Sie sind auf Seite 1von 38

Bulletin 1494

NEMA Disconnect Switches


2-1
2
Section Overview
Bulletin 1494V
Variable Depth Flange Mounted
Operating Mechanisms
Disconnect Type Page 2-3
Bulletin 1494V
Variable Depth Flange Mounted
Operating Mechanisms
Circuit Breaker Type Page 2-7
Bulletin 1494V
Variable Depth Flange Mounted
Remote or Dual Type
Operating Mechanisms
Disconnect Type Page 2-9
Circuit Breaker Type Page 2-9
Bulletin 1494F
Fixed-Depth Flange Mounted
Operating Mechanisms
Disconnect Type Page 2-11
Bulletin 1494F
Fixed-Depth Flange Mounted
Operating Mechanisms
Enclosed Disconnect Type Page 2-13
Continued on next page.
Bulletin 1494
NEMA Disconnect Switches
2-2
Section Overview, Continued
Bulletin 1494D
Fixed-Depth Flange Mounted
Operating Mechanisms
Circuit Breaker Type Page 2-15
Bulletin 1494M
Fixed-Depth Remote Operated
Flange Mounted Operating
Mechanisms
Disconnect Type Page 2-17
Bulletin 1494R
Variable-Depth Door Mounted
Operating Mechanisms
Disconnect Type Page 2-19
Bulletin 1491
Fuse Blocks
Available from 30A600A Page 2-30
Bulletin 1494V
Variable Depth Flange Mounted Operating Mechanisms
2-3
2
Disconnect Type
Bulletin 1494V
Adaptable to IP65
(Type 1, 3, 3R, 12) or
IP66 (Type 4, 4X)
Disconnect Switches
Available from
30A600A
Highly Visible ON and
OFF Indicator with a
Color Coded Handle
Can Be Used with Class
H, J and R Fuses
Optional Auxiliary
Contacts
TABLE OF CONTENTS
Description Page Description Page
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-27
Description
Bulletin 1494V variable depth ange mounted disconnect switches meet industrial
requirements for dependable manually operated disconnecting means. Operating
handles and disconnecting means are adaptable to IP65 (Type 1, 3, 3R, 12) or IP66
(Type 4, 4X) enclosures with ange-mount construction.
Conformity to Standards: Approvals:
Your order must include:
Cat. No. of the disconnect switch
(fusible or non-fusible).
Cat. No. of the operating handle.
Cat. No. of the connecting rod.
Cat. No. of the trailer fuse block kit.
Cat. No. of the fuse clip kit.
A complete installation consists of a
disconnect switch, an operating
handle, connecting rod, trailer fuse
block kit and fuse clip kit (for
installations that require fusing).
If required, Cat. No. of any
accessories.
IEC 947-3 CE Marked Per Low Voltage Directive
73/23/EEC, 93/68/EEC
CSA C22.2 No. 4
UL 98 CSA Certied (File No. LR 1234)
UL Listed (File No. E 47426)
To obtain a complete Disconnect Switch,
order the following components:
Operating Handle
Connecting Rod
+
Fuse Clip Kit
Disconnect Switch
(Auxiliary Contacts Shown
Are Optional)
Trailer Fuse Block Kit
OR + +
AND
Bulletin 1494V
Variable Depth Flange Mounted Operating Mechanisms
2-4
Product Selection
Fusible Disconnect Switch Kits
Includes switch, connecting rod, handle, trailer fuse block and fuse clips
Non-Fusible Disconnect Switch Kits
Includes switch, connecting rod, handle (line and load lug connectors located in Accessories section)
0 Ratings based on utilizing 2 poles in series to break one line of the DC supply voltage and the remaining pole breaking the second DC supply line.
O Long Connecting Rods Disconnect switch kits are also available with a long connecting rod. To order, add the letter L after the letter H,
N or R in the Cat. No.
O 50 HP at 200V AC; 60HP at 208V AC.
Complete Disconnect Switch Kits for IP65 (Type 1, 3, 3R and 12) Enclosures
Size
(A)
IEC Applications
Maximum kW
(AC23)
UL and CSA
Applications
Maximum HP
AC 1 DC 0
Fuse
Size
Fuse
Volt.
Fuse
Clips Cat. No. O
3, 50 Hz 3, 60 Hz
220
240V
380
440V
500
600V
115V
200
208V
230V 460V 575V 115V 230V 125V 250V
30 5.5 11 15 3 7.5 7.5 15 20 2 3 3 5 130A
250 H 1494V-DH233
250 R 1494V-DR233
600 H, J 1494V-DH633
600 R 1494V-DR633
60 11 22 37 7.5 15 15 30 50 3 10 5 10 3160A
250 H 1494V-DH266
250 R 1494V-DR266
600 H, J 1494V-DH666
600 R 1494V-DR666
100 22 45 55 25 30 60 75 20 61100A
250 H 1494V-DH611
250 R 1494V-DR611
600 H, J 1494V-DH611
600 R 1494V-DR611
200 48 90 110 O 60 125 150 40 101200A
250 H 1494V-DH622
250 R 1494V-DR622
600 H, J 1494V-DH622
600 R 1494V-DR622
400 90 185 257 75 125 250 350 50 201400A
250 H 1494V-DH644
250 R 1494V-DR644
600 H, J 1494V-DH644
600 R 1494V-DR644
600 150 295 375 150 200 400 500 50 401600A
250 H 1494V-DH606
250 R 1494V-DR606
600 H 1494V-DH606
600 R 1494V-DR606
600 J 1494V-DJ606
Complete Disconnect Switch Kits for IP65 (Type 1, 3, 3R and 12) Enclosures
Size
(A)
IEC Applications
Maximum kW (AC23)
UL and CSA Applications
Maximum HP
AC1 DC 0
Cat. No. O
3, 50 Hz 3, 60 Hz
220
240V
380
440V
500
600V
200
208V
230V 460V 575V 115V 230V 125V 250V
30 5.5 11 15 7.5 7.5 15 20 2 3 3 5 1494V-DN30
60 11 22 37 15 15 30 40 3 10 5 10 1494V-DN60
100 22 45 55 25 30 60 75 20 1494V-DN100
200 45 90 110 O 60 125 150 40 1494V-DN200
400 90 185 255 75 125 250 350 50 1494V-DN400
600 150 295 375 150 200 400 500 50 1494V-DN600
Accessories Page 2-21
Specifications Page 2-25
Approximate Dimensions Page 2-27
Prices Consult Sales Office or price list
Bulletin 1494V
Variable Depth Flange Mounted Operating Mechanisms
2-5
Product Selection, Continued
Disconnect Switches
Connecting Rods
Approximate dimensions are in millimeters (inches). Approximate dimensions are not intended for manufacturing purposes.
Operating Handles
0 Also rated operational current for utilization categories AC-20 and AC-21 (IEC 408). For 1 ratings or other AC or DC utilization categories,
consult Allen-Bradley Sales Office.
O Ratings based on utilizing 2 poles in series to break one line of the DC supply voltage and the remaining pole breaking the second DC supply line.
O Devices are field convertible from right hand to left hand flange operation.
O Connecting Rods and Operating Handles must be ordered separately.
O 50 HP at 200V AC; 60 HP at 208V AC.
O Enclosure depth is measured from the top of the flange to the disconnect means mounting surface (mm).
6 Two per installation required.
Maximum Operational Voltage U
e
660V
Size 0
(A)
IEC Utilization
Category AC-23
Maximum Rating kW
NEMA, UL, CSA
Maximum Rating HP
AC 1 DC O
Cat. No. OO
Switch Only
3, 50 Hz 3, 60 Hz
220
240V
380
440V
500
600V
200
208V 230V 460V 575V 115 230 125 250
30 5.5 11 15 7.5 7.5 15 20 2 3 3 5 1494V-DS30
60 11 22 37 15 15 30 50 3 10 5 10 1494V-DS60
100 22 45 55 25 30 60 75 20 1494V-DS100
200 45 90 110 O 60 125 150 40 1494V-DS200
400 90 185 257 75 125 250 350 50 1494V-DS400
600 150 295 375 150 200 400 500 50 1494V-DS600
Disconnect Switch
Size (A)
Enclosure Depth O
Cat. No. Minimum Maximum
30, 60, 100, 200
172 (6-3/4) 232 (9-1/8) 1494V-RA1
232 (9-1/8) 585 (23) 1494V-RA2
400, 600
229 (9) 235 (9-1/4) 1494V-RB1 6
229 (9) 585 (23) 1494V-RB2 6
Enclosure Type Description Mounting
Disconnect
Switch Cat. No.
IP65
(Type 1, 3, 3R, 12)
Painted
Metal
Right or
left ange
30, 60, 100 & 200A 1494V-H1
400A, 600A 1494V-H2
IP66
(Type 4, 4X)
Stainless
Steel
Right or
left ange
30, 60, 100 & 200A 1494V-W1
400A, 600A 1494V-W2
IP66
(Type 4, 4X)
Non-Metallic Right ange only
30, 60, 100 & 200A 1494V-R1
400A, 600A 1494V-R2
Accessories Page 2-21
Specifications Page 2-25
Approximate Dimensions Page 2-27
Prices Consult Sales Office or price list
Bulletin 1494V
Variable Depth Flange Mounted Operating Mechanisms
2-6
Product Selection, Continued
Fuse Clip Kits
Includes six clips and mounting hardware
Trailer Fuse Block Kits
For Class H and J fuses, select the proper fuse clip kit from the table above. For UL Class R fuse applications, non-removable
rejection type clips are mounted on the trailer fuse block at the factory. Three additional clips are included for mounting on the
disconnect switch.
0 Not required when installing 201 through 400A fuses on the 200A disconnect switch, Cat. No. 1494V-DS200.
O Down Fusing For all Class H and J applications, order the Trailer Fuse Block kit for the size disconnect being used and order the lower
ampacity Fuse Clip Kit. Note: The 100A disconnect size requires that an Adapter Kit, Cat. No. 1401-N170 also be ordered. For Class R
applications, refer to the trailer fuse block kit table above for listed devices.
O For use with Class J fuses only.
O Single Pole Fuse Block 3 required per installation.
Fuse Class
Fuse Clip Rating (A)
Cat. No. 250V 600V
H 30 1401-N41
H, J 60 30 1401-N42
H, J 60 1401-N43
H, J 100 100 1401-N44
H, J 200 200 1401-N45
H, J 400 400 1401-N46 0
Disconnect
Size (A)
UL Class C, H and J O UL Class R
Fuse
Size (A) Cat. No.
Fuse Size (A)
Cat. No. 250V 600V
30
030 1494V-FS30 30 1494V-FSR233
3160 1494V-FS63 30 1494V-FSR633
60
30 1494V-FSR636
3160 1494V-FS60 60 1494V-FSR266
61100 1494V-FS16 60 1494V-FSR666
100
60 1494V-FSR661
61100 1494V-FS100 100 100 1494V-FSR611
101200 1494V-FS21 O
200
100 1494V-FSR612
101200 1494V-FS200 200 200 1494V-FSR622
201400 1494V-FS42 O
400
200 1494V-FSR624
201400 1494V-FS400 400 400 1494V-FSR644
600
Class H Class J
401600 1491-N621 O
401600 1494V-FS600 600 600 1491-R621 O
Accessories Page 2-21
Specifications Page 2-25
Approximate Dimensions Page 2-27
Prices Consult Sales Office or price list
Bulletin 1494V
Variable Depth Flange Mounted Operating Mechanisms
2-7
2
Circuit Breaker Type
Bulletin 1494V
Adaptable to
IP65 (Type 1, 3, 3R, 12)
or IP66 (Type 4, 4X)
Enclosures
Circuit Breaker
Operating Mechanisms
Available 150A400A
Frame Breakers
Highly Visible ON and
OFF Indicator with a
Color Coded Handle
Optional Auxiliary
Contacts
TABLE OF CONTENTS
Description Page Description Page
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-26
Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-27
Description
Bulletin 1494V variable depth ange mounted disconnect switches meet industrial
requirements for dependable manually operated disconnecting means. Operating
handles and disconnecting means are adaptable to IP65 (Type 1, 3, 3R, 12) or IP66
(Type 4, 4X) enclosures with ange-mount construction.
Conformity to Standards: Approvals:
Your order must include:
Cat. No. of the circuit breaker.
Cat. No. of the operating handle.
Cat. No. of the connecting rod.
A complete installation consists of a
circuit breaker, an operating handle,
and connecting rod.
If required, Cat. No. of any
accessories.
IEC 947-3 CSA Certied (File No. LR 1234)
CSA C22.2 No. 4 UL Listed (File No. E 47426)
UL 98
To obtain a complete Operating Mechanism,
order the following components:
Circuit Breaker Operating Mechanism
(Circuit Breaker is Shown But Not Supplied
With Operating Mechanisms)
Operating Handle
Connecting Rod
+ + OR
Bulletin 1494V
Variable Depth Flange Mounted Operating Mechanisms
2-8
Product Selection
Circuit Breaker Type, Continued
Circuit Breaker Operating Mechanism The mechanism listed must be combined with a connecting rod, operating handle and
circuit breaker to obtain a functional device.
Connecting Rods
Approximate dimensions are in millimeters (inches). Approximate dimensions are not intended for manufacturing purposes.
Operating Handle
0 Circuit breakers to be provided by user.
3-Pole Circuit Breaker 0 Operating Mechanism
Manufacturer Size (A) Frame Designation
Right Hand
Cat. No.
Left Hand
Cat. No.
Cutler-Hammer/
Westinghouse
150
EHD, FD, FDB, FDC,
HFD, HMCP
1494V-M40 1494V-M40
Cutler-Hammer/
Westinghouse
250
JD, JDB, JDC,
HJD, HMCP
1494V-M50 1494V-M50
400
KD, KDB, KDC,
HKD, HMCP
1494V-M60 1494V-M60
Circuit Breaker
Frame Size (A)
Enclosure Depth
Cat. No. Minimum Maximum
150, 250 and 400
172 (6-3/4) 232 (9-1/8) 1494V-RA1
232 (9-1/8) 585 (23) 1494V-RA2
Enclosure Type Mounting
Circuit Breaker
Frame Size (A)
Operating Handle
Cat. No.
IP65 (Type 1, 3R, 3 and 12)
Right or
Left Flange
150, 250 & 400 1494V-H11
IP66 (Type 4, 4X Metallic)
Right or
Left Flange
150, 250 & 400 1494V-W11
Accessories Page 2-21
Specifications Page 2-26
Approximate Dimensions Page 2-27
Prices Consult Sales Office or price list
Bulletin 1494V
Variable Depth Flange Mounted Operating Mechanisms
2-9
2
Remote or Dual Type
Bulletin 1494V
Adaptable to IP65
(Type 1, 3, 3R, 12) or
IP66 (Type 4, 4X)
Enclosures
Disconnect Switches
Available from
30A600A
Highly Visible ON and
OFF Indicator with
Color Coded Handle
For Use with Disconnect
Switches or Circuit
Breaker
TABLE OF CONTENTS
Description Page Description Page
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-27
Description
Remote Handling Mechanisms Allow the operating handle to be mounted either
above or below the disconnect means.
Dual Operating Mechanisms Permit the control of two disconnect means utilizing
a common operating handle.
Operation Both the Remote and Dual Operating Mechanisms consist of two
components a main drive mechanism (which includes the operating handle) and
a remote drive mechanism. To obtain a functional device, these components must
be properly combined with a connecting link (supplied by customer), disconnect
means and connecting rod.
Conformity to Standards: Approvals:
Your order must include:
Cat. No. of the remote driver or main
drive dual operating mechanism.
If required, Cat. No. of any
accessories.
IEC 947-3 CSA Certied (File No. LR 1234)
CSA C22.2 No. 4 UL Listed (File No. E 47426)
UL 98
Main Drive Dual
Operating Mechanism
(Includes Operating Handle)
Remote Drive
Operating Mechanism
Bulletin 1494V
Variable Depth Flange Mounted Operating Mechanisms
2-10
Product Selection
Remote or Dual Type, Continued
Remote or Dual Operated Mechanisms Separate Components
0 Includes Main and Remote Drive Mechanisms. Does not include rectangular bar stock (1/4-inch) 6.35mm x (5/8-inch) 15.8mm connecting bar
between disconnecting means and connecting rod, to be supplied by user.
Type of
Mechanism
Enclosure
Type
Size
Mounting Cat. No. 0 Disconnect Switch
Circuit
Breaker
Remote
IP65
(Type 1, 3, 3R
and 12)
30A, 60A, 100A &
200A

Right 1494V-H5
Left 1494V-HL5
400A, 600A
Right 1494V-H8
Left 1494V-HL8

Cutler-Hammer/
Westinghouse
150A, 250A & 400A
EHD, FD, FDB, FDC,
HFD, HMCP, JD, JDB,
JDC, HJD, KD, KDB,
KDC, HKD
Right 1494V-H10
Left 1494V-HL10
IP66
(Type 4)
30A, 60A, 100A &
200A

Right 1494V-W5
Left 1494V-WL5
400A, 600A
Right 1494V-W8
Left 1494V-WL8

Cutler-Hammer/
Westinghouse
150A, 250A & 400A
EHD, FD, FDB, FDC,
HFD, HMCP, JD, JDB,
JDC, HJD, KD, KDB,
KDC, HKD
Right 1494V-W10
Left 1494V-WL10
Dual
IP65
(Type 1, 3, 3R
and 12)
Two 30A, Two 60A,
Two 100A or any
Combination of Two
30A through 100A
Switches

Right 1494V-H50
Left 1494V-HL50

Cutler-Hammer/
Westinghouse
Two 150A
EHD, FD, FDB, FDC,
HFD, HMCP
Right 1494V-H95
Left 1494V-HL95
IP66
(Type 4)
Two 30A, Two 60A,
Two 100A or any
Combination of Two
30A through 100A
Switches

Right 1494V-W50
Left 1494V-WL50

Cutler-Hammer/
Westinghouse
Two 150A
EHD, FD, FDB, FDC,
HFD, HMCP
Right 1494V-W95
Left 1494V-WL95
Accessories Page 2-21
Specifications Page 2-25
Approximate Dimensions Page 2-27
Prices Consult Sales Office or price list
Bulletin 1494F
Fixed-Depth Flange Mounted Operating Mechanisms
2-11
2
Disconnect Type
Bulletin 1494F
Adaptable to All
IP42 (Type 1) and IP65
(Type 12) Enclosures
with Right or Left Hand
Flange Construction
Disconnect Switch
Available from
30A200A
Highly Visible ON and
OFF Indicator
Can Be Used with Class
H, J and R Fuses
Optional Auxiliary
Contacts
TABLE OF CONTENTS
Description Page Description Page
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Disconnect Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Enclosed Disconnect Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-28
Description
Bulletin 1494F Fixed-Depth Flange Mounted Disconnect Switches meet industrial
requirements for a dependable manually operated disconnecting means. The Fusible
Disconnect Switch Assembly is made up of two components a Disconnect Switch
and Operating Mechanism and a Fuse Block Adapter Kit, with fuse clips.
Conformity to Standards: Approvals:
Your order must include:
Cat. No. of the disconnect switch
fusible or non-fusible.
Cat. No. of the Fuse Block Adapter
Plate Kit with fuse clips.
To obtain a complete fusible
disconnect switch the above items
must be on your order.
Accessories, if necessary.
IEC 947-3 CE Marked Per Low Voltage Directive
73/23/EEC, 93/68/EEC
CSA C22.2 No. 4
UL 98 CSA Certied (File No. LR 1234)
UL Listed (File No. E 47426)
To obtain a complete Fusible Disconnect Switch,
order the following components:
Cat. No. 1494F-NF30
Disconnect Switch and
Operating Mechanism
Cat. No. 1494F-J633
Fuse Block Adapter Plate Kit
With Fuse Clips
+
Bulletin 1494F
Fixed-Depth Flange Mounted Operating Mechanisms
2-12
Product Selection
Fusible Disconnect Switch Kits
Includes switch, operating mechanism and handle (line and load lug connectors located in the Accessories section on
page 2-22). To obtain a complete fusible disconnect switch, select the proper Fuse Block Adapter Plate Kit with fuse clips from
the table below.
Non-Fusible Disconnect Switch Kits
Includes switch, operating mechanism, and handle (line and load lug connectors located in the Accessories section on page 2-21).
Fuse Block Adapter Plate Kits with Fuse Clips
0 Does not include rectangular bar stock 6.35mm (1/4 in.) x 15.8mm (5/8 in.) connecting bar between switch and remote operating mechanism
and handle to be provided by user.
O Ratings based on utilizing 2 poles in series to break one line of the DC supply voltage and the remaining pole breaking the second DC supply line.
Disconnect Switches for IP42 (Type 1) and IP65 (Type 12) Enclosures 0
Size
(A)
IEC Applications
Maximum kW (AC23)
UL and CSA Applications
Maximum HP
AC 1 DC O
Open Type
Without Enclosure
Flange Construction
3, 50 Hz 3, 60 Hz Right Hand Left Hand

220
240V
380
440V
500
600V
200
208V 230V 460V 575V 115V 230V 125V 250V Cat. No. Cat. No.
30 5.5 11 15 7.5 7.5 15 20 2 3 3 5 1494F-NF30 1494F-NFL30
60 11 22 30 15 15 30 40 3 10 5 10 1494F-NF60 1494F-NFL60
100 22 45 55 30 30 60 75 10 20 1494F-NF100 1494F-NFL100
200 45 75 75 60 60 100 100 20 40 1494F-NF200 1494F-NFL200
Disconnect Switches for IP42 (Type 1) and IP65 (Type 12) Enclosures 0
Size
(A)
IEC Applications
Maximum kW (AC23)
UL and CSA Applications
Maximum HP
AC 1 DC O
Open Type
Without Enclosure
3 50 Hz 3, 60 Hz
Flange Construction
Right Hand Left Hand

220
240V
380
440V
500
600V
200
208V 230V 460V 575V 115V 230V 125V 250V Cat. No. Cat. No.
30 5.5 11 15 7.5 7.5 15 20 2 3 3 5 1494F-N30 1494F-NL30
60 11 22 37 15 15 30 40 3 10 5 10 1494F-N60 1494F-NL60
100 22 45 55 30 30 60 75 10 20 1494F-N100 1494F-NL100
200 48 90 110 60 60 100 100 20 40 1494F-N200 1494F-NL200
Disconnect
Size (A)
Fuse
Clips
UL Class R Dimension UL Class J Dimension Class H and C
250V 600V 600V 600V
Cat. No. Cat. No. Cat. No. Cat. No.
30
30
60
1494F-R233
1494F-R263
1494F-R633
1494F-R663
1494F-J633
1494F-J663
1494F-C633
1494F-C663
60
30
60
100

1494F-R266
1494F-R216
1494F-R636
1494F-R666
1494F-R616

1494F-J666
1494F-J616
1494F-C636
1494F-C666
1494F-C616
100
100
200
1494F-R211
1494F-R221
1494F-R611
1494F-R621
1494F-J611
1494F-J621
1494F-C611
1494F-C621
200
200
400
1494F-R222
1494F-R242
1494F-R622
1494F-R642
1494F-J622
1494F-J642
1494F-C622
1494F-C642
Accessories Page 2-21
Specifications Page 2-25
Approximate Dimensions Page 2-28
Prices Consult Sales Office or price list
Bulletin 1494F
Flange Mounted Operating Mechanisms
2-13
22
Disconnect Type
Bulletin 1494F
Non-Fusible Disconnect
Switch Available in Sizes:
30, 60, 100, 200 and 400A
Enclosure Rating Type
3/3R/4/12 Painted Steel
Rugged Quick-Make,
Quick-Break Snap Action
Switch with Visible
Blade Construction
Durable Flange Mounted,
Non-Metallic, Color Coded
Handle for Easy ON or
OFF Identification
Optional Push Buttons
and Pilot Lights
Disconnect Switch
Padlocking Capability to
Meet OSHA
External Mounting Feet
Enclosure Padlocking
Capability
Line Side, Load Side and
Ground Terminal Lugs
Provided
TABLE OF CONTENTS
Description Page Description Page
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Modications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-24
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29
Description
Bulletin 1494F line of NEMA enclosed disconnect switches are compact in size, but
ruggedly designed for long lasting performance. These switches are ideal for use as:
At Motor disconnect
Main safety switch
Your order must include:
Cat. No. of the disconnect switch
(fusible or non-fusible).
Cat. No. of the Fuse Block Adapter
Plate Kit with fuse clips.
To obtain a complete fusible
disconnect switch the above items
must be on your order.
Accessories, if necessary.
Conformity to Standards: Approvals:
UL 98 UL Listed (File No. E 14841)
CSA C22.2 No. 4
IEC 947-3
Bulletin 1494F
Flange Mounted Operating Mechanisms
2-14
Product Selection Modifications
Non-Fusible Disconnect Switch
Size
(A)
Maximum HP
Dim Ref.
IP65 (Type 3, 3R, 4, 12)
Painted Steel
IP66 (Type 4, 4X)
Stainless Steel
3, 60 Hz 1 60 Hz
Cat. No. Cat. No. 200 208V 230V 460V 575V 115V 230V
30 7.5 7.5 15 20 2 3 A11 1494F-FNP30 1494F-CNP30
60 15 15 30 40 3 10 A12 1494F-FNP60 1494F-CNP60
100 25 30 50 50 A12 1494F-FNP100 1494F-CNP100
200 50 60 125 150 A13 1494F-FNP200 1494F-CNP200
400 100 125 250 350 A14 1494F-FNP400 1494F-CNP400
Accessories Page 2-21
Modifications Page 2-24
Specifications Page 2-25
Approximate Dimensions Page 2-29
Prices Consult Sales Office or price list
Bulletin 1494D
Fixed-Depth Flange Mounted Operating Mechanisms
2-15
2
Circuit Breaker Type
Bulletin 1494D
Adaptable to Both
IP42 (Type 1) and IP65
(Type 12) Enclosures
with Right Hand Flange
Construction
Circuit Breaker
Operating Mechanisms
Available From
150A1200A Frame
Sizes
Highly Visible ON and
OFF Indicator
Optional Auxiliary
Contacts
TABLE OF CONTENTS
Description Page Description Page
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-26
Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-28
Description
Bulletin 1494D Fixed Depth Circuit Breaker Operating Mechanisms are designed to
operate commonly used molded case circuit breakers (which are to be supplied by
the user).
Conformity to Standards: Approvals:
Your order must include:
Cat. No. of the operating mechanism.
Cat. No. of the slide or bail mechanism.
Cat. No. of any accessories, if
required.
An operating mechanism and a slide or
bail mechanism must be combined
with the proper circuit breaker in order
to obtain a functional device.
IEC 947-3 CSA Certied (File No. LR 1234)
CSA C22.2 No. 4 UL Listed (File No. E 47426)
UL 98
Cat. No. 1494D-N4 and Cat. No. 1494D-N40
(Circuit Breaker Not Included. Auxiliary Contact and
Adapter Kit Must Be Ordered Separately)
To obtain a complete operating mechanism, order an
Operating Mechanism and Slide or Bail Mechanism.
Bulletin 1494D
Fixed-Depth Flange Mounted Operating Mechanisms
2-16
Product Selection
Circuit Breaker Type
Operator Mechanism and Slide/Bail Mechanisms Complete Operating Mechanism
0 Circuit breakers to be provided by user.
3 Pole Circuit Breaker 0 Operator Slide or Bail
Manufacturer
Frame
Size (A) Frame Designation Cat. No. Cat. No.
Cutler-Hammer/
Westinghouse
150 EHD, FD, FDB, FDC, HFD, HMCP 1494D-N4 1494D-N40
Cutler-Hammer/
Westinghouse
250 JD, JDB, JDC, HJD, HMCP
1494D-N5
1494D-N50
400 KD, KDB, KDC, HKD, HMCP 1494D-N60
600 LA, HLA, LC, HLC, LD, HLD
1494D-N3
1494D-N31
800 MA, HMA, MC, ND, HND, NDC 1494D-N41
800 NB Tri-Pac 1494D-N41T
1200 NB, HNB, NC, HNC, ND, HND, NDC 1494D-N43
Accessories Page 2-21
Specification Page 2-26
Approximate Dimensions Page 2-28
Prices Consult Sales Office or price list
Bulletin 1494M
Fixed-Depth Remote Operated Flange Mounted Operating Mechanisms
2-17
2
Disconnect Type
Bulletin 1494M
Adaptable to Both
IP42 (Type 1) and IP65
(Type 12) Enclosures
with Right or Left Hand
Flange Construction
Disconnect Switches
Available up to 200A
Highly Visible ON and
OFF Indicator
TABLE OF CONTENTS
Description Page Description Page
Product Specication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-28
Description
The disconnect switch is made up to two units the basic switch and the operating
mechanism. These two units must be properly combined with a connecting bar to
obtain a functional device. This method allows the user to determine specic
distances required between the disconnect switch and the operating mechanism.
This feature is often required when the enclosure is to be mounted high off the oor
making a conventional device difcult for personnel to operate. Note: The operating
mechanism can only be mounted below the switch.
Conformity to Standards:
Your order must include:
Cat. No. of the disconnect switch
(fusible or non-fusible).
Accessories, if necessary.
IEC 947-3
CSA C22.2 No. 4
UL 98
Right Hand Flange
Mounted, Remote
Operated, Non-Fusible Disconnect
Switch and Operating
Mechanism
Bulletin 1494M
Fixed-Depth Remote Operated Flange Mounted Operating Mechanisms
2-18
Product Selection
Fusible Disconnect Kits
Includes switch, fuse block adapter plate, fuse clips, operating mechanism and handle (line and load lug connectors located in
the Accessories section on page 2-22).
Non-Fusible Disconnect Kits
Includes switch, operating mechanism and handle (line and load lug connectors located in the Accessories section on page 2-22).
Fuse Block Adapter Plate Kits with Fuse Clips
0 Does not include rectangular bar stock 6.35mm (1/4 in.) x 15.8mm (5/8 in.) connecting bar between switch and remote operating mechanism
and handle to be provided by user.
O Ratings based on utilizing 2 poles in series to break one line of the DC supply voltage and the remaining pole breaking the second DC supply line.
Complete Disconnect Switch Kit for IP42 (Type 1) and IP65 (Type 12) 0
Size
(A)
IEC Applications
Maximum kW (AC23)
UL and CSA Applications
Maximum HP
AC 1 DC O
Open Type
Without Enclosure
3, 50 Hz 3, 60 Hz
Flange Construction
Right Hand Left Hand

220
240V
380
440V
500
600V
200
208V 230V 460V 575V 115V 230V 125V 250V Cat. No. Cat. No.
30 5.5 11 15 7.5 7.5 15 20 2 3 3 5 1494M-NF30 1494M-NFL30
60 11 22 30 15 15 30 40 3 10 5 10 1494M-NF60 1494M-NFL60
100 22 45 55 30 30 60 75 10 20 1494M-NF100 1494M-NFL100
200 45 75 75 60 60 100 100 20 40 1494M-NF200 1494M-NFL200
Complete Disconnect Switch Kit for IP42 (Type 1) and IP65 (Type 12) 0
Size
(A)
IEC Applications
Maximum kW (AC23)
UL and CSA Applications
Maximum HP
AC 1 DC O
Open Type
Without Enclosure
3, 50 Hz 3, 60 Hz
Flange Construction
Right Hand Left Hand

220
240V
380
440V
500
600V
200
208V 230V 460V 575V 115V 230V 125V 250V Cat. No. Cat. No.
30 5.5 11 15 7.5 7.5 15 20 2 3 3 5 1494M-N30 1494M-NL30
60 11 22 37 15 15 30 50 3 10 5 10 1494M-N60 1494M-NL60
100 22 45 55 30 30 60 75 10 20 1494M-N100 1494M-NL100
200 48 90 110 60 60 100 100 20 40 1494M-N200 1494M-NL200
Disconnect
Size (A)
Fuse
Clips
UL Class R Dimension UL Class J Dimension Class H and C
250V 600V 600V 600V
Cat. No. Cat. No. Cat. No. Cat. No.
30
30
60
1494F-R233
1494F-R263
1494F-R633
1494F-R663
1494F-J633
1494F-J663
1494F-C633
1494F-C663
60
30
60
100

1494F-R266
1494F-R216
1494F-R636
1494F-R666
1494F-R616

1494F-J666
1494F-J616
1494F-C636
1494F-C666
1494F-C616
100
100
200
1494F-R211
1494F-R221
1494F-R611
1494F-R621
1494F-J611
1494F-J621
1494F-C611
1494F-C621
200
200
400
1494F-R222
1494F-R242
1494F-R622
1494F-R642
1494F-J622
1494F-J642
1494F-C622
1494F-C642
Accessories Page 2-21
Specifications Page 2-25
Approximate Dimensions Page 2-28
Prices Consult Sales Office or price list
Bulletin 1494R
Variable Depth Door Mounted Operating Mechanisms
2-19
2
Disconnect Type
Bulletin 1494R
Adaptable to Both
IP42 (Type 1) and IP65
(Type 12) Enclosures
Disconnect Switches
Available from
30A200A
Highly Visible ON,
OFF and Open
Indicator
Can Be Used with Class
H (Bulletin 1491 Fuse
Block Kits), J and R
Fuses
TABLE OF CONTENTS
Description Page Description Page
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-20
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
Description
Bulletin 1494R rod operated disconnect switch is applicable to both IP42 (Type 1)
and manual type disconnect device. The complete Disconnect Switch consists of the
disconnect switch, operating handle, connecting rod and hitch pin.
Conformity to Standards: Approvals:
Your order must include:
Cat. No. of the disconnect switch.
If necessary, Cat. No. of any
accessories.
IEC 947-3 CSA Certified (File No. LR 1234)
CSA C22.2 No. 4 UL Listed (File No. E 47418)
UL 98
Disconnect Switch
(Auxiliary Contact Shown is Optional)
Operating
Handle
Connecting
Rod and
Hitch Pin
+ +
To obtain a complete Disconnect Switch Kit, order the following:
Cat. No. 1494R-N30
Bulletin 1494R
Variable Depth Door Mounted Operating Mechanisms
2-20
Product Selection
Disconnect Switch Kits
Includes switch, operating handle, connecting rod and hitch pin (line and load lug connectors located in the Accessories section
on page 2-22).
Longer Shafts Approximate dimensions are in mm (inches)
The standard lengths for shafts furnished with the disconnect switches are 241.3 (9-1/2) on the 30A and 60A and 279.4 (11) on the
100A and 200A. Longer shafts are available and must be ordered separately. Approximate dimensions are not intended for
manufacturing purposes.
0 Ratings based on utilizing 2 poles in series to break one line of the DC supply voltage and the remaining pole breaking the second DC supply line.
O To obtain a fusible disconnect switch, add Bulletin 1491 fuse blocks. See page 2-30.
Complete Non-Fused Disconnect Switch Kits for IP42 (Type 1) and IP65 (Type 12) Enclosures
Size
(A)
IEC Applications
Maximum kW (AC23)
UL and CSA Applications
Maximum HP
AC 1 DC 0
Open Type
Without Enclosure 3, 50 Hz 3, 60 Hz
220 240V 280 440V 500 600V 200 208V 230V 460V 575V 115V 230V 150V Cat. No. O
30 5.8 11 15 7.5 7.5 15 20 2 3 3 1494R-N30
60 11 22 37 15 15 30 40 3 10 5 1494R-N60
100 22 45 55 30 30 60 75 10 1494R-N100
200 45 90 110 60 60 125 150 1494R-N200
Shaft Kits
Disconnect Switch
Size (A) Length Cat. No.
30 457.2 (18) 1494R-N4
60 457.2 (18) 1494R-N4
100 609.6 (24) 1494R-N5
200 609.6 (24) 1494R-N6
Accessories Page 2-21
Specifications Page 2-25
Prices Consult Sales Office or price list
Bulletin 1494
Accessories Field Installed
2-21
2
Accessories
0 Requires an adapter kit on new installations.
O One auxiliary contact adapter kit enables up to two auxiliary contacts to be installed.
O Required on new installations only.
Description
For use with
Cat. No. Cat. No.
Auxiliary Contacts
1 N.O. Contact
1494F, 1494M
Disconnect Switch
1495-N8
Auxiliary Contacts
1 N.C. Contact
1494D, 1494V 0
Circuit Breaker
1495-N9
Auxiliary Contact Adapter Kit
150A Frame Cutler-Hammer/Westinghouse
1494D, 1494V
Circuit Breaker
1495-N21 O
Auxiliary Contact Adapter Kit
250A Frame Cutler-Hammer/Westinghouse
1494D, 1494V
Circuit Breaker
1495-N22 O
Auxiliary Contact Adapter Kit
400A Frame Cutler-Hammer/Westinghouse
1494D, 1494V
Circuit Breaker
1495-N16 O
Auxiliary Contact Adapter Kit
600A, 800A, 1200A Frame Cutler-Hammer/Westinghouse
1494D, 1494V
Circuit Breaker
1495-N13 O
Auxiliary Contact Adapter Kit
250A and 400A Frame Cutler-Hammer/Westinghouse
1494V
Circuit Breaker
1495-N23
Auxiliary Contacts
1 N.O. Contact
1494V
Disconnect Switch
595-A
Auxiliary Contacts
1 N.C. Contact
1494V
Disconnect Switch
595-B
Auxiliary Contact Adapter Kit
400A and 600A Disconnect
1494V
Disconnect Switch
595-N1
Auxiliary Contacts
1 N.O. Contact
1494R
Disconnect
Switch
30, 60A
895-A1
Auxiliary Contacts
1 N.C. Contact
895-B1
Auxiliary Contacts
1 N.O. and 1 N.C. Contact
895-C1
Auxiliary Contact Adapter Kit
for 1 contact
895-M11
Auxiliary Contact Adapter Kit
for 2 contacts
895-M12
Auxiliary Contacts
1 N.O. Contact
1494R
Disconnect
Switch
100, 200A
895-A2
Auxiliary Contacts
1 N.C. Contact
895-B2
Auxiliary Contacts
1 N.O. and 1 N.C. Contact
895-C2
Auxiliary Contact Adapter Kit
for 1 contact
895-M21
Auxiliary Contact Adapter Kit
for 2 contacts
895-M22
Auxiliary Contact
1 N.O. Contact
1494F
Enclosed
Disconnects
Only
1495-N30
Auxiliary Contact
1 N.C. Contact
1495-N31
Auxiliary Contact Adapter Kit O
(for a maximum of 2 contacts)
1495-N32
Auxiliary Contact
1 N.O. Contact and 1 N.C. Contact early break
1495-N33
Cat. No.
1495-N21
Cat. No.
1495-N23
Cat. No. 595-A
Cat. No. 595-B
Cat. No. 895-A1
Cat. No. 895-M11
Cat. No. 895-M21
Cat. No. 895-A2
Cat. No.
1495-N30
Cat. No.
1495-N31
Cat. No.
1495-N32
Cat. No.
1494F-N33
Prices Consult Sales Office or price list
Bulletin 1494
Accessories Field Installed
2-22
Accessories, Continued
0 All terminals of the 30A switches are furnished with self-lifting pressure plate connectors as standard.
Description
For use with
Cat. No. Cat. No.
Lug Connectors (3 per package)
1494V, 1494F,
1494M, 1494R
Disconnect
Switches
Disconnect
Size (A)
Wire Size
30 #14#8 AWG Wire 0
60 #14#4 AWG Wire 1494R-N1
100 #8#1/0 AWG Wire 1494R-N2
200 #6#4/0 AWG Wire 1494R-N3
400600 2 of #110350 MCM Wire 1494R-N10
Defeater Bracket Extension Kit
For use with operating handles that do not align properly
with the door catch or door hardware on enclosures with a
rolled lip ange construction.
All 1494V handles
(except 1494V-R1
and 1494V-R2)
1494V-H12
Alternate Mounting Kits
For use where the ange material thickness is greater than
4.8mm (3/16 in.).
Operating handles
1494V-H1 or
1494V-H11
1494V-H3
Operating Han-
dles 1494V-H2
1494V-H6
Channel Support Kits
For use to prevent exing of the operating handle mounting
surface. This is especially useful when the operating handle
is mounted on a channel in a multi-door enclosure.
Applies only to
operating handle
Cat. Nos. 1494V-
H1, W1, H11 and
W11 (does not
apply to dual or
remote operators).
1494V-H4
Cat. No. 1494R-N3
Cat. No. 1494R-H3
Prices Consult Sales Office or price list
Bulletin 1494
Accessories Field Installed
2-23
Accessories, Continued
Description
For use with
Cat. No. Cat. No.
Type 12 Door Hardware Kit includes:
handle, cam, defeater actuator lever, rollers and shims.
1494F-L1
Enclosure heights 762mm (30 in.) and less
Top and Side (Right Hand)
1494F,
1494M,
1494D
Top and Side (Left Hand) 1494F-LL1
Top and Bottom (Right Hand) 1494F-L2
Top and Bottom (Left Hand) 1494F-LL2
Enclosure Heights 762mm (30 in.) to 1219mm (48 in.)
1494F-L2 and
1494F-L3
Top, Side and Bottom (Right Hand)
Top, Side and Bottom (Left Hand) 1494F-LL2 and
1494F-L3
Enclosure Heights greater than 1219mm (48 in.)
Top, Side and Bottom (Right Hand) 1494F-L4
Top, Side and Bottom (Left Hand) 1494F-LL4
Enclosure Heights 1016mm (40 in.) and less
All 1494V
Top and Side (Right Hand) 1494V-L1
Top and Side (Left Hand) 1494V-LL1
Enclosure Heights 1016mm (40 in.) to 1529mm (60 in.)
Top, Side and Bottom (Right Hand) 1494V-L1 and
1494V-L2
Top, Side and Bottom (Left Hand) 1494V-LL1 and
1494V-L2
Enclosure Heights 1524 (60 in.) and greater
Top, Side and Bottom (Right Hand) 1494V-L3
Top, Side and Bottom (Left Hand) 1494V-L3
Multiple Door Interlock Kits
Interlock kits are designed to provide interlocking between
the master and auxiliary doors of the same enclosure and
for use with Cat. Nos. 1494F-L4 and 1494F-LL4 hardware
kits or 1494V-L3 and 1494V-LL3 hardware kits. Specify one
master door kit and as many auxiliary door kits as
necessary (9 maximum). Connecting bars must be supplied
by user.
1494F,
1494M,
1494D,
1494V
Master Door Interlock Kit 1494F-N20
Auxiliary Door Interlock Kit 1494F-N21
Conduit Hubs (non-metallic)
12.7mm (1/2 in.)
1494F
Enclosed
Disconnects
Only
1490-N1
19mm (3/4 in.) 1490-N9
25.4mm (1 in.) 1490-N10
31.75mm (1-1/4 in.) 1490-N11
38.1mm (1-1/2 in.) 1490-N5
50.8mm (2 in.) 1490-N6
63.5mm (2-1/2 in.) 1490-N7
76.2mm (3 in.) 1490-N8
Door Hardware Kit Showing
Top, Side and
Bottom Latching
Cat. No. 1494V-L1 Cat. No. 1494V-L3
Cat. No. 1494F-N20
Cat. No. 1490-N11
Prices Consult Sales Office or price list
Bulletin 1494
Modifications Factory Installed
2-24
2
Modifications
Bulletin 1494F Enclosed Disconnect Switches
0 Only one push button or pilot light may be added to a Bulletin 1494F Disconnect Switch.
O A maximum of two auxiliary contacts may be added to a Bulletin 1494F Disconnect Switch.
Description
For use with
Cat. No. Sufx Code
Signal Push Button (1 N.O.) 0
1494F
Enclosed
Disconnects
Only
-1S
Red Pilot Light 0 -4R
Green Pilot Light 0 -4G
Red Push to Test Pilot Light 0 -5R
Auxiliary Contact (1 N.O.) O -98
Auxiliary Contact (1 N.C.) O -99
Enclosure Door Viewing Window -203W
Prices Consult Sales Office or price list
Bulletin 1494
Disconnect Switches
2-25
2
Specifications
1494F Disconnect, 1494M Remote Type, 1494V Disconnect Type,
1494V Remote or Dual Type, 1494R Disconnect Type
Electrical Ratings
Frame Size
150A 250A 400A
Auxiliary Contacts
IEC Ratings
EEMAC/NEMA
I
th
10A

U
i
660V
ACII U
x
12120V
220240V
380400V
500600V
ACII I
e
6A
3A
1.5A
1.2A

B600, P300
Switch Size 30A 60A 100A 200A 400A 600A
Rated insulation voltage U
i
(UL) IEC (600) 660V
Contacts IEC 408 220240V/50 Hz
AC-23 rating kW 380/440V/50 Hz
500600V/50 Hz
5.5
11
15
11
22
37
22
45
55
45
90
110
90
185
257
135
275
420
Ratings:
CSA/NEMA/UL HP 230V/60 Hz
460V/60 Hz
575V/60 Hz
7.5
15
20
15
30
50
30
60
75
60
125
150
125
250
350
250
500
750
Auxiliary Contacts AC11 DC11
Ratings:
U
e
600V AC
600V DC
Make or Break
Make or Break
360VA 360VA 138VA 138VA
EEMAC/NEMA A600, P300
Mechanical
Degree of protection Operating handles: IP65 (Types 1, 3, 3R, and 12), IP66 (Types 4, 4x)
Mechanical life (Typical) 20,000 operations
Switching frequency (operations/hr) 30A, 60A, 100A and 200A sizes 300 maximum 400A and 600A size 240 Maximum
Environmental
Temperature Operating
Storage
5C+40C (+41F104F)
30C+65C (22F149F)
Altitude 2000m per IEC 337-1
Design Specication/Test Requirements
Dielectric strength 2500V for 1 minute
Electrical life 6000 operations at rated current
Construction
Switch body material Phenolic
Contact material Copper, tinplated
Terminals: 30A
60A
100A
200A
400A
600A
#10 - 32 screw and self-lifting pressure plate
1/4 - 28 screw-lug, copper alloy
5/16 - 24 screw-lug, copper alloy
3/8 - 24 screw-lug, copper alloy
1/2 - 24 screw-lug, copper alloy
5/8 - 22 screw-lug, copper alloy
Cable Size (mm2) 30A
60A
100A
200A
400A, 600A
1.510mm
2
(#14#8 AWG)
2.516mm
2
(#14#4 AWG)
1050mm
2
(#8#1/0 AWG)
1695mm
2
(#6#4/0 AWG)
350 MCM - 185mm
2
(2 of #1/0 AWG) (2 per lug)
Recommended Torque: 30A
60A
100A
200A
400A
600A
20 lb-in.
45 lb-in.
150 lb-in.
275 lb-in.
400 lb-in.
575 lb-in.
Construction
Mechanisms Zinc Plated Steel
Handles Steel, painted
Y
Y
[ ]
Y
Y
[ ]
Y
Y
[ ]
Y
Y
[ ]
Bulletin 1494
Circuit Breaker Type Operating Mechanisms
2-26
2
Specifications, Continued
1494D Circuit Breaker Type, 1494V Circuit Breaker Type
0 Refer to circuit breaker specifications for other limitations.
Electrical Ratings
Frame Size
150A 250A 400A
Auxiliary Contacts
IEC Ratings
EEMAC/NEMA
I
th
10A

U
i
660V
ACII U
x
12120V
220240V
380400V
500600V
ACII I
e
6A
3A
1.5A
1.2A

B600, P300
Mechanical Data
Mechanical Life (Typical) 10,000 10,000 10,000
Maximum # of Aux. Contacts 2 2 2
Construction
Mechanisms Zinc plated steel
Handles Steel, painted
Environmental Data
Ambient Temperature 0
Open
Enclosed
Storage
20C+55C (4F+131F)
20C+40C (4F+104F)
40C+65C (40F+149F)
Altitude 2000m
Relative Humidity
90% @ 20C
50% @ 40C
Bulletin 1494
Disconnect Switches and Circuit Breakers
2-27
2
Approximate Dimensions
Bulletin 1494V
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
0 Approximate dimensions are for reference only.
O This approximate dimension will vary by fuse class and size.
O Approximate dimension with Class J fuses.
Disconnect Switches 0
NEMA Size
(A) A
B O C
D E F Max Min Max
30
6-19/64
(160)
202
(7-31/32)
171
(6-3/4)
549
(21-5/8)
69.9
(2-3/4)
192
(7-9/16)
98.5
(3-7/8)
60
6-19/64
(160)
215
(8-15/32)
171
(6-3/4)
549
(21-5/8)
65.1
(2-9/16)
192
(7-9/16)
98.5
(3-7/8)
100
6-19/64
(160)
231.8
(9-1/8)
171
(6-3/4)
599
(28-5/8)
90.9
(3-37/64)
192
(7-9/16)
98.5
(3-7/8)
200
8-5/64
(205.2)
384.5
(15-9/64)
197
(7-3/4)
549
(21-5/8)
166.3
(6-35/64)
223
(8-25/32)
118
(4-21/32)
400
15-23/32
(399.2)
479.2
(18-7/32)
193.7
(7-5/8)
549
(21-5/8)
203.2
(8)
300.8
(11-27/32)
223.3
(8-51/64)
600
15-23/32
(399.2)
446.8
(17-19/32) O
193.7
(7-5/8)
549
(21-5/8)
304.8
(12)
300.8
(11-27/32)
223.3
(8-51/64)
Circuit Breakers 0
Frame A B
C
D E F
Min Max
150A
EHD, FD, FDB, FDC, HFD, HMCP
152.4
(6)

171.5
(6-3/4)
584.2
(23)
152.4
(6)
138.1
(5-7/16)
127
(5)
250A
JD, JDB, JDC, HJD, HMCP
285.8
(11-1/4)

200.0
(7-7/8)
573.1
(22-9/16)
254
(10)
145.2
(5-23/32)
246.8
(9-23/32)
400A
KD, KDB, KDC, HKD, HMCP
228.9
(11-3/8)

200.0
(7-7/8)
573.1
(22-9/16)
304.8
(12)
181.0
(7-1/8)
245.3
(9-21/32)
Circuit
Breaker
Auxiliary
When Used
Common Industrial
Flange Cut-Out
Trailer Fuse Block
Vertical Center Line of Operating Handle Drilling
Door
Provides for
Wire Bending
Space
Disconnecting
Means
Operating
Handle
Mounting
Surface
Disconnect Means
Mounting Surface
Enclosure
Flange
A
B
C
D
E
F
7/8 (22.2)
1/2 (12.8 )
(2) 9/32 (7.1)
Dia. Holes
(2) 9/32 (7.1)
Dia. Holes
Vertical
of Operating
Handle
Operator
Mech..
Square Corners
or 1/4 (6.4) R. Max.
1
(25.4)
1
(25.4)
1/4 R
(6.4)
1-9/16
(39.7)
9/16 (14.3)
1/2
(12.7)
Standard
4-11/16
(119.1)
1-27/32
(46.8)
2-7/8
(73)
Optional
FLANGE DRILLING
C
L
C
L
Vertical Center
Line of Operating
Handle
Square Corners
or 1/4 (6.35) R.
5
(127)
3
(76.2)
1/4
(6.35)
1/2
(12.7)
Center Line
Oper. Mech.
6-1/2
(165.1)
9/16
(14.3)
21/64 (8.3) Dia.
2-Holes
Flange Cut-Out
1494V 30200A
Flange Cut-Out
1494V 400600A
Bulletin 1494
Fixed-Depth Flange Mounted Operating Mechanisms
2-28
2
Approximate Dimensions, Continued
Bulletin 1494F, 1494M
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Bulletin 1494D
0 Minimum wiring space for the maximum wire size.
O Approximate dimensions are for reference only.
O This approximate dimension will vary by fuse class and size.
Circuit Breakers O
Cutler-Hammer/
Westinghouse Frame A B O
C
D E F Min Max
150A
EHD, FD, FDB, FDC, HFD, HMCP
198.4
(7-13/16)

161.9
(6-3/8)

152.4
(6)
142.9
(5-5/8)
163.5
(6-7/16)
250A
JD, JDB, JDC, HJD, HMCP
292.1
(11-1/2)

212.7
(8-3/8)

203.2
(8)
147.6
(5-13/16)
239.7
(9-7/16)
400A
KD, KDB, KDC, HKD, HMCP
292.1
(11-1/2)

212.7
(8-3/8)

304.8
(12)
174.6
(6-7/8)
239.7
(9-7/16)
600A
LA, HLA, LC, HLC, LD, HLD
288.9
(11-3/8)

241.3
(9-1/2)

203.2
(8)
304.8
(12)
267.5
(10-17/32)
800A
MA, HMA, MC, ND, HND, NDC
406.4
(16)

241.3
(9-1/2)

254
(10)
312.7
(12-5/16)
183.4
(15-3/32)
800A
NB TRI-PAK
558.8
(22)

241.3
(9-1/2)

254
(10)
312.7
(12-5/16)
535.8
(21-3/32)
1200A
NB, HNB, NC, HNC, ND, HND, NDC
406.4
(16)

241.3
(9-1/2)

304.8
(12)
312.7
(12-5/16)
183.4
(25-3/32)
H
S
L
K
F
D
P
Door Catch
MIN.
Disconnect Switch
NEMA
Size
(A) D F H K L P S 0
Without Door Hardware
30
30.2
(1-3/16)
36.5
(1-7/16)
215.9
(8-1/2)
11.9
(15/32)
182.6
(7-3/16)
54
(2-1/8)
52.4
(2-1/16)
60
30.2
(1-3/16)
36.5
(1-7/16)
215.9
(8-1/2)
11.9
(15/32)
182.6
(7-3/16)
54
(2-1/8)
82.6
(3-1/4)
100
30.2
(1-3/16)
36.5
(1-7/16)
215.9
(8-1/2)
11.9
(15/32)
182.6
(7-3/16)
54
(2-1/8)
206.8
(8-9/64)
200
31.8
(1-1/4)
42.9
(1-11/16)
282.6
(11-1/8)
20.6
(13/16)
241.3
(9-1/2)
57.9
(2-9/32)
264.3
(10-13/32)
Small and Intermediate Enclosures with Door Hardware
30
30.2
(1-3/16)
36.5
(1-7/16)
215.9
(8-1/2)
11.9
(15/32)
182.6
(7-3/16)
54.8
(2-5/32)
57.2
(2-1/4)
60
30.2
(1-3/16)
36.5
(1-7/16)
215.9
(8-1/2)
11.9
(15/32)
182.6
(7-3/16)
54.8
(2-5/32)
82.6
(3-1/4)
100
30.2
(1-3/16)
36.5
(1-7/16)
215.9
(8-1/2)
11.9
(15/32)
182.6
(7-3/16)
54.8
(2-5/32)
206.8
(8-9/64)
200
31.8
(1-1/4)
42.9
(1-11/16)
282.6
(11-1/8)
20.6
(13/16)
241.3
(9-1/2)
58.7
(2-5/16)
264.3
(10-13/32)
Large Enclosures with Door Hardware
30
30.2
(1-3/16)
36.5
(1-7/16)
215.9
(8-1/2)
11.9
(15/32)
182.6
(7-3/16)
57.2
(2-1/4)
69.9
(2-3/4)
60
30.2
(1-3/16)
36.5
(1-7/16)
215.9
(8-1/2)
11.9
(15/32)
182.6
(7-3/16)
57.2
(2-1/4)
82.6
(3-1/4)
100
30.2
(1-3/16)
36.5
(1-7/16)
215.9
(8-1/2)
11.9
(15/32)
182.6
(7-3/16)
57.2
(2-1/4)
206.8
(8-9/64)
200
31.8
(1-1/4)
42.9
(1-11/16)
282.6
(11-1/8)
20.6
(13/16)
241.3
(9-1/2)
59.5
(2-11/32)
264.3
(10-13/32)
Flange Cut-Out
Circuit
Breaker
Auxiliary
When Used
Common Industrial
Flange Cut-Out
Trailer Fuse Block
Vertical Center Line of Operating Handle Drilling
Door
Provides for
Wire Bending
Space
Disconnecting
Means
Operating
Handle
Mounting
Surface
Disconnect Means
Mounting Surface
Enclosure
Flange
A
B
C
D
E
F
Disconnect Switches O
NEMA
Size
(A) A B O
C
D E F Min Max
30
150.8
(5-15/16)
273.1
(10-3/4)
161.9
(6-3/8)

55.6
(2-3/16)
190.5
(7-1/2)
95.3
(3-3/4)
60
150.8
(5-15/16)
335
(13-3/16)
161.9
(6-3/8)

50.8
(2)
190.5
(7-1/2)
95.3
(3-3/4)
100
200.4
(7-15/16)
425.5
(16-3/4)
215.9
(8-1/2)

127
(5)
209.6
(8-1/4)
95.3
(3-3/4)
200
266.7
(10-1/2)
528.6
(20-13/16)
228.6
(9)

177.8
(7)
289
(11-3/8)
141.3
(5-9/16)
Bulletin 1494
Enclosed Disconnects
2-29
2
Approximate Dimensions, Continued
Bulletin 1494F
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Disc. Size
(A) DIM Ref. A B C D E F G H J
30 A11
228.6
(9)
228.6
(9)
28.2
(1-7/64)
254
(10)
82.5
(3-1/4)
165.1
(6-1/2)
63.5
(2-1/2)
102.8
(4-3/64)
9/32
(7.1)
60 & 100 A12
330.2
(13)
228.6
(9)
28.2
(1-7/64)
355.6
(14)
82.5
(3-1/4)
165.1
(6-1/2)
63.5
(2-1/2)
102.8
(4-3/64)
9/32
(7.1)
200 A13
533.4
(21)
266.7
(10-1/2)
28.2
(1-7/64)
558
(22)
101.6
(4)
203.2
(8)
63.5
(2-1/2)
124.6
(4-29/32)
9/32
(7.1)
400 A14
685.8
(27)
355.6
(14)
28.2
(1-7/64)
685.8
(27)
152.4
(6)
228.6
(9)
87.3
(3-7/16)
186.5
(7-11/32)
8.7
(11/32)
Ampere Rating (A)
Wire Size
Line and Load Terminals Ground Terminal
30 #14#6 AWG Wire (2) #10#4 AWG Wire
60 #14#4 AWG Wire (2) #10#4 AWG Wire
100 #8#1/0 AWG Wire (2) #10#4 AWG Wire
200 #6#4/0 AWG Wire (2) #6#4/0 AWG Wire
400 (2) #1/0 AWG - 250 kcmil (2) #6#4/0 AWG Wire
A
B
C
D
E
J Mounting Hole
G
H
F
Bulletin 1491
Fuse Blocks
2-30
2
Bulletin 1491
Fuse Blocks
Available from
30A600A
Can be used with
Class H, J and R fuses
TABLE OF CONTENTS
Description Page Description Page
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-31
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-32
Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-33
Description
These Bulletin 1491 Fuse Blocks have been designed for general purpose
applications. The bases of these blocks, either phenolic or porcelain, are rugged in
construction and provide ease in mounting and wiring.
Conformity to Standards: Approvals:
NEMA 512 CSA Certied (File No. LR 1234)
UL Listed (File No. E 34648)
30A Fuse Blocks
With Spring-Type Fuse Clips
and Self-Lifting Wiring Terminal Clamps
30A Fuse Blocks
With Spring-Type Fuse Clips
Class R Rejection Feature
and Self-Lifting Wiring Terminal Clamps
60A Fuse Blocks
With Spring-Type Fuse Clips
and Tang-Type Connections
on the Wiring Terminals
100A Fuse Blocks
With Wedge-Type Fuse Clamps
and Tang-Type Connections
on the Wiring Terminals
Bulletin 1491
Fuse Blocks
2-31
Product Selection
Fuse Blocks
0 These fuse blocks have porcelain bases.
O For two pole applications use two of Cat. No. 1491-N321.
O For two pole applications use two of Cat. No. 1491-N421.
O For two pole applications use two of Cat. No. 1491-N521.
O For three pole applications use three of Cat. No. 1491-N521.
O For two pole applications use two of Cat. No. 1491-N621.
6 For three pole applications use three of Cat. No. 1491-N621.
O For two pole applications use two of Cat. No. 1491-R621.
O For three pole applications use three of Cat. No. 1491-R621.
Fuse
Size
(A)
Maximum
Voltage (V)
No. of
Poles
Class CC
Cat. No.
Class H
Cat. No.
Class J
Cat. No.
Class R
Cat. No.
Class C
(HRC Form II)
Cat. No.
030
250
1
2
3

1491-N121
1491-N122
1491-N125

1491-R125

600
1
2
3

1491-R162

1491-N161

1491-N126

1491-N126

1491-R126

1491-E126
3160
250 3 1491-N226 1491-R226
600 3 1491-N266 1491-N266 1491-R266 1491-E126
61100 250600
1
2
3

1491-N321
0
O
1491-N333
1491-N321
0
O
1491-N333

1491-R333

1491-E333
101200 250600
1
2
3

1491-N421
O
1491-N433
1491-N421
O
1491-N433

1491-R433

1491-E433
201400 250600
1
2
3

1491-N521
O
O
1491-N521
O
O

1491-R523

1491-E521
401600 250600
1
2
3

1491-N621
O
6
1491-N621

6
1491-R621
O
O

Specifications Page 2-32


Approximate Dimensions Page 2-33
Prices Consult Sales Office or price list
Bulletin 1491
Fuse Blocks
2-32
Specifications
Fuse Blocks
Electrical
UL Fuse Type Class C Class CC Class H Class J Class R
CSA Fuse Type HRCI-C HRCI-Misc. HRCI-H HRCI-J HRCI-R
Maximum Fuse Cartridge Size
Maximum Voltage AC
DC
30A600A 30A 30A600A 30A600A 30A600A
600V 600V 600V 600V 600V
250V 250V 250V 250V 250V
Thermal Current Rating
Maximum Short Circuit Prospective Fault
Current
30A600A 30A 30A600A 30A600A 30A600A
100 kA 200 kA 10 kA 100 kA 200 kA
Mechanical
Degree of Protection IP00 IP00 IP00 IP00 IP00
Terminal Capacity mm
2
AWG
10 6 10 10 10
#8 (500 MCM) #10 #8 (500 MCM) #8 (500 MCM) #8 (500 MCM)
Construction
Fuse Clips Tin plated copper alloy
Terminals Tin plated copper alloy
Fuse Block Base
Phenolic or Porcelain
Environmental
Ambient Temperature
Open 20C+55C (4F+131F)
Enclosed 20C+40C (4F+104F)
Storage 40C+65C (40F+149F)
Altitude (per IEC 947-5) 2000m
Relative Humidity (per IEC 947-3) 90% at 20C and 50% at 40C
Product Selection Page 2-31
Bulletin 1491
Fuse Blocks
2-33
Approximate Dimensions
Fuse Size 130A
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
0 Alternate mounting holes.
O Dimension A must be held to insure fuse block rejection function.
Note: When fuse blocks are installed in a vertical plane, the block with the rejection numbers must be on the bottom.
Voltage
(V)
Class H Class J
Fuse Size
(A)
Maximum
Volts (V) Cat. No.
A O
0.020
B
Ref. A B A B
250 54.0 (2-1/8) 76.2 (3)
130
250 1491-R125 74.68 (2.94) 53.97 (2-1/8)
600 60.3 (2-3/8) 146.1 (5-3/4) 60.3 (2-3/8) 76.2 (3) 600 1491-R126 145.29 (5.72) 60.33 (2-3/8)
Drill & Tap
2 Holes
For No.
10-32
Screws
61.91
(2-7/16)
15.88
(5/8)
41.27
(1-5/8)
42.86
(1-11/16)
7.1 Dia.
(9/32)
157.16
(6-3/16)
79.38
(3-1/8)
53.97
(2-1/8)
34.92
(1-3/8)
31.80
(1-1/4)
Drill & Tap
2 Holes
For No.
10-32
Screws
76.20
(3)
38.10
(1-1/2)
14.29
(9/16)
14.29
(9/16) 14.29
(9/16)
B
A
Drill & Tap 4 Holes
For No. 10-32 Screws
119.06
(4-11/16)
46.04
(1-13/16)
1
130A, Single Pole, 600V
Cat. No. 1491-N161
Shipping Weight 0.45kg (1 lb)
130A, 2-Pole, 250V
Cat. No. 1491-N122
Shipping Weight 0.91kg (2 lb)
130A, 3-Pole, 250600V
Cat. No. 1491-N125 (250V)
Cat. No. 1491-N126 (600V)
Shipping Weight 0.45kg (1 lb)
Rejection
Feature
76.20
(3.00)
32.51
(1.28)
41.15
(1.62)
7.92
(.312)
19.05
(.75)
(4) Terminals Combination Of:
Double Quick-Connect
(.250 x .032) 20 A Max.,
And Pressure Plate Screw
(10-32 Sems).
(Ref.) Wire: #10 AWG Max. Cu Only
2 Holes
4.37 Dia.
(.172)
Cat. No. 1491-R162
Rejection Members
Drill and Tap For
#10-32 Screws
A
B
14.29
(9/16)
14.29
(9/16)
119.06
(4-11/16)
46.04
(1-13/16)
130A, 250600V
Cat. No. 1491-R125 (250V)
Cat. No. 1491-R126 (600V)
Shipping Weight 0.45kg (1 lb)
Bulletin 1491
Fuse Blocks
2-34
Approximate Dimensions, Continued
Fuse Size 3160A
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
0 Alternate Mounting Holes.
O Dimension A must be held to insure fuse block rejection function.
Notes:
1. When fuse blocks are installed in a vertical plane, the block with the rejection numbers must be on the bottom.
2. When using Cat. No. 1491-N321, install fiber washers between fuse blocks and mounting plates. Discard extra screws, washers and clamps on
multiple pole applications.
Voltage
(V)
Class H Class J
Fuse Size
(A)
Maximum
Volts (V) Cat. No.
A O
0.020
B
Ref. A B A B
250 60.3 (2-3/8) 95.3 (3-3/4)
3160
250 1491-R226 94.49 (3.72) 60.33 (2-3/8)
600 68.3 (2-11/16) 158.8 (6-1/4) 68.3 (2-11/16) 79.4 (3-1/8) 600 1491-R266 157.99 (6.22) 68.26 (2-11/16)
Voltage (V)
Class H Class J
A B A B
250 82.6 (3-1/4) 174.6 (6-7/8)
600 85.7 (3-3/8) 225.4 (8-7/8) 82.6 (3-1/4) 142.9 (5-5/8)
B A
Drill & Tap 4 Holes
For No. 10-32 Screws
141.29
(5-9/16)
46.04
(1-13/16)
14.29
(9/16)
14.29
(9/16)
1
3160A, 3-Pole, 250600V
Cat. No. 1491-N226 (250V)
Shipping Weight 0.45kg (1 lb)
Cat. No. 1491-N266 (600V)
Shipping Weight 0.91kg (2 lb)
Rejection Members
Drill and Tap For
#10-32 Screws
A
B
14.29
(9/16)
14.29
(9/16)
141.29
(5-9/16)
46.04
(1-13/16)
3160A, 250600V
Cat. No. 1491-R226 (250V)
Shipping Weight 0.45kg (1 lb)
Cat. No. 1491-R266 (600V)
Shipping Weight 0.91kg (2 lb)
69.85
(2-3/4)
53.97
(2-1/8)
B
26.99
(1-1/16)
26.99
(1-1/16)
A
Drill & Tap 4 Holes
For 1/4" -20 Screws
53.97
(2-1/8)
53.97
(2-1/8)
123.82
(4-7/8)
B
26.99
(1-1/16)
26.99
(1-1/16)
A
Drill & Tap 6 Holes
For 1/4" -20 Screws
53.97
(2-1/8)
53.97
(2-1/8)
53.97
(2-1/8)
177.80
(7)
B
26.99
(1-1/16)
26.99
(1-1/16)
A
Drill & Tap 8 Holes
For 1/4" -20 Screws
53.97
(2-1/8)
53.97
(2-1/8)
53.97
(2-1/8)
53.97
(2-1/8)
231.77
(9-1/8)
B
26.99
(1-1/16)
26.99
(1-1/16)
A
Drill & Tap 10 Holes
For 1/4" -20 Screws
Single Pole Application
Use One of Cat. No. 1491-N321
Approximate Shipping Weight 0.91kg (2 lb)
2-Pole Application
Use Two of Cat. No. 1491-N321
Approximate Shipping Weight Approx. 2 times wt. of 1-Pole
4-Pole Application
Use Four of Cat. No. 1491-N321
Approximate Shipping Weight Approx. 3 times wt. of 1-Pole
3-Pole Application
Use Three of Cat. No. 1491-N321
Approximate Shipping Weight Approx. 3 times wt. of 1-Pole
Bulletin 1491
Fuse Blocks
2-35
Approximate Dimensions, Continued
Fuse Size 61100A
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
0 Dimension A must be held to insure fuse block rejection function.
Notes:
1. When fuse blocks are installed in a vertical plane, the block with the rejection numbers must be on the bottom.
2. Fuse blocks with wedge type clamps (61A and above) can be oriented to mount all fuses either to the left or to the right of fuse clamp centers.
Voltage (V)
Class H Class J
A B A B
250 74.6 (2-15/16) 149.2 (5-7/8)
600 79.4 (3-1/8) 200.0 (7-7/8) 76.2 (3) 117.5 (4-5/8)
Fuse Size (A) Maximum Volts (V) Cat. No.
A 0
0.020
B
Ref.
61100
250
1491-R333
149.35 (5.88) 74.61 (2-15/16)
600 200.15 (7.88) 79.38 (3-1/8)
50.80
(2)
171.45
(6-3/4)
B
28.57
(1-1/8)
28.57
(1-1/8)
A
Drill & Tap 4 Holes
For 1/4" -20 Screws
3-Pole
Cat. No. 1491-N333
Approximate Shipping Weight 1.36kg (3 lb)
Rejection Members
Drill and Tap For
1/4-20 Screws
B
10.32
(13/32 Max.)
50.80
(2)
171.45
(6-3/4)
28.57
(1-1/8)
28.57
(1-1/8)
A
61100A, 250600V
Cat. No. 1491-R333
Shipping Weight 1.36kg (3 lb)
Bulletin 1491
Fuse Blocks
2-36
Approximate Dimensions, Continued
Fuse Size 101200A
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
0 Dimension A must be held to insure fuse block rejection function.
Note: When fuse blocks are installed in a vertical plane, the block with the rejection numbers must be on the bottom.
Voltage (V)
Class H or R Class J
A B A B
250 120.7 (4-3/4) 228.6 (9)
600 125.8 (4-61/64) 304.80 (12) 117.5 (4-5/8) 190.5 (7-1/2)
Rejection Members
Drill and Tap For
5/16-18 Screws
A
B
15.08 max.
(19/32 Max.)
69.85
(2-3/4)
222.25
(8-3/4)
34.92
(1-3/8)
34.92
(1-3/8)
101200A, 250600V
Cat. No. 1491-R433
Shipping Weight 3.2kg (7 lb)
Fuse Size
(A)
Maximum
Volts (V) Cat. No.
A 0
0.020
B
Ref.
101200
250
1491-R433
184.15 (7.25) 106.36 (4-3/16)
600 247.60 (9.75) 109.54 (4-5/16)
A B
50.80
(2)
28.57
(1-1/8)
50.80
(2)
82.55
(3-1/4)
101.60
(4)
9.52
(3/8)
9.52
(3/8)
Drill For 5/16" -18 Screw
A B
50.80
(2)
28.57
(1-1/8)
50.80
(2)
82.55
(3-1/4)
317.50
(12-1/2)
9.52
(3/8)
9.52
(3/8)
82.55
(3-1/4)
82.55
(3-1/4)
Drill For 5/16" -18 Screw
A B
50.80
(2)
28.57
(1-1/8)
50.80
(2)
82.55
(3-1/4)
425.45
(16-3/4)
9.52
(3/8)
9.52
(3/8)
82.55
(3-1/4)
82.55
(3-1/4)
82.55
(3-1/4)
Drill For 5/16" -18 Screw
A B
50.80
(2)
28.57
(1-1/8)
50.80
(2)
82.55
(3-1/4)
209.6
(8-1/4)
9.52
(3/8)
9.52
(3/8)
82.55
(3-1/4)
Drill For 5/16" -18 Screw
Single Pole
Cat. No. 1491-N521
Shipping Weight 3.2kg (7lb)
2-Pole Application
Use Two of Cat. No. 1491-N521
Shipping Weight 6kg (13 lb)
3-Pole Application
Use Three of Cat. No. 1491-N521
Shipping Weight 8.6kg (19 lb)
4-Pole Application
Use Four of Cat. No. 1491-N521
Shipping Weight 11.4kg (25 lb)
Bulletin 1491
Fuse Blocks
2-37
Approximate Dimensions, Continued
Fuse Size 201400A
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Fuse Size 401600A
0 Dimension A must be held to insure fuse block rejection function.
Notes:
1. When fuse blocks are installed in a vertical plane, the block with the rejection numbers must be on the bottom.
2. Fuse blocks with wedge type clamps (61A and above) can be oriented to mount all fuses either to the left or to the right of fuse clamp centers.
Fuse Size (A)
Maximum
Volts (V) Cat. No.
A 0
0.020
B
Ref.
201400
250
1491-R523
228.60 (9.00) 120.70 (4-3/4)
600 304.80 (12.00) 125.81 (4-61/64)
Voltage (V)
Class H or R Class J
A B A B
250 206.38 (8-1/8) 117.47 (4-5/8)
600 282.57 (11-1/8) 193.68 (7-5/8) 127.00 (6) 63.50 (2-1/2)
6.35 max.
(1/4 Max.)
28.57
(1-1/8)
B
A
Rejection Members
Drill and Tap
For 5/16-18
Screws
50.80
(2)
50.80
(2)
82.55
(3-1/4)
25.40
(1)
82.55
(3-1/4)
25.40
(1)
82.55
(3-1/4)
9.52
(3/8)
9.52
(3/8)
107.90
(4-1/4)
107.90
(4-1/4)
201400A, 250600V
Cat. No. 1491-R523
Shipping Weight 8.6kg (19 lb)
A
B
128.59
(5-1/16)
44.45
(1-3/4)
44.45
(1-3/4)
88.90
(3-1/2)
88.90
(3-1/2)
107.95
(4-1/4)
Single Pole
600A Terminations Only
Cat. No. 1491-N621
Shipping Weight 2.7kg (6 lb)
Bulletin 1491
Fuse Blocks
2-38
Approximate Dimensions, Continued
Fuse Size 401600A, Continued
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
127.00
(5)
127.00
(5)
88.90
(3-1/2)
88.90
(3-1/2)
44.45
(1-3/4)
44.45
(1-3/4)
44.45
(1-3/4)
88.90
(3-1/2)
88.90
(3-1/2)
44.45
(1-3/4)
44.45
(1-3/4)
44.45
(1-3/4)
Drill For 5/16 -18 Screw
128.59
(5-1/16)
107.95
(4-1/4)
107.95
(4-1/4)
206.38
(8-1/8)
282.57
(11-1/8)
401-600 Amp
250 Volts
401-600 Amp
600 Volts
88.90
(3-1/2)
88.90
(3-1/2)
107.95
(4-1/4)
117.35
(4-5/8)
193.55
(7-5/8)
401-600 Amp
250 Volts
401-600 Amp
600 Volts
127.00
(5)
88.90
(3-1/2)
88.90
(3-1/2)
44.45
(1-3/4)
44.45
(1-3/4)
88.90
(3-1/2)
88.90
(3-1/2)
44.45
(1-3/4)
44.45
(1-3/4)
Drill For 5/16 -18 Screw
128.59
(5-1/16)
107.95
(4-1/4)
107.95
(4-1/4)
117.35
(4-5/8)
193.55
(7-5/8)
206.25
(8-1/8)
282.45
(11-1/8)
401-600 Amp
250 Volts
401-600 Amp
600 Volts
401-600 Amp
250 Volts
401-600 Amp
600 Volts
127.00
(5)
127.00
(5)
88.90
(3-1/2)
88.90
(3-1/2)
88.90
(3-1/2)
88.90
(3-1/2)
88.90
(3-1/2)
88.90
(3-1/2)
44.45
(1-3/4)
44.45
(1-3/4)
44.45
(1-3/4)
Drill For 5/16 -18 Screw
128.59
(5-1/16)
107.95
(4-1/4)
107.95
(4-1/4)
206.38
(8-1/8)
282.57
(11-1/8)
401-600 Amp
250 Volts
401-600 Amp
600 Volts
88.90
(3-1/2)
107.95
(4-1/4)
127.00
(5)
44.45
(1-3/4)
44.45
(1-3/4)
44.45
(1-3/4)
44.45
(1-3/4)
44.45
(1-3/4)
88.90
(3-1/2)
107.95
(4-1/4)
117.47
(4-5/8)
193.68
(7-5/8)
401-600 Amp
250 Volts
401-600 Amp
600 Volts
2-Pole
400A Terminations Only
Cat. No. 1491-N621 (Amt. 2)
Shipping Weight 5kg (11 lb)
3-Pole
400A Terminations Only
Cat. No. 1491-N621 (Amt. 3)
Shipping Weight 7.3kg (16 lb)
4-Pole
400A Terminations Only
Cat. No. 1491-N621 (Amt. 4)
Shipping Weight 9.5kg (21 lb)