125-SV
2 250 40/40 3 440 10/10

NF250-SV
2 300 20/20 3 times rated current 3 500

3 times rated current

DSN switches These are standard MCCBs without the automatic tripping element. The tripping capacity is approximately six times the rated current. The appearance, size, drilling plan and available accessories are all identical to similar standard S and C Series MCCBs.
Type Rated current (A) Number of poles Rated voltage (AC/DC) Max. switching current (AC/DC)

DSN63-CV
63 2 500/ 250 378/155 3

DSN125-CV
125 2 500/ 250 750/ 310 3

DSN250-CV
250 2 500/ 250 1500/ 625 3

Type Rated current (A) Number of poles Rated voltage (AC/DC) Max. switching current (AC/DC)

DSN32-SV
32 2 3

DSN63-SV
63 2 3

DSN125-SV DSN125-SGV DSN160-SGV DSN250-SV DSN250-SGV


2 125 3 690/250 750/310 4 2 125 3 690/300 750/315 4 2 160 3 690/300 960/400 4 2 250 3 690/250 1500/625 4 2 250 3 690/300 1500/625 4

500/250 192/80

500/250 378/155

27

2. Special-purpose Breakers
400Hz, Instantaneous and Generator Protection

400Hz MCCBs
Standard MCCBs cannot be used in 400Hz circuits. When standard MCCBs are used in high-frequency circuits (eq. 400Hz), the instantaneous characteristics are shifted higher. The 400Hz MCCB is recommended for use in 400Hz circuits.
Type Rated current (A) Number of poles Rated insulation voltage (V) 690V 500V Rated breaking capacity (kA) 440V IEC 60947-2 (Icu / Ics) 400V 230V

Specifications The appearance, size, rated interrupting capacity, drilling plan, accessories, etc., are all identical to the standard S and H Series breakers of the same designation.
NF250-SV
125, 150 175, 200 2 690 3 8/8 30/30 36/36 36/36 85/85 4 2

NF125-SV
16, 20, 32, 40, 50, 63, 80, 100 2 3 8/8 18/18 25/25 30/30 50/50 4

NF125-HV
16, 20, 32, 40, 50, 63, 80, 100 2 3 10/8 30/23 50/38 50/38 100/75 4

NF250-HV
125, 150 175, 200 3 10/8 50/38 65/65 75/75 100/100 4

Low-instantaneous MCCBs
Low-Inst. MCCBs for Discrimination When a power fuse (PF) is used for high-voltage protection, make sure that the MCCB on the secondary side is compatible.
Type Number of poles Rated current (A) 600 400

Specifications

NF125-CV
2 3 2

NF125-SV
3 4

NF250-CV
2 3 2

NF250-SV
3 125, 150, 175 200, 225, 250 4

PF Time

Tr1

MCCB operating characteristic curve

PF short-time tolerance capacity

50, 63, 80, 100, 125

16, 20, 32, 40 125, 150, 175 50, 63, 80, 100,125 200, 225, 250

MCCB 1

Low-inst. MCCBs

Instantaneous trip (% of rated current)

MCCB 2

Current

Remarks: 1. Ensure compatibility with motor, etc., before use to prevent accidental tripping at start up. 2. Specify rated current and tripping characteristics. 3. There are no short time delay characteristics.

Fig. 4.12 Low-inst. MCCB characteristics The appearance, size, rated interrupting capacity, accessories, etc., are all identical to the standard instantaneous trip breakers of the same designation.

Generator Protection MCCBs


These breakers are designed for generator protection. Specifications
Type Number of poles

NF125-SEV
3 16-32 32-63 63-125 adjustable

NF125-HEV
3 16-32 32-63 63-125 adjustable

NF250-SEV
3 80-160 125-250 adjustable

NF250-HEV
3 80-160 125-250 adjustable

Rated current (A)

Instantaneous trip (% of rated current) Operating time at 150% of rated current (s) Rated insulation voltage (V) 690VAC 500VAC Rated breaking capacity (kA) IEC 60947-2 (Icu/Ics) 440VAC 400VAC 230VAC 8/8 30/30 36/36 36/36 85/85 10/8 50/38 65/65 75/75 100/100

300 (*1) 18~28 (*1) 690 8/8 30/30 36/36 36/36 85/85 10/8 50/38 65/65 75/75 100/100

Note: *1 The MCCB operating characteristics must be adjusted as follows. STD 3 (Is setting) LTD: minimum setting (TL = 12s setting)

28

2. Special-purpose Breakers
MDU Breakers

Measuring Display Unit (MDU)


Features

Available soon

Circuit breakers and measurement display units are integrated. With built-in VT and CT, the circuit breaker requires less space and contributions are made to reduced work and energy savings.

A low-voltage circuit breaker combines an MDU for measuring, displaying, and transmitting information on cable ways, and closely monitors energy consumption by measuring current, voltage, power, electric energy, harmonic current, leakage current, power factor, etc., to assist in energy savings. Since the circuit breaker saves its tripping information (causes and current values), causes of accidents can be investigated and corrected sooner.

Type Frame (A) Number of poles Suitability for use Rated insulation voltage (V) Rated current (A) Rated short-circuit breaking capacities (kA) AC IEC60947-2 (Icu/Ics) 690V 500V 440V 415V 400V 380V 230V 200V Reverse connection Installation and connections Front connection (F) Rear connection (R) Cassette-type accessories External accessories (*1)
Note: *1 For models with DP, the accessories below are not applicable. Electrical operation device (NFM) Mechanical interlock (MI) External operating handle (F, V, S) Handle lock device (HL-S) Enclosure (S, I, W)

NF250-SEV with MDU 250 3 33W 690 125-250A (adjustable) 8/8 18/18 36/36 36/36 36/36 36/36 85/85 85/85 Refer to P.16 Refer to P.16 4 34W 3

NF250-HEV with MDU 250 4 34W 690 125-250A (adjustable) 10/8 30/23 50/50 70/70 75/75 75/75 100/100 100/100 Refer to P.18 Refer to P.18

33W

Display (DP) on the breaker 4 Combination 1 2 1 2 1

Panelboard mounting 4 1

3 NF250-SEV/HEV with DP NF250-SEV/HEV Module (power input) Module (power input + transmission) Module (pre-alarm) MDU-DP-N (display) MDU-DP-C (display + network) Measuring Load current Line voltage Power (active/reactive) Energy (active/reactive) Display 14 Harmonic current Power factor Frequency Alarm OVER Trip cause (LTD, STD, INST) & trip current Pre-alarm Transmission 2 CC-Link Pulse output (electric energy) 2-a 2-b 3 2-a 2-b 3 4-a 4-b 3 4-a 1-a 1-a 1-a 1-a 1-b 1-b 1-b

1-b

4-b

29

Display on the circuit breaker body


Front connection
Insulation barrier (removable) Mtg hole Trip Button M8 bolt 18 (hex-socket) (65) 25 100 38.5 3 24 Mtg hole Trip Button 4.5 Insulation barrier (removable) 100 M8 bolt (hex-socket)

24

133 144 165 102 86.5

144 165

102 50

Operating characteristics selector

45 61 68 77 92

22 70 105

35 105 140 MDU unit

Operating characteristics selector

100

8.5

100

8.5

45 61 4 68 72 92

Neutral pole

22 70 105

35 105 140

Neutral pole

3-pole

4-pole

3-pole

4-pole

Breaker mounting

Panel mounting

Rear connection
Mtg plate t max.=3.2 Stud can be rotated 90 Insulation tube 4-pole 3-pole Mtg plate Stud can be t max.=3.2 rotated 90 Insulation 4-pole Breaker tube 3-pole 39.5 4-pole 3-pole Breaker

4-pole 3-pole

20

20

Connection allowance 22

R1

144

144

Connection allowance 22 15

88.5

15 68 77 MDU unit 71 106

M40.7 32.5 breaker 15 mtg screw 70 100 105 Insulation 9 1mm clearance tube M8 bolt on each side of handle Breaker mounting Front-plate cutout 6

6 15 9 M8 bolt 70 105

M40.7 breaker mtg screw

32.5 100

68 72

71 106

Insulation 1mm clearance tube on each side of handle Front-plate cutout Panel mounting

MDU Terminal
Breaker mounting
MDU terminal In the figure below the terminal cover is removed. Control power FG Control power P1 M3 screw Control power P2

Connector (removable)

1 2 3 4 5 6

1 2 No transmission Pulse output SLD CC-Link

3 4 5 114 DG DB

6 113 DA

52

4.5

30

2. Special-purpose Breakers
MDU Breakers
MDU panel mounting
Front connection
10 Insulation barrier (removable) 100 Mtg hole Trip Button M8 bolt (hex-socket)
8 .5

C 1

24

Breaker

25max. 144 165 102 50 4.5 or 9


8 .5

Operating characteristics selector

100

8.5

45 61 4 68 72 92 25max. 35 35 M40.7 (Bus t max.=7) or 5 4-pole 3-pole Bus drilling for direct connection Drilling plan

22 70 105

35 105 140

Neutral pole

3-pole

4-pole

Panel mounting

Rear connection
Mtg plate Stud can be t max.=3.2 rotated 90 Insulation 4-pole tube 3-pole 4-pole 3-pole Breaker Breaker

144

20

Connection allowance 22 15

6 15 9 M8 bolt 70 105

M40.7 breaker mtg screw

32.5 100 35 70

24 M40.7 or 5

68 72

71 106

Insulation 1mm clearance tube on each side of handle Front-plate cutout Panel mounting

35 35 105

3-pole

4-pole Drilling plan

MDU Terminal for panel mounting


Panel mounting
MDU terminal In the figure below the terminal cover is removed. 14.5 90 70 *Panel thickness 1~3.2mm Operation and display side 90

MDU connector

Panel holder plate 1 2 3 4 5 6 P2 P1 70 90 Control power

90

Terminal block

R2

72

91 35

Front-panel cutout

1 2 3 4 5 No transmission FG Pulse output 113 114 FG CC-Link DA DB DG SLD FG

126 144 6

31

72

52

126

1 C

3. Connection Method
1. Connection Types
Table 3-1: Connection types
Connection method (abbreviation) The front connection model will be delivered unless otherwise specified. Front connection models can be converted to other types using an appropriate connection component (separately available).

Front connection (F)

Rear connection (B)

Plug-in (PM)

Image

NF-C/S/H Series NF-U Series NV-C/S/H Series

(2P and 3P only)

2. Connection Accessories
Table 3-2: List of connection accessories
Type name NF32-SV, NF63-CV/SV/HV NV32-SV, NV63-HV NV63-CV/SV NF63-SV/HV NF125-CV/SV NF125-HV NF125-CV/SV, NV125-CV/SV NF125-HV, NV125-HV NF125-SV, NV125-SV, NF125-ZSV NF125-HV, NV125-HV, NF125-ZHV NF250-CV/SV NF250-HV NF250-CV/SV, NF125-SEV, NF250-SEV, NF125-SGV/LGV/HGV, NF160-SGV/LGV/HGV, NF250-SGV/LGV/HGV, NV250-CV/SV, NV125-SEV, NV250-SEV NF250-HV, NF250-HEV, NV250-HV, NV250-HEV, NF125-HEV, NV125-HEV NF125-SEV, NV125-SEV, NF250-SV, NF250-SEV, NV250-SV, NV250-SEV (*5) NF250-HV, NF250-HEV, NV250-HEV (*5), NF125-HEV, NV125-HEV 2P 3P 2P 4P 2P 3P 4P 2P SL-1SV4L (*1) SL-1SV4G (*2) SL-1SV3L (*1) SL-1SV3G (*2) SL-1SV4L (*1) SL-1SV4G (*2) SL-2SV4L (*3) SL-2SV4G (*4) SL-2SV3L (*3) SL-2SV3G (*4) SL-2SV4L (*3) SL-2SV4G (*4) SL-2SV4L (*3) SL-2SV4G (*4) SL-2SV3L (*3) SL-2SV3G (*4) SL-2UV4L (*3) SL-2UV4G (*4) SL-2UV3L (*3) SL-2UV3G (*4) SL-2UV4L (*3) SL-2UV4G (*4) Solderless terminal (SL) Rear studs (B-ST) (ST-05SV2) (ST-05SV3) (ST-05SV2) (ST-05SV4) (ST-1SV2) (ST-1HV2) (ST-1SV3) (ST-1SV4) (ST-2SV2) Plug-in (PM) (PM-05SV2) (PM-05SV3) (PM-NV05SV2) (PM-05SV4) (PM-1SV2) (PM-1HV2) (PM-1SV3) (PM-1SV4) (PM-2SV2)

3P

(ST-2SV3)

(PM-2SV3)

4P 2P

(ST-2SV4)

(PM-2SV4) (PM-2SV2) (PM-2SV3) (PM-2UV2) (PM-2UV3)

NF125-RGV, NF250-RGV 3P 2P NF125-UGV, NF250-UGV 3P 4P


Notes: *1 Connected wire size : 2.5 ~ 25mm2 *2 Connected wire size : 25 ~ 70mm2 *3 Connected wire size : 14 ~ 95mm2 *4 Connected wire size : 70 ~ 125mm2 *5 Please contact us for 4 pole of NV250-SEV, NV250-HEV.

3. Connection of Line and Load


The standard wiring of line and load on the circuit breaker is as shown in (a) normal connection on the right. Avoid the wiring shown in (b) reverse connection. This may lead to a decrease in breaking performance. However, the reverse connection is allowed for the following models (excluding models with MDU).
NF-C, NF-S, NF-H, NF-U and MB Series Reverse connection is allowed for the standard models. Load (a) Normal connection Line (b) Reserve connection Line Load

Normal and reverse connection methods

32

4. Accessories
Internal Accessories

1. Accessories
Table 4-1: Accessories
Internal accessories Alarm switch Auxiliary switch Function Electrically indicates the trip status of the circuit breaker. Electrically indicates the ON/OFF status of the circuit breaker. NF-C/S/H/U NV-C/S/H/U Applicable models Cassette-type accessories

Shunt trip

Electrically trips the circuit breaker from a remote distance. Permissible working voltages are 70 to 110% of the AC rated voltage or 70 to 125% of the DC rated voltage. Automatically trips the circuit breaker if the voltage is lowered. Working voltages are 70 to 35% of the UVT rated voltage. When the voltage recovers to 85% or higher, it is possible to reset the device and restart operation. Allows remote testing through application of a voltage. An external sequence common to SHT can be used. (The standard configuration requires the vertical lead-wire terminal unit (SLT).) Indicates that the load current exceeds the pre-alarm setting current.

NF-C/S/H/U NV-C/S/H/U

Undervoltage trip

NF-C/S/H/U NV-C/S/H/U

Test button module (*1) Pre-alarm module

NV-C/S/H

Electronic type

2. Switch Operation and Rating


Table 4-2: AL switch operation
Circuit breaker status AL switch contact
98/ALa (open) 96/ALb (closed) 95/ALc 98/ALa (closed) 96/ALb (open) 95/ALc

Table 4-4: ALAX switch rating


Switch type
AC Voltage (V) 460 3 5 Current (A) Resistive load Inductive load 2 3 Voltage (V) 250 125 30 0.2 0.4 4 DC Current (A) Resistive load Inductive load 0.2 0.4 3

OFF or ON

250 125

Trip

Please contact us regarding applications requiring smaller current values.

Table 4-3: AX switch operation


Circuit breaker status AX switch contact
14/AXa (open) 12/AXb (closed) 11/AXc 14/AXa (closed) 12/AXb (open) 11/AXc

OFF or Trip

ON

33

3. Maximum Number of Internally Mounted Accessories


Left-side mounting Handle Right-side mounting AL AX TBM SHT or UVT Lead-wire direction

Table 4-9: Combinations of accessories


Series NF

Cassette-type accessories NV

NF63-CV, NF125-CV

NF63-CV, NF125-CV, NF250-CV

NV63-CV, NV125-CV, NV250-CV

S Type

NF32-SV, NF63-SV, NF125-SV

NF32-SV, NF63-SV, NF125-SV NF125-SEV, NF125-SGV, NF160-SGV NF250-SV, NF250-SEV, NF250-SGV NF125-LGV, NF160-LGV, NF250-LGV

NV32-SV, NV63-SV, NV125-SV, NV125-SEV NV250-SV, NV250-SEV (*5)

NF63-HV

NF63-HV, NF125-HV, NF125-HEV NF125-HGV, NF160-HGV NF250-HV, NF250-HEV, NF250-HGV

NV63-HV, NV125-HV, NV125-HEV NV250-HV, NV250-HEV (*5)

NF125-RGV, NF125-UGV NF250-RGV, NF250-UGV 2 2, 3, 4 S 2, 3, 4

Poles AL/AX (standard) switches

AL

AX

AL + AX (*2) SHT or UVT (*1) AL + SHT or UVT (*1) AX + SHT or UVT (*1) (*1) (*3) (*1) (*2)

AL + AX + SHT or UVT (*1) TBM (*4)


Notes: *1 *2 *3 *4 Models with UVT require a UVT voltage module to be installed on the lead-wire terminal unit (no such voltage module is required for SHT). Second AX can be substituted for the AL on the left pole. SHT and UVT for left-pole installation can be produced if specified. Only the models with an SLT are available. EAL and PAL require a control power supply (shared 100 - 200VAC). For the 24VDC TBM only, please specify control voltage (the standard shared voltage is 100 - 240VAC/100 - 240VDC). *5 Please contact us for 4 pole of NV250-SEV, NV250-HEV.

Remarks: 1. Circled numbers indicate the order of installation. 2. Accessories of EAL, and TBM can be installed independent of installations of AL, AX, and MG (two units among EAL and TBM cannot be installed at the same time).

34

4. Accessories
Internal Accessories

4. Shunt Trip
Table 4-10: Standard coil rating
Series Cut-off switch

(SHT)
Input power requirement (VA) (*1) Voltage 100V 240V AC 380V 550V DC 100V 100-125V Operating time (ms) (*2)

All models

Equipped

100-240VAC 380-550VAC (Compatible to 50 and 60Hz) 100-125VDC

120

50

15 or less

Notes: *1 Secure a sufficient input power so that the voltage will not drop below the permissible lower working voltage (70% of the lowest rated voltage). *2 The operating time denotes the time from when the rated voltage is applied to SHT until when the main contact of the breaker starts to open.

5. Undervoltage Trip
Table 4-11: Standard coil rating
Series Voltage 100-130VAC/VDC (*1) All models 200-250VAC 380-480VAC (Compatible to 50 and 60Hz) 5 30 or less Input power VA (*1) (*2)

(UVT)
UVT Voltage Module
Circuit breaker D2

UVT voltage module D1 J1 J2


J1 J2

Operating time (ms)

The UVT voltage module is normally installed on the vertical lead-wire terminal unit (SLT) (a separate-mount type can be produced on request).

Notes: *1 The operating time denotes the time from when no voltage is applied to UVT until when the main contact of the breaker starts to open. *2 Time-delayed types can be produced. Details are available on request.

UVT voltage module wiring diagram (lead-wire connection)

6. Test Button Module


Table 4-12
Series Input rated control voltage Input control power (VA) NV-C/S/H, Compatible with 100-240VAC/VDC 1.5 or less 24VDC (*1)

(TBM)

Press the test button on the main body of the breaker while control voltage is applied to test the unit. The voltage must be applied to the main body of the breaker for more than two seconds when testing time-delayed NV models All models have a vertical lead terminal unit (SLT) as standard
18

TBM2 TBM1 87 (Terminal cover) 10.5 (10.5) 7 12.5 Ring-mark example 98/ALa , 96/ALb , 95/ALc C1/S1 , C2/S2

Note: *1 100-240VAC and 100-240VDC specifications are standard unless otherwise specified. Specifications for 24VDC are available on request.

7. Lead-wire Specifications
Table 4-13
Type Heatresistant wire Size Length (*1) 450mm Marking A ring-mark with the terminal symbol is attached to each lead wire 0.5mm2

Note: *1 400mm for models with four poles and right-pole installation.

Lead wires are normally extended laterally Grooves are provided on the side of the breaker for extending lead wires on the side of the breaker
18

8. Vertical Lead-wire Terminal Block


The circuit beaker can be mounted, and closely fitted, to the unit Terminal screws are arranged in a zigzag pattern, and screws can be tightened further after wiring A terminal cover is provided For front connection, rear connection and plug-in models (excluding PLT)

(SLT)
86.5 M3.5 M3.5 terminal screw

35

9. Cassette-type Accessories
The cassette-type accessories can be attached to or removed from a circuit breaker by the customer. Table 4-14: Model names of cassette-type accessories
Applicable models Frame size AL AX AL + AX Type of accessories SHT UVTN or UVTS UVTNAD130-05SVR NF32-SV, NF63-CV/SV/HV NF125-CV/SV/HV NF125-SGV/LGV/HGV NF125-RGV/UGV NF125-SEV/HEV NF160-SGV/LGV/HGV NF250-CV/SV/HV NF250-SGV/LGV/HGV NF250-RGV/UGV NF250-SEV/HEV 05 AL-05SV AL-05SVLS AL-05SVRS AX-05SV AX-05SVLS AX-05SVRS ALAX-05SV ALAX-05SVLS ALAX-05SVRS SHTA240-05SVR SHTA550-05SVR SHTD125-05SVR SHTA240-05SVRS SHTA550-05SVRS SHTD125-05SVRS UVTNAD130-05SVL UVTNA250-05SVR UVTNA250-05SVL UVTNA480-05SVR UVTNA480-05SVL UVTNAD130-05SVRS UVTNAD130-05SVLS UVTNA250-05SVRS UVTNA250-05SVLS UVTNA480-05SVRS UVTNA480-05SVLS (*1)

UVTSAD130-05SVR UVTSAD130-05SVL UVTSA250-05SVR UVTSA250-05SVL UVTSA480-05SVR UVTSA480-05SVL UVTSAD130-05SVRS UVTSAD130-05SVLS UVTSA250-05SVRS UVTSA250-05SVLS UVTSA480-05SVRS UVTSA480-05SVLS

SHTA240-05SVL NV32-SV, NV63-CV/SV/HV NV125-CV/SV/HV NV125-SEV/HEV NV250-CV/SV/HV NV250-SEV/HEV (*3) SHTA550-05SVL SHTD125-05SVL SHTA240-05SVLS SHTA550-05SVLS SHTD125-05SVLS

UVTNAD130-05SVL UVTNA250-05SVL UVTNA480-05SVL UVTNAD130-05SVLS UVTNA250-05SVLS UVTNA480-05SVLS

UVTSAD130-05SVL UVTSA250-05SVL UVTSA480-05SVL UVTSAD130-05SVLS UVTSA250-05SVLS UVTSA480-05SVLS

Model name explanation


Type of accessories Frame size With SLT (vertical lead-wire terminal block) (Lead-wire drawn unless otherwise specified)

Notes: *1

UVTN UVTS

Reset prohibited UVT Resettable UVT

SHT
Voltage SHT A240:100-240VAC A440:380-440VAC A550:380-550VAC D100:100VDC D125:100-125VDC

A240
UVTN, UVTS (*1)(*2)

05

SV R S
Installation R: Right-pole installation, 2-pole and 3-pole RF: Right-pole installation, 4-pole L: Left-pole installation Blank: Compatible with both left and right poles

The circuit breaker main body of UVTS can be reset even if not electrically energized. *2 The UVTN is not a cassette accessory. An order for the UVTN should be placed at the same time as an order of circuit breaker main body. *3 Please contact us for 4 pole of NV250-SEV, NV250-HEV. Remarks: 1. Refer to the list of combinations of accessories on page 44 for possible combinations and pole connections. 2. No cassette accessories are available for the corrosion-resistant models of AL and AX. 3. Cassette accessories cannot be mounted on circuit breakers with MG. 4. Cannot be mounted on a built-in circuit breaker with an SLT. 5. The four-pole circuit breakers with a right-pole SLT or UVT have different dimensions and model names. Please contact us for details.

AD130:100-130VAC/VDC Selectable A250:200-250VAC A480:380-480VAC

10. Pre-alarm Module


Can be mounted on the right side of electronic breakers Table 4-15
Type NF125/250-SEV/HEV NV125/250-SEV/HEV Pre-alarm module (contact output) (*2) Option (*1) Option (*1)
Operating time
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s

(PAL)

Pre-alarm characteristics
Pre-alarm pick-up current I t =OFF
6

LTD operating time TL 12 60 80 100s 20% (at 200%)

Notes: *1 Control power source of 100 to 200VAC is necessary. *2 In this case, no other accessory can be attached to the right pole.

Pre-alarm pickup current Ip Ir (0.7 0.75 0.8 0.85 0.9 0.95 1.0) 10% Pre-alarm operating time Tp Tp= 60 70 100 125
TL 2

20% 200 300 400 500600700 1000

(at 200%)

Percentage (%) of rated current or preset current rating

The self-holding models are standard. An auto-reset model is produced on request.

36

4. Accessories
External Accessories

1. F-type Operating Handle


Appearance (Color N1.5) External dimension drawing
Front plate Packing

Center of hinge and circuit breaker


Front plate Operating handle

ON

IP P

ED

Hinge (left) Circuit breaker X1 X2

Hinge (right)

O FF
R

K Trip button J Trip button G Trip button

ET N ES O P E

TR

H Trip button 35

Plate thickness (1.2 to 3.2) A2

Left hinge L X1 L

Right hinge X2 170 or more Less than 10

0 or more (5L + 85) or more

10 or more (5L + 120) or more

* The above drawing shows the layout of the hinge and the circuit breaker when viewed from the load side.

Breaker-mounted operating handle installed on a circuit breaker main body


Provides a circuit-disconnecting (isolating) function in combination with the breaker body Conforms to EN safety standards (EN 60204-1) Includes as standard a safety device which prevents breaker turning on when the cover is open Can be locked in the OFF position (a padlock of 35mm or 40mm can be used and a model with ON/OFF lock only can be produced on request) IP54 rating (IEC 60529)

Front plate drilling dimension drawing


Center of circuit breaker and operating handle
9 0

Circuit breaker mounting-hole drilling dimension drawing


Center of circuit breaker handle Circuit breaker Center of circuit breaker and operating handle Center of circuit breaker Center of circuit breaker handle

(a) (b) D D (b) (a) C Either M4 0.7 screw or 5 Either M4 0.7 screw or 5

78

78

4-12

(a)

(b)

(c)

Table 4-16
Type names F-05SV2 F-05SV F-05SVE F-1SV2 F-1SVE2 F-1SV F-1SVE

Summary of dimensions
Applicable models NFB Number of poles 2 3/4 2 3/4 2/3/4 NV32-SV NV63-CV, NV63-SV, NV63-HV NV125-CV, NV125-SV, NV125-HV NV Drilling plans Number of poles 2/3 3/4 (b) (a) (c) (a) 105 (b) (a) (c) (a) 104 15 Dimensions (mm) A (*1) B C 12.5 25 111 H D Trip button position H J (a): Breaker mounting screws (2 pcs) (b): Breaker - operating handle mounting screws (2 pcs) F-05SV2, NV125-SEV, NV125-HEV 2/3/4 NV250-CV, NV250-SV, NV250-HV NV250-SEV (*4), NV250-HEV (*4) 3/4 (c) (a) 107 35 126 K F-05SVE2, F-1SV2 and F-1SVE2 use (b) only. Mounting screws

NF32-SV NF32-SV NF63-CV, NF63-SV, NF63-HV NF125-CV, NF125-SV NF125-CV, NF125-SV NF63-HRV, NF125-HV NF125-SEV, NF125-HEV, NF125-SGV NF125-LGV, NF125-HGV, NF125-RGV

F-05SVE2 NF63-CV, NF63-SV, NF63-HV

30

F-2SV F-2SVE

NF160-SGV, NF160-LGV, NF160-HGV NF250-CV, NF250-SV, NF250-HV NF250-SGV, NF250-LGV, NF250-HGV NF250-SEV, NF250-HEV, NF250-RGV

Notes: *1 Shows dimensions for front connection types. For rear connection and plug-in types, the reference surface changes. *2 Do not remove the sponge packing installed to ensure protection rating of IP54. Install the packing that comes with the operating handle. *3 Operating the trip button can trip the circuit breaker with the door open (the trip button position differs from one model to another). *4 Please contact us for 4 pole of NV250-SEV, NV250-HEV.

Remarks: 1. Products with E in the model numbers are for emergency stop devices. 2. The standard models have reset-open specifications that allow the door to be opened only when reset (open operation). Products with OFF-open specifications are made on request and allow the door to be opened in the OFF position. 3. Products with the same ON/OFF indication specifications as the standard models are made on request even if the circuit breaker is installed on its side.

37

2. V-type Operating Handle


Appearance (Color N1.5) External dimension drawing
Front plate
ON

Center of hinge and circuit breaker


Front plate L L Hinge (right) Circuit breaker X A 61 X

OFF

TRI

PP

ED

Hinge (left)
R

K Trip button J Trip button G Trip button

ET ES

H Trip button

Plate thickness (1.2 to 3.2) 54

B (fixed type) 2 C (adjustable type) 2

L 0 or more

X (5L + 100) or more

* The above drawing shows the layout of the hinge and the circuit breaker when viewed from the load side.

Operating handle attached to the panel door and control settings attached to the breaker body
Provides a circuit-disconnecting (isolating) function in combination with the breaker body Conforms to EN safety standards (EN 60204-1) IP65 rating (IEC 60529) Can be locked with a commercial padlock (35mm and 40mm) in the OFF position The panel door can be opened in the OFF position In the ON and TRIP position, the panel door is locked so that it cannot be opened, but the panel door can still be opened in the ON and TRIP positions by pushing the release tab using a tool

Front plate drilling dimension drawing


Center of circuit breaker and operating handle 9 Center of circuit breaker and operating handle 54 54

Circuit breaker mounting-hole drilling dimension drawing


Center of circuit breaker handle Circuit breaker Center of circuit breaker and operating handle Center of circuit breaker Center of circuit breaker and circuit breaker handle Center of circuit breaker handle Center of circuit breaker

(a)

E Either M4 0.7 screw or 5

E Either M4 0.7 screw or 5

E Either M4 0.7 screw or 5

(b)

(c)

(d)

Table 4-17
Type names V-05SV2

Summary of dimensions
Applicable models NFB Number of poles 2 2/3 3 4 2 3 4 2/3 4 2/3 NV32-SV NV63-CV, NV63-SV, NV63-HV NV Drilling plans Number of poles 2/3 3 4 (b) (a) (c) (a) (d) (a) (b) (a) (c) (a) (d) (a) (c) (a) (d) (a) (c) (a) 41 4 (d) (a) 162 300 35 126 K 125 90 30 J 39 15 111 H (b): Breaker operating handle mounting screws and nuts (2 pcs each) V-05SV2, V-05SVE2, V-1SV2 and V-1SVE2 use (b) only with no nuts attached. A B Dimensions (mm) Fixed type Adjustable type (*1) C (min.) C (max.) D E 12.5 Trip button F position H Mounting screws (a): Breaker mounting screws (2 pcs) (4 pcs for 4P)

NF32-SV NF125-SVF NF32-SV NF63-CV, NF63-SV, NF63-HV

V-05SVE2 NF63-CV, NF63-SV, NF63-HV V-05SV V-05SVE V-1SV2 V-1SVE2

162

300

25

NF125-CV, NF125-SV NF125-CV, NF125-SV NF63-HRV, NF125-HV NF125-SEV, NF125-HEV, NF125-SGV NF125-LGV, NF125-HGV, NF125-RGV

V-1SV V-1SVE

NV125-CV, NV125-SV, NV125-HV

NV125-SEV, NV125-HEV NV250-CV, NV250-SV, NV250-HV NV250-SEV (*2), NV250-HEV (*2)

V-2SV V-2SVE

NF160-SGV, NF160-LGV, NF160-HGV NF250-CV, NF250-SV, NF250-HV NF250-SGV, NF250-LGV, NF250-HGV NF250-SEV, NF250-HEV, NF250-RGV 4

Notes: *1 For the adjustable type, the dimensions shown above are those when the adjustment unit V-AD3S (separately available) is mounted. *2 Please contact us for 4 pole of NV250-SEV, NV250-HEV.

Remarks: 1. Please contact us regarding applicable models other than those mentioned above. 2. IP65 rating (IEC 60529). 3. Operating the trip button can trip the circuit breaker with the door open (the trip button position differs from one model to another). 4. Products with E in the model numbers are for emergency stop devices.

Adjustable Type
Mounting the separately available adjustment unit V-AD3S to the built-in control settings, enables adjustment of the height between the breaker installation face and the panel door. Cut the shaft of the adjustment unit to fit the height.
Operating section Joint

Operation Lock While Panel Door Is Open


During checkup and other times when the panel door is open, the operation lock can be used to prevent the breaker from being turned on by accident. Lock by passing a padlock through the lock hole of the operating section of the operating handle.
Lock hole Operating section Padlock

Shaft

Warning mark

Joint clamp screw

38

4. Accessories
External Accessories

3. S-type Operating Handle


Appearance (Color N1.5) External dimension drawing
Operating plate Front plate Face plate 9 Max. 95 (*3) 41.5 4 47 70 ON OFF T R
IP

Front plate drilling dimension diagram


4-4.5 Operating plate 62 70 12 Deviation of 4mm or less Hinge A2 B2 (*2) C 2 Reference plane for mounting the circuit breaker Center of the circuit breaker

114

Clasp (*1) Center of the circuit breaker operating handle (*3) 17 43.5 4 Clasp (*1) 80

The handle can be locked at either ON or OFF position (three padlocks (40mm) can be installed, OFF-position lock only specifications are also acceptable) Degrees of protection (IEC 60529) IP5X
Remark: 1. Trip action can be displayed when the circuit breaker trips even if ON-position lock is selected (only in the case of a single padlock (35 mm)).

Max. 115

Front plate deviation of 4mm or less 100 or more (210 or more when the hinge is on the left) Front plate thickness 1.23.2

45 34 40 110

(*2) Clasp (option)

Table 4-18
Type names S-05SV

Summary of dimensions
Applicable models NFB NF32-SV, NF63-CV, NF63-SV, NF63-HV, NF50-HRV, NF125-CV, NF125-SV, NF125-HV NF125-SEV, NF125-HEV, NF125-SGV, NF125-LGV, NF125-HGV, NF125-RGV, NF160-SGV, NF160-LGV, NV NV32-SV, NV63-CV, NV63-SV, NV63-HV, NV125-CV, NV125-SV, NV125-HV Delivery category A (*4) 87

Dimensions (mm) B (*4) 102 C (*4) 104.5

S-2SV

NF160-HGV, NF250-CV, NF250-SV, NF250-HV, NF250-SGV, NF250-LGV, NF250-HGV, NF250-SEV, NF250-HEV, NF250-RGV

NV125-SEV, NV125-HEV, NV250-CV, NV250-SV, NV250-HV, NV250-SEV (*5), NV250-HEV (*5)

95

110

112.5

Notes: *1 The clasps are not supplied as standard, and should be prepared by users. Other details such as dimensions are available on request. *2 When the optional clasp is used. *3 The tolerance from the center of 62 is shown. *4 The dimensions of the front-face type are shown. Some of the back-face and plug-in types have a different reference plane for mounting the circuit breaker. *5 Please contact us for 4 pole of NV250-SEV, NV250-HEV.

Remark: 1. Not suitable for isolation.

4. Terminal Cover
Table 4-19
Large terminal cover (TC-L) Small terminal cover (TC-S) Transparent terminal cover (TTC) Rear terminal cover (BTC) Plug-in terminal cover (PTC)

Breaker type

A
B

A
B

A
C
B

A
B

A
C
B

C
(*1) (*2) (*1) (*2)

C
(*1) (*2) (*1) (*2) (*2) (*3) BTC-05SV2 (5065.55) BTC-05SV3 (7565.55) BTC-1SV2 (6065.56.5) BTC-1SV3 (9065.56.5) PTC-05SV2 (5065.55) PTC-05SV3 (7565.55) PTC-1SV2 (6065.56.5) PTC-1SV3 (9065.56.5)

NF32-SV, NF63-CV/SV/HV NF32-SV, NF63-CV/SV/HV, NV32-SV, NV63-HV NV63-CV/SV NF125-CV/SV NF125-CV/SV, NV125-CV/SV/HV NF125-HV NF125-SEV, NF125-HEV, NF125-SGV, NF125-LGV, NF125-HGV, NF125-RGV, NF160-SGV, NF160-LGV, NF160-HGV, NF250-CV, NF250-SV, NF250-HV, NF250-SGV, NF250-LGV, NF250-HGV, NF250-SEV, NF250-HEV, NF250-RGV, NV250-CV, NV250-SV, NV250-HV, NV250-SEV, NV250-HEV

2P 3P 2P, 3P 2P 3P 2P, 3P

TCL-05SV2 (5065.525) TCL-05SV3 (7565.525) TCL-1SV2 (6065.540) TCL-1SV3 (9065.540)

TCS-05SV2 (5065.55) TCS-05SV3 (7565.55) TCS-1SV2 (6065.56.5) TCS-1SV3 (9065.56.5)

(*1) (*2) (*1) (*2) (*2)

TTC-05SV2 (5065.525) TTC-05SV3 (7565.525) TTC-1SV2 (6065.540) TTC-1SV3 (9065.540)

TCL-2SV3 2P 3P (10565.540) TCL-2SV3L (10565.550)

(*2) (*3) (*2) (*4) TCS-2SV3 (10565.56.5) TTC-2SV3 (10565.540)

BTC-2SV3 (10565.56.5)

PTC-2SV3 (10565.56.5)

Notes: *1 Attach the letter F to the end of model names for models with F-type operating handle (Those are F-type operating-handle dedicated models which use screws for fixing). *2 Can be combined with the F-type or V-type operating handle as a standard feature. *3 Available for 200A rating or smaller (maximum wire size of 100mm2). *4 Available for 250A rating or smaller (maximum wire size of 150mm2). Remarks: 1. External dimensions shown in parentheses are in mm and correspond to the figure labels A, B and C in the format (ABC). 2. The wire sizes mentioned in notes (*3) through (*6) refer to 600V polyvinyl chloride wire. 3. Cover the exposed live conductors of crimp terminals with insulation tape.

39

5. Electrical Operation Device


Table 4-20
NF125-CV (3P) Applicable models (*1) NF125-SV (3P, 4P) NF125-HV Rated operating 24VDC voltage MDSD024-NF1SVJ NF125-SEV/HEV NF125-SGV/LGV/HGV/RGV NV125-CV/SV/HV NF160-SGV/LGV/HGV NF250-CV/SV/HV/SGV/LGV/HGV/RGV NF250-SEV/HEV MDSD024-NF2SVJ MDSAD240-NF2SVJ MDSD024-NV1SVJ MDSAD240-NV1SVJ NV125-SEV/HEV NV250-CV/SV/HV NV250-SEV/HEV (*2) MDSD024-NV2SVJ MDSAD240-NV2SVJ

Compatible with 100-240VAC /100-250VDC MDSAD240-NF1SVJ

Notes: *1 For other models, please order in conjunction with the circuit breaker. *2 Please contact us for 4 pole of NV250-SEV, NV250-HEV.

Table 4-21 Specifications


Rated operating voltage (allowable voltage range 85~110%) ON action Operating time (s) OFF action Charging action Power requirement (VA)
Remarks: 1. The standard terminal cover can be used. 2. Please contact us for details of the external dimensions.

24VDC 0.050.1

Compatible with 100-240VAC/100-250VDC 0.6 or less (self-holding) 1.2 or less (self-holding) 150

6. Mechanical Interlocks (MI)


Table 4-22
Applicable models NF32-SV, NF63-CV/SV/HV NF32-SV, NF63-CV/SV/HV NV32-SV, NV63-SV NV63-CV, NV63-SV NF63-SV/HV NF125-CV/SV NF125-CV NV125-CV/SV/HV NF125-SV/HV NF125-SEV, NF125-HEV, NF125-SGV, NF125-LGV, NF125-HGV, NF125-RGV, NF160-SGV, NF160-LGV, NF160-HGV, NF250-CV, NF250-SV, NF250-HV, NF250-SGV, NF250-LGV, NF250-HGV, NF250-SEV, NF250-HEV, NF250-RGV, NV125-SEV, NV125-HEV, NV250-CV, NV250-SV, NV250-HV, NV250-SEV (*1), NV250-HEV (*1)
Note: *1 Please contact us for 4 pole of NV250-SEV, NV250-HEV.

Number of poles 2P 3P 2P, 3P 4P 2P 3P 3P 4P 2P 3P 4P

Front connection/Rear connection/Plug-in

Dimension A (mm) 47.5

Panel mounting

Mounted directly on circuit breaker MI-05SVFB2

MI-05SV3 MI-05SV4 45 MI-05SV3

MI-05SVFP3

MI-05SVFB3 MI-1SVFB2

MI-05SVFP4

MI-1SVFP3

MI-1SVFB3 MI-2SVFB3

MI-1SV4 MI-05SV3 MI-2SV4

MI-1SVFP4 MI-2SVFP3 MI-2SVFP4

External dimension diagram


(front connection, rear connection and plug-in)

Drilling dimension diagram


(front connection, rear connection and plug-in)
4 (5.5 and 7.5 countersunk (rear) (*1)); use M50.8 flat countersunk head screws Center of mechanical interlock 15.5 63 (*3) 31 Center of circuit breaker Machine this part according to the front plate drilling dimensions of the main breaker 50 Center of mechanical interlock Center of circuit breaker A 120 (*2)

44

70 13 15 33

22

Stroke 1.5

Panel plate thickness (t1-3.2)

(Gap between circuit breaker and panel)

Notes: *1 When the panel plate thickness is 2.3 or more, prepare four holes (5.5 and 9.5 countersunk (rear)). *2 These are standard dimensions for two- and three-pole models, but can be altered on request. *3 The U Series have different dimensions. Please contact us for details. Remarks: 1. Please contact us for external dimensions of other models of different specifications. 2. Not isolation-compatible.

40

4. Accessories
External Accessories

7. Handle Lock Devices and Card Holder


Table 4-23
Lock cover (LC) Handle lock (HL) Handle lock (HL-S) (*2) Card holder Image

NF32-SV, NF63-CV/SV/HV NV63-CV NF32-SV, NF63-CV/SV/HV, NV32-SV, NV63-SV/HV NF125-CV/SV NF125-CV/SV, NV125-CV/SV/HV NF125-HV NF125-SEV, NF125-HEV, NF125-SGV, NF125-LGV, NF125-HGV, NF125-RGV, NF160-SGV, NF160-LGV, NF160-HGV, NF250-CV, NF250-SV, NF250-HV, NF250-SGV, NF250-LGV, NF250-HGV, NF250-SEV, NF250-HEV, NF250-RGV, NV125-SEV, NV125-HEV, NV250-CV, NV250-SV, NV250-HV, NV250-SEV (*3), NV250-HEV (*3)

2P 2P, 3P 3P 4P 2P 3P 4P 2P, 3P LC-05SV HLF-05SV HLN-05SV LC-05SV HLF-05SV HLN-05SV

(*1)

HLS-05SV2

HLS-05SV (*1) HLS-05SV2 HLS-05SV

CH-P No.5

2P 3P 4P LC-05SV

(*1) HLF-05SV HLN-05SV HLS-2SV

Notes: *1 HLF types are used for OFF-lock, and HLN types for ON-lock. *2 HL-S types are used for OFF-lock. *3 Please contact us for 4 pole of NV250-SEV, NV250-HEV. Remark: 1. Users are requested to prepare padlocks for HL and HL-S types (25mm padlock for HL, and 35mm padlock for HL-S).

8. IEC 35mm Rail Mounting Adapters


Table 4-24
Applicable models NF32-SV, NF63-CV/SV/HV, NV32-SV, NV63-CV/SV/HV Number of poles 2P, 3P Type names DIN-05SV 35 3.5 Mounting hook for IEC 35mm rail.

9. Insulating Barrier
The insulating barrier enhances the insulation between the phases of circuit breaker terminals. It also prevents accidents due to conductive foreign matter and dust, and secondary accidents when isolating a fault current.

(1) The insulating barrier is available for the models listed in the table below.
Table 4-25
Applicable models NFB
NF32-SV, NF63-CV, NF125-CV NF63-SV/HV, NF125-SV/HV NF125-SEV/HEV NF125-RV, NF250-CV/SV/HV/SEV/HEV NV32-SV, NV63-CV, NV125-CV NV63-SV/HV NV125-SV/HV NV125-SEV/HEV NV250-CV/SV/HV/SEV/HEV

(
NV

denotes optional)
Plug-in

Connection method Front connection Rear connection Standard attachment Standard attachment

Standard attachment

Remark: 1. Always mount the insulating barrier when it comes with the circuit breaker.

41

Insulating Barrier - Front (BA-F)


Table 4-26
Type names

Summary of dimensions
Applicable models NFB
NF32-SV, NF63-CV, NF125-CV NV32-SV NV63-CV NV125-CV 50 NF63-SV/HV, NF125-SV/HV NV63-SV/HV NV125-SV/HV 59.5 1 (*1) 2 3
B

NV

Delivery Dimensions (mm) Quantity per breaker category A B 2P 3P 4P

Reference diagram

BAF-05SV

Standard attachment

BAF-2SV

NF125-SEV, NF125-HEV, NF125-SGV, NF125-LGV, NF125-HGV, NF125-RGV, NV125-SEV/HEV Standard NF160-SGV, NF160-LGV, NV250-CV/SV/HV/SEV/HEV attachment NF160-HGV, NF250-CV, NF250-SV, NF250-HV, NF250-SGV, NF250-LGV, NF250-HGV, NF250-SEV, NF250-HEV, NF250-RGV

100

59.5

Note: *1 Not supplied with NV.

Insulating Barrier - Plug-in (BA-P)


Table 4-27
Type name

Summary of dimensions
Applicable models NFB NV Delivery Dimensions (mm) Quantity per breaker category A B 2P 3P 4P Reference diagram

NF125-SEV, NF125-HEV, NF125-SGV, NF125-LGV, NF125-HGV, NF125-RGV, NF160-SGV, NF160-LGV, BAP-2SV NF160-HGV, NF250-CV, NF250-SV, NF250-HV, NF250-SGV, NF250-LGV, NF250-HGV, NF250-SEV, NF250-HEV, NF250-RGV
B

NV125-SEV/HEV

Note: *1 Please contact us for 4 pole of NV250-SEV, NV250-HEV.

Standard NV250-CV/SV/HV/SEV/HEV (*1) attachment

172

74.5

42

5. Characteristics and Dimensions


Molded-case Circuit Breakers
NF32-SV NF63-CV NF63-SV NF63-HV
Type name Rated current In (A) Number of poles Rated insulation voltage Ui (V)

690V 500V Rated 440V short-circuit IEC 60947-2 415V AC breaking (Icu/Ics) 400V capacity 380V (kA) 230V DC 250V (*1) Standard attached parts (front connection)

NF32-SV 3 4 (5) 6 10 (15) 16 20 25 (30) 32 2 3 600 2.5/2.5 2.5/2.5 2.5/2.5 5/5 5/5 7.5/7.5 2.5/2.5

NF63-CV NF63-SV NF63-HV 3 4 (5) 6 10 (15) 3 4 (5) 6 10 (15) 10 (15) 16 20 25 16 20 25 (30) 32 16 20 25 (30) 32 (30) 32 40 50 40 50 (60) 63 40 50 (60) 63 (60) 63 2 3 2 3 4 2 3 4 600 600 690 2.5/2.5 2.5/2.5 7.5/7.5 7.5/7.5 2.5/2.5 7.5/7.5 10/8 2.5/2.5 7.5/7.5 10/8 5/5 7.5/7.5 10/8 5/5 7.5/7.5 10/8 7.5/7.5 15/15 25/19 2.5/2.5 7.5/7.5 7.5/7.5 Mounting screw: M40.755 (2 and 3P: 2pcs, 4P: 4pcs) Insulation barrier: (2P: 1pc, 3P: 2pcs, 4P: 3pcs) (*2)

Notes: *1 Use two poles for three- and four-pole products. Not available for use with connection as shown at the bottom of page 13. *2 Supplied with NF63-SV and NF63-HV.

NF63-SV

Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s AC 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 Time-delay trip Instantaneous trip DC Min. Max. Operating characteristics NF32-SV 3A~6A NF63-CV 3A~6A NF63-SV 3A~6A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s DC 0.02s Time-delay trip 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 Instantaneous trip 30 40 50 60 70 100 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 Time-delay trip Instantaneous trip AC Min. Max. Instantaneous trip current is fixed to AC600A120A and DC850A170A. Operating time Operating characteristics NF32-SV 10A~32A NF63-CV 10A~32A NF63-SV 10A~32A NF63-HV 10A~32A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s Min. 2s 1s 0.5s AC 0.2s 0.1s 0.05s DC Operating characteristics NF63-CV 40A~63A NF63-SV 40A~63A NF63-HV 40A~63A

Max. (60A~63A) Max. (40A~50A)

100% of rated current

100% of rated current

100% of rated current

Internal Accessories
Operating handle Left-side mounting AL AX
SHT or UVT

Ambient Compensating Curve


Lead-wire direction

Right-side mounting

Current rating (%)

120 110 100 90

2-pole

3, 4-pole

(Rated ambient 80 10 temperature 40C)

10

20

30

40

Rated ambient temperature


50

130

60

Ambient temperature (C)

External Accessories
Accessories Type name Reference page Accessories Mechanical interlock

F Operating handle V S LC Handle lock device


(*1)

2P 3, 4P 2P 3, 4P

HL HL-S

F-05SV2 F-05SV V-05SV2 V-05SV S-05SV LC-05SV HLF-05SV HLN-05SV HLS-05SV

37 38 39 41

MI TC-S

Small

2, 3P 4P 2P 3P 2P

Large
Terminal cover

TC-L

3P

Note: *1 HLF types are used for OFF-lock and HLN types for ON-lock.

4P 2P 3P 2P BTC Rear 3P 2P PTC Plug-in 3P IEC 35mm rail mounting adapters Skeleton TTC

Type name MI-05SV3 MI-05SV4 TCS-05SV2 TCS-05SV3 TCL-05SV2 TCL-05SV2L TCL-05SV3 TCL-05SV3L TCL-05SV4 TTC-05SV2 TTC-05SV3 BTC-05SV2 BTC-05SV3 PTC-05SV2 PTC-05SV3 DIN-05SV

Reference page

40

39

41

43

Front connection
Insulation barrier (removable) Mounting hole 50 24 Applicable wire size: 2 1.6 to 22mm (for M50.8 screw) 4.5 111 5.5 (8.5 for 60A and 63A) 8 25 12.5 max. (16 max. for 60A and 63A) (Conductor thickness t = 5 max.) 25 84 50 M50.8 screw (M8 for 60A and 63A) M40.7 taps or 5 Breaker

Trip button Neutral pole 25 50 50 75 75 100 4 8.5 22 25 45 61 68 72 90

112

130

2-pole

3-pole

4-pole

2-pole

3-pole

4-pole

Conductor drilling for direct connection

Drilling plan

Rear connection
2-pole Mounting plate t = 3.2 max. Insulation tube 42 (44 for 60A and 63A) 27 min. (29 min. for 60A and 63A) 112 8 M40.7 taps or 5 Breaker 4-pole 3-pole Breaker

111

112

R1

M6 screw 27 min. 68 72 42 (46 for 60A and 63A) (31 min. for 60A and 63A)

50

M40.7 breaker mounting screw 14 25 25 50

25 25 75 50 70

22.5

1.0mm clearance on each side of the handle frame

2-pole

3-pole

4-pole Front-panel cutout

Drilling plan

Plug-in
3-pole
Mounting plate Plug-in terminal block M50.8 Terminal block mounting screw 80 50

4-pole
105 Breaker (plug-in terminal block) 75 25 54

83.5

170

116

11 5.5

54 16.5 max. 25 25 55 6.5 57 82 50 107 7

85

M6 screw 21

Details of terminal

89

30

6 hole or M50.8 taps

2-pole

Conductor drilling

2-pole

3-pole

4-pole

Drilling plan

Remark: 1. Only two- and three-pole models are available for NF32-SV and NF63-CV.

54

80

52

44

5. Characteristics and Dimensions


Molded-case Circuit Breakers
NF125-CV NF125-SV NF125-HV
Type name

Rated current In (A)


Number of poles Rated insulation voltage Ui (V)

690V 500V Rated 440V short-circuit IEC 60947-2 AC 415V breaking (Icu/Ics) 400V capacity 380V (kA) 230V DC 250V (*1) Standard attached parts (front connection)

NF125-SV NF125-HV (15) 16 20 (30) 32 (15) 16 20 (30) 32 50 (60) 63 (75) 80 40 50 (60) 63 (75) 40 50 (60) 63 (75) 100 125 80 100 125 80 100 125 2 3 2 3 4 2 3 4 600 690 690 8/8 10/8 7.5/4 18/18 30/23 10/5 25/25 50/38 10/5 30/30 50/38 10/5 30/30 50/38 10/5 30/30 50/38 30/15 50/50 100/75 7.5/4 40/40 Mounting screw: M40.755 (2 and 3P: 2pcs, 4P: 4pcs) (*2) Insulation barrier: (2P: 1pc, 3P: 2pcs, 4P: 3pcs)

NF125-CV

Notes: *1 Use two poles for three- and four-pole products. If wired as shown at the bottom on page 13, three and four poles can be used for up to 400 and 500VDC, respectively. *2 Supplied with NF125-SV and NF125-HV.

NF125-SV

Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 50 6070 Time-delay trip AC DC Instantaneous trip Min. Max. Operating characteristics NF125-SV 15A~32A NF125-HV 15A~32A 4h 2h 1h 30min 20min 14min 10min 6min 4min Instantaneous trip current is fixed to AC600A120A and DC850A170A. Operating time 2min 1min Operating time 30s 20s 10s 5s Min. 2s 1s 0.5s AC 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 DC 0.2s 0.1s 0.05s 0.02s Time-delay trip Instantaneous trip 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 Time-delay trip Instantaneous trip 2s 1s 0.5s AC DC Operating characteristics NF125-CV 50A~100A NF125-SV 40A~100A NF125-HV 40A~100A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s Min. Operating characteristics NF125-CV 125A NF125-SV 125A NF125-HV 125A

Max. (60A~100A) Max. (40A~50A)

Max.

100% of rated current

100% of rated current

100% of rated current

Internal Accessories
Operating handle Left-side mounting AL AX
SHT or UVT

Ambient Compensating Curve


Lead-wire direction

Right-side mounting

Current rating (%)

120 110 100 90

2-pole

3, 4-pole

(Rated ambient 80 10 temperature 40C)

10

20

30

40

Rated ambient temperature


50

130

60

Ambient temperature (C)

External Accessories
Accessories Type name Reference page Accessories Mechanical interlock Type name Reference page

F Operating handle V S LC Handle lock device


(*1)

2P 3, 4P 2P 3, 4P

HL HL-S

F-1SV2 F-1SV V-1SV2 V-1SV S-05SV LC-05SV HLF-05SV HLN-05SV HLS-1SV

37 38 39

MI TC-S TC-L TTC BTC PTC

Small Large

41

Terminal cover

Skeleton Rear Plug-in

Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name. *3 Available for NF125-CV/SV.

2, 3P 4P 2P 3P 2P 3P 4P 2P 3P 2P 3P 2P 3P

Electrical operation device

MI-05SV3 MI-05SV4 TCS-1SV2 TCS-1SV3 TCL-1SV2 TCL-1SV3 TCL-1SV4 TTC-1SV2 TTC-1SV3 BTC-1SV2 BTC-1SV3 PTC-1SV2 PTC-1SV3 (*2)

40

39

40

45

Front connection
Insulation barrier (removable) M8 screw 50 24

Mounting hole

Solderless terminal for wire size 14~2/0AWG CU/AL

Breaker

112

130

84

50

4.5

Wire connection

8.5 8

8.5

Trip button 30 60 22 60 90

30 90 Neutral pole 120

45 61 68 19 max. Comb conductor 16.5 max. (Conductor thickness t = 5 max.)

30

30 M40.7 taps or 5

72 90

2-pole

3-pole

4-pole

2-pole

3-pole

4-pole

Conductor drilling for direct connection

Drilling plan

Rear connection
4-pole Insulation tube Mounting plate t = 3.2 max. 102 52 Stud can be rotated 90 3-pole 2-pole Breaker 2-pole 4-pole 3-pole Breaker

111

112

R1

R1

16

15 connection allowance

112

30 30 8.5 2.5 15 68 72 54.5 104.5 M8 bolt 2.5 15 Insulation tube 5 60 90 M40.7 breaker mounting screw 30 60 M40.7 taps or 5 18 30 90 57 86

28

1.0mm clearance on each side of the handle frame

2-pole

3-pole

4-pole

Drilling plan

Front-panel cutout

Plug-in
3-pole
Mounting plate Plug-in terminal block M50.8 Terminal block mounting nut or screw mounted directly 95 60

4-pole
125 90 30 56 Breaker (plug-in terminal block)

83.5

170

116

54

12

5.5

85

20 max. 56 67 97 127

21 89 30

M8 screw

30 8.5 65 6 hole or M50.8 taps

2-pole Conductor drilling

3-pole

4-pole

Details of terminal

2-pole

Drilling plan

Remarks: 1. The two-pole models of NF125-HV are three-pole models with the central pole removed. 2. Only two- and three-pole models are available for NF125-CV.

80

11

52

111

46

5. Characteristics and Dimensions


Molded-case Circuit Breakers
NF250-CV NF250-SV NF250-HV
Type name Rated current In (A) Number of poles Rated insulation voltage Ui (V)

Rated short-circuit IEC 60947-2 AC breaking (Icu/Ics) capacity (kA)

DC (*1)
Standard attached parts (front connection)

690V 500V 440V 415V 400V 380V 230V 250V

NF250-SV NF250-HV NF250-CV (*1) (100) (*1) (100) 125 150 160 175 125 150 160 175 125 150 175 200 200 225 250 200 225 250 225 250 2 3 4 2 3 4 2 3 690 690 600 8/8 10/8 30/30 50/38 10/8 36/36 65/65 15/12 36/36 70/70 25/19 36/36 75/75 25/19 36/36 75/75 25/19 85/85 100/100 36/27 20/20 (300V) 40/40 (300V) 15/12 Mounting screw: M40.755 (2 and 3P: 2pcs, 4P: 4pcs) Insulation barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs)

Note: *1 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. If wired as shown at the bottom of page 13, three-pole NF250-CV can be used for up to 400VDC, three-pole NF250-SV and NF250-HV up to 500VD and four-pole products up to 600VDC.

NF250-SV

Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 Time-delay trip 4 5 6 7 10 15 Instantaneous trip 20 30 40 AC DC Min. Operating time Operating characteristics NF250-CV 100A~225A NF250-SV 100A~225A NF250-HV 125A~225A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 Time-delay trip 3 4 5 6 7 10 15 Instantaneous trip 20 30 40 AC DC Min. Operating characteristics NF250-CV 250A NF250-SV 250A NF250-HV 250A

Max.

Max.

100% of rated current

100% of rated current

Internal Accessories
Lead-wire direction

Ambient Compensating Curve

Operating handle Left-side mounting

AL

AX

SHT or UVT

130

Right-side mounting

Current rating (%)

120 110 100 90

(Rated ambient 80 10 temperature 40C)

10

20

30

40

Rated ambient temperature


50

60

Ambient temperature (C)

External Accessories
Accessories F Operating handle V S LC Type name

Handle lock device

(*1)

HL HL-S

F-2SV V-2SV S-2SV LC-05SV HLF-05SV HLN-05SV HLS-2SV

Reference page Accessories 37 Mechanical interlock MI 38 TC-S Small 39

Type name

Reference page

2, 3P 4P 2, 3P 2, 3P 4P 2, 3P 2, 3P 2, 3P

41

Terminal cover

Large

TC-L

Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name. *3 Available for NF250-CV/SV.

Skeleton TTC BTC Rear PTC Plug-in Electrical operation device

MI-05SV3 MI-2SV4 TCS-2SV3 TCL-2SV3 TCL-2SV3L TCL-2SV4 TTC-2SV3 BTC-2SV3 PTC-2SV3 (*2)

40

39

40

47

Front connection
M8 bolt (hex-socket) 100
30

Mounting hole

Insulation barrier (removable)

24

Breaker
Solderless terminal for wire size 125 175A 14 95mm2 200 250A 70 125mm2 Wire connection

144

165

102

4.5

C 1

8.5

100

Trip button
22 70 105 35

25 max.

45 61

Or
8

10

35
.5

35

Neutral pole
105 140 4

68 72 92

M40.7 taps or 5

25 max.

3-pole

4-pole

3-pole

4-pole

(Conductor thickness t = 7 max.)

Conductor drilling for direct connection

Drilling plan

Rear connection
Insulation tube Mounting plate t = 3.2 max. Stud can be rotated 90
4-pole 3-pole 4-pole 3-pole

Breaker

Breaker

144

126

144

20

22

Connection allowance

M40.7 breaker mounting screw


15 15 68 72 71 106 9 M8 bolt 6 70 105 35 24

35 35 105 100

32.5

Insulation tube

70

M40.7 taps or 5

3-pole Drilling plan

4-pole

1.0mm clearance on each side of the handle frame

Front-panel cutout

Plug-in
4-pole 145

Mounting plate

34.5

Plug-in terminal block

3-pole 110

Breaker (plug-in terminal block)

190

165

24

144

70

11

151

54

28

15

20 9 M8 bolt 3-pole 70 70 107 Stud attachable in this direction only 105 142

21 31 89 112 30

M5 terminal block mounting screw

Insulation barrier

6 hole or M50.8 taps

4-pole 105 3-pole 105 4-pole 140

3-pole Drilling plan

4-pole

Remarks: 1. two-pole models are three-pole models with the central pole removed. 2. Only two- and three-pole models are available for NF250-CV.

56.5

80

56.5

Connection allowance

52

126

50

8 .

5
1 C

48

5. Characteristics and Dimensions


Molded-case Circuit Breakers
NF125-SGV NF250-SGV NF160-LGV NF125-HGV NF250-HGV NF250-RGV NF160-SGV NF125-LGV NF250-LGV NF160-HGV NF125-RGV
Type name Rated current In (A) Number of poles Rated insulation voltage Ui (V) 690V 500V 440V 415V 400V 380V 230V 200V 300V Rated short-circuit breaking capacity (kA) NF125-SGV 16-20, 20-25, 25-32 32-40, 35-50, 45-63 56-80, 70-100, 90-125 2 3 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 85/85 20/20 4 NF160-SGV 125-160 2 3 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 85/85 20/20 4 NF250-SGV 125-160 140-200 175-250 2 3 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 85/85 20/20 4 NF125-LGV 16-20, 20-25, 25-32 32-40, 35-50, 45-63 56-80, 70-100, 90-125 2 3 690 8/8 36/36 50/50 50/50 50/50 50/50 90/90 90/90 20/20 4 NF160-LGV 125-160 2 3 690 8/8 36/36 50/50 50/50 50/50 50/50 90/90 90/90 20/20 4 NF250-LGV 125-160 140-200 175-250 2 3 690 8/8 36/36 50/50 50/50 50/50 50/50 90/90 90/90 20/20 4

IEC 60947-2 (Icu/Ics)

AC

DC (*1)
Standard attached parts (front connection)

Mounting screw: M40.755 (2 and 3P: 2pcs, 4P: 4pcs) Insulation barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs) NF125-HGV 16-20, 20-25, 25-32 32-40, 35-50, 45-63 56-80, 70-100, 90-125 2 690V 500V 440V 415V 400V 380V 230V 200V 300V 3 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 100/100 40/40 4 NF160-HGV 125-160 2 3 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 100/100 40/40 4 NF250-HGV 125-160 140-200 175-250 2 3 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 100/100 40/40 4 NF125-RGV 16-20, 20-25, 25-32 32-40, 40-50, 50-63 63-80, 80-100, 100-125 2 3 690 125/125 150/150 150/150 150/150 150/150 150/150 NF250-RGV 125-160 160-200 200-250 2 3 690 125/125 150/150 150/150 150/150 150/150 150/150

Type name Rated current In (A) Number of poles Rated insulation voltage Ui (V) Rated short-circuit breaking capacity (kA)

NF250-SGV

IEC 60947-2 (Icu/Ics)

AC

DC (*1)
Standard attached parts (front connection)

Mounting screw: M40.755 (2 and 3P: 2pcs, 4P: 4pcs) Insulation barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs)

Note: *1 When wired as shown at the bottom of page 13, three-pole models can be used for up to 500VDC, and 4-pole models for up to 600VDC.

Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min Operating time 1min 30s 20s 10s 5s Min. 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 Time-delay trip 2 3 4 5 6 7 10 15 20 Current( 100% of Ir) Instantaneous tripping current( 100% of In) Instantaneous trip 30 40 50 6070 AC DC Max. Max. total breaking time
Operating Characteristics Thermal-Adjustable types NF125-SGV NF125-LGV NF125-HGV NF125-RGV Current setting Ir = 16-20A(Rated current In=20A) Current setting Ir = 20-25A(Rated current In=25A) Current setting Ir = 25-32A(Rated current In=32A)
lnstantaneous trip current AC DC 600A 120A 850A 170A

4h 2h 1h 30min 20min 14min 10min 6min 4min 2min Operating time 1min 30s 20s 10s 5s 2s 1s 0.5s AC 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 Time-delay trip 2 3 4 5 6 7 10 Current( 100% of Ir) Instantaneous tripping current( 100% of In) Instantaneous trip 15 20 30 40 DC Min. Max. total breaking time Max.
Operating Characteristics Thermal-Adjustable types NF125-SGV NF125-LGV NF125-HGV Current setting Ir = 32-40A(Rated current In=40A) Current setting Ir = 35-50A(Rated current In=50A) NF125-RGV Current setting Ir = 32-40A(Rated current In=40A) Current setting Ir = 40-50A(Rated current In=50A)
lnstantaneous trip current AC DC 600A 120A 850A 170A

4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s AC 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 Time-delay trip 2 3 4 5 6 7 10 Instantaneous trip 15 20 30 40 DC Max. total breaking time Min.
Operating Characteristic Curves Thermal-Adjustable types NF125-SGV NF125-LGV NF125-HGV Current setting Ir = 45- 63A(Rated current In= 63A) Current setting Ir = 56- 80A(Rated current In= 80A) NF125-RGV Current setting Ir = 50- 63A(Rated current In= 63A) Current setting Ir = 63- 80A(Rated current In= 80A)
lnstantaneous trip current ratio AC DC xln(%) xln(%) 1000 200 1300 260

4h 2h 1h 30min 20min 14min 10min 6min 4min 2min Operating time 1min 30s 20s 10s 5s 2s 1s 0.5s Min.

Max.

Operating Characteristic Curves Thermal-Adjustable types NF125-SGV NF125-LGV NF125-HGV Current setting Ir = 70-100A(Rated current In=100A) Current setting Ir = 90-125A(Rated current In=125A) NF160-SGV NF160-LGV NF160-HGV Current setting Ir = 125-160A(Rated current In=160A) NF250-SGV NF250-LGV NF250-HGV Current setting Ir = 125-160A(Rated current In=160A) Current setting Ir = 140-200A(Rated current In=200A) Current setting Ir = 175-250A(Rated current In=250A) NF125-RGV Current setting Ir = 80-100A(Rated current In=100A) Current setting Ir = 100-125A(Rated current In=125A) NF250-RGV Current setting Ir = 125-160A(Rated current In=160A) Current setting Ir = 160-200A(Rated current In=200A) Current setting Ir = 200-250A(Rated current In=250A)

Max.

lnstantaneous trip current ratio AC DC xln(%) xln(%) 1000 200 1300 260

AC 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 Time-delay trip 2 3 4 5 6 7 10 DC

Max. total breaking time

Instantaneous trip 15 20 30 40

Current( 100% of Ir) Instantaneous tripping current( 100% of In)

Current( 100% of Ir) Instantaneous tripping current( 100% of In)

Internal Accessories
Right-side mounting Operating handle Left-side mounting

Ambient Compensating Curve


Rated ambient temperature

130 Current rating (%)

AL

AX

120 110 100 90 80 -10 0 10 20 30

SHT or UVT

Lead-wire direction

40

50

60

Ambient temperature (C)

Remark: 1. Refer to page 34.

(rated ambient temperature 40C)

External Accessories
Accessories F Operating handle V S LC Type name

Handle lock device

(*1)

HL HL-S

F-2SV V-2SV S-2SV LC-05SV HLF-05SV HLN-05SV HLS-2SV

Reference page Accessories 37 Mechanical interlock MI 38 TC-S Small 39

Type name

Reference page

2, 3P 4P 2, 3P 2, 3P 4P 2, 3P 2, 3P 2, 3P

41

Terminal cover

Large

TC-L

Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name. *3 Available for NF250-CV/SV.

Skeleton TTC BTC Rear PTC Plug-in Electrical operation device

MI-05SV3 MI-2SV4 TCS-2SV3 TCL-2SV3 TCL-2SV3L TCL-2SV4 TTC-2SV3 BTC-2SV3 PTC-2SV3 (*2)

40

39

40

49

Front connection
Insulating barrier (removable) 100 Mounting hole
30

M8 bolt (hex-socket)

24 Breaker
Solderless terminal for wire size 125 175A 14 95mm2 200 250A 70 125mm2 Wire connection

144

165

102

4.5

8.5

100

Trip button

25 max.

45
Or

10

35

35

22 70 105

35 105 140 Neutral pole 4

61

68 72 92

8.5

M40.7 taps or 5

3-pole

4-pole

25 max. (Conductor thickness t = 7 max.)

3-pole

4-pole

Conductor drilling for direct connection

Drilling plan

Rear connection
4-pole

Mounting plate t max. = 3.2

Insulating tube

Stud can be rotated 90

4-pole 3-pole

3-pole

Breaker

Breaker

144

126

144

20

22

Connection allowance

M40.7 breaker mounting screw


15 15 68 72 71 106 6

24
70 105

35 35 105 100

32.5

9 M8 bolt

Insulating tube

35 70

M40.7 taps or 5

3-pole

4-pole

1mm clearance on each side of the handle frame

Drilling plan

Front-panel cutout

Plug-in
24 connection allowance 4-pole 145 3-pole 110
Breaker (plug-in terminal block)

Mounting plate

34.5

Plug-in terminal block

190

165

144

70

11

151

54

28

15

20

21 31 89 112 30

M5 terminal block mounting screw Insulating barrier

9 M8 bolt 3-pole 70 4-pole 105 3-pole 105 4-pole 140


Stud attachable in this direction only

70 107

105 142

6mm hole or M50.8 taps

3-pole

4-pole

Drilling plan

Remark: 1. Two-pole models are three-pole models with the central pole removed.

56.5

80

56.5

52

126
C 1

50

.5

50

5. Characteristics and Dimensions


Molded-case Circuit Breakers
NF125-SEV NF125-HEV NF250-SEV NF250-HEV
Type name

NF125-SEV 16-32 32-63 63-125 3 690V 500V 440V 415V 400V 380V 230V 250V 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85

NF125-HEV 16-32 32-63 63-125 3 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100

NF250-SEV 80-160 125-250 3 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85

NF250-HEV 80-160 125-250

Rated current In (A)


Number of poles Rated insulation voltage Ui (V)

3 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100

Rated short-circuit IEC 60947-2 AC breaking (Icu/Ics) capacity (kA)

DC
Standard attached parts (front connection)

Mounting screw: M40.755 (3P: 2pcs, 4P: 4pcs) Insulation barrier: (3P: 4pcs, 4P: 6pcs)

NF125-SEV

Operating Characteristics
10h 5h 2h 1h 30min 20min 14min 10min 6min 4min 2min Operating time Operating time 1min 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 0.6 0.7 1 1.25 2 I t OFF
2

10h Operating characteristics NF125-SEV NF125-HEV Current setting Ir 16-32 32-63 63-125 Rated current In 32A 63A 125A 5h 2h 1h 30min 20min 14min 10min 6min 4min 2min I t ON I t OFF STD pickup current Is Ir (22.533.54 567810) 15%
6 6

Operating characteristics NF250-SEV NF250-HEV Current setting Ir 80-160 125-250 Rated current In 160A 250A

LTD operating time at 125% (I t ON) 670s (TL = 100s set) 540s (TL = 80s set) 400s (TL = 60s set) 80s (TL = 12s set)

LTD operating time at 125% (I t ON) 670s (TL = 100s set) 540s (TL = 80s set) 400s (TL = 60s set) 80s (TL = 12s set)

LTD operating time TL 126080100s 20% (at 200%)

1min 30s 20s 10s 5s 2s 1s

I t ON I t OFF
6

LTD operating time TL 126080100s 20% (at 200%)

STD pickup current Is Ir (22.533.54 567810) 15%

STD operating time Ts 0.30.06s 0.20.04s I t ON INST pickup current Ii In 2~14 15%, Ir 14 15% 3 4 5 6 7 10
2

0.5s 0.2s 0.1s 0.05s 0.02s I t OFF


2

STD operating time Ts 0.30.06s 0.20.04s I t ON INST pickup current Ii In 2~14 15%, Ir 14 15% 2 3 4 5 6 7 10
2

0.10.03s

0.10.03s

Max. total breaking time 15 20 30 40

0.01s 0.6 0.7 1 1.25

Max. total breaking time 15 20 30 40

100% of current setting Ir Instantaneous tripping current (% of rated current or % of current setting Ir)

100% of current setting Ir Instantaneous tripping current (% of rated current or % of current setting Ir)

Internal Accessories

Ambient Compensating Curve


Derating of load current (%)
130 120 110 100 90 80 70 10 0 10 20 30 40 50 60

Operating handle Left-side mounting

AL

AX

SHT or UVT

Lead-wire direction

Right-side mounting

PAL

Rated ambient temperature

The rated current does not have thermal characteristics. Reduce the current as shown in the curve on the left chart if the ambient temperature exceeds 40 C.

(Note)

Ambient temperature (C)

External Accessories
Accessories F Operating handle V S LC Type name

Handle lock device

(*1)

HL HL-S

F-2SV V-2SV S-2SV LC-05SV HLF-05SV HLN-05SV HLS-2SV

Reference page Accessories 37 Mechanical interlock MI 38 Small 39 TC-S

Type name

Reference page

3P 4P 3P 3P 4P 3P 3P 3P

41

Terminal cover

Large

TC-L

Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name.

Skeleton TTC Rear BTC Plug-in PTC Electrical operation device

MI-05SV3 MI-2SV4 TCS-2SV3 TCL-2SV3 TCL-2SV3L TCL-2SV4 TTC-2SV3 BTC-2SV3 PTC-2SV3 (*2)

40

39

40

51

Front connection
30

Insulation barrier (removable)


100

M8 bolt (hex-socket)

24

Mounting hole

Solderless terminal for wire size 125 175A 14 95mm2 200 250A 70 125mm2 Wire connection

Breaker

Trip button
8 .5

144

165

102

10

4.5

25 max.

8.5

Trip characteristics selector


22 70 105 35

100

45 61

Or 8.5

35

35

Neutral pole
105 140 4

68 72 92
25 max.

M40.7 taps or 5

3-pole
(Conductor thickness t = 7 max.)

4-pole

3-pole

4-pole

Conductor drilling for direct connection

Drilling plan

Rear connection
4-pole

Mounting plate t = 3.2 max.

Insulation tube

Stud can be rotated 90

4-pole

3-pole

Breaker
3-pole

Breaker

144

126

144

20

22 connection allowance

15 15 68 72 71 106 9 M8 bolt

6 70 105

M40.7 breaker mounting screw


35

24

35 35 105 100

32.5

Insulation tube

70

M40.7 taps or 5

3-pole

4-pole

1.0mm clearance on each side of the handle frame

Drilling plan

Front-panel cutout

Plug-in
24 connection allowance 4-pole 145 3-pole 110

Mounting plate

34.5

Plug-in terminal block

190

165

54

70

11

144

151

28

15

20 9 M8 bolt 70 107
Stud attachable in this direction only

21 31 89 112 30

M5 terminal block mounting screw

105 142

3-pole 70

6 hole or M50.8 taps

Insulation barrier

4-pole 105 3-pole 105 4-pole 140

3-pole

4-pole

Drilling plan

Remark: 1. Products with data parenthesized come with PAL; built-in models with PAL have different external dimensions from the standard models.

56.5

80

56.5

52

126

50

C 1

52

5. Characteristics and Dimensions


Molded-case Circuit Breakers
NF125-UGV NF250-UGV
Type name Rated current In (A) Number of poles Rated insulation voltage Ui (V) 690V 500V 440V 415V 400V 380V 230V 200V 300V Rated short-circuit breaking capacity (kA) 2 NF125-UGV 16-20, 20-25, 25-32 32-40, 40-50, 50-63 63-80, 80-100, 100-125 3 690 15/15 200/200 200/200 200/200 200/200 200/200 200/200 200/200 4 2 NF250-UGV 125-160 160-200 175-225 3 690 15/15 200/200 200/200 200/200 200/200 200/200 200/200 200/200 4

IEC 60947-2 (Icu/Ics)

AC

DC Standard attached parts (front connection)

Mounting screw: M40.755 (2 and 3P: 2pcs, 4P: 4pcs) M40.773 (2 and 3P: 2pcs) Insulation barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs)

NF250-UGV

Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min Operating time 1min 30s 20s 10s 5s Min. 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 Time-delay trip 2 3 4 5 6 7 10 100% of rated current Instantaneous trip current 600A 120A(AC) 850A 170A(DC) Instantaneous trip 15 20 30 40 50 6070 AC Max. total breaking time Max. Operating time
Operating characteristics Thermal-adjustable types NF125-UGV 16A-20A(rated current In= 20A) 20A-25A(rated current In= 25A) 25A-32A(rated current In= 32A)

4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s 2s 1s 0.5s AC 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 Time-delay trip 3 4 5 6 7 10 Instantaneous trip 15 20 30 40 Min. Max. total breaking time Max. Operating time
Operating characteristics Thermal-adjustable types NF125-UGV 32A-40A(rated current In= 40A) 40A-50A(rated current In= 50A)

4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s 2s 1s 0.5s AC 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 Time-delay trip 2 3 4 5 6 7 10 Instantaneous trip 15 20 30 40 Max. total breaking time Min. Max.
Operating characteristic curves Thermal-adjustable types NF125-UGV 50A-63A(rated current In= 63A) 63A-80A(rated current In= 80A)

4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s AC 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 Time-delay trip 2 3 4 5 6 7 10 Instantaneous trip 15 20 30 40 Max. total breaking time Min. Max.
Operating characteristic curves Thermal-adjustable types NF125-UGV 80A-100A(rated current In=100A) 100A-125A(rated current In=125A) NF250-UGV 125A-160A(rated current In=160A) 160A-200A(rated current In=200A) 175A-225A(rated current In=225A)

100% of rated current Instantaneous trip current 600A 120A(AC) 850A 170A(DC)

100% of rated current

100% of rated current

Internal Accessories
Operating handle Right-side AL mounting

Ambient Compensating Curve


Rated ambient temperature

SHT or UVT

Current rating (%)

Left-side mounting

130

AX

120 110 100 90 80 -10 0 10 20 30

40

50

60

Ambient temperature (C)

Remark: 1. Refer to page 34.

(rated ambient temperature 40C)

53

Front connection

Insulation barrier (removable)


28

Mounting hole
100

M8 bolt (hex-socket)

24

Breaker
Solderless terminal for wire size 125~175A 14~95mm2 200~250A 70~125mm2 Wire connection
201

75

219

240

75

102

165

165

50

4.5

8.5 10

100

8.5

45 61

Trip button
22 70 105 35

35

35

23 max. (Conductor thickness t = 7 max.)

Neutral pole
105 140 4 68 72 92

M40.7 taps or 5

3-pole

4-pole

3-pole

4-pole

Conductor drilling for direct connection

Drilling plan

Rear connection

4-pole

Mounting plate t = 3.2 max.

Insulation tube

Stud can be rotated 90


4-pole 3-pole

3-pole

Breaker

Breaker

73 108 219 201 11.5

Connection allowance 22

219

20

R1

15 15 68 72 71 106 9 M8 bolt

6 70 105

M40.7 breaker mounting screw


35

24

35 35

32.5 100

Insulation tube

70

M40.7 taps or 5

105

1.0mm clearance on each side of the handle frame

3-pole Drilling plan

4-pole

Front-panel cutout

Plug-in

Mounting plate

34.5

Plug-in terminal block

24 Connection allowance

110

Breaker (plug-in terminal block) 56.5

219

265

70

11 6

151

129

15

20 70 9 M8 bolt
Stud attachable in this direction only

28

21 31 89 30

70 107

Insulation barrier

6 hole or M5 screw

105

Drilling plan

Remark: 1. Two-pole models are three-pole models with the central pole removed.

56.5

155

M5 terminal block mounting screw

52

54

5. Characteristics and Dimensions


Earth-leakage Circuit Breakers
NV32-SV NV63-CV NV63-SV NV63-HV
Type name Rated current In (A)
Number of poles Phase line Rated operational voltage Ue (V)

NV32-SV (5) 6 10 (15) 16 20 25 (30) 32 3 33W, 12W AC 100-440

NV63-CV

NV63-SV

NV63-HV

(5) (10) (15) 16 20 25 (5) (10) (15) 16 20 25 (15) 16 20 25 (30) (30) 32 40 50 (60) 63 (30) 32 40 50 (60) 63 32 40 50 (60) 63 2 12W 100-240 3 33W, 12W 2 12W 3 33W, 12W 3 33W, 12W

100-440 100-440 100-240 100-440 15 30 (15) 30 (15) 30 100/200/ 100/200/ (15) Rated current sensitivity (mA) 30 100/200/ 500 500 30 500 selectable High-speed type selectable selectable 0.1 0.1 0.1 0.1 at In Max operating time (s) 0.04 0.04 0.04 0.04 at 5In Rated current sensitivity (mA) Time-delay type Max operating time (s) Inertial operating time (s) (or more) Earth-leakage indication system Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) 440V 5/5 2.5/2.5 7.5/7.5 10/8 Rated 415V 5/5 2.5/2.5 7.5/7.5 10/8 short-circuit 400V 5/5 5/5 7.5/7.5 10/8 IEC 60947-2 AC breaking 230V 10/10 7.5/7.5 15/15 25/19 (Icu/Ics) capacity (kA) 200V 10/10 7.5/7.5 15/15 25/19 100V 10/10 7.5/7.5 15/15 25/19 Mounting screw: M40.755 (2pcs) (*1) Insulation barrier: (2P: 1pc, 3P: 2pcs) Standard attached parts (front connection) (15) 30 100/200/ 500 selectable

NV63-SV

Note: *1 Attached to NV63-SV and NV63-HV.

Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 Time delay trip Instantaneous trip Min. Max. Operating characteristics NV32-SV 6A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s Time delay trip 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 Instantaneous trip 30 40 50 60 70 100 Min. Max. Instantaneous trip current is fixed to 600A120A. Operating time Operating characteristics NV32-SV 10A~32A NV63-CV 16A~32A NV63-SV 16A~32A NV63-HV 16A~32A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s Min. 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 Max. (60A~63A) Max. (40A~50A) Operating characteristics NV63-CV 40A~63A NV63-SV 40A~63A NV63-HV 40A~63A

Time delay trip

Instantaneous trip

100% of rated current

100% of rated current

100% of rated current

Earth-leakage Tripping Characteristics


4h 2h 1h 30min 10min Rated non-operating current 4min 2min 1min Operating time 30s 10s 5s 2s 1s Rated current sensitivity High-speed type

Internal Accessories
Operating handle Left-side mounting Right-side mounting AL AX
SHT or UVT

TBM Lead-wire direction

Ambient Compensating Curve


Rated ambient temperature
130

Internal Wiring Diagram


Test button Load side

Current rating (%)

0.5s 0.2s 0.1s 0.05s 0.04s 0.02s 0.01s 25 50 100 500 1000

120 110 100 90 80 10

Line side

ZCT

10

20

30

40

50

60

Magnetic device

Senstivity selector

Ground-fault current ( 100% of rated current sensitivity)

Ambient temperature (C)

Leakage indication button

External Accessories
Operating handle
Accessories F V S LC
(*1)

Type name

Handle lock device

HL HL-S

F-05SV V-05SV S-05SV LC-05SV HLF-05SV HLN-05SV HLS-05SV

Note: *1 HLF types are used for OFF-lock and HLN types for ON-lock.

Reference page Accessories 37 Mechanical interlock MI 38 TC-S Small 39 Large TC-L Terminal Skeleton TTC cover 41 BTC Rear Plug-in PTC IEC 35mm rail mounting adapters

Type name MI-05SV3 TCS-05SV3 TCL-05SV3 TCL-05SV3L TTC-05SV3 BTC-05SV3 PTC-05SV3 DIN-05SV

Reference page 40

39

41

55

Front connection

Insulation barrier (removable) Mounting hole 50

M50.8 screw (M8 for 60 and 63A) 24

Applicable wire size: 2 1.6 to 22mm (for M50.8 screw)

M40.7 taps or 5 Breaker

Sensitivity current selector 130 112 4.5 Leakage indication button Test button Trip button 22 50 75 4 8.5 45 61 68 72 90 12.5 max. (16 max. for 60A and 63A) (Conductor thickness t = 5 max.) 25 111 5.5 (8.5 for 60 and 63A) 8 84 50

Conductor drilling for direct connection

Drilling plan

Rear connection

Mounting plate t = 3.2 max.

Insulation tube

M40.7 taps or 5 Breaker Breaker

112

111

112

R1

50 27 min. 68 72 42 M6 screw

M40.7 breaker mounting screw 14 25 50 70 1.0mm clearance on each side of the handle frame

Drilling plan

Front-panel cutout

Plug-in
Mounting plate Plug-in terminal block M50.8 terminal block mounting screw 80 50 Breaker (plug-in terminal block)

83.5

170

116

11

54 16.5 max. 7 25 82 6.5

5.5

85

21 89 30

M6 screw

6 hole or M50.8 taps

Details of terminal

Conductor drilling

Drilling plan

Remark: 1. Two-pole models are three-pole models with the central pole removed.

54

80

54

52

56

5. Characteristics and Dimensions


Earth-leakage Circuit Breakers
NV125-CV NV125-SV NV125-HV
Type name Rated current In (A)
Number of poles Phase line Rated operational voltage Ue (V)

NV125-CV (60) 63 (75) 80 100 125 3 33W, 12W AC 100-440 (15) 30 100/200/ 500 selectable

NV125-SV (15) 16 20 30 32 40 50 (60) 63 (75) 80 100 125 3 33W, 12W 100-440 4 34W 200-440

NV125-HV (15) 16 20 (30) 32 40 50 (60) 63 75 80 100 125 3 33W, 12W 100-440 4 34W 200-440

Rated current sensitivity (mA) High-speed type at In at 5In Rated current sensitivity (mA) Time-delay type Max operating time (s) Inertial operating time (s) (or more) Earth-leakage indication system 440V Rated 415V short-circuit IEC 60947-2 400V AC breaking (Icu/Ics) 230V capacity (kA) 200V 100V Standard attached parts (front connection) Max operating time (s)

30 100/200/500 selectable

(30) 100/200/500 selectable

0.1 0.1 0.1 0.04 0.04 0.04 (100/200/500 selectable) (100/200/500 selectable) (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0) Mechanical type (button) Mechanical type (button) Mechanical type (button) 50/38 10/5 25/25 50/38 10/5 30/30 50/38 10/5 30/30 100/75 30/15 50/50 100/75 30/15 50/50 100/75 30/15 50/50 Mounting screw: M40.755 (3P: 2pcs, 4P: 4pcs) (*1) Insulation barrier: (3P: 2pcs, 4P: 3pcs)

NV125-SV

Note: *1 Attached to NV125-SV and NV125-HV.

Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 50 60 70 Time delay trip Instantaneous trip Min. Max. Operating characteristics NV125-SV 15A~30A NV125-HV 15A~30A 4h 2h 1h 30min 20min 14min 10min 6min 4min Instantaneous trip current is fixed to 600A120A. Operating time 2min 1min Operating time 30s 20s 10s 5s Min. 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s Time delay trip 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 Instantaneous trip 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 Time delay trip Instantaneous trip Operating characteristics NV125-CV 60A~100A NV125-SV 40A~100A NV125-HV 40A~100A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s Min. Operating characteristics NV125-CV 125A NV125-SV 125A NV125-HV 125A

Max. (60A~100A) Max.(40A~50A)

Max.

100% of rated current

100% of rated current

100% of rated current

Earth-leakage Tripping Characteristics


4h 2h 1h 30min 10min Rated non-operating current Rated non-operating current Rated non-operating current Rated non-operating current Rated current sensitivity Rated current sensitivity Rated current sensitivity 4min 2min 1min Operating time 30s 10s 5s 2s Rated current sensitivity High-speed type Time-delay type 0.45s (MAX) Time-delay type 1s (MAX) Time-delay type 2s (MAX)

Internal Accessories
Operating handle Left-side mounting Right-side mounting AL AX
SHT or UVT

TBM Lead-wire direction

Ambient Compensating Curve


Rated ambient temperature
130

Internal Wiring Diagram


Test button Load side Line side

1s Inertial operating time 0.2s 0.1s 0.05s 0.04s 0.02s 0.01s 25 50 100 500 1000 25 50 100 500 1000 25 50 100 500 1000 25 50 100 500 1000 Inertial operating time

Current rating (%)

0.5s

120 110 100 90 80 10

ZCT

Inertial operating time

10

20

30

40

50

60

Ground-fault current (% of rated current sensitivity)

Ground-fault current (% of rated current sensitivity)

Ground-fault current (% of rated current sensitivity)

Ground-fault current (% of rated current sensitivity)

Ambient temperature (C)

Magnetic device

Senstivity selector

Leakage indication button

External Accessories
Accessories F Operating handle V S LC Type name

Handle lock device

(*1)

HL HL-S

F-1SV V-1SV S-05SV LC-05SV HLF-05SV HLN-05SV HLS-1SV

Reference page Accessories 37 Mechanical interlock MI 38 39 TC-S Small

Type name

Reference page

3P 4P 3P 4P

41

Terminal

Large

TC-L

Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name.

Skeleton TTC cover Rear BTC Plug-in PTC Electrical operation device

MI-05SV3 MI-1SV4 TCS-1SV3 TCL-1SV3 TCL-1SV4 TTC-1SV3 BTC-1SV3 PTC-1SV3


(*2)

40

39

40

57

Front connection
Solderless terminal for wire size

Mounting hole 50

Insulation barrier (removable) M8 screw Operating time selector (for time-delay type) Sensitivity current selector Leakage indication button Test button 50 24

14~2/0AWG CU/AL

Breaker

Wire connection

130

112

112

130

4.5

8.5 8

8.5

Trip button

22 60 90

30 90 Neutral pole 120

45 61 68 19 max. Comb conductor 16.5 max. (Conductor thickness t = 5 max.)

30

30 M40.7 taps or 5

72 90

3-pole

4-pole

3-pole

4-pole

Conductor drilling for direct connection

Drilling plan

Rear connection

4-pole Insulation tube Mounting plate t = 3.2 max. 102 52 Stud can be rotated 90 111 112 3-pole Breaker

4-pole 3-pole Breaker

R1

16

15 connection allowance

112

30 M40.7 breaker mounting screw 60 2.5 15 Insulating tube 90 8.5 30 60 18 30 90 M40.7 taps or 5 86

28

M8 bolt 2.5 15

1.0mm clearance on each side of the handle frame

68 72

54.5 104.5

3-pole Drilling plan

4-pole Front-panel cutout

Plug-in

3-pole
Mounting plate Plug-in terminal block M50.8 terminal block mounting nut or screw mounted directly 95 60

4-pole
125 90 30 54 Breaker (plug-in terminal block)

83.5

170

116

54 20 max. 12

5.5

85

21 89 30

M8 screw

8.5

97

127

Details of terminal

Conductor drilling

3-pole

4-pole Drilling plan

6 hole or M50.8 taps

Note: *1 Products with data parenthesized come with EAL or TBM; built-in models with EAL or TBM have different external dimensions from the standard models. Remark: 1. Only three-pole models are available for NV125-CV.

54

80

11

52

111

84

50

58

5. Characteristics and Dimensions


Earth-leakage Circuit Breakers
NV250-CV NV250-SV NV250-HV
Type name Rated current In (A)
Number of poles Phase line Rated operational voltage Ue (V)

NV250-CV 125 150 175 200 225 250 3 33W, 12W AC 100-440 30 100/200/500 selectable 3

NV250-SV 125 150 175 200 225 250 4 34W 200-440 3

NV250-HV 125 150 175 200 225 250 4 34W 200-440

33W, 12W 100-440

33W, 12W 100-440

Rated current sensitivity (mA) High-speed type at In at 5In Rated current sensitivity (mA) Time-delay type Max operating time (s) Inertial operating time (s) (or more) Earth-leakage indication system 440V Rated 415V short-circuit IEC 60947-2 400V AC breaking (Icu/Ics) 230V capacity (kA) 200V 100V Standard attached parts (front connection) Max operating time (s)

(30) 100/200/500 selectable

(30) 100/200/500 selectable

0.1 0.1 0.1 0.04 0.04 0.04 (100/200/500 selectable) (100/200/500 selectable) (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0) Mechanical type (button) Mechanical type (button) Mechanical type (button) 65/65 15/12 36/36 70/70 25/19 36/36 75/75 25/19 36/36 100/100 36/27 85/85 100/100 36/27 85/85 85/85 100/100 36/27 Mounting screw: M40.755 (3P: 2pcs, 4P: 4pcs) Insulation barrier: (3P: 4pcs, 4P: 6pcs)

NV250-SV

Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 Time-delay trip 4 5 6 7 10 15 Instantaneous trip 20 30 40 Min. Operating time Operating characteristics NV250-CV 125A~225A NV250-SV 125A~225A NV250-HV 125A~225A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating characteristics NV250-CV 250A NV250-SV 250A NV250-HV 250A

Earth-leakage Tripping Characteristics

4h 2h 1h 30min High-speed type Time-delay type 0.45s (MAX) Time-delay type 1s (MAX) Time-delay type 2s (MAX)

Max.

Max.

10min Rated non-operating current Rated non-operating current Rated non-operating current Rated non-operating current Rated current sensitivity Rated current sensitivity Rated current sensitivity 4min 2min Rated current sensitivity Inertial operating time 0.2s Inertial operating time 0.1s 0.05s 0.04s 0.02s 0.01s 500 1000

Operating time

30s 20s 10s 5s 2s 1s 0.5s 0.2s Min.

1min 30s 10s 5s 2s 1s 0.5s

Inertial operating time

25 50 100

500 1000

25 50 100

500 1000

25 50 100

500 1000

25 50 100

0.1s 0.05s 0.02s 0.01s 1 1.25 2 Time-delay trip 3 4 5 6 7 10 15 Instantaneous trip 20 30 40

Ground-fault current (% of rated current sensitivity)

Ground-fault current (% of rated current sensitivity)

Ground-fault current (% of rated current sensitivity)

Ground-fault current (% of rated current sensitivity)

100% of rated current

100% of rated current

Internal Accessories
Operating handle Left-side mounting Right-side mounting AL AX
SHT or UVT

Ambient Compensating Curve


130
Lead-wire direction

Internal Wiring Diagram


Test button Load side Line side

Current rating (%)

120 110 100 90 80 10

Rated ambient temperature

TBM

ZCT

Magnetic device
0 10 20 30 40 50 60

Senstivity selector

Ambient temperature (C)

Leakage indication button

External Accessories
Accessories F Operating handle V S LC Type name

Handle lock device

(*1)

HL HL-S

F-2SV V-2SV S-2SV LC-05SV HLF-05SV HLN-05SV HLS-2SV

Reference page Accessories 37 Mechanical interlock MI 38 39 Small TC-S

Type name

Reference page

3P 4P 3P 3P 4P 3P 3P 3P

41

Terminal cover

Large

TC-L

Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name.

Skeleton TTC Rear BTC Plug-in PTC Electrical operation device

MI-05SV3 MI-2SV4 TCS-2SV3 TCL-2SV3 TCL-2SV3L TCL-2SV4 TTC-2SV3 BTC-2SV3 PTC-2SV3


(*2)

40

39

40

59

Front connection
Insulation barrier (removable) Mounting hole Operating time selector (for time-delay type) Sensitivity current selector 144 165 165 144 Leakage indication button Test button 100 8.5 45 61 Neutral pole 4 140 68 72 92
25 max. (Conductor thickness t = 7 max.)
30

M8 bolt (hex-socket)

24

Solderless terminal for wire size 125 175A 14 95mm2 200 250A 70 125mm2 Wire connection
8 .5

Breaker

100

100

102

10

4.5

25 max. Or
8 .5

Trip button

35 M40.7 taps or 5

35

22 70 105

35 105

3-pole

4-pole

3-pole

4-pole

Conductor drilling for direct connection

Drilling plan

Rear connection
Insulation tube Mounting plate t = 3.2 max. Stud can be rotated 90 4-pole Breaker 3-pole 4-pole 3-pole Breaker

144

126

144

22 connection allowance

20

M40.7 breaker mounting screw 15 15 68 72 71 106 9 M8 bolt 6 70 105 35 Insulation tube 70

24 M40.7 taps or 5

35 35 105 100

32.5

1.0mm clearance on each side of the handle frame

3-pole Drilling plan

4-pole Front-panel cutout

Plug-in
24 connection allowance

4-pole 145 3-pole 110

34.5

Mounting plate

Plug-in terminal block

190

165

144

54

70

11

151

28

15

20 9 M8 bolt 3-pole 70 70 107


Stud attachable in this direction only

21 31 89 112 30

M5 terminal block mounting screw

105 142

Insulation barrier

6 hole or M50.8 taps

4-pole 105 3-pole 105 4-pole 140

3-pole Drilling plan

4-pole

Note: *1 Products with data parenthesized come with EAL or TBM. Built-in models with EAL or TBM have different external dimensions from the standard models. Remark: 1. Only three-pole models are available for the model of NV250-CV and NV250-HV.

56.5

80

56.5

52

126

50

C 1

60

5. Characteristics and Dimensions


Earth-leakage Circuit Breakers
NV125-SEV NV125-HEV NV250-SEV NV250-HEV
Type name Rated current In (A)
Number of poles Phase line type Rated operational voltage Ui Rated operational voltage Ue (V)

NV125-SEV 63-125 3 33W, 13W, 12W V AC 4 34W

NV125-HEV 63-125 3 33W, 13W, 12W 4 34W

NV250-SEV 125-250 3 33W, 12W 440 100-440

NV250-HEV 125-250 3 33W, 12W 440 100-440

440 100-440

440 100-440

Rated current sensitivity (mA) High-speed type Max operating time (s)

(30) (30) (30) (30) 100/200/500 selectable 100/200/500 selectable 100/200/500 selectable 100/200/500 selectable

0.1 0.1 0.1 0.1 at In 0.04 0.04 0.04 0.04 at 5In Rated current sensitivity (mA) (100/200/500 selectable) (100/200/500 selectable) (100/200/500 selectable) (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) Time-delay type Max operating time (s) (0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0) Inertial operating time (s) (or more) Earth-leakage indication system Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) 36/36 65/65 36/36 65/65 440V Rated 36/36 70/70 36/36 70/70 415V short-circuit IEC 60947-2 36/36 75/75 36/36 75/75 400V AC breaking (Icu/Ics) 85/85 100/100 85/85 100/100 230V capacity (kA) 85/85 100/100 85/85 100/100 200V 85/85 100/100 85/85 100/100 100V Mounting screw: M40.755 (3P: 2pcs, 4P: 4pcs) Insulation barrier: (3P: 4pcs, 4P: 6pcs) Standard attached parts (front connection)

NV250-SEV

Operating Characteristics
10h 5h 2h 1h 30min 20min 14min 10min 6min 4min 2min Operating time Operating time 1min 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 0.6 0.7 1 1.25 2 3 4 5 6 7 10 I t OFF
2

Earth-leakage Tripping Characteristics


10h 5h 2h 1h 30min 20min 14min 10min 6min 4min 2min LTD operating time at 125% (I t ON) 670s (TL = 100s set) 540s (TL = 80s set) 400s (TL = 60s set) 80s (TL = 12s set) LTD operating time TL 126080100s 20% (at 200%)
6

Operating characteristics NV125-SEV NV125-HEV Current setting Ir Rated current In 63-125 125A LTD operating time at 125% (I t ON) 670s (TL = 100s set) 540s (TL = 80s set) 400s (TL = 60s set) 80s (TL = 12s set) LTD operating time TL 126080100s 20% (at 200%)
6

Operating characteristics NV250-SEV NV250-HEV Current setting Ir Rated current In 250A 125-250

4h 2h 1h 30min 10min Rated non-operating current Rated non-operating current Rated non-operating current Rated non-operating current Rated current sensitivity Rated current sensitivity Rated current sensitivity 4min 2min 1min Operating time 30s 10s 5s 2s 1s 0.5s Inertial operating time 0.2s 0.1s 0.05s 0.04s 0.02s 0.01s 25 50 100 500 1000 25 50 100 500 1000 25 50 100 500 1000 25 50 100 500 1000 Inertial operating time Rated current sensitivity High-speed type Time-delay type 0.45s (MAX) Time-delay type 1s (MAX) Time-delay type 2s (MAX)

I t ON I t OFF
6

1min 30s 20s 10s 5s 2s 1s

I t ON I t OFF
6

STD pickup current Is Ir (22.533.54 567810) 15%

STD pickup current Is I r (22. 533. 54 567810) 15%

STD operating time Ts 0.30.06s 0.20.04s I t ON INST pickup current Ii In2~14 15%, Ir14 15%
2

0.5s 0.2s 0.1s 0.05s 0.02s I t OFF


2

STD operating time Ts 0.3 0.06s 0.2 0.04s I t ON INST pickup current Ii In2~14 15%, Ir14 15% 2 3 4 5 6 7 10
2

Inertial operating time

0.10.03s

0.1 0.03s

Ground-fault current (% of rated current sensitivity)

Ground-fault current (% of rated current sensitivity)

Ground-fault current (% of rated current sensitivity)

Ground-fault current (% of rated current sensitivity)

Max. total breaking time 15 20 30 40

0.01s 0.6 0.7 1 1.25

Max. total breaking time 15 20 30 40

100% of current setting Ir Instantaneous tripping current (% of rated current or % of current setting Ir)

100% of current setting Ir Instantaneous tripping current (% of rated current or % of current setting Ir)

Internal Accessories

Ambient Compensating Curve

Internal Wiring Diagram

Operating handle Left-side mounting Right-side mounting

AL

AX

SHT or UVT

Lead-wire direction
130

Test button
Rated ambient temperature
Characteristic setting part

TBM

PAL
Current rating (%)
120 110 100 90 80

Magnetic device
CT CT CT Senstivity selector

(Note *1)

(Note *2)

70 10

The rated current does not have thermal characteristics. Reduce the current as shown in the curve on the left chart if the ambient temperature exceeds 40C.
0 10 20 30 40 50 60

Notes: *1 For the 24VDC TBM only instruct us of a control voltage. (The standard shared voltage is 100-240VAC/100-240VDC.) *2 SLT equipped is standard. Control voltage (100-200VAC) is necessary.

Ambient temperature (C)

Magnetic device

Leakage indication button

External Accessories
Accessories F Operating handle V S LC Type name

Handle lock device

(*1)

HL HL-S

F-2SV V-2SV S-2SV LC-05SV HLF-05SV HLN-05SV HLS-2SV

Reference page Accessories 37 Mechanical interlock MI 38 39 TC-S Small

Type name

Reference page

3P 4P 3P 3P 4P 3P 3P 3P

41

Terminal cover

Large

TC-L

Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name.

Skeleton TTC BTC Rear PTC Plug-in Electrical operation device

MI-05SV3 MI-2SV4 TCS-2SV3 TCL-2SV3 TCL-2SV3L TCL-2SV4 TTC-2SV3 BTC-2SV3 PTC-2SV3


(*2)

40

39

40

61

Load side

Line side

ZCT

Front connection
Solderless terminal for wire size 125 175A 14 95mm2 200 250A 70 125mm2 Wire connection
30

Insulation barrier (removable) Mounting hole Operating time selector (for time-delay type) Sensitivity current selector Leakage indication button Test button Trip characteristics selector Trip button
22 70 105 35 105 140 100 100

M8 bolt (hex-socket)

24

Breaker

8 .
C 1

5
10

165

144

144

165

102

4.5

25 max. Or

100

8.5

45 61

.5

35

35

Neutral pole
4

68 72 92

25 max. (Conductor thickness t = 7 max.)

M40.7 taps or 5

3-pole

4-pole

3-pole

4-pole

Conductor drilling for direct connection

Drilling plan

Rear connection
4-pole

Mounting plate t = 3.2 max.

Insulation tube

Stud can be rotated 90

4-pole

3-pole

Breaker
3-pole

Breaker

144

126

144

20

22 connection allowance

15 15 68 72 71 106 9 M8 bolt

6 70 105

M40.7 breaker mounting screw


35

24

35 35 105 100

32.5

Insulation tube

70

M40.7 taps or 5

3-pole

4-pole

1.0mm clearance on each side of the handle frame

Drilling plan

Front-panel cutout

Plug-in
24 connection allowance 4-pole 145 3-pole 110

Mounting plate

34.5

Plug-in terminal block

190

165

144

54

70

11

151

28

15

20 9 M8 bolt 3-pole 70 70 107


Stud attachable in this direction only

21 31 89 112 30

M5 terminal block mounting screw Insulation barrier

105 142

6 hole or M50.8 taps

4-pole 105 3-pole 105 4-pole 140

3-pole

4-pole

Drilling plan

Note: *1 Products with data parenthesized come with PAL, EAL or TBM. Built-in models with PAL, EAL or TBM have different external dimensions from the standard models.

56.5

80

56.5

52

126

50

1 C

62

5. Characteristics and Dimensions


Motor-protection Breakers
NF63-CV NF32-SV NF63-SV
Type name Rated current In (A) Number of poles Rated insulation voltage Ui (V) JIS C 8201-2-1 Ann.1 440V JIS C 8201-2-1 Ann.2 415V IEC 60947-2 AC 400V EN 60947-2 380V (Icu/Ics) 230V 415V GB 14048.2 400V AC (Icu/Ics) 380V 230V NK 450V AC (Icu/Ics) 240V Standard attached parts (front connection) Rated short-circuit breaking capacity (kA) NF63-CV 4 5 7.1 8 10 12 16 25 32 40 45 NF32-SV 4 5 7.1 8 10 12 16 25 32

Specify MB

NF63-SV 4 5 7.1 8 10 12 16 25 32 40 45

3 3 3 600 600 600 2.5/2.5 2.5/2.5 7.5/7.5 2.5/2.5 2.5/2.5 7.5/7.5 5/5 5/5 7.5/7.5 5/5 5/5 7.5/7.5 7.5/7.5 7.5/7.5 15/15 2.5/2.5 2.5/2.5 7.5/7.5 5/5 5/5 7.5/7.5 5/5 5/5 7.5/7.5 7.5/7.5 7.5/7.5 15/15 2.5/2.5 2.5/2.5 7.5/7.5 7.5/7.5 7.5/7.5 15/15 Mounting screw: M40.755 (3P: 2pcs) (*2) Insulation barrier: (3P: 2pcs)

Notes: *1 Refer to page 64 for the external dimensions. *2 Supplied with NF63-SV.

NF63-SV

Operating Characteristics

4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 Time-delay trip 3 4 5 6 7 10 15 Instantaneous trip 20 30 40 Min. Max.(4A~5A) Operating time Max.(7.1A~8A) Operating characteristics NF32-SV 4A~8A NF63-CV 4A~8A NF63-SV 4A~8A

4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s Time-delay trip 0.01s Instantaneous trip Instantaneous trip current is fixed to 600A120A. Operating time Operating characteristics NF32-SV 10A~32A NF63-CV 10A~32A NF63-SV 10A~32A

4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s Operating characteristics NF63-CV 40A~45A NF63-SV 40A~45A

Max.(40A~45A)

Max.

Min.

Min.
2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s Time-delay trip 0.01s 100 1 1.25 Instantaneous trip

1 1.25

5 6 7

10

15

20

30

40 50 60 70

5 6 7

10

15

20

30

40

100% of rated current

100% of rated current

100% of rated current

Internal Accessories
Operating handle Left-side mounting AL AX
SHT or UVT

Ambient Compensating Curve


Rated ambient temperature
0 10 20 30 40 50
Lead-wire direction

130

Right-side mounting

Current rating (%)

120 110 100 90

(Rated ambient 80 10 temperature 40C)

60

Ambient temperature (C)

External Accessories
Accessories Type name Reference page Accessories Mechanical interlock

F Operating handle V S LC Handle lock device


(*1)

2P 3, 4P 2P 3, 4P

HL HL-S

F-05SV2 F-05SV V-05SV2 V-05SV S-05SV LC-05SV HLF-05SV HLN-05SV HLS-05SV

37 38 39 41

MI TC-S

Small

2, 3P 4P 2P 3P 2P

Large
Terminal cover

TC-L

3P

Note: *1 HLF types are used for OFF-lock and HLN types for ON-lock.

4P 2P 3P 2P BTC Rear 3P 2P PTC Plug-in 3P IEC 35mm rail mounting adapters Skeleton TTC

Type name MI-05SV3 MI-05SV4 TCS-05SV2 TCS-05SV3 TCL-05SV2 TCL-05SV2L TCL-05SV3 TCL-05SV3L TCL-05SV4 TTC-05SV2 TTC-05SV3 BTC-05SV2 BTC-05SV3 PTC-05SV2 PTC-05SV3 DIN-05SV

Reference page

40

39

41

63

NF125-SV
Rated short-circuit breaking capacity (kA)

Type name Rated current In (Amp.) Number of poles Rated insulation voltage Ui (V) Rated operational voltage Ue (V) AC JIS C 8201-2-1 Ann.1 440V JIS C 8201-2-1 Ann.2 415V IEC 60947-2 AC 400V EN 60947-2 380V (Icu/Ics) 230V 415V GB 14048.2 400V AC (Icu/Ics) 380V 230V NK 450V AC (Icu/Ics) 240V Standard attached parts (front connection)

NF125-SV (12.5) (16) (25) 32 (40) 45 63 71 90 100 3 690 230, 380/440 25/25 30/30 30/30 30/30 50/50 30/30 30/30 30/30 50/50 25/25 50/50 Mounting screw: M40.755 (3P: 2pcs) Insulation barrier: (3P: 2pcs)

Remark: 1. Refer to page 66 for the external dimensions.

NF125-SV

Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 50 60 70 100% of rated current Time-delay trip Instantaneous trip Min. Max. Operating characteristics NF125-SV 12.5A~32A 4h 2h 1h 30min 20min 14min 10min 6min 4min Instantaneous trip current is fixed to 600A120A. Operating time 2min 1min 30s 20s 10s 5s Min. 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s Time-delay trip 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 100% of rated current Instantaneous trip Operating characteristics NF125-SV 40A~100A

Max. (63A~100A) Max. (40A~45A)

Internal Accessories
Operating handle Left-side mounting AL AX
SHT or UVT

Ambient Compensating Curve


130

Right-side mounting

Current rating (%)

120 110 100 90

(Rated ambient 80 10 temperature 40C)

10

20

30

40

Rated ambient temperature


50

Lead-wire direction

60

Ambient temperature (C)

External Accessories
Accessories F Operating handle V S LC Handle lock device
(*1)

Type name 3P 3P F-1SV V-1SV S-05SV LC-05SV HLF-05SV HLN-05SV HLS-1SV

HL HL-S

Reference page Accessories Mechanical interlock MI 37 TC-S 38 Small TC-L 39 Large Terminal Skeleton TTC cover BTC Rear 41 PTC Plug-in Electrical operation device

Type name 3P 3P 3P 3P 3P 3P MI-05SV3 TCS-1SV3 TCL-1SV3 TTC-1SV3 BTC-1SV3 PTC-1SV3


(*2)

Reference page

40

39 40

Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name.

64

5. Characteristics and Dimensions


Motor-protection Breakers
NF250-SV
Rated short-circuit breaking capacity (kA) Type name Rated current In (A) Number of poles Rated insulation voltage Ui (V) JIS C 8201-2-1 Ann.1 440V JIS C 8201-2-1 Ann.2 415V IEC 60947-2 AC 400V EN 60947-2 380V (Icu/Ics) 230V 415V GB 14048.2 400V AC (Icu/Ics) 380V 230V NK 450V AC (Icu/Ics) 240V Standard attached parts (front connection) NF250-SV 125 150 175 200 225 3 690 36/36 36/36 36/36 36/36 85/85 36/36 36/36 36/36 85/85 36/36 85/85 Mounting screw: M40.755 (3P: 2pcs) Insulation barrier: (3P: 4pcs)

Remark: 1. Refer to page 70 for the external dimensions.

NF250-SV

Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 Time-delay trip 4 5 6 7 10 15 Instantaneous trip 20 30 40 Min. Operating characteristics NF250-SV 125A~225A

Max.

100% of rated current

Internal Accessories
Operating handle Left-side mounting AL AX
SHT or UVT

Ambient Compensating Curve


130

Right-side mounting

Current rating (%)

120 110 100 90

(Rated ambient 80 10 temperature 40C)

10

20

30

40

Rated ambient temperature


50

Lead-wire direction

60

Ambient temperature (C)

External Accessories
Accessories F Operating handle V S LC Handle lock device
(*1)

Type name F-2SV V-2SV S-2SV LC-05SV HLF-05SV HLN-05SV HLS-2SV

Reference page Accessories Mechanical interlock MI 37 Small TC-S 38 39 Large TC-L Terminal

Type name 2, 3P 3P 3P 3P 3P 3P MI-05SV3 TCS-2SV3 TCL-2SV3 TCL-2SV3L TTC-2SV3 BTC-2SV3 PTC-2SV3


(*2)

Reference page 40

HL HL-S

41

Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name.

Skeleton TTC Rear BTC Plug-in PTC Electrical operation device


cover

39

40

65

MEMO

66

6 . L O W- V O LTA G E S W I T C H G E A R T E C H N I C A L

67

I N F O R M AT I O N S E RV I C E V I A T H E I N T E R N E T

68

MITSUBISHI Molded-case Circuit Breakers & Earth-leakage Circuit Breakers


Country / Region Australia Chile China China Colombia Egypt Europe India Indonesia Korea Laos Lebanon Malaysia Myanmar Nepal Middle East Arab Countries & Cyprus Pakistan Philippines Saudi Arabia Singapore South Africa Taiwan Thailand Uruguay Venezuela Vietnam Rhona S.A. Mitsubishi Electric Automation (CHINA) Ltd. Mitsubishi Electric Automation (HongKong) Ltd. Proelectrico Representaciones S.A. Cairo Electrical Group Mitsubishi Electric Europe B.V. Mitlite Electric Company Pvt Ltd P. T. Sahabat Indonesia Mitsubishi Electric Automation Korea Co., Ltd Societe Lao Import Co., Ltd. Comptoir d'Electricite Generale-Liban Mittric Sdn Bhd Peace Myanmar Electric Co.,Ltd. Watt & Volt House Comptoir d'Electricite Generale-International-S.A.L. Prince Electric Co. Edison Electric Integrated, Inc. Center of Electrical Goods Mitsubishi Electric Asia Pte. Ltd. CBI-electric: low voltage Setsuyo Enterprise Co., Ltd United Trading & Import Co., Ltd. Fierro Vignoli S.A. Adesco S.A. CTY TNHH-TM SA GIANG Company Mitsubishi Electric Australia Pty. Ltd. Address 348 Victoria Road, Rydalmere, N.S.W. 2116, Australia Agua Santa 4211 P.O. Box 30-D Vina del Mar, Chile Mitsubishi Electric Automation Center, No. 1386 Hongqiao Road, Shanghai, 200336 10/F., Manulife Tower, 169 Electric Road, North Point, Hong Kong Carrera 53 No 29C-73 - Medellin, Colombia 9, Rostoum St. Garden City P.O. Box 165-11516 Maglis El-Shaab, Cairo - Egypt Gothaer Strasse 8, D-40880 Ratingen, Germany Plot No-32, Sector-6, IMT Maneser, P.O.Box 5045 Kawasan Industri Pergudangan, Jakarta, Indonesia 1480-6, Gayang-Dong, Gangseo-Gu, Seoul, Korea 43-47 Lane Xang Road P.O. BOX 2789 VT Vientiane Laos Cebaco Center - Block A Autostrade Dora, P.O. Box 11-2597 Beirut - Lebanon 5 Jalan Pemberita U1/49, Temasya Industrial Park, Glenmarie 40150 Shah Alam, Selangor, Malaysia NO137/139 Botataung Pagoda Road, Botataung Town Ship 11161, Yangon, Myanmar KHA 2-65, Volt House Dillibazar Post Box: 2108, Kathmandu, Nepal Cebaco Center - Block A Autostrade Dora P.O. Box 11-1314 Beirut - Lebanon 1&16 Brandreth Road, Lahore-54000, Pakistan 24th Fl. Galleria Corporate Center, Edsa Cr. Ortigas Ave., Quezon City Metro Manila, Philippines Al-Shuwayer St. Side way of Salahuddin Al-Ayoubi St. P.O. Box 15955 Riyadh 11454 - Saudi Arabia 307, Alexandra Road, #05-01/02 Mitsubishi Electric Building, Singapore 159943 Private Bag 2016, Isando, 1600, South Africa 6th Fl., No.105, Wu Kung 3rd, Wu-Ku Hsiang, Taipei, Taiwan, R.O.C. 77/12 Bamrungmuang Road, Klong Mahanak, Pomprab Bangkok Thailand Avda. Uruguay 1274, Montevideo, Uruguay Calle 7 La Urbina Edificio Los Robles Locales C y D Planta Baja, Caracas - Venezuela 10th Floor, Room 1006-1007, 255 Tran Hung Dao St., Co Giang Ward, Dist 1, Ho Chi Minh City, Vietnam Telephone + 61-2-9684-7777 +56-32-2-320-600 + 86-21-2322-3030 + 852-2887-8810 +57-4-235-30-38 +20-2-27961337 + 49-(0)2102-486-0 + 91-124-4695300 + 62-(0)21-6610651-9 + 82-2-3660-9572 + 856-21-215043 +961-1-240445 +603-5569-3748 +95-(0)1-202589 +977-1-4411330 +961-1-240430 + 92-(0)42-7654342 + 63-(0)2-634-8691 + 966-1-4770149 +65-6473-2308 +27-(0)11-9282000 + 886-(0)2-2298-8889 + 66-223-4220-3 +598-2-902-0808 +58-212-241-9952 +84-8-8386727/28/29

For Safety : Please read the instruction manual carefully before using the products in this catalog.