Sie sind auf Seite 1von 17

Pradeep Jain

3.1- 1/17

HOW TO INCREASE HEAT TRANSFER AND REDUCE WATERWALL TUBE FAILURE IN HIGH PRESSURE BOILERS
Dr. Pradeep Jain -DGM, NETRA- R&D, NTPC Limited,

ABSTRACT:
In spite of maintaining the very good water chemistry in water / steam cycle of thermal power plant, corrosion phenomena takes place in the boilers. The product of corrosion in the feed water system transported into the boiler and gets deposited on the internal surface of waterwall tubes. It leads to overheating and On-load corrosion and ultimately tube failure. To achieve the almost zero tube failure in waterwall of high pressure boilers, post-operational chemical cleaning is essential at the frequent intervals in the life span of power plant which will improve heat transfer and reduce under deposit onload corrosion. This paper will discuss the phenomena of localised corrosion, its remedial measures to achieve near zero tube failure.

INTRODUCTION
The NTPC Limited has more than 125 numbers of fossils red, sub critical, high pressure boilers ranging from 100 to 190 kg/cm2. The saturation temperature of boiler water varies from 250 370 C depending upon the boiler pressure. The capacity of these boilers varies from 60 MW to 500 MW, whereas the heat ux varies from 200-300 KW/m2. These boilers are generally drum type and a few once through types. Waterwall tubes of these boilers are made of carbon steel or low alloy steel. Dematerialized water is used in these boilers with proper boiler water treatment generally recommended by Original Equipment Manufacturer (OEM). Generally Non volatile treatment (NVT) i.e. TSP is used in most of the boiler to maintain the pH except a few boilers where, all volatile treatment (AVT) chemicals is used. Due to On-load corrosion in low pressure parts, condenser and heat exchangers of boilers, deposition of corrosion products and salt concentration takes place on the internal surface of waterwall tubes. Ingress of raw water due to condenser leaks into the feed water also increases the salt deposition and oxygen concentration on internal surface due to boiling. The condenser of 500 MW generators can contain 300 miles of tubing and approx. 50000 tube-to-tube-plate joints, so some in-leakage of the external cooling water is inevitable from time to time. Thermal conductivity of this deposit is very low (about 2 W/m/C) in comparison of carbon steel (about 50 W/mC), thus signicantly reduces the heat transfer and increases the outer metal temperature. Frequent tube failure has been observed in old boilers ran more than 100,000 hours due to internal localised corrosion. Tube failure investigation indicated that the main reason of waterwall tube failure is either due to hydrogen damage or caustic corrosion or overheating or the effect of all. Some of the case histories experienced in different capacities boilers of State Electricity Boards as well as NTPC Ltd. along with their remedial measures to attain zero tube

Pradeep Jain

3.1- 2/17

failure have been discussed in this paper.

How mild steel corrodes in boiler water


Waterwall tubes in most of the fossil-red boiler are made of carbon steel. In pure DM water, or in very dilute acid or alkaline solutions at boiler temperature, it normally corrodes very slowly to form the black iron oxide known as magnetite (Fe3O4). The overall reaction is: 3 Fe + 4 H2O ------- Fe3O4 + 4 H2 The corrosion rate is dependent by the rate at which the reactant (water) can reach the metal surface and the reaction product can leave the surface. In nearly neutral solutions, magnetite is very slightly soluble and it deposits as coherent and tenacious surface lm, which greatly impedes this two-way chemical trafc. The transport processes are dominated by slow state diffusion through the oxide layer and the corrosion rate is virtually independent of solution composition. The corrosion rate is also diminishes with time as the oxide thickness grows. Even after years of exposure, the layer is no more than a few microns thick. In more alkaline or more acid solutions, magnetite becomes increasingly soluble and precipitates in a different physical form. Instead of yielding a strongly coherent lm, it has a more porous structure. Soluble species can now diffuse relatively rapidly through the lm and the corrosion rate is much faster, although it still falls off the time as the oxide accumulated. The deposition of salts and corrosion products observed in different waterwall tubes has shown in the photograph no.1-4.

Photograph no.1 & 2 showing waterwall tubes of 60 MW boilers having a very thick deposit ranging

Pradeep Jain

3.1- 3/17

thickness 1.0-1.5 mm.

Photograph no. 3 & 4 showing a waterwall tube of 200 & 110 MW boilers having a thick iron oxide as well as hardness salt deposition which is non uniform in nature.

Regions of Heat Transfer in Boilers


Both recirculating drum type boilers and once-through boilers are in use in NTPC. Drum type boiler consists of three separate components: an evaporator (waterwall area), where water is converted to a steam-water mixture: a drum, in which two phases are separated and a super heater. A once-through boiler, on the other hand, is a single unit with sub-cooled (below the boiling point at that pressure) water entering at one end and superheated steam leaving at the other end. Because of its lower capital cost, the once-through type is becoming more popular and now NTPC is going for 660 MW super critical once-through boilers. The various regions of heat transfer in a once-through boiler tube, with uniform heat ux, are shown in Figure-1.

Pradeep Jain

3.1- 4/17

Figure-1 Showing water-steam formation in waterwall tube. Of the six different heat transfer regions, ve are usually present in a recirculation boiler (the exception is the dryout / post-dryout regions. dryout should not occur in recirculation boilers, but is possible if the ow in a tube is reduced for any reason, or if one or more adjacent tubes are plugged). At the inlet, both wall and liquid are below saturation temperature and heating is by convection. At some point along the tube, the wall temperature exceeds the saturation temperature and bubbles are formed on the wall, although the bulk liquid temperature is below saturation. This is the region of sub-cooled nucleate boiling. (Continuing along the tube, the region of saturated nucleate boiling, where the bulk liquid temperature reaches saturation, is then enters). As more steam is formed, small bubbles coalesce to form large bubbles (slug ow). Eventually, these combine to give a central core of steam and leave an annular ow of water along the wall. Further along the tube, the liquid lm on the wall becomes sufciently thin for convective heat transfer to the liquid surface coupled with direct evaporation to become the only means of heat transfer, because this method of heat transfer is highly efcient, nucleation of bubbles at the wall ceases through lack of sufcient superheat. At the same time, increasing steam velocity results in entrainment of liquid in the form of droplets. Depletion of the liquid lm by evaporation and droplet formation eventually results in complete dryout of the tube wall. A dramatic increase in wall temperature occurs at the dryout point. In the post-dryout region heat

Pradeep Jain

3.1- 5/17

transfer is by convection in the steam phase, the droplets gradually disappearing by evaporation. At low heat uxes direct impingement of droplets on to the wall may also occur. Evaporation of all droplets nally produces single phase superheated conditions.

WATER CHEMISTRY
Impurities and additives present in water fed to high pressure boilers are controlled within closely dened limits for two very good reasons. To reduce corrosion in the water-steam circuits to a minimum under normal and fault conditions (2) To reduce transport of iron oxide, hardness salts, silica etc. into the boiler and turbine. These substances deposit out on the heat transfer surfaces and turbine blades. Accelerated corrosion in many regions of high pressure boilers is known to be brought about by concentration of corrosive substances (chlorides, sulphates, hydroxides and phosphates) by boiling. The main water chemistry regimes used to reduce corrosion and transport of iron oxide etc. to a minimum are given in Table below together with the advantages and disadvantages of each regime. Regime Dissolved Oxygen level Protective oxide on tube surface Magnetite, Fe3O4 Advantages Disadvantages (1)

Presence of ammonia No neutralisation action at reduces transport of high temperature. iron from feed train Ammonia can attack copper into boiler containing alloys in condenser Ammonia is not and feed heaters in presence corrosive at high of oxygen temperature Na3PO4 Low <5 ppb) Magnetite, Neutralizes acid Na3PO4 or NaOH can be or NaOH Fe3O4 chloride and acid concentrated by boiling, dosed sulphates forming corrosive solutions. Reduced rate of No neutralising action High High >200 ppb) Hematite transport of iron into Ingress of chloride results in Oxygen (Alpha boiler compared with rapid corrosion. Fe2O3) low oxygen. Besides controlling the levels of dissolved oxygen and pH by means of chemical additives, as indicated

All volatile treatment (0.5 ppm NH3)

Low <5 ppb)

Pradeep Jain

3.1- 6/17

in Table, very strict limits are specied on the concentrations of many other substances. For example, in the case of a typical once-through boiler using all volatile treatment (AVT) water chemistry, upper limits for various substances under steady load conditions are as follows: Sodium Chloride N 2H 4 Cu + Ti 5 ppb 2 ppb 1.5 X O2 (Min 10 ppb) 2 ppb Sulphate Silica Iron 2 ppb 20 ppb 5 ppb

CORROSION AND DEPOSITION IN VARIOUS HEAT TRANSFER REGIONS:


Convective Heating region: In this region, at the inlet to a once through boiler, there have been no reported instances of tube failure owing to heat ux conditions. In the absence of boiling, the increase in corrosion rate should be small and related to the higher metal temperature and activation energy of the corrosion process in pure water. Studies on surfaces which have been oxidized under good water chemistry conditions show that even at high heat uxes as high as 800 kW/m2, negligible amounts of sodium and chlorine are taken up from NaCl, NaOH, NaHSO4, Na2SO4 and Na3PO4 solutions. Some iron is deposited from Fe (OH)2, which is likely to be the initial form of iron produced by protective or aggressive corrosion under alkaline conditions. Nucleate boiling regions: Three types of situation are possible. Two of these are concerned with the formation of oxide deposits with different porosities on a tube surface and the effect of this on corrosion. In the rst instance, all oxide is assumed to deposit from iron dissolved in solution and to form an oxide layer of low porosity (<10%). In the second situation, all oxide is considered to deposit from particles suspended in the liquid and to have a high porosity (>50%). The situation in a real boiler may lie anywhere between these two extremes. The third situation is concerned with boiling at defects on a tube surface. Oxide deposit of high porosity: Oxide of high porosity (>50%) is found to deposit in drum as well as once-through boilers under both low and high oxygen water chemistry conditions. The deposition rate is approx. proportional to the concentration of particulate iron oxide and the square of the heat ux. The best approximation to the real situation is given by

Pradeep Jain

3.1- 7/17

D = k q2 c t Where, D = amount of magnetite deposited (kg/m2) q = the heat ux (W/m2) c = concentration of iron in water (kg/m3) t = time (hour) k = constant ( approx. 5 X 10-13 / W2 m2/s In a wick boiling mechanism, salts dissolved in the boiler water can be concentrated by factors > 104 as shown in the gure-2.

Generally, the protective magnetite scale thickness is 10-15 microns in the waterwall tube. When the corrosion rate increases due to upset of water chemistry parameters in boiler, (due to salt ingress and concentration), the deposit formation also increases due to corrosion of metal and precipitation of contaminants whose water solubility decreases at higher temperature on the evaporator tube surface. To maintain the pH in boiler water, in case of reduction of pH due to salt ingress, addition of more Tri Sodium Phosphate (TSP) is required. In this process, at some places on the internal surface of waterwall tubes, deposit thickness increases and the protective iron oxide scale becomes non protective and porous in nature. Porous, insulating types of deposits allow boiler water to diffuse into the deposit where the water becomes trapped and boils. The boiling of deposit in entrapped water produces relatively pure steam which tends to diffuse out of the deposit, leaving behind super heated non-boiling equilibrium solution of caustic, which is responsible for caustic corrosion or acidic solution, which is responsible of hydrogen damage in waterwall tubes as discussed below.

Pradeep Jain

3.1- 8/17

CAUSTIC CORROSION

Figure-2 showing salt concentration under the deposit by Wick boiling phenomena If the salt concentrated under the deposit is having high pH due to concentration of caustic from TSP dosing, it start dissolution of protective magnetite (Fe3O4) layer on the evaporator tube wall inner surface and form sodium ferrite (NaFeO2) and sodium ferroate (Na2FeO2) as shown in the equation. Fe3O4 + 4 NaOH ------- NaFeO2 + Na2FeO2 + 2 H2O

Caustic corrosion has been shown in the photographs no.5 & 6. in waterwall tube of 200
MW boilers.

Pradeep Jain

3.1- 9/17

ACIDIC CORROSION
Solution of low pH is generated in high pressure boilers in two different ways: 1. pH of the entire boiler water is reduced when contaminants which are acidic or becomes acidic when heated in to the boiler. 2. The bulk boiler water remains alkaline but acidic solutions are generated within corrosion pits by the action of dissolved oxygen and chloride. The most common acid forming contaminant is sea water or a river water which is low in carbonate and sulphate. In the boiler, the acidity is increased locally to corrosive concentrations by boiling. In the acidic or highly alkaline conditions, iron reacts and hydrogen is liberated. Fe + 2 NaOH = Fe + 2 HCl = Na2FeO2 + H2 FeCl2 + H2

If the hydrogen is liberated in an atomic form, it is capable of diffusing into the steel. Some of this diffused, atomic hydrogen will combine at metal grain boundaries or inclusions to produce molecular hydrogen, or it will react with iron carbides in the metal to produce methane. Fe3C + 4 H = CH4 + 3 Fe

Because neither molecular hydrogen nor methane is capable of diffusing through the steel, these gases accumulate, primarily at grain boundaries. Eventually, the gas pressure created will cause separation of the metal at its grain boundaries, forming discontinuous, intergranular micro cracks as shown in the micrograph-1.

Pradeep Jain

3.1- 10/17

Micrograph-1 showing the ssures and cracks inside the metal due to hydrogen damage. As these micro cracks accumulate, tube strength diminishes until stresses imposed by the internal pressure exceed the tensile strength of the remaining, intact metal. At this point a thick-walled, longitudinal burst may occur depending on the extent of hydrogen damage as shown in photographs no. 7 & 8.

Photographs no. 7 & 8, Waterwall tubes show the failure due to hydrogen damage due to localised acidic condition.

EXPERIMENTAL PROCEDURE FOR DEPOSIT ASSESSMENT IN WATERWALL TUBE


Boiler tube sampling: Four waterwall tubes are cut from the four corner / sides of the high heat ux zone of the boilers, i.e. mainly from the uppermost portion of (2-3 meters above) burner zone. The tube sample are prepared as per ASTM D-3483, machined and cut longitudinally in two parts, one being the hot side (internal surfaces facing re side) and the other, the cold side (internal surfaces facing remote side). Internal deposition from the samples is removed for chemical analysis mechanically by pressing the machined sample in a vice. The average quantity of internal deposits is calculated separately for both the sides from the difference between sample tube weights, measured before and after the deposits are removed chemically.

Pradeep Jain

3.1- 11/17

Deposit quantity assessment: Waterwall tube samples are collected from site and machined on the outer surface. The outer machined surface of the tube is painted with corrosion resistant lacquer. The internal surface area (A, in cm2) is measured and the initial weight (W1, in mg) of the tube samples is measured. The waterwall tube sample is cleaned in 5% inhibited hydrochloric acid solvent at 65 C and put on a magnetic stirrer till the deposit is removed completely from the internal surfaces. Then it is washed with demineralised water and an alkaline solution and dipped in a surface passivation solution for 5-10 minutes. The nal weight of the sample (W2, in mg) is measured. The quantity of internal deposit (DQ, in mg.cm2) is calculated by the following formula. W1 W2 DQ = --------------A

CRITARIA FOR CHEMICAL CLEANING


Chemical cleaning of a boiler is suggested on the basis of the quantity of intenal deposit present in the waterwall tubes of the boiler. When the quantity of deposit exceeds 40 mg/cm2, the tube surfaces are considered to be very dirty surfaces as per the Indian Standard 10391-1998 and the chemical cleaning is suggested to improve the heat transfer and reduce the overheating. The guidelines are given in Table-1.

Table-1 showing limits of deposit quantity allowed in waterwall tubes at different pressure. The deposit quantity measured in high pressure boilers of different site are given here along with the trend chart and recommendations for chemical cleaning.

Pradeep Jain

3.1- 12/17

A List of NTPC boilers in which chemical cleaning carried out under the supervision of NTPC (R&D)
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18 . 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. Ramagundam, Boiler # 1, Ramagundam, Boiler # 2, Ramagundam, Boiler # 3, Tanda, Boiler # 1, Tanda, Boiler # 2, Tanda, Boiler # 3, Tanda, Boiler # 4, Talcher Thermal, Boiler # 1, Talcher Thermal, Boiler # 2, Talcher Thermal, Boiler # 3, Talcher Thermal, Boiler # 4, Badarpur, Boiler, #1 Badarpur, Boiler # 3 Badarpur, Boiler # 2 Badarpur, Boiler #4 Korba, Boiler #1 Singrauli, Boiler #3 Tanda, Boiler # 3, Vindhyachal, Boiler # 1, Farakka, Boiler #3 Ramagundam, Boiler #3 Unchhahar, Boiler #1 Rihand, Boiler #1 Ramagundam, Boiler #1 Vindhyachal, Boiler # 2 Vindhyachal, Boiler # 4 Kahalgaon, Boiler # 4 Farakka, Boiler # 2 200 MW 200 MW 200 MW 110 MW 110 MW 110 MW 110 MW 60 MW 60 MW 60 MW 60 MW 95 MW 95 MW 95 MW 210 MW 200 MW 200 MW 110 MW 210 MW 200 MW 200 MW 210 MW 500 MW 200 MW 210 MW 210 MW 210 MW 200 MW Oct. 1998 Sept. 1999 July 2000 June 2000 Feb. 2002 Jan. 2001 Aug. 2002 Dec. 1995 Feb. 1996 June 2002 May 2000 Dec. 2006 Oct. 2004 Nov. 2004 Aug. 2006 Oct. 2007 April 2008 May 2008 May 2008 July 2008 Aug. 2008 Aug. 2008 Sept. 2008 Sept. 2008 Oct. 2008 May 2009 May 2009 May 2009

CONCLUSIONS
Failure investigation studies of waterwall tubes of different capacity boilers indicated the reasons of tube failure are:

Pradeep Jain

3.1- 13/17

Formation of localised alkaline / acidic conditions is as per the mechanism of wick boiling phenomena under the deposit due to ingress of raw water into the condensate water. Acidic localised condition is responsible for hydrogen damage as observed in many old boilers where the deposit is very high and adherent type. Alkaline condition is responsible for caustic corrosion where the deposit is dense and porous in nature. Overheating of tubes due to deposition of salts on the internal surface of tube.

REMEDIAL MEASURES
It is suggested, to control the ingress of cooling water from the condenser tube leakage which will reduce the phenomena of salt concentration on the internal surface of boiler tubes. If the internal oxide growth increases from the limit as per the Indian Standards of IS-10391-98. Post operational chemical cleaning of boilers should be carried out to remove the existing porous deposit and to form a new adherent magnetite layer. Magnetite layer will work as a protective layer and reduce the possibilities of on-load corrosion.

ACKNOWLEDGEMENT
Authors are thankful to Shri Sharad Anand, E.D., NETRA, Shri A.K.Mohindru G.M. (NETRA-R&D) and Shri J. Rajendran AGM (NETRA-R&D) for his continued interest, valuable guidance and constant encouragement for chemical cleaning of boilers. The contributions of our colleagues of NTPC sites and NETRA, who have helped directly or indirectly for carryout the chemical cleaning, are greatly acknowledged.

REFERENCES
1. Test methods for accumulated deposition in a steam generator tube, 2005, ASTM International, West Conshohocken, PA, USA, ASTM Standard D-3483-05. Code of practice for chemical cleaning of boilers, 1998, Bureau of Indian Standards, New Delhi, IS-10391-98. Sugimoto A, Ueki, H. Sakuma, S., Proc. American Power Conference, 1972. Illinois institute of Technology, Chicago, IL, USA, 34, 764

2.

3.

Pradeep Jain

3.1- 14/17

4.

David E. Hendrik, Hydrogen attack on waterwall tubes in a high pressure boiler, Material Performance, Aug. 1995, pp-46-51. C. Syrett, Corrosion in fossils fuel power plant, EPRI, USA L. Tomlinson and A.M. Pritchard, Effects of heat ux on corrosion of high pressure boilers, Br. corrosion J., 1985, vol.20, No.4, pp-187-195. R.D. Port, Identication of corrosion damage in boilers, Material Performance, Dec. 1994, pp 45-51. G.M.W. Mann, History and causes of On-load water side corrosion in power plants, Br. Corrosion J., 1977, vol. 12 No.1, pp 7-14.

5. 6.

7.

8.

ABOUT THE AUTHOR

Dr. Pradeep Jain, M.Sc., MBA, Ph.D. (Chemistry) 4 years experience in O&M, Water Chemistry at Thermal Power plants, Satpura and Korba (MPEB) from 1982-86. Joined NTPC (R&D) in 1986 and having 23 years of work experience at in the eld of water chemistry and corrosion studies in High pressure Boilers, Turbines and Generators of power plants. Specialized in the eld of Post-operational chemical cleaning of high-pressure boilers and condensers. Carried out solvent selection studies and supervised post-operational chemical cleaning of 35 nos. of NTPC and 06 numbers of State Electricity Boilers and improve the heat transfer efciency and heat rate in the range of 20-30 Kcal/kwh.

Pradeep Jain

3.1- 15/17

Recently, he has visited to Fujairah water and power plant, UAE to nd out the Root cause Failure in evaporator tubes in HRSGs. It is an international consultancy work through NTPC - International consultancy group. Working in the eld of void fraction measurement and thermal monitoring in waterwall tubes to measure the heat ux, internal deposit and steam water ratio. Published research papers in national and international journals and le two patents for void fraction measurement techniques. Presently working as Deputy General Manager, NETRA-R&D Supporting Tables:

Table-2, Badarpur unit no. 1 was chemically cleaned once in Dec. 2006

Pradeep Jain

3.1- 16/17

Table-3, Badarpur unit no. 2 was chemically cleaned once in Nov. 2004

Table-4, Badarpur unit no. 3 was chemically cleaned once in Oct.. 2004

Pradeep Jain

3.1- 17/17

Table-5, Badarpur unit no. 4 was chemically cleaned once in Aug. 2006

Table-6, Badarpur unit no. 5, two stage chemical cleaning recommended in Dec. 2005

Das könnte Ihnen auch gefallen