Sie sind auf Seite 1von 32

VI

Rules for Classification and Construction Additional Rules and Guidelines


Guidelines for the Performance of Type Approvals

Test Requirements for Electrical / Electronic Equipment and Systems

Edition 2012

The following Guidelines come into force on 1 September 2012. Alterations to the preceding Edition are marked by beams at the text margin. Germanischer Lloyd SE Head Office Brooktorkai 18, 20457 Hamburg, Germany Phone: +49 40 36149-0 Fax: +49 40 36149-200 headoffice@gl-group.com www.gl-group.com "General Terms and Conditions" of the respective latest edition will be applicable (see Rules for Classification and Construction, I - Ship Technology, Part 0 - Classification and Surveys). Reproduction by printing or photostatic means is only permissible with the consent of Germanischer Lloyd SE. Published by: Germanischer Lloyd SE, Hamburg

VI - Part 7 GL 2012

Table of Contents

Chapter 2 Page 3

Table of Contents

Section 1 A. B. C. D.

General Conditions Scope .......................................................................................................................................... Reference to other Rules and Regulations .................................................................................. Definitions .................................................................................................................................. Documents for Submission ......................................................................................................... 11111 1 1 1

Section 2 A. B.

Requirements to be met by the Products General ....................................................................................................................................... Environmental Categories .......................................................................................................... 2- 1 2- 1

Section 3 A. B.

Test Requirements General ....................................................................................................................................... Tests ........................................................................................................................................... 1. Visual inspection ............................................................................................................... 2. Performance test ................................................................................................................ 3. Power supply failure .......................................................................................................... 4. Power supply variations ..................................................................................................... 5. Cold ................................................................................................................................... 6. Dry heat ............................................................................................................................. 7. Damp heat .......................................................................................................................... 8. Salt mist ............................................................................................................................. 9. Vibrations .......................................................................................................................... 10. Inclinations ........................................................................................................................ 11. Flammability ...................................................................................................................... 12. Pressure test ....................................................................................................................... 13. Insulation resistance ........................................................................................................... 14. High voltage ....................................................................................................................... 15. Electrostatic discharge ....................................................................................................... 16. Electromagnetic fields ....................................................................................................... 17. Conducted fast transients (burst) ........................................................................................ 18. Conducted high frequency interference ............................................................................. 19. Conducted slow transients (surge) ..................................................................................... 20. Conducted low frequency interference (harmonics) .......................................................... 21. Conducted emissions ......................................................................................................... 22. Radiated emissions from enclosure port ............................................................................ 3- 1 3- 1 3- 1 3- 2 3- 2 3- 2 3- 3 3- 4 3- 4 3- 5 3- 6 3- 8 3- 8 3- 9 3- 10 3- 10 3- 10 3- 12 3- 14 3- 14 3- 16 3- 18 3- 20 3- 20

VI - Part 7 GL 2012

Section 1

General Conditions

Chapter 2 Page 11

Section 1 General Conditions

A.

Scope

C. 1.

Definitions Electric/electronic equipment

1. These Guidelines apply to electrical, electromechanical and electronic equipment, computers and peripherals. 2. The scope of the tests required for a specific product will be determined on a case by case basis by GL depending on the product, its use and the environmental category to which it belongs. 3. GL reserve the right, in justifiable cases, to request the performance of additional tests. 4. Electrical and electronic equipment on board ships, required neither by classification rules nor by international conventions, liable to cause electromagnetic disturbance shall be of a type which fulfils the test requirements of Section 3, B.21 and B.22.

Electric/electronic equipment are products such as systems, appliances or components which consist of mechanical, electrical and electronic parts and combinations thereof. 2. Computer systems

Computer systems are equipment or systems such as PC, workstation or programmable controls which specific functions are designated by application software. 3. Peripherals

Peripherals are devices such as monitors, keyboards, sensors or actuators which are necessary for process monitoring and control. 4. Equipment subject to type approval

B.

Reference to other Rules and Regulations

1. These Guidelines are based on the IACS Unified Requirements E10, "Testing Procedure for Electrical, Control and Instrumentation Equipment, Computers and Peripherals covered by Classification". 2. In connection with these Guidelines also apply the GL Guidelines for Procedure (VI-7-1) as well as the GL Rules for Electrical Installations (I-1-3) and Automation (I-1-4). 3. Navigation and radiocommunication equipment and systems will be tested and approved in accordance with IEC publication 60945 "Maritime navigation and radiocommunication equipment and systems, General requirements, Methods of testing and required test results". The relevant test and performance standards for specific equipment and systems like SOLAS 74 as ammended, IMO instruments and IEC or ISO Publications are to be observed. 4. Other standards may be recognised, provided that they are equivalent or higher graded.

Equipment subject to type approval refers to all products (systems, appliances and components) identified as such in the relevant Rules for Classification and Construction. 5. Environmental categories

Classification of equipment on the basis of the expected environmental conditions, with regard to the necessary test conditions (temperature, relative humidity, vibrations).

D.

Documents for Submission

1. Documents shall be submitted in accordance with the GL Guidelines for Procedure (VI-7-1), Section 3, B. 2. In addition, in the case of computers and computer systems, documents shall be submitted in accordance with the GL Rules for Electrical Installations (I-1-3), Section 10. 3. The lists contained in the above Regulations are by way of example. If necessary, further documents may be required.

VI - Part 7 GL 2012

Section 2

Requirements to be met by the Products

Chapter 2 Page 21

Section 2 Requirements to be met by the Products

A.

General

B.

Environmental Categories

The requirements to be met by the products in terms of design, choice of materials, functions and operational conditions are set out in the relevant Rules for Classification and Construction and associated Guidelines.

The products will be allocated to the environmental categories A to H. The assignment of the environmental categories to the test conditions is specified in Section 3, Table 3.34.

VI - Part 7 GL 2012

Section 3

Test Requirements

Chapter 2 Page 31

Section 3 Test Requirements

A. 1.

General Choice of equipment under test

Example of use: Equipment subject to the Rules for Classification and Construction except for the tests "Electrostatic Discharge, Conducted fast transients (burst) and Conducted slow transients (surge) ". performance criterion B: The EUT shall continue to operate as intended after the test. No degradation of performance or loss of function is allowed, as defined in the relevant equipment standard in the technical specification published by the manufacturer. During the test, degradation or loss of function or performance which is self-recoverable is, however, allowed, but no change of actual operating state or stored data is allowed. Example of use: Equipment not subject to the Rules for Classification and Construction and the tests "Electrostatic Discharge, Conducted fast transients (burst) and conducted slow transients (surge)" for equipment subject to the Rules. performance criterion C: Temporary degradation or loss of function or performance is allowed during the test, provided the function is self-recoverable, or can be restored at the end of the test by the operation of the controls, as defined in the relevant equipment standard and in the technical specification published by the manufacturer: Example of use: Equipment not subject to the Rules for Classification and Construction.

In the case of series-manufactured products, the equipment under test (EUT) shall be taken from the current production cycle. The choice of equipment under test shall be agreed with GL. If the equipment under test is a prototype, GL reserve the right to carry out subsequent comparative tests on series-manufactured products. 2. Test sequence

There is no pre-defined test sequence. Before the start of the tests, the manufacturer shall determine the sequence and notify GL accordingly. All the tests required for the product shall be performed on one equipment under test. Any alternative arrangements are subject to consent. 3. Procedure of immunity tests to electromagnetic environment

For these tests the EUT shall conform to its normal operational configuration, mounting and earthing arrangements and shall operate under mentioned test conditions. Particular interfaces of the EUT with the external electromagnetic environment are referred to as ports. The physical boundary of the EUT through which electromagnetic fields may radiate or impinge is the enclosure port. Differential tests (line/line) are those applied between electrical power, signal and control lines. Common mode tests (line/earth) are those applied between groups of lines and a common reference, normally earth. For the tests the results are evaluated against performance criteria relating to the operating conditions and functional specifications of the EUT, and defined as follows: performance criterion A: The EUT shall continue to operate as intended during and after the test. No degradation of performance or loss of function is allowed, as defined in the relevant equipment standard and in the technical specification published by the manufacturer.

B. 1.

Tests Visual inspection GL Rules for Classification and Construction and Additional Rules and Guidelines the manufacturer's specifications the design drawings the specified standards

The equipment under test is tested for conformity with:

Chapter 2 Page 32

Section 3

Test Requirements

VI - Part 7 GL 2012

1.1

Test procedure

3.

Power supply failure

Not specified 1.2 Test conditions

This test serves to demonstrate that on restoration of the power supply no damage is caused to the equipment under test and malfunctions occur. 3.1 Test procedure

According to the environmental category 1.3 General instructions for test performance

The visual inspection is carried out before commencement of type approval and shall be repeated as necessary after each stage of the test with a view to detecting visible damage to the equipment under test. 1.4 Test result

Not specified 3.2 Test conditions

The test is deemed to have been passed if the equipment under test meets the requirements of GL Rules for Classification and Construction and Regulations, as well as the requirements of the specification and the documentation and does not show evidence of any visible damage. 2. Performance test

In the case of electrical components, the tests are performed at the rated operational voltage Ue and, in the case of hydraulic/pneumatic components, at the rated control pressure. 3 interruptions within a 5-minute period 30 s pause between switching off and switching back on. General instructions for test performance

The functions (switching points, characteristic curves, self-monitoring, etc.) are to be demonstrated. 2.1 Test procedure

3.3 None 3.4

Basis: Rules for Classification and Construction, product specification. 2.2 Test conditions

Test result

The tests are performed at the rated operational voltage Ue. Table 3.1 External environmental conditions in the test laboratory
+ 15 C to + 35 C 30 % to 90 % 860 hPa to 1060 hPa

The test is deemed to have been passed if the specified functions are demonstrated, the results fall within the specified tolerance limits and no damage to the equipment under test is detected. 4. Power supply variations

Temperature Relative humidity Atmospheric pressure

This test serves to demonstrate that in the event of power supply variations no damage is caused to the equipment under test and no permanent or temporary malfunctions occur. 4.1 Procedure

2.3

General instructions for test performance

Not specified 4.2 Test conditions

The functions to be tested shall be performed in accordance with the requirements of GL Rules for Classification and Construction and Regulations and the characteristic features of the equipment under test. International testing standards for specific equipment e.g. measuring relays and protection equipment are to be observed and may require additional testing. 2.4 Test result

In the case of electrical components, the basis for the tests is the rated operational voltage Ue and, in the case of hydraulic/pneumatic components, the rated control pressure, in accordance with the equipment specification. Voltage- and frequency deviations refer to the system nominal voltage and frequency. The range of the system nominal voltage and frequency within the test conditions are fulfilled shall be specified.

The test is deemed to have been passed if the specified functions are demonstrated, the results fall within the specified tolerance limits and no damage to the equipment under test is detected.

VI - Part 7 GL 2012

Section 3

Test Requirements

Chapter 2 Page 33

Table 3.2

Electrical supply (alternating current)


Frequency deviation (permanent) + 5% 5% 5% + 5%

4.4

Test result

Voltage deviation (permanent) + 6% + 6% 10 % 10 %

The test is deemed to have been passed if the specified functions are demonstrated, the results fall within the specified tolerance limits and no damage to the equipment under test is detected. 5. Cold

Voltage deviation (short-term, 1,5 s) + 20 % 20 %

Frequency deviation (short-term, 5 s) + 10 % 10 %

This test serves to demonstrate that under the influence of cold no damage is caused to the equipment under test and no permanent or temporary malfunctions occur. 5.1 Test procedure

Basis: IEC publication 60068-2-1 Test A): for products inside the ship Test B): for products on the open deck or in cold areas. Test conditions

Table 3.3

Electrical supply (rectified alternating current)


10 %

Voltage deviation (permanent)

5.2 Table 3.4 Electrical battery supply for equipment connected to the battery during charging
Voltage deviation + 30 % 25 %

The functional tests are performed at the rated operational voltage Ue. Table 3.7 A) Products installed inside the ship
Test chamber conditions (Fig. 3.1) Temperature 5 C 3 C 2h

Table 3.5

Electrical battery supply for equipment not connected to the battery during charging
Voltage deviation

Test duration

Table 3.8

B) Products installed on the open deck or in cold areas


Test chamber conditions (Fig. 3.1)

+ 20 % 25 %

Temperature

25 C 3 C 2h

Table 3.6

Pneumatic/hydraulic power supply


Control pressure deviation + 20 % 20 % Test duration: 15 minutes per test

Test duration

5.3

General instructions for test performance

Before commencing the test an insulation resistance measurement shall be taken in accordance with test No. 13. The equipment under test is placed in the test chamber at room temperature and remains connected, but not switched on, during the cooling phase and throughout the test. During the final 60 minutes of the test functional tests shall be performed at test temperature.

4.3

General instructions for test performance

If the test duration is not specified, the test shall be performed until such time as a stationary condition is achieved.

Chapter 2 Page 34

Section 3

Test Requirements

VI - Part 7 GL 2012

Once the test is complete and the equipment under test has reached room temperature once again, a further functional test shall be performed, as well as, as a retest, the insulation resistance measurement in accordance with test No. 13.
30 20

Table 3.10

B) Products installed in areas with increased heat stress or on the open deck

Test chamber conditions (Fig. 3.2) Temperature Relative humidity at test temperature 70 C 2 C 50 % 16 h

Temperature [C]

10 0 -10 -20 -30 0 0,5 1

5 C Test

Test duration after the EUT has reached the test temperature

- 25 C Test
1,5 2 2,5 3 3,5

6.3

General instructions for test performance

Hours [h]

Fig. 3.1 Cold test cycle 5.4 Test result

The equipment under test is placed in the test chamber at room temperature and remains connected and switched on throughout the test. During the final 60 minutes of the test functional tests shall be performed Once the equipment under test has reached room temperature once again a further functional test shall be performed.
80 70 60 50 40 30 20 10 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 16 h 70 C Test 55 C Test

The test is deemed to have been passed if the specified functions are demonstrated, the values of the insulation resistance measurement fall within the specified tolerance limits and no damage to the equipment under test is detected. 6. Dry heat

This test serves to demonstrate that under the influence of dry heat no damage is caused to the equipment under test and no permanent or temporary malfunction occur. 6.1 Test procedure

Temperature [C]

Hours [h]

Fig. 3.2 Dry heat test cycle 6.4 Test result

Basis: IEC publication 60068-2-2 6.2 Test A): products without increased heat stress Test B): products with increased heat stress or on the open deck. Test conditions

The test is deemed to have been passed if the specified functions are demonstrated, the results fall within the specified tolerance limits and no damage to the equipment under test is detected. 7. Damp heat

The functional tests are performed at the rated operational voltage Ue. Note Equipment to be mounted in consoles or switchboards together with other equipment shall be tested in accordance with test B). Table 3.9 A) Products installed in areas without increased heat stress
Test chamber conditions (Fig. 3.2) Temperature Relative humidity at test temperature Test duration 55 C 2 C 50 % 16 h

This test serves to demonstrate that under the influence of damp heat no damage is caused to the equipment under test and no permanent or temporary malfunctions occur. 7.1 7.2 Test procedure Test Db Test conditions

Basis: IEC publication 60068-2-30

The functional tests are performed at the rated operational voltage Ue. Table 3.11
Temperature Relative humidity Test duration
1 For tolerances see Fig. 3.3

Test chamber conditions (Fig. 3.3)


55 C 2 C 95 % 1 2 test cycles 2 (12 + 12 h)

VI - Part 7 GL 2012

Section 3

Test Requirements

Chapter 2 Page 35

7.3

General instructions for test performance

Before commencing the test an insulation resistance measurement shall be taken in accordance with test No. 13. The equipment under test is placed in the test chamber at room temperature. The test should start before the first cycle with a stabilizing period with 25 C 3 C and at least 95 % humidity for maximum 1 hour remains connected and switched on throughout the first test cycle. During the second test cycle the equipment under test is switched off except for the functional tests. Functional tests shall be performed at test temperature within the first 2 hours of the first and the last 2 hours of the second test cycle.

Once the equipment under test has reached room temperature once again a further functional test shall be performed, as well as, as a retest, the insulation resistance measurement in accordance with test No. 13. 7.4 Test result

The test is deemed to have been passed if the specified functions are demonstrated, the results fall within the specified tolerance limits and no damage to the equipment under test is detected. 8. Salt mist

This test serves to demonstrate that under the influence of a saline atmosphere no damage (corrosion) is caused to the components of the equipment under test and no functional affections occur. This test is only performed on products which are to be installed on the open deck area.

100

96 % 95 % 90 % 15 min Functional tests 2h 80 % 95 % 15 min Functional tests 2h +57 C +53 C

Relative humidity [%]

90 80

60 55 50

40

Temperature [C]

Functional tests 2h 30 25 20 3h 12 h 0,5 h 6h +22 C 3h EUT connected and switched off except for functional tests 1 cycle = 24 h 24 30 Hours [h] 36 42 48 0,5 h +28 C

10

EUT connected and switched on 1 cycle = 24 h 6 12 18

Fig. 3.3 Damp heat test cycle

Chapter 2 Page 36

Section 3

Test Requirements

VI - Part 7 GL 2012

8.1 8.2

Test procedure Test Kb Test conditions

Basis: IEC publication 60068-2-52

the insulation resistance measurement fall within the specified tolerance limits. 9. Vibrations

The functional tests are performed at the rated operational voltage Ue. Table 3.12
Severity level Number of sprayings Storage period in damp chamber

This test serves to demonstrate that under the influence of external initiated vibrations no damage is caused to the equipment under test and no permanent or temporary malfunctions occur. 9.1 Test procedure Test Fc Test conditions

Basic requirements
1 4 7 days, after each spraying

Basis: IEC publication 60068-2-6 9.2

The functional tests are performed at the rated operational voltage Ue. Equipment under test with a mass of 100 kg for characteristic curve 1 or 10 kg for characteristic curves 2a/b can be tested with reduced acceleration values, but the acceleration values may not be smaller than 0,35 g for characteristic curve 1 and 0,7 g for characteristic curve 2. The requirements shall be agreed with GL. Table 3.15 General vibration strain (characteristic curve 1)
Vibration strain (Fig. 3.4) Displacement Acceleration

Table 3.13

Spray chamber conditions


2 hours + 25 C 10 C 5 % sodium chloride (NACl); pH value 6,5 % to 7,2 % at 20 C 2 C

Spray duration Temperature

Saline solution

Table 3.14
Temperature

Damp chamber conditions (storage)


40 C 2 C 93 % + 2 % / 3 %

2 (+ 3 / 0) Hz up to 13,2 Hz 13,2 Hz up to 100 Hz Sweep rate

1,0 mm 0,7 g max. 1 oktave / minute

Relative humidity

8.3

General instructions for test performance The characteristic curve 1 applies to equipment and components which, in view of their mounting position, do not have to meet stringent requirements. Table 3.16 High vibration strain (characteristic curve 2a)
Vibration strain (Fig. 3.4) Displacement 2 (+ 3 / 0) Hz up to 25 Hz 25 Hz up to 100 Hz Sweep rate 1,6 mm 4g max. 1 oktave / minute Acceleration

Before commencing the test an insulation resistance measurement shall be taken in accordance with test No. 13 and a functional test shall be performed. During the test the equipment under test is connected but is not switched on. The test consists of 4 sprayings and 7 days' storage period functional tests shall be performed. On the 7th day of each storage period functional tests shall be performed. On completion of the test a functional test is performed and an insulation resistance measurement taken in accordance with test No. 13 and the condition of the equipment under test is evaluated (visual inspection). 8.4 Test result

The test is deemed to have been passed if the equipment under test exhibits no visible corrosion, the specified functions are demonstrated and the values of

The characteristic curve 2a applies to equipment and components operated on compressors or in the steering gear compartment, as well as under other comparable mounting conditions.

VI - Part 7 GL 2012

Section 3

Test Requirements

Chapter 2 Page 37

amax = 2,5 mm amax = 1,6 mm

amax = 1,0 mm Curve 3 Curve 1 175 a = _____ f2 Curve 4 570 a = _____ f2 2485 a = _____ f2

0,1

Amplitude a [mm]

0,01

Curve 2a/2b 1000 a= f2 2b = 2a +

0,001 0,0006 1 10 Frequency f [Hz] 100 1000

Fig. 3.4 Vibration curve

Table 3.17

High vibration strain (curve 2b)


Vibration strain (Fig.. 3.4) Displacement Acceleration

Table 3.18

Extreme vibration strain (characteristic curve 3)

Vibration strain (Fig. 3.4) Temperature 40 Hz up to 2000 Hz


4,0 g

Acceleration 10,0 g

2 (+ 3 / 0) Hz to 25 Hz 25 Hz to 300 Hz Sweep rate

1,6 mm

600 C

Sweep rate

max. 1 oktave/ minute

max. 1 octave/minute

The characteristic curve 2b applies for electric and electronic equipment mounted on combustion engines. This test applies only for new equipment after the 2 January 2013 and shall be performed at a temperature of 90 C.

The characteristic curve 3 applies to equipment and components installed on the exhaust gas pipes of die-sel engines, especially for medium and high speed engines. The minimum strain is: If even more severe vibration strain is expected at the location in question, the latter shall be considered for the test.

Chapter 2 Page 38

Section 3

Test Requirements

VI - Part 7 GL 2012

Table 3.19

Vibration strain on masts (characteristic curve 4)


Vibration strain (Fig. 3.4) Displacement Acceleration

Table 3.20

Inclinations
Static Dynamic up to 22,5 1 up to 22,5 1 10 seconds min. 15 minutes

Vertical Horizontal

22,5 22,5
2

2 (+ 3 / 0) Hz up to 15 Hz 15 Hz up to 50 Hz Sweep rate

2,5 mm 2,3 g max. 1 oktave / minute

Rolling period Test duration per level


1

The characteristic curve 4 applies to equipment and components installed on masts. 9.3 General instructions for test performance

On ships for the carriage of liquefied gases and chemicals, the emergency power supply is to remain operational up to a maximum athwart ship inclination of 30. The duration of the test should be sufficient to allow the behaviour of the equipment under test to be evaluated.

The equipment under test is fastened by means of its fastening devices in its normal mounting position in accordance with the manufacturer's instructions. The tests are performed in three mutually perpendicular axes (X:Y:Z). During the tests the functions shall be demonstrated on the equipment under test. At the start of the test the points of resonance of each axis are determined. If points of resonance are determined at tests according to curve 1, 2 and 4 on the equipment under test which have an amplification factor Q < 2, the test duration is 90 minutes per axis at a frequency of 30 Hz. For tests according to curve 3 a sweep over the complete frequency range with a duration of 120 minutes has to be performed in that case. If points of resonance are determined on the equipment under test which have an amplification factor Q 2, the test duration is 90 minutes per resonance frequency. In the case of several resonance frequencies are detected close to each other a sweep test can be chosen. The test duration is 120 minutes. 9.4 Test result

10.3

General instructions for test performance

The equipment under test is fastened by means of its fastening devices in its normal mounting position in accordance with the manufacturer's instructions. 10.4 Test result

The test is deemed to have been passed if the specified functions are demonstrated, the results fall within the specified tolerance limits and no damage to the equipment under test is detected. 11. Flammability

The flammability test is applicable to electrotechnical equipment, its sub-assemblies and components and to solid electrical insulating materials or other combustible materials. The tests serves to demonstrate that the fire hazard inside of electrotechnical equipment (end-products) by an electrically induced ignition is minimized and a propagation of fire is limited to the inner housing of the electrotechnical equipment 11.1 Test procedure

The test is deemed to have been passed if the specified functions are demonstrated, the results fall within the specified tolerance limits and no damage to the equipment under test is detected. 10. Inclinations

The following tests for the provision of the fire hazard should be performed after coordination with GL: glow-wire test to according to

This test serves to demonstrate that under the influence of inclinations the equipment under test remains operational and no unintentional switching operations or functional changes occur. 10.1 Test procedure

IEC Publication 60695-2-11 needle-flame test according to

Not specified 10.2 Test conditions

IEC Publication 60695-11-5 Alternatively material specific according to IEC 60695-11-10, UL 94 or IEC 60695-2-12 may be accepted.

The functional tests are performed at the rated operational voltage Ue.

VI - Part 7 GL 2012

Section 3

Test Requirements

Chapter 2 Page 39

11.2

Test conditions Flammability


Test IEC 60695-11-5 Test IEC 60695-2-11

Table 3.21

When flames were emitted during the glow-wire test, additional tests according to the above mentioned IEC e.g. with needle flame may be required. The test is considered passed if no flame or no incandescence have occurred or any flames or glowing on the test specimen extinguish not later than 30 seconds after removal of the glow-wire no ignition of the silk paper while dripping of the material Test material specific

Number of specimen Flame length Angle of application Test duration per test specimen Number of flames Test specimen

3 12 mm 1 mm 45 from the Horizontal 30 seconds 1 EUT

1 960 C Vertical 30 seconds 3 EUT

11.4.3

Classification V-0 and V-1 according to IEC 6069511-10 or UL 94 may be accepted depending on the thickness of the material is the same as on the test specimen. V-2 classified material should be additionally tested by the needle flame test. The glow wire flammability index GWFI according to IEC Publication 60695-2-12 should be 850 C or higher at the related thickness of the material. 12. Pressure test

11.3

General instructions for test performance

The needle flame test is used to simulate the effect of small flames that may arise in malfunctioning electrical equipment. A 12 mm high flame held at a 45 angle is applied to the base of the EUT for a specified period of time. Tissue paper is laid out 200 mm beneath the test specimen. The needle flame test should be used only for small parts. The glow-wire test is used to evaluate the risk of fire hazard. Cover and non-conducting material should be tested at 960 C 10 C for 30 s. 11.4 11.4.1 Test result Test according to IEC 60695-11-5

This test serves to demonstrate that components of electrical equipment exposed to pneumatic or hydraulic also withstand such pressures. 12.1 Basis: GL Guidelines Test Requirements for Components and Systems of Mechanical Engineering and Offshore Technology (VI-7-8) 12.2 Test conditions Test procedure

The test is deemed to have been passed if the following conditions are observed on the plastic components of the equipment under test (housing, coverings): no flame, no incandescence or in the event of a flame or incandescence being present, it shall extinguish itself within 30 s of the removal of the needle flame without full combustion of the test specimen. Any dripping material shall extinguish itself in such a way as not to ignite a wrapping tissue. The drip height is 200 mm 5 mm. 11.4.2 Test according to IEC 60695-2-11

Pressure and tightness tests are to be performed at room temperature. For the burst pressure test the test specimen is to be subjected to a continuously raised pressure up to the test pressure. 12.3 General instructions for test performance

During the test the equipment under test is connected and switched on. 12.4 Test results

The glow-wire test should not be used for small equipment or components, as listed in the above mentioned testing standard. Small equipment or components should be tested with the needle-flame test in 11.4.1.

The test is deemed to have been passed if no permanent deformations or other damages occur on the pressurized parts at the specimen and if no inadmissible leakages on the body or the closures can be detected. The burst pressure test is deemed to have been passed if the test pressure can be maintained over the test duration without leakage and if no other damage can be detected on the test specimen.

Chapter 2 Page 310

Section 3

Test Requirements

VI - Part 7 GL 2012

Table 3.22

Pressure tests
Pressure test Tightness test of the closure Nominal pressure Water or water-oil emulsion 2 min Burst pressure test 4 nominal pressure or maximum allowable working pressure Water or water-oil emulsion 2 min

Test pressure Test medium Test duration

1,5 nominal pressure Water or water-oil emulsion 2 min

13.

Insulation resistance

14.1

Test procedure

This test serves to demonstrate that the insulation resistance at the electrical connections of the equipment under test remains within the specified tolerance limits. The insulation resistance shall be measured before and, as a test, subsequent to the following tests: 13.1 cold (Test No. 5) damp heat (Test No. 7) salt mist (Test No. 8) high voltage (Test No. 14) Test procedure

Not specified 14.2 Test conditions

The test is performed with alternating current at 50 Hz or 60 Hz. Table 3.24 High voltage
Test voltage Ueff [V] 2 Ue + 500 1500 2000 2500 1 minute per test

Rated operational voltage Ue [V] up to 66 251 501 65

Not specified 13.2 Test conditions Insulation resistance


Test voltage Min. insulation resistance before [M] 10 100 after [M] 1 10

up to 250 up to 500 up to 690

Table 3.23
Rated operational voltage Ue [AC/DC] 65 V > 65 V

Test duration

14.3

General instructions for test performance

[DC] 2 Ue, min. 24 V 500 V

The test is performed on all connections with a corresponding test voltage, for each voltage potential: connections against each other whereby all connections of equal potential are interconnected

13.3

General instructions for test performance

Where practicable, the test is performed on all connections as follows: all connections in relation to frame potential connections against each other

The following applies to equipment fitted with protective circuit: Application of the test voltage may activate the surge protection devices, which shall disconnect the test voltage. Once the rated operational voltage has been switched on, the equipment under test shall be restored to operation without the need for replacement parts. If so, printed circuits with electronic components may be removed during the test. 14.4 Test results

Certain components e.g. for EMC protection may be required to be disconnected for this test 13.4 Test results

The test is deemed to have been passed if the values are not lower than those specified in the table. 14. High voltage

The test is deemed to have been passed if no flashover is observed. 15. Electrostatic discharge

This test serves to demonstrate that the dielectrical characteristics at the electrical connections of the equipment under test meet the requirements of the test standard, against each other and in relation to the frame potential.

This test serves to demonstrate that under the influence of electrostatic discharges no damage is caused to the equipment under test and no permanent malfunctions occur.

VI - Part 7 GL 2012

Section 3

Test Requirements

Chapter 2 Page 311

Table 3.25

Electrostatic discharge
Contact discharge Air discharge 3 6 kV 8 kV min. 10 individual discharges per polarity min. 1 second

15.2

Test conditions

Severity level Test voltage Test duration per test point Time between individual discharges Wave form parameters first peak current of discharge rise time current at 30 ns current at 60 ns

During the test, the equipment under test is operated at its rated operational voltage Ue. 15.3 General instructions for test performance

The tests are performed in accordance with the IEC publication. Electrostatic discharge will be performed at all hose points and surfaces of the equipment under test which can be touched by persons during operation. The following methods are used: contact discharge on conductive surfaces and coupling planes air discharge on insulating surfaces

22,5 A 0,7 to 1 ns 12 A 6A

15.1

Test procedure

Basis: IEC publication 61000-4-2.

Example of a test set-up for freestanding equipment is given in Fig. 3.5, for table-top equipment in Fig. 3.6.

Typical position for direct application

Indirect discharge by vertical coupling plane (VCP)

Protective conductor Typical position for discharge to vertical coupling plane (VCP) 0,1 m
0,5 mx 0,5 VCP m

Power cable Alimentation Power supply 470 kW

Insulation pallet h = 0,1 m Ground reference plane Signal cable Power supply

Fig. 3.5 Example of test set-up for floor standing equipment

Chapter 2 Page 312

Section 3

Test Requirements

VI - Part 7 GL 2012

Typical position for Typical position for indirect direct application discharge to horizontal coupling plane (HCP)

Typical position for indirect discharge to vertical coupling plane (VCP)

Horizontal coupling plane


1,6 m 0,8 m

P VC 0,5m ,5m

0,1

m u Ins Re 47sistor 0k W

lati

on

Ground reference plane

Non conducting table h = 0,8 m

Power supply

Fig. 3.6 Example of test set-up for table-top equipment

16.

Electromagnetic fields

Table 3.26
Severity level

Test chamber conditions


3 80 MHz to 2 GHz 1,5 10-3 dec/s (1%/ 3s) 10 V/m AM 80% at 1000 Hz 1 sinewave vertically and horizontally

This test serves to demonstrate that under the influence of electromagnetic fields no damage is caused to the equipment under test and nor permanent or temporary malfunctions occur. 16.1 Test procedure

Frequency range Sweep rate Field strength Modulation Polarization

Basis: IEC publication 61000-4-3. 16.2 Test conditions

1 If for tests of equipment an input signal with a modulation

During the test the equipment under test is operated at its rated operational voltage Ue. 16.3 General instructions for test performance

frequency of 1000 Hz is necessary a modulation frequency of 400 Hz should be chosen.

The tests are performed in accordance with the IEC publication. During the test functional tests shall be performed on the equipment under test.

If the wiring to and from the equipment under test is not specified, unshielded parallel conductors as usual in shipbuilding shall be used. Examples of a test set-up are given in Fig. 3.7 and Fig. 3.8.

VI - Part 7 GL 2012

Section 3

Test Requirements

Chapter 2 Page 313

Chamber wall Area of uniform field Shielded connection trough chamber wall Shielded power cable

Non-conducting table

0,8 m Field generating antenna


Cable length 1 m

Power cable filter

0,1 m Shielded signal cable Absorbing ferrite or EMI filter

Non-conducting support Optional anechoic material in case of semi-anechoic chamber to reduce floor refelections

Fig. 3.7 Example of test set-up for floor-standing equipment

Area of uniform field Non-conducting table

Wiring 1 m 3 m bundled non-inductively to 1 m overall length


No specific arrangement for wiring length < 1 m as is

Field generating antenna Wiring > 3 m or not specified illuminated length shall be 1 m

Absorbing ferrite or EMI filter Optional anechoic material in case of semi-anechoic chamber to reduce floor reflections

Fig. 3.8 Example of test set-up for table-top equipment

Chapter 2 Page 314

Section 3

Test Requirements

VI - Part 7 GL 2012

Table 3.27

Conducted fast transients (burst)


Power connections Data, control and communications connections

No damage, no permanent or temporary malfunction shall occur on equipment under test with software class requirement 4 or higher, or required by specific testing standards e.g. protection relays. 17.1 Test procedure

Severity level Coupling Test voltage (open circuit) Polarity Repetition rate of pulses Waveshape of voltage Burst-duration Burst-period Test duration per polarity and test point 2 kV

3 line / earth 1 kV

Basis: IEC publication 61000-4-4. 17.2 Test conditions

positive / negative 5 kHz 5 / 50 ns 15 ms 300 ms 5 Minutes 5 kHz

During the test the equipment under test is operated as its rated operational voltage Ue, on which the test voltage is superimposed. 17.3 General instructions for test performance

17.

Conducted fast transients (burst)

The tests are performed in accordance with the IEC publication. During the test functional tests shall be performed on the equipment under test. The test is performed at the feed lines and on external control, data and communications lines. If a galvanic coupling on the connections of the equipment under test is not possible a capacitive coupling clamp shall be used. Examples of a test set-up are given in Fig. 3.9 and Fig. 3.10.

This test serves to demonstrate that under the influence of interference on power and signal connections which may occur at switching contacts as a result of arcs, no damage is caused to the equipment under test and no permanent malfunctions occur.

PE N L

= protective earth = neutral = phase line

DC terminals shall be treated in a similar way EUT Power supply 1 m (cable) L N PE 0,1 m Coupling/decoupling network Grounding connection according to the manufacturer's specification Cc li = coupling capacitors = 33 nF = decoupling inductor > 100 mH Generator <1m C c li L N PE Filtering Power supply

Ground reference plane

Non-conducting support

Fig. 3.9

Example of test set-up for direct coupling of the test voltage to AC/DC power supply ports/terminals

VI - Part 7 GL 2012

Section 3

Test Requirements

Chapter 2 Page 315

When both EUT are tested simultaneously: l1 = l2 1 m between clamp and EUT When one EUT only is tested: l2 > 5 m or 5 l1 for decoupling purposes

EUT Power supply 0,1 m Non-conducting support Drounding connection according to the manufacturer's specification l1 l2

EUT Power supply 0,1 m Non-conducting support Grounding connection according to the manufacturer's specification

Capacitive coupling clamp

0,1 m Ground reference plane to Generator

Fig. 3.10

Example of test set-up for application of the test voltage by the capacitive coupling clamp

18.

Conducted high frequency interference

This test serves to demonstrate that under the influence of interference which may occur on power and signalling lines as a result of HF signal radiation, no damage is caused to the equipment under test and no permanent or temporary malfunction occur. 18.1 Test method

During application of HF interferences functional tests shall be performed on the equipment under test. Examples of a test set-up are given in Fig. 3.11 and Fig. 3.12. Table 3.28 Conducted high frequency interference
2 line / earth 3 Veff (130 dBV) 1 150 kHz to 80 MHz AM 80 % at 1000 Hz sinewave 2 1,5 10-3 dec/s (1 %/ 3 s)

Basis: IEC publication 61000-4-6. 18.2 Test conditions

During the test the equipment under test is operated at its rated operational voltage Ue, on which the test signal is superimposed. 18.3 General instructions for test performance

Severity level Coupling Carrier signal (open circuit) Frequency range Modulation Sweep rate

The tests are performed in accordance with the IEC publication. The power supply lines shall be treated directly while signal and data lines shall be treated via a coupling clamp.

1 For equipment installed on bridge deck and deck zone the test levels shall be increased to 10 Veff for spot frequencies in accordance with IEC 60945 at 2 MHz, 3 MHz, 4 MHz, 6,2 MHz, 8,2 MHz, 12,6 MHz, 16,5 MHz, 18,8 MHz, 22 MHz, 25 MHz. 2 If for tests of equipment an input signal with a modulation frequency of 1000 Hz is necessary a modulation frequency of 400 Hz should be chosen.

Chapter 2 Page 316

Section 3

Test Requirements

VI - Part 7 GL 2012

EUT

Generator

< 1m

0,1 m

*)

Coupling/decoupling network

Power supply

Non-conducting support *) Grounding connection according to the manufacturer's specification

Ground reference plane

Fig. 3.11 Example of test set-up for direct coupling

EUT 0,1 m < Coupling/ 50 W decoupling network < 0,3 m Monitoring probe Injection clamp AE

Non-conducting support (optional) Measuring equipment

Generator Short earthing strap

Ground reference plane Non-conducting support (optional)

Fig. 3.12 Example of a test set-up using injection clamps 19. Conducted slow transients (surge) 19.1 Test procedure

This test serves to demonstrate that under the influence of interference which may occur on power lines (AC and DC) as a result of high-energy interference (switching overvoltages caused by inductive loads), no damage is caused to the equipment under test and no permanent malfunctions occur. No damage, no permanent or temporary malfunction shall occur on equipment under test with software class requirement 4 or higher, or required by specific testing standards e.g. protection relays.

Basis: IEC publication 61000-4-5. 19.2 Test conditions

During the test the equipment under test is operated at its rated operational voltage Ue, on which the test pulse is superimposed. If the equipment under test has been fitted a standard with suppressors at its connections, these protective devices shall be included in the test.

VI - Part 7 GL 2012

Section 3

Test Requirements

Chapter 2 Page 317

Table 3.29

Conducted slow transients (surge)


Coupling line / line line / earth 2 0,5 kV 1 kV

19.3

General instructions for test performance

The tests are performed in accordance with the IEC publication. During application of interferences functional tests shall be performed on the equipment under test. Equipment under test using the same lines for power supply and signal transmission are to be tested according to Fig. 3.15. This applies also to data, control and communication connections of the equipment under test, which may get direct connection to power lines by external wiring required by applications. Examples of a test set-up are given in Fig. 3.13 to Fig. 3.15.

Severity level Test voltage (open circuit) Polarity Waveshape of voltage Repetition rate Test duration per test point

positive / negative 1,2 / 50 s min. 1 pulse / minute min. 5 pulses/ Polarity

Generator (Ri = 2 W) Decoupling network C = 18 mF L Power supply N PE Earth reference L = 1,5 mH EUT

Fig. 3.13 Example of test set-up for line-to-line coupling on power supply lines

Generator (Ri = 2 W)

R = 10 W C = 9 mF Decoupling network L Power supply N PE Earth reference L = 1,5 mH EUT

Fig. 3.14 Example of test set-up for line-to-earth coupling on power supply lines

Chapter 2 Page 318

Section 3

Test Requirements

VI - Part 7 GL 2012

Generator (Ri = 2 W)

R = 40 W C = 0,5 mF S2
0 1 2 3 4

S1 Auxiliary equipment Protection equipment Decoupling network

EUT

RL Earth reference

1)

Switch S1 - line/earth: 0 - line/line: positions 1 to 4 Switch S2 - during the test positions 1 to 4, but not in the same positions with switch S1 L = 20 mH, RL represents the resistive part of the coil

2) 3)

Fig. 3.15 Example of test set-up for unshielded interconnection lines

20.

Conducted low frequency interference (harmonics)

Table 3.30

DC supply voltage
3 Veff, max. 2 W 50 Hz to 10 kHz 1,5 10-3 dec/s (1%/ 3s) see 20.3

Signal level (sine) Frequency range Sweep range Test duration

This test serves to demonstrate that under the influence of interference caused in power supply networks as a result of system perturbations no damage is caused to the equipment under test and no permanent or temporary malfunctions occur. 20.1 Test procedure

Table 3.31 Not specified 20.2 Test conditions

AC 50/60 Hz supply voltage:

Test level: Ueff, max. 2 W (Fig. 3.17) up to 15th harmonics 15th to 100th harmonics 100th to 200th harmonics Test duration 10 % of Ue decreasing from 10 % to 1 % of Ue 1 % of Ue see 20.3

During the test the equipment under test is operated at its rated operational voltage Ue, on which the test voltage is superimposed, and, where necessary, at its rated operational current Ie.

VI - Part 7 GL 2012

Section 3

Test Requirements

Chapter 2 Page 319

20.3

General instructions for test performance

reaching saturation point. The harmonics shall be reciprocally tested at supply voltages of AC 50/60 Hz. The sweep rate shall be sufficiently slow to allow influences on the operational behaviour of the equipment under test to be readily detected.

The test signal is injected into the supply voltage via a coupling transformer (Fig. 3.16). The impedance should be < 1 . The coupling transformer shall be designed in such a way that it can also support the rated current of the equipment under test without

1 2 1 3

Generator Coupling transformer Voltmeter or oscilloscope

EUT

3 Power supply 2

Ground reference Example for coupling Generator Coupling transformer Power supply

L1 N pE

Fig. 3.16 Example of test set-up, conducted low frequency interference (harmonics)

10

% - Signal voltage of Ue

0,1 1 10 15 100 200

Harmonic, n

Fig. 3.17 Signal voltage for AC supply voltages

Chapter 2 Page 320

Section 3

Test Requirements

VI - Part 7 GL 2012

21.

Conducted emissions

22.

Radiated emissions from enclosure port

This test measures any signals generated by equipment which appear on its power supply port and which can, therefore, be conducted into the power supply, and potentially disturb other ship's equipment. 21.1 Test procedure

This test measures any signals radiated by an equipment which can potentially disturb other equipment. 22.1 Test procedure

Basis: CISPR 16-1, 16-2. 22.2 Test conditions

Basis: CISPR 16-1, 16-2. 21.2 Test conditions

During the test the equipment under test is operated of its rated operational voltage Ue. Table 3.33
Site

During the test the equipment under test is operated at its rated operational voltage Ue. Table 3.32
Site

Radiated emissions from enclosure port


Frequency range Limits 150 kHz 300 kHz 80 dBV/m 52 dBV/m 300 kHz 30 MHz 52 dBV/m 34 dBV/m 30 MHz 2 GHz 54 dBV/m except for: 156 MHz 165 MHz 24 dBV/m

Conducted emissions
Frequency range Limits 96 dBV 50 dBV 60 dBV 50 dBV 50 dBV

Bridge and open deck zone EMC 1 1

Bridge and open deck 10 kHz 150 kHz zone 150 kHz 350 kHz 350 kHz 30 MHz EMC 1 1 General power distribution zone EMC 2 1
1 see Table 3.34

General power distribution zone EMC 2 1

10 kHz 150 kHz 120 dBV 69 dBV 79 dBV 150 kHz 500 kHz 73 dBV 500 kHz 30 MHz

150 kHz 30 MHz 80 dBV/m 50 dBV/m 30 MHz 100 MHz 60 dBV/m 54 dBV/m 100 MHz 2 GHz 54 dBV/m except for: 156 MHz 165 MHz 24 dBV/m

1 see Table 3.34

21.3

General instructions for test performance

22.3

General instructions for test procedure

The emission shall be measured by means of the quasi-peak measuring receivers specified in CISPR 16-1-1. An artificial mains network in accordance with CISPR 16-2 shall be used. The measuring bandwidth in the frequency range 10 kHz to 150 kHz shall be 200 Hz, and in the frequency range 150 kHz to 30 MHz shall be 9 kHz. The power input cables between the AC and DC power ports of the EUT and the artificial mains network shall be screened and not exceed 0,8 m in length. Longer power cords shall be folded into a serpentine-like bundle and not coiled. If the EUT consists of more than one unit with individual AC and/or DC power ports, power ports of identical nominal supply voltage may be connected in parallel to the artificial mains supply network. Measurements shall be made with all measuring equipment and the EUT mounted on, and bonded to, an earth plane. Where provision of an earth plane is not practicable, equivalent arrangements shall be made using the metallic frame or mass of the EUT as the earth reference. 21.4 Test result

The radiation limit at distance 3 m from the enclosure port over the frequency range shall be measured. The quasi-peak measuring receivers specified in CISPR 16-1-1 shall be used. The receiver bandwidth in the frequency ranges 150 kHz to 30 MHz and 156 MHz to 165 MHz shall be 9 kHz, and in the frequency ranges 30 MHz to 156 MHz and 165 MHz to 2 GHz shall be 120 kHz. For frequencies from 150 kHz to 30 MHz measurements shall be made of the magnetic H-field. The correction factor for the antenna shall include the factor + 51,5 dB to convert the magnetic field strength to equivalent electric field strength. For frequencies above 30 MHz measurements shall be made of the electric E-field. The test antenna shall be placed at a distance of 3 m from the EUT. The centre of the antenna shall be at least 1,5 m above the ground plane. The E-field antenna shall be adjusted in height and the EUT shall be placed at the mid-point of a plane orthogonal to the test antenna and be rotated to achieve the maximum emission level. 22.4 Test result

The radio-frequency voltage at the power supply terminals of the EUT shall not exceed the limits shown in Fig. 3.18.

The radiation limit from the enclosure port shall not exceed the limits shown in Fig. 3.19.

VI - Part 7 GL 2012

Section 3

Test Requirements

Chapter 2 Page 321

120 110 100 96 90 80 70

EMC 2

EMC 1

dB [mV]

60 50 40 30 20 10 0 0,01 0,1 Frequency B EMC 1 EMC 2

B = 200 Hz

B = 9 kHz

0,15

0,35 0,5

1,5

30

1 [MHz]

10

100

Measuring receiver bandwidth Bridge and open deck zone General power distribution zone

Fig. 3.18 Radio frequency terminal voltage limits for conducted emission

Chapter 2 Page 322

Section 3

Test Requirements

VI - Part 7 GL 2012

Field strength E measured at 3 m 120 110 100 90 80 70 60 50 40 30 20 10 0 0,1

EMC 2

156 MHz - 165 MHz

dB [mV/m]

EMC 1

B = 9 kHz

B = 9 kHz

B = 120 kHz

0,15

0,3

1 Frequency B EMC 1 EMC 2

10 [MHz]

30

100

200

2000

1000

Measuring receiver bandwidth Bridge and deck zone General power distribution zone

Fig. 3.19 Limit values for radiated emissions from enclosure ports

VI - Part 7 GL 2012

Section 3

Test Requirements

Chapter 2 Page 323

Table 3.34

Required test conditions for the defined environmental categories


Environmental Conditions Test Conditions
Temperature Climate Vibrations
The short sign of the location EMC 1/ EMC 2 where the equipment is installed according to test 18, 21 and 22 should be added to the short sign of the environmental category.

Comments

Environmental Category

Closed Area

Open Deck Area

Temperature

Temperature

Temperature

Vibrations

Vibrations

Relative Humidity

Relative Humidity
95 %

Relative Humidity

Dry Heat

0 C up to to 100 % 45 C 0 C up to to 100 % 45 C 0 C up to to 100 % 55 C 0C up to to 100 % 55 C 0C up to to 100 % 90C 0 C to 40 C up to 80 %

0,7 g

55 C

5 C

55 C

Salt mist

Cold

0,7 g

For general applications

4g

55 C

5 C

55 C

95 %

4g

Has to withstand a high level of vibration strain, e. g. in steering gear compartment. Has to withstand a high degree of heat, e. g. for equipment to be mounted in consoles, housings. Has to withstand a high degree of heat and a high level of vibration strain, e. g. for equipment to be mounted on combustion engines and compressors. For use in air-conditioned areas. With GLs special consent only. Has to withstand the additional influences of salt mist and temporary inundation, e. g. on open deck. For use on masts, with the additional influence of salt mist. The provisions contained in the certificates shall be observed.

0,7 g

70 C

5 C

55 C

95 %

0,7 g

4g

70 C

5 C

55 C

95 %

4g

DT

4g

90 C 5 C

55 C

95 %

4g

0,7 g - 25 C to + 45 C - 25 C to + 45 C

55 C

5 C

55 C

80 %

0,7 g

up to 100 %

0,7 g

70 C

55 C 25 C

95 %

Test re0,7 g quired Test re2,3 g quired

up to 100 %

2,3 g

70 C

55 C 25 C

95 %

according to manufacturers specification only in combination with environmental categories A-G

Das könnte Ihnen auch gefallen