When selecting relays for bus protection , a major concern is the ability of the protective relaying scheme to restrain from tripping for close-in line faults. Tripping for bus faults, the reason for installing bus differential relaying, is less of a concern. During fault testing conditions, line circuit breakers, rather than bus sectionalizing circuit breakers or bus tie circuit breakers, should be closed to test bus integrity. Bus differential, which is the most sensitive and reliable method for protecting a substation bus, is installed at transmission and distribution substations and switchyards. Overcurrent protection may be used for bus protection at lower voltage substations.
Figure 1 - One-line diagram showing Bus, circuit breakers, CTs, and secondary wiring to Bus differential relay.
During the initial development of power systems, substation buses were protected with overcurrent differential relays as illustrated in Figure 1. CTs are connected so that relays respond to the difference between incoming and outgoing current. But, since the possibility of CT saturation cannot be eliminated for close-in line faults, overcurrent differential relays are delayed to coordinate with transmission- or distribution-line protection. For a close-in fault on the 230-21 line, the assumption is that busside CTs (connected to line relays) operate as designed, but that the line-side CTs (connected to the bus differential relay) saturate and that overcurrent bus differential relays must be coordinated with the line relaying.
Engineering Trainings
The instantaneous overcurrent bus differential relays initiate timers and the time overcurrent bus differential relays are coordinated with line relays. (Overcurrent bus differential relays are unacceptable if instantaneous clearing of bus faults is required.) If overcurrent relays with the settings and characteristics shown below are used to protect the 230-21 line, overcurrent bus differential relay settings could be determined as follows:
230-21 Line
TOC (51) Phase: TOC (51G) Ground:
- 5 Relay Amps, 800 Line Amps 1 Relay Amp, 200 Line Amps - #5 time dial, Inverse #6 time dial, Extremely Inverse
Bus Differential
TOC (51) Phase: Extremely Inverse
- Definite TOC Phase, Quick Trip
Browse EE Categories
Select SelectCategory Category
Advertisement
Recommended EE articles
Overvoltages Caused by
Using Protective
Lightning
APRIL 26, 2013
Voltage Systems
DECEMBER 11, 2012
TAGS
bus, ct, differential, overcurrent, protection, relays, settings,
Edvard - Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV high power busbar trunking (<6300A) in power substations, buildings and industry fascilities. Designing of LV/MV switchgears. Professional in AutoCAD programming and webdesign. Developer of awsome electrical design software ePlusMenuCAD . Present on Google+.
Become EEP's Contributor and introduce yourself to 70k+ of our readers all across the web.
2 Comments
[...] the diode recovery time as low as 100ns. Since MOSFETs cannot be protected by fuses, an electronic protection technique has to be used.With the advancement in MOS technology, ruggedized MOSFETs are replacing [...]
(reply)
[...] to fundamental frequency to reject harmonics produced by CT saturation.87/GT1Generator-transformer differential protection (87/GT1): the diff. relays for the generator-transformer has to be of sensitive high speed [...]
(reply)
Leave a Comment
Tell us what you're thinking... we care about your opinion! and oh, not to forget - if you want a picture to show with your comment, go get a free Gravatar!
NAME *
EMAIL *
WEBSITE
6 two =
SIGN ME UP FOR THE NEWSLETTER
Submit Comment
Science at Glance
Our mission is to be the leading provider of scientific information in the field of power and engineering in general. We publish, we share and we spread the knowledge. You're welcome to read, write and contribute to EEP in any way!
Energy Efficency
We see the results of power usage all around us. Every day, the generation and usage of energy produces more pollution than any other single industry. It's our time to use energy on smart and more efficent way. EEP is on your side!
Electrical Software
Electrical design without appropriate software and tools is impossible to imagine. This section covers professional engineering software for design, MV and LV network and photometric calculations, voltage drop and short circuit calculations etc.
2013 EEP - Electrical Engineering Portal. All Rights Reserved | Privacy Policy | 33 queries in 0.649 seconds.
Powered by CsanyiGroup