WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION
R410A
TECHNICAL MANUAL
TABLE OF CONTENTS
GENERAL FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
UNIT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 UNIT IDENTIFICATION CODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 DESCRIPTION OF COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 CONTROL SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
TECHNICAL DATA AND PERFORMANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 NOMINAL PERFORMANCES - LOW TEMPERATURE PLANTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 NOMINAL PERFORMANCES - MEDIUM TEMPERATURE PLANTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 HEATING PERFORMANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 COOLING PERFORMANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 PLANT SIDE HYDRAULIC PERFORMANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 SOURCE SIDE HYDRAULIC PERFORMANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 DOMESTIC HOT WATER SIDE HYDRAULIC PERFORMANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 OPERATING LIMITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 NOISE LEVELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21 OVERALL DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 MINIMUM OPERATING AREA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
GENERAL FEATURES
Unit description This series of water-water heat pumps satisfies the heating, cooling and domestic hot water production requirements of residential plants of small and medium size. daily switching programs for heating, cooling and domestic hot water production.
All the units are suitable for indoor installation and can be applied to fan coil plants, radiant floor plants and high efficiency radiators plants. As source both water (from well, river, lake) or brine solutions (from geothermic probes) can be used. The control system allows to manage not only the refrigerant circuit but the whole plant with the possibility to choose different solutions both for the heating and cooling plant and for the domestic hot water management. The possibility of solar panels or other heating sources integration is also available.
The refrigerant circuit, contained in an extractable box to simplify the maintenance operations, is equipped with rotary compressor mounted on damper supports, brazed plate heat exchangers, thermostatic expansion valve and reverse cycle valve (for reversible units). The circuit is protected by high and low pressure switches and flow switches on both the exchangers. The outdoor structure and the refrigerant circuit box are both thermally and acoustically insulated in order to create a double wall against sound propagation and to allow the installation in domestic places. To avoid vibration propagation towards the hydraulic circuit the refrigerant circuit box is placed on damper supports and the connection pipes are flexible. Moreover all the hydraulic pipes are thermally insulated to avoid condensate generation. All the units are accurately built and individually tested in the factory. Only electric and hydraulic connections are required for installation.
The domestic hot water management allows to control the three way valve, the storage tank and the anti-legionella cycles (if necessary). The cooling function can be realized through passive cooling (free cooling) , through active cooling (refrigerant circuit inversion) or through both systems actuated in sequence. When the unit is used in radiant floor plants, to avoid condensate generation, a room humidity sensor can be installed.
The heating function optimizes the flow water temperature according both to the ambient temperature and to the outdoor temperature through climatic curves adaptable to the building features. Its possible to manage a storage tank and two independent circuits (a direct one and a mixed one).
Unit identification code The codes that identify the units and the meaning of the letters used are described below.
HSW IH 7.1 VB AB 0 M 1
Unit type
IH - Units suitable for hydronic plant installation operating as heat pumps IP - Units suitable for hydronic plant installation operating as reversible heat pumps
Power supply
1 - 230V - 1 - 50 Hz 5 - 400V - 3N - 50 Hz
Operating range
M - Medium temperature. The unit is suitable to produce water at medium temperature
Unit version
VB - Base Version
Acoustic setting up
AB - Base setting up
Refrigerant type
0 - R410A
GENERAL FEATURES
Description of components External structure. Basement, lateral panels and frontal panel, are completely thermally and acoustically insulated in order to minimize thermal losses and noise emissions in the surroundings. Accessibility to internal parts is possible removing the frontal panel and the upper panel. For extraordinary manteinances also the rear panel can be removed. heat pumps), pressure connections SAE 5/16 - UNF 1/2 20 equipped with pin, gasket and blind nut, as required for the use of R410A refrigerant (they allow the complete check of the refrigerant circuit : compressor inlet pressure, compressor outlet pressure, thermostatic expansion valve upstream pressure and pressure drops accross the filter). All the pipes of the refrigerant circuit are properly insulated to avoid condensate generation and to minimize thermal losses. Hydraulic circuit. Both the hydraulic circuit on the plant side and on the source side are equipped with expansion vessel, air vents and drain valves. All the pipes are thermally insulated to avoid condensate generation and minimize thermal losses. The circuit on the plant side is moreover equipped with pressure safety valve, pressure gauge and three speed glandless pump while the water flow rate on the source side can be adjusted by means of a three speed glandless pump or by means of a two way valve. Electrical panel. It contains all the power, control and security components necessary to guarantee the unit to work properly. The unit is managed by a microprocessor controller to which all the electrical loads and the control devices are connected. The user interface, placed on the frontal panel of the unit, allows to view and to modify, if necessary, all the parameters of the unit. All the units are supplied with an outdoor temperature sensor, to be installed outside, in order to realize the climatic control.
5 3 2
Refrigerant circuit. It is contained inside an extractable box to simplify the maintenance operations. The box is placed on rubber vibration dampers and is connected to the hydraulic circuit through flexible pipes in order to avoid the propagation of the vibrations generated by the compressor outside the unit. The hermetic rotary compressor (1) is mounted on damper supports and is protected against overtemperatures and overcurrents. The heat exchangers on the plant side (2) and on the source side (3) are realized with brazed stainless steel plates, properly insulated to avoid condensate generation and to minimize thermal losses, and protected by a flow switch that detects whatever water flow lack. The expansion device (4), a thermostatic expansion valve with external equalizer, allows the unit to adjust itself to the different operating conditions keeping steady the set superheating. The refrigerant circuit of each unit contains moreover solid core hermetic filter dryer (5) to restrain impurity and moisture residuals that could be present in the circuit, high and low pressure switches in order to assure the compressor to operate inside the permitted limits, 4 way reverse cycle valve (6) to allow operating mode change reversing the refrigerant flow (only for reversible 6
GENERAL FEATURES
Control system The microprocessor controller is able to manage not only the unit itself but also all that components of the plant which allow to realize a complete system. The main functions of the control system are : room temperature control according to the outdoor temperature (climatic control) management of a heating and/or cooling mixed circuit (pump and 3 way mixing valve) management of a heating direct circuit (only pump) management of a storage tank for heating and/or cooling solar panels integration passive cooling
18:28
domestic hot water production (management of 3 way valve, storage tank, anti legionella cycles)
20.5 C
Room temperature
management of electrical heaters for heating and domestic hot water (3 steps logic) Besides the standard user interface present on all the units, wired or wireless remote thermostats are available which allow to control all the operating parameters of the unit and to acquire the temperature in the different zones in order to realize a more precise and comfortable control. The unit controller is able to manage a lot of different plant solutions enabling automatically the necessary control algorythms according to the components which have been connected.
room humidity control for cooling with radiant systems digital input for electrical energy low tariff
internal programmer clock (for heating, cooling and domestic hot water) alarm memory management and diagnostic
FS FS FS
The controller is able to manage up to two zones in heating (one by means of a mixed circuit and the other by means of a direct circuit) and one zone in cooling (by means of a mixed circuit). Its possible to realize more complex plants connecting to the heat pump controller further expansion modules in order to extend without limits the number of zones to be managed.
For each zone the following parameters can be set : set point daily or weekly operating time table climatic control curve room control sensor : it can be in common with the other zones or independent (in that case its necessary to install an additional room thermostat)
GENERAL FEATURES
Options
Pump 2 way valve 3 way valve Domestic hot water production 3 way valve with primary heat exchanger 3 way valve with secondary heat exchanger (for integrated tank) Passive cooling Integrative electrical heaters Soft starter Allows the circulation of the water on the source side. Modulates the water flow rate on the source side when the water circulation is assured by an external pump. Allow to divert the hot water produced by the heat pump from the heating circuit to the domestic hot water circuit. The hot water is diverted by the three way valve on an internal heat exchanger. An internal pump assures a correct domestic hot water flow through the other side of the heat exchanger. The hot water is diverted by the three way valve in a tank integrated in the unit (accessory). The domestic hot water is generated istantaneously by means of an internal heat exchanger and a modulating pump. Allows to use the source to cool down the plant water without activating the compressor. Integrate or replace the heating power supplied by the heat pump and are managed by the unit controller with a 3 step logic. Reduces the compressor start current.
The controller flexibility and the big number of options available allow to get, for each model, a lot of different configurations that integrate inside the heat pump many components of the plant and allow to realize compact and tested installations. Not reversible heat pump (IH) without options
In order to select the right configuration it is necessary to define the type of plant to which the heat pump will be connected, both for what concerning the heating and cooling circuits, and for what concerning the domestic hot water management. Reversible heat pump (IP) without options
FS
FS
FS
FS
FS
FS
FS
FS
GENERAL FEATURES
Option Domestic hot water production 3 way valve In this configuration the heat pump can be coupled to a domestic hot water tank equipped with a coil designed for a maximum water temperature between 55C and 60C. The anti legionella cycles have to be performed by means of electrical heaters placed on the heat pump outlet (see option Integrative electrical heaters) or directly inside the tank.
FS
FS
In this configuration the heat pump can be coupled to a domestic hot water tank without coil. The anti legionella cycles have to be performed by means of electrical heaters placed on the heat pump outlet (see option Integrative electrical heaters) or directly inside the tank.
FS
FS
FS
FS
FS
In this configuration the heat pump can produce instantaneously the domestic hot water using the hot water stored in the tank integrated in the unit (see accessory Domestic hot water production tank). The temperature of the domestic hot water at the unit outlet is adjusted modulating the speed of the pump on the primary side. The anti legionella cycles are not necessary.
FS
FS
FS
FS
GENERAL FEATURES
Accessories
Remote thermostat Remote control (wired or wireless) Wireless transmitter Wireless repeater Wireless adaptor for outdoor temperature sensor Condensate sensor Room hygrostat Room humidity sensor (with or without display) Rubber vibration dampers Transformer 230V / 24V - 3VA Domestic hot water production tank Pipes for solar panels connection Refrigerant circuit box Allows operating mode selection and set point adjustment. The on board temperature sensor can be used in order to realize a climatic control. Replicates all the control and visualization functionalities of the controller installed on the unit. The on board temperature sensor can be used in order to realize a climatic control. Connected to the unit controller, allows to communicate with wireless remote control and wireless outdoor temperature sensor. Extends wireless operating range. Allows to transform the wired outdoor temperature sensor, standard for all the units, in a wireless sensor. In cooling mode it allows the minimum flow temperature control when condensate generation occurs. In cooling mode it allows the minimum flow temperature control according to the room humidity. In cooling mode it allows the minimum flow temperature control according to the room dew point, calculated from the measured room humidity. Allow to reduce the transmission to the unit support plane of the mechanical vibrations generated by the compressor and by the fans in their normal operating mode. It assures the correct power supply for the condensate sensor and for the room humidity sensor. Integrated tank, to be installed under the unit, for domestic hot water production. Inside the tank a coil for solar panels integration is contained. Allow to move the connections of the solar integration coil, available on the tank (accessory), directly on the upper side of the unit. If a failure occurs inside the refrigerant circuit, it permits to restart the heat pump very quickly.
10
Model
3.1
230 - 1 - 50
5.1
230 - 1 - 50
7.1
230 - 1 - 50
9.1
230 - 1 - 50
11.1
230 - 1 - 50
U.M.
V-ph-Hz
R410A rotary 1 0 - 100 0,43 stainless steel brazed plates 1 0,53 stainless steel brazed plates 1 0,67 3 10 10 3 speed glandless pump 1 0,14 3 speed glandless pump 1 0,15 120 1,1 9,0
0 - 33 - 66 - 100
R410A rotary 1 0 - 100 0,67 stainless steel brazed plates 1 0,53 stainless steel brazed plates 1 0,67 3 10 10 3 speed glandless pump 1 0,14 3 speed glandless pump 1 0,15 120 1,1 9,0
0 - 33 - 66 - 100
R410A rotary 1 0 - 100 1,13 stainless steel brazed plates 1 0,67 stainless steel brazed plates 1 0,84 3 10 10 3 speed glandless pump 1 0,14 3 speed glandless pump 1 0,15 120 1,1 9,0
0 - 33 - 66 - 100
R410A rotary 1 0 - 100 1,13 stainless steel brazed plates 1 0,84 stainless steel brazed plates 1 1,04 3 10 10 3 speed glandless pump 1 0,14 3 speed glandless pump 1 0,15 120 1,1 9,0
0 - 33 - 66 - 100
n % kg
Compressor Quantity
Power steps Oil charge Type Quantity Water volume Type Quantity Water volume Plant side heat exchanger
n l
n l bar l l
Plant side hydraulic circuit Safety valve set point Expansion vessel volume Expansion vessel volume Plant side pump Type Quantity Installed power Type Quantity Installed power Volume
n kW
n kW l m2 kW %
11
Model
3.1
230 - 1 - 50 3,37
5.1
230 - 1 - 50 5,11
7.1
230 - 1 - 50 6,85
9.1
230 - 1 - 50 9,31
11.1
230 - 1 - 50 11,8
U.M.
V-ph-Hz kW -
Heating W10W35 ( source : water in 10C out 7C / plant : water in 30C out 35C )
0,59 5,71 578 798 7 60 0,90 5,68 874 51 14 1,24 1171 1612 22 41 5,52
kW l/h l/h
Available static head plant side Water flow rate source side IH Pressure drops source side Heating capacity Power input COP
1206
kPa kPa kW -
Heating B0W35 ( source : brine in 0C out -3C / plant : water in 30C out 35C )
2,49 0,58 4,29 427 673 5 63 3,77 0,89 4,24 646 58 11 5,06 1,22 4,15 866 51 17
kW l/h l/h
Available static head plant side Water flow rate source side Pressure drops source side Heating capacity Power input COP
1018
1359
kPa kPa kW -
Heating W10W35 ( source : water in 10C out 7C / plant : water in 30C out 35C )
0,58 5,69 566 780 6 60 3,30 0,89 5,63 857 52 13 5,01 1,23 1149 1579 21 41 5,46 6,72
9,13
11,6
kW l/h l/h
Available static head plant side Water flow rate source side Pressure drops source side Heating capacity Power input COP
1181
kPa kPa kW -
Heating B0W35 ( source : brine in 0C out -3C / plant : water in 30C out 35C )
2,44 0,57 4,28 418 658 5 64 3,70 0,88 4,20 634 997 10 58 4,97 1,21 4,11 850 52 17
kW l/h l/h
Available static head plant side Water flow rate source side IP Pressure drops source side Cooling capacity Power input EER
1471 2299
1331
kPa kPa kW -
Cooling W30W18 ( source : water in 30C out 35C / plant : water in 23C out 18C )
3,56 0,59 6,03 611 59 5 5,39 0,90 5,99 927 49 11 7,21 1,24 1242 1443 18 38 5,81
kW l/h l/h
Available static head plant side Water flow rate source side Pressure drops source side Cooling capacity Power input EER
710
1077
kPa kPa kW -
Cooling B30W18 ( source : brine in 30C out 35C / plant : water in 23C out 18C )
3,48 0,60 5,80 598 828 7 59 5,26 0,93 5,66 905 50 15 7,04 1,27 1212 1682 24 39 5,54
kW l/h l/h
Available static head plant side Water flow rate source side Pressure drops source side
1255
kPa kPa
Data declared according to EN 14511. The values are referred to units without options or accessories. Brine = water with 30% ethylene glycol.
12
Model
3.1
230 - 1 - 50 3,10
5.1
230 - 1 - 50 4,70
7.1
230 - 1 - 50 6,30
9.1
230 - 1 - 50 8,56
11.1
230 - 1 - 50 10,9
U.M.
V-ph-Hz kW -
Heating W10W45 ( source : water in 10C out 7C / plant : water in 40C out 45C )
0,71 4,37 529 686 5 61 1,08 4,35 801 54 11 1,48 1072 1384 17 44 4,26
kW l/h l/h
Available static head plant side Water flow rate source side IH Pressure drops source side Heating capacity Power input COP
1038
kPa kPa kW -
Heating B0W45 ( source : brine in 0C out -3C / plant : water in 40C out 45C )
2,29 0,70 3,27 391 560 4 65 3,47 1,07 3,24 592 849 8 60 4,65 1,46 3,18 792 54 13
kW l/h l/h
Available static head plant side Water flow rate source side Pressure drops source side
1127
kPa kPa kW -
Heating W10W45 ( source : water in 10C out 7C / plant : water in 40C out 45C )
Heating capacity Power input COP 0,70 4,34 519 672 5 62 3,04 1,07 4,31 785 54 10 4,61 1,46 1052 1355 16 45 4,23 6,18
8,39
10,7
kW l/h l/h
Available static head plant side Water flow rate source side Pressure drops source side Heating capacity Power input COP
1015
kPa kPa kW -
Heating B0W45 ( source : brine in 0C out -3C / plant : water in 40C out 45C )
2,24 0,69 3,25 382 546 3 65 3,40 1,06 3,21 581 828 8 60 4,57 1,44 3,17 779 54 12
kW l/h l/h
Available static head plant side Water flow rate source side IP Pressure drops source side Cooling capacity Power input EER
1106
kPa kPa kW -
Cooling W30W7 ( source : water in 30C out 35C / plant : water in 12C out 7C )
2,74 0,59 4,64 470 571 3 62 4,14 0,91 4,55 712 866 8 56 5,55 1,24 4,48 954 48 13
kW l/h l/h
Available static head plant side Water flow rate source side Pressure drops source side Cooling capacity Power input EER
1161
kPa kPa kW -
Cooling B30W7 ( source : brine in 30C out 35C / plant : water in 12C out 7C )
2,69 0,60 4,48 462 669 5 62 4,07 0,93 4,38 698 56 11 5,44 1,26 4,32 935 49 17
kW l/h l/h
Available static head plant side Water flow rate source side Pressure drops source side
1015
1359
kPa kPa
Data declared according to EN 14511. The values are referred to units without options or accessories. Brine = water with 30% ethylene glycol.
13
A B C D
Inlet temperature - source side [C] Power input ( brine and water )
Inlet temperature - source side [C] The graphs allow to get the corrective factors to be applied to the nominal performances in order to obtain the real performances in the selected operating conditions. The reference nominal conditions are : - water-water units : W10W35 (source : water in 10C out 7C / plant : water in 30C out 35C) - brine-water units : B0W35 (source : water in 0C out -3C / plant : water in 30C out 35C) Outlet temperature plant side : A = 55C B = 45C C = 35C D = 25C COP ( water )
3,0 2,8
1,8 1,7 1,6 1,5 1,4 1,3 1,2 1,1 1,0 0,9 0,8 0,7 0,6 0,5 0,4 -10 -5 0 5 10 15 20 25
3,0 2,8 2,6 2,4 2,2 2,0 1,8 1,6 1,4 1,2 1,0 0,8 0,6 0,4 -10
D C B A
2,6 2,4 2,2 2,0 1,8 1,6 1,4 1,2 1,0 0,8 0,6 0,4
D C B A
-5
10
15
20
25
-10
-5
10
15
20
25
14
The graphs allow to get the corrective factors to be applied to the nominal performances in order to obtain the real performances in the selected operating conditions. The reference nominal conditions are : - water-water units : W30W7 (source : water in 30C out 35C / plant : water in 12C out 7C) - brine-water units : B30W7 (source : brine in 30C out 35C / plant : water in 12C out 7C) Outlet temperature plant side : A = 24C B = 18C C = 12C D = 7C
Inlet temperature - source side [C] Power input ( brine and water )
1,8 1,7 1,6 1,5 1,4 1,3 1,2 1,1 1,0 0,9 0,8 0,7 0,6 0,5 0,4 -10 -5 0 5 10 15 20 25 30 35 40 45
A B C D
C D A B
-10
-5
10
15
20
25
30
35
40
45
The performances of the units, when used as brine - water, are referred to applications in which the source side fluid is a solution of water and 30% ethylene glycol by volume. Such a concentration guarantees a freezing temperature of about -15C and allows the unit to work inside the declared operating limits.
15
70
60
50
40
30
20
10
Flow rate [ l/h ] Pressure drops A = unit with option Domestic hot water production : 3 way valve B = unit with option Integrative electrical heaters C = unit with option Passive cooling
40
35
30
A B C
25
20
15
10
Flow rate [ l/h ] The graphs are referred to units operating with water at the temperature of 10C (density 1000 kg/m3). 16
35
30
25
20
15
10
Available static head - unit with option Source side flow rate management : Pump
80
70
60
50
40
11.1
30
20
10
The graphs are referred to units operating with water at the temperature of 10C (density 1000 kg/m3). 17
Flow rate [ l/h ] Domestic hot water side hydraulic performances Available static head A = unit with option Domestic hot water production : 3 way valve B = unit with option Domestic hot water production : 3 way valve with primary heat exchanger
80
70
A 9.1 11.1
60
50
40
30
20
10
Flow rate [ l/h ] The graphs are referred to units operating with water at the temperature of 10C (density 1000 kg/m3). 18
50 45 40 35 30 25 20 15 10 5 0 -5 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
35 30 25 20 15 10 5 0 -5 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
Passive cooling
19
3.1
230 - 1 - 50 5,9 1,3 36 32
5.1
230 - 1 - 50 7,7 1,7 45 35
7.1
230 - 1 - 50 10,1 2,2 52 38
9.1
230 - 1 - 50 13,3 2,9 82 41
11.1
230 - 1 - 50 17,0 3,7 112 43
U.M.
Maximum total current input Maximum total power input Maximum total start current Maximum total start current with soft starter (option)
V-ph-Hz A kW A A
M.I.C.
400 - 3N - 50 39,1 13,0 9,0 230 - 1 - 50 0,15 230 - 1 - 50 0,08 230 - 1 - 50 0,14 0,7 0,4 0,8
230 - 1 - 50
400 - 3N - 50 39,1 13,0 9,0 230 - 1 - 50 0,15 230 - 1 - 50 0,08 230 - 1 - 50 0,14 0,7 0,4 0,8
230 - 1 - 50
400 - 3N - 50 39,1 13,0 9,0 230 - 1 - 50 0,15 230 - 1 - 50 0,08 230 - 1 - 50 0,14 0,7 0,4 0,8
230 - 1 - 50
400 - 3N - 50 39,1 13,0 9,0 230 - 1 - 50 0,15 230 - 1 - 50 0,08 230 - 1 - 50 0,14 0,7 0,4 0,8
230 - 1 - 50
400 - 3N - 50 39,1 13,0 9,0 230 - 1 - 50 0,15 230 - 1 - 50 0,08 230 - 1 - 50 0,14 0,7 0,4 0,8
230 - 1 - 50
V-ph-Hz A A kW
F.L.A. F.L.I.
V-ph-Hz A kW
Domestic hot water production pump (with option 3 way valve with primary heat exchanger)
Power supply F.L.A. F.L.I. Maximum total current input Maximum total power input
V-ph-Hz A kW
Domestic hot water production pump (with option 3 way valve with secondary heat exchanger)
Power supply F.L.A. F.L.I. Maximum total current input Maximum total power input
V-ph-Hz A kW
63
125
250
[dB]
74 75 75 76 76
[dB(A)]
Reference conditions Performances referred to units operating in heating mode at nominal conditions W10W35. Unit placed in free field on reflecting surface (directional factor equal to 2). The sound power level is measured according to ISO 3744 standard. The sound pressure level is calculated according to ISO 3744 and is referred to a distance of 1 meter from the external surface of the unit.
20
3.1
5.1
7.1
9.1
11.1
U.M.
Pump
2 way valve 3 way valve 3 way valve with primary heat exchanger
Domestic hot water production tank Pipes for solar panels connection Refrigerant circuit box
Transport weights
Unit Unit without options Source side flow rate management Domestic hot water production Passive cooling Accessories Options 148 3 2 3 9 10 5 5 95 52 3 452 3 2 3 9 10 5 5 95 56 3 154 3 2 3 9 10 5 5 95 58 3 163 3 2 3 9 10 5 5 95 67 3 166 3 2 3 9 10 5 5 95 70 3
kg kg kg kg kg kg kg kg kg kg kg
Pump
2 way valve 3 way valve 3 way valve with primary heat exchanger
Domestic hot water production tank Pipes for solar panels connection Refrigerant circuit box
Operating weights
Unit Unit without options Source side flow rate management Domestic hot water production Passive cooling Accessories Options 133 4 3 5 13 14 8 6 202 5 137 4 3 5 13 14 8 6 202 5 139 4 3 5 13 14 8 6 202 5 148 4 3 5 13 14 8 6 202 5 152 4 3 5 13 14 8 6 202 5
kg kg kg kg kg kg kg kg kg kg
Pump
2 way valve 3 way valve 3 way valve with primary heat exchanger
Domestic hot water production tank Pipes for solar panels connection
21
8 1 2 3 4 5
7 6
53
90
90
80
80
80
90
90
85
852
600
600
600
Minimum operating area Rispect the free area around the unit as shown in figure in order to guarantee a good accessibility and facilitate maintenance and control operations.
B
A B
600 mm 300 mm
B
22
1678
The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual, if due to printing or typing mistakes. The manufacturer reserves the right to apply changes and improvements to the products at any time and without notice.
23
Ferroli spa 37047 San Bonifacio (Verona) Italy Via Ritonda 78/A tel. +39.045.6139411 fax +39.045.6100933 www.ferroli.it