Beruflich Dokumente
Kultur Dokumente
Building Ref
Vol
Sect
Page
1.2.1
EM
Flyleaf
Page 1
Building Ref
Vol
Sect
Page
1.2.1
EM
Page
2 3 4-5 6 7 8 9 9 9 9 9 9 9 9 10 11 12 13 14 15
Flyleaf
Page 2
Building Ref
Vol
Sect
Page
1.2.1
EM
Product
Subcontractor MVSG & EMVSG Transformer Power Factor (QC) & ATS MDB & EMDB DLP & DP ECB EDP EIB ELP EMCP, MCC & EMCC EPP ESDP LP PP UDP
Name of Provider
Drake & Skull SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC MESCO MESCO MOTS CEAG/ SAUDLIGHTING MOTS HONEYWELL MOTS MOTS MOTS MOTS MOTS MOTS MOTS
Address
P.O. BOX 151 P.O. BOX 89249, Riyadh 11682 P.O. BOX 89249, Riyadh 11682 P.O. BOX 41380, Riyadh 11521 P.O. BOX 41380, Riyadh 11521 P.O. BOX 23560, Riyadh 11436
Tel No.
059 858 9082 01 2651515 050 5100216 01 2651515 050 5100216 01 2650101 050 7257497 01 2650101 050 7257497 0 12653701 050 2881293 01 265 1010
E Mail Address
alaa.azizi@drakescull.com uday.kamath@sa.schneider-electric.com uday.kamath@sa.schneider-electric.com jeffrey.almario@mesco-sa.com jeffrey.almario@mesco-sa.com ayaqub@mots.com.sa slc@saudlighting.com ayaqub@mots.com.sa Mohammed.alsaadi@Honeywell.com ayaqub@mots.com.sa ayaqub@mots.com.sa ayaqub@mots.com.sa ayaqub@mots.com.sa ayaqub@mots.com.sa ayaqub@mots.com.sa ayaqub@mots.com.sa
P.O. BOX 23560, Riyadh 11436 P.O. BOX 23560, Riyadh 11436 P.O. BOX 23560 P.O. BOX 23560 P.O. BOX 23560 P.O. BOX 23560 P.O. BOX 23560
0 12653701 050 2881293 0 12653701 050 2881293 0 12653701 050 2881293 0 12653701 050 2881293 0 12653701 050 2881293 0 12653701 050 2881293 0 12653701 050 2881293 0 12653701 050 2881293 0 12653701 050 2881293
UPP
MOTS
ayaqub@mots.com.sa
USDP UPS
MOTS
ayaqub@mots.com.sa
Flyleaf
Page 3
Building Ref
Vol
Sect
Page
1.2.1
EM
Flyleaf
Page 4
Building Ref
Vol
Sect
Page
1.2.1
EM
Flyleaf
Page 5
Building Ref
Vol
Sect
Page
1.2.1
EM
VOLUME INDEX
Volume Title
Flyleaf
Page 6
Building Ref
Vol
Sect
Page
1.2.1
EM
S ECTION INDEX
Each of the above Volumes consists of the Sections listed below. The main Section Titles for each Volume is as listed below. Section Title
1 2 Introduction Maintenance Procedures
Content
Manual Index and general useful information Maintenance Procedures: Include the following information and items that detail essential maintenance procedures: Test and inspection instructions, Aligning, adjusting, & checking instructions, Fault finding guide, Lubrication requirements, list of required lubricants for equipment, Schedules for preventive & routine maintenance and service. Scheduled Maintenance & Service: Tabulate actions for daily, weekly, monthly, quarterly, semi-annual, and annual frequencies. Maintenance & Service Record: Include manufacturers' forms for recording maintenance. Spare Parts List and Source Information: Including lists of replacement & repair parts, with parts identified & cross referenced to manufacturers' maintenance documentation & local sources of maintenance materials & related services. Maintenance Service Contracts: Including copies of maintenance agreements with name and telephone number & contact details of service agent. Warranties and Bonds: Including copies of warranties & bonds & lists of circumstances & conditions that would affect validity of warranties or bonds along with notification procedures. Factory and site test reports. Commissioning records and reports.
Manufacturers' Maintenance literature Standard printed maintenance instructions & bulletins, Drawings, diagrams, & instructions required for maintenance,
Flyleaf
Page 7
Building Ref
Vol
Sect
Page
1.2.1
EM
FOREWORD
Each of the Volumes has been prepared in a format to give easy reference to all plant and equipment. Every effort has been made to deal with each system in a concise manner. However, to obtain a full and detailed picture of any particular system or plant item, this manual must be read in conjunction with the record drawings and relevant manufacturer's literature. To assist in the day to day running of the various plant a description of each is given, together with routine attention necessary to the main components. Regular inspection, monitoring and checking are necessary if the efficiency and control of plant is to be maintained at the level required. Regular maintenance and inspections are essential, if inconvenient and costly breakdowns are to be avoided. Although there is no way of guaranteeing against the possibility of breakdown, with regular and detailed inspections together with a preventive maintenance programme, the likelihood of such an occurrence can be greatly reduced. A correct maintenance programme will also ensure that the individual plant is running at maximum efficiency at all times. This will also extend plant life due to the continual monitoring of wear and changes that the systems undergo during their operating period and life. The maintenance programme will provide anticipated and continuous corrective action to avert and minimise deterioration. THE MANUAL DOES NOT REPLACE THE NEED FOR FULLY QUALIFIED OPERATORS.
It is important that the modification records in this section are referenced every time that the manual is used in order to ensure that information obtained from other sections is still valid. All operators must be made fully cognizant with the contents of this manual before operating the system.
Flyleaf
Page 8
Building Ref
Vol
Sect
Page
1.2.1
EM
GENERAL INFORMATION
Building Name :
College of Arts and Sciences (West Building)
Operating Systems & Equipment Maintenance Manual Ministry of Finance Riyadh, KSA Airport Road Riyadh 11177
: :
: :
Name of Main Contractor Address Date of Completion Date of Handover Date of Issue
: : : : :
Flyleaf
Page 9
Building Ref
Vol
Sect
Page
1.2.1
EM
10
MODIFICATION DETAILS
Modifications and authorised changes, which may affect the safety, reliability or maintenance of the health and safety files, are to be recorded and registered. Information on permitted modifications allowed for by manufacturers or designers should be included. All modification and changes must be recorded as they occur on the following record sheets: Modifications to Buildings Modifications to the Manual
Flyleaf
Page 10
Building Ref
Vol
Sect
Page
1.2.1
EM
11
Flyleaf
Page 11
Building Ref
Vol
Sect
Page
1.2.1
EM
12
Flyleaf
Page 12
Building Ref
Vol
Sect
Page
1.2.1
EM
13
Flyleaf
Page 13
Building Ref
Vol
Sect
Page
1.2.1
EM
14
IS S UE REGIS TER
Schedule of persons to whom each revision of this Manual should be issued Controlled Copy No. Name Company
Flyleaf
Page 14
Building Ref
Vol
Sect
Page
1.2.1
EM
15
Flyleaf
Page 15
Building Ref
Vol
Sect
Page
1.2.1
EM
Title
Manual Index Services Identification Identification of Conductors Fire Extinguisher Color Code
Page
2 3 3 4
Introduction
Page 1
Building Ref
Vol
Sect
Page
1.2.1
EM
1.2
MANUAL INDEX The maintenance manual consists of the sections listed below.
Section Title
1 2 Introduction Maintenance Procedures
Content
Manual Index and general useful information Maintenance Procedures: Include the following information and items that detail essential maintenance procedures: Test and inspection instructions, Aligning, adjusting, & checking instructions, Fault finding guide, Lubrication requirements, list of required lubricants for equipment, Schedules for preventive & routine maintenance and service. Scheduled Maintenance & Service: Tabulate actions for daily, weekly, monthly, quarterly, semi-annual, and annual frequencies. Maintenance & Service Record: Include manufacturers' forms for recording maintenance. Spare Parts List and Source Information: Including lists of replacement & repair parts, with parts identified & cross referenced to manufacturers' maintenance documentation & local sources of maintenance materials & related services. Maintenance Service Contracts: Including copies of maintenance agreements with name and telephone number & contact details of service agent. Warranties and Bonds: Including copies of warranties & bonds & lists of circumstances & conditions that would affect validity of warranties or bonds along with notification procedures. Factory and site test reports. Commissioning records and reports.
Manufacturers' Maintenance literature Standard printed maintenance instructions & bulletins, Drawings, diagrams, & instructions required for maintenance,
Introduction
Page 2
Building Ref
Vol
Sect
Page
1.2.1
EM
Introduction
Page 3
Building Ref
Vol
Sect
Page
1.2.1
EM
1.2.2
Introduction
Page 4
Building Ref
Vol
Sect
Page
1.2.1
EM
Content
General Inspection & Maintenance Notes Foreword Electrics ~ General Note Emergency Maintenance Medium Voltage Switch Gears & Power Transformers 13.8KV Maintenance Procedures (Planned) Maintenance Procedures (Corrective) Maintenance Hazards Disposal Instructions Low Voltage Main Distribution Boards & Distribution Panel Boards 380/230V Maintenance Procedures (Planned) Maintenance Procedures (Corrective) Maintenance Hazards Disposal Instructions Other Electrical Low Voltage Equipments, UPS, ATS, MCC, ECB, Capacitor Banks, Dimming System Maintenance Procedures (Planned) Maintenance Procedures (Corrective) Maintenance Hazards Disposal Instructions Lighting & SMALL Power System Maintenance Procedures (Planned) Maintenance Procedures (Corrective) Maintenance Hazards Disposal Instructions Cleaning of Luminaires Earthing & Lightning Protection Maintenance Procedures (Planned) Maintenance Procedures (Corrective) Maintenance Hazards Disposal Instructions Elevator System Maintenance Procedures (Planned) Maintenance Procedures (Corrective) Maintenance Hazards Disposal Instructions Maintenance Schedule Introduction
Building Ref
Vol
Sect
Page
1.2.1
EM
23 24 24 25 26
Maintenance Procedures
Page 2
Building Ref
Vol
Sect
Page
1.2.1
EM
It should be established that the means of protection against direct contact with any live conductors meets the requirements for the safety of any person and property from the effects of electric shock, fire and burns. For each method of protection against direct contact it should be established that there has been no deterioration of insulation; no removal of barriers or obstacles; no alterations to enclosures or access to live conductors which would reduce its effectiveness. Precautions should be taken, where necessary, to disconnect electronic and other equipment which may be damaged by subsequent testing. Special care must be taken where electronic components are fitted to protective and control devices, and installed in HF luminaires. If inspection and testing cannot be carried out in any part of the system, or is limited in any way, this should be recorded in the Periodic Inspection Report.
Maintenance Procedures
Page 3
Building Ref
Vol
Sect
Page
1.2.1
EM
2.1.3
Emergency Maintenance Depending on the type of breakdown, a decision must be taken on whether the matter is urgent or not, e.g. lamp failure, individual circuit fault or non-essential plant failure. In each of the above cases, the fault needs attention but is not generally considered urgent. When a breakdown occurs, action is to be taken immediately to render the system safe. In such cases the procedure is outlined in the operation manual for shutting down the system and switching off plant, etc. This must be carried out before any other action necessitated by the breakdown is initiated. This would include work on boilers or pumps, isolation of plant and electrical circuits because of leaks, etc. Always try to establish the cause of a breakdown rather than merely rectifying the effect. Although the immediate need may be to restore the system to working order without delay, by whatever means possible, never be satisfied with any action which only repairs the defect or replaces the part. Investigation in depth may be required to reveal some underlying fault which, if not corrected, may result in a recurrence of the trouble, or even perhaps later development of other more serious faults which are not yet apparent. Careful and complete details should be recorded of all breakdowns in a Maintenance Logbook. Date of occurrence and relevant equipment, details of breakdown, any previous maintenance work carried out, previous warnings or evidence of trouble which may (or may not) have been attended to, how the system was operating, any special circumstances, or similar information should be accurately and fully recorded, together with details of action taken, including temporary and/or permanent repairs or replacements. These records are not only useful to the operating staff, but often provide invaluable clues to outside specialists and service engineers.
Maintenance Procedures
Page 4
Building Ref
Vol
Sect
Page
1.2.1
EM
2.2 2.2.1
Me d ium Volta g e Switch Ge ars a n d P ower Tra n s fo rm ers 13.8KV Maintenance Procedures (Planned) Daily 1. Check that all meters and indicators are functioning correctly. Note readings and compare with those taken previously. 2. Check alarm indicators on the front compartment of the switchgear and transformer cabinet, carry out any corrective action as necessary. 3. Check for overheating, vibration and undue noise etc., and report to the Management for correction or repair immediately. Carry out repair as necessary. 4. Visually inspect indicator lamps and display units, replace any faulty ones as necessary, or check any wire disconnection. 5. Check warning and indication labels are securely in position. Bi-Annually 1. Clean and free from dust inside and outside the switchgear or transformer cabinet, one at a time; using compressed air and a suitable plastic nozzle. 2. Check the battery and charger (following the charger instruction). 3. Check the electrical and mechanical operation of the MV switchgear and transformer with OFF or ON load, following the manual instructions. Note: It is important to choose public holiday to do these checking and inspections. Yearly 1. Carry out tasks as described Bi-Annually. 2. The switchgear and transformer rooms shall be kept as clean and free from dust as possible. All accumulations of dust inside the switchgear and the transformer cabinet should be removed by blowing with compressed air or vacuum cleaner, using plastic nozzles. Finish by wiping with cloth moistened in alcohol. 3. Check all control and power cables and busbar joints. 4. Check all bolts are well tightened with a torque wrench. 5. Check the damping of cable bundles and that no cable is passing in sharp edges or corners. 6. Check all fixing components especially: the cover of busbar compartment, door access, tumbler, motor drive, transformer cabinet, protection relay, auxiliary relay, indicators, push buttons and selector switches. 7. All metering and protection units should be checked.
Maintenance Procedures
Page 5
Building Ref
Vol
Sect
Page
1.2.1
EM
Corrective maintenance operations allow for defective subassemblies to be replaced. The operations mentioned in the summary table here after can be carried out by the customer or by The Manufacturers After Sales agents. After each operation, carry out electric tests in compliance with the standards in force. Description Replacement on MV cubicles Busbar rating Earthing switch clamps and capacitive isolators Plug-in pins Upper and lower bushing Increase in the number of cables Flaps and flap operating mechanisms Extraction of a cubicle VT fuse VPIS voltage indicator box CT Anti-condensation resistor Earthing switch position auxiliary contact block Surge arrester Locking using plug-in padlocking lock(s) Plug-in padlocking electromagnetic locking Locking using earthing switch lock(1) Locking using earthing switch locks(2) Earthing switch electromagnetic lockin Locking using lock(s) for prevention of withdrawal Zero frequence toroid VT and VT compartment High voltage contacts on VT fuses Cable connection bar support isolators MV handles Circuit-breaker carriage position auxiliary contacts Withdrawable VT auxiliary contacts Withdrawable VT fuse blowing auxiliary contacts Printed circuit and relay support (STPI) Replacing the fans on cubicles Cleaning ventilation grids on cubicles Execution Comments
Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/
See Manufacturer Manual See Manufacturer Manual See Manufacturer Manual Consult Agent See Manufacturer Manual Consult Agent See Manufacturer Manual See Manufacturer Manual See Manufacturer Manual See Manufacturer Manual See Manufacturer Manual Consult Agent See Manufacturer Manual See Manufacturer Manual See Manufacturer Manual Consult Agent See Manufacturer Manual See Manufacturer Manual Consult Agent See Manufacturer Manual Consult Agent See Manufacturer Manual See Manufacturer Manual
Maintenance Procedures
Page 6
Building Ref
Vol
Sect
Page
1.2.1
EM
Care should be taken when removing SF6 which may contain decomposition products. It should not be released in an indoor environment and should be collected in a storage vessel. Care should be taken not to breathe SF6 removed from an item of equipment. If this possibility cannot be avoided, a respirator should be worn. This should be fitted with a filter capable of removing the gases described in arc decomposition products. Enclosures should be evacuated such as to remove as much as possible of the residual SF6.
In some cases, flushing enclosures with dry air 2.2.4 Disposal Instructions When the installation has reached the end of its useful life, the equipment should be carefully stripped out and removed from the premises and disposed of in a careful and controlled manner. End of life of SF6 - filled equipment SF6 - filled equipment which has been removed from service may require treatment to neutralize any decomposition products remaining after the SF6 has been removed. For environmental reasons. SF6 has to be removed and not released to the atmosphere, (see SF6 and the global environment). The need for neutralization is dependent on the level of decomposition. Prior to treatment, the SF6 should be removed and stored for recycling. The equipment should then be treated according to the expected decomposition level. After treatment, the equipment can be disposed of as normal waste (respecting local regulations), for example in a landfill site, or subjected to reclamation processes to recover the metals. Solutions used in the neutralization process can be disposed of as normal waste.
Medium and high decomposition: The internal surfaces of gas enclosures should be neutralized using a solution of lime (calcium hydroxide) prepared by diluting 1 kg of lime in 100 liters of water. The enclosure to be treated should, if possible, be filled with the lime solution for a period of 8 hours before emptying. If it is subsequently necessary to work on the enclosure, it should first be rinsed with clean water. For larger enclosures where filling is impractical, powders should be removed, using a vacuum cleaner equipped with a suitable filter, for neutralization separately. The internal surfaces should then be washed with the lime solution which should be left in place for at least one hour followed by rinsing with clean water.
Maintenance Procedures
Page 7
Building Ref
Vol
Sect
Page
1.2.1
EM
Low Volta g e Main Dis trib u tio n Bo a rd s a n d Dis trib utio n P a n e l Bo a rd s 380/230V Maintenance Procedures (Planned) Main Distribution Boards Weekly 1. Check that all metering instruments are functioning. Note readings and compare with those taken previously. 2. Check that operating tools, handles, keys, etc. are readily available in switchboard. 3. Inspect switchboard or circuit breakers enclosure for undue heating. Monthly 1. Carry out tasks as detailed for Weekly. 2. Check for undue noise, overheating or vibration, loose parts, tightness of screw/bolts and warping, and report to the management for correction or repair. 3. Visually check PACBs, MCCBs, fuse switches or isolators, for signs of arcing or burning. (Checking of the PACB may only be done if the circuit breaker is permitted to be opened for servicing and only under the instruction of the engineer in charge). 4. Examine resistors and devices object to overheating, where and when possible, without shutting down the essential loads. (Check with the supervising engineer). 5. Inspect earthing connections, power terminations and control circuits without shutting down the MDB as per Engineers instruction. 6. Remove all dust and debris inside cubicles or enclosures with the aid of a vacuum cleaner. 7. Check that PACBs stored energy mechanisms are charged. Correct any defects. Bi-annually 1. Carry out tasks as detailed for Monthly. 2. Check operation of MCCBs, PACBs and isolators using their integral switching arrangements to ensure that mechanisms are in good order. 3. Check for links, bridges for sign arcing. Ensure correct grade of fuse is fitted. Correct any defects. 4. Check electrical and/or mechanical operation of withdrawable main PACB at a time, in the test position and in the connected position, strictly in accordance with Engineers instructions, when MDB is not in use. Annually 1. Carry out tasks as detailed for Bi-annually. Note: Substation must be shut down and dead before further tasks are carried out. 2. Inspect electrical primary and secondary connections, cables and supports, insulation for discoloration, excessive corrosion, secure connections, clean contacts, insulation chaffing and embroiled or discoloured cable or insulator. Correct any defects. 3. Clean the stationary part of the switchgear with a clean cloth, use compressed dry air for inaccessible areas. 4. Examine all air filters for dust content, flush with water and re-coat with supercoat adhesive as recommended per manufacture.
Maintenance Procedures
Page 8
Building Ref
Vol
Sect
Page
1.2.1
EM
5. Check that all conduits and cable gland terminations associated with the switchboard are secure. Withdrawable LV Switchgear 6. Manually discharge (for safety) and draw out the circuit breakers, check, clean and lubricate the carriages. 7. Check all stationary primary disconnects for evidence of overheating and corrosion. 8. Inspect all circuit breakers draw-out captive positions, interlocks and shutter mechanism operation. All Circuit Breakers 9. Check anti-pump relay operation. 10. Check and clean insulated parts using a mild detergent, a lint free cloth, rinsing with clear water and dry. 11. Inspect arc chutes and contacts of circuit breakers, fuse-switches, isolators and repair or replace as per manufacturers procedures. 12. Check security of all electrical terminations and connections and tighten as necessary. 13. Check that all barriers and guards are in place and secure. 14. Check that phase labels giving circuit references are securely fixed. Replace any missing items and update information as necessary. 15. Ensure that 380 Volts and any other warning labels are in position where applicable. 16. Check door interlocks and that doors can be securely closed. If lock is provided, check that it functions correctly. 17. Check enclosure for paintwork condition and signs of corrosion. (Correct any defects.). 18. Visually inspect any under-voltage relays, clean and carry out a simulation test. 19. Check that the rating of the circuit breakers and setting of microprocessors (MPS), over-current and ground fault relay are correct with respect to the loading, type of load, cabling, etc., in the design data. Report any overloading and/or loads that are up to the set rating of the breaker. Make any possible adjustments. Report need for replacements and adjustments to the management. Two-yearly 1. Carry out tasks as detailed for Annually. 2. Measure insulation resistance for busducts, busbars and circuit breakers with 1000V megger, and compare with previous record. Repair as necessary. 3. Measure the insulation resistance of the secondary wiring selected on random basis with a 500V megger and record results. (It must not be less than 0.5 megohm). 4. Check continuity of all control circuits. 5. Measure circuit breaker contact resistance. 6. Carry out injection testing of all relays. 7. Carry out insulation resistance measurement of instrument transformers Withdrawable P.A.C.Bs 1. Clean and lubricate the circuit breaker housing safety shutter mechanisms. 2. Manually check the operation of the safety shutter mechanisms in accordance with manufacturers instruction procedures. 3. Inspect and clean the main isolating contact orifice bushings, using a clean, dry and non-fluff cloth.
Maintenance Procedures
Page 9
Building Ref
Vol
Sect
Page
1.2.1
EM
10
4. Clean the isolating contact plugs, using a carbon tetrachloride or silver polish, and under no circumstances abrasive material. Apply a thin film of silicon grease or petroleum jelly. 5. Clean and lubricate all moving surfaces of the position selector mechanism, including wheels, track and operating handle mechanism. Distribution and Branch Circuit Panelboards Quarterly Note: Advice and program with management, before carrying out tests, operation or repairs on any panel-board. 1. Visually check all MCCBs and/or isolators for any signs of arcing, burning or overheating. Carry out repairs as necessary. 2. Test any residual current devices (RCDs) where available by using their integral test mechanism. 3. Check contactors for undue noise or overheating. Check indicator lights and push buttons. 4. Clean out dust and debris from the individual items of equipments with the aid of a vacuum cleaner. 5. Check the loading of all outgoing circuits and record readings. Bi-annually 1. Carry out tasks as detailed Quarterly. 2. Check the operation of all breakers, isolators, RCDs etc. and ensure mechanisms are working in order. Correct any defaults. 3. Check that the rating of the MCCB is correct with regard to loading cabling, type of load etc. with particular reference to design data. Report any overloading and/or loads that are up to the set rating of the breaker. Report need for adjustment. 4. Check for proper fixation of all circuit breakers, security of all electrical termination and connections, and tighten as necessary. 5. Check that all barriers and guards are in place and secure. Adjust as necessary. 6. Check that all trunking, conduit or cable gland terminations associated with the panel are secure. Adjust as necessary. 7. Check that doors can be securely closed. If a lock is provided, check that it functions correctly. 8. Ensure that 380Volt and other warning labels are in position where applicable. 9. Check that phase discs and labels giving the panel and circuit references are securely fixed to the enclosure door. Replace or provide any missing items and update information as necessary. Annually 1. Carry out tasks as detailed Bi-Annually. 2. Test earth continuity of incoming supply circuit and measure loop resistance of each panelboard. 3. Check all exposed cable insulation for signs of damage inside each panelboard. Correct any defects. 4. Check enclosures for paint work condition and signs of corrosion. Correct any defects. 5. With a 500V Megger, test insulation resistance between busbars, and between busbars and earth. (N.B. All circuit breakers must be in Open position),
Maintenance Procedures
Page 10
Building Ref
Vol
Sect
Page
1.2.1
EM
11
6. Select at random two circuit breakers out of each panelboard and test its timecurrent curve using appropriate current injection test instrument. Report any discrepancies. (Tests are to be carried out in accordance to NFPA 70B, section 1810, 2.4). 2.3.2 Maintenance Procedures (Corrective) Circuit Breakers General Circuit breakers interrupt electrical current to stop power flow both for switching operations and during fault conditions. Molded case circuit breakers are usually located in low voltage distribution panels and in control boards. These are typically 120-volts alternating current (Vac), 125-volts direct current (Vdc), 240-Vac, and 480-Vac breakers for control, protection, and auxiliary power. Molded case breakers in panel boards should not be loaded more than 80% of rating per NFPA 70B, 11-2. Low voltage air breakers are usually located in motor starter cabinets, motor control centers, station service switchgear, or similar enclosures. These are typically 480 Vac for auxiliary power. Most breaker maintenance (except infrared scanning) must be performed with equipment de-energized. 2.3.3 Maintenance Hazards
2.3.4
Disposal Instructions
Maintenance Procedures
Page 11
Building Ref
Vol
Sect
Page
1.2.1
EM
12
Oth er Ele ctric a l Low Vo lta g e Eq u ip m e nts , UPS , ATS , MCC, ECB, Cap a c ito r Ba n ks , Dim m in g S ys te m ) Maintenance Procedures (Planned) Static Uninterruptable Power Supply UPS Daily 1. Check the installation and operating conditions: distance from wall, ventilation inlet and outlet, vents free, operating temperature, especially for the batteries. 2. Check that no faults are signalled by the lights. 3. The battery is automatically checked by the equipment and it indicates if the batteries should be checked or a battery fault is present. 4. Check that all fans are working properly. 5. Check all the fuses, replace if necessary. 6. Check the thrusters of the charger. Annually 1. A complete check-up can be done only by qualified personnel certified by UPS Supplier. 2. Check the status of the batteries through regular test (no supply and temporarily load) 3. Check the maintenance by-pass switch 4. Check the operation of the UPS in both cases, once the electricity is ON and the other when electricity is OFF 5. Check Fans and Ventilation of the UPS 6. Check if no permanent fault appears at its control panel. Dimming Control Panel Annually: 1. 2. 3. 4. 5. 6. Check dimming and switches modules within the dimming panel. Check the setting of all presets switches regarding the scenes and channels. Check the interfaces with other systems such as fire alarm. Check overheating and the ventilation of the room housing the dimming panel. Clean using appropriate means the accumulated dust in the panels. Check all electrical connection
Power factor corrector (CAPACITOR) Monthly 1. Check the connection of capacitor bank to switchboards. 2. Check the good functioning of the switching of capacitor banks based on the variation of the loads. 3. Check the good operation of its control panel. 4. Test and inspect the improvement of power factor. 5. Clean the accumulated dust using appropriate cleaning means.
Maintenance Procedures
Page 12
Building Ref
Vol
Sect
Page
1.2.1
EM
13
Check all reactors Check all contactors Check all cables and connections Check manufacturer and installation settings Check alarm history Check out the right settings of the circuit breakers and fuses ratings according to the capacitor range
Building Ref
Vol
Sect
Page
1.2.1
EM
14
1. Test the transfer switchs automatic control system 2. Check the operation of manual by pass. 3. Inspect the cleanness of the switch. 2.4.2 Maintenance Procedures (Corrective) UPS (Uninterruptable Power Supply) General This section is provided for maintenance technicians. It is assumed that all are familiar with: The laws of electricity The hazards of working with electricity. The basic principles of hybrid diaode-thyristor rectifier bridge technology for battery application.
Equipment All diagnostic verification can be performed with a multi-meter. The multi-meter must have AC/DC, capability, good accuracy and in some cases, a test clamp attachment. Preliminary Checks Always perform a few preliminary checks before starting maintenance: General visual inspection of equipment (for signs of overheating or electric discharge). Make sure that power is available. Attempt to clear the fault by pressing the button RESET.
Corrective Action The charger systems are composed of easy to locate functional modules (power pack, display unit, etc.). Corrective maintenance will usually entail no than changing a module if it is diagnosed as malfunctioning. A minimum recommended set spares should be kept on hand. Typically, evaluation of the battery voltage/charger output relationship for the giver settings and charge curve will be sufficient to determine whether there is a malfunction. Keep the following in mind to make a rapid, reliable diagnosis: If the equipment is inoperable (for instance if it is not powered), the charge should still operate with its basic functions.
Maintenance Procedures
Page 14
Building Ref
Vol
Sect
Page
1.2.1
EM
15
1. Measurement 2. Protection thresholds 3. Secondary charge curve function (equalization, etc.) Overcharging is usually the result of a control unit malfunction. Undercharging or no charging usually results from a power pack failure (mains fuse, circuit breaker, etc.) or, much rarely, from a control unit failure. 2.4.3 Maintenance Hazards Batteries have to be carefully maintained, frequent visual inspection for spill and bloating of batteries shall be carried out regularly. Cleaning of Corrosion on the enclosure has to be carried out to avoid accumulation. Electrical Hazards Battery systems present a risk of electrical shock and high short circuit currents. The following precautions should be observed when installing and maintaining batteries: 1. Remove all personal metal objects (watches and rings). 2. Use insulated tools, Wear full eye protection and rubber gloves. 3. Observe circuit polarities.(do not make or break live circuits) 4. Prior to handing batteries on a metal rack, assure the battery is not inadvertently grounded by measuring the voltage between the battery and the rack. It should be zero. If not, determine the cause and correct prior to proceeding. Fire, Explosion and Heat Hazards Lead acid batteries can contain an explosive mixture of hydrogen gas which can vent under overcharging conditions. Do not smoke of induce sparks in the vicinity of the battery. Do not install and charge batteries in a seals container. Mount the individual batteries with 0.5 inches of space between the batteries to allow for convection cooling. If contained, assure the container or cabinet and room have adequate ventilation to prevent an accumulation of potentially vented gas.
Maintenance Procedures
Page 15
Building Ref
Vol
Sect
Page
1.2.1
EM
16
Any Gelled or liquid emissions from Battery is electrolyte which contains dilute sulphuric acid which is harmful to the skin and eyes; is electrically conductive; and is corrosive. If electrolyte contacts the skin, wash immediately and thoroughly. If electrolyte enters the eyes, wash thoroughly for 10 minutes with clean water or a special neutralizing eye wash solution and seek immediately medical attention. Neutralized any spilled electrolyte with the special solutions contained in a spill kit or with a solution of 1lb. Bicarbonate of soda to 1 gallon of water. Refer to the current issue of the national Electrical Code. 2.4.4 Disposal Instructions ENVIRONMENTAL COMPATIBILITY, DISPOSAL Environmental concerns during development In contrast to earlier UPS devices, the number of components has been greatly reduced through the use of highly integrated components and modular construction. As a result, energy consumption during production is reduced. Particular attention was paid to reducing the volume, mass and variety of metals and plastics used. Environmental compatibility was an important criterion in the selection of parts obtained from vendors. Environmental concerns during production Components obtained from vendors are delivered primarily in reusable packaging. ASIC components and SMD elements are used on the flat component groups. Production is emission free. Environmental concerns for disposal The device can be stripped down into recyclable mechanical components with screw and snap connections. Within the area of the EU, disposal should be carried out by a certified disposal company. In other countries local regulations must be observed.
Maintenance Procedures
Page 16
Building Ref
Vol
Sect
Page
1.2.1
EM
17
2.5
2.5.1
Weekly 1. Visually inspect all luminaires to ensure that they remain clean. 2. Check all lighting units and replace any failed lamps, using same type, size and rating. 3. Correct any defective floodlight/luminaire immediately. Replace worn seals or gaskets and broken glass fronts or covers where required. Monthly 1. Carry out tasks as detailed Weekly. 2. Check all circuits for proper function and correct any defective ones immediately (breakers are ON, power is available to all circuit outlets and visual inspection of wiring, fixing, support, etc.). 3. Clean all luminaires and floodlights externally only with a damp cloth or sponge. An antistatic solution can be used. 4. Simulate mains failure condition on non-maintained emergency lighting units by putting off the power supply for a short period, to ensure correct functioning. Correct or replace any defective unit immediately. 5. Ensure correct operation of remote or local control where applicable. 6. Check incandescent lighting fixtures and re-lamp at 2000 hours running time as applicable to type of lamps. Note: Ladders or mobile low height lifters may be required.
Maintenance Procedures
Page 17
Building Ref
Vol
Sect
Page
1.2.1
EM
18
1. Carry out tasks as detailed for Monthly. 2. Check local switches (were provided) for correct operation and check security of switches and plates. Correct any defects. 3. Check cable and terminal exterior conditions to luminaires or floodlights. Replace any defective equipment. Correct as necessary or replace devices. 4. Visually inspect socket outlets and weatherproof plates for broken, damaged or deteriorated parts. 5. Inspect disconnect switches for proper fixation, loose springs, breaks or cracks in insulation, signs of flash over, clamps and straps, loose connections, blades and contacts, locking and interlocking mechanism, cable insulation for signs of overheating. Correct as necessary. Annually 1. Carry out tasks as detailed for Bi-Annually. 2. Re-lamp all fluorescent luminaires and metal halide floodlight in public spaces using same type, size and rating of lamps respectively. 3. Dispose of all lamps in a clean and safe professional manner. (Discharge lamps contain toxic substances. Wear protective gloves for this task). 4. Check security of all fixings, suspensions, poles, supports and cable termination, etc. and correct any defects. 5. Clean down all luminaires using compatible cleaning agent, damp cloth and rinsing where necessary, then dry up with dry cloth. 6. Examine lamp holders, sockets, fuses, fuse carriers or holders, control gear, cables and terminations, and internal wiring for signs of overheating and corrosion. Replace any defective component. 7. Check insulation resistance of socket outlet circuits (taking a minimum of two socket outlets) using a megger 500V. (Insulation resistance should not be less than 0.5 mega-ohms). Check continuity of earth conductors. 8. Test insulation resistance of disconnects switch circuit and continuity of earth conductors. 9. Carry out painting of all supports, brackets and poles. 10. Re-lamp all lighting fixtures with high pressure mercury vapour lamps (below 150W only) using same type, size and rating of lamps where applicable in public areas after every 1000 hours, elsewhere when 20% of lamps are burnt. Two-yearly 1. Carry out tasks as detailed for Bi-annually. 2. Test insulation resistance of all lighting circuits selected on random basis (shall not be less than 0.5 mega-ohms) earth continuity and check condition of insulation, conduits, flexible conduits, and connections at junction boxes and at luminaries. 3. Re-lamp all high pressure sodium fixtures and luminaries (150W and over) using same type, sizing and rating of lamps. 2.5.2 Maintenance Procedures (Corrective) When a defect in the system is discovered or reported, the defect should be recorded in a maintenance logbook and the appropriate action taken to remedy the defect as soon as practicable.
Maintenance Procedures
Page 18
Building Ref
Vol
Sect
Page
1.2.1
EM
19
A thorough inspection should always be carried out as soon as possible following a circuit fault. All equipment should be positively isolated and checked to ensure that the supply has been de-energised before any work is carried out on it. 2.5.4 Disposal Instructions Disposal of Exhausted Lamps - Fluorescent Lamps Small quantities of linear and compact fluorescent tubes should be broken in the packaging provided with the new lamps, if at all possible, and then disposed of as normal refuse. In the case of large quantities of fluorescent tubes, these must be disposed of in a suitable container and disposed of in accordance with Local Regulations. Care must also be taken, whether large or small quantities are being broken, to avoid flying glass. It is recommended that protective clothing, gloves and eye protectors be worn and the operation should be carried out in a well ventilated area. Fluorescent lamps are known to release a very small quantity of airborne dust when broken which has the potential to cause respiratory irritation in susceptible individuals. In such cases it is advisable to wear disposable filtered respiratory protection or preferably carry out the task in the open air. 2.5.5 Cleaning of Luminaires Diffusers and Plastic Controllers Note: Operatives undertaking the cleaning work should be well instructed and supervised to ensure continuing awareness of the fragility of the louvre optic. This awareness should be maintained throughout the cleaning work, when damage is most likely to occur, and be continued when handling and storing. Cleaning should be scheduled whenever necessary and co-ordinated with general maintenance if possible. Recommended procedures are as follows: (1) Wash in a solution of water and domestic detergent (2) Rinse with clean water after washing (3) Allow to dry (4) Apply an anti-static solution to prolong protection against dust contamination Paint Finished Surfaces Paint finished surfaces should be cleaned with a solution of water and domestic detergent applied with a cotton cloth. All surfaces should be wiped clean taking care not to scratch the paint finish. Satin Anodised Aluminium Surfaces Care must be taken when cleaning satin anodised aluminium surfaces, as it is only a surface finish and will be damaged if abrasive materials are used. Surfaces should be cleaned with a solution of water and domestic detergent applied with a cotton cloth. This will remove most stains
Maintenance Procedures
Page 19
Building Ref
Vol
Sect
Page
1.2.1
EM
20
EARTHING AND LIGHTNING P ROTECTION S YS TEM Maintenance Procedures (Planned) Earthing System Bi-annually 1. Check security of connections to main earth bar and tighten as necessary. 2. Check the integrity of all bonding connections and ensure that they remain secure and tight. 3. Check the integrity of the main neutral earthing connection at the L.V. switchgear neutral or at the transformer neutral. Ensure that a false leakage tripping will not occur. Note: Logbook is to be prepared for all inspection and testing procedures in which records will be kept. Electrode resistance is not to exceed 10ohm except for communication for which a maximum of 1.15ohm must be reached. Test is to be carried out with the power shut down. 4. Test electrode resistance between main earth bar and the electrode at the substation (once during the winter and once during the summer). 5. Inspect all the earthing installation for damage, deterioration and corrosion; check the conductor fixings for security, the connections for tightness and the continuity of earthing conductors. 6. Clean out all inspection pits and ensure lids fit correctly, and are appropriately marked as initially installed. Lightning Protection System Bi-annually 1. Check the fixings of conductors and components for security and check the installation for damage, deterioration and corrosion. 2. Ensure bonding of the lightning protection system to the main earth bars. 3. Check and verify that metallic structures are bonded to the lightning protection installation. 4. Test the electrical continuity of the conductors, bonds and joints. 5. Measure the resistance to earth of each earth rod or group of earth rods when disconnected from the installation. Compare the measured resistance with previous test results and investigate any significant change in resistance. 6. Measure the resistance of the installation o earth from random points in the installation. The resistance to the general mass of earth from any point of the complete installation should not normally exceed 10 ohms. 7. Record the situation of the installation, the measured earth electrode resistance, the individual earth rods or group of earth rods and the highest resistance measured at random points on the installation. 8. Clean out all inspection pits and ensure concrete lids fit correctly. 9. Inspect vertical down conductors and earth terminations. Check that conductors are securely fixed to the structure. 10. Check by air terminals, connections at air terminals or structures behaving as air terminals.
Maintenance Procedures
Page 20
Building Ref
Vol
Sect
Page
1.2.1
EM
21
Treatment of soil is needed by mixing additive chemicals. 2.6.3 Maintenance Hazards N/A 2.6.4 Disposal Instructions N/A 2.7 2.7.1 ELEVATOR S YS TEM Maintenance Procedures (Planned) Refer to Annex document 2.7.2 Maintenance Procedures (Corrective) Refer to Annex document 2.7.3 Maintenance Hazards Refer to Annex document 2.7.4 Disposal Instructions N/A
Maintenance Procedures
Page 21
Building Ref
Vol
Sect
Page
1.2.1
EM
22
2.8 2.8.1
MAINTENANCE S CHEDULE Introduction The schedules indicate the recommended intervals between routine maintenance tasks. Please note that these are for guidance only. The intervals stated may need to be varied depending upon the age of the plant, usage, etc. It is advisable to monitor plant operation regularly and maintain an up-to-date logbook. In this way, it will be possible to obtain a reliable indication of the amount of maintenance that the plant requires. It is important to remember that before work or inspection begins on any item of electrically operated plant, it must be isolated, preferably by removing the fuses in the control panel. Notices must also be posted advising others that the plant is being worked on. It should be noted that operation of the primary plant serving the works is controlled automatically by the Building Management System and may activate without warning at any time. Check before de-energising the plant whether it is interlinked with other plant (for example duty/standby fans), that may also need to be de-energised. A basic requirement of any piece of equipment that contains moving parts is correct lubrication. Reference should be made to the manufacturers literature and the lubrication schedule contained in this manual for details. Failure to lubricate as recommended will lead to a shortened plant life and premature failure. Systems will have been balanced to their correct design rates by commissioning engineers. Therefore if it is necessary to alter the set position of a valve, duct damper, etc. or to adjust the speed on a variable speed motor these must all be restored to their previous settings when the maintenance work is complete.
Maintenance Procedures
Page 22
Building Ref
Vol
Sect
Page
1.2.1
EM
23
2.8.2
MEDIUM VOLTAGE S WITCH GEARS AND P OWER TRANS FORMERS 13.8KV 2.3.0 LOW VOLTAGE MAIN DIS TRIBUTION BOARDS AND DIS TRIBUTION P ANEL BOARDS 380/230V ELECTRICAL LOW VOLTAGE EQUIPMENTS, UPS, ATS, MCC, ECB, CAPACITOR BANKS, DIMMING SYSTEM. LIGHTING AND SMALL POWER SYSTEM. 2.4.0
2.5.0
LEGEND Frequency
D Daily
W Weekly
M Monthly
Q Quarterly
A Annually
Maintenance Procedures
Page 23
Building Ref
Vol
Sect
Page
1.2.1
EM
24
Check
Main protective devices Regional electricity Supply voltage MCCB/MCB
Remedial Action
Check main protective devices. Wiring fault may have tripped breaker. Investigate fault, repair, test and reset protective device. Consult regional electricity company. Check if voltage at source is low and consult regional electricity company. Reset or replace MCCB/MCB as necessary. Check actual current drawn at distribution board is equal to or less than the design current. Check and reduce loading as necessary. Consult electrical engineer for advice if wiring/distribution system requires to be upgraded to meet increased demand Check phases are correct. Check loads are evenly balanced across all phases. Balance single phase loads across phases where necessary. Check all connections at MCCB/MCB distribution boards and re-terminate cables as necessary.
Failure of supply
Insufficient voltage
Sub-main current
Circuit load
Phases
Phases
Loss of continuity
Broken termination
Maintenance Procedures
Page 24
Building Ref
Vol
Sect
Page
1.2.1
EM
25
2.9.2
Check that the interlocking selector is in the Operation position. Turn the operating handle clockwise. Check that the switch is in the closed posit
Switch-disconnector cannot be opened. Switch-disconnector cannot be moved to the earthed position. Switch-disconnector cannot be moved from the open to earthed position. Cable compartment door will not open or close. Switch-fuse cubicle
Check that the interlocking selector is in the Operation position. Turn the operating handle anti-clockwise. Check that the switch is in the open position. Check that the interlocking selector is in the Test position. Turn the operating handle clockwise. Check that the switch is in the earthed position. Check that the interlocking selector is in the Test position. Turn the operating handle clockwise. Check that the switch is in the earthed position. Check that the interlocking selector is in the Door open position. If the switch is in the open position due to a fuse trip or motor operation, the notch on the operating shaft is to be turned downwards before the switch can be operated to the closed position. Check to see if a fuse has blown.
The switch-fuse has not operated even though a fuse has blown. Circuit-breaker cubicle
Check that the fuse is correctly fitted so that the trip pin indicator is pointing upwards.
Check that the switch is in the earthed position. The cable compartment door will not open. Check the interlocking selector is in the Door open position. Remove the key from the circuit-breaker before opening or closing the door. Ensure that the closing spring is fully charged, and that the interlocking coil is not energised The circuit-breaker will not go to the closed position. Check that the circuit-breaker key is in place and turned to the correct operating position. Check that the circuit-breakers auxiliary voltage plug is properly locked into the socket. Check that the control pin is on its position (HD4/S & VD4/S) Action Instrument Transformers Secondary measurements from the current transformers are not possible. Check that all shorting links on the secondary terminals of the current transformers have been removed.
Maintenance Procedures
Page 25
Building Ref
Vol
Sect
Page
1.2.1
EM
26
2.9.3 Fault
Ge n e ral Lig h tin g Possible Cause MCB tripped. Switch failure. Remedial Action Refer to MCB Trips fault Check connections to switch and renew if necessary. Check all connections to the distribution board. Conduct a capacitance ratio test to locate the approximate location of the break and renew the faulty section of cable. Check condition of lamp and control gear and renew as necessary. Refer to Troubleshooting Electrical Submain above. Check condition of luminaires for excess current drawn. Test and renew MCB if necessary. Check and renew switch if necessary. Check security of connections and re-tighten any that are loose. Investigate fault and remedy. Test cabling and return circuit breaker to the energised state.
Circuit continuity.
Equipment fault. Sub-mains failure. Equipment fault. MCB fault. Group of luminaires not functioning. Single luminaire not functioning. Luminaires in an area of the building not functioning. Two lamps within a four lamp luminaire are not functioning. Luminaire appears to be humming. Faulty local switch. Loose connection within luminaire. Fault in final circuit wiring has caused circuit breaker to trip. Usually each electronic ballast serves two lamps (one ballast per two lamps). If one lamp is defective, the other cannot function. Faulty ballast.
MCB Trips.
Maintenance Procedures
Page 26
Building Ref
Vol
Sect
Page
1.2.1
EM
Equipment Schedules
Page 1
Building Ref
Vol
Sect
Page
1.2.1
EM
Panel Ref
Part Identification
15636 15775 15779 16481 16483 24337 24351 24353 24354 24356 24403
Manufacturer
Local Source
MG Current Transformer (Ue.720V/ SC.5A/ IP20/ 1.2 In/ IEC.441)- 0 ~ 1000A C60N 2Pole MCB (Icu-10kA/415VIEC947,Class-3/ 30C/ C-curve)- 16Amps C60N 3Pole MCB (Icu-10kA/415VIEC947,Class-3/ 30C/ C-curve)- 20Amps C60N 3Pole MCB (Icu-10kA/415VIEC947,Class-3/ 30C/ C-curve)- 32Amps C60N 3Pole MCB (Icu-10kA/415VIEC947,Class-3/ 30C/ C-curve)- 40Amps C60N 3Pole MCB (Icu-10kA/415VIEC947,Class-3/ 30C/ C-curve)- 63Amps C60N 1Pole MCB (Icu-10kA/240VIEC947,Class-3/ 30C/ C-curve)- 16Amps
Equipment Schedules
Page 2
Building Ref
Vol
Sect
Page
1.2.1
EM
Panel Ref
Part Identification
24404 24405 24406 24407 24975 25001 25003 25004 26556 26588 26860 28052 28100 28101 29450
Manufacturer
Local Source
C60H 3Pole MCB (Icu-15kA/415VIEC947,Class-3/ 30C/ C-curve)- 32Amps C60H 3Pole MCB (Icu-15kA/415VIEC947,Class-3/ 30C/ C-curve)- 40Amps Vigi modules adaptable MCB-C60 3Pole 32~63 Amps- Sensitivity- 30mA Vigi modules adaptable MCB-C60 3Pole 0~25 Amps- Sensitivity- 30mA RCBO type MCB C60H (10kA/ IEC1009.2.2.Icu.30C), 30mA N+ 20 Amps Rotary Handle extended use to Moulded Case Circuit Breaker type NS80H NS80H 3Pole MCCB Magnetic Trip Unit (70kA/415V-IEC 947.2)- 80Amps NS80H 3Pole MCCB Magnetic Trip Unit (70kA/415V-IEC 947.2)- 50Amps Auxiliary contact for (IEC-60947) MCCBNS/NSX 100/630- OF/ SDE/ SDV
Equipment Schedules
Page 3
Building Ref
Vol
Sect
Page
1.2.1
EM
Panel Ref
Part Identification
33004 33011 33108 33220 33240 33513 33546 33558 33564 33576 33598 33599 33661 33878 54444
Manufacturer
Local Source
NS 3P MCCB Adjustable 630bN (50kA/440VIEC947/Micro.5.0)- 630Amps NS 3P MCCB Adjustable1000N (50kA/440VIEC947/Micro.5.0)- 1000Amps NS 3P MCCB Adjustable1250N (50kA/440VIEC947/Micro.5.0)- 1250Amps External sensor MCCB-NS, earth-fault protection (TCE): CT - 400/1600A Top front connection / circuit breaker 3P Fixed MCCB-NS- 630/1000 Amps Bottom front connection/ circuit breaker 3P Fixed MCCB- 630/1000 Amps Shunt trip coil for (IEC-60947-2/ 0.7xUn) MCCB-NS 800/3200-130V AC/DC Rotary Handle extended use to Moulded Case Circuit Breaker type NS 800/1600 Micrologic External Power supply module 220Volt AC/ 24 Volt DC output
Equipment Schedules
Page 4
Building Ref
Vol
Sect
Page
1.2.1
EM
Panel Ref
Part Identification
LV429338 LV429630 LV429631 LV429632 LV429634 LV429635 LV429636 LV429637 LV429740 LV430403 LV430630 LV430631 LV430632 LV430633 LV430830
Manufacturer
Local Source
NSX 3P MCCB Adjustable 100F (36kA/415VIEC947/ 40C/ TMD)- 25Amps NSX 3P MCCB Adjustable 100F (36kA/415VIEC947/ 40C/ TMD)- 16Amps NSX. 3P MCCB Magnetic Trip Unit 100F (36kA/415V/IEC947/MA)-100Amps NSX basic frame without trip 3P MCCB 160F (Icu-36kA/415V-IEC-60947.2) NSX 3P MCCB Adjustable 160F (36kA/415VIEC947/ 40C/ TMD)-160Amps NSX 3P MCCB Adjustable 160F (36kA/415VIEC947/ 40C/ TMD)-125Amps NSX 3P MCCB Adjustable 160F (36kA/415VIEC947/ 40C/ TMD)-100Amps NSX 3P MCCB Adjustable 160F (36kA/415VIEC947/ 40C/ TMD)- 80Amps NSX. 3P MCCB Magnetic Trip Unit 160F (36kA/415V/IEC947/MA)-150Amps
Equipment Schedules
Page 5
Building Ref
Vol
Sect
Page
1.2.1
EM
Panel Ref
Part Identification
LV431403 LV431406 LV431630 LV431631 LV431633 LV432678 LV432878 LV435104 LV435105 LV435106 LV435108 LV435109 LV4429035
Manufacturer
Local Source
NSX 3P MCCB Adjustable 400F (36kA/415VIEC947/ Micro.5.3A)-400Amps NSX 3P MCCB Adjustable 630F (36kA/415VIEC947/ Micro.5.3A)-630Amps NSX Thermal Magnetic Trip unit /IEC947/ 3Pole MCCB 100/250-100Amps NSX Thermal Magnetic Trip unit /IEC947/ 3Pole MCCB 100/250- 80Amps NSX Thermal Magnetic Trip unit /IEC947/ 3Pole MCCB 100/250- 63Amps NSX Thermal Magnetic Trip unit /IEC947/ 3Pole MCCB 100/250- 40Amps NSX Thermal Magnetic Trip unit /IEC947/ 3Pole MCCB 100/250- 32Amps NSX Thermal Magnetic Trip unit /IEC947/ 3Pole MCCB 100/250- 32Amps
Equipment Schedules
Page 6
Building Ref
Vol
Sect
Page
1.2.1
EM
Panel Ref
Replacement Part Details VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 00.75 KW VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 11.00 KW VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 15.00 KW VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 18.50 KW VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 22.00 KW VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 37.00 KW VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 45.00 KW VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 55.00 KW VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 240V- 00.75 KW VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 02.20 KW VFD (Altivar-61/ IEC947/ IP20) Electronics Motor Control- 480V- 03.00 KW
Part Identification ATV61H075N4 ATV61HD11N4 ATV61HD15N4 ATV61HD18N4 ATV61HD2 2N4 ATV61HD37N4 ATV61HD45N4 ATV61HD55N4 ATV61HU15M3 ATV61HU22N4 ATV61HU30N4
Manufacturer
Local Source
Equipment Schedules
Page 7
Building Ref
Vol
Sect
Page
1.2.1
EM
Panel Ref
Part Identification
ATV61HU40N4 ATV61HU55N4 ATV61HU75N4 GV2AP01 GV2L04 GV2L06 GV2L07 GV2L08 GV2L10 GV2L14 GV2L16 GV2L20 GV2L22 GV2L32
Manufacturer
Local Source
GV2-L06 3P Magnetic Trip Unit 100kA/ 415V/ IEC-947/ AC.3- 1.6 Amps GV2-L07 3P Magnetic Trip Unit 100kA/ 415V/ IEC-947/ AC.3- 2.5 Amps GV2-L08 3P Magnetic Trip Unit 100kA/ 415V/ IEC-947/ AC.3- 4.0 Amps GV2-L10 3P Magnetic Trip Unit 100kA/ 415V/ IEC-947/ AC.3- 6.3 Amps GV2-L14 3P Magnetic Trip Unit 100kA/ 415V/ IEC-947/ AC.3- 10 Amps GV2-L16 3P Magnetic Trip Unit 50kA/ 415V/ IEC-947/ AC.3- 14 Amps GV2-L20 3P Magnetic Trip Unit 50kA/ 415V/ IEC-947/ AC.3- 18 Amps GV2-L22 3P Magnetic Trip Unit 50kA/ 415V/ IEC-947/ AC.3- 25 Amps GV2-L32 3P Magnetic Trip Unit 50kA/ 415V/ IEC-947/ AC.3- 32 Amps
Equipment Schedules
Page 8
Building Ref
Vol
Sect
Page
1.2.1
EM
Panel Ref
Part Identification
GVAD1010 K1F027MLH LA9D11502 LA9D4002 LAD8N20 LAD9R1 LADN22 LC1D09F7 LC1D115F7 LC1D12F7 LC1D18F7 LC1D18M7
Manufacturer
Local Source
DP,ECB,EDP, Mounting for LC1-D 09/32 EDLP,ELP,EMCP.MCC, LC1 front mounting instantaneous auxiliary EPP,ESDP,LP,PP,UDP, contact blocks- 02-NO + 02-NC UPP,UPS Panel,USDP
LC1-D 3P Contactor (690V/IEC.947/ AC-3/ 50) coil 110Volt/ 60Hz- 09 Amps LC1-D 3P Contactor (690V/IEC.947/ AC-3/ 50) coil 110Volt/ 60Hz-115 Amps LC1-D 3P Contactor (690V/IEC.947/ AC-3/ 50) coil 110Volt/ 60Hz- 12 Amps LC1-D 3P Contactor (690V/IEC.947/ AC-3/ 50) coil 110Volt/ 60Hz- 18 Amps LC1-D 3P Contactor (690V/ IEC947/ AC-3/ 50) coil 220Volt/ 60Hz- 18 Amps
Equipment Schedules
Page 9
Building Ref
Vol
Sect
Page
1.2.1
EM
10
Panel Ref
Part Identification
LC1D25F7 LC1D32F7 LC1D32M7 LC1D40F7 LC1D50F7 LC1D65M7 LC1D80F7 LC1D80M7 LR9D5367 LR9D5369 LRD04 LRD06
Manufacturer
Local Source
LC1-D 3P Contactor (690V/ IEC947/ AC-3/ 50) coil 220Volt/ 60Hz- 65 Amps LC1-D 3P Contactor (690V/IEC.947/ AC-3/ 50) coil 110Volt/ 60Hz- 80 Amps LC1-D 3P Contactor (690V/ IEC947/ AC-3/ 50) coil 220Volt/ 60Hz- 80 Amps LR9D Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 60-100 Amps LR9D Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 90-150 Amps LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 0.40~0.63 A LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 1.0~1.6 Amps
Equipment Schedules
Page 10
Building Ref
Vol
Sect
Page
1.2.1
EM
11
Panel Ref
Part Identification
LRD07 LRD08 LRD10 LRD12 LRD14 LRD16 LRD21 LRD22 LRD3353 LRD3355 LRD3357 LRD3361 LRD3363 RM4TR32 RXZE2M114
Manufacturer
Local Source
LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 12~18 Amps LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 16~24 Amps LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 23~32 Amps LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 30~40 Amps LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 37~50 Amps LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 55~70 Amps LRD Thermal Over Load Relay (IEC947/ Class-10A) adjustable- 63~80 Amps Voltage Monitoring Relay (AC15. 3A) 3Phase 50/60Hz- 380/440 Volt 14 - Pin plug miniature control relay (IEC255.1) base for 250V/ 10Amps
Equipment Schedules
Page 11
Building Ref
Vol
Sect
Page
1.2.1
EM
12
Panel Ref
Part Identification
VW3A1102 VW3A1104R50 VW3A1105 VW3A4551 VW3A4552 VW3A4553 VW3A4554 VW3A4555 VW3A4556 XB4BA21 XB4BA31 XB4BA42 XB4BD21 XB4BD33
Manufacturer
Local Source
VFD Harmonice current reduction Line Chokes- ATV61HD11 - HD15N4 VFD Harmonice current reduction Line Chokes- ATV61HD18 - HD22N4 VFD Harmonice current reduction Line Chokes- ATV61HD30 - HD55N4 Push Button spring return(22mm/ IEC/EN.947/IP66/AC-15) 1N/C Black color Push Button spring return(22mm/ IEC/EN.947/IP66/AC-15) 1N/O Green color XB4BA31 Push Button spring return(22mm/ IEC/EN.947/IP66/AC-15) 1N/C Red color Selector Switch Standard - Off-ON 2Position (IEC-947.5/ IP66/4X) 1contact Selector Switch Standard - A-0-M 3Position (IEC-947.5/ IP66/4X) 1contact
Equipment Schedules
Page 12
Building Ref
Vol
Sect
Page
1.2.1
EM
13
Panel Ref
Part Identification
XB4BS542 XB4BVG1 XB4BVG3 XB4BVG4 XB4BVM4 XB4BVM5 XB4BVM6 ZBE101 ZBE102 ASK31.3/100 ASK31.3/150 ASK31.3/200 ASK31.3/250
Manufacturer
Local Source
Pilot- Lamp Integral LED bulb (IEC-60947.5/ IP66) -195~264Volt Yellow Pilot- Lamp Integral LED bulb (IEC-60947.5/ IP66) -195~264Volt Blue color Auxiliary contact for Normally Open use to extension for selector switch Auxiliary contact for Normally Closed use to extension for selector switch ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~100Amps ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~160Amps ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~200Amps ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~250Amps
Equipment Schedules
Page 13
Building Ref
Vol
Sect
Page
1.2.1
EM
14
Panel Ref
Part Identification
ASK31.3/30 ASK31.3/40 ASK31.3/50 ASK31.3/80 ASK41.4/400 ASK51.4/600 ASK81.4/100 ASK81.4/120 FQ0207-1000/5 FQ0207-1250/5
Manufacturer
Local Source
ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~400Amps ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~600Amps ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~1000Amps ASK Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: 2.5xIth)- 0~1250Amps FQ Ammeter/ M. Iron/ Class 1.5/ IEC 521/ Scale 90/ 96x96mm- 0~1000Amps FQ Ammeter/ M. Iron/ Class 1.5/ IEC 521/ Scale 90/ 96x96mm- 0~1250Amps
Equipment Schedules
Page 14
Building Ref
Vol
Sect
Page
1.2.1
EM
15
Panel Ref
Part Identification
FQ0207-200/5 FQ0207-250/5 FQ0207-400/5 FQ0207-500 FQ0207-630/5 39060 39061 39062 39064 39066 39068 39070 39084
Manufacturer
Local Source
Terminal block color Grey (EN-60715) 1single connection- 2.5 mm2 Terminal block color Grey (EN-60715) 1single connection- 4 mm2 Terminal block color Grey (EN-60715) 1single connection- 6 mm2 Terminal block color Grey (EN-60715) 1single connection- 10 mm2 Terminal block color Grey (EN-60715) 1single connection- 16 mm2 Terminal block color Grey (EN-60715) 1single connection- 35 mm2 Terminal block color Grey (EN-60715) 1single connection- 70 mm2 Terminal block color Grey (EN-60715) with blade type- 4 mm2
Equipment Schedules
Page 15
Building Ref
Vol
Sect
Page
1.2.1
EM
16
Panel Ref
Part Identification
39371 39372 39374 39376 39378 39403 39450 39451 39452
Manufacturer
Local Source
Terminal block color Green/Yellow (EN60715) 1connection- 16 mm2 Terminal block color Green/Yellow (EN60715) 1connection- 35 mm2 Terminal block color Grey end stoper standard - 8mm pitch rail. Terminal block color Grey (EN-60715) end caps standard- 2.5/4mm2 Terminal block color Grey (EN-60715) end caps standard- 6/10 mm2 Terminal block color Grey (EN-60715) end caps standard- 16/35 mm2
Equipment Schedules
Page 16
Building Ref
Vol
Sect
Page
1.2.1
EM
17
3.2 UPS SYSTEM Panel Ref Replacement Part Details MODEL 90NET/400
FUSE 1000A660V EXTRA FAST FUSE 2A 500V,2X32 DELAYED FUSE 500A 660V EXTRA FAST FUSE 6,3S, 500V, 2X32 DELAYED FUSE 800A,660V,EXTRA FAST IGBT H14, 800A, 1200V SCR 500A 1600V SCR/SCR 250A, 1600V RADIAL FAN DIODE 950A,1000V IGBT INTERFACE BOARD CAPACITOR 350VAC VARISTOR VARISTOR BOARD
Part Identification
Manufacturer
Local Source
SETRA
Equipment Schedules
Page 17
Building Ref
Vol
Sect
Page
1.2.1
EM
18
Part Identification
Manufacturer
Local Source
Equipment Schedules
Page 18
Building Ref
Vol
Sect
Page
1.2.1
EM
19
Part Identification
Manufacturer
Local Source
MG
PE12500201
Telemecanique Telemecanique MG (CDM) MG (CTC) SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC SCHNEIDER ELECTRIC Entrelec Entrelec Telemecanique Telemecanique Telemecanique CEWE
XB4BVBG33 XB4BVBG43 BBV22460 3985949A MGN 20545 PM820 CCEVA16662520 TCEC4A16688922 XB4BD53 XB4BG41 ZBE102 PE12500601 SCHNEIDER RIYADH INDUSTRIAL CITY 2
Equipment Schedules
Page 19
Building Ref
Vol
Sect
Page
1.2.1
EM
20
Panel Ref
Part Identification MG (CTC) MG (CTC) MG (DIPS) MG (DIPS) MG (DIPS) MG (CTC) MG (CTC) MG (CTC) MG (CTC) MG (CTC) WEIDMULLER ENTUS Entrelec SCHNEIDER ELECTRIC MG (CTC) MG (CTC) MG (PCR/PDM)
Manufacturer 25574919 9115658 51006538MO 51006538MO 51006538MO 398573A 877942Q1 VTJBS4B21F40 VTJBS4B21F40 VTJBS4B21F40 --K716060001 28851125 MGN61526 3731105 59636 S10MDT40J33TNT
Local Source
MV CUBICLE SM6
Equipment Schedules
Page 20
Building Ref
Vol
Sect
Page
1.2.1
EM
21
Panel Ref
Part Identification MG (CDM) MG (CTC) MG (CTC) MG (CTC) MG (Voiron) MG (Voiron) Entrelec TELEMECANIQUE TELEMECANIQUE CEWE SCHNEIDER ELECTRIC Entrelec AVERA Telemecanique Telemecanique Telemecanique MG (PCR/PDM) CEWE
Manufacturer 59903 PE12501801 INTEGRAL PART 3985916A MGN61526 MGN61526 CCEVA16662520 XB4BG41 XB4BD53 PE12500601 PM820 TCEC4A16688922 -----XB4BVBG33 XB4BVBG43 XB4BVBG53 59642 PE12500601
Local Source
MV CUBICLE SM6
Current Transd,DI125, 1PH, 4.20mA,CT 5A, CL.0.5, VX=80 276VAC/DC DIGITAL POWER METER VOLTAGE TEST BLOCK, 4P SURGE ARRESTOR, 15kV LED PILOT LIGHT, GREEN, 24 130VDC, STYLE 4 LED PILOT LIGHT, RED, 24 130VDC, STYLE 4 LED PILOT LIGHT, YELLOW, 24 130VDC, STYLE 4 COMM. INTERFACE MODULE, 12/24VDC, RS485, 2 - WIRE Current Transd. DI125,1PH, 4.20mA,CT 5A, VX=80 276VAC/DC
Equipment Schedules
Page 21
Building Ref
Vol
Sect
Page
1.2.1
EM
22
Panel Ref
Local Source
MG
PE12500201
MV CUBICLE SM6
CT : 17.5/38/95kV, 1k=21kA/1sec. CT CORE 1: 200 400/5A, 15 30VA, CL 0.5 CT CORE 2: 200 400/5A, 7.5 15VA, CL. 5P10 HEATING RESISTOR, 50W, 220V AC LED PILOT LIGHT, GREEN, 24 130VDC, STYLE 4 CAPACITIVE VOLT INDICATOR ADD ON CONTACT, 1nc ILLUMINATED PB BODY, 400V AC, 1nc ILLUMINATED P.B. HEAD, RED AUX. RELAY 4c/o, 110VDC
MG
PE12500201
3736436 XB4BVBG33 59903 ZB2BE102 ZB2BW061 ZB2BW343 RXM4AB2FD RXM4AB2FD XB4BG41 Page 22
AUX. RELAY 4c/o, 110VDC STAY PUT SELECTOR SW., 2 POS., w/ KEY
Equipment Schedules
Building Ref
Vol
Sect
Page
1.2.1
EM
23
Panel Ref
Part Identification Telemecanique Telemecanique Telemecanique Square D Florence MG (CTC) MG (Vorion) MG (Vorion) MG (Vorion) MG (Vorion) MG (Vorion) Telemecanique Weidmuller Weidmuller Weidmuller Weidmuller Weidmuller Weidmuller
Manufacturer ZBE101 ZBE102 ZBE102 PM810 3985941A 24332 26924 26924 26927 MGN61526 XB4BVBG43 1020200000 1020200000 1020200000 1020300000 1020200000 1020200000
Local Source
MV CUBICLE SM6
Equipment Schedules
Page 23
Building Ref
Vol
Sect
Page
1.2.1
EM
24
Panel Ref
Part Identification Weidmuller Weidmuller Weidmuller Entrelec Entrelec Weidmuller MG (Vorion) MG (DOITD) MG (CTC) MG (CTC) MG (DIPS) MG (DIPS) MG (DIPS) Telemecanique Telemecanique Telemecanique ENTES MG (CTC) MG (Vorion) MG (Vorion)
Manufacturer 1020300000 105920000 105920000 CCEVA16662520 TCEC4A16688922 1020300000 08998 3736436 25574919 9115658 51006538M0 51006538M0 51006538M0 ZB2BE102 ZB2BW061 ZB2BW343 K716740003 3985973A 24332 26924
Local Source
MV CUBICLE SM6
SWITCH DISCONNECTING FUSE MV FUSE, 6.3A, 24kV, L=442mm MV FUSE, 6.3A, 24kV, L=442mm MV FUSE, 6.3A, 24kV, L=442mm ADD ON CONTACT, 1nc. ILLUMINATED PB BODY, 400V AC, 1no ILLUMINATED P.B. HEAD, RED DIGITAL MULTI METER, Vx : 190 260VAC CM DISC. SW., 50A, 17.5kV, 21kA/1sec, (Inc. Cub) MINIATURE CB, 2A, 2P, 230/400VAC, C CURVE AUX. SWITCH 1C/O CONTACTS
Equipment Schedules
Page 24
Building Ref
Vol
Sect
Page
1.2.1
EM
25
Panel Ref
Part Identification
MG (Vorion) MG (Vorion) MG (Vorion) MG (CTC) MG (CTC) MG (CTC) MG (CTC) Weidmuller Weidmuller Weidmuller Entrelec Weidmuller CEWE MG (Vorion) Telemecanique Telemecanique
Manufacturer
26924 26927 MGN61526 877942Q1 VTJBS4B21F40 VTJBS4B21F40 VTJBS4B21F40 1020200000 1020200000 1020200000 TCEC4A16688922 1020200000 PE12500601 08998 XB4BD53 ZBE101
Local Source
MV CUBICLE SM6
Equipment Schedules
Page 25
Building Ref
Vol
Sect
Page
1.2.1
EM
26
Panel Ref
Part Identification
Telemecanique MG (CTC)
Manufacturer
ZBE101 3731105
Local Source
MG (CTC)
3731105
MV CUBICLE SM6
MG (CTC)
3731105
Equipment Schedules
Page 26
Building Ref
Vol
Sect
Page
1.2.1
EM
27
Panel Ref
Part Identification Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique Telemecanique
Manufacturer ZB2BW343 RXM040W RXM4AB2FD RXZE2S114M RXM040W RXM4AB2FD RXZE2S114M RXM040W RXM4AB2FD RXZE2S114M RXM040W RXM4AB2FD RXZE2S114M RXM4AB2FD RXM4AB2FD RXM4AB2FD RXM4AB2FD XB4BG41 ZBE101 ZBE102 ZBE102 ZBE102
Local Source
MV CUBICLE SM6
PROTECTION MODULE, 6 TO 250VDC DIODE AUX. RELAY 4c/o, 6A, 110VDC BASE SOCKET FOR RXM4 SEPARATE AUX. RELAY 4c/o, 6A, 110VDC AUX. RELAY 4c/o, 6A, 110VDC AUX. RELAY 4c/o, 6A, 110VDC AUX. RELAY 4c/o, 6A, 110VDC STAY PUT SELECTOR SW., 2 POS., w/ KEY ADD ON N.O. SWITCH ADD ON N.C. SWITCH ADD ON N.C. SWITCH ADD ON N.C. SWITCH
Equipment Schedules
Page 27
Building Ref
Vol
Sect
Page
1.2.1
EM
28
Panel Ref
Local Source
MG (CTC) MG (CTC) MG (CTC) MG (Vorion) MG (vorion) MG (vorion) MG (Vorion) MG (Vorion) MG (Vorion) MG (Vorion) MG (Vorion) Telemecanique AREVA AREVA AREVA MG (PCR/PDM) Weidmuller
ESDM1 3985252A 3985941A 24332 26924 26924 26927 MGN61526 26924 26927 MGN61526 XB4BVBG43 DDE9808005 DDE9808005 DDE9808005 59636 1020200000 SCHNEIDER RIYADH INDUSTRIAL CITY 2
MV CUBICLE SM6
Equipment Schedules
Page 28
Building Ref
Vol
Sect
Page
1.2.1
EM
29
Panel Ref
Part Identification
Weidmuller Weidmuller Weidmuller Weidmuller Weidmuller Weidmuller MG (PCR/PDM) Entrelec Entrelec Entrelec Entrelec Weidmuller Telemecanique
Manufacturer
1020200000 1020200000 1020200000 1020200000 1020200000 1020300000 59642 CCEVA16662520 TCEC4A16688922 CCEVA16662520 TCEC4A16688922 1020300000 XB4BVBG53
Local Source
MV CUBICLE SM6
TERMINAL WEMID DARK BEIGE, 1000V, 57A, 10 sq.mm COMM. INTERFACE MODULE, 12/24VDC, RS485, 2 WIRE CURRENT TEST BLOCK, 4P VOLTAGE TEST BLOCK, 4P CURRENT TEST BLOCK, 4P VOLTAGE TEST BLOCK, 4P TERMINAL WEMID DARK BEIGE, 1000V, 57A, 10 sq.mm LED PILOT LIGHT, YELLOW, 24 130VDC, STYLE 4
Equipment Schedules
Page 29
Building Ref
Vol
Sect
Page
1.2.1
EM
30
Part Identification MK/56891 BLK MK/56892 BLK MK/56420 WHI MK/56486 WHI MK/56482 WHI MK/56423 GRY MK/K5845 WHI MK/9762 BLU MK/K4896N WHI MK/K24331 WHI MK/56482 WHI MK/K9015 RED MK/K9215 RED MK/K9056 RED MK/K9766 RED MK/K24184 WHI K24371 WHI W K4893 WHI K24331 WHI K24357 WHI W Equipment Schedules
Manufacturer
Local Source
Page 30
Building Ref
Vol
Sect
Page
1.2.1
EM
31
PANEL REF
Replacement Part Details 13A 2G SP Switch Socket outlet,DE 13A 1G DP switch Socket Outlet,DE W/P 13A,Socket Unswitched,1G,white,IP56 32A 1Gang DP with Neon 20A DP 1w switch with Neon-1M 16A Cord Outlet-1M 2M Grid Plus Front Plate with Mounting Frame 1M Euro DataCom FrontPlate 4M Euro Datacom FrontPlate
Part Identification K24347 WHI W K24357 WHI W 56480 WHI K24305 WHI W K4896N WHI K4886 WHI K24332 WHI K24181 WHI K24184 WHI
MANUFACTURER
LOCAL SOURCE
Equipment Schedules
Page 31
Building Ref
Vol
Sect
Page
1.2.1
EM
Content
Installers Details Suppliers Details Reference Section from Project Specification Maintenance Service Agent details Maintenance Service Contracts Warranties & Bonds
Page
2 3 4 5 6 7
Maintenance Documentation
Page 1
Building Ref
Vol
Sect
Page
1.2.1
EM
Installers name MV Installation Drake & Skull Transformer Installation Drake & Skull Capacitor Installation Drake & Skull ATS Installation Drake & Skull Panel Boards Drake & Skull UPS System Drake & Skull Lighting System Drake & Skull
Maintenance Documentation
Page 2
Building Ref
Vol
Sect
Page
1.2.1
EM
4.2
Suppliers name MV Panels Schneider Electric Transformers Schneider Electric Capacitor Bank Aqesa ATS Aqesa MDB MESCO
Uday Kamath
Uday Kamath
+966507257497
Jefferey Almario
PP/ LP/ MCC/ DP/ DLP/ EDP/ EPP/ ESDP/ UDP/ UPP/ USDP/ EMCP/ELP MOTS ECB CEAG/SAUD LIGHTING EIB HONEYWELL
+966504151560 +96612651010 +96612653701 +96612653702 +966542923263
Mr.Fahad Al-Hobayb
Maintenance Documentation
Page 3
Building Ref
Vol
Sect
Page
1.2.1
EM
4.3
Product Name
MV Switchgear Transformers Power Panels Motor Control Panels Capacitors Transfer Switches Static Uninterruptible Power Supply Central Battery System Circuit Breakers Lighting Lighting Lighting controls Switch Boards Earthing System
Maintenance Documentation
Page 4
Building Ref
Vol
Sect
Page
1.2.1
EM
4.4
Product Name
Maintenance Documentation
Page 5
Building Ref
Vol
Sect
Page
1.2.1
EM
4.5
MAINTENANCE S ERVICE CONTRACTS For copies of the Maintenance Service Contracts along with the Service Agents contact details please refer to the following Table
Equipment
Telephone No.
Maintenance Documentation
Page 6
Building Ref
Vol
Sect
Page
1.2.1
EM
4.6
WARRANTIES & BONDS Copies of the following warranties and bonds are attached at the end of this section.
Equipment
Manufacturer
Maintenance Documentation
Page 7
Building Ref
Vol
Sect
Page
1.2.1
EM
S ECTION 5 TES T CERTIFICATES & COMMIS S IONING REP ORTS LIS T OF CONTENTS *
Item No.
5.1 5.1.1 5.1.2 5.1.3 5.1.4 5.1.5 5.2 5.2.1 5.2.2 5.2.3 5.2.4 5.2.5 5.2.6 5.2.7 5.2.8 5.2.9 5.3 5.3.1 5.3.2 5.3.3 5.3.4 5.4 5.4.1 5.4.2 5.5 5.5.1 5.6 5.6.1 5.7 5.7.1 5.8 5.8.1
LV DISTRIBUTION NETWORK
Low Voltage (LV) Switchgear Low Voltage (LV) Bus Duct Low Voltage Cables and Wires Switchboards Automatic Transfer Switch Disconnect Switch Main Distribution Boards Power Factor Correction (Capacitor) External Power Delivery Packages
UPS EQUIPMENT
Uninterruptible Power Supply Central Battery System Battery Rectifier/Charger
SMALL POWER
Lighting and Wiring Devices Emergency and Exit Lighting
EARTHING SYSTEM
Earthing System
*The Commissioning Forms which mentioned are Templates; the Test Certificates & Commissioning Reports will be submitted in Separate Binder/ Booklet. College of Arts, Humanities & Sciences (West Building) Test & Commissioning Records Page 1
Building Ref
Vol
Sect
Page
1.2.1
EM
Book n
Publication Ref.
A054-100 A054-101
ATS
EATON CORP/AQESA EMERSON/ASCO ADWAN A056-100 A056-101 A056-102
MDB/EMDB
MESCO EATON CORP/AQESA A057-100 A057-101
DLP
MOTS SETRAA AL-AMAL EATON CORP/AQESA ABB/HONEYWELL MESCO ECO A060-100 A060-101 A060-102 A060-103 A060-104 A060-105
DP
MOTS MESCO A061-100 A061-101
Manufacturers Literature
Page 1
Building Ref
Vol
Sect
Page
1.2.1
ECB
CEAG/Saudlighting RFPB/SCHNEIDER SETRAA/AL AMAL MESCO/COOPER COOPER A062-100 A062-101 A062-102 A062-103 A062-104
EDP
MOTS MESCO RFPB/SCHNEIDER SETRAA/AL AMAL HONEYWELL INARA ECO A063-100 A063-101 A063-102 A063-103 A063-104 A063-105 A063-106
ELP
MOTS MESCO RFPB/SCHNEIDER SETRAA/AL AMAL INARA HONEYWELL ECO A066-100 A066-101 A066-102 A066-103 A066-104 A066-105 A066-106
EIB
HONEYWELL ABB ECO A065-100 A065-101 A065-102
EMCP
MOTS MESCO RFPB/SCHNEIDER SETRAA/AL AMAL HONEYWELL SELCO ECO A068-100 A068-101 A068-102 A068-103 A068-104 A068-105 A068-106
EMCC
MOTS MESCO A070-100 A070-101
Manufacturers Literature
Page 2
Building Ref
Vol
Sect
Page
1.2.1
MCC
MOTS MESCO RFPB/SCHNEIDER SETRAA/AL-AMAL SELCO LOGSTRUP ECO A069-100 A069-101 A069-102 A069-103 A069-104 A069-105 A069-106
EPP
MOTS MESCO RFPB/SCHNEIDER SETRAA/AL-AMAL HONEYWELL ECO A071-100 A071-101 A071-102 A071-103 A071-104 A071-105
ESDP
MOTS RFPB/SCHNEIDER MESCO SETRAA/AL-AMAL A072-100 A072-101 A072-102 A072-103
LP/PP
MOTS MESCO RFPB/SCHNEIDER SETRAA/AL-AMAL ECO A074-100 A074-101 A074-102 A074-103 A074-104
UDP
MOTS MESCO RFPB/SCHNEIDER SETRAA/AL-AMAL ECO A076-100 A076-101 A076-102 A076-103 A076-104
UPP
MOTS A078-100
Manufacturers Literature
Page 3
Building Ref
Vol
Sect
Page
1.2.1
UPS
MOTS/CHLORIDE LIEBERT/EMERSON RFPB/CHOLRIDE SETRA-AL AMAL A079-100 A079-101 A079-102 A079-103
USDP
MOTS MESCO RFPB/SCHNEIDER SETRAA/AL-AMAL ECO A080-100 A080-101 A080-102 A080-103 A080-104
LRP
ABB HONEYWELL A082-100 A082-101
LIGHTING SYSTEM
ALADABRA LIGHTING ALISON BERGER ALKCO ARTEMIDE AUDREY PENDANT AXO LIGHT BEGA BEGA NARDEEN BELFER LIGHTING BOCCI LIGHTING BOOM (3.7.5) BRUCK LIGHTING CEAG COOPER LIGHTING CORELITE CRENSHAW LIGHTING CSL LIGHTING DELRAY DELTA LIGHT DESIGNPLAN-UK ECOSTA LIGHTING ECO-GREEN LIGHTING U.S.A. EDISON PRICE
Manufacturers Literature
Page 4
Building Ref
Vol
Sect
Page
1.2.1
EM
Manufacturers Literature
Page 5
Building Ref
Vol
Sect
Page
1.2.1
EM
6.5
Manufacturers Literature
Page 6