Beruflich Dokumente
Kultur Dokumente
Ba
Water-drainage piping
Socket-outlet
Gaz Radiator
Lighting
Metal bath
Metal door-frame
N11
Figure N19 below summarizes the main requirements prescribed in many national and international standards. Note: Section in brackets refer to sections of IEC 60364-7
Protection principles
c TT or TN-S systems c Differential protection v 300 mA if the earth electrode resistance is i 80 ohms instantaneous or short time delay (type S) v 30 mA if the earth electrode resistance is u 500 ohms c surge arrester at the origin of the installation if v supply is from overheadline with bare conductors, and if v the keraunic level > 25 c a protective earth (PE) conductor on all circuits Supplementary equipotential bonding in zones 0, 1, 2 and 3 SELV 12 V only 27
IP level 20
Switchgear
Socket-outlets
Installation materials
Ba ck
Switch operating handles Protection by and similar devices on 30 mA RCDs distribution panels, to be mounted between 1 metre and 1.80 metre above the floor
Zone 1
SELV 12 V
25
Zone 2
SELV 12 V or 30 mA RCD
24
Class II limited to strict minimum Class II limited to strict minimum Class II limited to strict minimum Only socket-outlets protected by : c 30 mA RCD or c Electrical separation or c SELV 50 V
Special appliances
Special aplliances Water heater Special appliances Water heater Class II luminaires
Zone 3
21
28
N12
Zone 1
25
Class II limited to strict minimum Class II limited to strict minimum Only socket-outlets protected by : c 30 mA RCD or c electrical separation or c SELV 50 V
Special appliances
Special appliances
Zone 2
Saunas (section 703) Work sites (section 704) Agricultural and horticultural establishments (section 705) Restricted conductive locations (section 706)
22 (indoor) 24 (outdoor) 24 Class II Conventional voltage limit UL reduced to 25 V Conventional voltage limit UL reduced to 25 V Protection against fire risks by 500 mA RCDs 44 35 Mechanically protected
2x
Protection of: c Portable tools by: v SELV or v Electrical separation c Hand-held lamps v By SELV c Fixed equipement by v SELV v Electrical separation v 30 mA RCDs v Special supplementary equipotential bonding
Fig. N19 : Main requirements prescribed in many national and international standards (continued on opposite page)
Ba
Protection principles Protection by 30 mA RCDs and equipotential bonding of all exposed and extraneous conductive parts TV-S system recommended TT system if leakage current is limited. Protective conductor 10 mm2 minimum in aluminium. Smaller sizes (in copper) must be doubled.
IP level
Switchgear
Socket-outlets
Installation materials
ck
55
The cable length for connection to pleasure craft must not exceeded 25 m
Medical locations (section 710) Exhibitions, shows and stands (section 711) Balneotherapy (cure-centre baths)
IT medical system equipotential bonding TT or TN-S systems Individual: see section 701 (volumes 0 and 1) Collective: see section 702 (volumes 0 and 1) Explosion risks in security zones Protection by RCDs or by electrical separation 23 4x
Socket-outlets shall be placed at a height of 0.80 m to 1.50 m from the ground. Protection of circuits by 30 mA RCDs (one per 6 socket-outlets) Protection of circuits by 30 mA RCDs (one per 6 socket-outlets) Protection by 30 mA RCDs Protection by 30 mA RCDs
Motor-fuel filling stations Motor vehicules External lighting installations (section 714) Mobile or transportable units (section 717)
Protection by 30 mA RCDs 30 mA RCDs must be used for all socket-outlets supplying equipment outside the unit
N13
Fig. N19 : Main requirements prescribed in many national and international standards (concluded)