Pressure Sensor - 2ZPS004704324

2.50"
0-5“ H2O Pressure Range - 5 VDC Operation
2.20"
Minimum Typical Maximum
Full Scale Output
(Positive Pressure) 3.92 VDC 3.95-4.05 VDC 4.08 VDC

GND (Green)
OUT (Black)
IN (Red)
Null Offset 0.17 VDC 0.2-0.3 VDC 0.33 VDC
12.0" APPROX.
Span* 3.59 VDC 3.65-3.85 VDC 3.91 VDC
Non-Linearity ±0.3 % Span ±0.5 % Span
Hystereisis And Repeatability ±0.03 % Span ±0.05 % Span

GND
OUT
IN
Temperature Error
Null +10° To 40°C ±1.0 % Span ±1.5 % Span
Span +10° To 40°C ±1.0 % Span ±1.5 % Span 1.29" UP 0.15" DIA.
Stability (1 Year) ±0.5 % Span 0.15"

Supply Voltage (Vs) 4.75 VDC 5.0 VDC 8.0 VDC 2ZPS004704324
2.94" S.P. Sensor
Common Mode Pressure 15 PSI
0.60"
Pressure Overload (-)LO
Positive Pressure (Hi Side) 25“ H2O
0.200" (3/16" Tubing Conn.)
Negative Pressure (Lo Side) 15“ H2O
Burst Pressure 0.125" (1/8" Tubing Conn.)
Positive Pressure (Hi Side) 50“ H2O
Negative Pressure (Lo Side) 25“ H2O Top View
*Span Is The Algebraic Difference Between End Points (Null Offset And Full Scale Output)

Warning! 1.95"
The plastic housing on the sensor is electrically
0.55"
conductive. Avoid contact with any electrical components.
It is acceptable to mount the sensor on grounded sheet
metal such as ductwork, electrical panels, etc.
1.00"
0.35"
Warning!
Use extreme care when mounting the sensor to avoid
damage to the plastic housing. Do not overtighten the
mounting screws! Do not use mounting screws which are Side View
too large for the holes!

General Notes
1.)Caution:The 2ZPS004704324 Pressure Sensor 2.)All Wiring To Be In Accordance With Local And
Should Be Mounted In A Vertical Position As Shown National Electrical Codes And Specifications.
With Arrow Pointing Up. ( Tubing Connections
Pointing Down). If This Mounting Position Is Not
Possible In Your Application, It May Be Mounted In
A Horizontal Position. When Mounted In A
Horizontal Position Accuracy Will Be Affected By
Approximately 2% Full Scale Null Shift Due To
Diaphragm Gravity Effect Error.

Duct Static Pressure Sensor Applications


Mounting Information
When The Sensor Is Used As A Duct Static
Pressure Sensor It May Be Mounted To The
Ductwork Near The Static Pressure Pickup Tube. If
The Sensor Is Mounted In This Manner, Away
From The Controller, The Modular Plug Must Be
Cut Off And 3-conductor 24 Gauge Minimum Wire
Must Be Butt Spliced To The Sensor Leads. The
Controller Has A Terminal Block Which Is
Paralleled With The Modular Jack To Allow Wiring
Connections. Total Wire Length Should Not
Exceed 100Ft. If Desired The Sensor May Also Be JOB NAME
Located Near The Controller, With The Modular
Plug On The Sensor Directly Connected To The
Mating Controller Jack. When This Method Is Used FILENAME
Tubing Must Be Run From The Sensor To The
Staic Pressure Pickup Tube. Tubing Should Not 036-22301-001-A-0602.CDR
Exceed 250 Ft. And Must Be Continuous Without
Any Splices. DATE: 06/28/02 DRAWN BY: B. CREWS
PAGE DESCRIPTION:
2ZPS004704324
1 of 1
Pressure Sensor
Form: 036-22301-001 Rev. A (0602) Supersedes: Nothing