SPD910 Differential Air Pressure Switch


This range of four SPD910 differential air ow switches are intended for use in air handling systems for the monitoring of air ducts, lters and fans. The enclosure is plastic with a rating of IP54. A set-point adjustment is provided under the clip-on clear plastic cover. The mounting bracket and tubing is supplied.

DESCRIPTION

See part number table on page 2

Medium Pressure Range Tolerable overload on one side Repeatability 0.2 3 mbar 0.5 5 mbar 1 10 mbar 5 20 mbar 10 50 mbar Resistive Load

Air and neutral gases 0.2 50 mbar 75 mbar at 30 75 C 50 mbar at 30 85 C

0.025 mbar 0.05 mbar 0.05 mbar 0.05 mbar 0.15 mbar Switching Load 5 A at 250 Vac 4 A at 30 Vdc Inductive 0.8 A at 250 Vac 0.7 A at 30 Vdc Materials in contact with the medium Case: PC 10% GF Cover: PC Diaphragm: Silicone LSR tempered 200 C, free of gas emissions Temperature Medium and ambiance 30 +85 C -22.. +185F Storage 40 +85 C -40.. +185F Mechanical > 106 switching cycles Screw terminals or AMP connectors 6.3 mm or 4.8 mm according to DIN 46244 Cable gland PG11 with cable strain relief IP 00 IP 54 Pipe 6.2 mm Adapter inside thread G1/8 ETL CE conformity DVGW according to DIN 1854 EU conformity: Low voltage directive 73/23/EWG Gas appliance directive: 90/396/EWG CE 0085 A P0918

Service life Electrical connection

Protection standard Pressure connections Tests / Admissions

Without Cover With Cover

Sensors & Input Devices SPD910 PART NUMBER


Part Number 004701090 004701080 004701070 004701060 Model Number SPD910-2000Pa SPD910-1000Pa SPD910-500Pa SPD910-300Pa Description Switch Pres Air SPD910-2000Pa Switch Pres Air SPD910-1000Pa Switch Pres Air SPD910-500Pa Switch Pres Air SPD910-300Pa Replaces SPD900-600Pa SPD900-200Pa

DIMENSIONS
Fig. 1

Flow area

1)

Fig. 2

Flow area

FUNCTION
The pressure switch has two separate pressure chambers, each with its own connection. The switch operates when the setpoint is either exceeded or not reached. Vacuum Monitoring Connect the pressure switch via P2. Do not connect P1. Leave P1 open. Pake sure that dirt can not get into P1. High Pressure Monitoring Connect the pressure switch via Pa. Do not Connect P2. Leave P2 open. Make sure that dirt can not get into P2. Filter Monitoring Connect P1 before the lter and P2 after it. Fan Monitoring Connect P1 after the fan (in blowing direction) and P2 before the fan.

Schneider Electric Telephone Europe: Malm, Sweden +46 40 38 68 50


03-00265-01-en

Telephone Asia Pacific: Singapore +65 6776 3166

www.schneider-electric.com
October 2011

2011 Schneider Electric. All rights reserved.