Sie sind auf Seite 1von 123

ARMY TM 5-685

NAVY NAVFAC MO-912

OPERATION, MAINTENANCE AND


REPAIR OF AUXILIARY GENERATORS

D E P A R T M E N T S O F T H E A R M Y A N D T H E N A V Y
AUGUST 1996
REPRODUCTION AUTHORIZATION/RESTRICTIONS

This manual has been prepared. by and for the Government and is
public property and not ‘subject to copyright.

Reprints or republication of this manual should include a credit


substantially as follows: “Joint Departments of the Army and the
Navy TM 5-685/NAVFAC MO-912, Operation Maintenance and Repair
of Auxiliary Generators, 26 August 1996”.
;P
1
ARMY T ECHNICAL MANUAL TM 5-685
; No. 5-685 NAVFAC MO-912
cI NAVY MANUAL
:!5.
, No. NAVFAC MO-912
1 -___ - HEADQUARTERS
ii”
? DEPARTMENTS OF THE ARMY AND THE NAVY
1 WASHINGTON, DC, 26 August 1996
;
b
t$B OPERATION, MAINTENANCE AND REPAIR OF AUXILIARY GENERATORS
,I
Paragraph Page
CHAPTER 1. INTRODUCTION
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . l-l l-l
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 l-l
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3 l-l
Explanation of abbreviations and terms ................................................... 1-4 l-l
2 EMERGENCY POWER SYSTEMS
Emergency power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-l 2-l
Types ofpowergeneration sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 2-l
Buildings & enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 2-2
Fuel storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4 2-2
Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 2-3
Distribution systems ..................................................................... 2-6 2-3
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7 2-4
Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8 2-4
Load shedding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9 2-8
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10 2-9
3. PRIME MOVERS
Mechanical energyy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-l 3-l
Diesel enginess. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 3-2
Types of diesel engines.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 3-3
Diesel fuel system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 3-6
Diesel cooling system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5 3-9
Lubrication system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6 3-12
Starting system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7 3-15
Governor/speed control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8 3-17
--
Air intake system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9 3-20
Exhaust systemm .......................................................................... 3-10 3-2 1
Service practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11 3-22
Operational trends and engine overhaul ................................................... 3-12 3-24
Gasturbineengines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 3-27
Gas turbine engine classifications. ........................................................ 3-14 3-27
Principlesofoperation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 3-28
Gas turbine fuel system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16 3-29
Gas turbine cooling system.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17 3-29
Lubrication system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18 3-3 1
Starting system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-39 3-35
Governor/speed control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20 3-35
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 1 3-37
Gas turbine service practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22 3-37
4. GENERATORS AND EXCITERS
Electrical energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-l 4-l
Generator operationn. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 4-l
Types of generators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3 4-l
AC generators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4 4-l
Alternator types.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5 4-l
Design.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6 4-7
Characteristics of generators. ............................................................. 4-7 4-7
Exciters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8 4-8
Characteristics of exciters ................................................................ 4-9 4-9
Field flashing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10 4-9
Bearings and lubrication.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11 4-9
Generator maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12 4-10
Insulation testin gg.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13 4-11

_
_
Approved for public release. Distribution is unlimited.
TM 5-685/NAVFAC MO-912

Paragraph Page
CHAPTER 5. SWITCHGEAR
Switchgear definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-l 5-l
--_
Types of switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2 5-l
Low voltage elements.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3 5-l
Medium voltage elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4 5-9
Transfer switchesss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5 5-13
Regulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6 5-15
Instrumentation.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7 5-17
Relays.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8 5-18
Miscellaneous devices.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9 5-20
6. OPERATING PROCEDURES
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-l 6-l
Attended stations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2 6-l
Unattended stations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3 6-2
Nonparalleled stations.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4 6-2
Paralleled with the electric utility system. ................................................. 6-5 6-4
Paralleled with other generating units. .................................................... 6-6 6-4
Operational testing.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7 6-4
7. ROUTINE MAINTENANCE
Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-l 7-l
Prime mover maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2 7-l
Generator and exciter maintenance ....................................................... 7-3 7-4
Switchgear maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4 7-5
8. LUBRICATING OIL PURIFICATION
Purification systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-l 8-l
Forms of contamination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2 8-1
Methods of purifyingg. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3 8-l
Oil maintenance procedures.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4 a2
APPENDIX A. REFERENCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-l
APPENDIX B. FUEL AND FUEL STORAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-l
APPENDIX C. LUBRICATING OIL.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . c-1
APPENDIX D. COOLING SYSTEMS AND COOLANTS. .............................................................. D-l
APPENDIX E. SAFETY.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-l
APPENDIX F. RECORDS.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-l
APPENDIX G. DIESEL ENGINES: OPERATION, TIMING, AND TUNING INSTRUCTIONS. ........................... G-l
GLOSSARY . . . . . . . . . . . . . . . . . . ..~............................................................................... Glossary- 1
INDEX . . . . . . . . . . . . . . . . . . ..~............................................................................... Index- 1

Page
Figure 2-l. Typical installation of an emergency power plant. .................................................... 2-3
2-2. Types of system grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2-3. Typical grounding system for a building ............................................................. 2-9
3-l. Typical gasoline powered emergency generator set, air cooled ......................................... 3-2
3-2. Typical small stationary diesel generator unit, air cooled. ............................................. 3-3
3-3. Typical large stationary diesel generator unit ........................................................ 3-3
3-4. Typical diesel power plant on transportable frame base. .............................................. 3-4
3-5. Timing diagramss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3-6. Diagram of typical fuel, cooling, lubrication, and starting systems ..................................... 3-7
3-7. Diesel engine liquid cooling system. ................................................................. 3-10
3-8. Cross section of diesel engine showing chamber for lubricating oil collection. ........................... 3-14
3-9. Diesel engine lubrication system.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
3-10. Battery for engine starting system.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
3-11. Chart of speed droop characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3- 17
3-12. Mechanical governor r ............................................................................... 3-19
3-13. Hydraulic governor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20
3-14. Carburetor and pneumatic governor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20
3-15. Oil bath air cleanerr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 1
3-16. Diagram of turbocharger operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
3-17. Performance data plots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-25
3-18. Maintenance data plots. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-26
3-19. Typical gas turbine engine for driving electric power generator. ....................................... 3-28
3-20. Gas turbine engine, turboshaft t ...................................................................... 3-28
3-2 1. Typical types of combustors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-30

ii
TM 5-685/NAVFAC MO-912

Page
Figure 3-22. Engine combustion section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 1
r
r
I

Ii ._ _ 3-23. Engine combustion liner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-32


tI 3-24. Air cooling modes of turbine vanes and blades ....................................................... 3-33
E$ 3-25. Turbine blade cooling air flow. ...................................................................... 3-34
[ 3-26. Turbine vane cooling air flow ....................................................................... 3-35
1 3-27. Lubrication system for gas turbine .................................................................. 3-36
[i 4-l. Typical alternating current generator. ............................................................... 4-2
7
[ 4-2. Brush-type excitation system, schematic. ............................................................ 4-2
;r - 4-3. Brush-type AC generator field and rotor. ............................................................ 4--3
4-4. AC generator field with brushless-type excitation system ............................................. 4-3
4-5. Two-wire, single-phase alternator ................................................................... 4-4
4-6. Three-wire, single-phase alternator ................................................................. 4-4
4-7. Three-wire, three-phase alternator .................................................................. 4-5
4-8. Four-wire, three-phase alternator ................................................................... 4--6
4-9. Dualvoltageandfrequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
4-10. Powertriangle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
5-l. Typical arrangement of metal enclosed switchgear. ................................................... 5-2
5-2. Typical switchgear control circuitry, one-line diagram. ................................................ 5-3
5-3. Typical time-current characteristic curve ............................................................ 5-4
5-4. Instrument transformers, typical applications. ....................................................... 5-5
5-5. Current flow in instrument transformers. “Polarity” marks show instantaneous flows. .................. 5-6
5-6. AC control circuitss. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
5-7. AC control circuits with tie breaker ................................................................. 5-7
5-8. Maintenance for typical low voltage switchgear with air circuit breakers. .............................. 5-8
5-9. Arc interruption in oil, diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
5-10. Air blast arc interrupter, diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
5-11. Cross sectional view of vacuum arc interrupter. ...................................................... 5-11
6-l. Typical station layout, one-line diagram ............................................................. 6-3
F-l. Emergency/Auxiliary generator operating log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-2
F-2. Emergency/Auxiliary generator operating log (reverse). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-3

LIST OF TABLES

Page
Table 3-l. Unit injector system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
3-2. Common rail injector system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
3-3. In-line pumps and injection nozzle system ........................................................... 3-8
3-4. Typical cooling system components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
3-5. Dieselenginestroubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
4-l. Generator inspection list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
4-2. Generator troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
4-3. Interpreting insulation resistance test results. ....................................................... 4-12
4-4. Condition of insulation indicated by dielectric absorption ratios ....................................... 4-12
5-1. Low voltage circuit breaker troubleshooting. ......................................................... 5-9
5-2. Switchgear equipment troubleshooting .............................................................. 5-16
5-3. Relay troubleshootingg. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-19
8-1. Oil quality standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
D-l. Antifreeze solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-2
G-l. Ignition delav and duration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-l

iii
TM 5-685/NAVFAC MO-912

CHAPTER 1
INTRODUCTION

1-1. Purpose. maintenance personnel must have access to all


This manual covers the various types of auxiliary other literature related to the equipment in use.
power generating systems used on military instal- This includes military and commercial technical
lations. It provides data for the major components manuals and engineering data pertaining to their
of these generating systems; such as, prime movers, particular plant.
generators, and switchgear. It includes operation b. Appendixes B through F provide details re-
of the auxiliary generating system components lated to fuel storage, lubricating oil, coolant, forms
and the routine maintenance which should be and records, and safety (including first aid). Texts
performed on these components. It also describes and handbooks are valuable tools for the trained
the functional relationship of these components and engineer, supervisor, and operator of a power plant.
the supporting equipment within the complete sys- The manufacturers of the components publish de-
tem. tailed operating, maintenance, and repair manuals.
Instructions, applicable to the equipment, are pro-
1-2. Scope. vided by each manufacturer and should be filed at
The guidance and data in this manual are intended the plant for safekeeping and use. Replacement cop-
to be used by operating, maintenance, and repair ies are available from each manufacturer.
personnel. It includes operating instructions, stan-
dard inspections, safety precautions, troubleshoot- 1-3. References.
ing, and maintenance instructions. The information Appendix A contains a list of references used in this
applies to reciprocating (diesel) and gas turbine manual. Other pertinent literature may be substi-
prime movers, power generators, switchgear, and tuted or used as supplements.
subsidiary electrical components. It also covers fuel,
air, lubricating, cooling, and starting systems. 1-4. Explanation of abbreviations and terms.
-
a. In addition to the information contained in Abbreviations and special terms used in this
this manual, power plant engineers, operators, and manual are explained in the glossary.

1-1
TM 5-685/NAVFAC MO-912

CHAPTER 2

EMERGENCY POWER SYSTEMS

2-1. Emergency power. ally is started manually; a class B plant may have
Emergency power is defined as an independent re- either a manual or an automatic start system. Ac-
serve source of electric energy which, upon failure cordingly, a class B plant is almost as costly to
or outage of the normal source, automatically pro- construct and operate as a primary power plant of
similar size. Usually, a class B plant is a
vides reliable electric power within a specified time.
permanent-type unit capable of operating between
a. A reliable and adequate source of electric
1000 and 4000 hours annually. The class C plant
power is necessary for the operation of active mili-
always has an autostart control system (set to start
tary installations. Power must also be available at
the plant when the primary power voltage varies or
inactive installations to provide water for fire pro- the frequency changes more than the specified op-
tection, energy for automatic fire alarms, light for erational requirements).
security purposes, heat for preservation of critical (1) A class B plant (considered a standby long-
tactical communications and power equipment, and term power source) is used where multiple commer-
for other operations. cial power feeders are not available or extended and
b. Power, supplied by either the local utility com- frequent power outages may occur. Total fuel stor-
pany or generated on-site, is distributed over the age must be enough for at least 15 days continuous
activity. The source of distribution may be subject to operation.
brownout, interruption or extended outage. Mis- (2) A class C plant is used where rapid restora-
sion, safety, and health requirements may require tion of power is necessary to feed the load. More
an uninterruptible power supply (UPS) or than one class C unit is usually used when the
standby/emergency supply for specific critical loads. technical load exceeds 300 kW at 208Y/120 volts or
Justifiable applications for auxiliary generator are: 600 kilowatts (kW) at 48OY/277 volts. Spare class C
(1) Hospitals (life support, operating room, units are sometimes provided for rotational mainte-
.._ emergency lighting and communication, refrigera- nance service. The autostart control system ensures
tion, boiler plant, etc.). that the load is assumed as rapidly as possible.
(2) Airfields (control tower, communications, Diesel engine prime movers may be equipped with
traffic control, engine start, security, etc.). coolant and lubricating oil heaters to ensure quick
(3) Data processing plant systems. starting. Recommended total fuel storage must be
(4) Critical machinery enough for at least seven days continuous opera-
(5) Communication and security. tion.
c. It is essential that a schematic showing the c. Emergency generators must provide adequate
loads to be carried by an auxiliary generator be power for critical loads of a building or a limited
available for reference. Do not add loads until it is group of buildings, heating plants, utility pumping
approved by responsible authority. plant, communication centers, or other such instal-
lations where interruption of normal service would
2-2. Types of power generation sources. be serious enough to justify installation of an auxil-
a. The critical uses of electric power at a site iary power plant. The plant must be reliable and
demand an emergency source of power whenever an easily started in all seasons of the year. The plant
outage occurs. Selection of the type of auxiliary gen- building should be completely fireproof with heating
erating plant is based on the mission of the particu- and ventilation facilities that satisfy the plant’s re-
lar site and its anticipated power consumption rate quirements. The space around the units should per-
during an emergency. The cost of plant operation mit easy access for maintenance and repair. Space
(fuel, amortized purchase price, depreciation, and should be provided within the building for safe stor-
insurance) and operation and maintenance person- age of fuel such as a grounded and vented “day”
nel requirements must be analyzed. Future load tank. Type and grade of fuel should be identified on
growth requirements of the site must be considered the tank. Important considerations for these plants
for size selection. included the following:
b. Auxiliary power generating plants are desig- (1) Selection of generators (size and quantity,
nated as either class B or class C. The design crite- type of prime mover, and load requirements).
ria for a class B plant is comparable to those of a (2) Determination of need for instrumentation
primary power plant. A primary power plant usu- (meters, gauges, and indicator lights).
2-1
TM 5-685/NAVFAC MO-912

(3) Selection of protective equipment (relays outlets and be well lighted with supplemental light-
and circuit breakers). ing for instrument panels. Heat for the building
(4) Determination of need for automatic start- should be steam, heat pumps or electric heaters to --
ers, automatic load transfer, etc. avoid hazards from explosive vapors.
(5) Selection of auxiliary generator size is c. Prime movers require a constant supply of
based on satisfying the defined electrical load re- large quantities of air for combustion of fuel. Com-
quirement (expressed as kilowatts). bustion produces exhaust gases that must be re-
d. Portable power plants are widely used on mili- moved from the building since the gases are hazard-
tary installations because of the temporary nature ous and noxious. The air is usually supplied via a
of many applications. The power plants (including a louvered ventilation opening. Exhaust gases are
diesel or gas turbine prime mover) are self- conducted to the outside by piping that usually in-
contained and mounted on skids, wheels, or semi- cludes a silencer or muffler (see fig 2-l).
trailers. Although the size of portable units may d. Precautions must be taken when environmen-
vary from less than 1 kW to more than 1,000 kW, tal conditions related to location of the generating
the most commonly used units are less than 500 kW system are extreme (such as tropical heat and/or
capacity. Reciprocating prime movers are usually desert dryness and dust). Cooling towers and spe-
used for portable power plants. Gas turbine engines cial air filters are usually provided to combat these
are frequently employed for smaller units because conditions. Arctic conditions require special heating
of their relatively light weight per horsepower. requirements.
e. Portable diesel powered generators usually op- e. When required for the auxiliary generating
erate at 1200, 1800 or 3600 revolutions per minute equipment, the building or enclosure should be fire-
(rpm), since high speeds allow a reduction in weight proof and constructed of poured concrete or concrete
of the generator plant. To keep weight down, such and cinder blocks with a roof of reinforced concrete,
ancillary equipment as voltage regulators, electric steel, or wood supports with slate or other fireproof
starters and batteries are sometimes omitted from shingles. Ventilation and openings for installation
the smaller generators. Starting may be done by and removal of materials and equipment should be
crank or rope, ignition by magneto, and voltage provided.
regulation through air-gap, pole-piece, and winding (1) Foundations. A generator and its prime
design. Portable plants usually have a minimum mover should be set on a single, uniform foundation
number of meters and gauges. Larger size portable to reduce alignment problems. The foundation
units have an ammeter, a frequency meter, a volt- should be in accordance with manufacturer’s recom-
meter, and engine temperature and oil pressure mendations for proper support of equipment and
gauges. Generator protection is obtained by fused dampening of vibrations. Foundation, prime mover,
switches or air circuit breakers. and generator should be mechanically isolated from
the building floor and structure to eliminate trans-
2-3. Buildings and enclosures. mission of vibrations. All mechanical and electrical
a. Auxiliary power generating equipment, espe- connections should allow for vibration isolation.
cially equipment having standby functions, should (2) Floors. The floors are usually concrete with
be provided with suitable housings. A typical power non-skid steel plates over cable and fuel-line
plant installation is shown in figure 2-l. The equip- trenches. The floor space should provide for servic-
ment should be located as closely as possible to the ing, maintenance, work benches, repair parts, tool
load to be served. Generators, prime movers, cabinets, desks, switchboard, and electrical equip-
switchboards, and associated switching equipment ment. Battery bank areas require protection from
should always be protected from the environment. corrosive electrolytes. Floors must be sealed to pre-
Many small units are designed for exterior use and vent dusting, absorption of oils and solvents, and to
have their own weatherproof covering. Transform- promote cleanliness and ease of cleanup. Plates and
ers and high-voltage switching equipment can be gratings covering floor trenches must be grounded.
placed outdoors if they are designed with drip-proof Rubber matting should be installed in front of and
enclosures. around switchboards and electrical equipment to
b. The buildings housing large auxiliary power minimize shock hazard.
generating systems (see fig 2-1) require adequate
ceiling height to permit installation and removal of 2-4. Fuel storage.
cylinder heads, cylinder liners, pistons, etc., using Fuel storage space should be provided near the
chain falls. An overhead I-beam rail, or movable plant, with enough capacity to allow replenishment
structure that will support a chain fall hoist, is in economical, reasonable intervals. The total fuel
necessary. The building should have convenience storage capacity should be large enough to satisfy
2-2
TM 5-685/NAVFAC MO-912

EXHAUST S I L E N C E R
AUTOMATIC AUTOMATIC
CRANKING TRANSFER
\
PANEL7 r SWITCH
tl I
VENT

~ I 10001
El lzTlwd $ ?___
1
DUCT
--of?
’ COOLING

PRIME
MOVER

VENTILATION
LOUVERS

CONCRETE
BASE -

/ VIBRATION
GENERATOR DAMPENERS

Figure 2-l. Typical installation of an emergency power plant.

the operational requirements of the class B or class age as liquids. Methods to determine tank contents
C generating plants that are used. Fuel logistics are covered in paragraph 5-7b(8).
should be considered when sizing fuel storage ca- d. Day tanks. A grounded and vented day tank,
pacity having not more than 275 gallons capacity, is in-
a. Fuels for the equipment described herein (re- stalled within the power plant building. The tank is
fer to app C) are combustible substances that can be normally filled by transfer pump from the installa-
burned in an atmosphere of oxygen. Two categories tion’s main storage tank. Provision should be made
of fuel storage are discussed: liquids and gases. In to fill the day tank by alternate means (or directly
either case, fuel storage tanks, associated pumps from safety cans or barrels) if the transfer system
and piping systems must be grounded and protected fails.
from galvanic, stray current or environmental cor-
rosion. 2-5. Loads.
b. Liquid fuel for auxiliary power generating sys- Most electrical plants serve a varied load of light-
tems is usually stored in buried tanks equipped ing, heating equipment, and power equipment,
with vent pipes and manholes. Above-ground tanks some of which demand power day and night. The
may be used for storage at some locations. These annual load factor of a well-operated installation
tanks usually have provisions for venting, filling will be 50 percent or more with a power factor of 80
and cleaning. A gauge with indicator is used to de- percent or higher. Equipment and controls must be
termine tank contents. Two tanks are necessary to selected to maintain frequency and voltage over the
ensure a continuous supply during tank cleaning load range.
(every two years) and maintenance operations. Pro-
visions must be made to use a gauge stick to posi- 2-6. Distribution systems.
tively determine depth of tank contents. Storage a. The load determines direct current (DC) or
tanks should be checked for settled water accumu- alternating current (AC), voltage, frequency (DC, 25
lated through condensation and the free water Hertz (Hz), 50 Hz, 60 Hz, 400 Hz), phases and AC
drained periodically. configuration (delta or wye). Voltage and other pa-
c. Gaseous fuel is stored in tanks either as a gas rameters of the distribution system will have been
or a liquid, depending on the type of fuel. Natural selected to transmit power with a minimum of con-
gas is stored as a gas. Butane and propane are version (AC to DC), inversion (DC to AC), (AC)
cooled and kept under moderate pressure for stor- transformer, impedance, and resistance loss. For a
2-3
TM 5-685/NAVFAC MO-912

given load; higher voltage, unity power factor, low longer insulation life of generators, motors, trans-
resistance/impedance, and lower frequency gener- formers, and other system components by suppress-
ally result in lower distribution losses. Use of equip- ing transient and sustained overvoltages associated
----
ment to change or regulate voltage, frequency or with certain fault conditions. In addition, system
phase introduces resistance, hysteresis and me- grounding improves protective relaying by provid-
chanical losses. ing fast, selective isolation of ground faults.
b. A lagging power factor due to inductive loads b. Equipment grounding, in contrast to system
(especially under-loaded induction motors) results grounding, relates to the manner in which
in resistive losses (I’R) because greater current is noncurrent-carrying metal parts of the wiring sys-
required for a given power level. This may be cor- tem or apparatus, which either enclose energized
rected by the use of capacitors at the station bus or conductors or are adjacent thereto, are to be inter-
by “run” capacitors at induction motors to have the connected and grounded. The objectives of equip-
generator “see” a near-unity but yet lagging power ment grounding are:
factor. (1) To ensure freedom from dangerous electric
c. Overcorrection, resulting in a leading (capaci- shock-voltage exposure to persons.
tive) power factor must be avoided. This condition (2) To provide current-carrying capability dur-
results in severe switching problems and arcing at ing faults without creating a fire or explosive haz-
contacts. Switching transients (voltage spikes, har- ard.
monic transients) will be very damaging to insula- (3) To contribute to superior performance of the
tion, controls and equipment. The electronics in ra- electric system.
dio, word and data processing, and computer arrays c. Many personal injuries are caused by electric
are especially sensitive to switching and lighting shock as a result of making contact with metallic
transients, over/under voltage and frequency members that are normally not energized and nor-
changes. mally can be expected to remain non-energized. To
d. The distribution system must include sensing minimize the voltage potential between noncurrent-
devices, breakers, and isolation and transfer feed carrying parts of the installation and earth to a safe
switches to protect equipment and personnel. value under all systems operations (normal and ab-
normal), an installation grounding plan is required.
2-7. Frequency. d. System grounding. There are many methods of -
The frequency required by almost all electrical system grounding used in industrial and commer-
loads is the standard 50 or 60 Hz. Most electrical cial power systems (refer to fig 2-2), the major ones
equipment can operate satisfactorily when the fre- being:
quency varies plus or minus ten percent (tlO%). (1) Ungrounded.
Steady state frequency tolerance (required for (2) Solidly grounded.
frequency-sensitive electronic equipment) should (3) Resistance grounding: low-resistance, high-
not exceed plus or minus 0.5 percent of design fre- resistance.
quency. Since some equipment are sensitive to fre- (4) Reactance grounding.
quency changes, operators must closely monitor fre- e. Technically, there is no generally accepted use
quency meters and regulate frequency when of any one particular method. Each type of system
necessary. grounding has advantages and disadvantages. Fac-
tors which influence the choice of selection include:
2-8. Grounding.
(1) Voltage level of the power system.
Grounding implies an intentional electrical connec- (2) Transient overvoltage possibilities.
tion to a reference conducting plane, which may be (3) Type of equipment on the system.
earth (hence the term ground) but more generally (4) Cost of equipment.
consists of a specific array of interconnected electri- (5) Required continuity of service.
cal conductors referred to as grounding conductors. (6) Quality of system operating personnel.
The term “grounding” as used in electric power sys- (7) Safety considerations, including fire hazard
tems indicates both system grounding and equip- and others
ment grounding, which are different in their objec- f. An ungrounded system is a system in which
tives. there is no intentional connection between the neu-
a. System grounding relates to a connection from tral or any phase and ground. “Ungrounded system”
the electric power system conductors to ground for literally implies that the system is capacitively
the purpose of securing superior performance quali- coupled to ground.
-
ties in the electric system. There are several meth- (1) The neutral potential of an ungrounded sys-
ods of system grounding. System grounding ensures tern under reasonably balanced load conditions will
2-4
TM 5-685/NAVFAC MO-912

VOLTAGE
RELAY

200-400A.I

TRANSFORMER -
____P
RESISTOR
IRATED FOR
2 TO 6A.I

C. D.

Figure 2-2. Types of system grounding.


A) UNGROUNDED GENERATOR, B) SOLIDLY GROUNDED, C) LOW RESISTANCE GROUNDING,
D) HIGH RESISTANCE GROUNDING

be close to ground potentials because of the ca- line voltage (i.e., square root of three (3) times
pacitance between each phase conductor and the normal line-to-neutral value). Over a period of
ground. When a line-to-ground fault occurs on time this breaks down the line-to-neutral insulation
an ungrounded system, the total ground fault and results in insulation failure. Ungrounded sys-
current is relatively small, but the voltage to ground tem operation is not recommended because of the
potential on the unfaulted phases can reach an high probability of failures due to transient
unprecedented value. If the fault is sustained, over-voltages (especially in medium voltage i.e., 1
the normal line-to-neutral voltage on the un- kilovolt (Kv)-15 Kv) caused by restriking ground
faulted phases is increased to the system line-to- faults.

2-5
TM 5-685/NAVFAC MO-912

(2) Overvoltage limitation is particularly im- Manufacturers Association 1-78 places a require-
portant in systems over 1 Kv, because equipment in ment on the design of synchronous generators that
these voltage classes are designed with less margin their windings shall be braced to withstand the
between 50/60 Hz test and operating voltages than mechanical forces resulting from a bolted 3-phase
low voltage equipment. The remaining various short circuit at the machine terminals. The current
grounding methods can be applied on system created by a phase-to-ground fault occurring close
grounding protection depending on technical and to the generator will usually exceed the 3-phase
economic factors. The one advantage of an un- bolted fault current. Due to the high cost of genera-
grounded system that needs to be mentioned is that tors, the long lead time for replacement, and system
it generally can continue to operate under a single impedance characteristics, a solidly grounded neu-
line-to-ground fault without significant damage to tral is not recommended for generators rated be-
electrical equipment and without an interruption of tween 2.4 Kv and 15 Kv.
power to the loads. (4) Limiting the available ground fault current
g. A solidly grounded system refers to a system in by resistance grounding is an excellent way to re-
which the neutral, or occasionally one phase, is con- duce damage to equipment during ground fault con-
nected to ground without an intentional intervening ditions, and to eliminate personal hazards and elec-
impedance. On a solidly grounded system, in con- trical fire dangers. It also limits transient
trast to an ungrounded system, a ground fault on overvoltages during ground fault conditions. The
one phase will result in a large magnitude of ground resistor can limit the ground fault current to a de-
current flow but there will be no increase in voltage sired level based on relaying needs.
on the unfaulted phase. h...Low-resistance grounding refers to a system in
(1) On low-voltage systems (1 Kv and below), which the neutral is grounded through a consider-
the National Electrical Code (NEC) Handbook, ar- ably smaller resistance than used for high-
ticle 250-5(b) requires that the following class of resistance grounding. The resistor limits ground
systems be solidly grounded: fault current magnitudes to reduce the damage dur-
(a) Where the system can be so grounded ing ground faults. The magnitude of the grounding
that the maximum voltage to ground on the un- resistance is selected to detect and clear the faulted
grounded conductors does not exceed 150 volts. circuit. Low-resistance grounding is used mainly on
(b) Where the system is 3 phase, 4 wire wye medium voltage systems (i.e., 2.4 Kv to 15 Kv),
connected in which the neutral is used as a circuit especially those which have directly connected ro-
conductor. tating apparatus. Low-resistance grounding is not
(c) Where the system is 3 phase, 4 wire delta used on low-voltage systems, because the limited
connected in which the midpoint of one phase wind- available ground fault current is insufficient to posi-
ing is used as a circuit conductor. tively operate series trip units.
(d) Where a grounded service conductor is (1) Low-resistance grounding normally limits
uninsulated in accordance with the exceptions to the ground fault currents to approximately 100 to
NEC articles 230-22, 230-30, and 230-41. 600 amps (A). The amount of current necessary for
(2) Solid grounding is mainly used in low- selective relaying determines the value of resistance
voltage distribution systems (less than 1000 volt (V) to be used.
system) and high-voltage transmission systems (2) At the o ccurrence e of a line-to-ground fault
(over 15 Kv). It is seldom used in medium-voltage on a resistance-grounded system, a voltage appears
systems (1 Kv to 15 Kv). Solid grounding has the across the resistor which nearly equals the normal
lowest initial cost of all grounding methods. It is line-to-neutral voltage. of the system. The resistor
usually recomrrended for overhead distribution sys- current is essentially equal to the current in the
tems supplying transformers protected by primary fault. Therefore, the current is practically equal to
fuses. However, it is not the preferred scheme for the line-to-neutral voltage divided by the number of
most industrial and commercial systems, again be- ohms of resistance used.
cause of the severe damage potential of high- i. High-resistance grounding is a system in which
magnitude ground fault currents. the neutral is grounded through a predominantly
(3) In most generators, solid grounding may resistive impedance whose resistance is selected to
permit the maximum ground fault current from the allow a ground fault current through the resistor
generator to exceed the maximum 3-phase fault cur- equal to or slightly more than the capacitive charg-
rent which the generator can deliver and for which ing current (i.e., I, > 31,,) of the system. The resis-
its windings are braced. This situation occurs when tor can be connected either directly from neutral to
the reactance of the generator is large in compari- ground for wye type systems where a system neu-
son to the system reactance. National Electrical tral point exists, or in the secondary circuit of a
2-6
TM 5-685/NAVFAC MO-912

grounding transformer for delta type systems where rent of about 8 A or less. This, however, should not
a system neutral point does not exist. However, be construed to mean that ground faults of a mag-
because grounding through direct high-resistance nitude below this level will always allow the suc-
entails having a large physical resistance size with cessful location and isolation before escalation oc-
a continuous current rating (bulky and very costly), curs. Here, the quality and the responsiveness of
direct high-resistance grounding is not practical the plant operators to locate and isolate a ground
and would not be recommended. High-resistance fault is of vital importance. To avoid high transient
grounding through a grounding transformer is cost overvoltages, suppress harmonics and allow ad-
effective and accomplishes the same objective. equate relaying, the grounding transformer and re-
(1) High-resistance grounding accomplishes sistor combination is selected to allow current to
the advantages of ungrounded and solidly grounded flow that is equal to or greater than the capacitive
systems and eliminates the disadvantages. It limits charging current.
transient overvoltages resulting from single phase j. Ground fault current can be reduced in distri-
to ground fault, by limiting ground fault currents to bution systems which are predominantly reactive
approximately 8 A. This amount of ground fault through reactance grounding. A reactor is connected
current is not enough to activate series over-current between the generator neutral and ground. The
protective devices, hence no loss of power to down- magnitude of the ground fault is directly related to
stream loads will occur during ground fault condi- the reactor size. The reactor should be sized such
tions. that the current flow through it is at least 25 per-
(2) Special relaying must be used on a high- cent and preferably 60 percent of the three phase
resistance grounded system in order to sense that a fault current. Because of the high level of ground
ground fault has occurred. The fault should then be fault current relative to resistance grounded sys-
located and removed as soon as possible so that if tems, reactance grounded systems are only used on
another ground fault occurs on either of the two high reactance distribution systems.
unfaulted phases, high magnitude ground fault cur- k. Whether to group or individually ground gen-
rents and resulting equipment damage will not oc- erators is a decision the engineer is confronted with
cur. when installing generator grounding equipment.
(3) High-resistance grounding is normally ap- Generators produce slightly non-sinusoidal voltage
plied on electrical systems rated 5kV and below. It waveforms, hence, circulating harmonic currents
is usually applied in situations where: are present when two or more generating units with
(a) It is essential to prevent unplanned sys- unequal loading or dissimilar electrical characteris-
tem power outages. tics are operated in parallel.
(b) Previously the system has been operated (1) The path for harmonic current is estab-
ungrounded and no ground relaying has been in- lished when two or more generator neutrals are
stalled. grounded, thus providing a loop for harmonic circu-
(4) NEC Articles 250-5 Exception No. 5 and lation. Because of the 120” relationship of other
250-27 have specific requirements for high imped- harmonics, only triple series (3rd, 9th, 15th, etc.)
ance grounding for system voltages between 480 harmonic currents can flow in the neutral. Har-
and 1000 Vi For those system voltages the following monic current problems can be prevented by: elimi-
criteria apply: nating zero sequence loops (undergrounding the
(a) The conditions of maintenance and su- generator neutrals); providing a large impedance in
pervision assure that only qualified persons will the zero sequence circuit to limit circulating cur-
service the installation. rents to tolerable levels (low or high resistance
(b) Continuity of power is required. grounding the generator neutrals); connecting the
(c) Ground detectors are installed on the sys- generator neutrals directly to the paralleling
tem. switchgear neutral bus and grounding the bus at
(d) Line-to-neutral loads are not served. one point only; or, grounding only one generator
(5) Depending on the priority of need, high re- neutral of a parallel system.
sistance grounding can be designed to alarm only or (2) An effective ground grid system in power
provide direct tripping of generators off line in order plants or substations is highly important and one
to prevent fault escalation prior to fault locating that deserves careful analysis and evaluation. The
and removal. High-resistance grounding (arranged primary function of a ground grid is to limit volt-
to alarm only) has proven to be a viable grounding ages appearing across insulation, or between sup-
mode for 600 V and 5 kV systems with an inherent posedly non-energized portions of equipment or
total system charging current to ground (31,J of structures within a person’s reach under ground
about 5.5 A or less, resulting in a ground fault cur- fault conditions. Reducing the hazard ensures the
2-7
TM 5-685/NAVFAC MO-912

safety and well being of plant personnel or the pub- cable trays, metal enclosures, etc.) should be electri-
lic at large. A ground grid system should also pro- cally continuous and bonded to the protective
vide a significantly low resistance path to ground grounding scheme. Continuous grounding conduc-
and have the capability to minimize rise in ground tors such as a metallic raceway or conduit or desig- __
potential during ground faults. nated ground wires should always be run from the
(3) The conductive sheath or armor of cables ground grid system (i.e., location of generators) to
and exposed conductive material (usually sheet downstream distribution switchboards to ensure
metal) enclosing electrical equipment or conductors adequate grounding throughout the electrical distri-
(such as panelboards, raceways, busducts, switch- bution system. Permanent grounding jumper cables
boards, utilization equipment, and fixtures) must be must effectively provide a ground current path to
grounded to prevent electrical shock. All parts of the and around flexible metallic conduit and removable
grounding system must be continuous. meters. Shielded cables must be grounded per
(4) Personnel should verify that grounding for manufacturers’ requirements. Shielded coaxial
the system is adequate by performing ground resis- cable requires special grounding depending on use
tance tests. and function. A voltmeter must be used for detecting
(5) The ground grid of the plant should be the potential differences across the break in a bonding
primary system. In some cases a metallic under- strap or conductor before handling.
ground water piping system may be used in lieu of a (9) A typical grounding system for a building
plant ground grid, provided adequate galvanic and containing heavy electrical equipment and related
stray current corrosion protection for the piping is apparatus is shown in figure 2-3. The illustration
installed, used and tested periodically. This practice shows the following:
is not acceptable in hazardous areas and is not (a) Grounding electrodes (driven into the
recommended if the piping system becomes sacrifi- earth) to maintain ground potential on all con-
cial. nected conductors. This is used to dissipate (into the
(6) The plant ground grid should have a system earth) currents conducted to the electrodes.
resistance of 10 ohms or less. Ground grid system (b) Ground bus (forming a protective ground-
resistance may be decreased by driving multiple ing network) which is solidly connected to the
ground electrode rods. A few rods, deeply driven and grounding electrodes. --
widely spaced, are more effective than a large num- (c) Grounding conductors (installed as neces-
ber of short, closely spaced rods. Solid hard copper sary) to connect equipment frames, conduits, cable
rods should be used, not copperplated steel. When trays, enclosures, etc., to the ground bus.
low resistance soils are deep, the surface extension (10) Radio frequency interference (RFI) is in-
rods may be used to reach the low resistance stra- terference of communications transmission and re-
tum. Bonding of ground conductors to rods should ception caused by spurious emissions. These can be
be by permanent exothermic weld (preferred) or generated by communications equipment, switching
compression sleeve, and not by bolted clamp (corro- of DC power circuits or operations of AC generation,
sion results in high resistance connection). Resis- transmission, and power consumers. The fre-
tance at each rod in a multiple system should not quencies and sources of RFI can be determined by
exceed 15 ohms. tests. Proper enclosures, shielding and grounding of
(7) Reliable ground fault protection requires AC equipment and devices should eliminate RFI.
proper design and installation of the grounding sys- RFI can be carried by conductive material or be
tem. In addition, routine maintenance of circuit pro- broadcast. Lamp ballasts, off-spec radio equipment
tective equipment, system grounding, and equip- and certain controls may be the prime suspects. The
ment grounding is required (refer to ground radio engineer or technician can trace and recom-
resistance testing, chap 7). mend actions to eliminate or suppress the emis-
(8) Equipment grounding refers to the method sions. Pickup of RFI can also be suppressed by in-
in which conductive enclosures, conduits, supports, creasing the separation distance between power and
and equipment frames are positively and perma- communication conductor runs.
nently interconnected and connected to the ground-
ing system. Grounding is necessary to protect per- 2-9. Load shedding.
sonnel from electric shock hazards, to provide Load shedding is sometimes required during emer-
adequate ground fault current-carrying capability gency situations or while operating from an auxil-
and to contribute to satisfactory performance of the iary power source in order to ensure enough power
electrical system. Electrical supporting structures gets to the critical circuits (such as the circuits re-
within the substation (i.e., metal conduit, metal quired for classified communications or aircraft
2-8
TM 5-685/NAVFAC MO-912

5GROUNDING ELECTRODE
CONFIGURATION-
LESS THAN IO FT

Figure 2-3. Typical grounding system for a building.

flight control). Emergency situations include the project and of the equipment, fuel cost and avail-
handling of priority loads during power “brown- ability, installation cost, and personnel availability
outs” and sharing load responsibilities with prime and cost. Factors related to prime movers must also
power sources during “brown-outs”. Usually load be considered: the diesel because of its relatively
shedding consists of a documented plan that in- low cost and good reliability record, as well as its
cludes a method for reducing or dropping power to ability to use liquid or gaseous fuel; the gas turbine
noncritical equipment. This plan should include an for permanent standby plants because it is rela-
updated schematic for load shedding reference and tively compact in relation to its high generating
“Truth Table” to ensure correct sequencing of drop- capacity (desirable if the anticipated power con-
ping and restoring loads on the system. Plans for sumption rate is high). The components of the typi-
load shedding are part of the emergency operating cal power systems are briefly described in the fol-
instructions and vary from one facility to another. lowing paragraphs.
The extent of load shedding and the sequence of
a. Prime movers are reciprocating engines, gas
dropping loads and restoring to normal are also
turbines, or other sources of mechanical energy
. contained in the plan.
used to drive electric generators.
2-10. Components . b. Governors control and regulate engine speed.
Standards for selection of components for an auxil- A governor must be capable of regulating engine
iary power plant are usually based on the electrical speed at conditions varying between full-load and
loads to be supplied, their demand, consumption, no-load and controlling frequency.
voltage, phase, and frequency requirements. Also to c. Generators are machines (rotating units) that
be considered are load trend, expected life of the convert mechanical energy into electrical energy.
2-9
TM 5-685/NAVFAC MO-912

d. Exciters are small supplemental generators g. Switchgear is a cabinet enclosure containing


that provide DC field current for alternating cur- devices for electric power control and regulation,
rent generators. Either rotating or static-type excit- and related instrumentation (meters, gauges, and
-
ers are used. indicator lights).
e. Voltage regulators are devices that maintain h. Instrumentation senses, indicates, may record
the terminal voltage of a generator at a predeter- and may control or modulate plant electrical, ther-
mined value. mal and mechanical information essential for
f. Transfer switches are used to transfer a load proper operation. It may also provide an alarm to
from one bus or distribution circuit to another, or to indicate an unacceptable rate of change, a warning
isolate or connect a load. The rating of the switch or of unsatisfactory condition, and/or automatic shut-
breaker must have sufficient interrupting capacity down to prevent damage.
for the service.
TM 5-685/NAVFAC MO-912

CHAPTER 3

PRIME MOVERS

3-1. Mechanical energy. (4) In the Otto cycle, the fuel/air mixture is
A prime mover is an engine that converts hydraulic, compressed and ignited by a timed spark. The exact
chemical, or thermal energy to mechanical energy ratio of fuel to air is achieved by carburization of a
with the output being either straight-line or rotary volatile fuel. Fuel injection is also in use in the Otto
motion. Rotary mechanical energy is used to drive cycle to achieve more precise fuel delivery to each
rotary generators to produce electrical energy. Over cylinder.
the last 125 years, the internal combustion engine, (5) Four-cycle SI gasoline engines are used as
steam turbine and gas turbine have displaced the prime movers for smaller portable generator drives
steam engine. Auxiliary electrical generators are (see fig 3-l). The advantages are:
today usually driven by either reciprocating engine (a) Low initial cost.
or gas turbine. These are available in wide ranges of (b) Light weight for given output.
characteristics and power rating, have relatively (c) Simple maintenance.
high thermal efficiency and can be easily started (d) Easy cranking.
and brought on line. In addition, their speed can be (e) Quick starting provided fuel is fresh.
closely regulated to maintain alternating current (f) Low noise level.
system frequency. (6) The disad vantages of using four-cycle SI
a. Fuel is burned directly in the internal combus- gasoline engines are:
tion engine. The burning air/fuel mixture liberates (a) Greater attendant safety hazards due to
energy which raises the temperature of the mixture use of a volatile fuel.
and, in turn, causes a pressure increase. In the (b) Greater specific fuel consumption than
reciprocating or piston engine this occurs once for compression ignition (CI) engines.
each power stroke. The pressure accelerates the pis- (7) Reciprocating CI engines. These operate on
- ton and produces work by turning the crankshaft the Diesel Cycle principle typical for all CI engines.
against the connected load. The-events are:
(1) Reciprocating spark ignition (SI) engines. (a) Intake stroke. Air is drawn into the cylin-
These engines operate on the Otto Cycle principle der.
typical for all reciprocating SI engines. The events (b) Compression stroke. Air is compressed,
are: raising the pressure but ‘also raising the tempera-
(a) Intake stroke. A combustible fuel/air mix- ture of the air above the ignition temperature of the
ture is drawn into the cylinder. fuel to be injected.
(b) Compression stroke. The temperature (c) Power stroke. A metered amount of fuel at
and pressure of the mixture are raised. greater-than-cylinder-pressure is injected into the
(c) Power (expansion) stroke. Ignition of the cylinder at a controlled rate. The fuel is atomized
pressurized gases results in combustion, which and combustion occurs, further increasing pressure,
drives the piston toward the bottom of the cylinder. thus driving the piston which turns the crankshaft.
(d) Exhaust stroke. The burned gases are (d) Exhaust stroke. The burned gas is forced
forced out of the cylinder. from the cylinder.
(2) Four strokes of the piston per cycle are re- (8) As with the SI four-cycle engine, the four
quired (four-stroke cycle or four-cycle). One power cycles of the CI engine occur during two revolutions
stroke occurs in two revolutions of the crankshaft. of the crankshaft, and one power stroke occurs in
(3) The output o fan engine can be increased every two revolutions.
with some loss in efficiency by using a two-stroke (9) The CI or d’ diesel engine may also use two-
(two-cycle) Otto process. During the compression cycle operation with increased output but at lower
stroke, the fuel/air mixture is drawn into the cylin- engine efficiency.
der. During the power stroke, the mixture in the (10) In the Diesel cycle, only air is compressed
cylinder is compressed. Near the end of the power and ignition of the fuel is due to the high tempera-
stroke, burned gases are allowed to exhaust, and ture of the air. The CI engine must be more stoutly
the pressurized new mixture is forced into the cyl- constructed than the SI engine because of the
inder prior to the start of the next compression higher pressures. The CI engine requires high-
stroke. pressure fuel injection.
3-1
T M 5-685/NAVFAC MO-9 12

(d) High efficiency up to rated load.


(4) The disadvantages of using a gas turbine
are:
(a) Initial cost is high.
(b) Fuel and air filtering are required to
avoid erosion of nozzles and blades.
(c) Fine tolerance speed reducer between tur-
bine and generator is required and must be kept in
alignment.
(d) Specialized maintenance, training, tools
and procedures are required.
(e) Considerable energy is required to spin
for start.
(f) High frequency noise level.
(g) Exhaust volume is considerable.
(h) A large portion of the fuel heat input is
used by the compressor.
(i) A long bedplate is required.
(j) Maximum load is sharply defined.
Figure 3-l. emergency (h) Efficiency is lower than reciprocating en-
gines.
c. Rotary spark ignition engines. These engines
b. Gas turbine engine. The fuel and air burn in a are typified by the Wankel-type engine operating on
combustion chamber in the gas turbine engine. The the Otto principle. Each of the four cycles occurs in
resulting high-pressure gases are directed through a specific sector of an annular space around the axis
nozzles toward the turbine blades and produce work of the shaft. The piston travels this annular cham-
by turning the turbine shaft. This is a continuous ber and rotates the shaft. The power stroke occurs
process in the continuous-combustion or constant- once in every shaft revolution, dependent on the
pressure gas turbine. design of the engine. This engine can produce a __
(1) Gas tu rb ines operate on the Brayton Cycle large amount of power for a given size. The high
principle. While a number of configurations are rpm, low efficiency, friction and sealing problems,
used for aircraft propulsion (turbofan, turboprop, and unfavorable reliability of this engine make it
etc.), the one used as a prime mover for auxiliaries unsatisfactory as a prime mover for auxiliary gen-
is generally the continuous combustion gas turbine. erators. These faults may be corrected as the devel-
In this process, air is compressed by an axial flow opment continues.
compressor. A portion of the compressed air is mixed
3-2. Diesel engines.
with fuel and ignited in a combustion chamber. The
balance of the compressed air passes around the Diesel engines for stationary generating units are
chamber to absorb heat, and then it is merged with sized from 7.5 kW to approximately 1500 kW and
the burned products of combustion. The pressurized diesel engines for portable generating units are
mixture, usually at 1000°F or higher, flows into a sized from 7.5 kW to approximately 750 kW. See
reaction turbine. figures 3-2 through 3-4. Efficiency, weight per
(2) The turbine drives the compressor and also horsepower, and engine cost relationships are rela-
produces work by driving the generator. A portion of tively constant over a wide range of sizes. Smaller
the exhaust gas may be recirculated and it is pos- engines, which operate in the high-speed range
sible to recover heat energy from the waste exhaust. (1200 and 1800 rpm), are used for portable units
The compressor uses a relatively large portion of because of their lighter weight and lower cost. Low-
the thermal energy produced by the combustion. and medium-speed (200 and 900 rpm) engines are
The engine efficiency is highly dependent on the preferred for stationary units since their greater
efficiencies of the compressor and turbine. weight is not a disadvantage, and lower mainte-
(3) The advantages of using a gas turbine are: nance cost and longer life offset the higher initial
(a) Proven dependability for sustained op- cost.
eration at rated load. a. The advantages of diesel engines include:
(b) Can use a variety of liquid and gaseous (1) Proven dependability for sustained opera-
fuels. tion at rated load.
(c) Low vibration level. (2) Efficiency.

3-2
TM 5-685/NAVFAC MO-912

(3) Adaptability for wide range of liquid fuels.


(4) Controlled fuel injection.
b. The disadvantages include:
(1) High initial cost.
(2) High weight per given output.
(3) High noise level.
(4) Specialized maintenance.
(5) Fuel injection system has fine mechanical
tolerances and requires precise adjustment.
(6) Difficult cranking.
(7) Cold starting requiring auxiliary ignition
aids.
(8) Vibration.

3-3. Types of Diesel Engines.


Various configurations of single and multiple diesel
engines, either two-cycle or four-cycle are used to
Figure 3-2 Typical small stutionary diesel drive auxiliary generators. Multi-cylinder engines
generator unit, air cooled of either type can be of “V” or in-line configurations.

--

Figure 3-3. Typical large stationary diesel generator unit.

3-3
TM 5-685/NAVFAC MO-912

Figure 3-4. Typical diesel power plant on transportable frame base.

The “V” configuration is favored when there is a port (or the exhaust valve closes), then the scaveng-
lack of space because “V” engines are shorter and ing air port is closed. The piston now compresses
more compact than in-line engines. Most engines in the air to heat it to a temperature required for
use are liquid-cooled. Air cooling is sometimes used ignition as the piston nears top dead center (TDC).
with single-cylinder and other small engines (driv- As the piston nears TDC, a metered amount of fuel
ing generators with up to 10 kW output). Air-cooled is injected at a certain rate. Injection atomizes the
engines usually reach operating temperature fuel, which is ignited by the high temperature, and
quickly but are relatively noisy during operation. combustion starts. Combustion causes the tempera-
a. Two cycle. The series of events that take place ture and pressure to rise further.
in a two-cycle diesel engine are: compression, com- (2) Power: As the piston reaches and passes
bustion, expansion, exhaust, scavenging, and air in- TDC, the pressure of the hot gas forces and acceler-
take. Two strokes of the piston during one revolu- ates the piston downward. This turns the crank-
tion of the crankshaft complete the cycle. shaft against the load connected to the shaft. The
(1) Compression. The cycle begins with the pis- fuel/air mixture continues to burn. As the piston
ton in its bottom dead center (BDC) position. The passes eighty percent (80%) to eighty-five percent
exhaust valve is open permitting burned gases to (85%) of the stroke travel towards BDC, it uncovers
escape the cylinder, and the scavenging air port is the exhaust port (or the exhaust valve is opened).
uncovered, permitting new air to sweep into the This allows exhaust gas to escape from the cylinder.
cylinder. With new air in the cylinder, the piston As the piston continues downward, it uncovers the
moves upward. The piston first covers the exhaust scavenging air port, allowing scavenging air (fresh
3-4
TM 5-685/NAVFAC MO-912

air at 3 pounds per square inch (psi) to 6 psi) to


sweep the cylinder, further purging the exhaust gas
and providing a fresh clean charge for the next
-.-
cycle. The piston reaches and passes through BDC.
The compression stroke then begins again.
b. Four-cycle. The series of events taking place in
a four-cycle engine are: inlet stroke, compression
stroke, expansion or power stroke, and exhaust
stroke. Four strokes (two revolutions of the crank-
shaft) are necessary to complete the cycle.
(1) Inlet stroke. As the piston starts downward
from TDC, the inlet (intake) valve opens and allows
the piston to suck a charge of fresh air into the
cylinder. This air may be supplied at a pressure
higher than atmospheric air by a supercharger.
(2) Compression stroke. As the piston nears ~cAv?~Z~~Z~ERIO~
BDC, the air inlet valve closes, sealing the cylinder. EXHAUST BlDW
Energy supplied by the crankshaft from a flywheel,
or power from other cylinders, forces the piston up-
ward toward TDC, rapidly compressing the air and
increasing the temperature and pressure within the
cylinder. A.
(3) Power stroke. As the piston approaches
TDC, an amount of fuel (modulated by the governor)
is injected (sprayed and atomized) into the cylinder
which is ignited by the high temperature, and com- FUEL INJECTOR
VALVE OPENS
bustion starts. Combustion, at a controlled rate,
further increases the temperature and pressure to AIR STARTING
accelerate the piston toward BDC. The expansion of VALVE OPENS7
the hot gases forces the piston down and turns the
crank against the load. Engine efficiency depends
on the fuel charge being completely burned during
the power stroke.
(4) Exhaust stroke. As the piston passes
through BDC at the end of the power stroke, the
exhaust valve opens. The piston, using stored en-
ergy from the flywheel or from the power stroke of
another cylinder, forces the burned gases from the
cylinder through the exhaust port. As the piston
approaches TDC, the exhaust valve is closed and
the air intake valve opens to begin another cycle. COMPRESS10
c. Engine timing. Engine timing is critical. Intake VALVE OPEN
and exhaust valves have to open a n d close to allow O V E R L A P - b AIR S T A R T
2 VALVE CLOSES
the greatest amount of work to be extracted from
combustion. They must also be open long enough to
allow fresh air to flow into and exhaust gas to flow
out of the cylinder. Fuel must be injected at proper
rates during certain periods of time to get smooth Figure 3-5. Timing diagrams
pressure rise and complete combustion. Timing for A) FOR A TWO STROKE CYCLE,
two-stroke cycle and four-stroke cycle engines dif- B) FOR A FOUR STROKE CYCLE.
fers (refer to the timing diagrams in fig 3-5). Dia-
gram A illustrates two forms of the two-stroke cycle The outer portion covers a port control (uniflow)
‘-__ engine. The inner portion covers the typical crank- system. Diagram B illustrates timing for a four-
case scavenging type with uncontrolled fixed ports. stroke cycle engine.

3-5
TM 5-685/NAVFAC MO-912

d. Advantages. Advantages of diesel power for material can seriously damage moving parts. Con-
generating units include the ability: to utilize spe- taminated fuel is a major vehicle by which dirt and
cific liquid or gaseous fuel other than highly volatile water enter the system. Fuel must be filtered before
refined ones (gasoline, benzene, etc.); to meet load use.
by varying the amount of fuel injected; to utilize a e. Starting fuels. Diesel engines used for auxil-
relatively slow design speed; and, to operate with- iary generators usually use distillate fuel for
out external furnaces, boilers or gas generators. quicker starting. These fuels are light oils that are
e. Disadvantages. Major disadvantages include: a similar to kerosene. Various additives are fre-
need to reduce cranking power by use of compres- quently used with fuel such as cetane improvers
sion relief during start and a powerful auxiliary which delay ignition for smoother engine operation,
starting engine or starting motor and battery bank; corrosion inhibitors, and dispersants. Appendix C
high-pressure, close-tolerance fuel injection systems contains information related to fuel and fuel stor-
capable of being finely adjusted and modulated for age.
speed/load control; weight; and, noise. f. Injection systems. Diesel engine manufacturers
usually use one of the following types of mechanical
3-4. Diesel fuel system. fuel injection systems: unit injection, common rail
A typical diesel engine fuel system is shown in fig- injection, or in-line pump and injection nozzle. A
ure 3-6. Information related to cooling, lubrication, limited number of diesel engines currently in use
and starting systems is also shown. Functional re- employ a common rail injection system. Electronic
quirements of a diesel engine fuel system include fuel injection has been developed for use in modern
fuel injection, injection timing, and fuel pressuriza- diesel engines refer to paragraph 3-4b(4). Unit in-
tion. jector, common rail injector, and in-line pump and
a. Fuel injection system. This system measures injection nozzle systems are described in tables 3-1
and meters fuel supplied to each cylinder of the through 3-3. Injection of fuel in any system must
engine. Either inlet metering or outlet metering is start and end quickly. Any delay in beginning injec-
used. In inlet metering, fuel is measured within the tion changes the injection timing and causes hard
injector pump or injector. In outlet metering, fuel is starting and rough operation of the engine. Delay in
measured as it leaves the pumping element. Instan- ending injection is indicated by heavy smoke ex-
taneous rate during injection must deliver fuel to haust and loud, uneven exhaust sounds. The end of
attain correct propagation of the flame front and injection (full shutoff) should be total with no
resulting pressure rise. dribble or secondary injections. Some injection sys-
b. Timing. Fuel injection timing is critical. The tems include a delivery or retraction valve for fuel
duration of fuel injection and the amount of fuel shutoff. In other systems, camshafts have cam lobes
injected vary during starting and partial, full, or designed with a sharp drop to assure rapid fuel
overload conditions, as well as with speed. The best shutoff.
engine start occurs when fuel is injected at (or just (1) Common rail injection. The common rail in-
before) TDC of piston travel because air in the com- jection system is an older system where fuel is sup-
bustion chamber is hottest at that instant. During piied to a common rail or manifold. A high-pressure
engine operation, the injection timing may need to pump maintains a constant pressure in the rail
be advanced to compensate for injection lag. Many from which individual fuel lines connect to the in-
modern injection systems have an automatic injec- jection or spray nozzle at each cylinder. Fuel is
tion timing device that changes timing to match drawn from the supply tank by the low-pressure
changes in engine speed. pump and passed through a filter to the suction side
c. Fuel pressurization. Fuel must be pressurized of the high-pressure pump. The high-pressure pump
to open the injector nozzle because the nozzle (or raises the fuel to the engine manufacturer’s speci-
injector tip) contains a spring-loaded check valve. fied operating pressure. Constant pressure is main-
The injection pressure must be greater than the tained in the system by the high pressure pump and
compression pressure within the compression related relief valve. If pressure is greater than the
chamber or cylinder. Between 1500 psi and 4000 psi relief valve setting, the valve opens and permits
pressure is required for injection and proper fuel some of the fuel to flow back (bypass) into the tank.
atomization. Specific information is provided in the Check valves in the injection nozzle prevent the
engine manufacturer’s literature. Fuel system com- return of fuel oil to the injection system by cylinder
ponents are listed in paragraph 3-4c. compression pressure.
d. Fuel contamination. Fuel injection equipment (2) Unit injection. This system consists of an
_-
is manufactured to precision accuracy and must be integral fuel-injector pump and injector unit. A com-
very carefully handled. A small amount of abrasive plete unit is required for each cylinder. Fuel oil is
3-6
TM 5-685/NAVFAC MO-912

Figure 3-6. Diagram of typical fuel, cooling, lubrication, and starting systems.

3-7
TM 5-685/NAVFAC MO-912

Table 3-l. Unit injector system. of each other. Fuel from the supply tank is passed
Component Purpose through a filter to the injector pump supply pipe.
The injector pump receives the fuel which is then
Gear pump Low pressure pump; delivers fuel from tank to
injected into the cylinders in proper quantity and at
injector: fuel also lubricates the pump.
a prearranged time.
Injector Meters, times, and pressurizes fuel: camshaft-
(3) Electronic Fuel Injection. The electronic
operated by pushrod and rocker arm; one injec-
tor for each cylinder. fuel injection system is an advanced design for mod-
ern diesel engines, intended to produce improved
Filters Protect machined components from dirt and
water in fuel.
starting and operating characteristics. Several sys-
tems have been developed, mainly for smaller and
Governor Controls engine speed. Varies position of the
intermediate-sized engines. Similarities to me-
injector plunger to vary amount of fuel in-
jected. chanical injection systems include the following: a
fuel pump (or pumps), a governor or speed regula-
Table 3-2. Common rail injector system. tor, filters, and fuel injectors. The major difference
between mechanical and electronic systems is the
Component Purpose computer which replaces the mechanical compo-
Low and Low-pressure pump delivers fuel from tank to nents (cams and pushrods) used to control fuel in-
high-pressure pump high-pressure pump; high-pressure pump deliv- jection. The computer processes data inputs (such
ers fuel to injectors at the desired operating
as engine speed and load, desired speed or governor
pressure: fuel lubricates governor and pumps.
setting, engine temperature, and generator load).
Governor Flyweight-type; controls maximum fuel pres- Computer output is precisely timed electrical sig-
sure; prevents engine overfueling; controls en-
gine idle and prevents overspeeding by control-
nals (or pulses) that open or close the fuel injectors
ling fuel supply: contained within main pump for optimum engine performance. Adjustment of in-
housing. jection timing is seldom required after the initial
Throttle Controlled by the operator; regulates fuel flow setup. Refer to the engine manufacturer’s literature
and pressure to injectors. for maintenance of injectors, pumps, and other fuel
Injector Meters, times and pressurizes fuel; camshaft- system components.
operated by pushrod and rocker arm: one injec- g. The main components of the fuel system. Fuel
tor for each cylinder. supply source, transfer pump, day tank, fuel injec-
Filters Protect machined components from dirt and tion pump, fuel injection nozzles, and filters and
water in fuel. strainers. These components are matched by the
engine manufacturer for optimum performance and
Table 33. In-line pumps and injection nozzle system. warranty protection.
(1) The fuel supply source is one or more stor-
age tanks. Each tank must have drain valves for
Injection pump Meters, times, pressurizes and controls fuel removal of bottom water, see paragraph 2-4 for
delivered to the injection nozzles; consists of genera! requirements. Additionally, the fuel system
single pumping element for each cylinder; tit-
ted into a common housing; operated by rocker
should include a day tank and a transfer pump, see
arm or directly from the camshaft. paragraph 2-4d.
(2) The follo wing paragraphs cover the fuel in-
Governor Usually the flyweight-type: may be mounted on
main injection pump housing; controls fuel de-
jection pump, fuel injection nozzles, and filters and
livery: variable-speed or limiting-speed type is strainers.
used. (3) A fuel injection pump accomplishes the
Fuel lines High-pressure type; transports fuel from pump
functions described in paragraph 3-4b(3). Addi-
to injection nozzles. tional details are provided in the following para-
graphs.
Injection nozzle Spring-loaded; hydraulically operated valve that
is inserted in the combustion chamber: one
(a) The fuel injection pump must perform
nozzle for each cylinder. two functions: first, deliver a charge of fuel to the
engine cylinder at the proper time in the engine
Filters Protect machined components from dirt and
water in fuel.
operating cycle, usually when the piston has almost
reached the end of the compression stroke; and sec-
ond, measure the oil charge delivered to the injector
supplied to the cylinders by individual pumps oper- so the amount of fuel is sufficient to develop the
ated from cams located on a camshaft or on an power needed to overcome the resistance at the
auxiliary drive. The pumps operate independently crankshaft.
3-8
TM 5-685/NAVFAC MO-912

(b) The fuel injection pump consists of a bar- quency of cleaning and replacing filter elements.
rel and a reciprocating plunger. The reciprocating Adjust the frequency to meet unusual local operat-
plunger takes a charge of fuel into the barrel and ing conditions. Generally, all metal-edge and wire-
delivers it to the fuel-injecting device at the engine mesh devices are called strainers, and all replace-
cylinder. able absorbent cartridge devices are called filters.
(4) Fuel injection nozzles for mechanical injec- Fuel filters approved for military use consist of re-
tion systems are usually of the spring-loaded, placeable elements mounted in a suitable housing.
needle-valve type. These nozzles can be adjusted to Simplex and duplex type fuel filters are available.
open at the predetermined pressure. Consult the Fuel strainers and filters must not contain pressure
manufacturer’s specifications before adjusting fuel relief or bypass valves. Such valves provide a means
injection valves. The nozzle components are as- for the fuel to bypass the strainer or filter, thereby
sembled carefully at the factory and must never be permitting the fuel-injection equipment to be dam-
intermixed. Most manufacturers use an individual aged by contaminated fuel. Filter capacity is gener-
pump for each cylinder (pump injection system) and ally described in terms of pressure drop between the
provide each cylinder with a spring-loaded spray input and output sides of the filter. However, fuel oil
valve. The spring keeps the needle from lifting until filters must be large enough to take the full flow of
the pump has delivered oil at a pressure greater the fuel oil pumps with a pressure drop across the
than the spring loading. As soon as the pressure filter not to exceed the engine manufacturer’s speci-
lifts the needle, oil starts to spray into the engine fications. Fuel filter elements should be changed
cylinder through an opening in the valve body. whenever the pressure drop across the filter nears
(5) Diesel fu e1 suppliers try to provide clean or reaches a specified value. Refer to manufactur-
fuel. However, contaminants (water, sand, lint, dirt, er’s instructions for information on the replacement
etc.) are frequently found even in the best grades. If of filter elements. Filter capacity at a given pres-
foreign material enters the fuel system, it will clog sure drop is influenced by the viscosity of the fuel.
the nozzles and cause excessive wear of fuel pumps The filter should have ample capacity to handle fuel
and injection valves. demand of the engine at full load. The larger the
(6) Sulphur, frequently found in fuel oil, is very filter, the less frequently it will have to be cleaned
undesirable. When sulfur is burned (during combus- and the better the filtering performance will be.
tion), sulfur dioxide and sulfur trioxide form. Both
substances will combine with water condensates to 3-5. Diesel cooling system.
form sulfuric acid. The maximum amount of sulfur Diesel engines are designed to be either air cooled
acceptable in fuel oil must not exceed one percent. or liquid cooled. Cooling is used to prevent the cyl-
The engine manufacturer’s recommendation should inder walls, the head, the exhaust manifold, and the
be used if acceptable sulfur in fuel oil requirements lube oil from overheating.
are more restrictive. Strainers and filters capable of a. An air-cooled system depends on an engine
removing fine particles are placed in the fuel line driven fan to blow ambient air over the fluted or
between supply tank and engine, or between engine finned surfaces of the cylinder head and through a
transfer pump and injection pump, or sometimes at radiator type oil cooler, and over the exhaust mani-
both places. The basic rule for placement of strain- fold. The exterior surfaces must be kept free of dirt
ers and filters is strainers before pumps, filters af- or corrosion. The oil must be kept free of sludge to
ter pumps. A filter should be placed in the storage secure adequate cooling. Air cooling is seldom used
tank fill line. This prevents accumulation of foreign on engines over 5 HP or on multicylinder engines.
material in the storage tank. Strainers protect the b. The liquid-cooled engine uses a treated coolant
transfer pumps. A strainer should also be placed forced to circulate through passages in and around
ahead of each fuel flow meter. Always locate filters the cylinder, head, exhaust manifold and a lube oil
and strainers where they are easily accessible for heat exchanger. The hot coolant is passed through
cleaning or replacement. Duplex filters should be the tubes of an air-cooled radiator, through the
provided for engines that run continuously so that tubes of an evaporative heat exchanger, or through
filter elements can be cleaned while the engine is a shell and tube heat exchanger. A typical liquid
running without interrupting its fuel supply. Pro- system is shown in figure 3-7.
vide space under the edge of disk filters for a recep- (1) Two basic types of liquid-cooling systems
tacle to receive material drained from the bottom of are attached and remote.
the filter when it is cleaned. If the filter or strainer (a) Attached. All components are mounted at
has an element that can be renewed or cleaned, the engine. It is used with smaller and/or portable
space must be allowed to permit its easy removal. engine generator sets and usually consists of an
Follow the manufacturer’s recommendations on fre- engine-driven pump circulating treated coolant in a
3-9
TM 5-685/NAVFAC MO-912

METAL ADIATOR
EDGE
MAKE UP
WATER+-----

WATER INLET

f FAN MOTOR
1 JACK WATER
1 TEMPERATURE
I REGULATING

f
I I
,
-_ I +- - - - - i_ --I OTHERMOMETER
I
SUMi’ I .-----
; - k-j & SH U T O f f VALVE

Figure 3-7. Diesel Engine Liquid Cooling System.

closed circuit through a radiator (engine-driven fan) (2) The engine and its components are de- -
or a water-cooled heat exchanger. signed to withstand the mechanical and thermal
(b) Remote. Primary coolant in a closed cir- stresses resulting from operating within certain pa-
cuit is piped to a heat exchanger system not rameters. The design also allows for the effects of
mounted with the engine. Pumps and controls may temperature on the strength, resistance to fatigue
also be remote. It is used for larger engines where and wear, the stresses induced by expansion and
size and complexity of heat dissipation systems are contraction, and allowance for wear and corrosion,
significant. It is also used to physically separate the etc.
liquid processing from the electrical generation and (a) Each component subject to heat is de-
control spaces. signed to operate within stated temperature iimits.
c. System description and operation. Successful Unsatisfactory operation, decreased life, damage or
operation of the engine depends upon the removal of failure will result if the engine operates outside of
excess heat from lubricating oil, after cooler, and these limits. Lubricants will lose their necessary
the engine components (cylinders, pistons, and properties, clearances between parts will become
valves) to keep the engine temperature within the too great or too little, and combustion of fuel will not
limits specified by the manufacturer. The kW rating be proper. Fuel, air, exhaust and coolant passages
of the associated electric generator may require may be fouled, melted, or chemically attacked, or
derating when any temperature at the operating misalignment and excessive vibrations may result.
engine exceeds the manufacturer’s limits. Table 3-4 (b) Hot spots, cold spots, general overheating
describes the various elements of the cooling sys- and general overcooling can each cause problems.
tem. Approximately one-third of the energy consumed by
(1) Overheating of the engine reduces the effec- an engine is removed by the cooling system.
tiveness of engine lubricants, accelerates engine (3) An engine used for auxiliary generator ser-
wear, and causes engine breakdown. Cooling pre- vice will be one of proven capability and reliability
vents excessive stresses in or between engine parts when operated within the limits specified by the
caused by unequal temperature within the engine. manufacturer. A particular engine will require -
Also, cooling prevents loss of strength caused by stated rate of coolant flow at certain inlet and outlet
overheating of the engine’s structural metal. temperatures under various rates of fuel energy
3-10
TM 5-685/NAVFAC MO-912
Table 3-4. Typical cooling system components. also decreases heat transfer. It should have good
heat capacity and contain an antifreeze, anti-
corrosion compound, and cleaning agent to keep
Coolant The liquid, usually treated water, used to re-
move excess heat from the engine. May be pri-
coolant passages in good condition. The coolant
mary, secondary. etc. should neither corrode nor attack any metals or
organic materials of the coolant system. It should
Coolant jackets Spaces surrounding block, cylinders, and heads,
or passages through which primary coolant is circulated not be hazardous.
under pressure to cool the engine components. (4) In rare cases, the engine may be cooled us-
Coolant pumps Water or primary (secondary, other) pump to
ing clean water in a once-through system. Cool wa-
circulate coolant (water) through engine pas- ter is pumped through the coolant passages, and the
sages to heat exchangers. hot water leaving the engine is discarded. This has
Thermostat Regulates coolant flow to maintain engine tem- many disadvantages and will not be further dis-
perature between specified limits. cussed.
Fan Provides air movement to cool air-cooled en- (a) Smaller engines may have a single cool-
gine or the radiator of a liquid-cooled engine to ant circuit (loop) through which coolant, leaving the
cool the coolant for recirculation. engine, passes and is returned to the engine.
Shutters Blades used to vary air flow across a radiator (b) Larger engines may require the use of
to regulate rate of heat removal from coolant. additional loops. In these, the engine coolant is in a
Would be closed when coolant is below normal primary loop. It is cooled by the medium circulating
temperature and open when coolant is warm.
May be thermostatically controlled.
in a secondary loop and the secondary coolant may
be cooled by another medium in a tertiary loop. No
Heat exchanger A device to exchange heat from one medium to
cooling medium mixes with another medium in
another. Usually a shell and tube-type ex-
changer. these “non-contact” systems.
(c) An example of a three-loop system is
Coolant tower A structure in which hot coolant is sprayed or
falls through air currents. As coolant evaporates
treated engine coolant in the primary loop passing
heat is given up by the remaining liquid cool- through a heat exchanger cooled by freshwater in a
ant. secondary loop. The “hot” freshwater may be used
Evaporative cooler A device to remove heat from medium by for building heating or may be passed through an-
evaporation of that medium in air (open cir- other heat exchanger cooled by brackish or saltwa-
cuit). May also be by non-contact heat ex- ter in the tertiary circuit on a once-through basis.
changer from one medium to an evaporating
The purpose of this arrangement is to keep the
second. Applicable where ambient temperature
and relative humidity are below certain values. seawater at low temperatures so that salts do not
form scale. Leakage of seawater into the freshwater
Treated coolant Coolant fluid, usually filtered water with addi-
tives to prevent freezing and to inhibit scale circuit is prevented by having the freshwater at
formation and corrosion. Required for primary higher pressure than the seawater. The freshwater
coolant circuit. May not be required for sec- circuit may operate at higher temperature and re-
ondary or other circuits. cover significant usable heat otherwise wasted.
Secondary system Describes the components of a second system Contamination of engine coolant is prevented by
used to extract heat from the primary heat ex- being at a higher pressure than the freshwater. The
changer. Used where waste heat may be used additives used in the engine coolant are a cost. Very
for building heating, etc.
little coolant is lost when the coolant circuit is
Tertiary system Describes components of a possible third sys- sealed. Heat capacity and temperature may be el-
tern to extract heat from a secondary system. evated by using a sealed, pressurized coolant loop.
Closed system Coolant does not come in contact with air or Coolant must be periodically tested to make sure
other fluids. correct amounts of active additives are present.
(d) At the e ngine the coolant cools the lubri-
cating oil, then the lower temperature areas, and
consumption and mechanical energy output. The finally the hotter sections.
coolant must not contain any suspended solids that (e) In the crankcase the oil cools the crank-
could settle and impede heat transfer or coolant shaft assembly. Sprayed or splashed oil cools the
flow. The coolant should be free of entrained or underside of the piston. Oil circulated to the cam-
dissolved air or other gases which could cause cor- shaft, rocker arms, and valve guides picks up heat
rosion and decrease heat transfer. The coolant and drains into the sump. The oil pump forces the
should not contain dissolved salts’ that could pre- hot lube oil through the oil filter and through the oil
cipitate or form an insulating scale coating which cooler to the pressure-oiled points. The oil must not
3-11
TM 5-685/NAVFAC MO-912

become so hot that it loses its lubricating properties (8) It is necessary to control temperatures at
or breaks down. various points of the engine and throughout the
(f) Coolant leaving the oil cooler flows to the cooling systems. This may be done by bypassing
cylinder water jackets, inlet ports and valves, injec- some portion of a coolant stream or by changing the
tors, exhaust ports and valves, intercooler or super- flow rate.
charger, turboblower, exhaust manifold jacket, and (9) Overcooling can cause problems. A warm
finally to the heat exchanger where it is recircu- engine is easier to start and can quickly be brought
lated to the engine. up to speed and loaded. Warm oil provides better
(5) Non-contact heat exchangers are used to initial oil circulation and lubrication which is vital
add or remove heat from one medium to another in cold weather. Heavy fuel oils must be at a tem-
without intermixing. A radiator or fin-fan cooler perature related to the viscosity required by the fuel
uses an airflow to remove and dissipate the heat. In system and injectors. The carburetor and inlet
a heat exchanger, one medium flows through tubes manifold of an SI engine must be warm enough to
and the second medium flows around the tubes. prevent “icing” and to vaporize the fuel/air mixture.
Generally, the medium having a higher tendency to Exhaust gas temperature must be kept above the
foul the exchanger surfaces is inside the tubes to dew point to prevent condensation and corrosion.
allow easier cleaning. The tubes may form part of a An engine running cold will not achieve rated effi-
sealed system. The tube bundle may be in an open ciency. Freezing of the coolant can cause breakage
tank or in a shell. The shell, enclosing the second or interfere with required flow and circulation.
medium, may be part of another sealed system. (10) Chemical control of the various cooling cir-
(6) Cooling towers and evaporative coolers are cuits is important. Strainers and filters remove sus-
both used to dissipate waste heat to the atmo- pended solids. Additives prevent corrosion, mineral
sphere. They may be used where ambient air is scale buildup, organic growth and organic fouling.
sufficiently cool and dry (low relative humidity) to Periodic sampling and analysis will indicate actual
absorb water vapor. As water is sprayed or divided concentrations of undesired materials dissolved in
into many small streams, some will evaporate to the the coolants. Comparison of test results will provide
passing air. The heat required to evaporate the wa- guidance for altering the treatment program. Some
ter is approximately 1050 Btu/lb and is extracted untreated freshwater and brackish or seawater pro- -
from the unevaporated water. Additionally, the air mote growth of barnacles, etc., that prevent proper
which is now moist may be warmed by the water (if flow and pressures. Visual inspection is recom-
the water was originally warmer than the air), thus mended when increasing pressure drops indicate
removing more heat from the water. In a cooling fouling. Physical and/or chemical cleaning may be
tower, the fluid to be cooled is exposed to the air. periodically required. Safety precautions must be
Approximately eighty percent (80%) of the heat re- followed when using most cleaning compounds.
moved is due to evaporation. The water leaving the
tower or cooler is usually five degrees Fahrenheit 3-6. Lubrication system.
(5°F) higher than the entering air. Towers may use The bearings and moving parts of all diesel engines
atmospheric draft or fans to move the air. Makeup are lubricated by a full-pressure system, see figure
water is required to replace that lost by evaporation 3-6. Lubricating oil requirements and specifications
or entrained spray. Water treatment and blowdown are covered in appendix C.
are necessary because salts are concentrated by the a. System elements. Smaller engines are usually
evaporation. Dust, etc., in the air will contaminate self contained. The smaller engine system will have
the exposed water. In an evaporative cooler, the many of the system elements used in the larger
coolant passes through tubes. The tube bundle lies engines, as follows:
inside a cooling tower. The cooling tower spray and (1) Lube oil h aving proper properties for the
air movement cool the tubes but do not mix with the specific engine design.
coolant. (2) Lube oil ant k or sump to hold the volume of
(7) Flow rates of fluid, fan speed, flow bypass, oil required.
etc. are controlled to maintain proper conditions. A (3) Oil feed pump(s) driven from the engine to
properly monitored, real-time, automatic control circulate clean cool pressurized oil (5 to 75 psi).
system is preferred over a manually-operated sys- (4) Oil feed piping, valves and controls to de-
tem, especially where some parts of the engine aux- liver oil to various lube points of the engine.
iliaries are remote or not in direct observation of (5) Engine internal oil passageways in the
operating personnel. Automatic data logging is of crankshaft-piston assembly and in block and head.
real value for determining trends and for trouble- (6) Hot oil sump to collect oil draining from all
shooting. the lubricated engine components.
3-12
TM 5-685/NAVFAC MO-912

(7) Hot oil sump pump (return oil pump, filter ing are provided for that changeover. The auxiliary
pump) to force hot used oil through filtering and/or pump is generally used long enough to return the oil
purifier and cooler. from the critical points and to check the pressure,
(8) Oil filter to remove suspended solids, dirt temperature and flow sensors, indicators, and con-
and sludge. trols to enable engine cranking. Pumps are usually
(9) Sampling valves for taking samples of oil gear-type with pressure regulation. The engine-
and filter solids periodically for testing and analy- driven pump speed is directly related to engine
sis. speed so that oil flow increases as speed increases.
(10) Transfer systems for adding new oil and b. Types and operation. Large diesel engines use
removing used oil from the engine lube system. a lubrication system different from that of smaller
(a) Lube oil must have certain properties for diesel engines. Because large engines require a
specific application. It must flow properly at the large quantity of oil, a separate sump tank is in-
minimum temperatures (pour point), have proper stalled to receive oil from the crankcase. The lubri-
viscosity (resistance to shear) between moving parts cating oil pump draws oil from the sump tank
and retain desired viscosity over the range of tem- through the strainers. Oil is then discharged, under
peratures in the engine (viscosity index). The oil pressure, into the oil cooler.
must resist oxidation (stability) that forms gum and (1) The oil then goes to a header, located on the
sludge and the associated catalytic effects of engine engine, with branches leading to the various parts
metals present (especially copper and lithium) in of the system. Leads extend from the header to each
the detergent additives. It must allow sludge par- main bearing. After the oil has been supplied to the
ticles to disperse and not clump or deposit through- main bearings, it passes through a drilled passage
out the engine. It will contain inhibitors to prevent in the crank web. The oil then passes through a hole
oxidation, a dispersing agent and a detergent to in the crank bearing journal to the connecting rod
keep surfaces clean. bearing and up through a drilled hole in the con-
(b) The physical specifications for crankcase necting rod to the wrist pin. At the wrist pin, the oil,
lube oil are not positive indications of suitability. in some engines, passes through a spray nozzle for
The experience of the engine manufacturer is guid- splash lubrication against the underside of the pis-
ance for recommended oils. The user must choose. ton for cooling. The oil then drains down to the
(c) Periodic sampling, analysis and evalua- engine crankcase and returns to the pump. Other
tion of results is important. An out-of-spec problem branches from the header rnay supply oil to the gear
will be evident. It is also necessary to look for trends trains, camshafts and bearings, rocker arms and
that warn of a condition that may become a major push rods, cylinder walls, turbo-chargers, blowers,
problem. An abnormal rise in the wear metals indi- and in some engines, to an oil-cooling system for
cates abnormal wear. Increasing sulphur content pistons. Engines may vary in many details, but the
and acidity indicates that the lube oil is being con- principles are the same in all.
taminated by high-sulfur fuel, oil blowby, etc. (2) Lubricati ng systems of small engines usu-
(d) The lube oil tank must be sufficiently ally are self-contained. The crankcase or a separate
large to hold the oil required for the engine. It must oil pan underneath the engine contains all the oil
be kept clean and closed to prevent contamination used in the system. Figure 3-8 is a cross section of a
of the oil. A vent with flame arrestor should exist. diesel engine, showing lube oil flow.
The tank is the reservoir that feeds the oil pumps. c. Process. The diesel engine lubrication system
The pump suction line should be above any possible must circulate, filter, and cool large quantities of
sludge or water at the bottom. The tank and all the lubricating oil. Figure 3-9 shows a schematic ar-
components of the lube system should be of materi- rangement of the main components of a diesel lubri-
als that will not contaminate the oil. cation system. The arrows show the flow of lube oil
(e) Lube oil pumps circulate the oil at pres- through the system.
sure (5 to 75 psi depending on engine design and d. Oil storage. All high-speed engines and most
system pressure losses when cold) through the oil medium and low-speed engines use the crankcase
feedline to the engine lube oil header. An auxiliary base or a sump integral with the crank-case for
electrically-driven pump is used prior to starting a storing lubricating oil. Several engines operate with
cold engine to provide warm oil to all points, espe- a so-called dry crankcase to avoid crankcase oil fog
cially to heavily loaded main, crank, and wrist pin that may cause excessive cylinder lubrication. Such
bearings, to make sure the lubricating film is engines must have an outside sump tank placed so
formed at first movement. This auxiliary pump may that oil from the crankcase will drain into it. One
also serve as an automatic standby should a normal design has an elevated, closed pressure tank to
engine-driven pump system fail. Controls and valv- which oil is pumped from the crankcase. Open,
3-13
TM 5-685/NAVFAC MO-912

CYLINOER HEA9 II

COMBUSTION CHAMBER <

PLATFORM < COVER FOR ACCESS


TO SCAVENGING AIR VALVES

CYLINOER LINERS ’
WATER COOLED COOLING OIL AREA
OF PISTON HEAD

EXHAUST HEADER
SCAVENGING
AIR HEADER

‘Y FRAMES d SCAVENGING
AIR PASSAGE
REMOVABLE COVERS

CRANKPIN AND INJECTION PUMP


Jj
MAIN BEARING SHELL2 \_

CRANKSHAFT CONNECTING ROD

TIE RCO . BEDPLATE

Figure 3-8. Cross Section of a diesel engine showing chamber for lubricating oil collection.

elevated tanks and two sets of pumps are also used. end of the engine, either inside or outside the crank-
Sump capacities vary with horsepower. case, and driven by the crankshaft. In other en-
e. Lube oil pumps. In most engines, an engine- gines, the pump is mounted on the end and driven
driven rotary pump supplies pressure needed to cir- from the camshaft gears. Larger diesel engines fre-
culate oil through the engine lubrication system. Oil quently have an auxiliary, motor-driven pump that
pressure varies from 5 to 60 pounds, depending on circulates oil to the bearings before the engine is
diesel engine type. The pressure depends on the started. As soon as the engine is up to speed, the
amount of clearance in the bearings and the capac- pump shuts down. The auxiliary pump also serves
ity of the pump. as an emergency lubricating oil pump in case the
f. Types of pumps. Lubricating oil pumps are usu- engine-driven pump fails. Finally, the auxiliary
ally built into and driven by the engine. In high- pump circulates the oil for a time after the engine is
speed engines, the oil pump is usually placed in the shut down to cool bearings, journals, and pistons.
crankcase sump and driven from the camshaft by a When this method is used, a check valve in the
vertical shaft. In larger engines, the pump can be discharge line of the auxiliary pump is necessary to
chain-driven by the crankshaft, or mounted at the prevent the oil from flowing back when the engine
3-14
TM 5-685/NAVFAC MO-912

LUBE OIL IN-\ 7

WATER INLET

LUBE OIL
FILTER

ERATURE
,_DRAlN LATING

_ I
WATER OUT
I

LUBE OIL OUT

SUMP

Figure 3-9. Diesel engine lubrication system.

comes up to speed and the auxiliary pump is shut sible. Also, the coils may be placed in the side jack-
down. The check valve also prevents loss of oil in ets. Some designs have the coil tubes in the cooling
case of leakage. water header, while in others, water entering the
g. Heating. Circulating lubricating oil absorbs cooler is bypassed around the jacket system.
heat from the engine. Frictional heat is absorbed i. Oil filters. Proper installation and maintenance
from the bearings. The oil film on the cylinder walls of oil filters and mechanical operation of the engine
absorbs heat from the combustion space before this are equally important for treatment of oil. Preven-
oil film drains into the crankcase. Heat must be tion of contamination and removal of contaminants
dissipated by a cooler if the temperature is to be should be coordinated. Because high-detergent oils
kept below 230” Fahrenheit. At higher tempera- are used in engines, the purification system should
tures, oil oxidizes and sludge forms. An oil cooler is not remove the additive. Cellulose filter cartridges
necessary when heat dissipated from the oil (by do not remove the additive, but a fuller’s earth filter
conduction through the walls of the sump and by does. In large engine installations, a centrifuge may
contact with water-cooled surfaces in the engine) is be used with filter purifiers, or large continuous oil
insufficient to keep the temperature below manu- purifiers may be used in lieu of the centrifuge. Cen-
facturer’s recommendations. A cooler is particularly trifuging does not remove acids because acidic com-
necessary for engines having oil-cooled pistons. pounds have approximately the same specific grav-
h. Coolers. The oil cooler should be placed in the ity as oil. Batch settling effectively removes organic
oil circuit after the lubricating oil filter. The filter acids from oil, improving its neutralization number.
then handles hot oil of lower viscosity than if it When purifiers are used, they should be used in
received cooled oil. The filter performance is better addition to, not in place of, lube oil filters.
and the pressure drop through it is less with this
arrangement. Coolers are usually mounted on the 3-7. Starting system.
side of the engine or on the floor alongside of the The starting system for diesel engines described in
engine base. Cooling water passes through the this manual must perform as follows for automatic
cooler before entering the engine jackets. Excep- start-up when primary electric power fails: com-
tions, such as placing the oil-cooling coils in the press the air in the combustion chambers and de-
water jackets at one end of the engine, are permis- liver fuel for combustion. To do this, the starting
3-15
T M 5-685/NAVFAC MO-912

system must rotate (crank) the engine at a speed (2) Air starting. Some larger engines may use
sufficient to raise the cylinder air charge to the fuel an air starting system. Compressed air at a pres-
igniting temperature. See figure 3-6. sure of 250 or 300 psi is delivered to the working
a. Types. Two types of starting systems are avail- cylinder’s combustion chambers during the power
able for the required automatic start-up capability: stroke. This action results in positive and fast rota-
electric starting and air starting. tion (cranking). Depending on the manufacturer’s
(1) Electric starting. Most small diesel engines design, compressed air can be delivered to all or
use an electric starting system. This type of system selected cylinders. This type of system requires an
is generally similar to a starter for an automotive air compressor and receivers or air bottles for stor-
gasoline engine. Smaller diesel engines use a l2- age of compressed air.
volt battery-powered system for cranking. Starter (3) Air starter motor. Pneumatic air starter mo-
and battery systems of 24, 32, and 48 volts are often tors are highly reliable. Air starter motors develop
used for larger engines. A typical system consists of enough torque to spin the engine at twice the crank-
storage batteries (as required for voltage output) ing speed in half the time required by electric
connected in series, a battery charging system, and starter motors. Compressed air at a pressure of 110
the necessary grounding and connecting cables. See to 250 psi is stored in storage tanks, regulated to
figure 3-10. 110 psi and piped to the air motor. A check valve

-
BATTERY CONNECTING C:ABLE

CABLE TO

CABLE TO GROUND

Figure 3-10. Battery for engine starting system.

3-16
TM 5-685/NAVFAC MO-912

installed between the compressor and the storage


tanks will prevent depletion of compressed air
should the plant system fail. Air starter motors are
suitable on diesel engine driven generators ranging
from 85 kW up to the largest diesel engine genera- 106
tor.

3-8. Governor/speed control.


A diesel engine used in an auxiliary generator must
have a governor to regulate and control engine
speed. Since an automatic governor functions only
with a change in speed, constant engine speed may
not be totally possible and “hunting” can occur due
to over-correction. The governor’s sensitivity is de-
termined by the minimum change in speed of the
prime mover which will cause a change in governor
setting; its speed regulation is the difference in gen-
erator speeds at full-load and no-load divided by the
arithmetical mean of the two speeds. Refer to the
96
glossary for descriptions of governor characteristics.
a. Usually, this ratio is stated as a percentage,
with synchronous speed considered rather than
mean speed. For example, a generator with a syn-
chronous speed of 1,200 rpm, operated at 1,190 rpm
when fully loaded and 1,220 rpm with no load, has
2.5 percent speed regulation. 92
b. The governor must be capable of speed adjust- 0 20 40 60 80 IOC
PER CENT, LOAD
ment so the proper governed speed can be selected.
In most governors, this adjustment is made by SPEED VS LOAD-MECHANICAL GOVERNOR
changing the tension of the main governor spring.
A 6% DROOP-RATED SPEED AT 00% LOAD
The governor should also be adjustable for speed 8 6% DROOP- RATED SPEED AT 0% L O A D
regulation so the droop of the speed-load curve can C 80 6 % DROOP - INTERMEDIATE SETTINGS
be altered as required to suit operating conditions. E 4% DROOP-RATED SPEED AT 50% LOAD
Determine the curve by observing the generator
speed or frequency at various loads and plotting Figure 3-11. Chart of speed droop characteristics.
them as abscissa against the loads (from no-load to
full-load) as ordinates. The curve droops at the full-
the speed. Speed droop is usually adjusted by
load end (hence, the expression “speed droop” of the
lengthening or shortening the governor operating
governor).
levers, changing the ratio between governor move-
c. An example of speed droop characteristics is
ment and throttle or gate movement.
shown in figure 3-11. The characteristics are for a
mechanical governor but the same principles can be e. Alternating Current (AC) Generators. Gover-
used for other engine/governor applications. The nors of prime movers driving AC generators which
chart is based on a six percent speed droop governor operate in parallel with other generators must have
on an engine running at rated speed at no load. enough speed regulation or speed droop to prevent
When full load is applied, engine speed drops to 94 surging of the load from one generator to another.
percent (94%) of rated value (line B). The engine Ordinarily, three to five percent speed regulation is
can be brought to rated speed at full load by reset- adequate. Some governors have antisurging devices
ting the governor (line A). However, with the load to damp out the surges. Speed regulation should be
removed, engine speed would increase beyond its increased if the surges continue. Speed regulation of
rated limit. Intermediate speed settings are shown governors controlling AC generators affects the fre-
by lines C and D. Line E shows speed droop at 50 quency and the load division between generators
percent (50%) load. but has almost no effect upon voltage.
d. Speed droop can be determined quickly by f. Direct C urrent (DC) Generators. Regulation of
loading the generator to full-load, observing the DC generators affects voltage regulation and the
speed, unloading the generator, and again observing division of load between generators. In general, the
3-17
TM 5-685/NAVFAC MO-912

speed regulation of generators operated in parallel and automatic equipment can be applied to the hy-
should be the same for each machine. Speed regula- draulic governor.
tion for generators operating individually should be (a) The hydraulic governor requires pressur-
as favorable as possible without causing generator ized oil for operation. This oil can come from the
surge resulting from sudden load changes. Ordi- engine or from a separate sump in the governor. Oil
narily, 2.5 percent speed regulation is satisfactory is admitted to an auxiliary oil pump in the governor.
Voltage regulation of DC generators may be accom- The auxiliary pump furnishes necessary pressure to
plished through adjustment of the speed droop of actuate the governor mechanism. In the governor
the governor. shown, the fuel to the engine is decreased by the
g. Types of governors. Usually four types of gov- action of the fuel-rod spring (10) on the fuel rod ( 12)
ernors are used; mechanical, hydraulic, pneumatic, and increased by the opposing action of the hydrau-
and electronic. When speed regulation must be lic serve piston (14), the admission of oil to which is
more precise, such as Defense Communications controlled by a pilot valve (4). The pilot valve is
Agency sites where no more than 0.8 percent varia- controlled by flyweights of the governor (5) which
tion is permitted, an electronic (isochronous) gover- are driven by the governor shaft through gearing to
nor is used. the engine. The centrifugal force of the flyweights in
(1) The mechanical governor used in small air- rotation is opposed by the speeder spring (6), the
cooled engines may be part of the fly-wheel. The compression of which determines the speed at
governor in multicylinder engines is usually a sepa- which the governor will control the engine. The
rate assembly driven by gear or belt from a cam- speeder-spring compression is adjusted through the
shaft or crankshaft. A typical mechanical governor,
rotation of the speed-adjusting shaft (8) which
shown in figure 3-12, operates as follows: the gov-
raises or depresses the spring fork (7) through its
ernor drive gear (2) drives the governor shaft (10)
linkage lever.
and the governor weights (4). Centrifugal force
(b) The droop of the speed-load characteristic
moves the weights away from the shaft which push
the operating-fork riser (6) against the operating is adjusted by changing the effective length of the
fork (ll), rotating the operating-fork shaft (7) and floating lever (11). This is accomplished by moving
moving the governor arm (9). In the external view, the droop-adjusting bracket forward or backward in
the governor spring (A) is connected to the governor the slot of the floating lever. The effective length of
arm and opposes movement of the governor weights the lever should be shortened to decrease the speed
away from the shaft. Adjusting screw (c) adjusts the droop and lengthened to increase the speed droop.
tension of the governor spring, establishing the (3) The pneumatic governor (air-vane type) is
speed at which the prime mover operates. The used in certain small generator plants (see fig
greater the governor-spring tension, the lower the 3-14). The engine flywheel includes an integral fan
governed speed. The auxiliary adjusting screw (D) which forces air outward from the drive shaft. The
adjusts the droop of the governor. Turning this amount of air flowing from the engine depends on
screw in closer to the arm decreases the droop of the engine speed. A movable air vane is placed in the air
governor; this screw should be turned in as far as stream. The air vane (blade) acts as a governor
possible without allowing the engine to surge. Aux- since the air pressure depends upon engine speed.
iliary adjusting screw (B) is turned in to damp out The air pressure on the vane is opposed by a gover-
surging of the engine at light-load or no-load; it nor spring and these forces operate through linkage
should not be turned in so far that it increases the to control the throttle of the engine.
speed of the generator at no-load. (4) Electronic (isochronous) speed control is the
(2) The hydraulic governor (see fig 3-13) is maintenance of constant engine speed independent
used on large prime movers as well as diesel en- of the load being carried (zero droop). An isochron-
gines as small as 100 hp. The governor usually ous governor will maintain, or can be adjusted to
includes: a speed-responsive device, usually fly- maintain, constant engine speed (within 0.2 percent
weights; a valve mechanism; a regulating cylinder variation). This type of governor can be a combina-
and piston; and a pressure pump and relief valve. tion of a conventional hydraulic governor and an
The assembly is adjustable for various ranges of electronic load-sensing system, or an all-electric
speed and sensitivity. The hydraulic principle pro- system.
vides greater power than could be obtained from a (a) Speed control by the hydraulic governor,
mechanical type. Since the flyweights only control see paragraph 3-8d(2), depends on variation in cen-
an easily moved pilot valve (which in turn controls trifugal force created by flyweights (centrifugal
the hydraulic action), the governor can be made to forces are not used in electric types). This force
operate accurately and smoothly. Remote control operates a piston-type pilot valve which controls the
3-18
TM 5-685/NAVFAC MO-912

01 BEARING

\
011 OPERATING FORK

012 BUMPER SPRING -

n
(13) BUMPER SPRING SCREW L \
w
COCK NUT
- E X T E R N A L VIEW

ADJUSTING
0 14 BUMPER SPRING SCREW

SCREW
I

DRIVE
GEAR

ADJUSTABLE I
SCREW
GOVERNOR
SPRING

Figure 3-12. Mechanical Governor.

3-19
TM 5=685/NAVFAC MO-912

flow of high-pressure oil to a servomotor, thereby


operating fuel controls.
(b) The isochronous system uses electronic
sensing and amplifying devices that actuate a type
of servomotor throttle control. The system is used
with power generation where precise frequency con-
trol is required. An isochronous system may be sen-
sitive to frequency changes (engine speed) or to both
frequency and load. When responsive to load
changes, the system corrects fuel settings before
load changes can appreciably modify engine speed
or frequency.
3-9. Air intake system.
Approximately 15 pounds of air is required to burn
one pound of fuel. Accordingly, the air requirement
for a 2000 horsepower engine is about 3600 cubic
feet per minute. The same horsepower-to-air rela-
tionship applies to engines for other power ratings.
FROM ENGINE Intake air carries dust particles, water vapor and
other foreign material. Since these materials can
damage moving parts within the engine, filtration
Figure 3-13. Hydraulic Governor. of the intake air is necessary. A 2000 horsepower
1) PLUNGER, 2) GEAR PUMP DRIVE, 3) GEAR PUMP engine, breathing air containing three parts per
IDLER, 4) PLUNGER PILOT VALVE, 5) FLYWEIGHT,
million dust contamination, would take in 25
6) SPEEDER SPRING, 7) SPRING FORK,
8) SPEED-ADJUSTING SHAFT, 9) SPEED-ADJUSTING pounds of foreign material in 1000 operating hours.
LEVER, 10) SPRING, 11) FLOATING LEVER, An air intake system must collect, filter, and dis-
12) FUEL ROD, 13) TERMINAL LEVER, tribute the required air to the engine cylinders. This
14) SERVO PISTON must be accomplished with a minimum expenditure
of energy (pressure drop). The objective of air filtra-
tion is the reduction of engine component wear. Sev-
eral types of air filters or air cleaners are used. The
pleated-paper type are strainers, porous enough to
THROTTLE ADJUSTING SCREW pass air but able to remove solid particles larger
than 0.002 of an inch. Larger engines use an oil-
GOVERNOR BLADE
bath air cleaner (see fig 3-15). In oil-bath cleaners
air is drawn through an oil bath. Solid particles are
trapped and settle in the unit’s bottom pan.
a. Supercharging. Supercharging increases the
amount of air taken into a working cylinder. This
provides the injected fuel oil with more oxygen to
enable combustion of a larger charge of air/fuel mix-
ture. Power output of a certain size engine is
thereby increased, enabling use of smaller engines
where space prohibits larger engines.
(1) Advantages. The power output of a natu-
rally aspirated engine is limited by the normal pres-
sure and oxygen content of the atmosphere. When
NEEDLE VALV supercharging is used, the intake valve (port) closes
with the cylinder under the initial pressure. Super-
charging is particularly effective at higher alti-
ADJUSTING
tudes. The supercharged engine can develop greater
horsepower than the standard naturally-aspirated
unit. The fuel consumption of a supercharged unit
will not exceed that of comparable horsepower sizes
Figure 3-14. Carburetor and pneumatic governor. of naturally-aspirated units.
3-20
TM 5-685/NAVFAC MO-912

but the coolant should be allowed to circulate


through the supercharger.
(4) Operating instructions. Manufacturer’s in-
structions must be followed to ensure proper opera-
tion of superchargers. Filtered air only should enter
the air inlet, because foreign matter can cause rotor
imbalance and damaging vibration. The manufac-
turer’s recommendations for lubrication must be fol-
lowed. Proper lubrication is necessary because the
unit operates at high speed and at high tempera-
ture. Not more than 15 seconds should elapse be-
tween the start of rotation and an oil pressure indi-
cation of 12 to 71 psi. Coolant circulation through
the turbocharger should be regulated so the tem-
perature rise does not exceed 30” Fahrenheit at full
engine load. A rise in excess of 30” Fahrenheit indi-
cates faulty circulation. Coolant should be allowed
to circulate through the turbocharger for about 5
minutes after the engine is shutdown.
b. Aspiration. The term “naturally-aspirated” is
applied to engines that are not supercharged. A four
stroke cycle engine performs its own air pumping
action with the piston intake stroke. When it is
supercharged, a four-stroke engine with a blower or
turbocharger provides pressure in the intake mani-
fold greater than atmospheric. The increased pres-
Figure 3-15. Oil bath air cleaner:
sure in the intake manifold is referred to as “boost”.
Two stroke cycle engines require an air supply un-
(2) Methods. The most successful method of su-
der pressure to provide scavenging air.
percharging is the use of a turbocharger driven by
exhaust gas (see fig 3-16). The heat and energy 3-10. Exhaust system.
pulsations in the exhaust gas, which are usually Components. The exhaust system consists of the
lost in the exhaust silencer, are used to drive a engine exhaust manifold and includes piping, ex-
single-stage centrifugal turbine. The exhaust gas pansion joints, silencers, and exhaust pipe. Also the
turbine is coupled to a centrifugal compressor that system may include exhaust waste heat recovery
compresses the air to a pressure of four or five equipment. The purpose of the system is to remove
psi. The engine’s pressurized air is then delivered to exhaust gas from engine cylinders to the atmo-
the individual cylinders through the intake mani- sphere. Parts of the system are shown in figure 3-6.
fold. (a) Leak-free. Exhaust systems must be leak free
(3) Disadvantages. Although the supercharged to protect personnel from asphyxiation, and equip-
engine has many advantages over nonsupercharged ment from fire and explosion. Exhaust from gaso-
engines, its disadvantages are not insignificant. The line engines can contain dangerous carbon monox-
turbocharger is another piece of equipment to main- ide. Diesel engine exhaust includes objectionable
tain and operate. It operates at varying speeds de- smoke and odors. On supercharged engines, leaks
pending on engine load, barometric pressure, inlet ahead of the turbine cause a loss of power.
air temperature, exhaust temperature, smoke con- (b) Piping. Exhaust piping must be the correct
tent of the exhaust, or accumulations of dust and size to minimize exhaust back pressure. Connec-
dirt on the impeller and diffuser. It may operate at tions between exhaust manifold and piping should
very high speed (up to 120,000 rpm) with a full load have an expansion joint and the exhaust pipes
on the engine and thus be subjected to all the should slope away from the engine. Also the exhaust
troubles of high-speed equipment. With proper pipes should have suitable devices to prevent entry
maintenance, however, the turbocharger can be op- of rainwater. The length of tail pipes from silencer
erated very successfully. If the turbocharger fails, to atmosphere should be kept to a minimum.
the engine can usually be operated at reduced load (c) Silencers. Silencers are used to reduce or
as a nonsupercharged engine. The turbocharger can muffle engine exhaust noise. Silencing engine ex-
be partially dissembled and the opening blocked off, haust sounds consists of trapping and breaking up
3-21
TURB’ IMPELLER

GAS INLET

_-

ENGINE
CYLINDER
EXHAUST GAS
DISCHARGE

ENGINE EXHAUST GAS FLOW AMBIENT AIR


!=) COMPRESSED AIR FLOW JNLET

Figure 3-16. Diagram of turbocharger operation.

the pressure waves. Usually, a cylindrical unit with 2744 is provided at the back of this publication. A
baffles, expansion chambers, and sound absorption completed example of DD Form 2744 is located in
materials is used. appendix F, figure F-l. It is authorized for electronic
generation.
3-11. Service practices. (1) Record keeping. Engine log sheets are an
a. Maintenance program. Service practices for important part of record keeping. The sheets must
diesel engines consist of a complete maintenance be developed to suit individual applications (i.e.,
program that is built around records and observa- auxiliary use) and related instrumentation. Accu-
tions. The maintenance program includes appropri- rate records are essential to good operations. Notes
ate analysis of these records. DD Form 2744 should be made of all events that are or appear to be
(Emergency/Auxiliary Generator Operation Log) outside of normal range. Detailed reports should be
should be used to record inspection testing of logged. Worn or failed parts should be tagged and
emergency/auxiliary generators. A copy of DD Form protectively stored for possible future reference and
3-22
TM 5-685/NAVFAC MO-912

analysis of failure. This is especially important Table 3-5. Diesel engines troubleshooting-Continued
when specific failures become repetitive over a pe- EXCESSIVE SMOKING AT IDLE
riod of time which may be years. Cause Remedy
(2) Log sheet data. Log sheets should include
Clogged injector. Clean all injectors, refer to appendix G. Refer
engine starts and stops, fuel and lubrication oil con- Leaking head gasket to manufacturer’s instruction and correct as
sumption, and a cumulative record of the following: or blowby. Engine due required. Schedule the overhaul and correct as
(a) Hours since last oil change. for overhaul. Incorrect required. Perform timing procedures. refer to
timing. appendix G.
(b) Hours since last overhaul.
(c) Total hours on engine. EXCESSIVE SMOKING UNDER LOAD
(d) Selected temperatures and pressures. The same causes for The same remedies for “idle” apply.
b. Troubleshooting. Perform troubleshooting pro- “idle” apply.
cedures when abnormal operation of the equipment Air intake restricted. Check air intake and correct as required.
is observed. Maintenance personnel should then re-
High exhaust back Check exhaust system and turbocharger; correct
fer to log sheets for interpretation and comparison pressure. as required.
of performance data. Comparisons of operation
Poor quality fuel. Replenish fuel supply with fresh, proper quality
should be made under similar conditions of load and
fuel.
ambient temperature. The general scheme for
troubleshooting is outlined in the following para- Engine overloaded. Reduce load to proper ievel.

graphs. LOW POWER OR LOSS OF POWER


(1) Industrial practices. Use recognized indus- Air intake restricted. Check air intake and correct as required.
trial practices as the general guide for engine ser-
Poor quality fuel. Replenish fuel supply with fresh, proper quality
vicing. Service information is provided in the manu-
fuel.
facturer’s literature and appendixes B through G.
(2) Reference Literature. The engine user must Clogged injector. Clean all injectors, refer to appendix G.

refer to manufacturer’s literature for specific infor- Faulty throttle linkage Check linkage and governor refer to manufac-
mation on individual units. For example, refer to or governor setting too turer’s instructions and correct as required.
low.
table 3-5 for troubleshooting an engine that has
developed a problem. Clogged filters and Clean filters and screens.
screens.
Table 3-5. Diesel engines troubleshooting. Engine overloaded. Reduce load to proper level.

HARD STARTING OR FAILS TO START Engine due for over- Schedule the overhaul and correct as required.
Cause Remedy haul.

Air intake restricted. Check intake and correct as required. Incorrect timing. En- Perform timing procedure, refer to appendix G.
gine requires tune-up. Perform tune-up procedure, refer to appendix
Fuel shut-off closed, Make sure shut-off is open and supply is at G.
low supply of fuel. proper level.
DOES NOT REACH GOVERNED SPEED
Poor quality fuel. Replenish fuel supply with fresh, proper quality
fuel. The same causes for The same remedies for “low power”, apply.
“low power”, apply.
Clogged injector. Clean all injectors, refer to appendix G.
EXCESSIVE FUEL CONSUMPTION
Injector inlet or drain Check all connections and correct as required.
connection loose. En- Schedule the overhaul and correct as required. Air intake restricted. Check air intake and correct as required.
gine due for overhaul.
High exhaust back Check exhaust system and turbocharger; correct
Incorrect timing. Perform timing procedure, refer to appendix G. pressure. as required.

ENGINE MISSES DURING OPERATION Poor quality fuel. Replenish fuel supply with fresh. proper quality
fuel.
Air leaks in fuel suc- Check fuel suction lines and correct as re-
tion lines. quired. Faulty injector. Clean all injectors, refer to appendix G.

Restricted fuel lines. Check fuel lines and correct as required. Engine overloaded. Reduce load to proper level.

Leakage at engine Refer to manufacturer’s instructions and correct Engine due for over- Schedule the overhaul and correct as required.
valves. as required. haul.

Incorrect timing. Perform timing procedure, refer to Appendix G. Incorrect timing. Perform timing procedure, refer to appendix G.

EXCESSIVE SMOKING AT IDLE ENGINE QUITS

Restricted fuel lines. Check fuel lines and correct as required. Air intake restricted. Check air intake and correct as required.

3-23
TM 5-685/NAVFAC MO-912

Table 3-5. Diesel engines troubleshooting---Continued Table 3-5. Diesel engines troubleshooting-Continued

ENGINE QUITS ENGINE RUNNING TOO HOT


Cause Remedy Cause Remedy

High exhaust back Check exhaust system and correct as required. Low coolant level. Air Refer to appendix D.
pressure turbocharger. in system.

Fuel shut-off closed, Make sure shut-off is open and supply is at ENGINE KNOCKS
low supply of fuel. proper level.
Poor quality fuel. Replenish fuel supply with fresh, proper quality
Poor quality fuel. Replenish fuel supply with fresh, proper quality fuel.
fuel.
Air leaks in fuel suc- Check fuel suction lines and correct as re-
Faulty injector. Clean all injectors, refer to appendix G. tion lines. quired.
ENGINE SURGES AT GOVERNED SPEED Engine overloaded. Reduce load to proper level.
Air leaks in fuel suc- Check fuel suction lines and correct as re- Engine running too Repeat the procedures for “too hot”, above.
tion lines. quired. hot.
Faulty injector. Clean all injectors, refer to appendix G. Faulty vibration Correct as required, refer to manufacturer’s
damper or flywheel. instructions.
Leaks in oil system. Check for oil leaks, check oil lines, check
crankcase drain plug and gasket; correct as re- Engine due for over- Schedule the overhaul and correct as required.
quired. haul.
Engine due for over- Schedule the overhaul and correct as required.
haul. Piston rings or cylinder liners may be worn.
3-12. Operational trends and engine over-
SLUDGE IN CRANKCASE haul.
Fouled lubricating oil Check strainers and filters, remove and service a. Trending data. Usually, a graphic presentation
strainer or filter. as required, reinstall on engine with new gas- of data simplifies detection of a trend toward dete-
kets. riorating engine performance. Samples of graphic
Faulty thermostat. Check coolant thermostats, engine may be too aids are shown in figures 3-17 and 3-18. These
cool. include plots of fuel and lubricating oil consumption
Dirty lubricating oil. Drain old oil, service strainers and filters, refill versus electric load (power production), monthly
with fresh oil. pressure checks (engine parameters), and mainte- __
LUBRICATING OIL DILUTED
nance data showing cylinder wear and crankshaft
deflection. Interpretation of data and details are
Fuel in lubricating oil. Check for loose injector inlet or drain connec- provided in the specific engine manufacturer’s lit-
tion; correct as required. Drain old oil, service
strainers and filters, refill with fresh oil.
erature. These kinds of data aid in developing crite-
ria for equipment performance and determining the
Coolant in lubricating Check for internal coolant leaks. Correct as need for engine overhaul or other repair.
oil. required. Drain old oil, service strainers and
filters, refill with fresh oil.
(1) Samples of information appearing in figure
3-17 are as follows:
LOW LUBRICATING OIL PRESSURE (a) “A” on the chart may indicate lack of op-
Faulty oil line, suction Check oil lines for good condition, fill to erating hours.
line restricted, low oil proper oil level with fresh oil. (b) “B” on the chart may indicate a peak
level. value or seasonal characteristic.
Engine due for over- Schedule the overhaul and correct as required. (c) “C” on the chart may indicate the result of
haul. Piston rings, crankshaft bearings, or cylinder frequent starts or stops. “D” on the chart indicates a
liners may be worn.
steady improvement.
ENGINE RUNNING TOO HOT (d) “E” on the chart shows lubricating oil
High exhaust back Check exhaust system and turbocharger; correct consumption. The steady decline at “F” may indi-
pressure. as required. cate a developing engine problem (i.e., oil control
ring failure, lube oil leakage into combustion areas,
Faulty thermostat. Check coolant thermostats; correct as required.
or excessive oil feed).
Low lubricating oil Fill to proper level with fresh oil. (2) Samples of information appearing in part A
level.
of figure 3-18 are as follows:
Engine overload. Reduce load to proper level. (a) “A” on the chart may indicate faulty fuel
Faulty cooling system Check components; correct as required. Fill injectors, or deviations in fuel timing.
component (pump, cooling system to proper level with coolant. (b) “B” on the chart (sharp rise in compres-
hose, radiator fan belt). sion) can be caused by carbon build up or may indi-
cate new piston rings were installed.
3-24
TM 5-685/NAVFAC MO-912

PLOT OF FUEL AND LUBE OIL CONSUMPTION VS. LOAD

0
I5
14
13
12
I I
I O
9
8
?
6
5
4
3
2

ENGINE NO. 19-

Figure 3-l7. Performance data plots.

(c) “C” on the chart may indicate a develop- (refer to the troubleshooting table) consult the spe-
ing engine problem. cific manufacturer’s literature for instructions.
(d) “D” on the chart indicates engine gover- c. Overhaul procedure. Engine overhaul requires
nor positions relative to "A", “B”, and "C”. disassembly of the engine. Verify that all engine
b. Engine overhaul. An engine consists of struc- parts comply with the manufacturer’s specifications
tural parts and moving parts. Structural parts are and tolerances.
those having no movement relative to each other. (1) Inspect structural parts as follows:
They do not involve clearances, adjustments, or lu- (a) Foundations for deformation and cracks.
brication. These parts consist of the following: foun- (b) Bedplate for cracks and distortion; bear-
dation, bedplate, foundation bolts, frames, cylinders ing supports for good condition.
and block, cylinder heads, covers and associated (c) Foundation bolts for tightness and gen-
gaskets, and auxiliary housings. Moving parts are eral good condition including straightness.
those that normally require fitting and/or clearance (d) Frames for cracks, distortion, and gen-
adjustment. These parts consist of the following: eral good condition.
crankshaft (including journal surfaces, counter- (e) Cylinders and cylinder blocks for cracks;
weights, gears, and flywheels), main bearings, water jacket areas for corrosion, scale, and rust;
thrust bearings, camshafts and bearings, connect- machined surfaces for smoothness.
ing rods and bearings, pistons (including rings and (f) Cylinder heads for cracks; water jacket
pins), timing gear mechanisms, and auxiliary or areas for corrosion, scale, and rust; valve seats for
accessory drives. All of these parts are engineered cracks; machined surfaces for smoothness.
- - and designed by the engine manufacturer to per- (g) Covers and gaskets for distortion and
form a particular task. When the need to overhaul cracks; use satisfactory gaskets only after anneal-
an engine is indicated by operational malfunctions ing; use new seals and gaskets other than copper.
3-25
TM 5-685/NAVFAC MO-912

PLOT OF MONTHLY PRESSURE CHECKS


100 ’ 7 4
I .
,o 90 ’ ,
X
z 60 1 1 I I I I I

50 COMPRESSION
90
: 60
F 10
3;
2 60
GOVERNOR
SO
g 40
of 30
w
; 20 ’
c3 I O
0 f 4
JAM. FEB. MAR. APR. MAY JUN. JUL. AUG. SEP. OCT. NOV. OEC.

ENGINE NO._ A V E R . L O A D D U R I N G T E S T . _ KW 4
‘9-

A.

--

KEY
- ALONG ENGINE C.L.
---- ACROSS ENGINE CL.

B.
Figure 3-18. Maintenance data plots.
A) ‘AS-FOUND” PRESSURES, B) MEASUREMENTS OF MECHANICAL WEAR INDICATORS.
TM 5-685/NAVFAC MO-912

(2) Inspect moving parts as follows: each part for an engine should be available.
(a) Crankshaft for out-of-alignment condi- e. Parts salvage. Certain parts may be replaced
tion; journal surfaces for highly polished condition prior to their failure due to a preventive mainte-
“.__
and absence of scratches, nicks, etc.; and counter- nance program. It may be possible to restore these
weights, gears, and flywheels for proper condition. parts to specified tolerances. Refer to specific manu-
Verify that crankshaft complies with manufactur- facturer’s literature for recommendations and in-
er’s requirements. An engine crankshaft is a costly structions. The following information is a general
and vulnerable component. Special care in handling guide:
is required. Accurate alignment is essential to good (1) Worn pump shafts and cylinder liners may
engine operation. Removal or installation may re- be built up and machined to specified dimensions.
quire hoisting. Refer to the manufacturer’s instruc- (2) Grooves in pistons may be machined and l

tions for details and proper procedures. oversize rings specified for use.
(b) Main be arings for highly polished condi- (3) Press-fitted bushings and bearings may
tion, cracks, deformation and absence of scratches, loosen. The related body part may be machined to a
nicks, etc. new dimension and oversize bushings and bearings
(c) Thrust bearings for cracks and deforma- fitted.
tion; surfaces for smoothness and absence of (4) Worn journals on crankshafts and cam-
scratches and nicks. shafts may be built up and machined to specified
(d) Camshaft cams and cam faces for worn or dimensions.
deformed condition; journal surfaces and bearings
for highly polished condition and absence of 3-13. Gas turbine engines.
scratches, nicks, etc; and cam contours and cam
The following provides a general description of gas
followers for good condition.
turbine engines used for power generation. Informa-
(e) Connecting rods for cracks or other flaws
tion is also provided in paragraph 3-lb of this
by magnaflux or dye penetrant method and for
manual. For generating electric power, a turboshaft
bending and for parallelism; bearings for highly pol-
(shaft turbine ) engine is used (see fig 3-19). In a
ished condition and absence of scratches, nicks,
cracks, and deformation. turboshaft engine, the turbine provides power in
“-_ (f) Pistons for cracks and warped condition; excess of that required to drive the engine compres-
verify pistons, rings, and pins comply with manu- sor. The excess power is applied as rotary driving
facturer’s requirements; and rings and pins for gen- torque available at an output shaft. The power to
eral good condition. drive the output shaft is extracted from the same
(g) Timing gear mechanisms for good condi- turbine that drives the compressor. The turbine is
tion; backlash for manufacturer’s tolerance require- usually connected through a gearbox to the genera-
ments; and gear teeth for general good condition. tor. The gearbox is used for speed reduction.
(h) Auxiliary or accessory drives for good op-
erating condition. Consult the specific manufactur- 3-14. Gas turbine engine classifications.
er’s literature for instructions. a. Pressure and stages. Gas-turbine engines used
d. Repair parts and supplies. Certain repair for auxiliary power generator sets are classified as
parts and supplies must be available for immediate high-pressure-turbine (HPT) or low-pressure-
use. Refer to specific manufacturer’s literature for turbine (LPT) types. Additionally, the engines are
recommendations. The following information is a classified by the number of stages employed in the
general guide: turbine design. In general, the more stages used in
(1) The following parts should be renewed at the design, the greater the engine torque. All of the
each: gaskets, rubber sleeves, and seals. Adequate turbine rotor stages in the multi-stage turbine are
quantities should be maintained. connected to a common shaft.
(2) The following parts have a reasonably pre- b. Power requirement. For a specified prime
dictable service life and require replacement at pre- mover power requirement, the engine design can be
dictable periods: fuel injectors, pumps, governors, either a single-stage, large diameter turbine or an
and valves. A one-year supply should be main- equivalent small diameter multi-stage turbine.
tained. c. Simple cycle. Most engines are designed to use
(3) The following parts have a normally long natural gas and/or liquid fuel similar to kerosene.
life and, if failure occurs, could disable the engine These are called simple-cycle engines.
for a long period of time: cylinder head, cylinder d. Compressor and combustor. Most engines have ”
liner, piston and connecting rod, gear and chain an axial flow compressor and a cannular or annular
drive parts, and oil pressure pump. One item of combustion section (combustor).
3-27
TM 5-685/NAVFAC MO-912

3-15. Principles of operation. the combustor provide a spark to ignite the fuel/air
a. Components. A typical gas turbine engine con- mixture for engine start-up. The igniters are deac-
sists of a compressor, combustor and turbine (see fig tivated after start-up has been accomplished. Hot
-
3-20). combustion gases are expelled through the turbine.
(1) The compressor is driven by the turbine (3) The turbine extracts energy from the hot
through a common shaft. Air enters the compressor gases, converting it to rotary power which drives
via an inlet duct. The compressor increases the air the compressor and any load, such as a generator.
pressure and reduces the air volume as it pumps air Exhaust gases are vented via ductwork to the atmo-
to the combustor and through the engine. sphere.
(2) Fuel (liquidd and/or natural gas) is delivered (4) The air intake for a gas turbine engine usu-
to the combustor by a fuel system consisting of a ally consists of a plenum chamber with a screened
manifold, tubes, and nozzles. Electrical igniters in inlet duct opening. The plenum chamber and duct

Figure 3-19. Typical gas turbine engine for driving electric power generator.

EXHAUST
I I DUCT

INLET TOR
DUCT

Kd /
SHAFT GEARBdX

Figure 3-20. Gas turbine engine, turboshaft.

3-28
P TM 5-685/NAVFAC MO-912

are engine emplacement features that may vary at connected by tubes to allow flame propagation dur-
different installations. Air entering the duct passes ing ignition and operation.
through a filter assembly. The filters remove debris
‘L 3-16. Gas turbine fuel system.
and other material that would otherwise be drawn
into the engine compressor and other operating ar- System components. The system provides the engine
4 eas causing damage. Usually the lowest part of the with the proper amount of fuel to sustain operation.
plenum is equipped with a drain for removal of System components include filters, a fuel manifold,
moisture. fuel tubes, and nozzles. Off-engine components in-
z b. Sequence of euents. Combustion causes an in- clude the fuel control equipment and a supply sys-
crease in gas temperature proportionate to the tem.
amount of fuel being injected, a moderate increase a. Fuel. Fuel (liquid and/or natural gas) enters
in velocity, and a negligible decrease in pressure. the tubular fuel manifold ring via the supply sys-
Approximately 25 percent of the compressor’s total tem. The fuel tubes direct the fuel from the mani-
air flow is used for combustion at an air/fuel ratio of fold to the fuel nozzles which are mounted in the
about 15:l. The remaining 75 percent of compressor fuel swirlers (see fig 3-22 and 3-23). Compressor
air output is fed to the combustor and to cool com- discharge air flows radially inward through the
bustor liners for cooling combustion gases before primary swirler in the combustion liner, which
they enter the turbine. rotates the air circumferentially and mixes it with
(1) The sequence of events during turbine en- the fuel. Air entering radially inward through
gine start-up and operation is as follows: the secondary swirler is caused to rotate in the
(a) Air is drawn into the compressor by ro- opposite direction. As the two counter-rotating mix-
tating the engine. Rotation is accomplished by the tures join, the fuel mixes completely with the air.
engine starter. The engine is rotated to the speed at This process promotes complete mixing of the fuel
which it becomes self-sustaining. and air and, therefore, more complete burning of
(b) As the engine shaft is rotated and accel- the mixture resulting in less smoke emission and
erated by the starter, fuel is fed to the combustor. more uniform temperature distribution within the
When the air pressure is high enough, the air/fuel combustor.
mixture is ignited by an electrical spark. b. Ignition. Ignition is accomplished by one or
‘“_ (c) The electrical spark is deactivated after two igniter plugs. At ignition, the igniters are acti-
ignition occurs. Since the air/fuel mixture is con- vated and fuel is injected into the swirlers. After
tinuously fed to the combustor by the turbine and ignition, the igniters are deactivated (refer to para
compressor, and since there is a flame in the com- 3-15b( 1)).
bustor after ignition, engine operation is self-
sustaining. 3-17. Gas turbine cooling system.
(d) Rotation of th e engine by the starter is a. Approximately 25 percent of the air entering a
necessary after combustion takes place to help ac- combustor is mixed with fuel and burned. The re-
celerate the engine to rated speed. Once the engine maining air is mixed with the products of combus-
speed has increased to approximately 60 percent of tion to reduce the temperature of gases entering the
rated speed, the starter is deactivated. turbine to a safe operating level. Cooling is accom-
(e) Gas turbine engines have dual-fuel capa- plished by engine airflow.
bility since they may use either liquid or gaseous b. Three forms of air cooling of the vanes and
fuel. Generating units with these engines are reli- blades are used, either separately or in combina-
able and virtually free of vibration. tions. The types of cooling are convection, impinge-
(2) Types of combustors. Combustors for gas ment, and film (see fig 3-24).
turbine engines for generators are either cannular (1) Convection. For convection cooling, air
. or annular-type with newer engines usually having flows inside the vanes or blades through serpentine
an annular combustor. The annular-type engine is paths and exits through the blade tip or holes in the
described in this manual. See figure 3-21 for de- trailing edge. This form of cooling is used in the
(r tails. The annular combustor consists of a continu- area of lower gas temperature (see fig 3-25).
ous circular inner and outer casing or shell; the (2) Impingement. Impingement cooling is a
space between the casings is open. The cannular form of convection cooling, accomplished by direct-
combustor consists of inner and outer combustion ing cooling air against the inside surface of the
casings mounted coaxially around the engine airfoil through small internal high velocity air jets.
compressor/rotor shaft. A cluster of burner cans are Cooling is concentrated at critical sections, such as
LL leading edges of vanes and blades (see fig 3-26).
located between the two casings. The cans are inter-

3-29
TM 5-685/NAVFAC MO-912

COMBUSTION SECTION

INNER
COMBUSTION
CASING

~~
CANNULAR COMBUSTOR COMBUSTION OUTER CASING

FUEL

DIFF'U

ANNULAR COMBUSTOR

Figure 3-21. Typical types of combustors.


ABOVE: CANNULAR TYPE; BELOW: ANNULAR TYPE

3-30
TM 5-685/NAVFAC MO-912

HIGH PRESSURE
TURBINE OUTER CASING

Figure 3--22. Engine combustion section.

(3) Film. Film cooling is a process whereby a bution to bearings. Off-engine components include
layer of cooling air is maintained between high tem- flexible oil lines between on-engine and off-engine
perature gases and the external surfaces of the tur- components, oil cooler, oil tank, lubrication supply
bine blades and vanes. In general, film cooling is the differential pressure sensor, and lubrication pump.
most effective type. Oil is supplied by jet or spray to bearings in other
areas via tubes. The engine starter is usually lo-
3-18. Lubrication system. cated in an accessory gearbox.
a. The lubrication system for a gas turbine en- (1) A-Sump. Oil for A-- sump components is usu-
gine is usually self-contained with the engine and ally piped from a gearbox into the sump. Internal
supplies oil for lubrication and cooling during en- passages and manifolding carry the oil to the
gine operation (see fig 3-27). Engine bearings in the A-sump housing. A double-headed nozzle supplies
compressor, combustor, and turbine areas (identi- oil to the forward bearing and the undercooled car-
fied as areas A, B, and C, respectively) are supplied bon seal runner for the bearing. The second bearing
by the system. System pressure is approximately 75 is lubricated through oil nozzles mounted on a
psi and is usually maintained by a supply and scav- power take-off housing. Oil is supplied to the rear
enge pump (refer to scavenging in appendix C). bearings through jets on the forward and aft sides of
Most systems include a heat exchanger to cool the the bearing. The carbon seal runner for the bearing
oil and an oil supply tank. is cooled by oil which has lubricated the power take-
b. On-engine components usually include lubri- off unit and the compressor forward shaft, and is
cation supply and scavenge piping, a supply tem- then sprayed outward through holes in the shaft.
perature RTD sensor (resistance temperature detec- This oil is then passed through holes at the seal
tor), and chip detectors at A, B, and/or C oil runner where an oil slinger moves it away from the
collection sumps. Nozzles are provided for oil distri- carbon seal.
3-31
TM 5-685lNAVFAC MO-912

OUTER SHELL

Figure 3-23. Engine combustion liner.

(2) B-Sump. Oil enters the B-sump via a frame engines, the rearmost nozzle has two heads with
strut and is directed through tubing in the housing two jets in each head. One set of jets sprays oil on
to the mid-engine bearing oil nozzles. Each nozzle the bearing. The other set sprays oil on the bearing
has two jets. One jet supplies oil to the bearing and locknut which causes the oil to spray on the rear
the other jet supplies oil to the carbon seal runner wall of the C-sump cover and vent collector to cool it
for the bearing. and reduce coking. The adjacent bearing oil nozzle
(3) C-Sump. Oil enters the C-sump through a also usually has two heads with two jets in each.
feed tube and is diverted internally through Two jets direct oil onto the bearing and the others
manifolding and tubing to the oil nozzles. In many direct oil to the carbon seal runner for the bearing.
3-32
TM 5-685/NAVFAC MO-912

SC
FI
TU

SCHEMATIC OF TYPICAL
FIRST STAGE TURBINE
INLET STATIONARY VANES

CONVECTION

Figure 3-24. Air cooling modes of turbine vanes and blades.

3-33
TM 5-685/NAVFAC MO-912

EALER TIP

CAP ~-,
NO

LEADING BLADE
-
INLET HOLES TRAILING BLADE

SQUEALER TIP AIR DISCHARGE


HOLES

CA

BLADE PLATFORM

MATING
SURFACE

AIRFOIL AIR TRAILING BLADE


INLET HOLES

Figure 3-25. Turbine blade cooling air flow.


TM 5-685/NAVFAC MO-912

INSERT
COVER

FRONT tNSERT

NOSE HOLES

16TH STAGE
SC3TS

Figure 3-26. Turbine vane cooling air f l o w .

(4) Scavenging. Scavenging is accomplished by b. Fuel. As the engine is accelerated by the


a multi-element lubrication and scavenge pump. starter, fuel is supplied when a specified rotational
One element is used for pumping. The other ele- speed is attained. When this speed is attained, the
ments are used for forward and aft scavenging of compressor and engine-driven fuel pump will de-
the B-sump and C-sump. Oil in the A-sump drains liver sufficient air and fuel, respectively to the com-
by gravity into the accessory gearbox. bustion chamber to sustain satisfactory combustion.
(5) Venting. S ome lubrication systems are c. Ignition system. An ignition system, consisting
vented. To maintain high differential pressure of an ignition exciter, igniter plug lead assemblies,
across the carbon seals to prevent oil leakage, a and igniter plugs, is required. Fuel ignition is en-
high sump vent capacity is required. The A and C sured by one or two igniter plugs connected to the
sumps vent through the engine output shaft and exciter by the separate igniter leads. The plugs are
vent collector to ambient. The B-sump vents to the located in the combustion chamber. Each plug con-
turbine exhaust gas stream. sists of center and outer electrodes with a semicon-
ductor surface coating at the tip between the two
3-19. Starting system. electrodes. The semiconductor ma.terial is used as a
Gas turbine engine starters must be capable of ro- shunt to aid in ionizing the air gap between the two
tating an engine up to a speed-at which it becomes electrodes so that the plugs will fire. An air shroud
self-sustaining. The starter must provide sufficient covers the end of the plug immersed in the air
torque to accelerate the engine from a standstill to a stream for cooling.
self-sustaining speed within a specified time. Al- d. Specialized system. Starting systems are
though it must continue to assist the engine in ac- highly specialized and are usually applicable to a
celerating up to a predetermined speed. given i nstallation or site. Refer to supplier’s on-site
a. Electric motor. An electric starter motor is usu- technical literature for details.
ally used for a gas turbine engine in service as an
auxiliary generator prime mover. The starter ro- 3-20. Governor/speed control.
tates the engine compressor shaft via the gear train a. Engine operation. The engine is started by an
in the accessory gearbox. In most installations the external power source. Once the engine reaches idle
starter can be energized either automatically or speed, it is self-sustaining. All it needs is adequate
manually. supplies of air and fuel. Combustion gas drives the
3-35
TM 5-685/NAVFAC MO-912

Figure 3-27. Lubrication system for gas turbine.

3-36
TM 5-685/NAVFAC MO-912

turbine which is mounted on a common shaft with nance program that is built around records and
k
L the compressor. The compressor draws in the air for observation. The program is described in the manu-
rc combustion and also drives the gearbox gear train. facturer’s literature furnished with each engine. It
-
About two-thirds of the power derived from combus- includes appropriate analysis of these records.
tion is required to sustain combustion. The remain- b. Record keeping. Engine log sheets are an im-
ing power is available for work purposes and drives portant part of record keeping. The sheets must be
the output shaft. developed to suit individual applications (i.e., auxil-
b. Speed signal. An engine speed signal, gener- iary use) and related instrumentation.
ated by magnetic pickups (speed transducers) in the c. Log sheet data. Log sheets should include en-
gearbox, provides electrical signals that are propor- gine starts and stops, fuel and lubrication oil con-
tional to engine speed. The signal causes a dc volt- sumption, and a record of the following:
age to be generated. (1) Hours s ince e last oil change.
c. Thermocouples. Thermocouples sense the tur- (2) Hours since first put in service or last over-
bine discharge/inlet total temperature. The electri- haul.
cal temperature sensing signal is an average of the (3) Total ho urs on engine.
operating temperature profile. d. Oil analysis program. Use of a Spectrometric
d. Pressure sensing. Sensing of compressor dis- Oil Analysis Program is recommended to determine
charge static pressure and turbine discharge pres- the internal condition of the engine’s oil-wetted
sure is also required for engine speed control. These (wear metal) components, such as bearings, gears,
pressures are combined to produce an electrical sig- and lubrication pump.
nal equal to pressure ratio. (1) The program should be used as a supple-
e. Computer. The three signals (speed, tempera- ment to the regular maintenance procedure of chip
ture, and pressure ratio) are summed in an detection and filter inspection. Normal wear causes
acceleration/deceleration computer. Computer out- microscopic metal particles (smaller than one mi-
put functions with a governor to meter fuel required cron) to mix with the lubricating oil and remain in
for engine operation. If required, a signal derived suspension. Samples of oil taken from the engine
from a tachometer can be used to determine a rate- after a shutdown will contain varying amounts of
of-change feedback signal. wear-metal particles.
-_ (2) Oil samples should be removed from the
3-21. Compressor. engine at the time intervals specified by the engine
The function of the compressor is to raise the pres- manufacturer. A sample should always be taken
sure and reduce the volume of the air as it pumps from the same location on the engine (this may vary
it through the engine. An axial flow or centrifugal from each engine). Refer to manufacturer’s litera-
flow compressor is used. Most engines use a multi- ture. See appendix C paragraph C-le(2).
stage, axial flow compressor such as described (a) Metal content. Evaluation of the oil’s
herein. The axial flow consists of two major sub- wear-metal content is very important. The quantity
assemblies: the rotor assembly and the stator as- of wear-metal in the sample as well as type (iron or
sembly. Axial flow compressor efficiency is better steel, silver, chromium, nickel, etc.) must be evalu-
than centrifugal flow compressor efficiency. Cen- ated and recorded.
trifugal flow compressors were first used in early (b) failure forecast. Evaluation records are
design gas turbine engines. The main component is intended as an aid in forecasting what components
an impeller which is mounted on a common shaft are in danger of failing. Contamination of the oil
with the turbine. These compressors are generally sample must be prevented to avoid false indication
used with smaller engines and have a fairly low of engine internal conditions. ,
pressure ratio. The design has lower efficiency than e. Industrial practices. Use recognized industrial
the axial-flow design but is less expensive to manu- practices as the general guide for engine servicing.
facture. Service information is provided in manufacturer’s
literature and appendixes B through G.
3-22. Gas turbine service practices. f. Reference Literature. The engine user should re-
a. Maintenance program. Service practices for fer to manufacturer’s literature for specific informa-
gas turbine engines consist of a complete mainte- tion on individual units.

3-37
TM 5-685/NAVFAC MO-912

CHAPTER 4

GENERATORS AND EXCITERS


-

4-1. Electrical energy. needed to direct the flow of current in one direction.
Mechanical energy provided by a prime mover is The generator rotating commutator provides the
converted into electrical energy by the generator rectifying action.
(see fig 4-l). The prime mover rotates the generator 4-4. AC generators.
rotor causing magnetic lines of force to be cut by
a. AC generators are considered either brush or
electrical conductors. Electrical energy is thereby
brushless, based on the method used to transfer DC
produced by electromagnetic induction. The ratio of
exciting current to the generator field. In addition,
output energy generated by input energy is ex-
AC generators are classified as salient-pole or
pressed as a percentage and always shows a loss in
nonsalient-pole depending on the configuration of
efficiency.
the field poles. Projecting field poles are salient-pole
4-2. Generator operation. units and turbo-type (slotted) field poles are
nonsalient-pole units. Typical AC generator
a.A generator consists of a number of conducting armatures are shown in figures 4-3 and 4-4.
coils and a magnetic field. The coils are called the b. Damper windings on the rotor stabilize the
armature. Relative motion between the coils and speed of the AC generator to reduce hinting under
magnetic field induces voltage in the coils. This changing loads. If the speed tends to increase,
action is called electromotive force (emf). A sche- induction-generator action occurs in the damper
matic for a typical generator system is shown in windings. This action places a load on the rotor,
figure 4-2. tending to slow the machine down. If the speed
b. An alternating current (AC) generator needs a tends to decrease, induction-motor action occurs in
separate direct current (DC) source to feed the mag- the damper winding, tending to speed the machine
netic field. The required DC is provided by an exter- up. The windings are copper bars located in the
’ .___ nal source called an exciter. Usually, the exciter is a faces of the rotor pole pieces. Mounted parallel to
small DC generator that is driven by the generator the rotor axis, the bars are connected at each end by
rotor. The exciter may be mounted on the rotor shaft a copper ring.
or rotated by belt-drive. Some generating systems c. AC generators that operate at a speed that is
use a static, solid-state exciter to provide DC. exactly proportional to the frequency of the output
c. A voltage regulator controls the induced volt- voltage are synchronous generators. Synchronous
age by regulating the strength of the electromag- generators are usually called alternators.
netic field established by the exciter. Frequency is
controlled by the speed at which the prime mover 4-5. Alternator types.
rotates the rotor. Alternators are single-phase or polyphase. Varia-
tions include three-phase alternators used as
4-3. Types of generators. single-phase units by insulating and not using one
Depending on the type of generating equipment em- phase lead. Since the lead is unused, it is not
ployed, the electrical energy produced is either di- brought out to a terminal. The kilowatt rating is
rect current ( D C ) or alternating current (AC). reduced from that of the three-phase unit as limited
a. AC generators. AC generators are classified as by the amount of current carried by a coil. An alter-
single-phase or polyphase. A single-phase generator nator designed only for single-phase operation usu-
is usually limited to 25 kW or less and generates AC ally does not have coils in all of the armature slots
power at a specific utilization voltage. Polyphase because end coils contribute little to the output volt-
generators produce two or more alternating volt- age and increase the coil impedance in the same
ages (usually two, three, or six phases). proportion as any other coil.
b. DC generators. DC generators are classified as (a) Single-phase alternators are usually used in
either shunt, series, or compound-wound. Most DC smaller systems (limited to 25kW or less) and pro-
generators are the compound-wound type. Shunt duce AC power at utilization voltages.
generators are usually used as battery chargers and (1) Terminal voltage is usually 120 volts. The
as exciters for AC generators. Series generators are electric load is connected across the terminals with
sometimes used for street lights. The emf induced in protective fuses. One voltmeter and one ammeter
a DC generator coil is alternating. Rectification is measure the output in volts and amperes, respec-
TM 5-685/NAVFAC MO-9122

--

Figure 4-l. Typical alternating current generator.

EXCITER GENERATOR

; I
I

A
I 11
I T2
I

I
I
TJ

I STATOR
WINDINGS

; / j ;;=I j ALkRNATOR "O&E F E E D B A C K = ’

- - - -I - - - - - - - - - - - - - - - - - - - - - - - -

Figure 4-2. Brush-type excitation system, schematic.


TM 5-685/NAVFAC MO-912

DAMPER

SLIP R

Figure 4-3. Brush-type AC generator field and rotor:

Figure 4-4. AC generator field and rotor with brushless-type excitation system.

tively The two-wire alternator has two power termi- and 240 volts between the two ends. The load is
nals, one for each end of the armature coil (see fig connected between the two outside wires or between
4-5). either outside wire and neutral, depending upon the
(2) The thre e-wire, single-phase alternator has voltage required by the load. Assuming alternator
three power terminals; one from each end of the voltage to be 120/240 volts, load 1,0 and load 2,0
armature coil and one from the midpoint (neutral, would consist of 120-volt lamps and 120-volt single-
see fig 4-6). Terminal voltage is usually 120 volts phase power equipment. Load 1,2 would consist of
from the midpoint to either end of the armature coil 240-volt power equipment. Two voltmeters and two
TM 5-685/NAVFAC MO-912

TO E X C I T E R AMMETER LOAD

Figure 4-5. Two-wire, single-phase alternator.

- a
- v
1
l
I

0 LOAD
TO EXClTER 1. 1,
1.2

AMMETER

Figure 4-6. Three-wire, single-phase alternator.

ammeters (or equivalent) are required to determine of single-phase windings spaced 120 electrical de-
the load in kilovoltamperes (kVA). grees apart around the armature. One electrical
(b) Polyphase alternators are two, three, or six degree is equivalent to one degree of arc in a two-
phases. Two-phase power is used in only a few lo- pole machine, 0.50 degree of arc in a four-pole ma-
calities. Six-phase is primarily used for operation of chine, 0.33 degree of arc in a six-pole machine, and
rotary converters or large rectifiers. Three-phase so on. The three single-phase windings are con-
alternators are the most widely used for power pro- nected in series to form the delta connection, and
duction. Polyphase alternators have capacities from the terminals are connected to the junction point of
3 kW to 250,000 kW and voltage from 110 V to each pair of armature coils (see fig 4-7). The total
13,800 V. Two general types of three-phases alterna- current in a delta-connected circuit is always equal
tor windings are the delta winding used in three- to the vector sum of currents in two-phase wind-
wire, three-phase alternators, and the star or wye ings. The instantaneous current flows out to the
winding used in four-wire, three-phase types. load through two windings and returns from the -
Three-wire, three-phase alternators have three sets load through the third winding. Since the coils are
TM 5-685/NAVFAC MO-912

SINGLE PHASE
VOLTMcTERS AMMETERS LOAD

. I ,* . I _’
VM AM. LOAD
GENERATOR
EXCITER ROTOR STATOR PHASE LOAD

VM AM LOAD

Figure 7.92 Three-wire, three-phase alternator.

similar physically and electrically, equal voltages (d) The fou r-wire, three-phase alternator (see fig
are generated and applied to the terminals. Due to 4-8) has three sets of armature coils spaced 120
spacing of the coils about the armature, the maxi- electrical degrees apart about the armature, the
mum voltage between the pairs of terminals does same as the three-wire, three-phase alternator. One
not occur simultaneously. The characteristics of end of each of the three coils is connected to a
‘i-- three- wire, three-phase (or delta) alternators are: common terminal (neutral). The other end of each
(1) The amount of current through the alterna- coil is connected to separate terminals (phase ter-
tor terminals is the algebraic sum of current minals). Thus, the four-wire alternator has four
through the alternator coils. terminals which connect to the three-phase con-
(2) The currents are not equal in magnitude or ductors and the neutral of the power-plant bus.
time. When each end of each coil is brought out to sepa-
(3) Connection between coils can be made ei- rate terminals, the connections between coils are
ther inside or outside the generator. made outside of the alternator, enabling installation
(c) In a 60-Hertz machine, each coil experiences of a more comprehensive protective relaying sys-
maximum instantaneous voltage, first positive and tem.
then negative, 120 times each second. Disregarding (e) The four-wire, three-phase alternator can be
voltage direction, the maximum instantaneous volt- connected to a transformer instead of the power-
ages occur on successive coils 0.003 seconds apart. plant bus by using a wye-wye transformation. Ir-
Due to time differences between the voltages and regular (double or triple) harmonics, which may be
resulting currents, the amount of current through produced, can be suppressed by using a core-type
the alternator terminals and the amount through transformer. A third or tertiary winding with a delta
the alternator coils are not equal in magnitude or connection may also be used as a suppressor. A
time. The current through the alternator is 73 per- wye-delta transformer may be used if the power
cent greater than through the coils. Coil and termi- plant bus is three wire and the alternator is four
nal voltages are the same magnitude. Three voltme- wire wye connected.
ters and three ammeters (or equivalent) are (f) Four-wire three-phase, dual voltage and
required to measure the load on the alternator. The frequency alternators are also used. These are sup-
average value of the three currents times the aver- plied in sizes from 15 to 1500 kW, 127-220 volts,
age value of the three voltages plus 73 percent gives three-phase, 60 Hertz, or 230-400 volts, three-
a close approximation of the alternator load in phase, 50 Hertz. Dual stator coils are used on each
kilovolt-amperes. Two single-phase or one two- phase. Coil ends are brought out to a terminal board
\_
element polyphase kilowatt-hour meter is required for making connections. Voltage and frequency com-
to measure the alternator output in kilowatt-hours. binations are shown in figure 4-9.
4-5
TM 5-685/NAVFAC MO-912

VOLTMETERS SlNCLE PHASE


LOAD
AMMETERS LINE TO LOAD
NEUTRAL LINE TO LINE
I
GENERATOR I/I
EXCITER ROTOR
7

7 -r

LOAD
1.2

3 2 ’
VM. AM. LOAD LOAD
2,o 30 l;O 2.3
t . ,
Q

I )I, *
l * Y

VM.
390

Figure 4-8. Four-wire, three-phase alternator.

VOLTAGE AN0 FREQUENCY COM ATIONS


ENGINE-GENERATOR SETS USED ERSEAS

STATOR

(A) SERIES COIL CONNECTION (B 1 PARALLEL COIL CONNECTION

Figure 4-9. Dual voltage and frequency.


TM 5-685/NAVFAC MO-912

(g) Most parts of the world have standard- end of each coil is connected to separate terminals.
ized on either 50 or 60 Hertz alternating current Conductors attached to the four terminals carry the
L power. Sixty Hertz power is commonly used in the current to the system’s switchgear and on to the
United States. Fifty Hertz power is used in many load.
t countries outside the United States. The ratio be- d. Collector slip rings. Slip rings are usually
tween the 60-50 Hertz frequencies is 6:5. Electrical made of nonferrous metal (brass, bronze or copper);
energy received at one frequency can be converted iron or steel is sometimes used. Slip rings usually
to a different frequency by using a frequency do not require much servicing. The wearing of
changer. If a large power requirement exists, it may grooves or ridges in the slip rings is retarded by
be more economical to use a special alternator to designing the machine with limited endplay and by
produce power at the desired frequency The appli- staggering the brushes. Surfaces of the slip rings
cable equation is: should be bright and smooth, polishing can be per-
V=KxQlxNxf formed with fine sandpaper and honing stone. Elec-
where V = generated voltage trolytic action can occur at slip ring surfaces pro-
K = constant value number (speed) ducing formation of verdigris. Verdigris is a
8 = phase/phase angle greenish coating that forms on nonferrous metals.
N = number of turns
Electrolytic deterioration can be prevented by re-
f = line frequency
versing the polarity of the slip rings once or twice a
(h) The generated voltage is proportional to the
year. The stator of the three-wire, three-phase unit
strength of the magnetic field, phase, and number of
also has three sets of armature coils spaced 120
turns in series between terminals and the speed.
electrical degrees apart. The ends of the coils are
4-6. Design. connected together in a delta configuration. Conduc-
tors are attached to the three connecting points.
a. Components. A typical AC generator consists of
a stationary stator and a rotor mounted within the 4-7. Characteristics of generators.
stator (see fig 4-l). The stator contains a specific
number of coils, each with a specific number of a. Voltage. Generated voltage is the emf denoting
windings. Similarly, the rotor consists of a specific the electric pressure between phases in the arma-
“X- ture. The magnetic flux linking each armature coil
number of field poles, each with a specific number of
windings. In addition to the rotor and stator (refer changes as the machine rotates. The change in flux
to paragraphs 4-6b and 4-6c, respectively), a gen- per turn occurs at the conductors in the armature
erator has a collector assembly (usually consisting slots. Each conductor is regarded separately as it
of collector slip rings, brushes, and brush holders). cuts the flux. At a specific rotating speed, instanta-
The slip rings are covered in paragraph 4-6d. DC neous volts per conductor are proportional to air
flows from the exciter, through the negative brush gap flux density at the conductor.
and slip ring, to the rotor field poles. The return b. Current. Current is the rate of transfer (flow)
path to the exciter is through the positive brush and of electricity, expressed in amperes. Field current
slip ring. required for a particular load condition, i s deter-
b. Rotor. The rotor contains magnetic fields which mined by the magnetic circuit, in conjunction with
are established and fed by the exciter. When the armature and field windings. Load current is equal
rotor is rotated, AC is induced in the stator. The to the generated voltage divided by the impedance .
changing polarity of the rotor produces the alternat- of the load.
ing characteristics of the current. The generated c. Speed. Normally, a generator operates at a con-
voltage is proportional to the strength of the mag- stant speed corresponding to the frequency and
netic field, the number of coils (and number of wind- number of poles. Variations may occur due to
ings of each coil), and the speed at which the rotor changes in driving torque, load, field excitation, or
turns. terminal voltage.
c. Stator. The frame assembly is the main compo- d. Frequency. AC frequency is determined by the
nent of the stator. Insulated windings (or coils) are rotating speed and number of poles of the generator.
placed in slots near an air gap in the stator core. Frequency is usually expressed in Hertz, the fre-
There is a fixed relationship between the unit’s quency used most is 60 Hertz. A two-pole generator
number of phases and the way the coils are con- must operate at 3600 rpm to maintain 60 Hertz.
nected. The stator in a four-wire, three-phase unit Four-pole and six-pole units must operate at 1800
has three sets of armature coils which are spaced rpm and 1200 rpm, respectively, to maintain 60
120 electrical degrees apart. One end of each coil is Hertz. Frequency at 60 Hertz is expressed in the
connected to a common neutral terminal. The other following equation:
TM 5-685/NAVFAC MO-912

Frequency = (Speed in rpm) (Pairs of poles) generator fields is provided in several forms includ-
(60 Hertz) 60
ing field-flash voltage from storage batteries and
e. Power. Power is the term used to describe the
voltage from a system of solid-state components. DC
rate at which electric energy is delivered by a gen-
generators are either separately excited or self-
erator and it is usually expressed in watts or kilo-
excited.
watts (lo3 watts).
b. Excitation systems in current use include
(1) Watts. W att s are units of active or working
power, computed as follows: volts x measured or direct-connected or gear-connected shaft-driven DC
apparent amperes x power factor. generators, belt-driven or separate prime mover or
(2) Volt amperes reactance (Mars). Vars are motor-driven DC generators, and DC supplied
units of reactive or nonworking power (1 var = 1 through static rectifiers.
reactive volt-ampere). c. The brush-type exciter can be mounted on the
(3) Power factor. Power factor is the ratio of same shaft as the AC generator armature or can be
active or working power divided by apparent power. housed separately from, but adjacent to, the genera-
The relationship of apparent power, active power, tor (see fig 4-2). When it is housed separately, the
and reactive power is shown in figure 4-10. The exciter is rotated by the AC generator through a
hypotenuse represents apparent power, the base drive belt.
represents active power, and the altitude of the d. The distinguishing feature of the brush-type
power triangle represents reactive power. Power generator is that stationary brushes are used to
factor (the cosine of angle 0) is a unitless number transfer the DC exciting current to the rotating
which can be expressed in per unit or in percentage. generator field. Current transfer is made via rotat-
For convenience, kilo (103) is often used with the ing slip rings (collector rings) that are in contact
terms volt- amperes, watts and vars in order to with the brushes.
reduce the number of significant digits. e. Each collector ring is a hardened-steel forging
% Power Factor = kW x 100 that is mounted on the exciter shaft. Two collector
kVA
rings are used on each exciter, each ring is fully
4-8. Exciters. insulated from the shaft and each other. The inner
a. An AC or DC generator requires direct current ring is usually wired for negative polarity, the outer
to energize its magnetic field. The DC field current ring for positive polarity.
is obtained from a separate source called an exciter. f. A rotating-rectifier exciter is one example of
Either rotating or static-type exciters are used for brushless field excitation. In rotating-rectifier excit-
AC power generation systems. There are two types ers, the brushes and slip rings are replaced by a
of rotating exciters: brush and brushless. The pri- rotating, solid-state rectifier assembly (see fig 4-4).
mary difference between brush and brushless excit- The exciter armature, generator rotating assembly,
ers is the method used to transfer DC exciting cur- and rectifier assembly are mounted on a common
ren t to the generator field s. Static excitation for the shaft. The rectifier assembly rotates with, but is

ANGLE 0

Figure 4-10. Power triangle.

4-8
TM 5-685/NAVFAC MO-912

insulated from, the generator shaft as well as from one to support each end of the armature shaft. On
each winding. some generators, one end of the shaft is supported
g. Static exciters contain no moving parts. A por- by the coupling to the prime mover and one bearing
tion of the AC from each phase of generator output is used at the other end. The selections of bearing
is fed back to the field windings, as DC excitations, type and lubrication are based on generator size,
through a system of transformers, rectifiers, and type of coupling to prime mover, and expected us-
reactors. An external source of DC is necessary for age. A generator is usually equipped with either
initial excitation of the field windings. On engine- sleeve or ball bearings which are mounted in end
driven generators, the initial excitation may be ob- shields attached to the generator frame.
tained from the storage batteries used to start the b. Sleeve bearings. Sleeve bearings are usually
engine or from control voltage at the switchgear. bronze and are lubricated with oil.
(1) Most u nit s with sleeve-type bearings have a
4-9. Characteristics of exciters. reservoir for the oil and a sight gauge to verify oil
a. Voltage. Exciter voltages in common use in- level. Bearings and the reservoir are fully enclosed.
clude 63 and 125 volts for small units and 250, 375, (2) Distribution of oil to shaft and bearings
or 500 volts for large units. Exciters with normal from the reservoir is by an oil-slinger ring mounted
self-excitation are usually rated at about 135 per- on the generator shaft. Rotation of the slinger ring
cent of rated voltage and a rate buildup of about 125 throws the oil to the top of the bearing. Holes in the
volts per second. Working range is between 75 and bearing admit oil for lubrication.
125 percent of rated exciter voltage. (3) Some units with sleeve-type bearings have
b. Current. An exciter provides direct current to an absorbent fiber packing, saturated with oil,
energize the magnetic field of an AC generator. Any which surrounds the bearing. Holes in the bearing
DC generator or storage battery may be used as a admit oil for lubrication.
field current source. c. Ball bearings. Ball bearings (or roller-type
c. Speed. Speed, in rotating exciters, is related to bearings) are fully enclosed and lubricated with
generator output voltage. Usually, if magnetic field grease.
intensity is increased (by higher rotating speed), (1) Most units with ball or roller-type bearings
output voltage of the generator is also increased. are equipped with a fitting at each bearing to apply
d. Power. Exciter voltage to the magnetic field of fresh grease. Old grease is emitted from a hoie (nor-
an AC generator is usually set at a predetermined mally closed by a plug or screw) in the bearing
value. A voltage regulator controls the generator enclosure.
voltage by regulating the strength of the magnetic (2) Some units are equipped with prepacked,
field produced in the exciter. lifetime lubricated bearings.
d. Bearing wear. Noise during generator opera-
4-10. Field flashing. tion may indicate worn bearings. If source of noise
a. Field flashing is required when generator volt- is the generator bearing, replacement of the worn
age does not build up and the generating system bearing is recommended.
(including the voltage regulator) does not have field- e. Service practices. Service practices for genera-
flash capability. This condition is usually caused by tors and exciters consist of a complete maintenance
insufficient residual magnetism in the exciter and program that is built around records and observa-
generator fields. In some cases, a generator that has tions. The program is described in the manufactur-
been out-of-service for an extended period may lose er’s literature furnished with the component. It in-
its residual magnetism and require flashing. Re- cludes appropriate analysis of these records.
sidual magnetism can be restored by flashing the f. Record keeping. Generator system log sheets
field thereby causing a current surge in the genera- are an important part of record keeping. The sheets
tor. Refer to the voltage regulator manufacturer’s must be developed to suit individual applications
literature for procedural instructions. (i.e., auxiliary use).
b. Solid-state components may be included in the g. Log sheet data. Log sheets should include sys-
voltage regulator. Perform field flashing according tem starts and stops and a cumulative record of
to the manufacturer’s instructions to avoid equip- typical equipment operational items as follows:
ment damage. (1) Hours of operation since last bearing lubri-
cation.
4-11. Bearings and lubrication. (2) Hours of operation since last brush and
a. Location. Several types of bearings, each with spring inspection or servicing.
specific lubrication requirements, are used on the (3) Days since last ventilating and cooling
generators. Usually, a generator has two bearings, screen and duct cleaning.
4-9
TM 5-685/NAVFAC MO-912

h. Industrial practices. Use recognized industrial d. Troubleshooting. Perform general trouble-


practices as the general guide for generator system shooting of the equipment (as outlined in the follow-
servicing. ing table) if a problem develops. Refer to the manu-
i. Reference Literature. The generator system user facturer’s literature for repair information after
should refer to manufacturer’s literature for specific diagnosis.
information on individual units.

4-12. Generator maintenance.


Table 4-2. Generator trouble shooting.

a. Service and troubleshooting. Service consists of NOISY OPERATION


Cause Remedy
performing basic and preventive maintenance
checks that are outlined below. If troubles develop Unbalanced load or coupling Balance load and check alignment
or if these actions do not correct a problem, refer to misalignment
the troubleshooting table 4-1. Maintenance person- Air gap not uniform Center rotor by replacing or
nel must remember that the manufacturer’s litera- shimming bearings
ture supersedes the information provided herein.
Coupling loose Tighten coupling
b. Operational check. Check the equipment dur-
ing operation and observe the following indications. OVERHEATING
(1) Unusual noises or noisy operation may in- Electrical load unbalanced Balance load
dicate excessive bearing wear or faulty bearing
Open line fuse Replace line fuse
alignment. Shut down and investigate.
(2) Equipment overheats or smokes. Shut Restricted ventilation Clean, remove obstructions
down and investigate. Rotor winding shorted. opened or Repair or replace defective coil
(3) Equipment brushes spark frequently. Occa- grounded
sional sparking is normal, but frequent sparking Stator winding shorted, opened or Repair or replace defective coil
indicates dirty commutator and/or brush or brush grounded
spring defects. Shut down and investigate. Dry bearings Lubricate
c. Preventive maintenance. Inspect the equipment
Insufficient heat transfer of cooler Verify design flow rate: repair or -. ._
as described once a month. Maintenance personnel replace
unit
should make a check list suited to their particular
needs. The actions listed in table 4-l are provided NO OUTPUT VOLTAGE
as a guide and may be modified. Refer to manufac- Stator coil open or shorted Repair or replace coil
turer’s instructions. Rotor coils open or shorted Repair or replace coils

Table 4-l. Generator inspection list. Shorted sliprings Repair as directed by manufacturer

Inspect Check For Internal moisture (indicated by Dry winding


low-resistance reading on megger)
Brushes Amount of wear, Improper wear, Spring Voltmeter defective Replace
Tension
Ammeter shunt open Replace ammeter and shunt
Commutator Dirt, Amount of wear, Loose leads, Loose
bars OUTPUT VOLTAGE UNSTEADY

Collector Rings Grooves or wear. Dirt, carbon, and/or Poor commutation Clean slip rings and reseat
copper accumulation. Greenish coating brushes
(verdigris)
Loose terminal connections Clean and tighten all contacts
Insulation Damaged insulation. Measure and record
Fluctuating load Adjust voltage regulator and
insulation resistance.
governor speed
Windings Dust and dirt, Loose windings or
connections OUTPUT VOLTAGE TOO HIGH

Bearings Loose shaft or excessive endplay. Over-excited Adjust voltage regulator


Vibration (defective bearing) One leg of delta-connected stator Replace or repair defective coils
Bearing Housing Lubricant leakage, Dirt or sludge in oil open
(sleeve bearings)
FREQUENCY INCORRECT OF FLUCTUATING
Ventilation and cooling Obstruction of air ducts or screens. Loose
Speed incorrect or fluctuating Adjust speed-governing device
system or bent fan blades
TM 5-685/NAVFAC MO-912
Table 4-2. Generator trouble shooting-Continued test that can indicate the contamination of insula-
VOLTAGE HUNTING tion by moisture, dirt or carbonization. There are
“C4u Cause Remedy other tests available to determine the quality of
insulation, but they are not recommended because
External field resistance in out Adjust resistance they are generally too complex or destructive. An
position
insulation resistance test should be conducted im-
Voltage regulator contacts dirty Clean and reseat contacts mediately following generator shutdown when the
STATOR OVERHEATS IN SPOTS windings are still hot and dry. A megohmmeter is
Open phase winding
the recommended test equipment.
Cut open coil out of circuit and
replace at first opportunity. Cut and c. Before testing the insulation, adhere to the fol-
replace the same coil from other lowing:
phases (1) Take th e equipment to be tested out of ser-
Rotor not centered Realign and replace bearings, if vice. This involves deenergizing the equipment and
necessary disconnecting it from other equipment and circuits.
Unbalanced circuits Balance circuits
(2) If disco nnecting the equipment from the cir-
cuit cannot be accomplished, then inspect the in-
Loose connections or wrong Tighten connections or correct
stallation to determine what equipment is con-
polarity coil connections wrong connections
nected and will be included in the test. Pay
Shorted coil Cut coil out of circuit and replace particular attention to conductors that lead away
at first opportunity from the installation. This is very important be-
FIELD OVERHEATING cause the more equipment that is included in a test,
Shorted field coil Replace or repair
the lower the reading will be, and the true insula-
tion resistance of the apparatus in question may be
Improper ventilation Remove obstruction, clean air masked by that of the associated equipment. It is
ducts
always possible, of course, that the insulation resis-
ALTERNATOR PRODUCES SHOCK WHEN TOUCHED tance of the complete installation will be satisfac-
Reversed field coil Check polarity. Change coil leads tory, especially for a spot check. Or, it may be higher
than the range of the megohmmeter, in which case
Static charge High-speed belts build up a static
charge
nothing would be gained by separating the compo-
Connect alternator frame to a nents because the insulation resistance of each part
ground strip would be still higher.
(3) Test for foreign or induced voltages with a
4-13. Insulation testing. volt-ohm-milliammeter. Pay particular attention
a. The failure of an insulation system is the most once again to conductors that lead away from the
circuit being tested and make sure they have been
common cause of problems in electrical equipment.
properly disconnected from any source of voltage.
Insulation is subject to many effects which can
(4) Large electrical equipment and cables usu-
cause it to fail; such as mechanical damage, vibra-
ally have sufficient capacitance to store a dangerous
tion, excessive heat or cold, dirt, oil, corrosive va-
amount of energy from the test current. Therefore,
pors, moisture from processes, or just the humidity
discharge capacitance both before and after any
on a muggy day. As pin holes or cracks develop, testing by short circuiting and grounding the equip-
moisture and foreign matter penetrate the surfaces ment and cables under test. Consult manufacturer’s
of the insulation, providing a low resistance path for bulletins and pertinent references to determine,
leakage current. Sometimes the drop in insulation prior to such shorting or grounding, if a specified
resistance is sudden, as when equipment is flooded. “discharge” or “bleed” or “grounding” resistor should
Usually, however, it drops gradually, giving plenty be used in the shorting/grounding circuit to limit
of warning, if checked periodically. Such checks per- the magnitude of the discharge current.
mit planned reconditioning before service failure. If (5) Generally, there is no fire hazard in the
I, there are no checks, a motor with poor insulation, normal use of a megohmmeter. There is, however, a
for example, may not only be dangerous to touch hazard when testing equipment located in inflam-
when voltage is applied, but also be subject to burn- mable or explosive atmospheres. Slight sparking
out. may be encountered when attaching test leads to
b. The electrical test most often conducted to de- equipment in which the capacitance has not been
termine the quality of armature and alternator field completely discharged or when discharging capaci-
winding insulation is the insulation resistance test. tance following a test. It is therefore suggested that
It is a simple, quick, convenient and nondestructive use of a megohmmeter in an explosive atmosphere
4-11
TM 5-685/NAVFAC MO-912

be avoided if at all possible. If however testing must f. The ratio of two time resistance readings is
be conducted in an explosive atmosphere, then it is called a Dielectric Absorption Ratio. It is useful
suggested that test leads not be disconnected for at in recording information about insulation. If the
least 30 to 60 seconds following a test, so as to allow ratio is a lo-minute reading divided by a l-minute
time for capacitance discharge. reading, the value is called the Polarization Index.
(6) Do not use a megohmmeter whose terminal Table 4-4 gives values of the ratio and correspond-
operating voltage exceeds that which is safe to ap- ing relative conditions of the insulation that they
ply to the equipment under test. indicate.
d. To take a spot insulation reading, connect the
megohmmeter across the insulation to be tested and Table 4-3. Interpreting insulation resistance test results.
operate it for a short, specific timed period (60 sec-
onds usually is recommended). Bear in mind also TEST RESULTS
that temperature and humidity, as well as the con- Condition What to Do

dition of your insulation, affect your reading. Your


1. Fair to high values and No cause for concern
very first spot reading on equipment, with no prior well-maintained
test, can be only a rough guide as to how “good” or
“bad” the insulation is. By taking readings periodi- 2. Fair to high values, but showing Locate and remedy the cause and
a constant tendency towards check the downward trend
cally and recording them, you have a better basis of lower values
judging the actual insulation condition. Any persis-
tent downward trend is usually fair warning of 3. Low but well-maintained Condition is probably all right, but
cause of low values should be
trouble ahead, even though the readings may be
checked
higher than the suggested minimum safe values.
Equally true, as long as your periodic readings are 4. So low as to be unsafe Clean, dry out or otherwise raise
consistent, they may be OK, even though lower than the values before placing
equipment in service (Test wet
the recommended minimum values. You should equipment while drying out)
make these periodic tests in the same way each
time, with the same test. connections and with the 5. Fair or high values, previously Make tests at frequent intervals
well-maintained but showing until the cause of low values is
same test voltage applied for the same length of sudden lowering located and remedied; or until the
time. Table 4-3 includes some general observations values have become steady at a
--.
about how you can interpret periodic insulation re- lower level but safe for operation;
sistance tests and what you should do with the or until values become so low that
results. it is unsafe to keep the equipment
in operation
e. Another insulation test method is the time re-
sistance method. It is fairly independent of tem-
perature and often can give you conclusive informa- Table 4-4. Condition of insulation indicated bY dielectric
tion without records of past tests. You simply take absorption ratios. *
successive readings at specific times and note the
Insulation 60/30-Second I Oi 1 -Minute Ratio
differences in readings. Tests by this method are Condition Ratio Polarization Index
sometimes referred to as absorption tests. Test volt-
ages applied are the same as those for the spot Dangerous - Less than 1
reading test. Note that good insulation shows a con-
Questionable 1.0 to 1.25 1.0 to 2
tinual increase in resistance over a period of time. If
the insulation contains much moisture or contami- Good 1.4 to 1.6 2 to 4
nants’ the absorption effect is masked by a high Excellent Above 1.6** Above 4**
leakage current which stays at a fairly constant
value-keeping the resistance reading low. The * These values must be considered tentative and relative; sub-
time resistance test is of value also because it is ject to experience with the time resistance method over a period
independent of equipment size. The increase in re- of time.
sistance for clean and dry insulation occurs in the ** In some cases with motors, values approximately 20 percent
same manner whether a generator is large or small. higher than shown here indicate a dry brittle winding which will
You can therefore compare several generators and fail under shock conditions or during starts. For preventive
maintenance, the motor winding should be cleared, treated and
establish standards for new ones, regardless of their dried to restore winding flexibility.
kW ratings.

4-12
TM 5-685/NAVFAC MO-912

CHAPTER 5

.- SWITCHGEAR

5-1. Switchgear definition. bus are typical heavy-duty conductors rated for use
Switchgear is a general term covering switching between 601 volts AC and 38,000 volts AC, as re-
and interrupting devices that control, meter and quired.
protect the flow of electric power. The component 5-3. Low voltage elements.
parts include circuit breakers, instrument trans-
formers, transfer switches, voltage regulators, in- a. Circuit breakers. Either molded-case or air cir-
cuit breakers are used with low voltage switchgear.
struments, and protective relays and devices.
Usually the air circuit breakers have draw-out con-
Switchgear includes associated interconnections
struction. This feature permits removal of an indi-
and supporting or enclosing structures. The various
vidual breaker from the switchgear enclosure for
configurations range in size from a single panel to
inspection or maintenance without de-energizing
an assembly of panels and enclosures (see fig 5-l). the main bus.
Figure 5-2 contains a diagram of typical switchgear (1) Air circuit breakers. Air circuit breakers are
control circuitry. Switchgear subdivides large blocks usually used for heavy-duty, low voltage applica-
of electric power and performs the following mis- tions. Heavy-duty circuit breakers are capable of
sions: handling higher power loads than molded-case
a. Distributes incoming power between technical units and have higher current-interrupting capac-
and non-technical loads. ity. Air circuit breakers feature actuation of contacts
b. Isolates the various loads. by stored energy which is either electrically or
c. Controls auxiliary power sources. manually applied. Accordingly, the mechanism is
d. Provides the means to determine the quality powered to be put in a position where stored energy
and status of electric power. can be released to close or open the contacts very
e. Protects the generation and distribution sys- quickly. Closing or tripping action is applied man-
tems. ually (by hand or foot power) or electrically (where
a solenoid provides mechanical force). The me-
5-2. Types of switchgear. chanical force may be applied magnetically. Air
Voltage classification. Low voltage and medium circuit breakers contain power sensor overcurrent
voltage switchgear equipment are used in auxiliary trip devices that detect an overcurrent to the load
power generation systems. Switchgear at military and initiate tripping or opening of the circuit
installations is usually in a grounded, metal enclo- breaker.
sure (see fig 5-l). Per the Institute of Electrical and (a) Manual circuit breakers employ spring-
Electronics Engineers (IEEE), equipment rated up operated, stored-energy mechanisms for operation.
to 1000 volts AC is classed as low voltage. Equip- Release of the energy results in quick operation of
ment equal to or greater than 1000 volts but less the mechanism to open or close the contacts. Oper-
than 100,000 volts AC is classed as medium voltage. ating speed is not dependent on the speed or force
a. Low voltage. Major elements of low voltage used by the operator to store the energy.
switchgear are circuit breakers, potential trans- (b) Fast and positive action prevents unnec-
formers, current transformers, and control circuits, essary arcing between the movable and stationary
refer to paragraph 5-3. Related elements of the contacts. This results in longer contact and breaker
switchgear include the service entrance conductor, life.
main box, switches, indicator lights, and i nstru- (c) Manual stored-energy circuit breakers
ments . The service entrance conductor and main have springs which are charged (refer to the glos-
bus (sized as required) are typical heavy duty con- sary) by operation of the insulated handle. The
ductors used to carry heavy current loads. charging action energizes the spring prior to closing
b. Medium voltage. Medium voltage switchgear or opening of the circuit breaker. The spring, when
consists of major and related elements as in low fully charged, contains enough stored energy to pro-
voltage switchgear. Refer to paragraph 5-4 for de- vide at least one closing and one opening of the
tails. Construction of circuit breakers employed in circuit breaker. The charged spring provides quick
the two types of switchgear and the methods to and positive operation of the circuit breaker. Part of
accomplish breaker tripping are the primary differ- the stored energy, which is released during closing,
ences. The service entrance conductors and main may be used to charge the opening springs.
5-1
TM 5-685/NAVFAC MO-912

Figure 5-l. Typical arrangement of metal enclosed switchgear.

(d) Some manual breakers require several ate. Arcing and intermediate contacts are adjusted
up-down strokes to fully charge. The springs are to open after the main contacts open to reduce burn- _-
released on the final downward stroke. In either of ing or pitting of the main contacts.
the manual units, there is no motion of the contacts (i) A typical power sensor for an air circuit
until the springs are released. breaker precisely controls the breaker opening time
(e) Electrical quick-make/quick-break break- in response to a specified level of fault current. Most
ers are operated by a motor or solenoid. In small units function as overcurrent trip devices and con-
units, a solenoid is used to conserve space. In large sist of a solenoid tripper and solid-state compo-
sizes, an AC/DC motor is used to keep control-power nents. The solid-state components are part of the
requirements low (4 amps at 230 volts). power sensor and provide precise and sensitive trip
(f) When the solenoid is energized, the sole- signals.
noid charges the closing springs and drives the (2) Molded-c ase circuit breakers. Low current
mechanism past the central/neutral point in one and low energy power circuits are usually controlled
continuous motion. Motor-operated mechanisms au- by molded-case circuit breakers. The trip elements
tomatically charge the closing springs to a predeter- act directly to release the breaker latch when the
mined level. When a signal to close is delivered, the current exceeds the calibrated current magnitude.
springs are released and the breaker contacts are Typical time-current characteristic curves for
closed. The motor or solenoid does not aid in the molded-case circuit breakers are shown in figure
closing stroke; the springs supply all the closing 5-3.
power. There is sufficient stored-energy to close the (a) Thermal-magnetic circuit breakers have
contacts under short-circuit conditions. Energy for a thermal bi-metallic element for an inverse time-
opening the contacts is stored during the closing current relationship to protect against sustained
action. overloads. This type also has an instantaneous mag-
(g) A second set of springs opens the contacts netic trip element for short-circuit protection.
when the breaker receives a trip impulse or signal. (b) Magnetic trip-only circuit breakers have
The breaker can be operated manually for mainte- no thermal elements. This type has a magnetic trip-
nance by a detachable handle. ping arrangement to trip instantaneously, with no
(h) Circuit breakers usually have two or purposely introduced time delay, at currents equal
three sets of contacts: main; arcing; and intermedi- to, or above, the trip setting. These are used only for
5-2
TM 5-685/NAVFAC MO-912

450 VOLTS, 3PH 60 CPS


GENERATOR BUS

LEGEND
---.--.----.--- _
- AMMETER - FREOUENCY HETER VR - VOLTAGE REGULATOR
r;! - WATTMETER S$ - SYNCHROSCOPE PT - POTENTIAL TRANSFORMER
VM - VOLTMETER - TEMPERATURE METER CT - CURRENT TRANSFORMER
- GEN. CKT BREAKER B- GE. CKT BREAKER
QOV - GOVERNOR
F^u - FUSE

Figure 5-2. Typical switchgear control circuitry, one-line diagram.

short-circuit protection of motor branch circuits (1) Ratings. A PT is rated for the primary volt-
where motor overload or running protection is pro- age along with the turns (step down) ratio to secure
vided by other elements. 120 VAC across the secondary.
(c) Non-automatic circuit interrupters have (2) Application. The primary of potential trans-
no automatic overload or short circuit trip elements. formers is connected either line-to-line or line-to-
These are used for manual switching and isolation. neutral, and the current that flows through this
Other devices must be provided for short circuit and winding produces a flux in the core. Since the core
overload protection. links the primary and secondary windings, a volt-
b. Potential transformers. A potential trans- age is induced in the secondary circuit (see fig 5-4).
former (PT) is an accurately wound, low voltage loss The ratio of primary to secondary voltage is in pro-
instrument transformer having a fixed primary to portion to the number of turns in the primary and
secondary “step down” voltage ratio. The PT is secondary windings. This proportion produces 120
mounted in the high voltage enclosure and only the volts at the secondary terminals when rated voltage
low voltage leads from the secondary winding are is applied to the primary.
brought out to the metering and control panel. The (3) Dot convention. A dot convention is used in
PT isolates the high voltage primary from the me- figure 5-5. The dot convention makes use of a large
tering and control panel and from personnel. The dot placed at one end of each of the two coils which
step down ratio produces about 120 VAC across the are mutually coupled. A current entering the dotted
secondary when rated voltage is applied to the pri- terminal of one coil produces an open-circuit voltage
mary. This permits the use of standard low voltage between the terminals of the second coil. The volt-
meters (120 VAC full scale) for all high voltage cir- age measured with a positive voltage reference at
cuit metering and control. the dotted terminal of the second coil.
5-3
TM 5-685/NAVFAC MO-912

CURRENT IN AMPERES AT- ~3.8bJOLTS


1

09 z
08 -
0 7 uA
r
06 G

01

CURRENT IN AMPERES AT 13.8K VOLTS

Figure 5-3. Typical time-current characteristic curve.

c. Current transformers. A current transformer either a toroid (doughnut) winding with a primary
(CT) is an instrument transformer having low conductor wire passing through the “hole”, or a sec-
losses whose purpose is to provide a f’ixed primary tion of bus bar (primary) around which is wound the
to secondary step down current ratio. The primary secondary. The bus bar CT is inserted into the bus
to secondary current ratio is in inverse proportion to being measured. The CT ratio is selected to result in
the primary to secondary turns ratio. The secondary -
a five ampere secondary current when primary
winding thus has multiple turns. The CT is usually rated current is flowing (see fig 5-4).
5-4
TM 5-685/NAVFAC MO-912

POTENT I A L CURRENT
TRANSFORMER TRANSFORMER

LI D

V-VOLTMETER W-WATTMETER A-AMMETER

Figure 5-4. Instrument transformers, typical applications.

(1) Ratings. Toroidal CTs are rated for the size cuit. Never open a CT secondary while the primary
of the primary conductor diameter to be surrounded circuit is energized.
and the primary to secondary current (5A) ratio. d. Polarities. When connection secondaries of PTs
Bus bar type CTs are rated for the size of bus bar, and Cts to metering circuits the correct polarities of
primary voltage and the primary to secondary cur- all leads and connections must be in accordance
rent 5A) ratio. with the metering circuit design and the devices
(2) Application. The primary of a CT is either connected. Wrong polarity connections will give
the line conductor or a section of the line bus. The false readings and result in inaccurate data, dam-
secondary current, up to 5A, is directly proportional age and injury. All conductors and terminations
to the line current. The ratio of the primary to should carry identification that matches schemat-
secondary current is inversely proportional to the ics, diagrams and plans used for construction and
ratio of the primary turns to secondary turns. maintenance.
(3) Safety. A CT, in stepping down the current, e. Control circuits. Switchgear control circuits
also steps up voltage. The voltage across the second- provide control power for the starting circuit of the
ary is at a dangerously high level when the primary prime movers and the closing and tripping of the
is energized. The secondary of a CT must either be switchgear circuit breakers. Additionally, the con-
shorted or connected into the closed metering cir- trol circuits provide control power to operate the
5-5
TM 5-685/NAVFAC MO-912

various relays and indicating lights associated with


the control circuitry. The control circuits are classi-
fied as either AC or DC.
(1) ACcontrol circuits. AC control circuits usu- __
PRIMARY ally derive their power from the source side of the
circuit breaker being controlled. This procedure ap-
plies to main incoming line circuit breakers, genera-
tor circuit breakers, and feeder circuit breakers (see
fig 5-6). Depending on the system voltage, the con-
trol power can be taken directly from the main bus
since it can be connected through a control power
transformer.
(2) Tie break er control circuits. In systems us-
ing a tie breaker, the control power for the tie
breaker and the feeder breakers is supplied through
a throw-over scheme so control power is available if
either side of the tie breaker is energized (see fig
5-7). In applications that require synchronizing cir-
cuitry, the running and incoming control buses are
usually supplied via the potential transformers. The
transformer primaries are connected to both the
Figure 5-5. Current flow in instrument transformers. ‘Polarity” line side and the load side of the circuit breakers
marks show instantaneous flows. that are used for synchronizing. The transformer

MAIN INCOMING LINE GENERATOR


\ CONTROL
\ POWER
I TRANSFORMER
FUSE CONTROL POWER
I * TRANSFORMER

CONTROL
/\
MAIN ’
POWER
T
GE N E R A T O R > &
BUS BR E A K E R I

I F U S E ,

FEEDER
BREAKER
/
\ L O A D /’ LOAD

Figure 5-6. AC control circuits.


TM 5-685/NAVFAC MO-912

LOAD

Figure 5-7. AC control circuits with tie circuit breaker.

secondaries are connected to the proper control bus program that is built around equipment and system
through contacts on the synchronizing switch, or records and visual inspections. The program is de-
through contacts on certain auxiliary relays. The scribed in the manufacturer’s literature furnished
synchronizing switch would be used for manual op- with the components. If a problem develops, the
eration and the auxiliary relay would be used when user should perform general troubleshooting proce-
automatic synchronizing is provided. dures. The program includes appropriate analysis of
(3) DC control circuits. DC control circuits de- the records.
rive their power from a battery source consisting of (1) Record keeping. Equipment and system log
a bank of batteries and a battery charger that main- sheets are important and necessary functions of
tains the batteries at the proper charge. The battery record keeping. The log sheets must be specifically
bank can be rated at various levels ranging between developed to suit individual application (i.e., auxil-
24 volts and 125 volts DC. Those circuits that re- iary use).
quire a source of control power completely indepen- (2) Troublesh oo ting. Perform troubleshooting
dent of the power system are connected to the DC procedures when abnormal operation of the system
control bus. Examples of these are the prime mover or equipment is observed. Maintenance personnel
starting circuits, and in some cases, the trip circuits must then refer to records for interpretation and
for the circuit breakers when devices, other than comparison of performance data (i.e., log sheets).
the direct-acting overcurrent trip devices, are used. Comparisons of operation should be made under
Also, the closing circuits for the circuit breakers are equal or closely similar conditions of load and ambi-
sometimes connected to the DC control bus. ent temperature. The general scheme for trouble-
f. Service practices. Service practices for low volt- shooting is outlined in the following paragraphs and
age switchgear consist of a complete maintenance troubleshooting table.

5-7
TM 5-685/NAVFAC MO-912

(a) Use recognized industrial practices as the several times during the period, preferably under
general guide for servicing and refer to manufactur- load. If the breaker is operated by a relay or a
er’s literature. switch, it should be so operated at this time.
(b) The user should refer to manufacturer’s ( e ) Service for molded-case circuit breakers
literature for specific information on individual cir- consists of the following procedures. Inspect connec-
cuit breakers. tions for signs of arcing or overheating. Replace
(c) General service information for circuit faulty connectors and tighten all connections. Clean
breakers includes the following safety require- the connecting surfaces. Perform overload tripping
ments. Do not work on an energized breaker. Do not tests. Verify automatic opening of breaker. Verify
work on any part of a breaker with test couplers that the magnetic tripping feature is operating. Per-
engaged. Test couplers connect the breaker to the form circuit breaker overload tripping tests. Proper
control circuit during testing. Spring-charged action of the breaker tripping components is veri-
breaker mechanisms shall be serviced only by per- fied by selecting a percentage of breaker current
sonnel experienced in releasing the spring load in a rating (such as 300%) for testing. This overload is
controlled manner. Make operational tests and applied separately to each pole of the breaker to
checks on a breaker after maintenance, before it is determine how it will affect automatic opening of
returned to service. Do not work on a spring- the breaker. Refer to manufacturer’s test informa-
charged circuit breaker when it is in the charged tion. Turn the breaker on and off several times to
position. verify satisfactory mechanical operation.
(d) Switchgear needs exercise. If the circuit ( f ) Service for air circuit breakers consists of
breaker remains idle, either open or closed, for six the following procedure (see fig 5-8). Install the
months or more, it should be opened and closed safety pin to restrain the closing spring force. With

/
CONNECTED
ALL POWER CON-
NECTED (PR I MA R Y 8
CONTROL)

CONTROL POWER
STILL CONNECTED

--DISCONNECTED
ALL POWER DISCON-
NECTED

ry WITHDRAWN
BREAKER WITHDRAWN
READY FOR REMOVAL

--
Figure 5-8. Maintenance for typical low voltage switchgear with air circuit breakers.

5-8
TM 5-685/NAVFAC MO-912

the pin in place, the contacts will close slowly when Table 5-l. Low voltage circuit breaker
troubleshooting-Continued
the breaker is manually operated. Inspect connec-
tions for signs of arcing or overheating. Replace Note
faulty connectors and tighten all connections. Clean
Refer to manufacturer’s literature for specific information on
the connecting surfaces. An infrared (IR) survey is a
individual circuit breakers.
recommended inspection procedure. The IR survey
should be performed when the circuit breaker is Cause Remedy
under load and closed to detect overheating of con- FALSE TRIPPING
nections. Perform general troubleshooting of the Overcurrent pick-up too low Check application of overcurrent
breaker (refer to the following table) if a problem trip device
develops. If the trouble cannot be corrected, refer to Overcurrent time setting too short Check application of overcurrent
the manufacturer’s literature for specific informa- trip device
tion on individual breakers. Instrument transform-
Mechanical binding in over- Correct binding or replace over-
ers require no care other than keeping them dry condition current trip device current trip device
and clean. Refer to manufacturer’s literature if spe-
cific information is required. Information related to Captive thumbscrew on power sen- Adjust power sensor. Tighten
sor loose. Fail safe circuitry reverts thumbscrew on desired setting
control circuit components is provided in paragraph characteristics to minimum setting
5-3e of this chapter. and maximum time delay
Ground sensor coil improperly con- Check polarity of connections to
nec ted coil. Check continuity of shield
Table 5-l. Low voltage circuit breaker troubleshooting. and conductors connecting the ex-
ternal ground sensor coil
Note
FAILURE TO CLOSE AND LATCH
Refer to manufacturer’s literature for specific information on
Binding in attachments preventing Realign and adjust attachments
individual circuit breakers.
resetting of latch
Cause Remedy Latch out of adjustment Adjust latch
OVERHEATING Latch return spring too weak or Replace spring
Contacts not aligned Adjust contacts broken
- Contacts dirty, greasy, or coated Clean contacts Hardened or gummy lubricant Clean bearing and latch surfaces
with dark film
Safety pin left in push rod Remove safety pin
Contacts badly burned or pitted Replace contacts
Motor burned out Replace motor
Current-carrying surfaces dirty Clean surfaces of current-carrying
parts Faulty control circuit component Replace or adjust faulty device

Corrosive atmosphere Relocate or provide adequate en- BURNED MAIN CONTACTS


closure Improper contact sequence (main Increase arcing contact wipe Adjust
contacts not sufficiently parted contact opening sequence Refer to
Insufficient bus or cable capacity Increase capacity of bus or cable when arcing contacts part) opening. Refer to manufacturer’s
literature for contact maintenance
Bolts and nuts at terminal connec- Tighten, but do not exceed, elastic
and adjustment information. Also
tions not tight limit of bolts or fittings
refer to paragraph 5-3a( I )(,g)
Current in excess of breaker rating Check breaker applications or
Short-circuit current level above Requires system study and possible
modify circuit by decreasing load
interrupting rating of breaker replacement with breaker having
Inductive heating Correct bus or cable arrangement adequate interrupting capacity

FAILURE TO TRIP
Travel of tripping device does not Adjust or replace tripping device 5-4. Medium voltage elements.
provide positive release of tripping
latch a. Circuit breakers. Medium voltage switchgear
uses oil, air-blast, or vacuum circuit breakers. Usu-
Worn or damaged trip unit parts Replace trip unit
ally the circuit breakers have draw-out construction
Mechanical binding in overcurrent Correct binding condition or re- to permit removal of an individual breaker from the
trip device place overcurrent trip device
enclosure for inspection or maintenance without de-
Electrical connectors for power Tighten, connect, or replace electri- energizing the main bus. All of these circuit break-
sensor loose or open cal connectors ers can quickly interrupt and extinguish the electric
Loose or broken power sensor con- Tighten or re-connect tap coil tap arc that occurs between breaker contacts when the
nections connections contacts are separated.

5-9
TM 5-685/NAVFAC MO-912

(1) Oil circuit b reakers. When the contacts are high-pressure air is directed across the arc pushing
separated in oil, the interrupted voltage and cur- the arc against the splitter. The arc is broken at
rent can be greater as compared to contact separa- current zero and carried downstream.
--
tion in air at room temperature. (3) Vacuum circuit breakers. Vacuum arc inter-
(a) Arc interruption is better in oil than air ruption is the newest and quickest method of extin-
because the dielectric strength of oil is much greater guishing an electric arc. This type of breaker (see
than air. Also, the arc generates hydrogen gas from figure 5-11) is oil-less, fireproof and nearly mainte-
the oil (see fig 5-9). The gas is superior to air as a nance free. Service life is very long. Arc interruption
cooling medium. is very rapid, usually in the first current zero. High
(b) Usually the contacts and the arc are en- dielectric strength of a small vacuum gap contrib-
closed in a fiber arcing chamber, with exhaust ports utes to the rapid interruption of the arc. Short con-
on one side, to increase the capacity. tact travel permits the mechanism to part the con-
(2) Air circuit breakers. Arc extinction by high tacts much faster than for oil breakers.
pressure air blast is another method of quickly in- (4) Warning. Mechanical indication of “open”
terrupting and extinguishing electric arc. Cross- may not be true. Always make sure no voltage exists
blast type breakers are usually used in medium on load/line side before performing any work.
voltage switchgear. b. Potential transformers. A potential trans-
(a) A cross-blast breaker uses an arc chute former (PT) is an accurately wound, low voltage-loss
with one splitter (insulating fin) that functions as instrument transformer having a fixed primary to
an arc barrier (see fig 5-10). secondary “step down” voltage ratio. The PT is
(b) The arc is drawn between the upper and mounted in the high voltage enclosure and only the
lower electrodes. During interruption, a blast of low voltage leads from the secondary winding are

FIBER WALLS STATIONARY


FORMING ARCING CONTACT
CHAMBER \ I

EXHAUST

ARC
HYDROGEN

SPLITTERS

MOVING
CONTACT

Figure 5-9. Arc interruption in oil, diagram.


TM 5=685/NAVFAC MO-912

(2) Application. Refer to paragraph 5-3b(2) for


ORIFICE PLATE __I - application information .
c. Current transformers. A Current Transformer
I

(CT) is an instrument transformer having low


-

j -
HIGH AIR PRESSURE LOW AIR PRESSURE losses whose purpose is to provide a fixed primary
to secondary step down current ratio. The primary
AIR BLAST, to secondary current ratio is in inverse proportion to
the primary to secondary turns ratio. The secondary
winding thus has multiple turns. The CT is usually
either a toroid (doughnut) winding with primary
I conductor wire passing through the “hole” or a unit
UPSTREAM
ARCING
DOWNSTREAM
ARCING
section of bus bar (primary), around which is wound
ELECTRODE ELECTRODE the secondary, inserted into the bus run. The CT
ratio is selected to result in a five ampere secondary
current when primary rated current is flowing.
ORIFICE PLATE ___+
(1) Ratings. Current transformers are usually
rated at 5 amperes in the secondary circuit.
Figure 5-10. Air blast arc interrupter, diagram. (2) Application. Refer to paragraph 5-3c(2) ap-
plication information.
brought out to the metering and control panel. The d. Control circuits. Switchgear control circuits for
PT isolates the high voltage primary from the me- medium voltage are functionally similar to those
tering and control panel and from personnel. The used for low voltage systems. The control circuits
step down ratio produces about 120 VAC across the are similarly classified as either AC or DC.
secondary when rated voltage is applied to the pri- (1) AC control circuits. Refer to the description
mary. This permits the use of standard low voltage provided in paragraph 5-3e( 1).
meters (120 VAC full scale) for all high voltage cir- (2) DC control circuits. Refer to the description
cuit metering and control. provided in paragraph 5-3e( 3).
(1) Ratings. Potential transformers are usually e. Service practices. Service practices for medium
rated at 120 volts in the secondary circuit. voltage switchgear consist of a complete mainte-

Flexible insulating Electrical Vacuum


Metallic Vacuum Contacts
Bellows
Assembly

Metal-to-insulation Metal Lapor Eleckc Arcing Metal-tcLinsulation


Vacuum Seal Condensing Shield Region Vacuum Seal

Figure 5-11. Cross sectional view of vacuum arc interrupter:

5-11
TM 5-685/NAVFAC MO-912

nance program that is built around equipment, sys- not biodegradable, some restrictions to their use
tem records, and visual inspections. The program is apply. Silicone insulating liquid can be used as sub-
described in the manufacturer’s literature fur- stitute for PCBs when authorized by the Base engi-
.-
nished with the components. If a problem develops, neer. Special handling is required if PCBs are used
the user should perform general troubleshooting in any equipment. Refer to 40 CFR 761 for PCB
procedures. The program includes appropriate details. PCBs are powerful solvents. Handling and
analysis of the records. disposal information and special gloves are re-
(1) Record keeping. Equipment and system log quired. Check condition, alignment, and adjustment
sheets are important and necessary functions of of contacts. Verify that contacts surfaces bear with
record keeping. The log sheets must be specifically firm, even pressure. Use a fine file to dress rough
developed to suit individual applications (i.e., auxil- contacts; replace pitted or burned contacts. Wipe
iary use). clean all parts normally immersed in liquid, remove
(2) Troubleshooting. Perform troubleshoot- traces of carbon that remain after the liquid has
ing procedures when abnormal operation of the drained. Inspect insulating parts for cracks, or
system or equipment is observed. Maintenance per- other damage requiring replacement. Test the di-
sonnel must then refer to records for interpretation electric strength of the liquid, using a 0.1 inch gap
and comparison of performance data (i.e., log with 1.1 inch diameter disk terminals. If strength is
sheets). Comparisons of operation should be made less than 22 kV, remove and filter or replace with
under equal or closely similar conditions of load and new liquid having a dielectric strength of at least 26
ambient temperature. The general scheme for kV. Filter the liquid whenever inspection shows ex-
troubleshooting is outlined in the following para- cessive carbon, even if its dielectric strength is sat-
graphs. isfactory, because the carbon will deposit on insulat-
(a) Use recognized industrial practices as the ing surfaces decreasing the insulation strength.
general guide for servicing and refer to manufactur- Liquid samples should be taken in a large-mouthed
er’s literature. glass bottle that has been cleaned and dried with
(b) The user should refer to manufacturer’s benzene. Use a cork stopper with this bottle. Draw
literature for specific information on individual cir- test samples from the bottom of the tank after the
cuit breakers. liquid has settled. The samples should be from the
(c) General service information for circuit tank proper and not from the valve or drain pipe.
breakers includes the following safety require- Periodically remove the liquid from the tank and
ments. Do not work on an energized breaker. Do not wipe the inside of the tank, the tank linings, and
work on any part of a breaker with the test couplers barriers to remove carbon. Inspect breaker and op-
engaged. Test couplers connect the breaker to the erating mechanisms for loose hardware and missing
control circuit during testing. Maintenance closing or broken cotter pins, retaining rings, etc. Check
devices for switchgear are not suitable for closing in adjustments and readjust when necessary (refer to
on a live system. Speed in closing is as important as the manufacturer’s instruction book). Clean operat-
speed in opening. A wrench or other maintenance ing mechanism and lubricate as for air-magnetic
tool is not fast enough. Before working on the type breakers (refer to the manufacturer’s instruc-
switchgear enclosure, remove all draw-out devices tion book). Before replacing the tank, operate
such as circuit breakers and instrument transform- breaker slowly with maintenance closing device to
ers. Do not lay tools down on the equipment while verify there is no friction or binding to prevent or
working on it. It is too easy to forget a tool when slow down its operation; then, check the electrical
closing an enclosure. operation. Avoid operating the breaker any more
(d) Switchgear needs exercise. If the circuit than is necessary when testing it without liquid in
breaker remains idle, either open or closed, for six the tank. It is designed to operate in liquid and
months or more, it should be opened and closed mechanical damage can result from excessive op-
several times during the period, preferably under eration without it. When replacing the tank, fill to
load. If the breaker is operated by a relay or a the correct level with liquid, be sure the gaskets are
switch, it too should be operated at this time. undamaged and the tank nuts and flange nuts on
(e) Service circuit breakers using insulating gauges and valves are tightened properly to prevent
liquid require special handling. Elevate the breaker leakage.
on an inspection rack and untank it to expose the (f) Service air-blast type circuit breakers.
contacts. The insulating liquid usually used in cir- Circuit breakers should be serviced (tested, exer-
cuit breakers is mineral oil. Equipment using liq- cised, and calibrated) at intervals not to exceed two
-
uids containing polychlorinated biphenyls (PCBs) years (refer to AR 420-43). Withdraw the breaker
may still be in use. Since PCBs are carcinogenic and from its housing for maintenance. Circuit breakers
5-12
TM 5_685/NAVFAC MO-912

are designed to perform up to 5000 and 3000 opera- ment is not possible. The operating mechanism is
tions for 1200 ampere or 200 ampere breakers, re- similar to that used in other medium voltage circuit
spectively, without major overhaul. More frequent breakers, and the general outlines are the same for
servicing may be necessary if operating conditions maintenance work. The enclosures are similar. Fig-
are severe. Inspection and servicing should be per- ure 5-11 shows a breaker with the primary electri-
formed after every fault clearing operation. Refer to cal contacts exposed. The stationary contact is sol-
instructions provided by the manufacturer. Wipe idly mounted; the moving contact is mounted in the
insulating parts, including bushings and the inside enclosure with a bellows seal. Contact erosion is
of box barriers; clean off smoke and dust. Repair measured by the change in external shaft positions
moderate damage to bushing insulation by sanding after a period of use. Consult the manufacturer’s
smooth and refinishing with a clear insulating var- instruction book. High voltage applied during test-
nish. Inspect alignment and condition of movable ing may produce X-ray emission. Personnel per-
and stationary contacts. Check their adjustment as forming a hi-pot test must stay behind a protective
described in the manufacturer’s instruction book. To shield during testing. Condition of the vacuum is
check alignment, close the breaker with pieces of checked by a hi-pot test applied every maintenance
tissue and carbon paper between the contacts and period. Consult manufacturer’s instruction book for
examine the impression. Do not file butt-type con- test procedures. The contacts in a vacuum circuit
tacts. Contacts which have been roughened in ser- breaker cannot be cleaned, repaired or adjusted.
vice may carry current as well as smooth contacts. The vacuum bottle is usually replaced if the test
Remove large projections or “bubbles” caused by un- indicates a fault.
usual arcing, by filing. When filing to touch up, keep
the contacts in their original design; that is, if the 5-5. Transfer switches.
contact is a line type, keep the area of contact lin- During actual or threatened power failure, transfer
ear, and if ball or point-type, keep the ball or points switches are actuated to transfer critical electrical
shaped out. Check arc chutes for damage. Replace load circuits from the normal source of power to the
damaged parts. When arc chutes are removed, blow auxiliary (emergency) power source. When normal
out dust and loose particles. Clean silver-plated power is restored, the transfer switches either auto-
breaker primary disconnecting devices with alcohol matically retransfer their load circuits to the nor-
or silver polish (refer to the manufacturer’s instruc- mal supply or must be transferred manually. Volt-
tion book). Lubricate devices by applying a thin film age and frequency-sensing relays are provided to
of approved grease. Inspect breaker operating monitor each phase of the normal supply. The relays
mechanism for loose hardware and missing or bro- initiate load transfer when there is a change in
ken cotter pins, retaining rings, etc. Examine cam, voltage or frequency in any phase outside of prede-
latch and roller surfaces for damage or excessive termined limits. Additionally, the relays initiate
wear. Clean and relubricate operating mechanism retransfer of the load to the normal source as soon
(refer to the manufacturer’s instruction book). Lu- as voltage is restored in all the phases beyond the
bricate pins and bearings not disassembled. Lubri- predetermined pick-up value of the relay. A transfer
cate the ground or polished surfaces of cams, rollers, switch obtains its operating current from the source
latches and props, and of pins and bearings that are to which the load is being transferred.
removed for cleaning. Check breaker operating a. Types of transfer switches. There are two types
mechanism adjustments and readjust as described of transfer switches: electrically operated or manu-
in the manufacturer’s instruction book. If adjust- ally operated. Electrically operated transfer
ments cannot be made within specified tolerances, switches also come with an optional bypass func-
excessive wear and need for a complete overhaul is tion.
indicated. Check control device for freedom of op- ( 1) Electrically operated. An electrically oper-
eration. Replace contacts when badly worn or ated switch obtains its operating current from the
burned. Inspect breaker control wiring for tightness source to which the load is being transferred. A
of connections. After the breaker has been serviced, separate voltage supply is used in some systems.
operate it slowly with closing device to check ab- Electrically operated switches consist of three func-
sence of binding or friction and check that contacts tional elements: main contacts to connect and dis-
move to the fully-opened and fully-closed positions. connect the load to and from the sources of power;
Check electrical operation using either the test cabi- sensing circuits to constantly monitor the condition
net or test couplers. of the power source and provide the information
(g) Service vacuum circuit breakers. This necessary for switch and related circuit operation;
breaker has primary contacts enclosed in vacuum and transfer mechanism to make the transfer from
containers (flasks), and direct inspection or replace- source to source.
5-13
TM 5-685/NAVFAC MO-912

(a) Circuit breaker type. Circuit breaker (1) Automatic. Automatic transfer switches
transfer switches are mechanically held devices us- have voltage sensing relays for each phase. The
ing two circuit breakers. Usually the breaker han- sensing relays are connected to the normal power
dles are operated by a transfer mechanism which bus, behind the protecting devices.
provides double-throw switching action connecting (a) The transfer switch is connected to the
one circuit terminal to either of two others. The normal power source under normal conditions.
transfer mechanism is operated electrically by a When the sensing relays detect a sustained drop in
unidirectional gear motor (motor and integral the voltage of the normal power source, the relays
speed-reducing gearbox) or by dual motor operators will automatically start the auxiliary generator. The
with all parts in positive contact at all times. These transfer switch operates upon a sustained drop in
switches can also be operated manually and have voltage in any phase of the normal source (approxi-
provisions for disengaging the generator when nec- mately a 30 percent drop and delay of about two
essary. seconds) to start the auxiliary generator.
(b) Neutral position. Some transfer switches (b) When voltage and frequency of the auxil-
have a neutral position. However, the switch is me- iary generator are at rated values, and the normal
chanically and electrically interlocked so that a neu- power source is still below normal, the automatic
tral position is not possible during electrical opera- control will transfer the load to the emergency
tion. Also, load circuits cannot be connected by the source.
switch to normal and emergency sources simulta- (c) Upon return of normal power to within 10
neously whether the switch is operated electrically percent of rated voltage on all phases and after a
or manually. preset time delay, the switch automatically trans-
(c) Contactor type. Contactor type transfer fers the load to the normal source. Usually the aux-
switches have mechanically or electrically held
iliary generator will run unloaded for about five
contactors with a command load bus. The switches
minutes after the transfer, before it shuts down.
are mechanically and electrically interlocked so that
The controls automatically reset for the next emer-
a neutral position is not possible under normal elec-
gency start.
trical operation. Additionally, the load circuits can-
(d) Usually the controls of a power transfer
not be connected to normal and emergency sources
simultaneously. system have a test switch. This permits simulation
(2) Bypass function. An electrically operated of failure of the normal power source and test of
transfer switch can be provided with a bypass func- transfer switch operation.
tion. The bypass function manually transfers the (e) Power transfer indicators are provided in
power around the automatic transfer switch. The most automatic transfer systems to indicate the cur-
electrically operated switch can then be tested, re- rently used power source. Usually an amber light
moved, and repaired. The bypass function may or marked “Emergency Power” shows that the system
may not cause a momentary interruption to the load is on emergency power when illuminated. A white
depending upon the manufacturer. The bypass is light marked “Normal Power” shows that the sys-
purely a manual function, therefore, if the source to tem is receiving power from its normal source when
which the bypass is connected fails the bypass must illuminated.
be manually transferred to the alternate source. (2) Nonautomatic. In nonautomatic operation,
Bypass transfer switches are only used in the most an operator is needed to manually transfer to or
critical applications where the load is operational from the emergency power source. The operator can
continuously. usually make the transfer without opening an en-
(3) Manually operated. Manual transfer closure. The transfer is usually based on instrument
switches are mechanically held devices using two indications and is made by placing the transfer
circuit breakers operated by a handle. All parts are switch in the required emergency or normal posi-
in positive contact at all times. The switch is me- tion.
chanically interlocked; it is impossible for the load (a) Power transfer indicators are provided
circuits to be connected to normal and emergency for the operator. An amber light (Emergency Power)
sources simultaneously. Manually operated transfer shows that the system is on emergency power when
switches are available with single or dual operating illuminated. A white light (Normal Power) shows
handles. A common operating mechanism across the that the system is receiving power from its normal
two breakers mechanically connects and operates source when illuminated.
the breakers. (b) The operator is usually provided with an
b. Operation. Transfer switches have two operat- override switch which bypasses the automatic
ing modes: automatic and non-automatic. transfer controls. This feature permits indefinite
5-14
TM 5-685/NAVFAC MO-912

connection of the emergency power source regard- (2) Static voltage regulators. A static regulator
less of the condition of the normal power source. usually has a static voltage sensor instead of a
c. Service practices. Service practices for transfer voltage-regulating relay.
switches consist of a complete maintenance pro- (a) Operation. The voltage sensor output is
gram that is built around records and visual inspec- applied to a solid-state or magnetic amplifier and a
tions. The program includes appropriate analysis of discriminator circuit. Signals are thereby provided
these records. for changing alternator output to raise or lower the
(1) Record keeping. Equipment and system log voltage as required. The voltage zone between ini-
sheets are important and necessary functions of tiation of raising or lowering control action is called
record keeping. The log sheets must be specifically the voltage band. The band must be more than the
developed to suit auxiliary use. minimum correction obtainable through the regula-
(2) Troubleshooting. Use recognized industrial tor or regulator hunting will occur.
practices as the general guide for transfer switch (b) Accessories. Accessories include either
and systern troubleshooting. Troubleshooting of sys- thermal delay relays or a resistance capacitance
tem circuits that are not performing according to network to provide time delay for load trend correc-
specifications and to the required performance level tion. Time delay retards the signal until accumu-
should be accomplished as follows: refer to engi- lated time outside the voltage limit, less accumu-
neering data and drawings pertaining to the par- lated time inside the voltage limit, exceeds the time
ticular plant. delay setting.
(a) The user should refer to manufacturer’s (3) Static exciter regulators. A static exciter
literature for specific information on individual regulator supplies the alternator field with DC volt-
transfer switches. age obtained from a three-phase, full wave bridge
(b) Perform general troubleshooting of the rectifier.
transfer switch if a problem develops. Refer to the (a) Operation. A small part of the alterna-
manufacturer’s literature for specific information. tor’s output goes to the regulator which meters the
Usually, all control elements are renewable from rectified DC voltage back to exciter’s field windings.
the front of the switch without removing the switch The rectified DC voltage produces a 60 cycle ripple.
from its enclosures and without removing the main If the ripple gets into the field windings, an electri-
power cables. cal discharge from windings to shaft can occur. A
filter can be used to reduce ripple. The discharge is
5-6. Regulators. caused because copper in the field windings and the
A voltage regulator maintains the terminal voltage metal shaft act like the plates in a capacitor. This
of an alternator or generator at a predetermined action may result in shaft and bearing pitting and
value. Voltage is controlled by regulating the eventual bearing failure. A static exciter is a manu-
strength of the electromagnetic field produced in factured subassembly, assembled and wired at the
the alternator exciter. A voltage regulator automati- manufacturer’s plant, usually using one or more
cally overcomes voltage drop within the alternator silicon rectifiers to convert AC voltage to DC. The
by changing field excitation automatically as it var- subassembly usually includes a regulator and a fil-
ies with the load. ter. Refer to the manufacturer’s literature for test
a. Types of regulators. The types of voltage regu- and adjustment details.
lators are electromechanical, static voltage, and (b) Accessories. Accessories include either
static exciter. thermal delay relays or a resistance capacitance
(1) Electro
o -mechanical voltage regulators. network to provide time delay for load trend correc-
These regulators usually have a servo-control sys- tion (refer to para 5-6a(2)(b). A suppressor circuit or
tem with three principal elements. ripple filter is usually provided to bypass ripple to
(a) First is a voltage sensing device with a ground before it gets to the generator field.
voltage regulating relay. The device monitors the b. Service practices. Service practices for voltage
output voltage and sends a signal to the control regulators consist of a complete maintenance pro-
circuits. gram that is built around records and visual inspec-
(b) Second i s an amplifying section with or tions. The program includes appropriate analysis of
without time delay, which amplifies the voltage sig- these records.
nal. (1) Record keeping.Equipment and system log
(c) Third is a motor drive which responds to sheets are important and necessary functions of
the signal by moving a tap changer or induction record keeping. The log sheets must be specifically
regulator in a direction to correct the voltage. developed to suit auxiliary use.
5-15
TM 5-685/NAVFAC MO-912

(2) Troubleshooting. Use recognized industrial Table 5-2. Switchgear equipment


troubleshooting-Continued
practices as the general guide for servicing. Refer to
manufacturer’s literature for specific information Note
on individual voltage regulators. Troubleshooting
Refer to manufacturer’s li terature for specific information on
procedures include the following: individual equipment.
(a) Check voltage for compliance with manu-
facturer’s specifications.
(b) Check fo r 1 oose or insecure electrical con- RELAYS FAILING TO TRIP BREAKERS
nections. Contacts improperly adjusted Adjust contacts. verify proper wipe
(c) Check for correct setting, refer to manu-
facturer’s literature. Open or short circuit in relay con- Check to verify that voltage is ap-
(d) Check for unregulated voltage. Refer to nections plied and that current is passing
through relay in question
manufacturer’s literature.
(e) Check the enclosure. Should be weather Improper application of target and Verify proper tripping action of
holding coil target and holding coi IS
tight.
(f) Check motor for proper operation and Faulty or improperly adjusted tim- If timing device is of bellows or
loose connections. Clean and lubricate as required. ing devices oil-film type, clean and adjust. if of
induction-disk type, check for me-
Refer to manufacturer’s literature for details. chanical interference. Refer to
(g) Voltage regulators and associated equip- manufacturer’s literature
ment are normally mounted within switchgear NOISES DUE TO VIBRATING PARTS
equipment and are interconnected with different Loose bolts or nuts permitting ex- Tighten to proper torque value
components. The proper operation and trouble- cessive vibration
shooting of voltage regulator equipment can depend Loose laminations in cores of Tighten loose nuts or core clamps
on these different components. Perform the proce- transformers, reactors, etc. to proper torque value
dures in the following table:
CONNECTIONS OVERHEATING

Table 5-2. Switchgear equipment troubleshooting. Increase of current due to overload Increase the carrying capacity (in-
conditions crease the number or size of con-
Note ductors) Remove excess current
from circuit
Refer to manufacturer’s literature for specific information on
individual equipment. Connecting bolts and nuts not tight Tighten ail bolts and nuts to proper
torque value
Cause Remedy
FAILURE IN FUNCTION OF ALL INSTRUMENTS AND DEVICES
WATTHOUR METER INACCURATE HAVING POTENTIAL WINDINGS
Meter may be dirty or damaged Install new meter, return faulty Loose nuts, binding screws or bro- Tighten all loose connections to
meter to repair depot for repair and ken wire at terminals proper torque value or repair bro-
calibration ken wire circuits
Faulty wiring or connections Inspect and repair as necessary Blown fuse in potential transformer Renew blown fuses
circuit
WATTHOUR METER FAILS TO REGISTER
Blown potential transformer fuse, Renew blown fuses Check wiring Open circuit in potential trans- Repair open circuit and check en-
broken wires or other fault in con- and repair as required former primary or secondary cir- tire circuit for continuity and good
nections cuits condition
Wedge or block accidently left at Remove wedge or block Verify that BREAKER FAILS TO TRIP
time of test or inspection meter is in good operating condi- Mechanism binding or sticking Lubricate breaker mechanism; refer
tion caused by lack of lubrication to manufacturer’s instructions
DAMAGED CONTROL, INSTRUMENT TRANSFER SWITCH, Mechanism out of adjustment Adjust all mechanical devices,
OR TEST BLOCKS (toggles, stops, buffers, opening
Burned or pitted contacts Dress or clean burned contacts or springs, etc.) according to manu-
replace with new contacts if neces- facturer’s instructions
sary
Failure of latching device Examine surface of latch, replace
RELAYS FAILING TO TRIP BREAKERS latch if worn or corroded. Check
Improper setting Adjust setting to correspond with latch wipe, adjust according to
circuit conditions. Refer to manu- manufacturer’s instructions
facturer’s instructions
Damage trip coil Replace damaged coil
Dirty, corroded or tarnished con- Clean contact with knife or tile Do
tacts not use emery cloth or sand-paper

5-16
TM 5-685/NAVFAC MO-912

Table 5-2. Switchgear equipment (4) Frequency. Frequency of alternating cur-


troubleshooting-Continued rent is indicated on a frequency meter. The meter
Note scale is usually graduated in 50/60 Hertz.
(5) Speed. Rotational speed of the prime mover
Refer to manufacturer’s literature for specific information on is indicated by a tachometer in revolutions per
individual equipment.
minute (rpm). Generating systems covered herein
usually use an impulse tachometer, including the
inductor and eddy current types. These tachometers
use a magnetic pick-up to sense speed.
(6) Temperature. Several temperature values
Faulty connections (loose or bro- Repair faulty wiring, tighten all (including coolant, lubricating oil and exhaust) are
ken wire) in trip circuit binding screws to proper torque usually required to assure safe prime mover opera-
value tion. Each value is monitored by a sensing device
OIL CONTAMINATED with a remote indicator or thermometer. The sens-
Carbonization from too many op- Drain oil and filter, clean or re- ing device can be thermocouple or a combination of
erations place. Add fresh oil. Clean inside sensing bulb and capillary tube.
of tank and all internal parts of
(a) Thermocouple. A thermocouple consists of
breaker; refer to manufacturer’s
instructions a pair of electrical conductors, each of different
metal, which are joined at the end adjacent to the
Condensation due to atmospheric Same procedure as above temperature to be measured. A thermal emf is pro-
conditions
duced at the junction of the conductors. The other
Overheating Eliminate cause of overheating end of each conductor is connected to a voltmeter
which measures and indicates the thermal emf.
5-7. Instrumentation. (b) Sensing bulb and capillary tube. T h e
sensing bulb and capillary tube contain a specific
Switchgear instrumentation, based on the complex- amount of liquid or gas whose pressure varies with
ity of the complete system, may include all or any temperature. The variation appears on the ther-
combination of indicating, recording, and metering mometer and represents the temperature of coolant,
instruments. Potential and current transformers oil or exhaust.
are used to isolate instrument circuits from the (7) Pressure. Pressure in the prime mover is
power circuit. Usually, the secondary winding of indicated by sensing devices and remote gauges.
potential transformers is rated at 120 volts. Current Usually a bourdon tube is used. The variation ap-
transformer output is 5 amperes. pears on the gauge and represents lubricating oil or
a. Types of instrumentation. Instrumentation in- other pressure. Other pressure values may be
cludes indicating and recording types. shown on the system instrument panel depending
b. Application. Information related to instrument on the type of prime mover and the overall system
transformer application is covered in paragraphs requirements. These pressure values include start-
5-3b( 2) and 5-3c(2). ing air, turbo boost, scavenging air, exhaust mani-
(1) Voltage. Voltage values are indicated by a fold and fuel gas. Gauges or meters are used for
voltmeter. indication as required.
(2) Current. Current values are indicated by an (8) Fuel level. Various methods are used for
ammeter. fuel level measurement. Fuel in underground stor-
(3) Power. Power values are described as watts, age tanks can be measured by immersing a cali-
vars and power factor (refer to para 4-7e for addi- brated dip stick in the tank. For day tanks, a glass
tional information). sight-gauge or a float actuated gauge can be used to
(a) Watts. Watts or kilowatts (units of electric measure the quantity of liquid fuel, Remote indica-
power) are indicated by a wattmeter. tors using pneumatic, electric or hydraulic devices
(b) Vars. V a rs or kilovars (units of reactive are also used.
power) are obtained by multiplying effective value (9) Running time. The amount of time an aux-
of current, effective value of voltage and the sine of iliary generating system operates is a required part
the angular phase difference between current and of system record keeping. Time is usually recorded
voltage. on a digital measuring device or counter located on
(c) Power factor. Power factor, the ratio of the system instrument panel. Usually the counter is
active power to apparent power, is displayed on a used with electric or electronic circuitry. An electric
power factor meter. The meter scale is usually system usually has an AC synchronous motor that
graduated in percentage power factor. is geared to the counter. Accuracy of motor and
TM 5-685/NAVFAC MO-912

counter depends on the frequency of the generator stalled to protect generator stator windings from
output voltage. An electronic system also records internal shorts and overheating are sensitive to
operating time on a digital measuring device. This faults in the generator and do not respond to faults
system measures time by counting the number of outside the generator. These relays act rapidly to --
cycles produced by the frequency of the generator prevent damage to the generator and isolate the
output voltage. Counter indications are propor- generator from the system. Relay action includes
tional to frequency vs time. de-energizing the generator field winding. Protec-
tive relays are provided in systems when reverse
5-8. Relays. power flow occurs. Those relays operate on a succes-
Relays are used with the automatic controls for aux- sion of power reversals and current impulses to
iliary power generating systems. A relay responds to detect loss of synchronism. Protective relays include
electrical or other operating parameters and causes the following types:
an abrupt change in the control circuits when the (a) Overcurrent. Overcurrent relays function
measured values change. A relay consists of a sens- when current flow exceeds the normal or desired
ing element and a control element with contacts. value. Induction disk relays with time delay and
a. Types of relays. Relays used in switchgear in- cup type relays (without time delay) are known as
clude general purpose and protective types. electromechanical type relays. Solid state relays are
(1) General purpose. General purpose relays normally used on more recently installed equip-
function as part of regulation and verification de- ment.
vices throughout the system including the prime (b) Overvoltage. Overvoltage relays function
mover. when voltage exceeds the normal or desired value.
(a) Industrial. Portions of electrical systems Induction disk relays with time delay and cup type
are energized or de-energized under normal or ab- relays without time delay are used.
normal conditions by relays. Since the relays are (c) Undervoltage. Undervoltage relays func-
usually used with subsystems or equipment circuit tion when voltage is less than normal or desired
breakers, the overall operating plan must be electri- value. Induction disk relays with time delay may be
cally coordinated. Coordination is usually accom- used in a balanced position between minimum and
plished by designing the system circuitry to selec- maximum voltages.
tively initiate the opening or closing of the relays. (d) Reverse power. Reverse power relays
Relays constantly monitor the power system. function whenever power flows in the reverse direc- --
(b) Overload. 0 verload relays are used to tion from normal or desired. These relays detect loss
provide overload protection for the auxiliary motors. of synchronism.
When an overload condition occurs in any of the (e) Underfrequency. Underfrequency relays
three phases in which heaters are inserted, it will function whenever the desired frequency becomes
cause the relay to trip. less than normal value. This condition is usually
(c) Time delay. Relays employed for time de- the result of reduced prime mover speed and may be
lay purpose are usually solid-state type. Some pneu- caused by the prime mover governor or excess elec-
matic relays may still be in use. Pneumatic relays trical load.
utilize a bellows type arrangement to provide the (f) Differential. Differential relays function
time delay. They can be adjusted for time periods of due to the difference between two quantities of the
less than a second to several minutes. same kind such as, two currents or two voltages.
(d) Solid-state. Solid-state relays derive their Differential relays, usually used to detect stator
time delay from a combination of several electronic winding electrical failure, respond to current per-
components. They are also adjustable between frac- centage differences. Current or voltage transform-
tions of a second to several minutes. ers used in differential network should be in
(e) Voltage sensitive. Voltage sensitive relays matched sets. Percentage differential relays are
are used to sense an increase or decrease in a spe- also used to prevent relay operation for faults due to
cific voltage. They provide an output signal when current transformer ratio error outside the pro-
the voltages pass the preset level. tected zone. In this application, the overcurrent re-
(2) Protective relays. Protective relays detect, lay operates instantly when there is a bus short
isolate, and/or indicate abnormal electrical condi- circuit but will not operate if a current transformer
tions. The operation of circuit breakers or other secondary opens. The contacts of the two relays are
protective devices is initiated by relays as required. connected in series.
Some of the electrical hazards protected against are (g) Current balance. A current balance relay
short circuit, overcurrent, over or under voltage, circuit monitors two or more current circuits and ---
and phase or frequency irregularities. Relays in- provides an output if the difference between any
5-18
TM 5-685/NAVFAC MO-912

two exceeds the setting of the relay. The relay (j) Note that differential relays are usually
senses the difference between the current of one very sensitive devices that use polarized sensing
generator and the current of another generator or circuitry. Repeat the pickup test. Use the second
the average of all other generators. Relay output test for comparison with previous and future test
may be used to trip bus tie contactors and split a data. Refer to manufacturer’s instructions.
parallel system to remove an unbalance. c. Record keeping. Equipment and system log
(h) Ground fault protection. Ground fault sheets are important and necessary functions of
protection is usually provided by a ground sensor record keeping. The log sheets must be specifically
relay which measures the sum of currents in the developed to suit auxiliary use.
lines to the load in a three-phase system. Another d. Troubleshooting. Perform troubleshooting pro-
relay is sometimes added to the transformer cedures when abnormal operation of the system or
neutral-to-ground connection for backup. equipment is observed. Maintenance personnel
b. Testing of relays. Periodic testing of relays is must then refer to records for interpretation and
considered preventive maintenance. The preventive comparison of performance data, i.e., log sheets.
maintenance program is built around records and Comparisons of operation should be made under
visual inspections and includes analysis of the equal or closely similar conditions of load and ambi-
records. ent temperature. The general scheme for trouble-
(1) The frequency y of testing is dependent on shooting is outlined in the following table.
the variables involved i.e., type of relay, environ-
mental conditions, history, and experience. The am- Table 5-3. Relay troubleshooting.
bient operating temperature must be recorded.
Note
Most relays have draw-out construction so that a
relay can be separated from its enclosure. Discon- Refer to manufacturer’s literature for specific information on
nection for test or repair is usually not required. individual equipment.

(2) Checks and tests to be performed are deter- Cause Remedy


mined by the type of relay. The schedule for perfor-
MAGNET-OPERATED INSTANTANEOUS TYPE
mance of tests should comply with the requirements High Trip Action
of AR 420-43. Proceed as follows: Faulty coil Install coil with correct rating
(a) Inspect the relay cover before testing. Re-
Low Trip Action
move dust and other foreign matter to prevent it Shorted turns on high trip Test coil and replace with new coil
from entering the relay. Record the inspection re- if found defective
sults.
Mechanical binding; dirt, corrosion Clean parts
(b) Check relay for “flag” indication. Also,
check cover glass for fogging. If fogging is excessive, Assembled incorrectly See manufacturer’s instructions
investigate the cause. MAGNET-OPERATED INVERSE-TIME TYPE
(c) Check all connections for proper tight- Slow Action Trip
ness. If necessary, tighten to proper torque value. Fluid too heavy, vent too small, or Change fluid and open vent
(d) Check a rmature and connect gaps. Com- temperature too low slightly, regulate temperature
pare with previous measurements. Adjust gaps if Worn parts Replace and adjust
necessary and refer to manufacturer’s instructions. Fast Trip Action
(e) Check contacts for burned or eroded con- Worn, broken parts Replace and adjust
dition. Burnish if necessary and refer to manufac-
Fluid too light, vent too large or Change fluid to proper grade Close
turer’s instructions. temperature too high vent slightly or regulate tempera-
(f) Verify proper contact operation. Open or ture. Clean dashpots and refill with
close contacts to observe proper trip or reclose ac- fresh fluid or proper grade
tion and refer to manufacturer’s instructions. THERMAL TYPE
(g) Apply current or voltage to verify that Fails to Trip Causing Motor Burnout
pickup is within manufacturer’s tolerances. Wrong size heater Check rating with recommenda-
(h) Reduce th e current until the relay drops tions on instruction sheet
out or fully resets. Verify that there is no binding Mechanical binding; dirt, corrosion Clean and adjust
during operation and refer to manufacturer’s in-
Relay damaged by short circuit Replace relay
structions.
(i) Verify that related devices such as capaci- Motor and relay in different ambi- install motor and control near each
tors are functioning properly and refer to manufac- ent temperature other or make temperature uniform
for both
turer’s instructions.

5-19
TM 5-685/NAVFAC MO-912

Table 5-3. Relay troubleshooting-Continued tery. In addition, batteries provide power for
switchgear control and power to trip some circuit
Note
breakers. Most applications for auxiliary power use
Refer to manufacturer’s literature for specific information on some form of “wet” lead acid battery, however, some -__
individual equipment.
systems use “dry” nickel cadmium (nicad) batteries.
Cause Remedy Both types of batteries produce direct current re-
Trips at Too Low Temperature peatedly by chemical reactions. Batteries must be
Wrong heater Check rating with manufacturer’s recharged after each use to restore their power. Wet
instruction sheet cell batteries require scheduled maintenance. This
Assembled wrong See manufacturer’s instructions includes a visual inspection of all cells, a weekly
hydrometer reading of the sample cell, and monthly
Relay in high ambient temperature Install controls closer to each other
or make temperature uniform readings of floating voltage, water level, hydrom-
eter, and temperature of each cell. Cell connectors
Fails to Reset
must be kept. clean and tight to prevent heating due
Broken mechanism; worn parts; Replace broken parts, clean and
corrosion, dirt adjust. Install new relay to high resistance or voltage drop. Tops of cells must
be kept free of dirt or conductive materials. Charg-
ing area must be exhausted to positively prevent
5-9. Miscellaneous devices. hydrogen build up and explosion.
Miscellaneous devices include control switches, d. Surge capacitors. Surge absorbing capacitors
push buttons, indicating lights, batteries, surge ca- are sometime used, with or without lightning ar-
pacitors, lightning arresters, maintenance tools, resters, to modify the shape of the surge voltage
test equipment, and fuses. wave. These capacitors operate at voltages of 240,
a. Control switches and push buttons. Switchgear 480, 600 and higher for single or three-phase opera-
and related control panels contain complete controls tion. Capacitor banks, formed by individual units
for all functions of the auxiliary generator equip- connected in parallel, are sometimes used. Fuses
ment. Control for voltage regulation, phase adjust- and circuit breakers with time-current characteris-
ment, current compensation, engine operating pa- tics are used to prevent rupture of the capacitor
rameters as well as engine start, stop, and running case under severe conditions. Safety precautions
speed, battery charging and brightness or dimming must be observed when working on capacitors.
of indicator lights are usually provided. (1) Surge capacitors using polychlorinated
b. Indicating lights. White indicating lamps with biphenyls (PCBs) may still be in use. Refer to 40
colored caps are used to show breaker positions. CFR 761. Since PCBs are carcinogenic and are not
Green lights indicate open breakers, red lights indi- biodegradable, some restrictions to their use apply.
cated closed breakers. White lights, when used, are (2) Special handling is required if PCBs are
energized from potential transformers to indicate used in any equipment. PCBs are powerful solvents.
live circuits. Some stations include amber or orange Handling and disposal information and special
lights to indicate that the circuit has been tripped gloves are available in the base engineer’s office.
automatically. Low voltage lamps, connected in se- e. Lightning arresters. A lightning arrester (a
ries with appropriate resistors, are usually used to protective device) limits voltage caused by a light-
reduce lamp size and glare. Red and green lights ning strike and bypasses the related current surge
are usually wired so that they are energized to a ground system which absorbs most of the strike
through the trip coil of the breaker. An opening in energy. An overvoltage condition can also be caused
the trip coil circuit is indicated by a dark unlit lamp. by a fault in the electrical system.
Similar indicating lamps and colored caps are used (1) There are two general types of arrester
to indicate normal and abnormal conditions for designs, valve type and expulsion type. The valve
other control functions of the system. type has one or more sets of spark gaps (series
c. Batteries. Storage batteries and battery sys- connected) which establish spark-over voltage, in-
tems are frequently a part of an auxiliary power terrupt the flow of current, and prevent high
system. Batteries are used for prime mover crank- current flow. The expulsion type has an arc extin-
ing, or an uninterruptible power system. The bat- guishing chamber in series with the gaps to inter-
teries maintain a charge through the application of rupt the power frequency current which flows after
a “floating” battery charger. As the battery dis- the gaps have been sparked over. Design refine-
charges its energy the charger increases its charge ments include using oxide film coated components
rate by increasing the flow of current into the bat- and sealing the inner components in a chamber
tery. The converse is true as the battery reaches a filled with an inert gas. Aluminum cells are used in
full charge, a very small current flows into the bat- some units.
5-20
TM 5-685/NAVFAC MO-912

(2) Installed lightning arresters can retain a (9) Electrical analyzer: An instrument for mea-
lethal electric charge. Accordingly, lightning arrest- suring the various parameters of AC circuits. It
ers must be considered as loaded to full circuit po- consists of a voltmeter, ammeter, wattmeter, and
tential unless disconnected from the circuit and power factor meter. The analyzer also includes two
grounded. current transformers and switches necessary for
f. Special maintenance tools. Always use the use. It can be used for testing insulation.
proper tool for the job being done. Avoid the use of (10) Certification. Test equipment should have
improvised tools or tools in poor condition. Store valid calibration certification.
tools not in use properly. h. Fuses. Fuses detect circuit overload conditions
(1) Hand tools include the following: screw- and open when there is too much current flowing.
drivers, pliers, wrenches, wire insulation strippers, Fuses are the safety valves of the installation’s elec-
and wire cutters. trical system and provide the most economical type
(2) Powered hand tools include the following: of circuit protection.
hydraulic, pneumatic and electrical. Unless an elec- (1) Application. There are many types of fuses
trical tool is battery powered or double insulated, with various characteristics. Always verify that a
make sure the tool has a line cord with a grounded fuse, whether a new or replacement unit, is of the
conductor and polarized grounding plug. Make sure proper type and rating before installing. Never ar-
the receptacle to be used is properly grounded. bitrarily replace one type of fuse with another fuse
(3) Machine tools include grinding wheels and of the same physical size just because it fits the fuse
cutting tools. holder. The fuse used should have the correct cur-
g. Test equipment. Before using any test equip- rent and voltage ratings, proper time delay and
ment make sure that it has valid calibration certifi- current limiting characteristics and an adequate in-
cation. Test equipment required for switchgear terrupting rating to protect the circuit and its com-
maintenance usually includes many or all of the ponents. Fuse holders should never be altered or
following items. forced to accept fuses which do not fit.
(1) Multim eter. The multimeter is sometimes (2) Construction. A fuse consists of two main
called a volt-ohm-milliammeter or VOM. It is a parts: the fusible link and the enclosing housing or
single test instrument with a number of different body. The link is a metallic alloy that melts when
ranges for measuring voltage, current, and resis- excessive current flows through it, thereby breaking
tance. the circuit. When the current heats the alloy to its
(2) Voltmeter. An instrument used for measur- melting point, the link breaks and an arc forms.
ing voltage. Its scale indicates microvolts, millivolts, Melting continues rapidly until the resultant gap is
volts or kilovolts. too wide for the arc to span. A fuse usually can carry
(3) Voltamm et er.. An instrument used as either a 100 percent load indefinitely and will blow in a
a voltmeter or an ammeter. specified time at 150 percent overload. The follow-
(4) Ohmmeter.. An instrument used for measur- ing fuse types are usually used.
ing resistance. It consists of a DC milliammeter, a (a) Current limiting fuses. Current limiting
DC source, and a resistor network. fuses are used where necessary to limit the amount
(5) Ammeter. An instrument that measures the of fault energy flowing through a fuse to the circuit.
amount of current in amperes. Its meter shows cur- A fuse must clear a fault in less than l/2 cycle of the
rent value in microamperes, milliamperes, or fault current sine wave to be considered a current
kiloamperes. limiting fuse. If the fault current is allowed to flow
(6) Frequency meter. An instrument for mea- for % cycle or more, the maximum (peak) fault cur-
suring the frequency of an alternating current. Its rent is passed through the fuse. A current limiting
scale shows Hertz (cycles per second), kiloHertz fuse must act quickly to limit the energy let through
(kilocycles), or megaHertz (megacycles). the fuse to the protected circuit. The total clearing
(7) Wattmet er.. An instrument for measuring time of a fuse is made up of two components; the
electric power. Its scale is usually graduated in melting time, and the arcing time. The fault current
watts or kilowatts. reaches maximum at the conclusion of the melting
(8) Megohmmeter. A device that is a high range time, much less than l/4 cycle. An arc is established
ohmmeter, sometimes referred to as a megger. It inside the fuse at the conclusion of the melting time.
consists of a hand driven, motor driven, or battery The arc presents a high resistance to the flow of
driven generator as the DC source, and a meter. It fault current and the current decays to zero, clear-
is used to measure insulation resistance and other ing the fault. Whenever possible de-energize the
high resistance. It can be used to check for continu- fuse-holder circuit before removing or installing a
ity, grounds, and short circuits. fuse.
5-21
TM 5-685/NAVFAC MO-912

(b) Metal-en cZ osed fuse. Fuse enclosed in an sion of gases during operation. A dropout fea-
oil filled metal housing and used (up to 7,500 volts) ture that automatically disengages the fuse when it
for protecting transformer banks and other distri- operates may be used. These fuses usually have
bution elements. Refer to the manufacturer’s litera- seals to keep moisture out of the interrupting cham-
ture for details. ber. Refer to manufacturer’s literature for instruc-
(c) Glass-enclosed fuse. Fuse enclosed in a tions.
glass tube filled with arc quenching liquid. Carbon ( f ) Replace fuse holders and clips which
tetrachloride is the liquid frequently used. Refer to are worn or make poor contact. Remove oxidation
the manufacturer’s literature for details. and corrosion from fuses, holders and clips. Deter-
(d) Expilsion fuse. Fuse enclosed in a fiber mine the causes of overheating and correct as re-
tube filled with dry (powdered) boric acid. When the quired.
fuse element blows, the boric acid produces a gas i. Synchroscope. A synchroscope, usually in-
which aids in promptly deionizing the arc. Used on stalled on a switchgear control panel, is used to
circuits up to 138 kV. Refer to the manufacturer’s determine the phase difference or degree of syn-
literature for details. chronism of two alternating current quantities or
(3) Checks and examinations. Examine fuse two generators. The synchronism always indicates
terminals and holders for discoloration caused by the condition of the incoming machine with respect
heat from poor contact and/or corrosion. Checks to to the bus. If the frequency of the incoming machine
be performed are determined by the type of fuse and is higher than the bus frequency, the synchroscope
fuse holder, proceed as follows: point revolves in the “fast” direction. If the fre-
(a) Inspect fuse and fuse holder contact sur- quency of the incoming machine is lower than the
faces for pitting, burning, alignment, and spring bus frequency, the synchroscope pointer revolves in
pressure. Badly pitted or burned components must the “slow” direction. If the pointer stops at a posi-
be replaced. tion other than 0 degrees, it indicates that the in-
(b) Examine the fuse unit, and renewable el- coming machine is at the same frequency as the bus
ement if the fuse type is used, for corrosion. Check but out of phase. Correct the phase error by adjust-
for signs of discharge tracking on the fuse. Replace ing the prime mover governor of the incoming ma-
components that show deterioration. chine for higher speed. The synchroscope pointer
(c) Verify that all attaching parts are in- should revolve slowly in the “fast” direction. The
stalled and tightened to proper torque value. machines are paralleled when the pointer reaches
(d) Check fu se tubes made of fiber or other the 0 degree position while traveling in the “fast”
organic material. Refinish the fuse tube as required. direction. When paralleled, the pointer will stay at 0
Refer to manufacturer’s literature. degrees. Refer to manufacturer’s literature for spe-
(e) Check vented expulsion fuses. Some fuses cific operation and inspection information on indi-
may have condensers or mufflers to restrict expul- vidual equipment.

5-22
TM 5-685/NAVFAC MO-912

CHAPTER 6
OPERATING PROCEDURES
-\
6-1. Requirements. the normal power source, the sensing devices are
A successfully operating auxiliary power generating activated and initiate a starting signal to the prime
system has several requirements. First, the equip- mover. An alarm circuit is also initiated at this time
ment in the system must be selected with ease of to alert the operator that normal power has been
operation and maintenance as prime consider- lost and the emergency unit has started. As the
ations. Second, the equipment must be installed by prime mover approaches rated speed, excitation is
competent personnel. automatically applied to the generator. The power
a. Adequate records must be kept during instal- plant will then remain in this condition, i.e., rated
lation and operational shakedown so that any fu- speed and voltage, until the operator closes the cir-
ture modifications can be implemented with mini- cuit breaker connecting the emergency generator to
mal research. Third, the operating personnel must the load. If the station has more than one generator,
be thoroughly trained in proper operating proce- and the load requires more than one generator, the
dures. Training must include performance of main- operator must initiate the synchronizing circuitry.
tenance as well as operation. Fourth, a detailed Using the techniques provided in paragraphs 6-5
record keeping system must be instituted. and 6-6, the operator must parallel the second gen-
b. The record keeping system must include a li- erator with the first. If additional generators are
brary of the various equipment manufacturers’ in- required, they must be added to the system in the
structions, operating log sheets, routine mainte- same manner. The operator can then adjust the
nance instructions, maintenance log sheets, and
governors and excitation controls to obtain the de-
piping and electrical drawings. The records should
sired load division and reactive power division be-
be assembled in binders or folders and stored in the
tween generators.
installation’s engineering office for availability and
c. The automatic mode is similar to the semi-
safekeeping.
automatic mode up to the point that the unit
L&_- 6-2. Attended stations. reaches rated speed and voltage. When the speed
a. Attended stations have one or more operators and voltage have stabilized, if the unit is picking up
on duty around the clock or for a portion of the day a completely dead plant, a closing signal is initiated
if the plant is not used full time. Plants that have to the circuit breaker. The circuit breaker energizes
an operator on duty only for a portion of the day the desired loads. If the load demands more than
sometimes require an operator’s presence during one unit, as the second unit reaches its operating
the entire period that the plant is supplying power speed and voltage, automatic synchronizing cir-
to the system. Attended stations can be operated in cuitry is enabled. The speed of the incoming unit
a manual mode, a semi-automatic mode, or an au- will be adjusted automatically, and when the syn-
tomatic mode. If the plant is manned at all times, chronizing relay is satisfied that the conditions are
the manual or semi-automatic mode is usually em- correct, a closing signal to the circuit breaker for the
ployed. In the manual mode, the operator has com- second unit will be sent. If additional units are
plete control of the power plant and would start the needed, the automatic synchronizing circuitry will
prime mover, bring it to operating speed, apply ex- be switched as the units become available. Once
citation to the generator, and close the circuit normal power is again available, the procedure for
breaker to pick up the station load. When parallel- returning the load to the normal bus is usually done
ing with another generator, the operator must per- in the manual mode. Installations that permit par-
form the paralleling procedures described in para- alleling with the electric utility system can
graph 6-6. If paralleling with the electric utility retransfer without an interruption of power. If par-
system is desired, approval must be obtained from alleling is not permitted, there will be a momentary
the utility and the need for special relaying, such as outage when the switching is performed. Some in-
reverse power relays, must be determined. The pro- stallations are designed with an automatic
cedures for parallel utility operation are described retransfer to normal power. However, these are usu-
in paragraph 6-5. ally the smaller-rated units that use a transfer
b. In the semi-automatic mode, sensing devices switch arrangement rather than circuit breakers for
‘L-- monitor the normal source of power. Upon a loss of switching loads.

6-1
TM 5-685/NAVFAC MO-912

6-3.. Unattended stations. load, readings should be taken according to the op-
Unattended stations operate without an operator in erating log developed for that station. When the
attendance. Their operation is the same as an at- unit is no longer required and the load has been
tended station used in the automatic mode. removed, operate the engine at no load, or at some --
preset idle speed to allow the engine to cool gradu-
6-4. Nonparalleled stations. ally. When the cooling period has expired, shut the
a. Nonparalleled stations are those stations that engine down. Cooling periods vary for different
do not have provisions for connecting the emergency prime movers. Refer to manufacturer’s instructions.
generator bus to the commercial bus. It also applies Stop the auxiliaries that do not stop automatically.
to a station that has a tie breaker between two Make an inspection of the unit, looking for any
incoming lines that, because of electric utility regu- unusual conditions.
lations, cannot be connected together. Electrical in- e. It is essential that each power generator have
terlocks are used to prevent an unwanted parallel- a complete set of standard operating procedures.
ing from occurring. These interlocks usually consist The procedures include an up-to-date one-line dia-
of two circuit breakers electrically connected. The gram of the electrical system showing the genera-
arrangement is such that only one circuit breaker tors and the associated switchgear components (see
can be in the closed position at a time, thus prevent- fig 6-l). Notes and legends are usually included
ing paralleling. with the diagram.
b. In some arrangements, mechanical interlocks
AM Ammeter AS Ammeter Switch
may also be provided. A mechanical interlock is a VS Voltmeter Switch
VA4 Voltmeter
device that physically prevents both circuit break- WM Wutt-hour Meter WHDM Wutt-hour Demand Meter
ers from being closed at the same time. This method CPT Control Power Transformer VAR Volt-Ampere Meter
also prevents paralleling from occurring. CT Current Transformer PT Potential Transformer
c. Immediately before starting the prime movers, G1 ,G2 Generators FU Fuse
make a thorough inspection to insure that the fol- f. Before the unit is started an inspection should
lowing is in order. Verify that engine generator is be made. This can be done in conjunction with the
not set to operate in a semi-automatic or automatic inspection of the prime mover. Look for any mate-
starting mode during prime mover inspections. If rial or loose parts that could be drawn into the
not, extreme caution should be used. Unexpected generator. Make sure that the air flow will not be ---
start of prime mover while inspecting can lead to restricted either on the intake or exhaust.
severe injury or death. Check for leaks in the lubri- g. When the prime mover has the generator at
cating system, the fuel system, and the cooling sys- operating speed, excitation can be applied. Adjust
tem. If any of the auxiliaries are belt-driven, check the voltage regulator until the generator is at rated
for tightness of the belts. Check for proper levels of voltage. Adjust the governor control for the prime
oil, water and fuel. Look for tools or other loose mover so that the generator is at rated frequency.
objects, such as rags, that may have been left in the Close the main circuit breaker connecting the gen-
area, and remove. If air pressure is a part of the erator to the load. If necessary adjust the voltage
starting system, make sure the air pressure is at control for rated voltage and the governor control
the correct value. Verify that none of the intake air for rated frequency. Readings of various parameters
vents or exhaust ports are blocked. Start auxiliary are taken according to the operating log for that
pumps (lube oil, fuel or water) that are necessary station. Care must be taken so that the generator is
prior to running the unit. operated at or below its nameplate rating. After the
d. When the preparations for starting have been unit has been shut down, a visual inspection similar
completed, a start signal is given to the prime to that performed prior to startup can be performed.
mover. The engine (prime mover) should start to h. Proper operation of the switchgear requires a
rotate and, under control of the governor, accelerate knowledge of the standard operating procedures
to idling speed. Once the speed has stabilized, read and the familiarity with the one-line diagram of the
the pressure and temperature gauges to make sure electrical system. It requires some knowledge of the
that normal pressure and temperatures are being various protective relays and other devices associ-
maintained. Listen to any unusual noises. Shut the ated with the system. The operator must be able to
engine down if any unusual pressures or tempera- recognize an impending problem by observing the
tures are observed, or if unusual noises are heard. meters or other indicators. The operator can then
Be familiar with the engine manufacturer’s litera- take proper action. The operator must be able to
ture for information on acceptable pressures and perform some basic troubleshooting and mainte-
temperatures. Once the unit has been placed under nance.
s3ItlvIlIxnV
NOIlVlS
2 'ON sna ABOZ/OZI-A2 8'CI ULJ I 'ON SW
0
UV
OOS-B-Cl.-WV
TM 5-685/NAVFAC MO-912

6-5. Paralleled with the electric utility system. tive load (vars) can be controlled by adjusting the
a. Stations that can be paralleled with electric voltage control. To remove load from the generator,
utility systems have the same basic characteristics reduce the load by decreasing the governor control
as those discussed in paragraph 6-2. They have while observing the kW meter for the generator.
additional features including synchronizing cir- When the kW meter indicates zero, open the gen-
cuitry and, in the case of the unattended station, an erator circuit breaker. The load will now be trans-
automatic mode. ferred to the electric utility bus. The prime mover
b. The prime movers in these stations can be can then be shut down by following normal proce-
operated in the manual or automatic mode. Opera- dures.
tion in the manual mode is discussed in paragraph
6-2a. In the automatic mode, relays in the 6-6. Paralleled with other generating units.
switchgear will sense the loss of commercial power a. Stations that have two or more generators that
and provide a starting signal to the prime mover. It can be operated in parallel have the same basic
will then accelerate under control of the governor to characteristics as previously discussed in para-
the operating speed. The remainder of the prime graphs 6-2 and 6-3. In addition, they may have
mover operation is as previously discussed. automatic synchronizing circuitry and also droop
c. This discussion is the same as paragraph 6-4d circuits for the voltage regulators. The automatic
with the exception that if the station is in auto- synchronizing circuitry includes speed-matching re-
matic, excitation will be applied by the automatic lays, voltage-matching relays, and automatic syn-
circuitry. Also, in automatic the main circuit chronizing relays. These relays function when the
breaker will close automatically, provided the in-
station is in the automatic mode and when two or
coming line circuit breaker is open.
more AC sources are in agreement within specified
d. The comments regarding proper switchgear
limits of phase angle and frequency. The voltage
operation as noted in paragraph 6-4h pertain to
regulator droop circuits are energized when two or
paralleling with the utility system. In addition, this
type of system requires paralleling circuitry which more generators are operated in parallel. Their pur-
is part of the switchgear. It includes one or more pose is to prevent the undesirable condition of cir-
synchronizing switches, a synchroscope, synchroniz- culating currents between generators.
ing lights, incoming voltmeter, incoming frequency b. Parallel operation of generators with regula- -
meter, running voltmeter, and a running frequency tors is accomplished by appropriate cross-current
meter. The synchronizing circuitry is energized by compensation. The method employs an equalizing
turning the synchronizing switch on. reactor or compensator which adds a small voltage,
e. The synchroscope indicates the condition of the proportional to the reactive current delivered by the
incoming machine with respect to the bus. If the generator, to the voltage delivered by the potential
frequency of the incoming machine is higher than transformers. This gives a slight droop to the volt-
that of the bus, the synchroscope pointer will re- age held by the regulator on reactive loads and
volve in a clockwise or “fast” direction. The operator divides reactive currents in proportion to load cur-
should adjust the governor control of the incoming rents. Differential compensation is used when line-
prime mover until the synchroscope pointer is re- droop compensators are installed to automatically
volving slowly in the “fast” direction. The machines increase the voltage as the load increases. With this
should be paralleled by closing the breaker of the connection, all the equalizing reactors or compensa-
incoming generator when the pointer reaches 12 tors are connected in series. There is no current flow
o’clock. Because there is a slight lag in the breaker in the equalizing reactors under balanced load con-
or switching mechanism, it is good practice to start ditions. If the load is unbalanced, the currents flow
the breaker closing operation at about the 11:30 through the regulators to decrease the excitation of
position or slightly before the pointer reaches 12 the generator carrying excessive reactive currents.
o’clock. This increases the excitation of the generator carry-
f.: Synchronizing lamps provide a means of check- ing low reactive current.
ing the synchroscope for proper operation. As the
pointer revolves, the lamps go alternately bright 6-7. Operational testing.
and dark in unison. Both lamps must be dark as the a. Emergency generator power units must be op-
pointer passes 12 o’clock or the synchroscope is de- erated under load conditions periodically to insure
fective. their reliability. The period for this exercising will
g. Now that the generator is paralleled with the vary from station to station. It is important that -___
electric utility system, the load (kW) can be con- accurate logs be kept of the conditions encountered
trolled by adjusting the governor control. The reac- during the exercising.
6-4
TM 5-685/NAVFAC MO-912

b. It is suggested that the manufacturer of the the electric utility system another method is used.
auxiliary power unit be consulted to determine the After paralleling, the load on the generator can be
time intervals in which the auxiliary power unit controlled by adjusting the governor control.
should be exercised and the length of each exercise. d. In addition to exercising the units, it is also
National and local codes may enter into this consid- desirable to periodically perform an operational
, eration. test. This test is accomplished by opening the cir-
c. The procedures used for exercising the units cuit breaker from the electric utility and verify-
will also vary from station to station. The most ing that the necessary relays and contactors ener-
desirable condition is to use the actual load. How- gize such that the emergency generator breaker
ever, this is not always possible and in these cases a closes and starts the auxiliary power generating
load bank can be used. A load bank is generally a system. Performance of the test simulates a loss of
portable set of resistors that allows a generator to commercial power. The frequency of this test is de-
be tested under load by disconnecting the generator pendent on the nature of the load, i.e., critical or
from the actual load and connecting it to the load non critical, but is usually performed on a monthly
bank. In those stations th at permit paralleling with basis.

6-5
TM 5-685/NAVFAC MO-912

CHAPTER 7
ROUTINE MAINTENANCE

7-1. Instructions. station log sheets, related records, and the manu-
a. Manufacturers provide specific instructions for facturer’s recommendations.
the use and care of each of their products. Their (2) Checklist.
instructions are the result of wide experience ob- (a) Values. Check valve operation.
tained under varying conditions and should be fol- (b) Fuel injection nozzles. Check fuel injec-
lowed closely. Maintenance personnel should always tion nozzles for secure mounting and connections
check equipment first for signs of physical damage each time the engine is shut down. Torque down the
before performing any other checks. nozzles according to the manufacturer’s instruc-
b. Routine maintenance instructions consist of tions.
scheduled inspections of prime movers, generators (c) Starting system. Check the general condi-
and exciters, and switchgear. When a need for ser- tion of the air compressor, air lines, and valves,
vice or repair is indicated, refer to the manufactur- when applicable. Briefly pop open the system’s
er’s literature for specific information. Service safety valve weekly. Check for proper operation. Re-
records of the auxiliary power systems are filed in fer to manufacturer’s instructions for details.
the installation’s engineering office. (d) Governor alarms and instruments. Check
c. Maintenance information provided in this operation of governor alarms and instruments. Re-
manual supplements the manufacturer’s instruc- fer to manufacturer’s instructions‘
tions but does not supersede them. Checklists and (e) Pressure gauges. Check pressure gauges
schedules furnished herein are intended as guides and clean exposed indicating elements. Refer to
for operators and service personnel. manufacturer’s instructions.
d. Since auxiliary power systems are operated (f) Intake and exhaust systems. Check air fil-
intermittently, the usual time frames for routine ters and engine exhaust. A smoking exhaust indi-
I--
maintenance such as weekly, monthly, quarterly, cates incorrect adjustments. Clean air filters as nec-
annually may not apply. Accordingly, “short-term” is essary.
used for tasks to be performed less frequently. Ex- (g) Exhaust Lines. Clean and inspect exhaust
ceptions are noted in the manufacturer’s manual. lines. On two-cycle engines, remove carbon from
e. Electrical systems acceptance tests are func- exhaust ports and clean thermocouples. Refer to
tional tests to verify the proper interaction on all manufacturer’s instructions for frequency of checks.
sensing, processing, and action electrical devices. It (h) Evaporative cooling. Refer to manufac-
is critical that these tests be performed on standby turer’s instructions for cooling tower maintenance.
generator power systems to ascertain the safe and Inspect and oil fanshaft bearings, oil damper bear-
operational reliability of a system. A system must be ings and linkage. Inspect spray nozzles; clean as
tested as a united series of devices in addition to the necessary. Clean pump suction screen. Clean sump
testing of individual components. For systems that pan. Inspect cooling coil. If scale has formed, circu-
include auto-start, auto-transfer, and/or auto-
late cleaning solution. Do not operate fan while
synchronizing equipment, every six months utility
cleaning coil. Check belts for condition and proper
electrical power should be removed (open main cir-
tension. Refer to manufacturer’s instructions.
cuit breaker) from a building, or part of the facility
(i) Fuel oil system. Clean fuel oil strainers as
that is supplied electrical power by commercial
power/generation combination to ascertain that the required by operating conditions. Check the system
system will operate under abnormal conditions. components for clean condition. Refer to manufac-
turer’s recommendations.
7-2. Prime mover maintenance. (j) Fuel filters and centrifuges. Check fuel oil
Routine maintenance instructions for prime movers filters and centrifuges. Check fuel oil system for
consist of short- and long-term checklists for diesel leaks and correct as required. Refer to manufactur-
and gas turbine engines. er’s instructions.
a. Short-term (diesels). Short-term checklist for (k) Lubricating systems. Check mechanical
‘L-- diesel engines. lubrication hourly during operation. Oil all hand
(1) General comments. Before performing any lubrication points, following manufacturer’s in-
tasks required by the following checklist, review the structions. Correct leaks.
7-1
TM 5-685/NAVFAC MO-912

(l) Sight-feed Lubricators. Clean sight-feed (d) Camshaft and drive. Check and adjust
lubricating oil strainers as necessary. Check for ad- gears and/or timing chain. Refer to manufacturer’s
equate lubricant supply. instructions.
(m) Lubricating oil filters. Check lubricating (e) Camshaft bearings. Inspect and adjust
oil filters. Clean and replace filter elements as nec- camshaft bearing clearances. Refer to manufactur-
essary. er’s instructions.
(n) Piston assembly and connecting rods. On (f) Fuel injection nozzle inspection. A f t e r
two-cycle engines, remove upper handhole inspec- 2000 hours of use, remove and check nozzles in the
tion cover from side of engine immediately after the test stand. Service and adjust nozzles following
engine is shut down, and inspect the piston for manufacturer’s instruction.
proper lubrication. (g) Fuel injection pumps. Inspect fuel injec-
(o) Cylinders and cylinder heads. Use com- tion pumps for secure mounting, cleanliness, and
pressed air to blow out indicator connections. Clean proper operation.
indicators and install. Refer to manufacturer’s in- (h) Fuel injection pump inspection. Disas-
structions. semble and recondition all injection pump nozzles
(p) Crankshaft, crankpin and main bearings. after 2000 hours of use. Repair or replace worn or
Remove crankcase covers immediately after engine damaged parts. Reassemble and adjust, following
is shut down. Check main and crankpin bearings for the manufacturer’s instructions.
proper lubrication. Check bearing temperatures for (i) Air Lines. Drain water from air lines and
excessive heat by hand-touch. Refer to manufactur- tank monthly or as necessary. Drain valves are usu-
er’s instructions for frequency of checks. ally located at the lowest point(s) in the air feed
(q) Gauges and instruments. Verify that system.
gauges and instruments have up-to-date calibration (j) Air valves. Clean air valves and reseat if
certifications. Read and record all indications of necessary. Refer to manufacturer’s instructions.
gauges, thermometers and other instruments at (k) Air compressor. Disassemble and over-
regular intervals as required by the operating log. haul the air compressor and starting equipment
(r) Turbocharger. Observe every four hours every five years based on frequency of use of the
during operation. Check for general condition and auxiliary power plant.
signs of vibration. Evaluate vibration if present. (l) Pressure gauge inspection. Check the date -
(s) Turbocharger impeller. Check turbo- of calibration. Verify that gauges have valid calibra-
charger impeller for accumulated dirt and axial tion certification. Calibrate per manufacturer’s in-
endplay. Dirt may indicate faulty filtering equip- structions as required.
ment. Clean and service according to manufactur- (m) Governor overhaul. Overhaul the gover-
er’s instructions. nor after 2000 hours of use or when needed as
b. Long- term (diesels). Long-term checklist for indicated. Repair or replace worn or damaged parts.
diesel engines. Performance of checklist tasks is Reassemble and adjust, following the manufactur-
related to frequency and extent of use of the auxil- er’s instructions.
iary power plant. (n) Muffler (silencer). Keep the muffler and
(1) General comments. The following tasks waste heat equipment, boiler or heat exchange
should be performed annually, unless otherwise clean. Accumulations of unburned lubricating oil
noted, following performance of short-term checks. and soot or carbon are potential fire hazards. Make
(2) Checklist and schedule. sure fuel combustion is as efficient as possible. Re-
(a) Valve inspection. Inspect exhaust valves; fer to manufacturer’s instructions.
clean and remove carbon on two-cycle engines and (o) Cooling systems. Inspect piping and
valves as necessary. Refer to manufacturer’s in- valves for leaks and clean the heat exchanger. Per-
structions. form cooling system maintenance, refer to appendix
(b) Inlet valves
. . Inspect and regrind inlet and D, herein, and manufacturer’s instructions.
exhaust valves and valve seats as necessary. Refer (p) Cooling tower. Drain and clean cooling
to manufacturer’s instructions. tower; clean and inspect piping, circulating pumps
(c) Valve springs and guides. Check valve and equipment. Refer to appendix D.
spring length and tension and inspect valve stems, (q) Cooling system service. Clean and inspect
bushings, and guides annually or after 2000 hours entire cooling system yearly. Overhaul pumps and
of use, whichever comes first. Replace parts as nec- recondition valves and other equipment as neces-
essary. Refer to manufacturer’s instructions. sary. Refer to manufacturer’s instructions.

7-2
TM 5-685/NAVFAC MO-912

(r) Fuel oil tanks and lines. Drain service crankwebs for crankshaft deflection. Check journal
tanks and lines. Remove water and sediment. level and clean oil passages. Replace bearings as
Check heating coil for proper operation. Refer to necessary and adjust running clearance following
appendix B. the manufacturer’s instructions.
(s) Lubricating oil cooler. Clean and inspect (ad) Turbocharger inspection. Disassemble,
lubricating oil cooler for leaks and good condition. clean and inspect entire turbocharger following the
Clean outer surfaces more often under dusty oper- manufacturer’s instructions and specifications.
ating conditions for more efficient cooling. Refer to (ae) General overhaul. Overhaul diesel en-
manufacturer’s instructions. gines and driven equipment every ten years or
(t) Crankcase. Drain crankcase semi- annu- about 16,000 hours of auxiliary use. Follow the
ally or more frequent based on number of hours run manufacturer’s recommendations and instructions.
per manufacturer’s recommendations or acceptable Comply with the manufacturer’s specifications.
industrial engine maintenance procedures. Inspect c. Short-term (gas turbines). Short-term checklist
lubricating oil pumps; flush crankcase and refill. for gas turbines. Checks are limited to inspection
Refer to manufacturer’s instructions and to the and cleaning tasks that can be performed on the
Army Oil Analysis Program (TB 43-0210) for in- exterior of an engine.
structions. (1) General C omments. Before performing any
(u) Lubricating oil pump. Inspect the pump tasks required by the following checklist, review the
after 2000 hours of use for proper operation. Refer station log sheets, related records and the manufac-
to manufacturer’s specifications for the pump.
turer’s recommendations.
(v) Cylinder heads. Remove cylinder heads
(2) The following precautions must be met.
according to the manufacturer’s instructions after
Shut the engine down. Apply “Do not operate” tags
2000 hours of use. Inspect cylinder liners. Clean
to the operating controls. Open the engine auto-
and inspect water jackets. Remove scale&and corro-
sion as necessary. Inspect and measure diameter of matic start circuit. Deactivate the fire extinguishing
cylinder liners. Check gaskets for annealing, brittle- system. Keep all engine enclosure doors open while
ness or cracks. Install new gaskets if necessary. working on the engine. Allow engine to cool down
(w) Piston assembly inspection. On four- before working on it.
cycle engines, pull one piston after 2000 hours of (3) Checklist.
use and inspect for proper cooling, lubrication and (a) Inlet inspection. Verify that the inlet
carbon deposits. Inspect piston rings and wrist pin drain at lower part of duct is open and free of any
and the cylinder liner for compliance with engine obstruction so that moisture (rain or condensation)
manufacturer’s specifications. can run off. Check inlet temperature sensor for
(x) Inspection of pistons. Pull pistons after signs of damage. Clean sensor and surrounding
4000 hours of engine use. Clean and inspect all area with approved solvent to remove dirt and con-
parts for wear, proper lubrication and cooling. taminants. Refer to manufacturer’s instructions.
Verify that rings and ring clearances comply with Make sure sensor is securely attached to engine.
engine manufacturer’s specifications. (b) Exhaust inspection. Visually inspect en-
(y) Cylinder inspection. Use the barring de- gine exhaust casing, struts, and center body for
vice (jacking bar) to turn each piston to top dead cracks, nicks and other signs of damage. Refer to
center during step x. Inspect each cylinder liner for manufacturer’s instructions. Inspect exhaust stack
scoring. Refer to manufacturer’s instructions. for freedom from obstructions and general good con-
(z) Anchor bolts. Check anchor bolts for dition.
proper torque value. (c) Chip detectors. Engines usually have
(aa) Flywheel bolts. Check flywheel bolts for plugs with magnetic chip detectors at lubrication
proper torque value. Refer to manufacturer’s in- sumps. During normal operation, some fuzz-like
structions. Verify alignment and coupling to genera- particles will be found on the detectors. Also, other
tor, comply with specifications. materials (non-metallic sludge and/or flakes, bronze
(ab) Main and crankpin bearings. Remove powder, aluminum chips, etc.) may accumulate on
bearing caps; check journals and bearings for the plugs. Refer to manufacturer’s literature for
proper lubrication, wear or scoring. Check main specific information. Check chip detectors for elec-
bearings for proper alignment. Refer to manufactur- trical continuity while installed. Continuity is an
er’s instructions. indication of contamination. Remove chip detectors
(ac) Crankshaft. Verify compliance with en- if contaminated. Discard packing and clean chip
gine manufacturer’s specifications. Examine crank- detector. Check chip detector for good thread and
shaft for cracks. Measure distance between proper magnetism. Place new packings on chip de-

7-3
TM 5-685/NAVFAC MO-912

tectors and install on engine. Tighten to proper air at about 25 psi monthly. Check brushes for wear
torque. and indications of arcing and chattering monthly.
(d) External inspection. Inspect engine Check condition of slip rings. Refer to manufactur- -
tubes, hoses, tube/hose fittings, electrical assem- er’s instructions.
blies and connectors for security, and overheating (g) Static exciters. Verify that the equipment
and damage due to leakage. Perform inlet and ex- is clean and free from dirt and moisture. Verify that
haust inspection as described previously. Check all connections are tight. Check connections for cor-
standoffs, brackets and struts for looseness, cracks, rosion and clean as required.
and damage. Check ignition exciter, igniter plugs b. Long-term. Long-term checklists for genera-
and leads for damage, overheating and security. tors and exciters.
Check mechanical control for signs of excessive (1) General comments. The following tasks
wear, damage and security. Check fuel manifold for should be performed annually unless otherwise
leaks, signs of damage and security. Check for rust noted, following performance of short-term checks.
and/or corrosion. (2) Checklist and schedule.
d. Long-term (gas turbines). Long-term checks (a) Coupling Lubrication. Drain lubricant,
usually affect interior areas of the engine and are disassemble and clean the coupling annually or
seldom performed in the field. Repairs, if necessary, whenever necessary. Reassemble, using new gas-
may involve changes in component balance relation- kets and fresh lubricant. Refer to manufacturer’s
ships and should be performed at the designated instructions for flexible coupling.
overhaul location. Refer to the manufacturer’s lit- (b) Brush replacement. When brushes have
erature for information. worn to half their original length, replace, seat
properly and adjust brush rigging tension from 2.5
7-3. Generators and exciters. to 3.6 psi on brush riding surface. Repair and re-
Routine maintenance instructions for generators place damaged or worn brush rigging parts. Refer to
and exciters consist of short- and long-term check- manufacturer’s instructions.
lists for rotating and static type equipment. (c) Brush electrolysis. Electrolytic action can
a. Short- term. Short-term checklists for genera- occur at collector ring surfaces. This action forms a
tors and exciters. greenish coating (verdigris) on brass, bronze or cop- ---
(1) General comments. Before performing any per. Effects of this action can be reduced or elimi-
tasks required by the following checklist, review the nated by reversing the polarity annually or as re-
station log sheets, related records and the manufac- quired. Refer to manufacturer’s instructions.
turer’s recommendations. (d) Commutator and collector rings. Clean
(2) Checklist . commutator and collector rings with vacuum. Clean
(a) Air screens or filters. Air screens or filters oil film and dirt with approved solvent. Dry with
should be changed when the air flow is restricted compressed air at about 25 psi. Check for rough-
enough to increase generator operating tempera- ness, hard spots and out-of-round condition. Service
ture. Refer to manufacturer’s literature. commutator and collector rings as necessary follow-
(b) Exciter coupling (if applicable). When the ing manufacturer’s instructions.
generator unit is shut down prior to operation, wipe (e) Rotor winding. Rotor maintenance begins
off excess lubrication from the coupling to prevent with measuring and recording the insulation resis-
spatter. tance before the unit is placed in service. Refer to
(c) Coupling Leaks and alignment. When the manufacturer’s literature for instructions. The rotor
generator has been shut down, check for lubrication should be thoroughly cleaned annually and in-
leaks and tightness of coupling. Note ahy evidence spected as follows: Check the damper winding for
of improper alignment and correct if necessary. loose bars and the connection of each bar to its ring
(d) Axial position. Check axial position of the segment. Check the joints in the ring segments be-
prime mover, generator and exciter shafts for cor- tween poles. Refer to manufacturer’s instructions.
rect alignment and angularity. Check clearance per manufacturer’s specifications
(e) Bearings. Lubrication of generator and between blower and coils. Check the field coils for
exciter bearings is required. Refer to manufactur- movement and separation. Clean dirt and oil from
er’s literature for instructions for pressure and winding and air passages. Check condition of turn-
nonpressure lubricated bearings. to-turn insulation on strap field coils. Verify condi-
(f) Rotary exciters. Brushes and brush rig- tion of ground insulation on pole pieces. Check all --
ging. Remove carbon dust from collector ring and connections between field coils and lead-out connec-
commutator with vacuum and dry with compressed tions to collector rings. Measure and record insula-
7-4
TM 5-685/NAVFAC MO-912

tion resistance between field coils and ground in- relays such as thermal, current overload, overspeed,
cluding the collector rings. Refer to manufacturer’s liquid level, lubricating oil pressure and/or flow, fre-
instructions. Check bearings and journals for dam- quency change, etc. Refer to manufacturer’s litera-
_--_ age or excessive wear. Compare micrometer read- ture for inspection procedures. Verify that all con-
ings with the manufacturer’s table of wear limits. nections are tight and free of corrosion.
Repair or replace mechanical parts to meet these (c) Conductors and coils. Clean and inspect
specifications. Dry out according to manufacturer’s conductors and coils monthly. Verify that coating of
instructions. Repair insulation damage and coat insulating varnish is in good condition (clean,
with approved insulating varnish. smooth and polished) and there are no indications of
(f) Rotor balancing. Measure and record vi- overheating or corona arcing.
bration limits of repaired unit when it is started. (d) Switches. Inspect switches for proper
Refer to manufacturer’s specifications for vibration alignment, firm contacts and smooth operation
limits for the specific unit. Perform static or dy- monthly. Burned or pitted copper contact surfaces
namic balancing of the unit, according to instruc- may be dressed with 2/O sandpaper. Do not dress
tions, if necessary. silver contacts.
(g) Stator winding. Measure and record insu- (e) Circuit breakers. Trip and close circuit
lation resistance between stator winding and breakers, check for proper operation quarterly.
ground at the machine terminals annually. Check time delay and freedom of movement. Refer
(h) Stator service. Open up the stator annu- to manufacturer’s instructions.
ally. Clean thoroughly and inspect for the following: (f) Coils and heaters. Check coils and heaters
broken, damaged, loose or missing wedges; move-
quarterly for secure mounting and circuit continu-
ment or distortion of coil ends; security of all lash-
ity. Check controls and thermostats for proper op-
ing and spacers; tightness of coil supports; cooling
eration, refer to manufacturer’s instructions.
passages are open and clean; looseness of coils in
(g) Contactors.. Check magnet surfaces of
slots; cracks or other damage to coil insulation; and,
contactors quarterly for cleanliness. Remove gun,
connections between coils and around the frame.
Measure and record insulation resistance between rust or corrosion. Adjust for even contact pressure
winding and ground at the machine terminals. according to manufacturer’s instructions.
Compare the values with those recorded when the (h) Voltage regulators. Check voltage regula-
machine was first put in service. tors for proper operation and adjustments quarterly.
(3) Checkli st and schedule for solid-state excit- Various makes and types are used. Refer to the
ers. Solid-state equipment does not require long- manufacturer’s literature for instructions.
term checks. If the equipment does not function b. Long- term. Long-term checklists for switch-
properly, refer to the manufacturer’s literature for gear. Performance of tasks is related to frequency
information. Repair or replace as required. and extent of use of the auxiliary power plant.
(1) General comments. The following tasks
7-4. Switchgear maintenance. should be performed annually unless otherwise
Routine maintenance instructions for switchgear noted, following performance of short-term checks.
consist of short- and long-term checklists. The procedures are general but apply primarily to
Deenergize switchgear before performing mainte- draw-out equipment.
nance. Disconnect primary and secondary sources of (2) Checklist and schedule.
power. (a) Meters and instruments. Check meters
a. Short-term. Short-term checklists for switch- and instruments against a verified standard. Re-
gear. turn defective or inaccurate meters and instru-
(1) GeneralZ comments. Before performing any ments to the manufacturer or designated repair lo-
tasks required by the following checklist, review the cation for service and calibration.
station log sheets, related records, manufacturer’s (b) Buses. Inspect ‘buses and connections for
recommendations and NFPA-70E, Electrical Safety signs of overheating or weakening of insulating sup-
Requirements for Employee Workplaces. ports. Overheating is indicated by discoloration of
(2) Checklist. the busbar. Inspect insulators for cracks and/or arc
(a) Panels and other exterior surfaces. Panels tracks. Replace defective insulators. Tighten busbar
and exterior surfaces must be kept scrupulously and terminal connections to the proper torque
clean at all times. value.
(b) Relays and actuating mechanisms. Clean (c) Indicating devices and interlocks. Check
and inspect relays and actuating mechanisms indicating devices and interlocks for proper opera-
monthly. Many types of relays are used. Identify the tion. Refer to manufacturer’s instructions.
7-5
TM 5-685/NAVFAC MO-912

(d) Disconnecting devices. Check primary (g) Environmental conditions. More frequent
disconnecting device contacts for signs of overheat- inspections of the switchgear must be made when
ing or abnormal wear. Clean contacts with silver unusual service conditions exist, such as contami-
polish. Clean disconnecting device contacts and ap- nating fumes, excessive moisture, or extreme heat --
ply light coating of approved lubricant. or cold. Additional protection may be required if
(e) Enclosure. Verify that interior anchor adverse conditions are present.
bolts and structural bolts are tight. Inspect cable (h) Ground resistance. Measure and record
connections for signs of overheating. Tighten loose ground resistance values using a ground resistance
connections as required. test set. Compare these values with those recorded
( f ) Circuit breakers. Manually operate each during previous tests. The tests indicate grounding
breaker while in test position, verify proper opera- system effectiveness and possible deterioration
tion. Refer to manufacturer’s instructions. since the last tests.
TM 5-685/NAVFAC MO-912

CHAPTER 8

h- LUBRICATING OIL PURIFICATION

8-1. Purification systems. cally neutral, highly absorbent material. Cotton,


Oil purification systems, either in the engine pres- cellulose waste, or paper is usually used as the
sure system or oil supply system are classified by absorbent filtering material. The filter tank is pro-
the method of flow used’ in purifying the oil. The vided with necessary entry and exit ports, internal
systems frequently used are the bypass and full- tubing (perforated and solid), check valves and ori-
fices to ensure proper flow of the oil through the
flow types as follows:
filtering material. Filters are more efficient than
a. In the bypass system part of the total oil circu-
strainers in removing very small particles and are
lating in the engine passes through the filter or
usually designed to process strained oil. Refer to the
purifying equipment. The system continuously
filter manufacturer’s literature for details and ser-
cleans a small portion of the oil and, in general, vicing instructions.
removes contaminants as fast as they are formed in (2) Chemically actiuated. Absorbent filters con-
the engine. Thus, new oil may deteriorate but will tain chemically activated material instead of chemi-
gradually stabilize when the effectiveness of the cally neutral material. Construction of absorbent-
filtration system matches the rate of production of type and adsorbent-type filters is similar. The
contaminants. filtering materials include charcoal, clay and fuller’s
b. In the full-flow system all of the oil circulating earth. These materials remove water, acidic compo-
in the engine passes through filtering equipment nents, and may absorb certain light petroleum ele-
prior to going to the engine. ments, waxes or residual products. They usually
accomplish good purification and may reduce acid-
8-2. Forms of contamination. ity as well as remove the solid contaminants. Absor-
Refer to appendix C paragraph C-le(2) for informa- bent or adsorbent filters may be used on straight
tion on complete sample testing. Oil contamination run, uncompounded mineral oils where there is no
usually occurs in one of two forms, as follows: danger of removing essential additives. Absorbent
a. Impurities such as dirt, carbon particles or filters (chemically-neutral filters) should be used in
other solid matter entering the oil. conjunction with compounded or additive-type oil.
b. Undesirable substances such as water, poly- Refer to the filter manufacturer’s literature for de-
merized products of oil breakdown, acids and other tails and servicing instructions. Ensure that the
chemical matter entering the oil. filtering system complies with the engine manufac-
turer’s recommendations.
8-3. Methods of purifying. c. Centrifuging. An oil purification centrifuge
Oil purification is accomplished by the use of one, or usually consists of a stationary bowl that encloses a
any combination, of the following methods: strain- rotating element. The element, mounted on a verti-
ing, filtering, centrifuging, or reclaiming. cally arranged axis, rotates at a high speed within
a. Straining. The usual type of oil strainer can be the bowl. High-speed rotation causes a column of oil
woven wire screen or perforated sheet metal. Edge- to form in the portion of the element nearest the
type and wire-wound strainers are also used. The center and a column of water to balance this at the
edge-type consists of stacks of metal discs separated outer edge of the centrifuge bowl. Solid particles
by thin washers. The wire-wound type consists of a having a gravity value heavier than that of the oil
spool wrapped with finely serrated wire forming a are thrown outward, and the heavy solids accumu-
clearance between adjacent wires. Strainers are de- late in the centrifuge bowl. Water is removed by the
signed to remove solid particles from the oil, usually high gravity differential produced by the high speed
between 0.0015 and 0.003 inches in size, depending of the centrifuge. Effective mechanical separation
on the engine manufacturer’s specifications. Refer occurs; however, materials in a suspended state are
to the strainer manufacturer’s literature for details not always removed by this method. Chemical con-
and servicing instructions. taminants are separated only if they have a mark-
b. Filtering. Filtering is accomplished using edly different specific gravity from that of the oil.
chemically neutral or chemically activated filtering Polymerized products having a gravity similar to
material. that of oil are not separated and, in general, fuel oil
(1) Chemically neutral. The oil filter usually dilution is not affected or corrected. The centrifuge
consists of a canister or tank containing a chemi- is used extensively in fuel oil purification but has
8-1
TM 5-685/NAVFAC MO-912

reduced application to diesel and internal combus- Table 8-I. Oil quality standards-Continued
tion engine lubricants. If used in an oil reclaiming
system, it is usually only a part of the total process.
Refer to the manufacturer’s literature for details
and servicing instructions.
d. Reclaimming. Various types of oil reclaiming
equipment are used. Most reclaimers operate with
the oil heated at about 4OO”F, which drives off water
vapor and lighter fuel oil dilution. Highly effective
reclamation of regular mineral oil is possible. Al-
most complete removal of additive material occurs
during reclaiming. Oils produced from a reclaimer 8-4. Oil maintenance procedures.
must be limited to services not requiring an addi- The following information is a general guide for
tive oil. Operation at temperatures above 400°F re- maintenance of lubricating oil.
sult in partial breakdown of the lubricating oil, a. Water and sediment. Clean by centrifuging.
which can produce an oil having a higher viscosity b. Viscosity. Treat with oil reclaimer to drive off
than the original oil. Oil reclaimers are normally dilution.
used for processing oil between the impure oil and c. Viscosity. Centrifuge C hot) to remove heavy
the clean oil system or may route the reclaimed oil sludge. If necessary, add straight run mineral oil of
to a separate tank for use in other lubricating ser- lower viscosity.
vices. Refer to the manufacturer’s literature for de- d. Corrosion. Treat with activated-type reclaimer.
tails and servicing instructions. If an additive oil is in use, the presence of corrosive
e. Oil quality standards. Oil quality standards qualities indicates that the additive is exhausted.
are provided below. New oil must be used if the benefit of additives is
required. Used oil may be reclaimed and used for
Table 8-1. Oil quality standards.
other services not requiring the additive.
Normal Maximum e. Particles. Passage of particles larger than the
Water and Sediment 1 .oc;/c 5.0%
filter’s specifications are a definite sign of channel-
Water 0.5% 3.0% ing or structural damage to filter elements. Replace
Sediment 0.5% 2.0% filter cartridges.

8-2
TM 5-685/NAVFAC MO-912

APPENDIX A
I REFERENCES
--_

Government Publications.
AR 420-43 Facilities Engineering Electrical Services
DA PAM 738-750 Functional Users Manual for the Army Maintenance Management Sys-
tem (TAMMS)
MIL-STD-188-124 System Grounding Standards
NAVFAC MO-207 Operation and Maintenance of Internal Combustion Engines
TB 750-65 1 Use of Antifreeze Solutions, Antifreeze Extender, and Cleaning Com-
pounds in Engine Cooling Systems
TM 5-682 Facilities Engineering; Electrical Facilities Safety
TM 5-683/NAVFAC Facilities Engineering; Electrical Interior Facilities
MO-ll6/AFJMAN 32-1083
TM 750-254 Cooling Systems-Tactical Vehicles
40 CFR 761 Toxic Substances Control Act
Nongovernment Publications.
American Society for Testing and Materials (ASTM):
1916 Race St., Philadelphia, PA 19103
D-877 Dielectric Voltage Tests
D-923 Sampling Insulating Liquids
D-1524 Liquid Color Tests
D-1534 Liquid Acidity Tests
National Fire Protection Association (NFPA):
1 Batterymarch Park, Quincy, MA 02269
NFPA 70 National Electric Code, (1993)
NFPA 70B Recommended Practice for Electrical Equipment Maintenance, ( 1994)
Prescribed Form
DD Form 2744 Emergency/Auxiliary Generator Operating Log (Inspection Testing)

‘-,

A-1
TM 5-685/NAVFAC MO-912

APPENDIX B

4-, FUEL AND FUEL STORAGE

B-1. Diesel fuel. once every six months). Deterioration of stored fuel
Diesel fuel should comply with Federal Specifica- is caused by three factors: oxidation, microorganism
tions W-F-800 MIL-F-16884, or specifications for contamination and corrosion.
JP-8. These specifications include grades DF-A, (1) Oxidation occurs directly or through cata-
DF-1, DF-2 or types I and II. All are suitable for lytic action. Oxygen from the air or fuel combines
use under applicable temperature and service con- with fuel hydrocarbons causing oxidation. Result-
ditions. Different grades of fuel should not be ant oxidation continues as long as oxygen is
mixed. present. Metals suspended in the fuel act as cata-
a. Cleanliness. Fuel must be clean. All dirt, dust, lysts. Metals can enter the fuel during refining,
water, sediment, and other contaminants must be distribution or storage. The engine fuel system can
kept out of the fuel to prevent damage to engine fuel thereby be damaged.
injection equipment. The specified grade of clean (2) Microorganism contamination is caused by
fuel must be used to ensure long, economical engine bacteria and fungus that exist in the bottom water.
operation. Handling of fuel must be reduced to a Waste by-products of the microorganisms form a
minimum to avoid entry of contaminants. Delivery self-sustaining corrosive environment. The by-
of fuel to storage tanks and then pumping it directly products can form a gelatinous mass which plugs
to the day tank through filters is a recommended fuel lines and filters, and forms a fuel sludge
procedure. Filters must be installed in all engine thereby reducing engine efficiency and possibly
fuel lines and must be cleaned as recommended by damaging the engine.
the engine manufacturer. (3) Corrosion of the storage tank does not di-
b. Contamination. Stored fuel and fuel storage rectly deteriorate the fuel. Corrosion can destroy a
systems must be inspected at regular intervals such metal storage tank, usually at the bottom. Metals
as every 90 days. Samples for detecting fuel con- that enter the fuel act chemically to speed up oxida-
taminations are as follows: tion. The combination of microorganism growth and
(1) Inspect fuel filters for indication of microor- water causes oxidation.
ganism growth, rust, scale, or sediment. In a glass
jar, collect a sample of diesel fuel from the bottom of B-2. Gas turbine fuel.
the tank. Solid contaminants will settle and collect Fuel for gas turbines consists of natural gas or light
at the bottom of the jar. Clean the filters as directed distillate oil such as kerosene or commercial jet
by manufacturer’s instructions. engine fuel, Jet A or Jet A-l. All are suitable for use
(2) Detect water in diesel fuel by collecting in a under applicable temperature and service condi-
glass jar a sample of fuel from the bottom of the tions. Most gas turbines can burn fuels used by
tank. Fuel and water will separate when the sample diesel engines. Gas and oil fuels should not be
is allowed to settle, water will sink to the bottom of mixed.
the jar. Fuel with water in it may appear white and a. Cleanliness. Fuel must be clean. All dirt, dust,
cloudy when agitated. water, sediment, and other contaminants must
(3) Detect gasoline or kerosene in diesel fuel by be kept out of fuel to prevent damage to engine
collecting a sample (refer to b above). Fuel and con- components. Only the specified grade of clean fuel
taminants will separate when the sample is allowed should be used to ensure reliable engine operation.
. to settle, the gasoline or kerosene will float on the Handling of fuel must be reduced to a minimum to
fuel. avoid entry of contaminants. Refer to paragraph
(4) Detect Oil soluble soaps in diesel fuel by C-1a for information relating to cleanliness of liq-
having an appropriate laboratory test performed. uid fuel. Natural gas should be passed through sev-
Avoid this kind of contamination, do not use galva- eral fine screen filters, to remove solid particles and
nized storage tanks or piping. water vapor, before it is fed to the gas turbine en-
(5) Prevent condensation within storage tanks gine.
by keeping the tanks full. Tanks must be kept full b. Contamination. Stored fuel and fuel storage
during cold weather. systems must be inspected at regular intervals such
c. Storage. Fuel tanks used for storage must have as every 90 days. Examples for detecting fuel con-
drain valves for removal of bottom water (to be done tamination in distillate (liquid) fuels are given in
TM 5-685/NAVFAC MO-912

paragraph C-lb( 1) through (5). Perform the follow- B-3. Fuel storage maintenance procedures.
ing checks when cleaning filters for a natural gas
a. Provide the base engineer’s office with the re-
system. ports and results of inspections performed in para- ---.
(1) Inspect the solid particles removed by fine graphs C-lc and C-2c. The base engineer will re-
screen filters. Determine if the particles are dust or view this data and take appropriate corrective
dirt, or the type of metal if metallic. action which may include any or all of the following.
(2) Inspect water accumulation for acid or al- (1) Add an a nt’ioxidant to prevent oxidation or
kaline content. “aging” of a fuel.
c. Storage. Methods and problems for storing dis- (2) Add a fungicide or biocide to destroy organ-
tillate (liquid) fuels are described in paragraph isms present in the water beneath stored fuel.
C-lc. Information relating to storing natural gas (3) Add a metal deactivator because metals in
fuel follows: fuel catalyze or speed up oxidation. Inhibitors that
(1) Natural gas can be stored in low pressure place an amine film on metal surfaces are available.
surface containers or high pressure sub-surface con- Amines are organic compounds that neutralize an
tainers and metal bottles. electrical charge in metals.
(2) Liquefied natural gas can be stored in insu- b. Note that any chemical or additive that is
lated metal tanks installed as sub-surface units. added to stored fuel must be approved by the Envi-
(3) The type of storage employed for natural ronmental Protection Agency. Also, the base engi-
gas depends on plant requirements and fuel avail- neer’s office should monitor the removal of bottom
ability. water from storage tanks (refer to para B-1c).

B-2
TM 5-685/NAVFAC MO-912

APPENDIX C
LUBRICATING OIL

C-1. Diesel engine oil. d. Changing oil. Lubricating oil must be changed
Lubricating oil for diesel engines should comply periodically. Refer to recommendations by the en-
with Federal Specifications MIL-L-2 104 and gine manufacturer to specific conditions, time inter-
MIL-L-9000. Oil that complies with the specifica- vals, and instructions. General oil change proce-
dures are as follows:
tions produces acceptable amounts of carbon resi-
(1) Operate the engine before draining old oil.
due during engine use and has acceptable pour,
Oil should be drained while warm and immediately
flash, and fire points. Straight mineral oil is the
after engine shut down because contaminants are in
basic ingredient. Inhibitors or chemicals are added
suspension and will drain readily.
to the oil by the oil refiner to ensure compatibility (2) Obtain a sample of the drained oil and de-
with a range of engines operating under varying liver it to the base engineer for testing. Drained oil
conditions. The user must observe recommenda- should be examined for fuel dilution, acidity, and
tions by the engine manufacturer for specific types presence of solids and other contaminants. Testing
and grades of oil for optimum engine performance. helps establish the overall condition of the engine
a. Characteristics. Engine lubrication requires and approximate frequency of need for oil changes.
selection of the proper oil. Refer to the engine man- (3) Observe the viscosity of drained oil. In die-
ufacturer instructions. Examples of required oil sel engines oil viscosity increases during service due
characteristics are as follows: to the gradual oxidation of the oil. Viscosity de-
(1) Oil should h ave sufficient viscosity to pre- creases if fuel gets into the oil by passing the piston
vent metal-to-metal contact. Oils with lower SAE rings or through leaks.
numbers are lighter and flow more readily than oils e. Oil analysis program.
with higher numbers. Heavier oils, those with (1) Personnel in the engineer’s office, and other
higher SAE numbers, may cause sluggish operation cognizant personnel, should refer to the Army Oil
and power loss. Analysis Program (AOAP) for sampling and analy-
(2) Oil should remain stable during use under sis information. The program is described in
changing temperatures and conditions for satisfac- TB 43-0210.
tory service. (2) The an a1 ysis of periodic samples of the lu-
(3) Check th e engine periodically, such as every bricating oil should report the character and
six months, for accumulation of sludge in the engine amount of contaminants, wear metals and additives
filters and strainers and around valve springs. Re- in the oil. However, some amounts of wear metals
fer to the engine manufacturer’s literature for spe- and contaminants will have been collected by the
cific information. chip collectors, strainers, filters, separators of the
(4) Oil must be free of water and sediment. system and also as sludge. To secure the total pic-
Collect a sample of oil in a glass jar. Allow the ture it is necessary to analyze all such collected
sample to settle. Water and solid contaminants material to determine the total rate of
settle to the bottom of the jar. increase/decrease of each. This will indicate what
b. Additives. Straight mineral oil does not have has occurred during the period between samples.
detergent qualities. Therefore, various compounds (3) The prudent responsible operator will log
are added to the oil. These additives keep the en- and use all such data to track trends that give
gine clean by controlling varnish formation or re- warning of conditions that may result, if uncor-
sisting chemical changes to reduce oxidation. Other rected, in major problems.
additives form a protective film against corrosive
acids. C-2. Gas turbine oil.
c. Mixing oils. Different refineries may use differ- Lubricating oil for gas turbines should comply with
ent types of additives or certain characteristics of Federal Specifications MIL-L-23699 or MIL-L-
the mineral oil may vary. Mixing types of oil may 7808. Oil that complies with the specification can
change the necessary detergent actions. To obtain withstand the high temperatures encountered dur-
maximum benefit from additive type oils do not mix ing engine operation.
them with straight mineral oil. Concentrations of a. Additives. Various compounds are added to
the additives is reduced when detergent oils and mineral oil to provide the special characteristics
straight oils are mixed. required for use in gas turbines. The user must
C-1
TM 5-685/NAVFAC MO-912

observe lubricating oil recommendations by the en- (2) Deliver the drain oil sample and particles to
gine manufacturer for optimum engine perfor- the base engineer for tests and analysis. The pres-
mance. ence of some particles in the drain oil is usually ._--
b. Changing oil Refer to the engine manufactur- considered normal by the engine manufacturer.
er’s literature for recommendations related to spe- (3) Refer to the manufacturer’s literature. An
cific conditions, time intervals, and instructions for oil analysis program is usually recommended, in-
changing the lubricating oil. cluding a spectrometric analysis of the metal par-
(1) Collect a sample of old oil when oil is ticles. It is necessary to collect and evaluate data for
drained from the engine storage tank. Examine the type and quantity of engine wear-metals. Study of
drain plug or valve, filter, and chip detector if used, this data shows trends of engine wear and expected
for metal particles. Save the particles for analysis. future reliability.

--
TM 5-685/NAVFAC MO-912

APPENDIX D
COOLING SYSTEMS AND COOLANTS

D-1. Coolant. flushing or cleaning the system with compound


The coolant used in diesel engines usually consists when necessary. Engines used in Arctic regions are
of a mixture of ethylene glycol antifreeze, corrosion covered in paragraph D-4.
inhibitor, and fresh water. When the engine is used a. Testing antifreeze. Perform tests to verify
in an extremely cold area, such as Arctic regions, a freeze protection and reserve alkalinity.
special antifreeze mixture is used. Specifications re- (1) Test for freeze protection using the combi-
lated to the mixtures are as follows: nation antifreeze and battery tester, stock number
Antifreeze, Ethylene glycol MIL-A-46 153
6630-00-105-1418. Instructions for using the
Antifreeze, Arctic- type MIL-A-11755 tester are included with it.
Inhibitor, Corrosion O-1-490 (2) Test for reserve alkalinity (corrosion protec-
The specification for cooling system cleaning compound is tion) using the reserve alkalinity test kit, stock
MIL-C-10597.
number 6630-00-169-1506.
D-2. Engine water treatment. (3) Cooling systems with freeze protection be-
low - 7 degrees F ( -22 degrees C) that fail the
The prime consideration in a closed water cooling
reserve alkalinity test may be replenished with cor-
system is proper water treatment to ensure no cor-
rosion or scale occurs during static or dynamic en- rosion inhibitor, stock number 6850-00-753-4967.
gine conditions. Replenishment is a one-time service. If the reserve
a. Acceptable conditions. In most modern diesel alkalinity test is failed again, replace the coolant. If
engines the following cooling water conditions are the system passes the test, record the date.
acceptable: b. Inspecting coolant.
(1) pH 8.5 to 10 (1) Inspect the coolant visually for cleanliness.
(2) Chlorid e and Sulfate 100 ppm Obtain a coolant sample and place it in a clean glass
(3) Total Dissolved Solids 500 ppm container. After allowing about five minutes for set-
(4) Total Hardness 200 ppm tling, examine the sample for contamination (rust,
b. Softened water. If possible softened water foreign particles, and/or sediment). The sample may
should be utilized to reduce the total hardness level have some color (same color as original antifreeze)
of the engine cooling loop. The use of softened water and should be clear.
will increase engine performance by reducing the (2) Examine the sample to determine the type
precipitation of calcium and magnesium at elevated and quantity of contamination. Rust, a chemical
temperature conditions, ensuring higher heat combination of iron, water, and air, is frequently
transfer rates. found. The presence of rubber particles usually in-
c. Antifreeze. Typically, engine cooling systems in- dicates deterioration of hoses. Replacement hoses
corporate antifreeze solutions which inhibit scale may be indicated. Sediment may be caused by im-
and protect the cooling system when temperatures purities in the water used in the coolant. Contami-
are encountered below freezing. Ethylene glycol nants in the coolant can clog a radiator or heat
mixed with a corrosion inhibitor such as triazoles
exchanger and cause engine and generating system
form an inhibiting film on metal surfaces that acts
breakdown.
as a barrier in the corrosion process. The following
c. Cleaning the system. Clean the cooling system
concentration curves should be utilized when add-
whenever the coolant is drained. Usually the sys-
ing glycol solutions to engine cooling system.
d. Concentration. As indicated by the chart the tem requires nothing more than thorough flushing
concentration should exceed 30 percent. If more out with fresh water. Refer to the engine manufac-
than 60 percent of solution is added two effects will turer’s literature for instructions. If any part of the
be realized; first a decrease in heat transfer rates, system is rusted or partially clogged, it is necessary
second a lowering of the system freeze protection. to use cooling system cleaning compound and condi-
tioner, stock number 6850-00-598-7328. Do not use
D-3. Cooling system maintenance. the compound as a routine maintenance procedure.
Maintenance consists of periodically testing the an- Instructions for using the compound are included
“-._
tifreeze, inspecting the coolant for cleanliness, and with it.
TM 5-685/NAVFAC MO-912

D-4. Filling the cooling system. c. Do not dilute arctic-type antifreeze with water
Refer to the engine manufacturer’s literature for or inhibitor. It is ready for use as issued.
instructions on filling the cooling system. This is
applicable to either new systems or those just Table D-l. Antifreeze solutions.
cleaned and serviced.
GUIDE FOR PREPARATION OF ETHYLENE
a. Cooling system protection is required for all GLYCOL ANTIFREEZE SOLUTIONS
liquid cooled diesel engines. In areas where tem- Lowest Estimated Pints of Antifreeze Needed to
peratures no lower than -55 degrees F ( -48 de- Temperature in Area Prepare I -Gallon of Solution
grees C) are expected, prepare a solution according +2O”F (-7°C) I .so
to the table D-l below. When temperatures below +IO”F (- 12°C) 2.00
freezing are not expected, use a weak solution such 0°F (- 18°C) 2.75
as one pint of ethylene glycol antifreeze for each - 10°F (-23°C) 3.25
gallon of solution for general protection against rust - 20°F ( - 29°C) 3.50
-30°F (-34°C) 4.00
build up and scale formation with the engine. - 40°F ( - 40°C) 4.25
b. Use arctic-type antifreeze in areas where tem- - 50°F ( - 46°C) 4.50
peratures below -55 degrees F ( -48 degrees C) are - 55°F ( - 48°C) 4.75
expected.

D-2
TM 5-685/NAVFAC MO-912

APPENDIX E

SAFETY

E-1. General. (3) Do not touch any part of an operating en-


The base engineer and his representatives are re- gine, as the engine becomes extremely hot. Wear
sponsible for general safety conditions, for enforce- insulated gloves as necessary.
ment of safety rules, and for the condition and use (4) Wear approved ear protection if the engine
is operating.
of all protective devices. The base engineer is re-
(5) Do not remain in the room or enclosure, or
sponsible for the competency of his representatives.
in the plane of rotation, when starting or monitor-
E-2. Safe operation. ing the engine.
(6) Attach an approved safety clearance tag
Safe operational practices must be followed to pre-
such as DA Form 4324 to the starting control when
vent injury to personnel and damage to equipment. work is being done.
These practices are applicable to diesel engines, gas (7) Make sure the engine, generator, and re-
turbines, and generators including associated elec- lated equipment are clean. Keep oil-soaked rags out
trical equipment. Protective devices include carbon of the generating facility to avoid a fire hazard.
dioxide fire extinguishers and first aid kits. When- c. Generators. Personnel must be familiar with
ever carbon dioxide extinguishers are used, enter recommendations and procedures described in TM
the area where used cautiously. Make sure the area 5-682.
has been ventilated thoroughly before entering.
Never use water to extinguish a fire in the engine, E-3. Electrical safety.
generator, or associated electrical equipment. a. General. All operating must be familiar with
a. Diesel engines. The engine operator must per- the following general safety precautions.
form the following visual checks before and during (1) Do not rely on safety devices. Never assume
operation. power is off or disconnected. Use and/or look for a
(1) Make sure engine coolant is at the proper safety clearance tag before working on high voltage
level and has the proper amount of antifreeze. equipment.
Check hoses for good condition. (2) Use rubber gloves, with valid “usefulness”
(2) Make sure engine air requirements for com- certification, when working on equipment or trans-
bustion are met. Check air filters and cleaners for mission lines.
cleanliness and good condition. (3) Stand on good rubber mat when working on
(3) Make sure the engine, generator, and re- generator equipment or switchgear.
(4) Have a person qualified in first aid for elec-
lated equipment are clean. Keep oil-soaked rags out
trical shock present at all times when working.
of the generating facility to avoid a fire hazard.
b. Rescue of shock victims.
(4) Guard against accidental or unintentional
(1) Protect yourself with dry insulating mate-
starting when work is being done on the engine or
rial.
associated equipment. Attach an approved safety (2) Open the circuit, wear rubber gloves to pull
clearance tag such as DA Form 4324 to the starting the victim away from the live conductor. Do not
control when work is being done. touch the victim with bare hands until the circuit is
(5) Make sure engine lubricant and fuel are at open.
the proper levels. c. First aid. Look for hemorrhage, stoppage of
b. Gas turbines. The engine operator must be breathing, wounds, fractures, etc. Indications of
alert for the presence of health and fire hazards. shock include: pale face, clammy and sweaty condi-
Make sure the generating facility is well ventilated tions, weakness, and a weak and rapid pulse. Do the
when using cleaning solvents. The following re- following in any emergency.
quirements must be met when the engine room is (1) Send for a doctor or carry the victim to a
entered. doctor.
(1) The gas turbine shall be shut down or lim- (2) Make sure the victim is comfortable. Keep
ited to idle power. the victim warm, quiet, and flat on the back.
(2) The enclosure door shall be kept open. If (3) Loosen the victim’s clothing. If breathing
the gas turbine is operating, station an observer at has stopped, apply artificial resuscitation. Study
the enclosure door. the procedures in TM 5-682, Section VIII. Do not
E-1
TM 5-685/NAVFAC MO-912

wait until an emergency requiring aid occurs, know (5) Feel for th e patient’s pulse. Failure to find a
what to do. pulse does not indicate death. Immediately begin
(4) Treat serious bleeding and stoppage of artificial resuscitation. Continue until the doctor
.-
in that order before anything else is done. arrives.
TM 5-685/NAVFAC MO-912

APPENDIX F

RECORDS

F-1. Manufacturer’s forms. corrective measures. This data helps determine the
Manufacturers provide specific instructions for the need for further maintenance. Supervisors can de-
use and care of their products. Very often these velop a local checklist and use it for inspections not
instructions include forms and log sheets for record requiring generator operations. Complete a DD
keeping on an hourly or daily basis for continuously Form 2744 for each scheduled emergency or auxil-
operating engines and generators. iary generator exercise. When possible, fill out the
forms during unscheduled power outages. During
F-2. DD Form 2744 (Emergency/Auxiliary extended generator operations, check generators as
Generator Operation log). frequently as manpower and scheduling permit.
Use DD Form 2744 for inspection testing of Only one form is necessary for each event. Annotate
emergency/auxiliary generators. Enter readings im- each check on the back of the form, to assist in
mediately after start and prior to shut-down. If the troubleshooting if a problem arises between checks.
engine runs more than one hour, record every two The workcenter should keep completed forms for
hours with a minimum of two readings. Use the quick reference. If desired, place a second copy on
form to record system performance during inspec- the unit in a protective cover. The supervisor re-
tion and testing. Record information such as operat- sponsible for maintaining emergency/auxiliary gen-
ing data, condition of lube oil (viscosity test), condi- erators and associated equipment must review com-
tion of plant and subsystems, deficiencies and pleted forms periodically.

F-1
TM 5-685/NAVFAC MO-912

EMERGENCY/AUXILIARY GENERATOR OPERATING LOG (INSPECTION TESTING)


1 m ENGINE DATA 6. VOLTAGE REGULATOR (See Note 7)
a. MAKE b. MODEL _. .:;:... ~::::. :::::. ::. :: .:_ ‘. :::: ‘_‘.~.~_~.~_~.‘.~_~.~,~.~.~.~.~.~.~.~.~ U N REMARKS
(y@ii-p?<_;? ({4 &< ‘-Q . ;i ‘i- i_.!‘/ a. REGULATOR
c. SERIAL NUMBER d. RPM MOUNTS L/
\Q‘S &fl/ 1 6 il i;, b. RHEOSTAT CONDITION
lCorroded,connections, \/
c. HOUR METER (11 START (2) FINISH etc.
(7
C_i;L:‘L .
3c
:‘) -
‘._L 20,~ y 7. AUTOMATIC TRANSFER PANEL (See Note 7)
. . . . . . . . . . . ._._.,., :.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:
,.;,.,._.,._..._.;,. ~.~~._~.~_~_~_‘_‘:.:.:...
.~.~.~.~,~.~,~,~.~‘..~~._~,,...........
f. INSPECTION TEST OPERATOR g. D TE ...:.:.:.:.:.:.:.,.
‘‘..‘‘..‘‘..‘‘..‘~.~_~..~.‘‘..~.‘.~.~ :::.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.:.~:.:.:.:.:
.~_~,~_~.._.~.~.~.~_~.~,~.~,~.~..~~.,~~..~~_~..~.~~..~~..~~,~.~.~.~~::::::
:.:.:.:.:.:.:.:.:.:.:.:.::.:.:.:.:.: .~.~.~ S U N REMARKS
c jclr ~~~:'~\fQq~ 'g-pl
15 q.q
a. CONTACTS BURNED L/
h. BASE/POST i. UNIT ,
LtX mbk -
5-s ii I'Y
-
b. MECHANISM BINDING .J
2. ALTERNATOR DATA
a.
K&i-l?
MAKE b. MODEL !J
c. WIRING DAMAGED
2a‘r C!

c. SERIAL NUMBER d. KW RATING d. COMPONENTS


i/
‘sy ! y’ Lb,’ OVERHEATED
t. VOLTS ., ~ f. PHASE 8. COOLING SYSTEM (See Note 2 )
4%
L -’ Qt
1 a. TEMP. DURING STANDBY b. TEMP. DURING OPERATIONS
g. SHOP SUPERVISOR h. DATE; 1 I’-, 5 y_ 1 ‘3 (:I @= 6
-xb’& 14J?\\( &J 5 /yl p&7 c. COOLANT ADDED lLeve/J d. ANTIFREEZE PROTECTION (See
Y
i. LOCATION lBuildingJ j. RECORD IDENT NUMBER 7 -cl *uL Note 33 -- 5 ’ F
, -i ib
.3 2, 3 cc :: % l,i‘ !t ‘-;) e. FAN BELT CONDITION f. RADIATOR AND LOUVER CON-
3. GENERAL CONDITIONS /See Note 7) c? ‘6 DITION (?c
REMARKS 9. LUBE OIL SYSTEM
a. OIL CHANGED (Xl b. OIL ADDED (Sum /eve/J
a. CLEANLINESS ,Jc \ YES NO YES NO

b. EXHAUST / c. LUBE OIL CONDITION lViscosityJ d. LEVEL IN GOVERNOR


CONDITION v’ c; p.+_
ITEM (See Note 2 J ALTERNATOR EXCITER
c. ENGINE VIBRATION
L/ I ..
d. LOOSE ITEMS T,ij.i ,+I: l-7 \ ,-;
10. KW LOAD 3 >(I
fBolts, Linkage, etc. J / i-4 p;,c PHl PH2 PH3
t
11. AMPERAGE
& +q c(Q
c. TURBO VIBRATION /
‘t PHl PH2 PH3
12. VOLTAGE
f. WATER LEAKS (XI g. LOCATION OF LEAK $(? .&I 4 &!

YES NO A’r ” i<,Il i-1 It, /(T{ ?Lt crpj iq


.
13. BRUSHES AND
4. FUEL SYSTEM (See Note 7) BRUSHES RIGGING
i
S U N REMARKS 14. SLIP RING
a. FUEL LEVEL (Day Tank) CONDITION
15. COMMUTATOR
b. FUEL LEVEL [Storage CONDITION
Tank) PHl PH2 PH3
16. VOLTAGE
c. WATER DRAINED (XJ d. FUEL LEAKS (XJ (Commerciall da;. r)$(! i\ei,
.>
YES NO YES lx1 NO 17. BATTERY CHARGER
c. LOCATION OF LEAK b. AMPS I
I L5
I
5. BATTERY BANK (See Note 7 ) 18. HYDROMETER 19. STARTING AIR 20. AMBIENT
U N REMARKS, READING lPsiJ TEMP. ioF/
+jH
L<i_' 3 i-" '7
II. CONNECTIONS
J <cl jqk3::r i Ctlj 21. FILTER CHANGE
$i\ )‘nv\‘y’ nE:fi;:j&i 5 ~ (1. L U B E O I L fXJ b. FUEL fXJ c. AIR INTAKE /XI
b. CLEANLINESS
J f &?‘d iz c’_&)._i Ea >:I Y E S NO XI YES 1 1 NO 1 YES NO
22. UNIT STARTED ON (XJ
c. ELECTROLYTE LEVEL
1ST TRY 2ND TRY 3RD TRY NOT AT ALL .
Use the reverse side of this form and/or 8-l /2 x 11” paper if required for additional comments, continuation of item entries (identify by item
number), and for corrective action(s) taken.
NOTE 1: Mark S for Satisfactory, U for Unsatisfactory, N for Normal, or indicate in Remarks column, as applicable.
NOTE 2: Enter data as indicated. Where no instrumentation is provided, indicate Satisfactory, Unsatisfactory, etc., as applicable.
NOTE 3: Enter Antifreeze Protection as the freeze temperature in degrees (F) as indicated on an appropriate hydrometer.

DD FORM 2744, MAY 96 LOCAL REPRODUCTION AUTHORIZED.

Figure F-1. Sample DD Form 2744 (Emergency /Auxiliary Generator Operating Log

F-2
TM 5-685/NAVFAC MO-912
c

c
Figure F-1. Sample DD Form 2744 (Emergency/Auxiliary Generator Operating Log (page 2)
TM 5-685/NAVFAC MO-912

APPENDIX G
DIESEL ENGINES: OPERATION, TIMING, AND TUNING INSTRUCTIONS

G-1. Starting and stopping. and subsequent use when needed. An engine can be
a. General. Starting and stopping procedures ap- damaged by improper shutdown or starting prac-
ply to diesel engines that are not equipped with an tices.
automatic start and shutdown feature such as the G-2. Engine timing.
manually operated engine used in a Class B system.
The procedures may be used if an engine is to be a. Timing function. The fuel injection system
exercised. Instructions for the operator, including must be timed so that combustion starts at, or just
operation and recording of instrument data, are before, piston top dead center (TDC).
provided. (1) Early ignition produces excessively high
b. Starting. Before starting make sure engine an- cylinder pressures and detonation from the rapid
cillary equipment is ready to function. The major pressure rise. Late ignition occurs when the piston
portion of normal wear occurs while starting a cold is moving away from the cylinder head, conse-
engine or an engine which has been idle. Proper quently the expansion ratio is reduced and effi-
ciency is lost. Another timing function is the rate of
starting technique includes inspection to verify that
injection, or the duration of the injection period.
the engine and its accessory plant are ready for
(2) Injection continues over a measurable pe-
operation, adequate fuel is available, and lubricat-
riod of time, usually expressed in degrees of crank-
ing oil, coolant and other supplies are at proper
shaft rotation. It is desirable to inject the fuel as
levels. Starting involves proper positioning of the quickly as possible without creating high cylinder
engine, use of the starting system and proper accel- pressures. The fuel burning period should be com-
eration to operating speed. Starting also includes pleted within the 15-20 degrees of crankshaft rota-
application of the load to the engine. tion after top dead center.
c. Operation. After engine operation starts and (3) The time of start of injection is determined
the load is applied, operator duties include following by ignition delay, since initial combustion must be
the load variations and making necessary opera- secured by top dead center, or slightly before. Dura-
tional adjustments. The operator must continuously tion of the injection period is determined by the
observe operation to determine deviations from nor- allowable rate of pressure rise in the cylinder. If
mal or acceptable including ranges of operating ignition delay is assumed to be .0025 second, the
pressures, temperatures or other operational pa- following applies to high, medium and low speed
rameters. Unusual sounds, smells, vibrations of os- engines operating at 1,800,600 and 300 rpm respec-
cillations of the engine and major variations in in- tively.
strument readings, may indicate some abnormal
condition. Table G-1. Ignition delay and duration.
- -
d. Recording. Instrument readings and operator ENGINE SPEED
observations must be recorded for analysis. These Description High Medium Low
data may indicate trends toward deterioration or Engine RPM I .800 600 _wo
need for adjustment. Entries on engine and related Rcvolutions/second 30 I0 5
logs must be at regular intervals and accurate. Degrees/second 10,800 3,600 I ,?wo
Ignition delay. degrees 27 9 4.5
e. Operational maintenance. The operator should
Probable duration, degrees 30 20 IS
be alert to possible malfunctions or deviations dur-
ing operation. Operational adjustments such as (4) Note that the high-speed engine would re-
pressure and temperature should be noted and re- quire an injection start timing 27 to 30 degrees
corded, if unusual. Ancillary equipment must be before top dead center, and that all fuel is in the
inspected during engine operation. cylinder by 3 degrees after top dead center. Pressure
f. Stopping. Proper technique in stopping the en- rise is rapid once ignition starts, because nearly all
gine and shutting down the ancillary equipment is of the fuel is in the cylinder. As speed is reduced, a
necessary. Correct shutdown permits the engine to later start of injection is possible. For the medium-
cool without excessive distortion of parts or stresses speed engine, about half of the total fuel charge is in
being imposed. The engine will be ready for restart the cylinder when ignition occurs, but the balance of
the charge is injected into the burning portion.
G-1
TM 5-685/NAVFAC MO-912

(5) For the 1ow-speed engine, about one-third of (f) Check air filter. Change air filter oil if oil
the fuel charge is present, while two-thirds of the bath type.
charge is injected at a controlled rate after ignition (g) Check high idle speed.
occurs. In practice, the lower speed engines use a (h) Check low idle speed 1
lower octane fuel. Since such engines are usually (i) Check engine for correct horsepower. Use
large, a relatively coarse atomization is used, re- dynamometer.
sulting in greater ignition delay. In low-speed en- (j) Visually check engine for leaks.
gines, actual fuel timing is usually in the range (k) In addition to these items, some engines
from 7 to 12 degrees before top dead center. may require additional adjustment or checking be-
(6) The med’ium-speed d engines usually are fore the tune-up is complete.
timed from 10 to 18 degrees before top dead center (2) Major tune-up includes the following:
while high-speed units will range as much as 35 to (a) Retorque cylinder head.
40 degrees before top dead center. Generally, the (b) Adjust tappet clearance.
duration of injection decreases with speed. (c) Clean and adjust injectors and/or injec-
b. Timing procedure. Timing is established by tion nozzles.
setting the fuel injection cam with the control sys- (d) Check pump static timing.
tem in the maximum fuel position. Since the fuel (e) Change fuel filters and strainers. Drain
cam is usually symmetrical, lost motion affects the engine coolant.
opening and closing times equally. For example, if (f) Service air cleaner.
an engine were timed at full load for opening 10 (g) Check and overhaul injection pump if
degrees before top dead center and closing 10 de- needed.
grees after top dead center, at half load, the timing (h) Check high idle speed.
might be 6 degrees before top dead center to 6 de- (i) Check low idle speed.
grees after top dead center. By lowering fuel pres- (j) Check engine for correct horsepower. Use
sure, the injection period can be lengthened to ap- dynamometer
proach the full load values. Balance is secured by (k) Visually check engine for leaks.
adjusting the lost motion device for each of the cyl- (3) During the tune-up, check for any loose
inders. It is important to maintain all fuel nozzle bolts or hose clamps that may be a potential trouble
tips in good condition, and to have carefully spot. Also, replace all gaskets, such as tappet cover
matched orifices on the nozzle. The nozzle orifice gaskets, pump gaskets, timing cover gaskets, and _-
and duration of injection are the only balancing any other gaskets that have been disturbed during
adjustments. Since duration should be similar for the tune-up.
all cylinders, matched orifices must be used. Always
install new fuel nozzle orifices in full sets for a G-4. Engine failure and repairs.
common rail engine. a. Failure identification. A well planned and ex-
ecuted preventive maintenance program reduces
G-3. Engine tuning. the possibilities of experiencing a catastrophic en-
a. General Tuning of diesel engines is necessary gine failure. However, it is not completely possible
whenever the engine is not running normally, has to prevent or anticipate such a failure. Indication of
lost power, or has operated the number of hours some of these failures are as follows:
that constitute a tune-up interval. (1) Crankcase explosions. If, during operation,
b. Tune-up categories. There are two categories of explosions can be heard in the crankcase, shut the
tune-up, minor and major. Refer to the time interval engine down immediately. Allow the engine to cool
specified by the manufacturer for minor and major before removing any cover plates for inspection.
tune-ups. The specific manufacturer’s literature (2) Runaway engine. May be caused by a stuck
should be consulted for tune up details related to fuel pump rack or defective engine safety stop. Lu-
the engine in use. bricate the control linkage when the engine is at
(1) Minor tune-up includes the following: rest or shut off the fuel supply to the engine, as
(a) Retorque cylinder head. This is optional; necessary.
follow manufacturer’s instructions. (3) Sudden stop. May be caused by overload,
(b) Adjust tappet clearance. low lubricating oil, seized engine components, or
(c) Adjust injector timing or setting on en- empty fuel tank. Inspect to identify the problem.
gine using unit injectors. Allow the engine to cool before removing any cover
(d) Check pump static timing on engines us- plates.
ing a pump-nozzle combination. (4) Unusual noises. Can be caused by fuel in- -+*
(e) Change fuel filters and strainers. jection equipment troubles, a loose or broken con-
G-2
TM 5-685/NAVFAC MO-912

necting rod, faulty piston rings or wrist pins, or a culties originating from by-products or effects of
loose flywheel. Inspect to identify the problem. the initial failure. Therefore, carefully check all
b. Repairs. Repairs must be prompt and thorough of the related and resultant functions of the faulty
L to restore the engine to serviceable condition as part or any other component affected by it to make
rapidly as possible. Such repairs normally depend sure that the engine has been thoroughly restored
on the immediate repair parts inventory but may to operable condition. For example, if a connect-
*
also require maximum ingenuity in producing a ing rod bearing fails, replace the bearing and exam-
useable repair part. Particular attention must ine the crank journal to see if it has been scored
be given to not only the part which failed, but or damaged and if all oil passages to the piston
also to all other parts which might be affected are properly clear. Also, verify that connecting rod
by the failure. Merely replacing an obviously de- bolts or adjacent main bearings have not been af-
fective part often will lead to a series of diffi- fected.

G-3
TM 5-685/NAVFAC MO-912

Section I
Abbreviations
A, AMP kv
amperes kilo volts

AC kw
alternating current kilo watts

AS LPT
ammeter switch low pressure turbine

BDC NEMA
bottom dead center National Electrical Manufacturers Association
C NFPA
Centigrade National Fire Protection Association

CFM PCB
cubic feet per minute polychlorinated biphenyls
CFR PH
Code of Federal Regulation pouvior hydrogene
Cl PPM
compression ignition parts per million
CPT psi
control power transformer pounds per square inch
L CT PT
current transformer potential transformer
DC RFI
direct current radio frequency interference
EMF RPM
electromotive force revolutions per minute
F RTD
Fahrenheit resistance temperature detector
FU SI
fuse spark ignition
HP TDC
horsepower top dead center

HPT UPS
high pressure turbine uninterruptible power supply

Hz V
hertz volt
IR VAR
infrared volt amperes reactance

kVAR, kilovars VM
I voltmeter
!I kilo volt amperes reactance
-- kVA VOM
II
kilo volt amperes volt ohm milliammeter
Glossary 1
TM 5-685/NAVFAC MO-912

vs WHDM
I voltmeter switch watt-hour demand meter
W WM
watt
Section II
Terms
Alternating current impulse per cylinder for every four strokes of the
An electric current that is continually varying in piston. One stroke is one pass through the cylinder.
value and reversing its direction of flow at regular
Fuel filter
intervals. A cycle is one complete set of positive and
Device used to separate solids, impurities, and wa-
negative values of an alternating current. The num-
ter from the fuel.
ber of cycles occurring in one second (cycles per
second or Hertz) is called frequency. Alternating Gear pump
current voltage is expressed as volts AC. Delivers fuel from tank to injectors.
Brayton cycle Governor
The operating principle by which a gas turbine en- A mechanism used to control the speed of an engine.
gine operates, called constant pressure combustion.
Governor characteristics
Charge (circuit breaker) Terms used in discussion of a governor:
The loading or tensioning of circuit breaker springs a. Governor sensitivity. Ability to detect a change
by compression and/or extension. in engine speed, expressed as percent of rated top
speed.
Circuit breaker
b. Governor speed droop. Change in engine speed
A device for closing and/or interrupting a circuit
as load increases, expressed as percent of rated
without damage to itself or the equipment it is pro-
speed.
tecting when properly applied within its rating. The
c. Governor reset. Adjustment to the governor (in-
interruption feature of this device functions when
ternal or external) which changes the set speed at _
an abnormal condition such as an overload or short
any given load point.
circuit occurs. The device usually is set to trip at
d. Isochronous governor. A governor with auto-
125 percent of full load current.
matic reset which compensates for speed droop.
Dew point Constant engine speed is maintained regardless of
Dew point is the temperature at which dew starts to load.
form (vapor condenses into liquid). e. Governor output. Measure of power the gover-
nor can provide to activate the fuel control mecha-
Direct current
nism. Expressed in pounds per inch or pounds per
An electric current that flows continually in one
foot.
direction. Direct current voltage is expressed as
volts DC. Grounding
Grounding is the connection of a low resistance me-
Electromotive force
tallic conductor between the power distribution sys-
The potential, or voltage, developed by a dynamo or
tem’s neutral lead and earth (or an equivalent con-
battery.
ducting body). Grounding safely clears line-to-
Emergency power ground faults.
A power source (held in reserve) that is available for
use in the event of failure of the normal power Hertz
source. Transfer to and/or from emergency power A unit of frequency equal to one cycle per second
can be automatic or manual. (refer to alternating current).

Fault current Hunting


Current flowing to a fault. It may be leakage, a Periodic increase and decrease (oscillation) in
short circuit, or a direct ground. speed, voltage, or other quantity.
Four cycle (four stroke) engine Injector
A reciprocating (piston) engine, using gasoline or Meters, times, and pressurizes fuel to be delivered
diesel oil for fuel. The engine produces one power to the cylinder.
Glossary 2
TM 5-685/NAVFAC MO-912

Magnetism Switchgear
Property of certain materials which exerts a me- General term, covers switching and interrupting de-
chanical force, attraction or repulsion, on an adja- vices including their associated control, instrumen-
cent mass of similar materials. tation, metering, protective devices, and housing.
Used relative to generation, transmission, distribu-
Otto cycle tion, and conversion of electric power.
The operating principle by which a piston (recipro-
cating) engine operates, called constant volume Tachometer
combustion. Instrument that measures angular speed, such as
that of a rotating prime mover shaft. Tachometers
Polychlorinated biphenyls covered herein usually use a magnetic pick-up to
PCB, a liquid with high dielectric strength that was sense speed.
used as an insulator in power transformers, relays,
Two-cycle (two-stroke) engine
circuit breakers, etc.
A reciprocating (piston) engine using diesel oil for
Scavenging fuel. The engine produces one power impulse per
The removal of exhaust (burned) gases from the cylinder for every two strokes of the piston. One
cylinders of a piston (reciprocating) engine. Also, stroke is one pass through the cylinder.
refers to the collection and removal of excess lubri- Turbocharge
cating oil from a bearing housing in a gas turbine A method of increasing the volume of air charge in
engine. the cylinders of piston engines to produce higher
power output. Flow of exhaust gases operates a tur-
Supercharge
bocharger.
A method of increasing the volume of air charge in
the cylinders of piston engines to produce higher Voltage regulator
power output. A belt or chain driven blower is used A device which controls the output voltage of a gen-
to supercharge an engine. erator.

Glossary 3
v

TM 5-685/NAVFAC MO-912

INDEX
.
Air intake . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–9 DC generators . . . . . . . . . . . . . . . . . . . . . . . . . ..4–3b
Alternator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4–5 Voltage regulator . . . . . . . . . . . . . . . . . . . . . . . ..4–2c
Polyphase . . . . . . . . . . . . . . . . . . . . . . . . . . ...4-5a(1) Generators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4–1
Single . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...4-5a(2) Governor . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–8.3–20
Auxiliary power . . . . . . . . . . . . . . . . . . . . . . ..1–1,2–3a Electronic (Isochronous) . . . . . . . . . . . . . . . .3–8g(4)
Batteries . . . . . . . . . . . . . . . . . . . ... . . . . . . . . . . . ..5–9c Hydraulic governor . . . . . . . . . . . . . . . . . . ..3–8g(2)
Bearings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4–11 Mechanical governor. . . . . . . . . . . . . . . . . ..3–8g(l)
Ball bearings . . . . . . . . . . . . . . . . . . . . . . . . . . ..4-llc Pneumatic governor.. . . . . . . . . . . . . . . . . ..3–8g(3)
Sleeve bearings . . . . . . . . . . . . . . . . . . . . . . . ..4-llb Governors . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..2–10b(2)
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–21 Ground grid . . . . . . . . . . . . . . . . . . . . . . . . . . . ..2–8k(2)
Cooling system . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–5 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..2–8
Air-cooled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–5a Equipment grounding . . . . . . . . . . . . . . . . . . ..2–8b
Coolant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5c(4)(f) Ground fault . . . . . . . . . . . . . . . . . . . . . . . . . . .2-8f(1)
Liquid-cooled . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–5b Ground fault current . . . . . . . . . . . . . . . . . . . . . . 2-8j
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4–7b High-resistance grounding . . . . . . . . . . . . . . . ..2–8i
Current transformers . . . . . . . . . . . . . . . . . . . . . ..5–3c Low-resistance grounding . . . . . . . . . . . . . . . . 2–8h
Diesel Engines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–2 Neutral potential . . . . . . . . . . . . . . . . . . . . . ..2–8f(l)
Distribution systems . . . . . . . . . . . . . . . . . . . . . . . ..2–6 Resistance grounding . . . . . . . . . . . . . . . . . . ..2–8h
Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . ..2–6.2–7 Solid grounding . . . . . . . . . . . . . . . . . . . . . . ..2–8g(2)
Power factor . . . . . . . . . . . . . . . . . . . . . . . . . . . ..2–6a Solidly grounded . . . . . . . . . . . . . . . . . . . . . . . . ..2–8g
Emergency generators . . . . . . . . . . . . . . . . . . . . . ..2–2c System grounding. . . . . . . . . . . . . . . . . .12–8a.,2–8d
Emergency power . . . . . . . . . . . . . . . . . . . . . . . . . . ..2–1 Grounding system
Engine timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–3c Ground bus . . . . . . . . . . . . . . . . . ... . . . . . . ..2–8k(l)
Equipment grounding . . . . . . . . . . . . . . . . . . ..2–8k(8) Grounding conductors . . . . . . . . . . . . . . . .2–8k(9)(c)
Exciters . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..2–l0a, 4-8 Grounding electrodes. . . . . . . . . . . . . . . ..2–8k(9)(a)
Brush-type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4-8c Harmonic current . . . . . . . . . . . . . . . . . . . . . . ..2–8k(1)
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4-9b Hospitals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..2–lb(1)
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4-9d Instrumentation . . . . . . . . . . . . . . . . . . . . . . . . . . . ..5–7
Rotating-rectifier . . . . . . . . . . . . . . . . . . . . . . . ..4–8f Insulation testing . . . . . . . . . . . . . . . . . . . . . . . ...4-13
Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4-9c Lightning arresters, . . . . . . . . . . . . . . . . . . . . . . ..5–9e
Static exciters . . . . . . . . . . . . . . . . . . . . . . . . . .. .4-8g Load shedding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..2–9
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...4-9a Loads . . . . . . . . . . . . . . . . . . . . . . . . ... . . . . . . . . . . ..2–5
Exhaust system . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–10 Low voltage switch gear..... . . . . . . . . 5–2a(l),5–3
Field flashing . . . . . . . . . . . . . . . . , . . . . . . . . . . ...4-10 Air circuit breakers . . . . . . . . . . . . . . . . . . ..5–3a(1)
Floors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..2–3e(2) Circuit breakers . . . . . . . . . . . . . . . . . . . . . . . ..5–3a
Foundations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–3e( 1) Lubrication system . . . . . . . . . . . . . . . . . . . ..3–6.3–18
Four-cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–3b Lube oil . . . . . . . . . . . . . . . .3-6a(10)(a), 3–6a(10)(d)
Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4-7d Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..7–1
Fuel injection system . . . . . . . . . . . . . . . . . . . . . ..3–4a Medium voltage . . . . . . . . . . . . . . . . . . . ..5–2a(2), 5–4
Fuel storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..2–4 Air circuit breakers . . . . . . . . . . . . . . . . . . ..5–4a(2)
Day tanks, . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..2–4d Circuit breakers . . . . . . . . . . . . . . . . . . . . . . . ..5–4a
Fuel system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–4 Current transformers . . . . . . . . . . . . . . . . . . . ..5–4c
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..5–9h Oil circuit breakers . . . . . . . . . . . . . . . . . . ..5–4a(1)
Current limiting fuses . . . . . . . . . . . . . . . 5–9h(2)(a) Potential transformers . . . . . . . . . . . . . . . . . . . 5–4b
Expulsion fuse . . . . . . . . . . . . . . , . . . . . ..5–9h(2)(d) Vacuum circuit breakers . . . . . . . . . . . . . . ..5–4a(3)
Glass-enclosed fuse . . . . . . . . . . . . . . . . ..5–9M2)(c) Oil filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–6i
Metal-enclosed fuse . . . . . . . . . . . . . . . . ..5–9h(2)(b) Oil purification . . . . . . . . . . . . . . . . . . . . . . . . . . ..8–la
Gas turbine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–lb Operational testing . . . . . . . . . . . . . . . . . . . . . . . . ..6–7
Gas turbine engines . . . . . . . . . . . . . . . . . . . . . . ..3–13 Plants . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . ..2–2b
Generator operation . . . . . . . . . . . . . . . . . . . . . . . ...4-2 Polarities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..5–3d
Exciter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4–2b Portable diesel . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..2–2e
AC generators . . . . . . . . . . . . . . . .. 4-2b. 4-3a, 4-4 Portable power plants . . . . . . . . . . . . . . . . . . . . ..2–2d
Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4–2a Potential transformers . . . . . . . . . . . . . . ..5–3b.5–4b
Index 1
-

TM 5-685/NAVFAC MO-912

Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-7e Starting system . . . . . . . . . . . . . . . . . . ..0. ..3–7.3–19


Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . ..4-7e(3) Air starting . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–7b
Power generation . . . . . . . . . . . . . . . . . . . . . . . . . . ..2–2 Electric starting . . . . . . . . . . . . . . . . . . . . . . . ..3–7a .
Prime movers . . . . . . . . . . . . . . . . . . . . ..2–3c, 3–1, 7–2 Stator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4-6c
Protective relays . . . . . . . . . . . . . . . . . . . . . . . ..5–8a(2) Stroke . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–la
Current balance . . . . . . . . . . . . . . . . . . . . . 5-8a(2)(g) Surge capacitors . . . . . . . . . . . . . . . . . . . . . . . ..5–9d(l)
Differential . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8a(2)(f) Switchgear . . . . . . . . . . . . . . . . . . . . .. 2–10g, 5–1, 7–4
Ground fault protection . . . . . . . . . . . . . 5-8a(2)(h) Voltage classification . . . . . . . . . . . . . . . . . ... .5-2a
Overcurrent . . . . . . . . . . . . . . . . . . . . . . . ..5–8a(2)(cz) Synchroscope . . . . . . . . . . . . . . . . . . . . . . . . ..5-9i, 6-5e
Overvoltage, . . . . . . . . . . . . . . . . . . . . . ...5-8a(2)(b) Test equipment.....,...,.,.. . . . . . . . . . . . . . ..5–9g
Reverse Power . . . . . . . . . . . . . . . . . . . ...5-8a(2)(d) Ammeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9g(5)
Underfrequency . . . . . . . . . . . . . . . . . . . . ..5–8a(2)(e) Electrical analyzer . . . . . . . . . . . . . . . . . . . ..5-9g(9)
Undervoltage . . . . . . . . . . . . . . . . . . . . . ...5-8a(2)(c) Frequency meter . . . . . . . . . . . . . . . . . . . . . ..5–9g(6)
Regulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..5–6 Megohmmeter . . . . . . . . . . . . . . . . . . . . . . . ..5–9g(8)
Electro-mechanical voltage regulators . ..5–6a(1) Multimeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9g( 1)
Static exciter regulators . . . . . . . . . . . . . . . .5–6a(3) Ohmmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9g(4)
Static voltage regulators. . . . . . . . . . . . . . . . 5–6a(2) Voltammeter . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9g(3)
Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..5–8 Voltmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-9g(2)
Overload . . . . . . . . . . . . . . . . . . . . . . . . . . ..5–8a(l)(b) Wattmeter . . . . . . .... .. . . . . . . . . . . . . . . . . 5–9g(7)
Solid-state . . . . . . . . . . . . . . . . . . . . . . . . ..5–8a(l)(d) Tie Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . ..5–3e(2)
Time delay . . . . . . . . . . . . . . . . . . . . . . . . ..5–8a(l)(c) Transfer switches . . . . . . . . . . . . . . . . . . . . . 2-10f, 5-5
Voltage sensitive, . . . . . . . . . . . . . . . . . ...5-8a(l)(e) Two cycle . . . . . . . . . . . . . . . . . . . ... . . . . . . . . . . . ..3–3
Rotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4-6b Vans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4-7e(2)
Semi-automatic mode . . . . . . . . . . . . . . . . . . . . ..6-2b Voltage, generated . . . . . . . . . . . . . . . . . . . . . . ...4-7a
Slip rings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4-6d Voltage regulators . . . . . . . . . . . . . . . . . . ..2–10e. 5-6
Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4-7c Watts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..4-7e(l)
Speed control . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3–20

Index 2
TM 5-685/NAVFAC MO-912

The proponent agency of this publication is the Office of the


Chief of Engineers, United States Army. Users are invited to send
-
comments and suggested improvements on DA Form 2028 (Rec-
ommended Changes to Publications and Blank Forms) directly
c to Director, U.S. Army Center for Public Works, ATTN: CECPW-EE,
7701 Telegraph Rd., Alexandria, VA 2231593862.

By Order of the Secretaries of the Army and the Navy:

DENNIS J. REIMER
General, United States Army
Official: Chief of Staff

pati JOEL B. HUDSON


Administrative Assistant to the
Secretary of the Army

D. J. NASH
Rear Admiral CEC, United States Navy
Commander, Naval Facilities Engineering
Command

Distribution:
Army:
To be distributed in accordance with initial distribution number
(IDN) 344596, requirements for TM 5-685.
TM 5-685/NAVFAC MO-912

EMERGENCY/AUXILIARY GENERATOR OPERATING LOG (INSPECTION TESTING)


- 1. ENGINE DATA 6. VOLTAGE REGULATOR (See Note 7)
3. MAKE b. MODEL U N REMARKS

a. REGULATOR
J. SERIAL NUMBER d. RPM MOUNTS
rr
b. RHEOSTAT CONDITION
lCorroded,connecrions,
c. HOUR METER (1) START (2) FINISH etc.

I
1 7. AUTOMATIC TRANSFER PANEL (See Note 1)
f. INSPECTION TEST OPERATOR g. DATE REMARKS

a. CONTACTS BURNED
h. BASE/POST i. UNIT

’ b. MECHANISM BINDING
2. ALTERNATOR DATA
m. MAKE b. MODEL
I c . WIRINQ DAMAQED

:. SERIAL NUMBER d. KW RATING d. COMPONENTS


OVERHEATED
a. VOLTS f. PHASE 8. COOLING SYSTEM (See /Vote 21
. a. TEMP. DURING STANDBY’ b. TEMP. DURING OPERATIONS
8. SHOP SUPERVISOR h. DATE
c. COOLANT ADDED (Level) d. ANTIFREEZE PROTECTION (See
I. LOCATION (Building) j. RECORD IDENT NUMBER Note 3)

e. FAN BELT CONDITION f. RADIATOR AND LOUVER CON-


3. GENERAL CONDITIONS (See /Vote 1) DITION

U N REMARKS 9. LUBE OIL SYSTEM


a. OIL CHANGED /XI b. OIL ADDED (Sum level)
II. CLEANLINESS
YES NO YES NO

b. EXHAUST c. LUBE OIL CONDITION Wiscosifyl d. LEVEL IN GOVERNOR


CONDITION
ITEM (See Note 21 ALTERNATOR EXCITER
c. ENGINE VIBRATION
. 10. KW LOAD
d. LOOSE ITEMS
- (Bolts. Linkage, etc. I PHl PH2 PH3
11. AMPERAGE
c. TURBO VIBRATION
PHl PH2 PH3
12. VOLTAGE
f. WATER LEAKS (XI g. LOCATION OF LEAK
YES NO 13. BRUSHES AND
4. FUEL SYSTEM {See Note 1) BRUSHES RIGGING
S U N REMAFiKS 14. SLIP RING
a. FUEL LEVEL /Day Tank) CONDITION
16. COMMUTATOR
b. FUEL LEVEL (Storage CONDITION
Tank) PHl PH2 PH3
16. VOLTAGE
c. WATER DRAINED fX/ d. FUEL LEAKS /XI /Commercial)
YES NO YES NO 17. BATTERY CHARGER
c. LOCATION OF LEAK a. VOLTS b. AMPS

I I
5. BATTERY BANK /See Note 1) 1 18. HYDROMETER 1 19. STARTING AIR 1 20. AMBIENT
U N REMARKS READING Psi) TEMP. l“FI

a. CONNECTIONS
21. FILTER CHANGE
a. LUBE OIL /XI b. FUEL /XI c. AIR INTAKE /XI
b. CLEANLINESS
YES NO YES NO YES NO
22. UNIT STARTED ON /XI
c. ELECTROLYTE LEVEL
1ST TRY 2ND TRY 3RD TRY NOT AT ALL

Use the reverse side of this form and/or 8-l /2 x 1 1” paper if required for additional comments, continuation of item entries (identify by item
number), and for corrective action(s) taken.
NOTE 1: Mark S for Satisfactory, U for Unsatisfactory, N for Normal, or indicate in Remarks column, as applicable.
NOTE 2: Enter data as indicated. Where no instrumentation is provided, indicate Satisfactory, Unsatisfactory, etc., as applicable.
NOTE 3: Enter Antifreeze Protection as the freeze temperature in degrees (F) as indicated on an appropriate hydrometer.

DD FORM 2744, MAY 96 LOCAL REPRODUCTION AUTHORIZED.


TM 5-685/NAVFAC MO-912

I
I
I
I
L
i
--I
1
I

"U.S. G.P.0.:1996-404-611:40009

Das könnte Ihnen auch gefallen