Sie sind auf Seite 1von 87

D TYPE

lift control system

SPECIFICATION AND INSTALLATION MANUAL

Manual ver. 2.0 Program ver. 4.17

SEC ELECTRONICS
tel: ++ 386 5 753 2006 fax: ++ 386 5 753 2007

Neverke 30 6256 Koana, SLOVENIA email: sec.electronics@siol.net web: http://www.secelectro.com

ISO 9001 Q-446

The information held in this manual may be modified without notice and SEC electronics will not be responsible for changes that may occur in the future.

No part of this manual can be reproduced, for any reason, in any form or by any means ( including recording and photocopying) without the written consent of SEC electronics.

Before the control panel installation, wiring, commissioning and inspection, read this instruction manual carefully.

Keep the manual in a safe place and available to engineering and installation personnel during the control panel functioning period.

SEC electronics is not responsible for those mistakes that may be found in this manual and for the damages that they may cause.

All rights reserved.

D-type manual

291 801 104

CONTENTS

SAFETY SIMBOL LEGEND 0. 1. 1.1. 2. 2.1. 2.2. 2.3. 2.4. 2.5. 3. 3.1. 3.2. 4. 4.1. 4.2. 5. 5.1. 5.2. 5.3. 5.4. 5.5. 6. 6.1. 6.2. 6.3. 6.4. 6.5. 6.6. 7. 7.1. 7.2. SAFETY PRECAUTIONS PRODUCT LIABILITY AND WARRANTY TERMS OF WARRANTY INSPECTION PROCEDURE UPON DELIVERY INSPECTION PROCEDURE CONTROL PANEL TYPE DESIGNATION NAMEPLATE STANDARD SPECIFICATIONS DISPOSAL OF THE DEVICE INSTALLATION GUIDELINES MECHANICAL SPECIFICATION INSTALLATION MOUNTING CLEARANCE WIRING PROCEDURE AC INPUT CONNECTION MAIN MOTOR CONNECTION PROGRAMMING WITH PROGRAMMER PAGE 1 PARAMETERS PAGE 2 INPUT STAGES DEFINITION PAGE 4 LAST EVENTS CONTROL TABLE PAGE 5 ERROR TABLE PRESETING AND FACTORY RESET PROGRAMMING WITH COMPUTER CONNECTION TO PC PAGE 1 OR PARAMETERS DEFINITION PAGE 2 OR INPUTS DEFINITION PAGE 3 OR ONLINE INPUTS AND OUTPUTS MONITORING PAGE 4 OR LAST EVENTS TABLE PAGE 5 OR ERROR TABLE ABBREVIATIONS TERMINALS ON CONTROL PANEL ELEMENTS ON CONTROL PANEL

5 6 9 9 10 10 10 11 12 12 13 13 14 15 15 16 17 24 34 36 37 38 39 39 39 40 41 42 42 43 43 45

D-type manual

291 801 104

8.

COUNTING SENSORS CONNECTION AND POSITION COUNTING SYSTEM NUMBER 1 - 8 COUNTING SYSTEM NUMBER 1 COUNTING SYSTEM NUMBER 2 COUNTING SYSTEM NUMBER 4 WITH SEPARATED MAGNETS COUNTING SYSTEM NUMBER 4 COUNTING SYSTEM NUMBER 5 COUNTING SYSTEM NUMBER 6 COUNTING SYSTEM NUMBER 7 COUNTING SYSTEM NUMBER 8

47 48 49 50 51 52 53 54 55 56 57 57 57 58 59 59 59 60 60 61 65 66 66 72 74 77 79 81 81 82 82 83 83 83 83 84 85 85 86 87

9. 9.1. 9.2. 9.3. 10. 10.1. 10.2. 10.3. 10.4. 10.5. 10.6 11. 11.1. 11.2. 11.3 11.4. 11.5 12. 12.1. 12.2. 12.3. 13. 13.1. 13.2. 13.3. 13.4. 14. 14.1. 14.2.

CONNECTION DURING INSTALLATION PHASE POWER SUPPLY MOTOR CONNECTION MAINTENANCE AND SAFETY CONNECTION START UP PRE POWER CHECK VOLTAGE AND CONTROL ELEMENTS CHECK MAINTENANCE MODE NORMAL MODE TROUBLESHOOTING ERROR CODE READING FROM INDICATOR D-type LIFT CONTROLLER TECHNICAL INFORMATION TECHNICAL CHARACTERISTIC D-type MODULE TERMINALS INPUTS FOR CALLS CONNECTION OUTPUTS CONNECTION OPERATING IN DUPLEX MODE SAFETY CIRCUIT 186 GENERAL FEATURES DETAILS AND CONNECTIONS REQUIREMENTS FOR INSTALLATION MAINTENANCE CARE SERVICE REPAIRS CUSTOMER SERVICE GUIDE TO ELECTROMAGNETIC COMPATIBILITY THE EMC DIRECTIVE AND APPLICABLE STANDARD EMC COMPLIANT ELECTRICAL CABINET WIRING RULES

DECLARATION OF CONFORMITY ADDENDUMS FOR NEWER PROGRAM VERSIONS PRESET PARAMETERS

D-type manual

291 801 104

SAFETY SYMBOL LEGEND

WARNING:

Commands attention to an operating procedure, practice, condition, or statement, which, if not strictly observed, could result in personal injury or death. Commands attention to an operation procedure, practice, condition, or statement, which, if not strictly observed, could result in damage or destruction of equipment. Commands attention to an operating procedure, practice, condition, or statement that must be highlighted.

CAUTION:

NOTE:

D-type manual

291 801 104

0. SAFETY PRECAUTIONS
WARNING - ATTENTION
Drive systems cause mechanical motion. It is the responsibility of the user to ensure that any such motion does not result in an unsafe condition. Factory provided interlocks and operating limits should not be bypassed or modified.

WARNING ELECTRICAL SHOCK AND BURN HAZARD


When using instruments such as oscilloscopes to work on live equipment, the oscilloscopes chassis should be grounded and a differential amplifier input should be used. Care should be used in the selection of probes and leads and in the adjustment of the oscilloscope so that accurate readings may be made. See instrument manufacturers instruction book for proper operation and adjustment to the instrument.

WARNING FIRE AND EXPLOSION HAZARD


Fires or explosions might result from mounting control panels in hazardous areas such as locations where flammable or combustible vapors or dusts are present. Control panels should be installed away from hazardous areas, even if used with motors suitable for use in these locations.

WARNING STRAIN HAZARD


Improper lifting practices can cause serious or fatal injury. Lift only with adequate equipment and trained personnel. When carrying equipment without packaging the boards or metal panels can cause damage to the equipment and injury to you.

WARNING CRUSHING HAZARD


Risk of crushing and damage to the control panel if it does not have a firm stand. Be sure to place the control panel on a flat surface witch can support its weight before installation! Do not stand the control panel on end as it could fall over.

WARNING HIGH TEMPERATURE


After prolonged use, the parts in control panel will reach a maximum temperature of 90 oC. Touching them with bare hands can be painful. Allow the unit to cool before you get near the hot parts. When braking resistors are used (they are normally installed at the top or in the side of the box) this resistors can reach a maximum temperature of 200 oC. Touching them with bare hands can cause serious or fatal injury.

ATTENTION ELECTRIC SHOCK


Control panel, motors and all other equipment must be ground connected according to the NEC ( Code Electrique National).

WARNING / ATTENTION
Replace all covers before applying power to the control panel. Failure to do so may result in death or serious injury.

WARNING / ATTENTION
Control panels are electrical apparatus for use in industrial installations. Parts of the control panels are energized during operation. The electrical installation and the opening of the device should therefore only be carried out by qualified personnel. Improper installation of motors, control panel or other equipment may therefore cause the failure of the device as well as serious injury to persons or material damage. Control panels are not equipped with motor overspeed protection logic. Follow the instructions given in this manual and observe the local and national safety regulations applicable.

D-type manual

291 801 104

CAUTION / PRECAUTION
Do not connect power supply voltage that exceeds the standard specification voltage fluctuation permissible. If excessive voltage is applied to the control panel, damage to the internal components will result.

CAUTION / PRECAUTION
Do not operate the control panel without the ground wire connected. The motor chassis should be grounded to earth through a ground lead separate from all other equipment ground leads to prevent noise coupling. The grounding wires shall be sized in accordance with the NEC or Canadian Electrical Code. The connection shall be made by a UL listed or CSA certified closed-loop terminal connector sized for the wire gauge involved. The connector is to be fixed using the crimp tool specified by the connector manufacturer.

CAUTION / PRECAUTION
Do not perform a megger test between the control panel terminals or on the control circuit terminals.

CAUTION / PRECAUTION
Because the ambient temperature greatly affects control panel life and reliability, do not install the control panel in any location that exceeds the allowable temperature. Leave the ventilation cover attached for temperatures of 40 oC or below.

CAUTION / PRECAUTION
The control panel must be mounted on a wall that is constructed of heat resistant material. While the control panel is operating, the temperature of the control panel parts can rise to a temperature of 90 C. In case when braking resistors are used, the temperature of this resistor can rise up to 200 C.

D-type manual

291 801 104

NOTE
The terms controller, lift controller and control box are sometimes used interchangeably throughout the industry. We will use the term control panel in this document 1. Never remove the covers while the AC Input power supply is switched on. Minimum time to wait before working on the terminals or inside the device is 1 minute after disconnecting for control panels without electronic regulators for motors and 5 minutes for control panels with electronic regulators ( VVVF, ACVV, soft start) Do not touch or damage any components when handling the device. The changing of the isolation gaps or the removing of the isolation and covers is not permissible. If the doors have to be removed (or opened) because the room temperature is higher than 40 degrees, the user has to ensure that no occasional contact with live parts may occur. Protect the control panel from impermissible environmental conditions (temperature, humidity, shock etc.) No voltage should be connected to the output terminals for the motors, magnets, valves, lights and switches ( terminals 5, 6, 7, 8, 9, 10, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 25, 25a, 26, 26a, 27, 31, 40, 45, 46, 47, 48, 56, 57, 58, 59, 77, 78, 79, 80, 100, 101, 102, 103, 104, 105, 106, 107, 108, 121, 122, 123, 130, 131, 132, 222, 351, 352, 358, 360, 371, 372) A capacitative load ( e.g. Var compensation capacitors) should not be connected to the outputs for the motors (terminals 5, 6, 7, 8, 9, 10, 12, 13, 14, 15, 16, 17, 18, 19, 20) Always connect the control panel to the protective ground ( PE ) via the marked connection terminals ( 0 or GND ) and the housing ( 0 or GND ). Control panels have ground discharge currents greater than 3,5 mA. EN 50178 specifies that with discharge currents greater than 3,5 mA the protective conductor ground connection ( 0 or GND ) must be fixed type and doubled for redundancy. The electrical commissioning should only be carried out by qualified personnel, who are also responsible for the provision of a suitable ground connection and a protected power supply feeder in accordance with the local and national regulations. No dielectric tests should be carried out on parts of the control panel. A suitable measuring instrument ( internal resistance of at least 10 kohm/V ) should be used for measuring the signal voltages. If the control panel has been stored for longer than three years, the operation of the capacitors may be impaired. Before commissioning devices that have been stored for long periods, connect them to a power supply for two hours with no load connected in order to regenerate the capacitors, ( the input voltage has to be applied without enabling the functionality). The control panel may start accidentally in the event of a failure, even if it is disabled, unless it has been disconnected from the AC input feeder.

2.

3.

4.

5.

6.

7.

8.

9.

10.

D-type manual

291 801 104

1. PRODUCT LIABILITY AND WARRANTY


We guarantee the faultless condition of our product as described in our advertising, the product documentation we have published, and this manual. Product characteristics over and above this are not guaranteed. Claims for damages are generally excluded, except in the case of proven premeditation, gross negligence by SEC electronics, or the absence of any promised features. In particular we do not accept any liability if the control panels are used with other systems, encoders, switches, power supply systems and drive motors for which the control panels are unsuitable as stated in this manual or which fail to conform with the customary state of technology by virtue of their individual design. We also disclaim responsibility for any damage to lift facilities and building facilities due to malfunction of the product or due to errors in this manual. We are not responsible for violation of the patents and other rights of third parties. We shall not be liable for any damage resulting from improper handling as defined in this manual. We expressly exclude liability for lost profit and especially for consequential damage due to the nonobservance of safety regulations and warnings and/or resulting from accessories not supplied by SEC electronics. SEC electronics products are designed for a long service life. They confirm with the current state of science and technology and were individually tested in all their promised functions prior to shipment. SEC electronics is continuously engaged in product and market analysis in the interest of further development and constant improvement. However, if any malfunctions or breakdowns occur in spite of all the preventive measures, you should notify the customer service department in Neverke, Slovenia. We assure you that suitable action to rectify the damage will be taken without delay.

1.1. TERMS OF WARRANTY


We guarantee the products proper working order as defined in this operating manual for a period of 24 months after shipment as per delivery note. Repairs will only be carried out free of charge if this manual was observed for storage, transportation, installation, commissioning and operation. Interventions in a unit by the customer or third parties are only allowed after special consultation with SEC electronics. If this condition is not observed, SEC electronics will accept no responsibility for any damage to the unit, injury to persons or consequential damage; in this case the warranty shall expire. SEC electronics also disclaims all responsibility for unit faults resulting from damaged or functionally defective equipment in the control panels environment or following the use of accessories which were not supplied by SEC electronics. The General Terms of Business of SEC electronics shall apply.

D-type manual

291 801 104

2. INSPECTION PROCEDURE
2.1. UPON DELIVERY INSPECTION PROCEDURES
A high degree of care is taken in packing our control panels and preparing them for delivery. They should only be transported with suitable transport equipment (see weight data). Observe the instructions printed on the packaging. This also applies when the device is unpacked and installed.

Upon delivery, check the following:


the packaging for any external damage whether the delivery note matches your order

Open the packaging with suitable tools. Check whether:


any parts were damaged during transport the device type corresponds to your order

In the event of any damage or of an incomplete or incorrect delivery please notify the responsible sales offices immediately. The devices should only be stored in dry rooms within the specified temperature ranges.

NOTE:

A certain degree of moisture condensation is permissible if this arises from changes in temperature ( see Permissible Environmental Conditions ). This does not however, apply when the devices are in operation. Always ensure that there is no moisture condensation in devices that are connected to the power supply

2.2. CONTROL PANEL TYPE DESIGNATION


The technical specification of the control panel is stated in the type code. Example D 078/01 where letter D corresponds to D-type lift control panel This code is also the same as is the code in the confirmation of order and other related papers. A Label with the type code is located at the bottom right corner of the control panel.

D-type manual

10

291 801 104

2.3 NAMEPLATE
Check that all the data stated in the nameplate enclosed with the control panel corresponds to what has been ordered.

SEC ELECTRONICS
Type ____________ S/N __________________ Input frequency __________ Brake _____________________ Valves ___________________

Input voltage ______________ Rated current _______________ Retiring cam ______________

Dimensions __________________________________________

Type S/N Input voltage Input frequency Rated current Brake Retiring cam Valves Dimensions

- control panel model - serial number ( type code) - power supply voltage - power supply frequency - output rated current - rated voltage of brake ( in electric lift) - rated voltage of retiring cam - rated voltage of valves ( in hydraulic lift) - dimensions of control panel H x W x D

Nameplate is located in the left side of the box door.

D-type manual

11

291 801 104

2.4.

STANDARD SPECIFICATIONS
Ta Ambient temperature Installation location Degree of protection Installation altitude Temperature operation 0 +50 oC -20 +55 oC -20 +70 oC 5% to 85% 1 g/m3 to 25 g/m3 without moisture condensation or icing Class 3K3 as per EN50178 5% to 95% 1 g/m3 to 29 g/m3 Class 1K3 as per EN50178 95% 60 g/m3 greatest absolute air humidity if the device is brought suddenly from 70 to 15 oC A light condensation of moisture may occur for a short time occasionally if the device is not in operation ( Class 2K3 as per EN50178) 86 to 106 kPa (Class 3K3 as per EN50178) 86 to 106 kPa (Class 1K4 as per EN50178) 70 to 106 kPa (Class 2K3 as per EN50178) IEC 68-2 Part 2 and 3 EN50178 IEC68-2 Part 6 EN12015 and EN12016 (see chapter EMC Guidelines ) CE 0 +40 oC; 40 +50 oC with current derated to 0.8 rated output current Pollution degree 2 or better ( free from direct sunlight, vibration, dust, corrosive or inflammable gases, fog, vapor oil and dripped water, avoid saline environment) IP 44 Up to 1000 m above the sea level; for higher altitudes a current reduction of 1,2% for every 100 m of additional height applies

ENVIRONMENT

storage transport Air humidity operation storage transport

Air pressure operation storage transport Climatic conditions STANDARD Clearance and creepage Vibration EMC compatibility Approvals

2.5. DISPOSAL OF THE DEVICE


SEC electronics will take back old units free of charge provided they are delivered carriage paid to the SEC electronic factory in Neverke, Slovenia Applicable local waste treatment and disposal regulations must be observed if you dispose of a unit yourself or replace any components. SEC electronics shall accept no liability for any parts and components that are not disposed of properly! The following details are useful for disposal purposes: the control panel box is made of steel, usually painted the back panel is made of steel or aluminum, usually without lacquering or surface treatment regulations on the disposal of electronic parts and components apply for disposal of p.c. boards, LCD units and other electric parts

D-type manual

12

291 801 104

3. INSTALLATION GUIDELINES
3.1. MECHANICAL SPECIFICATION

Control panel dimensions and fixing holes dimensions Doors can be left or right side opening. 700 x 500 x 200 500 700 200 450 650 107,5 285 107,5 40 30 10 CONTROL PANEL DIMENSIONS ( information on nameplate) 700 x 800 x 800 x 800 x 1000 x 1000 x 1000 x 500 x 600 x 600 x 600 x 600 x 600 x 600 x 250 200 250 300 250 300 350 500 600 600 600 600 600 600 700 800 800 800 1000 1000 1000 250 200 250 300 250 300 350 450 550 550 550 550 550 550 650 750 750 750 950 950 950 107,5 157,5 157,5 157,5 157,5 157,5 157,5 285 285 285 285 285 285 285 107,5 157,5 157,5 157,5 157,5 157,5 157,5 40 40 40 40 40 40 40 30 30 30 30 30 30 30 10 10 10 10 10 10 10 900 x 800 x 350 800 900 350 700 870 150 500 150 40 40 8

A B C D1 D2 E1 E2 E3 F1 F2 G fi

mm mm mm mm mm mm mm mm mm mm mm

NOTE:

In case when VVVF control panel is used, the braking resistor is mounted on the control panel. Dimensions of braking resistor depends on model, power and manufacturer. Braking resistor can be fixed at the side or at the top of the box.

D-type manual

13

291 801 104

3.2. INSTALLATION MOUNTING CLEARANCE


The dimensions specified in this manual and weights should be taken into consideration when the device is mounted. The technical equipment required ( carriage or crane for large weights) should be used. Improper handling and the use of unsuitable tools may cause damage.

NOTE:

NOTE: NOTE:

The maximum angle of inclination is 30o The control panels must be mounted in such a way that the free flow of air is ensured. The clearance to the device must be at least 150 mm. A space of at lease 50 mm must be ensured at the front. Devices that generate a large amount of heat must not be mounted in the direct vicinity of the control panel.

D-type manual

14

291 801 104

4. WIRING PROCEDURE
4.1. AC INPUT CONNECTION
The device must be connected to a protective grounding which will be the first to be connected and the last one to be disconnected. Flexible copper cables, class 5, type O5V-K must be used for mains connection of the device. These copper cables must be short circuit protected with external fuses. Thermomagnetic differential switches for protection can be used.

NOTE:

Residualcurrent ( FI-type) circuitbreakers can be tripped inadvertently when power is switched on if a noise filter is being used (VVVF and ACVV control panels). In these cases only use residualcurrent circuitbreakers with a drop-out delay.

Cable diameters and dimensions of protective switches must be consistent with table 4.4.4 for input voltage 400 V AC (415 V AC) or table 4.4.5 for input voltage 230 V AC (240 V AC).

INPUT VOLTAGE 400 VAC


P In Ci Cl S1 S2 S3 S4 kW A mm2 mm2 A A A A 3 8,6 2,5 2,5 16 25 16 25 4 10,5 2,5 2,5 16 25 16 25 5,5 13,5 4 2,5 20 25 16 25 7,5 17,5 6 2,5 25 40 16 25 10 20,5 6 2,5 32 40 16 25 11 24 10 2,5 32 40 16 25 15 32 16 2,5 40 63 16 25 18,5 39 16 2,5 50 63 16 25 22 46 25 2,5 63 80 16 25 25 54 25 2,5 80 100 16 25 30 62 35 2,5 80 100 16 25 37 72 50 2,5 100 125 16 25 45 87 50 2,5 125 160 16 25

INPUT VOLTAGE 230 VAC


P In Ci Cl S1 S2 S3 S4 kW A mm2 mm2 A A A A 3 13,5 4 2,5 20 25 16 25 4 16,5 4 2,5 20 25 16 25 5,5 22 6 2,5 32 40 16 25 7,5 29 10 2,5 40 63 16 25 10 37 16 2,5 63 63 16 25 11 41 25 2,5 63 80 16 25 15 54 25 2,5 80 100 16 25 18,5 66 35 2,5 100 125 16 25 22 77 50 2,5 100 125 16 25 25 87 50 2,5 125 160 16 25

P In Ci Cl S1 S2 S3 S4

rated power rated current diameter of wires for main supply (mm2) diameter of wires for lighting connection (mm2) thermomagnetic main switch curve type C (value is equivalent to short circuit current) differential main switch sensitivity 300 mA thermomagnetic switch lighting curve C differential switch lighting sensitivity 30 mA

D-type manual

15

291 801 104

4.2. MAIN MOTOR CONNECTION


Cable diameters must be consistent with table below for input voltage 400 V AC (415 V AC) or table below for input voltage 230 V AC (240 V AC).

INPUT VOLTAGE 400 VAC


P In Isd Cm Csd kW A A mm2 mm2 3 8,6 2,5 4 10,5 2,5 5,5 13,5 4 7,5 17,5 10 4 2,5 10 20,5 12 6 2,5 11 24 14 6 4 15 32 19 10 6 18,5 39 23 16 10 22 46 27 25 10 25 54 31 25 16 30 62 36 35 16 37 72 42 35 25 45 87 50 50 25

INPUT VOLTAGE 230 VAC


P In Isd Cm Csd P In Isd Cm Csd kW A A mm2 mm2 3 13,5 7,8 4 2,5 4 16,5 10 4 2,5 5,5 22 13 6 4 7,5 29 17 10 4 10 37 22 16 6 11 41 24 16 10 15 54 28 25 16 18,5 66 33 35 16 22 77 45 50 25 25 87 50 50 25

rated power rated current star / delta current diameter of wires for motor (mm2) diameter of wires for star delta connection (mm2)

D-type manual

16

291 801 104

5. PROGRAMMING WITH PROGRAMMER


The Programmer is specially made for programming D - type lift controllers. It does not need an external supply for operation. It will work the moment it is connected to the PRG socket of the controller board. After a short self diagnostic routine it will be ready for operation.

On the programmer you will find seven keys: READ WRITE PAGE UP PARAMETER UP PARAMETER DOWN VALUE UP VALUE DOWN And three separated displays for: LEFT MIDDLE RIGHT one digit display to display page number two digit display to display parameter number or error number two digit display to display parameter value or error code IT IS STRONGLY RECOMMENDED NOT TO CONNECT THE PROGRAMMER WHILE LIFT IS RUNNING! IT IS RECOMMENDED THAT THE PROGRAMMER BE DISCONNECTED WHEN PROGRAMMING OR MONITORING IS COMPLETE!

NOTE NOTE

D-type manual

17

291 801 104

The programmer will store all data in its internal non-volatile integrated circuit even after it is disconnected from the supply. The programmer can therefore be used to transfer data to another control panel. The data in the programmer is stored on six separate pages. The pages can be selected by pressing key PAGE UP

- page 1

PARAMETERS

For transfer of data from control panel to programmer, press key READ, with page 1 selected in page number display. Only data for page 1 will be transferred from control panel to programmer. On this page all parameters for adjusting the lift are stored. On the two digit display parameters we can see parameter number. On the two-digit display value we will see parameter's value. To move between parameters, press keys PARAMETER UP and PARAMETER DOWN.

D-type manual

18

291 801 104

To change the value of each parameter press keys, VALUE UP or VALUE DOWN. To transfer data for page 1 from programmer to control panel press keys: first WRITE and than PAGE UP at the same time. Transfer will be made only if maintenance drive (input 69) is active. All data for page 1 will be transferred.

- page 2

INPUT STAGES DEFINITION

To transfer data from control panel to programmer, press key READ, with page 2 selected in the page number display. Only data for page 2 will be transferred from the control panel to programmer. On this page the functional inputs stages are set as N/O or N/C. On the two digit display parameters we can see the number of input. On the two digit display value we will see its state. Setting 0 gives a normally open input and setting 1 gives a normally closed input.

D-type manual

19

291 801 104

The stage is changed with keys VALUE UP or VALUE DOWN. The input number is changed with keys PARAMETER UP and PARAMETER DOWN. To transfer data for page 2 from programmer to control panel press keys: first WRITE and than PAGE UP at the same time. Transfer will be made only if maintenance drive (input 69) is active. All data for page 2 will be transferred.

- page 4

LAST EVENTS CONTROL TABLE

To transfer data from control panel to programmer, use the key, READ, with page 4 selected in the page number display. Only data for page 4 will be transferred from control panel to programmer. On transfer the last ten events will be transferred from the control panel to the programmer. The serial number of events will be displayed on the two digit display of parameters. The last event has serial number 10 and previous events count down to serial number 1. To move between events press keys PARAMETER UP or PARAMETER DOWN. On two-digit display of value we have the code of each event. We can convert the code to the corresponding event with the coding table found in chapter 4.

D-type manual

20

291 801 104

By pressing VALUE UP OR VALUE DOWN we see on the two digit display the value corresponding to the floor where the event occurred.

- page 5

ERROR TABLE

To transfer data from the control panel to the programmer, we must press key READ, with page 5 selected in the page number display. Only data for page 5 will be transferred from control panel to programmer. The complete error table will be transferred from the control panel to the programmer. The maximum number of errors in the error table is 80. On the two-digit display of parameters we see the serial number of the error. After transfer the last number of the error in the error table will be displayed. We can view previous errors by pressing keys PARAMETER UP or PARAMETER DOWN. On two digit display of value we can see the code of the error. We can convert the code to the error by using the error-coding table in chapter 5.

D-type manual

21

291 801 104

By pressing VALUE UP OR VALUE DOWN we see on the two digit display the value corresponding to the floor where the error occurred.

To clear the error table press keys: first WRITE and than PAGE UP at the same time. Error table in programmer and in control panel will be cleared.

D-type manual

22

291 801 104

- page 6

POSITION AND TRAVEL OF LIFT

Page 6 monitors the position, direction and speed of the lift. The programmer, once connected will automatically start at page 6. On the two digit display of parameters we can see the position of the lift within the shaft. On the two digit display we can see the direction and speed of the lift as shown below: - display is empty = Lift is stood at a floor

- one bar in lower display =

Lift is in slow speed down

- two bars in lower display =

Lift is in fast speed down

- one bar in upper display =

Lift is in slow speed up

- two bars in upper display =

Lift is in fast speed up

Data is transferred from control panel to programmer in periods of one second.

If communication between programmer and control panel not work, Err sign will appear

NOTE

CONTROLLER MUST BE IN MAINTENANCE OPERATION TO EXECUTE WRITING DATA FROM PROGRAMMER TO CONTROLLER.

D-type manual

23

291 801 104

5.1. PAGE 1
01 OPEN DOOR TIME

PARAMETERS
1 - 60 sec. 1 - 60 sec. 1 - 90 sec.

Time in which doors will remain open at a floor

02 EXTEND OPEN DOOR TIME 03 HOLD DOOR TIME

Additional time which will add to open door time (01) when input Photocell (input 76) is activated

Timer is active when we use door type 5 or 8 (parameter 48). In this case after the timed period the outputs for doors will cancel as long as the lift stays at the floor. If timer is set on value 1 then antivandal is not in function.

04 CLOSING DOOR TIME

1 - 60 sec.

Time in which the doors must close - input 305 must be active. If input is not active when timer comes to zero, the doors will open again. After three attempts without a result the timer 07 (door error) will activate, then after this time there will be one attempt to close the doors. Also the error will be logged in the error table

05 SECURITY LOCK TIME

1 - 20 sec.

Time in which locks must be made after closing doors. Input 306 must be active. If the input is not active when the timer comes to zero, the doors will open again. After three attempts without a result the timer 07 (door error) will activate, and after this time there will be one attempt to close and lock the doors. Also the error will be logged in the error table.

06 EXCHANGE CLOSE OPEN TIME 07 DOOR ERROR TIME

0.1 - 9.0 sec. 1 - 10 min.

Time delay between close relay de-energizing and open relay energizing.

Time which will start after 3 errors in doors closing or locking. Also all commands will be cleared when this is active.

08 PARKING TIME 1,

1 - 60 min.

Time after which the lift will go to the parking floor 1 if there is no landing or car calls. Parking floor 1 is defined in parameter 51.

09 PARKING TIME 2,

1 - 60 min.

Time after which the lift will go to parking station 2 if there is no landing or car calls. Parking station 2 is defined in parameter 52. Parking station 2 has priority over parking station 1. This parking station is normally used for lowering hydraulic lifts to the lowest station after 15 minutes without calls.

10 DIRECTION HOLD TIME

1 - 20 sec.

Time in which the output for the direction is still present after arrival at the floor. (outputs 131 and 132). Also the lift will continue to travel in this direction if a call is active in the same direction when time comes to zero..

11 ARRIVAL GONG TIME


Timer for output arrival at floor - gong ( output 122 )

1 - 20 sec.

D-type manual

24

291 801 104

12 CAR EXTRACTION FAN TIME

1 - 90 sec.

Timer to define how long the output for the car extraction fan (relay RE9 outputs 419,420) remains on after the end of travel. If this timer is set to 90 the DEMONSTRATION DRIVE option is active. This mean that computer generate random calls to keep lift running. To disable this function this parameter must be programmed to some other value.

13 STAR DELTA TIMER

0 - 20 sec.

Timer for the pump change-over in star delta connection. On starting, outputs (relay RE4 terminals 407,408) and (relay RE6 terminals 410,411) are activated. After the star delta timer output (relay RE6) goes off and output (relay RE5 terminals 413,414) goes on.

14 PUMP OR VALVES DELAY TIME

0.0 - 9.9 sec.

Timer defining the delay of outputs for the pump or valves after the end of travel in up direction on hydraulic lifts. Selection between pump or valves is made with parameter 30 (settings 2 or 4 ).

15 SWITCH DE-BOUNCE TIME

0.0 - 9.0 sec.

Timer to eliminate double counting because of bad contacts on the switches for counting and positioning. This timer is active on inputs 61, 62, 63, 64, 65 and 66. After changing the state of these inputs the input is enabled for the period of this timer. The timer runs for each input independently.

16 STABILIZATION TIME

0.0 - 9.0 sec.

Timer starts after the end of travel. In the period of this timer all activities are disabled. After this time expires the next stage starts (opening doors, drive with fast or slow speed etc. )

17 TRAVEL TIME - FAST SPEED

0 - 450 sec.

Security timer. Timer runs when the lift is in fast speed. When the lift reaches switch for stop in station the timer runs again. The lift must reach next station or stop before this timer reaches zero. If the timer reaches zero during fast speed all outputs are disabled. Reset is only possible by switching the power off and back on after a few seconds. Unit of setting is 5 seconds per unit. (1 = 5 sec., 2 = 10 sec. etc). Timer is disabled when it is set to 00.

18 TRAVEL TIME - SLOW SPEED

0 - 450 sec.

Security timer. Timer runs when the lift is in slow speed. The lift must stop before this timer reaches zero. If the timer reaches zero during slow speed all outputs are disabled . Reset is only possible by switching the power off and back on after a few seconds Unit of setting is 5 seconds per unit. (1 = 5 secs, 2 = 10 secs etc)) Timer is disabled when it is set to 00.

19 TRAVEL TIME MAINTENANCE

0 - 450 sec.

Security timer. Timer runs when the lift is driven on maintenance. The lift must stop before this timer reaches zero. If the timer reaches zero during maintenance drive all outputs are disabled. Reset is only possible by switching the power off and back on after a few seconds Unit of setting is 5 second. ( 1 = 5 secs, 2 = 10 secs etc) Timer is disabled when it is set to 00..

30 LIFT TYPE
0 1 2 3 4 -

0-4

electric two speed - or one speed electric VVVF hydraulic type 1 - delay of pump on travel UP time of delay is defined in parameter14 (delay time) hydraulic type 2 - no delays hydraulic type 3 - delay of valves on travel UP time of delay is defined in parameter14 (delay time)

D-type manual

25

291 801 104

31 OPERATION SYSTEM
1 - up and down collective two buttons - max. 6 floors
1-6 2-6 1-5 cabin call; inputs: 81,82,83,84,85,86 call down; inputs: 87,88,89,90,91 call up; inputs: 92,93,94,95,96

1-9

2 down collective only single button- max. 8 floors


1-8 1 2-8 cabin call; inputs: 81,82,83,84,85,86,87,88 call up; input: 89 call down; inputs: 90,91,92,93,94,95,96

3 down collective all floors + 2 floors up and down, single button 8 stops max
1-8 1 2 3-8 cabin call; inputs: 81,82,83,84,85,86,87,88 call up; input: 89 call up and down; input: 90 call down; inputs: 91,92,93,94,95,96

4 up and down collective two buttons - max. 11 floors


1 - 11 cabin and floor call; inputs: 81,82,83,84,85,86,87,88,89,90,91,92,93,94,95 supply for cabin up and down calls 141, 142, 143, 144 NOTE additional board D-switch is required

5 down collective all floors , single button 9 stops max.


1-9 2-8 cabin call; inputs: 81,82,83,84,85,86,87,88,89 call down; inputs: 90,91,92,93,94,95,96 NOTE calls in stations 1 and 9 are connected together in floor and car

6 down collective all floors - max. 15 floors

1 - 15 cabin and floor call; inputs: 81,82,83,84,85,86,87,88,89,90,91,92,93,94,95 supply for cabin calls 141, 142supplies for down calls 143, 144 NOTE additional board D-switch is required

7 - APB - only 1 call at any one time - max. 16 floors


1 - 16 cabin and floor call on same input; inputs: 81,82,83,84,85,86,87,88,89,90,91,92,93,94,95,96.

8 APB simple operation max. 16 floors


1 16 cabin and floor call on the same input; inputs: 81,82,83,84,85,86,87,88,89,90,91,92,93,94,95,96

9 up collective max. 8 floors


18 18

cabine call; inputs: 81,82,83,84,85,86,87,88 call up (upper station call down); inputs: 89,90,91,92,93,94,95,96

32 COUNTING SYSTEM
1 - 4 switches
stop up input 61 stop down input 62 slow speed up input 65 slow speed down input 66

0-8

2 1 switch
stop and slow speed input 61

D-type manual

26

291 801 104

3 - 3 switches - relevelling possible with closed doors ( NOT FOR USE IN EU )


stop up and down inputs 61,62,64 slow speed input 65

4 - 3 switches
stop up input 61 stop down input 62 slow speed input 65

5 - 2 switches
stop up and down input 61 slow speed input 65

6 - 6 switches - tip 1 + zone A and zone B


zone A input 61 zone B input 62 relevelling down input 63 relevelling up input 64 slow speed up input 65 slow speed down input 66

7 - 5 switches - tip 4 + zone A and zone B


zone A input 61 zone B input 62 relevelling down input 63 relevelling up input 64 slow speed input 65

8 - 5 switches - tip 5 + zone A and zone B


zone A input 61 zone B input 62 relevelling down input 63 relevelling up input 64 slow speed up input 65.

33 NUMBER OF FLOORS

2 - 16

Defines the number of floors for the lift. Change of value will be valid only after restart of CPU (power off and on)

34 DOOR OPEN IN FLOOR 1 no/yes 35 DOOR OPEN IN FLOOR 2 no/yes 36 DOOR OPEN IN FLOOR 3 no/yes 37 DOOR OPEN IN FLOOR 4 no/yes 38 DOOR OPEN IN FLOOR 5 no/yes 39 DOOR OPEN IN FLOOR 6 no/yes 40 DOOR OPEN IN FLOOR 7 no/yes 41 DOOR OPEN IN FLOOR 8 no/yes

01 01 01 01 01 01 01 01

D-type manual

27

291 801 104

42 ARRIVAL (GONG) OUTPUT TYPE


1 starts on change down to slow speed

1-4

output 122 is activated when the lift changes speed from fast to slow. Length of time is defined in parameter 11

2 - starts when lift stops at floor level


output 122 is activa ted when lift has stopped at floor level Length of time is defined in parameter 11

3 - starts in slow speed but only active if floor call present

output 122 is activated when lift changes speed from fast to slow but only if the landing call is active at the current floor. Length of time is defined in parameter 11

4 - starts when lift has stopped at floor and has active floor call

output 122 is activated when lift arrives at floor level but only if the landing call is active at that floor. Length of time is defined with parameter 11

43 DIRECTION INDICATOR OUTPUT TYPE


1 when lift running + direction hold time
output for direction (131 or 132) is active during all drive time (fast and slow speed) and during direction hold time (parameter 10) .

1-4

2 when lift running only

output for direction (131 or 132) is active during all drive time (fast and slow speed)

3 when lift is in slow speed and waiting at floor

output for direction (131 or 132) is active when lift is in slow speed and when waiting at a floor. When the lift is waiting at a floor without calls both outputs (131 and 132) are activated

4 when lift is waiting at a floor

output for direction (131 or 132) is active when lift is waiting at a floor. When lift is waiting at a floor without calls both outputs (131 and 132) are activated

44 DOORS IN FIRE ALARM open / close

10

Definition for doors when fire alarm input (input 307) is activated. Input for fire alarm is defined as on when the remote alarm contact is closed. Conversion to a normally closed contact is not possible. When lift came into fire station doors are opened and closed. Doors can be opened with cabin call, landing call or door open buttons. If the parameter value is 1 doors in fire station stays open.

45 OUTPUT FROM FIRE ALARM


0 Lift works normally after end of fire alarm
After input (307 - fire alarm) goes off the lift resumes work normally

0-2

1 - Power off and on after end of fire alarm


After input (307 - fire alarm) goes off, restart of CPU is necessary for normal working (power off and power on again)

2 - maintenance on and maintenance off after fire alarm


After input (307 - fire alarm) goes off it is necessary for maintenance input (69) to be switched on and off for normal working to be resumed

D-type manual

28

291 801 104

46 FIREMAN DRIVE no / yes


0 - fireman drive is disabled

0-1

1 - when the lift is on firemans mode, (input 307 is on) and input 73 (priority drive) is activated, firemans use is possible. In this stage only cabin calls are in use. If the input for firemans drive goes off the lift will return to the fire alarm station. Additional controller operation in EN81-72 norm: If maintenance mode is present on fire alarm , output 121 cabin overload is blinking with 0,5Hz frequency. Input for photocell (terminal 74) is not active doors are closing. - If the fireman drive and fire alarm are present doors are closing after two minutes regardless to input obstruction door (terminal 76). At the same time output 121 (buzzer) and 108 (door slow speed) are activated.

WARNING!
Output 108 (door slow speed) it can be used only when is not used for output position. When it can not be used we must assure correct door opening with additional reley logic.

47 STOP SWITCH FAULT WHEN STOPPED AT FLOOR no / yes 0 - 1


0 - if the lift drops the input for the stop signal after it has stopped at a floor before the time of stabilization (parameter 16) The lift will continue to the next floor in the same direction in fast speed. 1 - if the lift drops the input for the stop signal after it has stopped at a floor before the time of stabilization (parameter 16) The lift is reversed back to previous floor in slow speed in the opposite direction

48 DOOR TYPE
1 - photocell / semiautomatic NOTE: NOT FOR USE IN THE EU

1-8

photocell is connected between inputs 304 and 305. Doors locks are connected in series between inputs 305 and 306. The output relay RE7 drives the retiring cam

2 - manual / semi-automatic - input priority drive is on when the car is empty NOT FOR USE IN THE EU
photocell is connected between inputs 304 and 305. doors locks are connected in series between inputs 305 and 306. The output relay RE7 drives retiring cam. Input 73 - priority drive becomes on, with car empty. If the car is empty the lift will respond to a floor call even if the car door is not closed

3 - folding ( bus ) / semi-automatic

car door contact is connected between inputs 304 and 305 series connected switches of landing doors are connected between inputs 305 and 306. Outputs RE7 and RE8 drives opening and closing of car door. Car door will remain open when the lift is waiting at floors

4 - automatic / semi-automatic

car door contact is connected between inputs 304 and 305 series connected switches of landing doors are connected between inputs 305 and 306. Outputs RE7 and RE8 drive opening and closing of car door. Car door remains open when lift is waiting at a floor

D-type manual

29

291 801 104

5 - automatic doors without limit switches / semi-automatic


car door contact is connected between inputs 304 and 305 series connected switches of landing doors are connected between inputs 305 and 306. Outputs RE7 and RE8 drive opening and closing of car door. Car door remains open when lift is waiting at floor. When lift is waiting at floor after time defined with parameter 03, output RE8 for open door goes off

6 - automatic / automatic
car door contact is connected between inputs 304 and 305 series connected switches of landing doors are connected between inputs 305 and 306. Outputs RE7 and RE8 drives opening and closing of car door. Car door parks closed when lift is waiting at floor..

7 - automatic / automatic - waiting with open door NOTE: NOT FOR USE IN THE EU

car door switch is connected between inputs 304 and 305 series connected switches of landing doors are connected between inputs 305 and 306. Outputs RE7 and RE8 drive opening and closing of car door. Car door remains open when lift is waiting at floor.

8 - automatic doors without limit switches / automatic

car door switch is connected between inputs 304 and 305 series connected switches of landing doors are connected between inputs 305 and 306. Outputs RE7 and RE8 drive opening and closing of car door. Car door is parked closed when lift is waiting at floor. Park time defined with parameter 03 output RE8 for open door goes off

49 PRE-OPENING OF DOOR

0-2

0 - disabled 1 - reserved 2 - when relevelling switches + zone A and zone B are on pre-opening is activated when the lift approaches in slow speed to floor and the three inputs below are activated: when traveling up when traveling down 63 relevelling down 64 relevelling up 61 zone A 61 zone A 62 zone B 62 zone B

50 SPEED ON MAINTENANCE slow / fast 51 PARKING STATION 1

1-2 0-1

Definition of parking station 1. If input value is 0 parking 1 is disabled. Time without calls needed before parking 1 is defined with parameter 08

52 PARKING STATION 2

0-1

Definition of parking station 2. If input value is 0 parking 2 is disabled. Time without calls needed before parking 2 is defined with parameter 09

53 FIRE ALARM STATION

1 - 15

Defines fire alarm floor. Setting 0 is not possible. Lift goes to fire alarm floor when input for fire alarm (input 307) becomes active.

D-type manual

30

291 801 104

54 POSITION INDICATOR TYPE


0 - decimal type - 1 output per floor
In this version the outputs below are used as position outputs: 1. floor output 101 2. floor output 102 3. floor output 103 4. floor output 104 5. floor output 105 6. floor output 106 7. floor output 107 8. floor output 108 + output 101, if there is more then 8 floors 9. floor output 108 + izhod 102 10. floor output 108 + output 103 11. floor output 108 + output 104 12. floor output 108 + output 105

1-6

1 - binary type 1=A, 2=B, 3=C, 4=D


In this version the outputs below are used as position outputs: A output 101 B output 102 C output 103 D output 104 Combination for floors is as follows: A 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 B 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 C 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 D 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 Floor 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

D-type manual

31

291 801 104

2 - binary type 1=A, 2=B, 3=C, 4=D


In this version the outputs below are used as position outputs: A output 101 B output 102 C output 103 D output 104 E output 105 A 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 B 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 C 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 D 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 E 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Floor 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16.

36

7 segment direct type

In this versions the segments below are used as position outputs:

101 = 1-a 102 = 2-b 103 = 3-c 104 = 4-d 105 = 5-e 106 = 6-f 107 = 7-g 108 = parameter value 3 or 4 = 7-g; 108 = parameter value 5 or 6 = 2-b and 3-c

3 station numbers: 4 station numbers: 5 station numbers: 6 station numbers:

-2,-1,0,1,2,3,4,5,6,7,8,9 -1,0,1,2,3,4,5,6,7,8,9 0,1,2,3,4,5,6,7,8,9,10,11,12,13,14,15 1,2,3,4,5,6,7,8,9,10,11,12,13,14,15,16

D-type manual

32

291 801 104

5.2. PAGE 2

INPUT STAGES DEFINITION

61 INPUT 61 STOP UP ( ZONE A ) NO / NC ( 0 - 1 ) 62 INPUT 62 STOP DOWN ( ZONE B ) NO / NC ( 0 - 1 ) 63 INPUT 63 SLOW UP - RELEVELLING UP NO / NC ( 0 - 1 ) 64 INPUT 64 SLOW DOWN - RELEVELLING DOWN NO / NC ( 0 - 1 ) 65 INPUT 65 SLOW UP NO / NC ( 0 - 1 ) 66 INPUT 66 SLOW DOWN NO / NC ( 0 - 1 ) 67 INPUT 67 CABIN FULL LOAD NO / NC ( 0 - 1 ) 68 INPUT 68 CABIN OVERLOAD NO / NC ( 0 - 1 ) 69 INPUT 69 MAINTENANCE ON NO / NC ( 0 - 1 ) 70 INPUT 70 MAINTENANCE UP NO / NC ( 0 - 1 ) 71 INPUT 71 MAINTENANCE DOWN NO / NC ( 0 - 1 ) 72 INPUT 72 DOOR CLOSING BUTTON NO / NC ( 0 - 1 ) 73 INPUT 73 PRIORITY DRIVE NO / NC ( 0 - 1 ) 74 INPUT 74 DOOR PHOTOCELL NO / NC ( 0 - 1 ) 75 INPUT 75 DOOR OPENING BUTTON NO / NC ( 0 - 1 ) 76 INPUT 76 DOOR OBSTRUCTION NO / NC ( 0 - 1 ) 81 FIRE AND FIREFIGHTERS DRIVE EU standard / Australian standard ( 0 1 ) 82 DOOR OPENING OUT OF STATION (first drive) no / yes ( 0 - 1 ) 83 RESERVED 84 RESERVED 85 RESERVED 86 RESERVED 87 RESERVED 88 RESERVED 89 RESERVED 90 RESERVED 91 RESERVED 92 RESERVED 93 RESERVED 94 RESERVED 95 RESERVED 96 RESERVED

D-type manual

33

291 801 104

5.3. PAGE 4
List of event codes: 50 Door open 51 Door preliminary open 52 Door close 53 Door lock 54 Error in closing door cycle 55 Fast speed up 56 Slow speed up 57 Stabilization after drive cycle 58 Fast speed down 59 Slow speed down 60 Fireman's drive 61 Maintenance drive 62 Parking drive 63 Waiting for call 65 Safety circuit missing in terminal 36 66 Door is not locked 67 Travel timer fast speed 68 Travel timer slow speed 69 Travel timer maintenance speed 70 Car overload 71 Thermal protection is activated 72 Relevelling up 73 Relevelling down 74 Error in elements check 75 Lift hold 76 Priority drive. 77 Door photocell 79 Maintenance drive down 80 Maintenance drive up 81 Hydraulic pump star 82 Error in door 83 Slip correction up 84 Slip correction down 85 Fireman's drive 86 Car door is not closed 87 Landing door is not closed 88 Error in parameters 89 Slow speed limiter 91 Error in re-levelling cycle 92 Door jammed error 94 Error fast speed limit switches 95 Error first drive 96 Error safety 36

LAST EVENTS CONTROL TABLE

D-type manual

34

291 801 104

5.4. PAGE 5

ERROR TABLE

Errors in error table explanation and solutions:

01 Second slip correction


Lift has tried to correct slip from floor after stopping two times unsuccessfully - error in mechanical brake in electric lift - brake in electric lift or valves in hydraulic switched off too late - zone for stop magnet in station is too short - slow speed is too fast (hydraulic or VVVF) - error on elements for slow speed (lift attempts to stop in fast speed)

02 First slip correction


Lift has tried to correct slip from floor after stopping. First correction fails, second one passes - error in mechanical brake in electric lift - brake in electric lift or valves in hydraulic switched off too late - zone for switch stop in station is too short - slow speed is too fast (hydraulic or VVVF) - error on elements for slow speed (lift attempts to stop in fast speed)

03 Error in counting
Lift approaches bottom or top floor with wrong position number - error in limit switch for fast speed at bottom (input 301) switch must be off when in zone for slow speed at bottom floor - error in limit switch for fast speed at top (input 302) switch must be off when in zone for slow speed at top floor - error on supply voltage for limit switches for fast speed - magnet to activate bi-stable limit switch for fast speed is too close to switch or wrong polarity (this can cause two pulses) - number of floors defined in parameter 33 is not correct.

04 Error on pre-opening
Error in Lift pre-opening cycle - one of three conditional inputs failed during pre-opening- or opening in drive up inputs: 63 relevelling down, 61 zone A, 62 zone B in drive down inputs: 64 relevelling up, 61 zone A, 62 zone B - wrong position of switches or magnets - error on safety circuit 185 for pre-opening-opening and relevelling with open door - error on elements for slow speed - pre-opening-opening in fast speed

05 Error on car door


Error while closing car door - error on car door contact - when door is closed input 304 and 305 must be activated - error on motor or elements for drive motor for car door - time in parameter 04 (closing door time) is too short timer comes to zero before door is closed - error in power supply for car door contact

07 Error on door locks


Error while locking landing doors (after closing car door) - error in switches on landing doors when doors are locked inputs 304, 305, and 306 must be activated - time in parameter 05 (security lock time) is too short timer comes to zero before doors are locked - error in power supply for locks switches

D-type manual

35

291 801 104

09 Error on switch for stop up


Error on input 61 - stop up - error on switch or on magnet - error on other switches for stop or slow speed - when using bi-stable magnetic switch - magnet is too close to switch ( two pulses) - error on power supply for switches

10 Error on switch for slow speed up


Error on input 65 - slow speed up - error on switch or on magnet - error on other switches for stop or slow speed - when using bi-stable magnetic switch - magnet is too close to switch ( two pulses) - error on power supply for switches

11 Error on switch for stop down


Error on input 62 - stop down - error on switch or on magnet - error on other switches for stop or slow speed - when using bi-stable magnetic switch - magnet is too close to switch ( two pulses) - error on power supply for switches.

12 Error on switch for slow speed down


Error on input 66 - slow speed down - error on switch or on magnet - error on other switches for stop or slow speed - when using bi-stable magnetic switch - magnet is too close to switch (two pulses) - error on power supply for switches

14 Error on input 308 - elements check


Input 308 was off more than 5 seconds when lift was waiting at floor - one of contractor or relays was not released after end of drive K1, K2, K3, K4, K6, K7, K9, K31, K32, K33, R11, R12, R13, R17 - error on security circuit 185 when elevator stopped at floor - error on external element for temperature check connected to inputs 381, 382 - motor overheating - controller for thermistors TH1 detected overheat - error on controller for thermistors TH1 or phase sequence controller - error on control voltage on controller

15 Error travel timer fast speed


Error on security timer for fast speed - timer reaches zero before lift changes speed or stops at floor - error with ropes or oil pressure - error on elements for drive ( contractor, relays, valves ) - timer setting is to short

16 Error travel timer slow speed


Error on security timer for slow speed - timer reaches zero before lift changes speed or stops at floor - error with ropes or oil pressure - error on elements for drive ( contractor, relays, valves ) - timer setting is to short

D-type manual

36

291 801 104

17 Error travel timer maintenance speed


Error with security timer for maintenance speed - timer reaches zero before lift changes speed or stops at floor - error with ropes or oil pressure - error on elements for drive ( contractor, relays, valves ) - timer setting is to short

19 Error in parameters
Error in parameters in memory circuit on PCB - error because parameters in memory circuit changed incorrectly check all parameters - value in one or more parameters is not within the limits - error with memory circuit on PCB.

NOTE

In this case all parameters ( page 1 ) and Input definitions ( page 2 ) must be read to the programmer, check if they are good, and write to the control panel again. After this switch the power of control panel off and on again

20 Error on limit switches for fast speed


Limit switches for fast speed both off at the same time - error on bottom limit switch for fast speed (input 301) switch must be off when in zone for slow speed at bottom floor - error on top limit switch for fast speed (input 302) switch must be off when in zone of slow speed for top floor - error with power supply for limit switches

22 Error while relevelling


While relevelling one o f the inputs 61 o r 62 (zone A or zone B) goes off - while relevelling one of the inputs 61 or 62 (zone A o r zone B) goes off - error on switches or magnets - error on elements for drive (contractor, relays, valves) - elevator has relevelled more than 10 times in a period of 2 minutes - error on safety circuit 185 for relevelling and pre-opening-opening

23 Error on door photocell input


Input 74 door photocell was activated more than 1 minute Lift runs on without checking input 74 door photocell - error on photocell connected to input 74 - error on definition of input (NO / NC) with parameter 74 - error on power supply for photocell connected to input 74

25 Error first drive


Error in lift first drive at restart. - error on prelimit switches - error on stop switches - error on power supply

29 Error security 36
Continuous errors (more than 5 in one minute) on security 36 (terminal 303) - bad connection or interrupted safety line - continuous disconnections of high pressure safety on hydraulic

D-type manual

37

291 801 104

5.5. PRESETING AND FACTORY RESET


Parameter preseting is made during the production process and it depens of customer order. With that parameters is also made complete testing. Preset parameters are placed on the last page of instructions. There is also place made where installer can write parameters which he will change during the instalation.

WARNING
SEC ELECTRONICS is not responsible for all additional parameter changing, which would be made from non authorizated person and could bring to controller or person damage. FACTORY RESET can be made when the power is ON and the controller is in maintenance mode (terminal 69). We must activate for 1 second, fire drive (terminal 307), maintenance up and maintenance down (terminals 70 and 71 ) at the same time. These function is possible only 10 seconds after the controller is powered ON (controller signal LED is ON ).

WARNING
When factory reset is made parameters are diferent as preset values. Is essential to made parameter correction. Look to the list of preset parameters or contact SEC ELECTRONICS!

WARNING
During the factory reset procedure it could came to uncontrollable controller activity so all controller outputs must be disconected.

D-type manual

38

291 801 104

6. PROGRAMMING WITH COMPUTER


6.1. CONNECTION TO PC
Programming with PC is possible through RS 232 line. The drawing of cable is:

Special program for programming D type control panel runs under Microsoft Excel c program. Normally, three files must be in CD with this program: 1. 2. 3. xxxxxx.xls the Microsoft Excel c file with running program xxxxxx.dll supporting dll file which support connection between program and computer serial port readme.txt with description where to install dll file and how to use program

Through programming with PC all features of programming with programmer are accessible and some more things.

6.2. PAGE 1 or PARAMETERS DEFINITION

Parameters
Parameter 01 Open door time 03 Hold door time 05 Lock door time 07 Door error time 08 Parking time 1 09 Parking time 2 11 Arrival gong time (* 1 - 60s *) (* 1 - 60s *) (* 1 - 20s *) (* 1 - 10min *) (* 1 - 60min *) (* 1 - 60min *) (* 1 - 20s *)
Factory value

Parameter 30 Lift type 31 System type 32 Copying system 34 Door open in 1. floor 35 Door open in 2. floor 36 Door open in 3. floor 37 Door open in 4. floor 38 Door open in 5. floor 39 Door open in 6. floor 40 Door open in 7. floor 41 Door open in 8. floor (* 0 - 4 *) (* 1 - 9 *) (* 1 - 8 *)

Factory value

3 1 1 10 10 0,5 1 1 2 2 5 20

0 1 4 6 1 1 1 1 1 1 1 1

02 Extend open door time (* 1 - 60s *) 04 Closing door time (* 1 - 60s *) 06 Exchange close/open (* 0,1 - 9,9s *)

33 Number of stations (* 2 - 6/8/11/1516 *)

10 Direction hold time (* 1 - 20s *) 12 Cabin blower time (* 1 - 90s *)

D-type manual

39

291 801 104

13 Star delta time 14 Pump delay time 15 Switch time 16 Stabilisation time

(* 0 - 20s *) (* 0,1 - 9,9s *) (* 0,0s - 9,9s *) (* 0,0 - 9,9s *)

1 1 1 1 300 300 0

42 Arrival output type 44 Doors in fire alarm 45 Ouput from fire alarm 46 Fireman drive 48 Door type 49 Preopening doors 50 Speed on maintenance 51 Parking station 1 52 Parking station 2 53 Fire alarm station 54 Output for position

(* 1 - 4 *) (*0 - 1*) (*0 - 2*) (*0 - 1*) (* 1 - 8 *) (* 0 - 2 *) (* 1 - 2 *) (* 0 - n *) (* 0 - n *) (* 1 - n *) (* 0 - 6 *)

1 1 0 0 0 1 6 0 1 0 0 1 0

43 Directions outputs type (* 1 - 4 *)

17 Flight time - fast speed (* 0 - 450s *) 18 Flight time - slow speed (* 0 - 450s *) 19 Flight time - maint. speed (* 0 - 450s *)

47 Relevel on arrival to floor (* 0 - 1 *)

Windows and Excel are trademarks of Microsoft Inc.

6.3. PAGE 2 or INPUTS DEFINITION

I / O type
Input logic (pos/neg=0/1) 61 Input 61 stop up 62 Input 62 stop down 63 Input 63 slow relevel up 64 Input 64 slow relevel down 65 Input 65 slow speed up 66 Input 66 slow speed down 67 Input 67 full load cabin 68 Input 68 overload cabin 69 Input 69 maintenance on 70 Input 70 maintenance up 71 Input 71 maintenance down 72 Input 72 door closing button 73 Input 73 priority drive 74 Input 74 door photocell 75 Input 75 door opening button 76 Input 76 door stuck
Factory value

Parameter 81 Fire and firefighter drive (0=EU, 1=AUS) 82 Doors open out of station 83 Reserved 84 Reserved 85 Reserved 86 Reserved 87 Reserved 88 Reserved 89 Reserved 90 Reserved 91 Reserved 92 Reserved 93 Reserved 94 Reserved 95 Reserved 96 Reserved

Factory value

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

D-type manual

40

291 801 104

6.4. PAGE 3 or ONLINE INPUTS AND OUTPUTS MONITORING

I / O status
Input Input stop up Input stop down Input relevel down Input relevel up Input slow speed up Input slow speed down Cabin full load Cabin overload Maintenance on Maintenance up Maintenance down Doors closing Priority drive Door photocell Door open button Door stuck End fast speed down End fast speed up Protections Land doors close Cabin doors close Doors locks close Fire drive Elements check state Output 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 0 1 Drive down Drive up Fast speed Pump delta Pump on Cabin blower Doors opening Pump star Doors closing Directions up Directions down Error Beep Gong state 0 1 1 1 1 1 0 0 1 1 0 0 0 0

Calls
UP button 16 15 14 13 12 11 10 9 0 0 0 0 0 0 0 0 call indicator 0 0 0 0 0 0 0 0 DOWN button 0 0 0 0 0 0 0 0 call indicator 0 0 0 0 0 0 0 0 CAR button 0 0 0 0 0 0 0 0 call indicator 0 0 0 0 0 0 0 0

D-type manual

41

291 801 104

8 7 6 5 4 3 2 1

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

6.5. PAGE 4 or LAST EVENTS TABLE

Last events
Message(FIFO) Waiting for call Doors close Doors open Waiting for call Stabilisation Slow speed down Fast speed down Doors lock Mes. nr. 63 52 50 63 57 59 58 53 Station 1 1 1 1 1 16 16 16 16

6.6. PAGE 5 or ERROR TABLE

Errors table
Error E4 Counting E4 Counting Error nr. 3 3 Station 3 1

NOTE

For programming with computer read also readme file on CD with program

D-type manual

42

291 801 104

7. ABBREVIATIONS
7.1. TERMINALS ON CONTROL PANEL
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 25a 26 26a 27 28 29 31 31a 32 33 34 35 35a 36 37 38 39 40 41 42 43 45 46 47 48 ground L1 input L2 input L3 input N input motor U1 motor V1 motor W1 motor U2 motor W2 motor V2 3F 400V (415V) AC 50 Hz (60 Hz)

main motor on electric elevator or pump motor on hydraulic elevator

L input phase for cabin light power for transformer door motor U1 door motor V1 door motor W1 door motor U1 door motor V1 door motor W1 DOOR A

DOOR B

blower motor U1 ( only on electric elevator ) blower motor V1 blower motor W1 blower in cabin 230V AC oil heater thermal switch for blower motor ( only on electric elevator ) thermal switch for blower motor brake ( only on electric elevator ) brake second terminal ( if brake voltage is not insulated with transformer) retiring cam ( only on semiautomatic door ) retiring cam second terminal ( if retiring cam voltage is not insulated with transformer) +48V fast speed limit switch down fast speed limit switch up safety circuit start safety circuit after stop in cabin safety circuit after stop maintenance safety circuit after rope malfunction switch safety circuit after overspeed brake switch safety circuit after stop in shaft switch safety circuit after end limit switch safety circuit after overspeed governor switch safety circuit after landing doors switches safety circuit after cabin door switch safety circuit after landing doors lock switches +48V open contact for door - common open contact for door - opening open contact for door - closing end switch door opening end switch door closing

D-type manual

43

291 801 104

51 52 56 57 58 59 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 101 102 103 104 105 106 107 108 121 122 123 131 132

zone A switch zone B switch solenoid valve down solenoid valve up solenoid valve fast speed down solenoid valve fast speed up stop up switch stop down switch relevelling down switch relevelling up switch slow speed up switch slow speed down switch cabin full load switch cabin overload maintenance drive on switch maintenance drive up switch maintenance drive down switch button force door closing priority drive switch door photocell switch button force door opening door obstruct ion switch 0V (ground) for cabin call buttons 0V (ground) for landing call buttons +24V for cabin call lamps +24V for landing call buttons cabin call 1 cabin call 2 cabin call 3 cabin call 4 cabin call 5 cabin call 6 cabin call 7 cabin call 8 landing call landing call landing call landing call landing call landing call landing call landing call output output output output output output output output

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

position position position position position position position position

output cabin overload output arrival to station - gong output out of work output direction down output direction up

D-type manual

44

291 801 104

221 222 276 276a 277 277a 351 352 538 360 371 372 383 384

serial indicator - ground serial indicator - data solenoid valve down - hydraulic BERINGER with module ELRV solenoid valve up - hydraulic BERINGER with module ELRV

switch for emergency lowering switch for emergency lowering output for emergency door opening solenoid valve for emergency lowering ( 12V DC ) output emergency alarm ( 12V DC ) output emergency light ( 12V DC ) thermistors in main motor or pump motor

7.2. ELEMENTS ON CONTROL PANEL


K1 K2 K3 K4 K6 K6A K18 K31 K32 K33 K20 K21 K22 K61 K62 K63 K64 R1 R2 R3 R4 R10 R11 R12 R13 R14 R17 R18 R30 R31 R32 R91 R92 R93 contactor UP contactor DOWN contactor FAST SPEED contactor SLOW SPEED contactor motor ( VVVF lift ) contactor motor ( VVVF lift ) contactor RETIRING CAM contactor PUMP STAR contactor PUMP ON contactor PUMP DELTA contactor motor BLOWER contactor door OPEN contactor door CLOSE contactor in safety circuit for relevelling and preopening contactor in safety circuit for relevelling and preopening contactor in safety circuit for relevelling and preopening contactor in safety circuit for relevelling and preopening safety relay on safety circuit 185 safety relay on safety circuit 185 safety relay on safety circuit 185 safety relay on safety circuit 185 relay light in car relay down relay up relay up and down relay safety after cabin door relay fast speed relay retiring cam relay emergency lowering relay emergency lowering relay emergency opening door relay down hydraulic BERINGER module ELRV relay up - hydraulic BERINGER module ELRV relay maintenance - hydraulic BERINGER module ELRV

Ver. 2.02

D-type manual

45

291 801 104

F1 F2 F4 F5 F6 F7 F8 F31 V1 V2 V3 V4 V9 RE1 RE2 RE3 RE4 RE5 RE6 RE7 RE8 RE9 RE10 RE12 RE11 RE13 RE14 RE18 RE17 RE22 RE16 RE15 RE21 RE19 RE20

fuse for electronic board Doppler LC 3F fuse for door motor fuse transformer fuse transformer fuse 24V fuse 48V fuse 230V AC for contactors 3F fuse for motor solenoid valve down solenoid valve up solenoid valve slow speed solenoid valve fast speed solenoid valve emergency lowering relay down relay up relay fast speed relay pump on relay pump delta relay pump star relay door close relay door open relay cabin blower relay position 1 relay position 2 relay position 3 relay position 4 relay position 5 relay position 6 relay position 7 relay position 8 relay cabin overload relay arrival to station - gong relay out of work relay direction up relay direction down

D-type manual

46

291 801 104

8. COUNTING SENSORS CONNECTION AND POSITION


D type control panels can work with 7 different counting sensor installations. Correct counting system is selected through programming with parameter 32 on page 1 ( see 9.1 page 68 ) All inputs for counting ( input 61, 62, 63, 64, 65 and 66) can be programmed as normally open or normally close inputs depending on switches used. Some notes for installation:

NOTE NOTE

bistable switches must be mounted correctly cable is on bottom side of switch There must be 10 mm space between magnet and switch for proper operation

NOTE

magnet must be mounted at 90 degree angle according to switch

NOTE

switches and magnets must not be mounted near to other metal parts ( bolts, brackets)

NOTE NOTE NOTE

magnets for bistable switches must be correctly oriented ( black white) first time bistable switches must be triggered manually ( by magnet ) prelimit switches described in this manual are bistable magnetic type which is not always acceptable especially for speeds up to 1 m/s where prelimit switches must be mechanical type ( as final limit switch ) final limit switch is not described in this manual but it is obligatory

NOTE

D-type manual

47

291 801 104

D-type manual

48

291 801 104

D-type manual

49

291 801 104

D-type manual

50

291 801 104

D-type manual

51

291 801 104

D-type manual

52

291 801 104

D-type manual

53

291 801 104

D-type manual

54

291 801 104

D-type manual

55

291 801 104

D-type manual

56

291 801 104

9. CONNECTION DURING INSTALLATION PHASE


WARNING ATTENTION This wiring is temporary wiring acceptable only during installation phase.
Wiring and use of lift systems under these conditions is permitted only for qualified personnel. Only qualified personnel may undertake the moving of the lift. After end of work, lift must be switched OFF. After installation phase, this temporary wiring must be removed, and replaced with normal and valid wiring system

WARNING ATTENTION Involved personnel must be made fully aware that when using this
wiring during installation phase, the only safety element for stopping lift is the stop button. No other device is connected to the system during this period.

WARNING ATTENTION All wire bridges for terminals short circuit connection must be removed
after the installation period and replaced with the valid wiring system.

WARNING ATTENTION This method for installation is not valid in all countries. In this case local
and national safety regulation must be considered.

9.1. POWER SUPPLY


Power supply must be applied to the control panel. In some version terminal Lc is used instead 11.

NOTE

After switch ON check phase sequence device. BOTH LED DIODES MUST LIT. If not, switch supply OFF and change wires between terminals 2 and 3 ( correct phase sequence)

9.2. MOTOR CONNECTION


Terminals for one speed motor ( hydraulic direct start, hydraulic soft start, electric one speed electric VVVF, electric ACVV )

D-type manual

57

291 801 104

Terminals for two speed motor ( electric two speed)

Terminals for one speed motor with 6 wires ( hydraulic star delta start)

9.3. MAINTENANCE AND SAFETY CONNECTION


If switch for maintenance drive is normally close ( parameter 69 is 1) connection is:

If switch for maintenance drive is normally open ( parameter 69 is 0) connection is:

NOTE

At hidraulic lift instalation we must also bridge terminals 30 and 30A (final limit switch). Prelimit and final limit switches are not connected in this case and therefore offer no protection from over travel of the lift car 58 291 801 104

WARNING ATTENTION

D-type manual

10. START UP
10.1. PRE POWER CHECKS
The following should be checked before switching ON the control panel: Grounds / Grounding Verify ground connections control panel to main motor and control panel to car Verify ground connections input to control panel Verify AC Input, AC Output and control wiring arent grounded Connections Verify Verify Verify Verify Verify AC Input connections main motor connections prelimit switches connections safety line connections stop in station switches connections ( ( ( ( ( 0, 1, 2, 3, 4, 11 ) 5, 6, 7, 8, 9, 10 ) 27, 28, 29 ) 31, 32, 33, 34, 34A, 35, 35A, 36, 37, 38, 39 ) 51, 52, 61, 62, 63, 64 )

Switch maintenance drive ON

( 69 )

WARNING On first switching on, the control panel must be in maintenance mode 10.2. VOLTAGE AND CONTROL ELEMENTS CHECK
After first switching on the control voltages in system: Measure 48V DC on terminal 40. Measured voltage must be in range between 40 and 50 V DC

NOTE

This voltage doesnt have smoothing capacitor

Measure 24V DC on terminal 80. Measured voltage must be in range between 16 and 23 V DC

NOTE

This voltage doesnt have smoothing capacitor

Measure 12V DC from accumulator charger on faston connectors by removing accumulator. Red faston connector is +12V DC and black one is ground. Measured voltage must be in range between 13 and 15 V DC

NOTE

When accumulator is applied this voltage goes down to 13 V DC

Check phase sequence device. BOTH LED DIODES MUST LIT. If not, switch supply OFF and change wires between terminals 2 and 3 ( correct phase sequence) Check PTC module ( thermistor control ). LED PTC OK must lit. If not, check thermistors and switches connected on terminals 281, 282, 283, 284.

D-type manual

59

291 801 104

10.3. MAINTENANCE MODE


Move the car upward by pressing maintenance up button ( terminal 70 ). Lift must stop on upper prelimit switch ( terminal 29 ) which means that this switch function normally. Check of upper prelimit switch is possible with LED FAST SPEED LIMIT SWITCH UP. This LED is ON when switch is ON. Move the car downward by pressing maintenance down button ( terminal 71 ). Lift must stop on lower prelimit switch ( terminal 28 ) which means that this switch function normally. Check of lower prelimit switch is possible with LED FAST SPEED LIMIT SWITCH DOWN. This LED is ON when switch is ON. Check the function of final limit switch ( bottom and top ). On maintenance mode door tests are possible: By pressing car call 1 ( terminal 81 ), doors will open By pressing car call 2 ( terminal 82 ). doors will close

WARNING Maintenance up button must move lift up. If lift goes down, change wires in main motor
connections. If a two speed motor is applied, the fast speed wires must be changed also.

WARNING In hydraulic lift check correct pump rotation. If pump runs in reverse change wires in
pump motor connections

10.4. NORMAL MODE


If lift works normally in maintenance mode, switch from maintenance mode to normal mode. If lower prelimit switch is ON: Lift will start down with fast speed. Lift will switch to slow speed when lower prelimit switch goes off. Lift will stop in station when stop down signal goes on. If lower prelimit switch is OFF: Lift will start up with fast speed. Lift will switch to slow speed when slow speed up signal will come. Lift will stop in station when stop up signal goes on. After lift comes to the station all functions work normally. Doors will open and lift is ready for operation.

NOTE

When lift is in station LED ELEMENTS CHECK must light. This LED checks the operation of relays, contactors, thermo switches and thermistors

All inputs can be controlled through LEDs. When LED is lit switch is closed.

WARNING ATTENTION

Prelimit and final limit switches are not connected in this case and therefore offer no protection from over travel of the lift car

D-type manual

60

291 801 104

NOTE NOTE

LED 5V DC indicate presence of internal voltage + 5V DC. Voltage can be incorrect because LED only indicates presence and not level of volts LED 24V DC indicate presence of voltage + 24V DC. Voltage can be incorrect because LED only indicate presence and not level of volts

D-type manual

61

291 801 104

10.5. TROUBLESHOOTING
LIFT WILL NOT OPERATE IN MAINTENANCE MODE check AC input voltage on terminals 1, 2 and 3, check AC input neutral on terminal 4, check AC input voltage on terminal 11 ( if exist) check proper operation of phase sequence and failure device. In normal operation both LEDs lit. check fuses and motor protection devices check low voltage in system: 48V DC on terminal 40 ( 40 50 VDC ) 24V DC on terminal 80 ( 16 23 VDC ) 5V DC LED in PCB 5V DC

check safety line on terminals 31, 36, 37, 38, 39 ( use first LEDs in PCB safety circuit 36, 37, 38 and 39 ). Measure also voltage in terminals 31, 36, 37, 38 and 39. Voltage range must be between 40 and 50 VDC. LEDs are only indicators for voltage presence but voltage can be too low. check prelimit switches on terminals 28 and 29 ( use first LEDs in PCB fast speed limit switch up and down ). Measure also voltage in terminals 28 and 29. Voltage range must be between 40 and 50 VDC. LEDs are only indicators for voltage presence but voltage can be too low. check if computer works by looking at LED error table indicator . LED must blink if computer works normally in maintenance mode check parameters and input definitions. ( see section PROGRAMMING ). Specially check parameters and definitions related to maintenance mode: parameter 50 speed on maintenance definition 69 input maintenance ON definition definition 70 input maintenance UP definition definition 71 input maintenance DOWN definition definition 81 input car call 1 definition ( door opening on maintenance mode) definition 82 input car call 2 definition ( door closing on maintenance mode) check action with programmer on page 6 (see section PROGRAMMING WITH PROGRAMMER ) if there is one or two bars up or down, computer works normally and problem is in power section

LIFT WILL NOT OPERATE IN MAINTENANCE DOWN DRIVE check action with programmer on page 6 (see section PROGRAMMING WITH PROGRAMMER ) if there is one or two bars down, computer works normally and problem is in power section: check motor, valves or brake connection check contactors and relays if there is no action in programmer check prelimit switch down ( terminal 28 ) LED fast speed limit switch down. Measure also voltage in terminal 28. Voltage range must be between 40 and 50 VDC. LEDs are only indicators for voltage presence but voltage can be too low.

D-type manual

62

291 801 104

LIFT WILL NOT OPERATE IN MAINTENANCE UP DRIVE check action with programmer on page 6 (see section PROGRAMMING WITH PROGRAMMER ) if there is one or two bars up, computer works normally and problem is in power section: check motor, valves or brake connection check contactors and relays if there is no action in programmer check prelimit switch up ( terminal 29 ) LED fast speed limit switch up. Measure also voltage in terminal 29. Voltage range must be between 40 and 50 VDC. LEDs are only indicators for voltage presence but voltage can be too low.

LIFT WILL NOT START IN NORMAL MODE check if lift operates normally in maintenance mode. Lift must operate normally in both directions in maintenance mode check LED error table indicator . LED must NOT blink. If LED is blinking some of the conditions are missing check door operation. Doors must close ( safety line 39 ). Check conditions which will prevent door closing: input 76 door obstruction signal input 74 door photocell signal input 75 button door opening check also related input definitions ( definitions 74, 75 and 76) (see section PROGRAMMING ) check conditions which prevent normal mode: input 68 input 73 input 307 check also related input definitions ( definitions car overload key priority drive fire drive input 68 and 73) (see section PROGRAMMING )

check action with programmer on page 6 (see section PROGRAMMING WITH PROGRAMMER ) if there are two bars , computer works normally and problem is in power section: check motor, valves or brake connection check contactors and relays ( especially for fast speed ) check parameters and definitions ( see section PROGRAMMING), use error table or last event table for help to find out reason for abnormal work. SUGGESTION: clear the error table ( see section PROGRAMMING PAGE 5 ) switch control panel off and after 30 seconds on again if lift does not start in normal operation look to the error table there must be at least one error which caused this situation if error table is still empty use last events table to find out the reason by looking at last event in lift ( see section PROGRAMMING - PAGE 4 )

D-type manual

63

291 801 104

LIFT WILL NOT STOP IN STATION FIRST TIME AFTER POWER ON check stop in station signals ( terminals 51, 52, 61, 62, 63, 64 ) Measure also voltage in these terminals. Voltage range must be between 40 and 50 VDC. LEDs are only indicators for voltage presence but voltage can be too low. check appropriate input definitions for these inputs ( definitions 61, 62, 63, 64 )

LIFT STOPPED IN STATION AFTER FIRST TIME BUT WILL NOT ACCEPT CALLS check ELEMENTS CHECK input ( terminal 308 ). LED for this input must lit when lift is in station check FIRE DRIVE input ( terminal 307 ). LED for this input must NOT be lit when lift is in station check safety circuit 185, LED safety OK must lit, if not the device or zone switches are not working properly, see section SAFETY CIRCUIT 185

LIFT COUNTS TWO FLOORS INSTEAD ONE check operation of magnetic switches ( switches for prelimit signals, slow speed signals, stop signals and zone signals) check bistable magnetic switches, distance between switches and magnets must be 1 cm check if there is some bolts or nuts near to the magnets ( they can work like magnets if they are too close to the magnets if magnets are mounted on the guide rails they must be on the outside of the guide, because on the other hand magnetic switches will not work properly

LIFT SOMETIMES STOPS IMMEDIATELY AFTER STARTING check stop is not station switches ( terminals 61 and 62 or LEDs STOP UP and STOP DOWN) both LEDs must be LIT when lift stops in station.

D-type manual

64

291 801 104

10.6. ERROR CODE READING FROM INDICATOR


It is possible to read error code from indicator when elevator is not working. Procedure is as follows: This function will only work with indicators connected to parallel outputs ( terminals 101 to 108 ). Indicator type can be type 0 or type 2. ( parameter 54 is 0 or 2 ). When elevator is not operating, the indicator will be off ( all outputs are off ). If now one of the call butons are pressed, the indicator will transmit error code. First it will blink from 1 to 5 times with position of station 1 and than it will blink from 1 to 5 times with position of station 2. After this operation it will not repeat the operation for 1 minute. After this time procedure can be repeated as above. From these two numbers it is possible to calculate the error code which is the same as error table code reading with programmer. First number must be multiplied by 5 and then second number must be added. The result is the error code number. Explanation of the error is described in chapter 5.4 Error table ( page 37 ). Example: First series of blinks (flashing of digits) Second series of blinks (flashing of digits) 2 x 5 = 10 10 + 4 = 14 =2 =4 result is 14

Error 14 is Error in input 308 elements check

NOTE

The visible digit shown on the display is not important. It is the number of flashes or blinks which must be considered.

D-type manual

65

291 801 104

11.

D-type LIFT CONTROLLER TECHNICAL INFORMATION

11.1. TECHNICAL CHARACTERISTICS


terminals on PCB Power supply computer signalization 211, 213 201, 202 voltage 12VAC (10 - 14VAC) 18VAC (14 - 24VAC) current max. 1000 mA max. 2000 mA voltage must be only for computer supply voltage have no capacitor for stabilization it must be from same phaze ( R,S,T) as 48V voltage for inputs 61 to 76 and 301 to 308. Also voltage 48V don't need any capacitor for stabilisation common 204

Input voltage inputs

61 - 76

inputs

301 - 308

48VDC (not stabilized) (35VDC - 51VDC) 48VDC (not stabilized) (35VDC - 51VDC) max. 60 V AC/DC

typ. 5 mA

typ. 5 mA

common 300

Outputs RE10 - RE22

RE1 - RE9

max. 500 mA for output NO INDUCTIVE LOAD max. 250 V AC/DC max. 1000 mA for output NO INDUCTIVE LOAD

D-type manual

66

291 801 104

D-type manual

67

291 801 104

D-type manual

68

291 801 104

D-type manual

69

291 801 104

D-type manual

70

291 801 104

D-type manual

71

291 801 104

11.2. D type MODULE TERMINALS


77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 100 101 102 103 104 105 106 107 108 121 122 123 130 131 132 +24V +24V 0V 0V for cabine calls - lamps for landing calls - lamps for cabine calls buttons for landing calls buttons or cabine call 1 or cabine call 2 or cabine call 3 or cabine call 4 or cabine call 5 or cabine call 6 or call down 2 or call down 3 or call down 4 or call down 5 or call down 6 or call up 1 or call up 2 or call up 3 or call up 4 or call up 5 or APB call 1 or APB call 2 or APB call 3 or APB call 4 or APB call 5 or APB call 6 or APB call 7 or APB call 8 or APB call 9 or APB call 10 or APB call 11 or APB call 12 or APB call 13 or APB call 14 or APB call 15 or APB call 16

cabine call 1 cabine call 2 cabine call 3 cabine call 4 cabine call 5 cabine call 6 cabine call 7 cabine call 8 landing call 1 landing call 2 landing call 3 landing call 4 landing call 5 landing call 6 landing call 7 landing call 8 input input input input input input input input input input input input input input input input output output output output output output output output output output output output output output output

stop up stop down relevelling down relevelling up slow speed up slow speed down cabine full load cabine overload maintenance on maintenance up maintenance down door closing priority drive door photocell door opening door obstruction common for position outputs, overload output, gong output, out of work output position 1 position 2 position 3 position 4 position 5 position 6 position 7 position 8 cabine overload arrival to station gong lift is out of work common for directions direction down direction up

D-type manual

72

291 801 104

201 202 203 204 211 213 214 221 222 300 301 302 303 304 305 306 307 308 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 F1 F2 B2 U22 U41 U9 U3 PRG

voltage supply 24V AC for signalization output voltage +24V for signalization output voltage 0V for signalization

voltage supply 10V AC for computer protective ground output voltage 0V for serial position display output voltage 24V DATA for serial position display common for inputs 301, 302, 303, 304, 305, 306, 307 and 308 input fast speed limit switch down input fast speed limit switch up input safety line after all cabine safety elements input safety line before cabine door input safety line after cabine door input end safety line after landing doors (or doors locks) input fire drive input elements check output output fast speed output output direction down output common direction output direction up

output pump on output NC output COM output NO output NC output COM output NO

pump star

pump delta

output output door close output common door output door open output output cabine blower fuse for computer ( 1A) fuse for 24V (3.15A) rectifier for 24V 6A / 600V integrated circuit for cabine calls 1 8 ULN2803A DIL integrated circuit for landing calls 1 8 ULN2803A DIL memory circuit 93C56 program circuit EPROM 27c256 or 27c512 RJ45 socket for programing ( RS232C)

D-type manual

73

291 801 104

11.3. INPUTS FOR CALLS CONNECTION


D-type control panel have 16 inputs for calls. These inputs can be defined as different inputs according to setting in parameter 31. Generally, D-type control panel can operate as follows:

up to 6 stops UP and DOWN collective selective system up to 8 stops DOWN collective selective system up to 9 stops DOWN collective selective system ( 1. and 9. call is the same in car and in floor) up to 11 stops UP and DOWN collective selective system ( D-type switch board is used) up to 15 stops DOWN collective selective system ( D-type switch board is used) up to 16 stops APB system

When D-type switch board is used LED lights in call buttons or diodes on inputs must be installed. Definition of different inputs in different systems is follows: UP and DOWN collective selective system maximal 6 stops ( parameter 31 is 1 )

DOWN collective selective system maximal 8 stops ( parameter 31 is 2 or 3) UP collective selective system maximal 8 stops ( parameter 31 is 9)

D-type manual

74

291 801 104

UP and DOWN collective selective system with D-type switch board maximal 11 stops (parameter 31 is 4)

DOWN collective selective system maximal 9 stops ( parameter 31 is 5 )

DOWN collective selective system with D-type switch board maximal 15 stops ( parameter 31 is 6 )

D-type manual

75

291 801 104

APB system maximal 16 stops (only 1 call) ( parameter 31 is 7 )

simple operation max. 16 floors ( parameter 31 is 8 )

D-type manual

76

291 801 104

11.4. OUTPUTS CONNECTION


D-type control panels have 13 relay outputs. 8 outputs are for position and 5 are for other functions. Also one transistorized serial output is in control panel. This output is compatible with SEC indicators PK 95 and PK96 and voice announcers VM95. This serial line has information about position, direction, car overload, arrival to station and out of work. Outputs can be connected in different ways: Connection for decimal position indicator:

Connection for binary indicator SEC ( inputs needs negative signal):

D-type manual

77

291 801 104

Connection for binary indicator (inputs needs positive signal):

D-type manual

78

291 801 104

11.5.OPERATION IN DUPLEX MODE


Both program versions must be equal when two control panels are operating in duplex mode.

DUPLEX CABLE CONNECT ION


Two D-type control panels can be connected so that they work in group (duplex) mode. They have to be connected together with duplex cable trough PRG sockets, no parameter change is needed.

Duplex cable

The drawing of duplex cable is:

Only original duplex cable must be used to avoid problems in operation. Cable must be 360 grounded near the PRG socket with omega element. Duplex cable must always be separated from other signal or power cables. Distance between cable and other cables must be minimal 10 cm. If cable is crossing other cables this crossing must be made at 90 angle. Maximal length of duplex cable is 5 m. When cable is disconnected elevators will immediately work in simplex mode. If programmer is connected to the PRG socket, the computer will recognize the difference and it will communicate with programmer. For this operation it is not necessary to disconnect power supply. NOTE If serial cable is disconnected take care that the connector will not touch ground or other terminals.

D-type manual

79

291 801 104

LANDING CALLS CONNECTION SYSTEM TYPE (P31) 1, 2, 3, 5, 7, 8 AND 9


Output calls can be connected parallel to both control panels or only to one control panel. If output calls are connected only to one control panel of duplex system this will work because panels communicate through serial cable and they exchange all information about landing calls. Normally landing calls are connected to both control panels so that at least one elevator works normally when other one is switched off. The drawing of connection: Elevator A: Elevator B: landing calls power supply

Terminal 77 ------------------------------- Terminal 77 ------------------- 0V Terminal 79 --------------------------------------------------------I>I------- 24V Terminal 79 --------I>I----/ ... Terminal 89-------------------------------- Terminal 89 ------------------- Terminal 90-------------------------------- Terminal 90 ------------------- Terminal 91-------------------------------- Terminal 91 ------------------- ... All used landing calls should be connected together!

landing calls

LANDING CALLS CONNECTION SYSTEM TYPE P31=4


Landing calls should be connected to only one control panel when using system type 4 (up to 11 floors up and down collective) and D-type switch module. Landing calls information is transferred to other control panel via serial (duplex) cable. We recommend connection of landing calls UP to one and landing calls DOWN to other control panel. Thus, basic operation of one elevator will be insured in case of switching off other control panel.

LANDING CALLS CONNECTION SYSTEM TYPE P31=6


Landing calls should be connected to only one control panel when using system type 6 (up to 15 floors down collective) and D-type switch module. Landing calls information is transferred to other control panel via serial (duplex) cable.

D-type manual

80

291 801 104

12. SAFETY CIRCUIT 186


12.1. GENERAL FEATURES

This circuit is specially developed to make it possible to move the car while the doors are open. Circuit board 76 x 86 mm with heigh of 35 mm for installation in control unit 4 x 3mm hole for mounting

The following manouvres are possible: - advanced door opening - relevelling upwards or downwards with the doors open

Circuit content:

- 3 x safety relay with six guided contacts - 2 x LED diode for status display - 7 x terminal for connection

Supply voltage Supply current Ambient temperature Degree of protection EMC compatibility Approvals

+ 48 VDC Max. 200 mA Max. 45 o C IP00 EN12015 and EN12016 CE

D-type manual

81

291 801 104

12.2. DETAILS AND CONNECTIONS


Schematic plan of safety circuit 186

The circuit does not need any additional power supply. All relays are made for 48 V DC supply. Explanation of work: - elevator control unit give 48 VDC to terminal 3 when elevator start - slow speed in arriving to station. This voltage must stay all the time to the next start - then magnetic switch ZONE A give 48 VDC to terminal 2 - and magnetic switch ZONE B give 48 VDC to terminal 1 - in this case connection is closed between terminals 4 - 5 and 6 - 7 - when elevator stopped in station elevator control unit should check one of link (4 5 or 6 7) - in the case that there is no connection elevator must not proceed to drive - LED I1 - LED I2 parallel to input 1 parallel to input 2

Explanation of LED:

12.3. REQUIREMENTS FOR INSTALLATION


-This product should be installed into a controller with minimum protection level of IP2X -The maximum voltage permissible for the series connection is 230 VAC or VDC -The safety series connection which are connected to terminals 4-5 and 6-7 should be protected with maximum 4 Amp fuse -Applied voltage for relays ( +48V DC ) should be fused with a maximum of 4 Amp fuse -The ambient temperature at which the unit ideally functions is between 0 C and 55 C -Once the equipment has been installed a test run should be carried out in both upward and downward directions stopping at every landing, so the control unit can check the perfect operation of the module

D-type manual

82

291 801 104

13. MAINTENANCE
13.1. CARE
The control panels must be installed according to the relevant installation regulations. They do not require any particular maintenance. They should not be cleaned with a wet or moist cloth. The power supply must be switched off before cleaning.

13.2. SERVICE
The screws of all terminals on the device should be re-tightened two weeks after initial commissioning. This should be repeated each year. If control panels have been stored for more than three years, the capacitors may have been impaired. Before commissioning these devices, it is advisable to regenerate the capacitors by connecting them to the voltage for two hours with the control panel disabled. After these operations the device is ready to be installed without limitations.

13.3. REPAIRS
Repairs of the device should only be carried out by the specialist personnel ( qualified by the manufacturer) If you carry out a repair on your own, observe the following points: when ordering spare parts do not only state the device type but also the device serial number. It is also useful to state the serial number of processor card and version of operation program ( sticker on the program circuit U3 )

SPARE PARTS
U3 integrated circuit with operation program. Type is 27C256 or 27C512. Integrated circuit must be properly oriented. Use correct tool for extracting to avoid damage on socket U9 integrated circuit with parameters. Type is 93C56. Integrated circuit must be properly oriented. Use correct tool for extracting to avoid damage on socket U22 integrated circuit drivers for button lamps 1 8. Type is ULN 2803.Integrated circuit must be properly oriented. Use correct tool for extracting to avoid damage on socket U41 integrated circuit drivers for button lamps 9 16. Type is ULN 2803.Integrated circuit must be properly oriented. Use correct tool for extracting to avoid damage on socket B1 rectifier for 12V CPU supply. Type is KBU6K. Rectifier is soldered. Replacement of these components must be made by specialist personnel B2 rectifier for 24V supply for buttons and lamps. Type is KBU6K Rectifier is in the four screw terminals. Observe proper orientation ( + AC AC - ) F1 fuse 2A for 12V CPU supply. Fuse is glass type 5 x 20 mm in socket USE OF INPROPER FUSE CAN DAMAGE PRINTED CIRCUIT BOARD F2 fuse 3,15A for 24V. Fuse is glass type 5 x 20 mm in socket. USE OF INPROPER FUSE CAN DAMAGE PRINTED CIRCUIT BOARD

D-type manual

83

291 801 104

Legend:

U3 U9 U22 U41 B1 B2 F1 F2 PRG

integrated circuit with program integrated circuit with parameters integrated circuit drivers for button lamps 1 8 integrated circuit drivers for button lamps 9 16 rectifier for 12V CPU supply rectifier for 24V supply for buttons and lamps fuse 2A for 12V CPU supply fuse 3,15A for 24V socket for programmer or PC cable

13.4. CUSTOMER SERVICE


For customer service, please contact your SEC ELECTRONICS office.

D-type manual

84

291 801 104

14. GUIDE TO ELECTROMAGNETIC COMPATIBILITY


14.1. THE EMC DIRECTIVE AND APPLICABLE STANDARD
The EMC Directive 89/336/EEC, and as amended by Directives 91/263/EEC, 92/31/EEC, 93/68/EEC and 93/97/EEC requires that in order to guarantee the free movement of electrical and electronic apparatus, and to create an acceptable electromagnetic environment, all such apparatus shall ensure that the electromagnetic disturbances produced by the apparatus do not affect the correct functioning of other apparatus or radio and telecommunications networks as well as related equipment and electricity distribution networks. The apparatus is also required to have an adequate level of intrinsic immunity to electromagnetic disturbances to enable it to work as intended. SEC lift control panels are according to the Guidelines on the application of Directive 89/336/EEC Clause 6.2.3.2 Components performing a direct function not intended to be placed on the market for distribution and final use The SEC position It is responsibility of the user to determinate the category under which the product is obtained however. SEC, in common with most other manufacturers, has prepared this document on the following basis: The sales are of the restricted distribution class Neither a CE mark nor a Declaration of Conformity are permitted under the EMC Directive

This product is intended only for professional assemblers. The responsibility for the maintenance of EMC compliance of an installation shall be with the installer and not the manufacturer. The manufacturer is required to provide recommendations and guidelines for maintaining EMC compliance after installation and this is given in this guide. The CE mark and Manufacturers Declaration of Conformity on SEC control panels relate to compliance with the Low Voltage directive only. The product standard for lift control panel is EN 12015 for emission and EN12016 for immunity and all SEC control panels have been tested for conformity with the various levels applicable under the standard. Next normative references are used: Emission: Immunity: EN 55011 EN 55014 EN EN EN EN 61000 61000 61000 61000 4 4 4 4 2 3 4 11

D-type manual

85

291 801 104

14.2. EMC COMPLIANT ELECTRICAL CABINET WIRING RULES


PANELS AND CABINETS Mounting panel and cabinet ( including the doors ) have to be grounded, with a direct connection to the ground bus. REMOVAL OF THE PAINT FROM THE SUPPORT AREAS The paint should be removed from the mounting panel and chassis support areas. WARNING The anodized aluminum does not conduct

GROUND TERMINALS OF THE CONTROL PANEL SEC control panels are provided with two ground terminals ( green-yellow terminal with mark 0 and ground terminal with multi screws ) one must be connected to the ground bus MINIMAL DISTANCE BETWEEN SIGNAL AND POWER CABLES The minimum distance between parallel signals and power cables is 30 cm. Possible crossings have to be made at 90o. SHIELDING OF THE SUPPLY FOR AN AC MOTOR The AC motors have to be supplied through a four pole shielded cable ( three phases plus a green/yellow ground wire), or though four unshielded cables, which are inserted inside a metal channel. It is important that a direct connection ( four cables ) between the panel grounding and the motor ground has been made and that the fourth cable had been inserted in a shield. GROUND CONNECTION TO BOTH SIDES OF THE CABLE SHIELD ( AC MOTOR ) The shield of the supply cable of the AC motors must be grounded on both sides in order to obtain 360o contact, that means the whole shield. This can be accomplished using suitable metallic EMC cables press grounded at full 360o at the input of the cabinet and of the motors terminal strip. If this connection is not possible, the shielded cables should be brought inside the cabinet and connected with an omega connector to the mounting panel- The same must be done on the motor side. In case a 360o connection on the motors terminal strip is not possible, the shield must be grounded before entering into the terminal strip. This should be done on the metal support of the motor, using an omega connector. In case a metal duct has to be used, it should be grounded at full 360o where possible. PIGTAIL AVOIDANCE While grounding the shields of the cables, one has to use a 360o connection ( E.g. omega bus ) with a pigtail connection to be absolutely avoided. By pigtail is meant the connection to earth ground of the cable shield by means of an additional wire. SUPPLY CABLES TO THE DC MOTORS The supply cables of DC motor do not need to be shielded. DIRECT CONNECTION BETWEEN THE GROUND BUS AND MOTOR CHASSIS Independently from ground-connection of the motors chassis, it must always be connected to the ground wire ( green/yellow ) coming from the panel ground bus. MAXIMAL LENGTH OF THE AC MOTORS CABLES INSIDE THE CABINET From the grounding of the screen side cabinet of the panel terminal strip, the supplys cables have to measure 30 cm maximum. ENCODER CABLES The encoder cable must be shielded and grounded at the panel at a full 360o. The female connector on the inverter has been foreseen for that connection, therefore it is enough to have the cable shield connected at 360o in the conductive case of the male connector. In order to check that the shield is not connected on the motor side remove the encoder connector from the inverter and verify with a tester the presence of a high impedance between the shield and the metal case of the encoder or of the motor.

D-type manual

86

291 801 104

SEC ELECTRONICS
___________________________________________________________________________________

Declaration of Conformity
Manufacturer: SEC ELECTRONICS Neverke 30 6256 KOSANA SLOVENIA Details of electrical equipment Model number:

D - TYPE Doppler V 0.0 03/2000 LIFT CONTROLLER PCB EN 12016 EN 12015

Harmonised Standard applied:

and complies with the previsions of the following EC Directive(s): 73/23/EEC modified by 93/68/EEC and named Low Voltage Directive 2000

CE marking from: Authorised Signatory:

Name: Position: Date of Issue:

Milan Samsa Managing director 01. 03. 2001

Place of Issue:

Neverke

D-type manual

87

291 801 104

Das könnte Ihnen auch gefallen