INSTALLATION AND MAINTENANCE INSTRUCTIONS

FRM-1 Relay Control Module


Specifications Normal Operating Voltage: Maximum Current Draw: Average Operating Current: EOL Resistance: Temperature Range: Humidity: Dimensions: Accessories:

12 Clintonville Rd Northford, CT 06472-1653 (203) 484-7161

15 to 32 VDC 6.5 mA (LED on) 270A (LED flashing) Not used 32F to 120F (0C to 49C) 10% to 93% Noncondensing 41/2 H x 4 W x 11/4 D (Mounts to a 4 square by 21/8 deep box.) SMB500 Electrical Box; CB500 Barrier
appropriate wiring diagrams. 2. Set the address on the module per job drawings. Note: Some panels support extended addressing. In order to set the module above address 99 on compatible systems, carefully remove the stop on the upper rotary switch with thumb in the direction shown in Figure 1. 3. Secure module to electrical box (supplied by installer), as shown in Figure 2A. Figure 1. Removing rotary switch stop:

Before Installing This information is included as a quick reference installation guide. Refer to the appropriate Notifier control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules. NOTICE: This manual should be left with the owner/user of this equipment. General Description The FRM-1 Relay Control Module is intended for use in intelligent, two-wire systems where the individual address of each module is selected using the built-in rotary switches. It allows a compatible control panel to switch discrete contacts by code command. The relay contains two isolated sets of Form-C contacts, which operate as a DPDT switch and are rated in accordance with the table in the manual. Circuit connections to the relay contacts are not supervised by the module. The module also has a panel controlled LED indicator. This module can be used to replace a CMX-2 module that has been configured for Form-C operation. Compatibility Requirements To ensure proper operation, this module shall be connected to a compatible Notifier system control panel (list available from Notifier). Mounting The FRM-1 mounts directly to 4 square electrical boxes (see Figure 2A). The box must have a minimum depth of 21 /8. Surface mounted electrical boxes (SMB500) are available from Notifier. Wiring NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. When using control modules in nonpower limited applications, the CB500 Module Barrier must be used to meet UL requirements for the separation of power-limited and nonpower-limited terminals and wiring. The barrier must be inserted into a 4x4x21 /8 junction box, and the control module must be placed into the barrier and attached to the junction box (Figure 2A). The power-limited wiring must be placed into the isolated quadrant of the module barrier (Figure 2B). 1. Install module wiring in accordance with the job drawings and

9 8 7 6 5
LOOP

ONES

67 8 9 5 10 11 4 3 12 13 2 1 0 15 14 TENS 6789 5 4 3 2 10

0 1 2 3 4

ADDRESS

A78-2318-07

Figure 2A. Module mounting with barrier:

Figure 2B:

LO OP

4 5 6 78 3 9 TENS 2 10 10 1211 15 4 5 6 7 8 14 13 3 9 ON 2 ES 1 0 AD DR ES S

9 1 0
LO OP

4 5 6 78 3 9 TEN 2 10 S 10 1211 15 4 5 6 7 8 14 13 9 ON 2 ES 1 0 AD DR ES S

9 1 0

ISOLATED QUADRANT

A78-2611-11

A78-2610-08

N500-47-00

I56-1170-04

Relay Contact Ratings:

CURRENT RATING
3A 2A .9 A .9 A .5 A 1A .5 A .7 A

MAXIMUM VOLTAGE
30 VDC 30 VDC 110 VDC 125 VAC 30 VDC 30 VDC 125 VAC 75 VAC

LOAD DESCRIPTION
Resistive Resistive Resistive Resistive Inductive (L/R=5ms) Inductive (L/R=2ms) Inductive (PF=.35) Inductive (PF=.35)

APPLICATION
Non Coded Coded Non Coded Non Coded Coded Coded Non Coded Non Coded

All relay switch contacts are shipped as shown in Figure 3, but may have transferred during shipping. To ensure that the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.

Figure 3. Relay module wiring diagram:


COMMUNICATION LINE 32 VDC Max. SHIELDED-TWISTED PAIR IS RECOMMENDED

CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY


)( )+(
FROM PANEL OR PREVIOUS DEVICE

TO NEXT DEVICE

)( )+(

CONTROL MODULE

RELAY COMMON 2 NORMALLY CLOSED 2 NORMALLY OPEN 2 RELAY COMMON 1 NORMALLY CLOSED 1
LOOP

9 8 7 6 5

0 1 2 3 4
ADDRESS

)( )+(
NORMALLY OPEN 1

IF ANY WIRING TO TERMINALS 3 9 IS NONPOWER LIMITED, THE CB500 BARRIER IS REQUIRED. THE CB500 INCLUDES A NONPOWER LIMITED LABEL, WHICH MUST BE PLACED OVER THE POWER LIMITED TERMINAL INFORMATION ON THE NAMEPLATE LABEL.

MODULE DOES NOT SUPERVISE CONTROLLED CIRCUITS

A78-2286-09

N500-47-00

I56-1170-04 2001 Notifier