Sie sind auf Seite 1von 8

SPEC. NO.

CE(GSW)/SPV/ BELAKAVADI

SOLAR PV POWER PLANTS

SECTION C Page 1 of 8

SECTION C SPECIFIC RE !IRE"ENTS 1.## E !IP"ENT TO BE S!PPLIED$ The scope of the work includes The Design, manufacture, supply, erection, testing and commissioning of 5 MWp capacity grid interactive solar PV plant and the grid connecting equipments including all associated civil works required for the power evacuation through the !V line at "elakavadi village in Mandya District of !arnataka# $quipment shall %e complete with all fittings and accessories as detailed herein# DETAILED SCOPE OF WORK a) SOLAR PV PLANTS &The Design, $ngineering, manufacture, 'uality surveillance, Testing at manufacturer(s works, Packing and )upply of crystalline technology solar PV plant of 5MWp capacity grid interactive plant including comprehensive insurance, )torage, intrasite transportation, erection, testing and commissioning of the system including all connected civil works# Plant shall consist of required num%ers of *5+ !W solar PV arrays# %) GRID CONNECTING E !IP"ENTS The Design, $ngineering, manufacture, 'uality surveillance, Testing at manufacturer(s works, Packing , supply, erection, testing and commissioning including comprehensive insurance of the grid connection equipments vi,#, --!V )witching cu%icle with switchgears, !V switchgear and protection system, transformers, lightning arrestors, isolators, )./D/ system etc#, required for the power evacuation through the !V line, including all associated civil works# &) 0peration and maintenance of the grid connected )PV plants for a period of three years from the date of commissioning# '.## *#*#* *#2 ASSOCIATED CIVIL WORKS$ .utting and clearing of trees, plants etc#, in a%out *5 acres of land to ensure shadow free area# )ite grading, levelling, e1ploratory drills if necessary and consolidation of the area pertaining to the installation of )PV modules of solar plant# $m%edment of structures suita%le for mounting PV modules on ground in a%out *5 acres of land# 3aying of earthing equipments 4 structures and connecting to the main ground mat as per the statutory requirements#

1.1

SPEC. NO. CE(GSW)/SPV/ BELAKAVADI

SOLAR PV POWER PLANTS

SECTION C Page ' of 8

*#5

.utting of ca%le trenches wherever necessary, construction of all round compound wall for the entire plant including the power evacuation line %ay and providing suita%le gates# 6as specified7 8ormation of roads vi,# peripheral , internal roads, pathways with asphalt , providing foundation for transformers, structures and water drainage ducts, lightning, arrestors etc# .onstruction of 2 9os# of control rooms of :5+ )q# mtrs#6Total7 area to house control, protection, )./D/ system and panels, as per enclosed drawing alongwith lo%%y,seminar hall , %athroom, kitchen etc## SOLAR PV PLANT $ach )03/; PV <nit shall consist of following equipments= -# *# 5# 5# # @# :# A# -+# --# -* )olar PV arrays with modules of suita%le rating# >nverters with )./D/ Mounting structures .a%les and hardwares ?unction %o1 and distri%ution %o1es $arthing kit 3ightning arrestors PV. pipes and accessories Tool kit .ontrol room and civil pedestals )pares for 2 years

*#+5

*#+

(.##

).##

GRID CONNECTING E !IP"ENTS$ a7 !V, #2 MV/,--!V4 !V, 2 phase,5+ B, Transformer, !V )witchgear, control and protection equipments# %7 -*5+ !V/,+#5-54-- !V, 2 phase, 5+B, Transformer with switchgear and protection equipments c7 d7 3ightning arrestor, of rating + !V , suita%le for !V system

-- !V .u%icle consisting of .urrent Transformer, Potential Transformer, )8 4 Vacuum circuit "reaker, "us %ar, isolators , protection system etc with incoming and outgoing feeders# -- !V switchgear,--!V transformers,-- kv >solators, !V isolators # 2 .0;$ C3P$ .a%le ,-:5sq#mm, aluminum armoured ca%le confirming to >) @+A: carrying nearly *@ amps6earth 7 and 22*

e7 f7 f7

SPEC. NO. CE(GSW)/SPV/ BELAKAVADI

SOLAR PV POWER PLANTS

SECTION C Page ( of 8

amps in 6air7 of required 5++m length7# g7 !V switchgear , !V isolators #

length for

power evacuation 6a%out

kv transformer,

!V lightning arrestors,

h7-- kv switchgear with .Ts,PTs and protection equipments# h7 2 .0;$ C3P$ .a%le ,:++sq#mm, aluminum armoured ca%le , i7 /.); aluminium conductor# *.## +.## )upply, erection, testing and commissioning of )./D/ system for the remote monitoring of the plant# 0peration and maintenance of )PV Plant along with grid connecting equipments for a period of three years from the date of commissioning# Training of !P.3 personnel for smooth operation D Maintenance of the Plant shall %e provided# OT-ER WORKS$ )upply and providing illumination for the proposed )PV plant, evacuation system, intermediary area up to !V 3ine# The illumination of the plant , yard and compound wall shall make use of solar power# / separate %attery supported -+ !W solar PV %uilding integrated system shall %e provided for illumination of the plant# )upply and erection of galvani,ed steel ground wire of suita%le dia# with hard ware for lightning protection of the )PV Plant and switchyard equipment and grounding as per statutory requirement# Providing all round compound safety4protection# wall for the entire )PV plant for its

,.## @#+-

@#+*

@#+2 @#+5

)upply of all miscellaneous materials like hardwares, clamps and connectors, glands, lugs etc#, and supply of essential spares for the )PV plant and the grid connecting %ay required for trou%le free operation for three years# )upply and installation of suita%le fire protection equipments as per statutory requirement# )upply and installation of %attery %anks with main and stand%y and %attery chargers as per specification for switchgear and protection## )upply and installation of adequate air conditioning system for control and protection equipments .omputers# , scada system etc#,

@#+5 @#+ @#+@

SPEC. NO. CE(GSW)/SPV/ BELAKAVADI

SOLAR PV POWER PLANTS

SECTION C Page ) of 8

@#+: @#+A 8.##

)upply and installation of danger %oards, sign %oards, hoardings etc#, as per statutory needs# )upply and installation of effective communication system as specified TRANSFOR"ERS$ -7 2++ !V/, --4 !V , 2 phase, 5+ B, ,09/9 Transformer *7 -*5+ !V/, 5-54--+++V, 2 phase, 5+ B, Dyn-- connected, 5E impedance voltage, outdoor type transformers #and accessories# a) 11 KV SWITC-GEAR C!BICLE The --!V switch gear cu%icle comprising of protection4 interlocking 4 annunciation 4 interFtripping 4 automatic 4 manual operation schemes for the purpose of satisfactory and efficient operation of the equipment# %7 !V switchgear and protection system comprising of protection4 interlocking 4 annunciation 4 interFtripping 4 automatic 4 manual operation schemes for the purpose of satisfactory and efficient operation of the equipment

..##

..1

GENERAL DESIGN AND OPERATING CONSIDERATIONS --!V switch gear cu%icle shall consist of current transformers, potential transformers, sf 4 vacuum circuit %reaker, %us %ar , isolators ,protective devises etc# The )witch%oard4panel foundations and fi1ing devices shall %e strong enough to withstand the forces in normal operation and in a%normal conditions with forces superimposed due to occurrence of earthquake and short circuit simultaneously# !V switchgear alongwith .T, PT, )8 %reaker protection devices## The copies of type test reports for similar type of switchgears4 accessories and foundation equipments, if tested earlier, should %e furnished along with the %id# >f these types of switchgears have not %een type tested earlier, the same has to %e arranged %y the contractor at his own cost and test reports to %e furnished for review#

..'

APPLICABLE STANDARDS <nless otherwise specified elsewhere in this specification, the rating, performance and testing of -- !V cu%icle and associated panels , !V switchgear and associated panels shall conform to the latest revision of standards#= Fea/01e2 of 11 KV a34 ++ KV &0%5&6e a7 /lternating current .ircuit %reakers = %7 Voltage transformers

1#.##

SPEC. NO. CE(GSW)/SPV/ BELAKAVADI

SOLAR PV POWER PLANTS

SECTION C Page * of 8

c7 d7 e7 f7 g7 h7 i7 G7 k7 l7 m7 p7

.urrent transformers= /. disconnectors 6isolators7 and earthing switches# /. metal enclosed )witchgear D .ontrol gear for rated voltages Direct acting >ndicating digital ele# Measuring >nstruments D accessories# /. $nergy meters /. Watt hour meters $lectrical ;elays for power system protection )tatic protective relays Push %utton4 switches "ushings# .ommon spec# for high voltage )witchgear D .ontrol gear standards Degree of protection provided %y enclosure 6>P code7

11.## >f %idder is offering equipments conforming to the standards other than those stipulated a%ove, he should esta%lish in the %id that standards adopted %y him are compara%le with relevant >ndian )tandards or >$. )tandards# 8urther a comparative statement in respect of only those provisions in standards adopted %y him, which are different from those provisions in standards, shall %e furnished# /lso, the %idder must supply copies in $nglish language of the standards and codes adopted %y him 6>f these are in different languages, copies translated in H$nglish( may %e furnished7 to latest standards of engineering, design and workmanship in all respects shall %e capa%le of performing in commercial operation in a manner accepta%le to the owner# 1'.## SPARES "idder shall supply the essential spares along with main equipment for three years trou%le free operation and maintenance#The cost of spares shall %e included in the lumpsum price# 1(.## "AINTENANCE RE !IRE"ENT -2#+$asy access shall %e provided for all components in the )PV plant and grid connecting equipments# Maintenance platform shall %e provided for easy inspection of all the equipments# -2#+* -2#2 >f special tools are required for installation and maintenance, the %idder shall indicate the same and to %e supplied free of cost# The Vendor shall furnish operating and maintenance instruction manual to ena%le the purchaser to carry out maintenance of equipment effectively and safely#

1).## TEST AND TEST REPORTS

SPEC. NO. CE(GSW)/SPV/ BELAKAVADI

SOLAR PV POWER PLANTS

SECTION C Page + of 8

-5#+-

The )upplier shall carryout all routine tests as specified in relevant standards on all maGor components in presence of the purchasers representative at works %efore despatch and furnish copies of test reports for purchaserIs approval, >f required, stage inspection will %e carried out %y the purchaser# )<PP3>$; shall carryout all routine and functional tests as specified in the relevant standards on the assem%led )PV Plant and grid connecting equipments with all accessories of the equipment in the presence of the P<;.B/)$;(s representative %efore despatch and furnish copies of the test reports for approval %efore despatch# TESTS ON TRANSFOR"ERS $ /ll routine tests, pressure test and oil leakage tests shall %e conducted# The following shall %e conducted transformer tank = Vacuum test = Pressure test= I37e1/e12$ Temperature rise test to %e conducted# "o406e2$ BV test upto 2 !V for minute and meggering with 5++ volt megger#

-5#+*

-5#+2

-5#+5

/ll au1iliary equipment shall %e tested as per the relevant standards# Test certificates shall %e su%mitted for %ought out items# /ll relevant tests as per >) shall %e conducted# C3P$ ca%le and 3yn1 conductor shall %e tested as per >)#

-5#+5

1*.## CO"PLETNESS OF E !IP"ENT /ll the fittings and accessories that might not have %een mentioned specifically in the specification %ut are necessary for equipmentJs of the plant, shall %e deemed to %e included in the specification and shall %e supplied and furnished %y the .ontractor without any charge# 1+.## LA8O!T RE !IRE"ENTS The overall dimensions of the )PV Plant and grid equipments shall suit the space provided for the layout requirements# The arrangement to suit this space is to %e intimated at the time of approving the general arrangement drawing of the equipments, shall %e agreed upon %y the Vendor without any commercial 4 delivery implications#

1,.## DELIVER8 AND CO"PLETION PERIOD$

SPEC. NO. CE(GSW)/SPV/ BELAKAVADI

SOLAR PV POWER PLANTS

SECTION C Page , of 8

The )PV plant and grid equipments including all accessories and spares shall %e delivered within 5 months from the date of 30/# The entire work including erection, testing , commissioning of the plant as indicated in the scope shall %e completed within @ months from the date of 30/# 18.## G!ARANTEE The .09T;/.T0; shall guarantee the material and workmanship of all components and operation of the equipment and shall meet the requirement of the specification# )hould the performance test result at works deviate from the guaranteed values including the specified tolerance the .09T;/.T0; shall correct his equipment at no e1tra cost to the P<;.B/)$; and repeat the performance tests within a reasona%le period as agreed to %y the P<;.B/)$;# /s regard to the component clauses if the .09T;/.T0; fails to meet the guaranteed values su%Gect to tolerances specified, the P<;.B/)$; will levy a penalty#

1..## TENDER EVAL!ATION a7 The ">DD$; shall comply with parameters as specified in the %id specification# 9o credit will %e given during tender evaluation if parameters %etter than those specified are offered %y the ">DD$;# %7 The P<;.B/)$; reserves the right to split the order# ">DD$; shall specifically confirm that the unit price quoted %y them are valid for any increase or decrease in the quantity specified#

'#.## ERECTION9 TESTING AND CO""ISSIONING *+#+)cope of erection, testing and commissioning shall cover the following# -# *# 2# 5# 5# 7 *+#+* ;eceipt and unloading at site# Transportation from place of unloading to stores )torage Transportation from stores to place of erection $rection, testing and commissioning# >nsurance at all stages#

Prices for total erection, testing and commissioning shall %e quoted, as called for in )ectionF$# The )upplier shall carry out preFcommissioning checks4 tests as per the standard commissioning procedures#

'1.## GENERAL

SPEC. NO. CE(GSW)/SPV/ BELAKAVADI

SOLAR PV POWER PLANTS

SECTION C Page 8 of 8

<nit prices quoted in the price schedule shall hold good for any additions4deletions during detailed engineering stage# The "idder shall comply with the )PV Plant particulars as specified in Data )heet# 9o credit will %e given during the tender evaluation if design particulars %etter than those specified are offered %y the "idder# "idder shall su%mit the design and performance data of the equipment offered %y filling up data sheetF" in )ectionFD# Tenderer shall follow the tender specification strictly and conditional tenders will %e reGected# ''.## PRICES FOR S!PPL89 ERECTION9 TESTING AND CO""ISSIONING The lumpsum prices quoted for supply, inclusive of essential spares, erection, testing and commissioning will %e considered in the evaluation of %ids# '(.## CO""ERCIAL DEVIATIONS 9o commercial deviations are accepta%le and all commercial conditions shall %e as per our specification# /ny commercial deviation taken will not %e considered for tender evaluation# ').## ARRANGING WATER AND POWER S!PPL8 Water and electricity required during construction and 0DM period shall %e arranged %y the contractor# 2 num%ers of %ore wells shall %e installed for water required for the plant# /dequate capacity of power supply for construction4operation and maintenance of the plant shall %e arranged %y the contractor# /ll e1penses in this regard shall %e %orne %y the contractor#

Das könnte Ihnen auch gefallen