Sie sind auf Seite 1von 9

MAN Ferrostaal Power Industry GmbH

Anlage, Projekt-Nr.: Fajr I Power Expansion Project, 250 MW OCPP Plant, Project-No.: 2005/102780 Beschreibung:
Description:

HAZARDOUS AREA CLASSIFICATION


FAJR1-EL-YK-EK-DSD0327

Seiten / Pages:
Anlagen / Appendices:

9 none

Dokumenten-Nr.:
Document-No.:

Status:
Status:

Rev. 2

Zugehrige Dokumente:
Related documents:

- FAJR1-EL-YK-EK-DSD0328 Hazardous area classification layout


Index
Rev.

Datum
(Jahr-Monat-Tag) Date (year-month-day)

Erstellung bzw. nderungen (Seiten)


Issue resp. modifications (pages)

Abteilung
Department

bearbeitet durch
prepared by

geprft durch
checked by

freigegeben durch intern extern


released by internal external

1 2

2006-03-06 2006-04-04

First Issue Updated

DIA DIA

Donato Donato

Alze Alze

Nahrwold Nahrwold

Tiberti Tiberti

MAN Ferrostaal Power Industry GmbH Hohenzollernstrae 24 D-45128 Essen Phone: Fax: E-mail: Internet: +49. 201. 818-50 +49. 201. 818-5154 info@manfs-power.com www.manfs-power.com

Jede Art von Vervielfltigung, auch teilweise, nur mit der Zustimmung von MAN FS-PI. Any kind of reproduction, also in part, only with the consent of MAN FS-PI.

Page 1 of 9

MAN Ferrostaal Power Industry GmbH

CONTENTS Page No.


1 2 3 4 5 6 SCOPE .............................................................................................................................3 STANDARDS ..................................................................................................................4 REFERENCE DOCUMENTS .......................................................................................5 FLAMMABLE MATERIAL............................................................................................5 DESIGN ENVIROMENTAL CONDITIONS ...............................................................6 VALVES ..........................................................................................................................6 6.1 Installation ...........................................................................................................6 6.2 EMISSION SOURCE ...........................................................................................6 6.3 CLASSIFICATION ...............................................................................................7 7 BREATHER PIPE IN ATMOSPHERE .......................................................................8 7.1 Installation ...........................................................................................................8 7.2 Emission Source ................................................................................................8 7.3 CLASSIFICATION ...............................................................................................8

Page 2 of 9

MAN Ferrostaal Power Industry GmbH

SCOPE Scope of this document is to define and classificate the Hazardous areas relevant to the valves and breather pipes installed on the Gas Fuel piping that feed the new Gas Turbines (GT16 and GT17) that will be installed in the FAJR 1 Power Extension located at BANDAR-IMAM (IRAN). The examined equipment are installed on the Gas Fuel piping included between the following flanges: connection to existing Fuel Gas Main Line, connection to GT16 skids (Fuel gas system, safety shut down valve, fuel gas metering), connection to GT17 skids (Fuel gas system, safety shut down valve, fuel gas metering).

The Hazardous area classification inside each GT skid has been determinated from the manufacturer (GEF). The considered equipment /points are: valve 00EKG01AA01 (manual and solenoid valve) valve 00EKG01AA02 (N2 purge) valve 60EKG01AA03 (drain) valve 60EKG01AA01 (vent) valve 70EKG01AA03 (drain) valve 70EKG01AA01 (vent) Breather pipe in atmosphere of the GT16 fuel gas system (60EKG06BZ001) Breather pipe in atmosphere of the GT16 fuel gas safety shut down valve skid (60EKG07BZ001) Breather pipe in atmosphere of the GT17 fuel gas system (70EKG06BZ001) Breather pipe in atmosphere of the GT17 fuel gas safety shut down valve skid (70EKG07BZ001)

Page 3 of 9

MAN Ferrostaal Power Industry GmbH

STANDARDS The determination and classification of the hazardous areas considered in this document are in accordance with the follows applicable IEC std: IEC 60079-10 Pubblication date Edition 2002-06 4.0

Electrical apparatus for explosive gas atmospheres Part 10: Classification of hazardous areas.

Page 4 of 9

MAN Ferrostaal Power Industry GmbH

REFERENCE DOCUMENTS The following documents have been used for reference: FAJR1-IC-XG-EK-DSD0104 rev.5 FAJR1-MC-XH-EK-DSD0107 rev.1 FAJR1-MC-UH-ZU-GEF0618 rev.B Gas Turbine Generator Unit P&I Gas Fuel system interconnecting piping Piping arrangement Fuel Gas GT Unit No. 6 and No.7 General documentation general arrangementHazardous areas layout

FLAMMABLE MATERIAL According to the contract Volume III _ ANNEX 2A-1-table 6.5 the prevalent flammable gas is Methane CH4 (83,23%). The meaning characteristics of the Methane CH4 are: Spontaneous ignition temperature Relative density of gas Mass concentration (M) Mass Volumetric (liquid) Lel % VOL Ratio of the specific heat () Flash point Temperature class and group Gas constant (R) Factor [(+1)/ (-1)] [ J/Kmol K ] [ C ] [ Kg/Kmol ] [ Kg/m ] % [ C ] <0 0,554 16,04 415 4,40 = 0,029kg/m 1,31 537 II AT1 8314 7,45

Page 5 of 9

MAN Ferrostaal Power Industry GmbH

DESIGN ENVIROMENTAL CONDITIONS All the considered equipment/points are installed in open space, without barriers (wall, enclosure, etc.), therefore with free air circulation: Air minimum speed (w) Maximum temperature Barometric Pressure Ventilation availability Ventilation efficency factor (f) Ventilation efficency level [m/s] [ C ] [ mbar ] 0,5 52 1013 Good 1 medium

6 6.1

VALVES Installation

All valves are installed on the Gas Fuel piping. The installation is in open space, with free air circulation . 6.2 EMISSION SOURCE

Each equipment has the following emissions: - Continuous level emission: Negligible - Second level emission: Fortuitous emission consequent to a break. The parameters used to define the area classification around each equipment are the following: Hole dimension relevant to the emission Maximum pressure Emission time Safety factor Initial concentration Discharge Temperature Discharge factor [c] [Xo] [A] 2,5 10 6 m(= 2,5mm) 28 bar 30s 0,5 50% 32C 0,8

Page 6 of 9

MAN Ferrostaal Power Industry GmbH

Sonic emission 6.3 CLASSIFICATION

[]

Considering the high pressure in the piping and the source system type, in case of emission as defined in the above par., the system pressure do not suffer a considerable reduction. Therefore, it is possible to define the emission flow rate [dg/dt]max as follow:
2 dG = c A + 1) dt
0,5

P T R M
0,5

With the parameters listed in the above chapters, the Emission Flow Rate is 0,0094 kg/s therefore, the critical distance dz is:

k LEL% dz = 16,5 ( P 10 ) M A =< 0,5m 100 Considering all the elements in case of break: - emission level : second - ventilation efficiency level : medium - ventilation availability : good It is possible to define the area around each equipment with a good safety margin as follows:
5 0, 4

ZONE Form Diameter

2 Spheric 0,5m

Page 7 of 9

MAN Ferrostaal Power Industry GmbH

7 7.1

BREATHER PIPE IN ATMOSPHERE Installation

The breather pipe in atmosphere relevant to Fuel gas conditioning and metering skid of each GT is installed in open space, with free air circulation . 7.2 Emission Source

During the normal operation of each GT, from the breather pipe can occur of the occasional emission. According to IEC60079-10 attcahment A, the system has been classified as follows: First Level Emission The parameters used to define the area classification around to the top of each breather pipe are the following: Hole dimension relevant to the emission Maximum pressure Discharge Temperature Discharge factor Sonic emission [c] [] [A]

314 10 6 m(= 314mm)


28 bar 32C 0,97 1

7.3

CLASSIFICATION

Considering the high pressure in the piping and the source system type, in case of emission as defined in the above par., the system pressure do not suffer a considerable reduction. Therefore, it is possible to define the emission flow rate [dg/dt]max as follow:
2 dG = c A + 1) dt
0,5

P T R M
0,5

With the parameters listed in the above chapters, the Emission Flow Rate is 1,435 kg/s. Therefore, the critical distance dz is:

42300 dG / dT F dz = 1,2 = 72m M LEL%Vol w

Page 8 of 9

MAN Ferrostaal Power Industry GmbH

Considering all the elements: - emission level : first - ventilation efficiency level : medium - ventilation availability : good It is possible to define the area over the top of each breather as follows: ZONE Form Diameter 1 cone-shaped 72 m