When selecting relays for bus protection , a major concern is the ability of the protective relaying scheme to restrain from tripping for close-in line faults. Tripping for bus faults, the reason for installing bus differential relaying, is less of a concern. During fault testing conditions, line circuit breakers, rather than bus sectionalizing circuit breakers or bus tie circuit breakers, should be closed to test bus integrity. Bus differential, which is the most sensitive and reliable method for protecting a substation bus, is installed at transmission and distribution substations and switchyards. Overcurrent protection may be used for bus protection at lower voltage substations.

Latest Technical Articles


Power Transformer Turns Ratio Test
JANUARY 17, 2014

Automatic transfer switch (ATS) between two lowvoltage utility supplies


JANUARY 15, 2014

Figure 1 - One-line diagram showing Bus, circuit breakers, CTs, and secondary wiring to Bus differential relay.

During the initial development of power systems, substation buses were protected with overcurrent differential relays as illustrated in Figure 1. CTs are connected so that relays respond to the difference between incoming and outgoing current. But, since the possibility of CT saturation cannot be eliminated for close-in line faults, overcurrent differential relays are delayed to coordinate with transmission- or distribution-line protection. For a close-in fault on the 230-21 line, the assumption is that busside CTs (connected to line relays) operate as designed, but that the line-side CTs (connected to the bus differential relay) saturate and that overcurrent bus differential relays must be coordinated with the line relaying.

Calculating the shortcircuit current across the terminals of a synchronous generator


JANUARY 13, 2014

Engineering Trainings

http://electrical-engineering-portal.com/bus-protection-overcurrent-differential[1/19/2014 1:26:46 AM]

Bus protection - Overcurrent differential | EEP

The instantaneous overcurrent bus differential relays initiate timers and the time overcurrent bus differential relays are coordinated with line relays. (Overcurrent bus differential relays are unacceptable if instantaneous clearing of bus faults is required.) If overcurrent relays with the settings and characteristics shown below are used to protect the 230-21 line, overcurrent bus differential relay settings could be determined as follows:

230-21 Line
TOC (51) Phase: TOC (51G) Ground:
- 5 Relay Amps, 800 Line Amps 1 Relay Amp, 200 Line Amps - #5 time dial, Inverse #6 time dial, Extremely Inverse

IOC (50) Phase: IOC (50G) Ground:


- 20 Relay Amps, 4000 Line Amps 15 Relay Amps, 3000 Line Amps

Bus Differential
TOC (51) Phase: Extremely Inverse
- Definite TOC Phase, Quick Trip

Browse EE Categories
Select SelectCategory Category

SOURCE: Unknown, Chapter 16 Bus Protection

Advertisement

Recommended EE articles

Overvoltages Caused by

Flexibility and Reliability of

Using Protective

The Role of Fuse in Low

http://electrical-engineering-portal.com/bus-protection-overcurrent-differential[1/19/2014 1:26:46 AM]

Bus protection - Overcurrent differential | EEP

Lightning
APRIL 26, 2013

Numerical Protection Relay


DECEMBER 27, 2012

Relay For Fighting Against Faults


DECEMBER 17, 2012

Voltage Systems
DECEMBER 11, 2012

TAGS
bus, ct, differential, overcurrent, protection, relays, settings,

FILED UNDER CATEGORY


Protection

Edvard - Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV high power busbar trunking (<6300A) in power substations, buildings and industry fascilities. Designing of LV/MV switchgears. Professional in AutoCAD programming and webdesign. Developer of awsome electrical design software ePlusMenuCAD . Present on Google+.

Become EEP's Contributor and introduce yourself to 70k+ of our readers all across the web.

2 Comments

RSS Feed for Comments

Power Semiconducto Device MOSFET | EEP


OCT 28, 2013

[...] the diode recovery time as low as 100ns. Since MOSFETs cannot be protected by fuses, an electronic protection technique has to be used.With the advancement in MOS technology, ruggedized MOSFETs are replacing [...]
(reply)

Protection Of Generators And Transformers | EEP


JUN 15, 2013

[...] to fundamental frequency to reject harmonics produced by CT saturation.87/GT1Generator-transformer differential protection (87/GT1): the diff. relays for the generator-transformer has to be of sensitive high speed [...]
(reply)

Leave a Comment

RSS Feed for Comments

http://electrical-engineering-portal.com/bus-protection-overcurrent-differential[1/19/2014 1:26:46 AM]

Bus protection - Overcurrent differential | EEP

Tell us what you're thinking... we care about your opinion! and oh, not to forget - if you want a picture to show with your comment, go get a free Gravatar!

NAME *

EMAIL *

WEBSITE

WE BELIEVE YOU'RE AN ENGINEER, BUT NEVERTHELESS ... *

6 two =
SIGN ME UP FOR THE NEWSLETTER

Submit Comment

Science at Glance
Our mission is to be the leading provider of scientific information in the field of power and engineering in general. We publish, we share and we spread the knowledge. You're welcome to read, write and contribute to EEP in any way!

Energy Efficency
We see the results of power usage all around us. Every day, the generation and usage of energy produces more pollution than any other single industry. It's our time to use energy on smart and more efficent way. EEP is on your side!

Electrical Software
Electrical design without appropriate software and tools is impossible to imagine. This section covers professional engineering software for design, MV and LV network and photometric calculations, voltage drop and short circuit calculations etc.

2013 EEP - Electrical Engineering Portal. All Rights Reserved | Privacy Policy | 33 queries in 0.649 seconds.

Powered by CsanyiGroup

http://electrical-engineering-portal.com/bus-protection-overcurrent-differential[1/19/2014 1:26:46 AM]

Das könnte Ihnen auch gefallen