Sie sind auf Seite 1von 2

ADDC Testing and Protection Section

Station:
Contract:
ConsuItant:
Contractor:
Feeder ID:
ReIay: Relay Type: Numerical Relay Model: Delta Relay Make: VATECH
CT Ratio Prim. Current Sec. Current Burden, VA Class Rct
600/400/1 600 1 15 - 10 5P15 -
Fault Current, f L-L Fault L-G Fault
Min. Fault Current, A 11000 8100
Max. Fault Current, A 22000 16200
sec .........Eq. 1
1.06 .........Eq. 2
sec
sec
.........Eq. 3
sec
sec (for Sample)
PMS: 0.8
TMS: 0.125
High Set
(I>>):
10xn
Yes/No
Yes/No
Outgoing Feeder (Typical)
Setting CaIcuIation ProtocoI for IDMT Overcurrent ReIay Settings
CT Data:
FauIt Data:
FAULT SETTING CALCULATION FOR IDMT O/C
PMS (Plug Multiplier Setting):
PSM (Plus Setting Multiplier):
'=[(fmin/Prim.Current) * (Sec.Rated
Current/PMS)]
22.92
GeneraI Data:
Overload Current: 480 (125% of Full load current of Protected Object)
Curve Selected:
Operating time at TMS 1, sec
'=0.14/[(PSM)0.02 - 1]:
2.17
0.8
Normal nverse (N)
Assuming Prot. Op. time, sec:
(0.3sec)
0.3
0.139
Hence TMS: ('= (0.3+0) / (Result
from Eq.1)
Grading Margin (0.3sec) 0
Final TMS set at: 0.125
Operating time at TMS 0.125, sec
'=0.14*0.125/[(PSM)0.02 - 1]:
0.271
s settings co-ordinated with downstream side:
s settings co-ordinated with upstream side:
Operating time at TMS 0.2, sec
'=0.14*0.2/[(PSM)0.02 - 1]:
0.433
Adopted Settings:
42608022.xls/DMT OC-Outgoing 1/1
ADDC Testing and Protection Section
Station:
Contract:
ConsuItant:
Contractor:
Feeder ID:
ReIay: Relay Type: Numerical Relay Model: Delta Relay Make: VATECH
CT Ratio Prim. Current Sec. Current Burden, VA Class Rct
600/400/1 600 1 15 - 10 5P15 -
Fault Current, f L-L Fault L-G Fault
Min. Fault Current, A 11000 8100
Max. Fault Current, A 22000 16200
sec .........Eq. 1
1.09 .........Eq. 2
sec
sec
.........Eq. 3
sec
PMS: 0.2
TMS: 0.2
High Set
(I0>>):
8xn
Yes/No
Yes/No
Normal nverse (N)
Operating time at TMS 1, sec
'=0.14/[(PSM)0.02 - 1]:
1.59
FauIt Data:
FAULT SETTING CALCULATION FOR IDMT O/C
GeneraI Data:
Earth Fault Current: 0.2 (25% of OC PMS)
Setting CaIcuIation ProtocoI for IDMT Earth FauIt ReIay Settings
CT Data:
Operating time at TMS 0.2, sec
'=0.14*0.2/[(PSM)0.02 - 1]:
0.319
Hence TMS: ('= (0.3+0) / (Result
from Eq.1)
0.188
Final TMS set at: 0.2
PMS (Plug Multiplier Setting): 0.2
s settings co-ordinated with upstream side:
Outgoing Feeder (Typical)
PSM (Plus Setting Multiplier):
'=[(fmin/Prim.Current) * (Sec.Rated
Current/PMS)]
67.50
Curve Selected:
Grading Margin (0.3sec) 0
Assuming Prot. Op. time, sec:
(0.3sec)
0.3
Adopted Settings:
s settings co-ordinated with downstream side:
42608022.xls/DMT EF-Outgoing 1/1

Das könnte Ihnen auch gefallen