BPL UPS
in the Enterprise Environment
Loop Start TK
BPL-IP-PBX
Trunk Line
BPL FXO
TDM PBX
ETHERNET (LAN)
Analog lines
BPL FXS
Analog Phones
BPL
POS Terminals
BPL PFE Series - The on-line UPS with Active Input Power Factor enhancement.
BPL PFE 101 (1/1) 10kVA BPL PFE 301 (3/1) 10kVA - 40kVA BPL PFE 303 (3/3) 10kVA - 40kVA
Applications: IT Majors, Data Centres, Cloud Service Providers, Computer Labs, Browsing & Internet Centres Surveillance Cameras & Equipment, Telecom & Networking Equipment with Fax, POS Devices, Critical & Emergency Lighting Health Care Systems, Operation Theatres, Diagnosis Equipment, Lifesaving Equipment, Treadmill & Gym, Educational Institutions, Printing Machines, Photocopiers, Digital Colour Labs, Recording Studios, Home Theatres. BPL SCN - The on-line UPS specically designed for MRI and CT Scanner applications of any make. BPL SCN (3/3) 60kVA - 150kVA BPL IAN Series - The on-line UPS (with 0.9PF & <10% THDi) designed for Industrial Applications. BPL IAN 303 (3/3) 60kVA - 240kVA Applications: CNC, Laser Cutting Machine, Automotive Manufacturing, Metal Smelting, Extrusion, Annealing, Kiln, Industrial Ovens, Tetra Packing Industry, Chemical Process, Oil & Gas Pipeline Control, Conveyors, Escalators and Material Lifts, Stone Crusher, Tiller, Centralised Air Conditioners and Pharmaceutical Industry. BPL GSS Series - The Grid Sharing Solar UPS with MPPT 10kW - 100kW Applications: Agricultural Pumps and Others, Educational Institutions, Hospitals, Industrial Applications.
CAUTION
BPL Equipment is to be handled by a competent person Proper Biasing of the UPS before connecting the battery is a must Always use Rubber Hand Gloves & Shoes Use proper earthing to avoid shocks Disconnect the battery, power input and discharge all components before disconnecting the module Use tag for every input and output
BPL Telecom Private Limited 11th KM, Bannerghatta Road, Arakere, Bangalore - 560 076. Ph: +91-80-2648 4314/4348/4350/4388/0209 Business Enquiry: upsenquiry@bpltelecom.com Product Service: customercare@bpltelecom.com www.bpl.in
Release Version July 1302 V02
BPL Telecom, an early Indian pioneer in Communications and Power Sector Electronics now brings you a range of power conditioning solutions and on-line UPS systems. Our products are supported by trained sales and service teams spread across the country. We can respond to your needs at short notice to provide you with a solution that meets your specic needs.
INPUT
Input voltage Input voltage window Input frequency Input current harmonics Input power factor Power walk in 415V AC (3 Phase & Neutral) 330- 470V 50Hz 10% With <10% THDi the input PF is improved and reduces the burden on the input power source > 0.9 Soft start for 0 - 20 seconds walk-in
SALIENT FEATURES
BPL power conditioning UPS Systems reduce wear and tear on expensive equipment connected to your power supply and prevent break-downs Process losses due to unexpected power stoppages are eliminated Our robust products eliminate the need for frequent maintenance and minimise disruption of work BPL UPS Systems are highly efficient and reduce the total cost of ownership
RECTIFIER
Type Voltage regulation Ripple Voltage Converter protection 12-Pulse rectier ()1% < 2% without battery Advanced electronic protection for device safety backed up with MCBs/MCCBs and fast acting fuses
INVT
Inverter type Power factor Nominal Voltage Balanced / Unbalanced load Frequency Wave form Linear load and Non - linear load harmonic distrotion Transient response Over load capacity Nominal output current / phase Crest factor IGBT based MPWM with instantaneous sine wave control 0.8 lag 400V Phase-Phase : 230V Ph-Neutral (1%), 120 0.5 regulation & phase shift 50Hz 0.1% True sine wave < 2%, < 6% Remains within 5% & recover to normal within 20 msec 100% continues / 125% - 1min / 150% - 5sec 60kVA - 70A / 80kVA-93A / 100kVA-115A 120kVA-140A / 150kVA-173A / 200kVA-231A / 240kVA-278A 3:1
The primary source of power of the BPL Grid Sharing Solar UPS is Solar Power, the total load is shared between Solar & Grid during the mains availability and between solar & Battery during mains power failure. The UPS output gives conditioned power without change over & is ideal for critical applications. When solar power is adequate to cater to the load demand, no power is drawn from the Grid and the solar power would take care of Battery charging, any short fall in solar power availability, the decit power is drawn either from Grid or Battery. BPL Grid Sharing Solar UPS comes with high efciency of conversion of Solar energy, the output of MPPT is fed to the intelligent power sharing module which ensures maximum power utilization from the solar Panel. 1 KW of Solar Power (Which needs a oor space of 3m X 3m) will save approximately 5 Units of Electricity per day. Featured products: Solar INVTS specially designed for irrigation pump sets. Three phase solar INVTS for industrial application, farm houses, resorts, lifts and emergency lighting systems without battery and grid. Application-specic solar UPS for: Educational institutions CT, MRI and ultrasound scanners
SOLAR UPS
CHARGER
Charge type Charging current standard CCCV 0 - 20A Advanced electronic protection for device safety backed up with MCBs / MCCBs and fast acting fuses, high speed pulse by pulse electronic device protection, over voltage / under voltage protection, electronic over current trip with reset and manual bypass UPS manager-PC/Network interface and mobile phone interface Cross load sharing-active parallel redundancy (CLS - APR)
Indigenous Design as per international standards ensures value for investment with long product life.
Solar Panel
EFFICIENCY Temperature compensated Float cum Boost Charger Power monitoring and Sharing Mode IGBT Inverter with Galvanic isolation
Overall efciency on 100% load Operating ambient temp Enclouser protection grade Testing standard 90 - 93% 0 - 40C IP - 20 As per IEC 62040 - 3
BATTERY
OUTPUT
Double conversion On-line with the latest MPWM technology using IGBT
INPUT
INPUT VOLTAGE INPUT WINDOW INPUT FREQUENCY INPUT PFC @ 100% LOAD POWER WALK IN 230V AC 1 170 - 270V 50Hz 10% 0.99 >0.90 >0.95 >0.9 Soft start for 0-20 seconds power walk-in 415V AC 3 & N 330 - 470V
SOLAR INPUT
OPERATING MPPT VOLTAGE MAXIMUM PANEL CURRENT REVERSE POLARITY PROTECTION BACK FEED PROTECTION 6 Pulse/12 Pulse MPPT EFFICIENCY CONFIGURATION SHARING METHOD SHARING PERCENTAGE 150V - 180V 50A Short Circuit Diode Protected using reverse diode 96% ( Peak) Grid Sharing Parallel Operation of Solar and Grid Power 0 - 100% depending on the availability of solar power against the power Demand of the load. 180V - 330V 100A 330V 250A
RECTIFIER
TYPE VOLTAGE REGULATION RIPPLE VOLTAGE CONVERTER PROTECTION ( ) 1% < 2% without battery Advanced Electronic Protection for device safety backed up with MCBs & fast acting fuses IGBT based full bridge
INVT
INVERTER TYPE POWER FACTOR NOMINAL VOLTAGE REGULATION FREQUENCY WAVE FORM TOTAL HARMONIC DISTORTION TRANSIENT RESPONSE 100% OVER LOAD CAPACITY NOMINAL OUTPUT CURRENT CREST FACTOR MODE OF OPERATION ISOLATION INVERTER PROTECTION MANUAL BYPASS OVERALL EFFICIENCY @100% LOAD ALARMS LED INDICATIONS USER FRIENDLY LCD DISPLAY CHARGER TYPE ENCLOUSER PROTECTION GRADE COOLING ACOUSTIC NOISE LEVEL AMBIENT TEMPERATURE STORAGE TEMPERATURE HUMIDITY ALTITUDE TESTING STANDARD SOFTWARE INTERFACE-OPTIONAL CONNECTIVITY-OPTIONAL 125% 150% LINEAR LOAD NON LINEAR LOAD 50 Hz 0.1Hz True Sine wave < 2% < 6% Continuous 1 Minute 5 Seconds 34.8A 3:1 Designed for continuous operation True online with complete galvanic isolation I/P to O/P galvanic isolation Advanced Electronic Protection for device safety backed up with MCBs & fast acting fuses, high speed pulse by pulse electronic device protection over voltage / under voltage protection, Electronic over current trip with reset. Provided > 87% > 90% >88% > 93% 70A 23A - 35A 140A - 346A 4:1 < 5% < 6% Remains within +/- 5 % & recover to normal within 20msec IGBT based MPWM with instantaneous sine wave control 0.8 lag 220 VAC / 230 VAC 220VAC / 230VAC ( ) 1% 400 V Ph- Ph :230V Ph - Neutral 200V Ph - Ph : 115V Ph - Neutral ( ) 1% Balanced & unbalanced load
BATTERY
BATTERY TYPE CHARGER TYPE TEMPERATURE COMPENSATION CHARGING CURRENT SMF / TUBULAR Float cum Boost / CCCV 5 mv / Cell / C variation 0 - 30A 0 - 40A 0 - 50A
INVT
INVERTER TYPE POWER FACTOR NOMINAL VOLTAGE REGULATION-BALANCED LOAD REGULATION-UNBALANCED LOAD UNBALANCED LOAD PHASE SHIFT OVER LOAD CAPACITY CREST FACTOR IGBT based MPWM with instantaneous Sine wave Control 0.8 lag 230V / 50Hz ( ) 1% NA NA 125% for 1 Minute : 150% for 10 Seconds 3:1 230V / 50Hz ( ) 1% NA NA 400V / 50Hz ( ) 1% ( ) 1% 120 0.5
PROTECTIONS
Under Voltage / Over voltage Over Temperature Battery Low Over Load Short Circuit ENCLOSURE PROTECTION IP-20
Input / Low / Fail, Output overload, Over temperature, Battery low Mains on, Charger on, Inverter on, Battery Low, Overload, Inverter Trip Input Voltage, Output voltage, Load percentage, Output frequency, Battery voltage CVCC IP - 20 Forced air <60db @ 1.5 meter 0 to 40 Deg C -10 to 70 Deg C Up to 95% RH Non condensing <3000 feet above sea level(without derating) As per IEC 62040 - 3 UPS manager-PC/network/GSM Via RS-232 for a single PC or RJ 45 connector for multiple PC TESTING STANDARD As per IEC 62040 - 3 / IEC 61683 CCCV
Note: Specications are indicative of our standard models and are subject to change without notice.
Note: Specications are indicative of our standard models and are subject to change without notice.