VFD-V Series

CHAPTER 6
Parameters 00-00 00-01 00-02

PARAMETER SUMMARY
Functions Settings Factory Customer Setting Factory setting Factory setting 0

System Parameter 00

Identity Code

= =

00-03

00-04

set according to different model types Rated Current Display set according to different model types Parameter Reset 10: parameter reset (60Hz) 9: parameter reset (50Hz) bit 0=1: unable to read the parameter bit 1=1: unable to change the frequency and torque commands bit 2=1: unable to operate the digital keypad Star-up Display of the 0: F (frequency command) Drive 1: H (output frequency) 2: U (multi-function display of 00-04) 3: output current Definitions of the 0: output voltage Multi-Function 1: DC-BUS voltage Display 2: voltage command 3: multi-step speed 4: step speed of the procedure operation 5: remaining time of the execution on the procedure operation 6: remaining number of times for the abnormal start-up 7: counter value 8: torque loading 9: power factor 1.000 10: power factor angle 0~180 11: output power Kw 12: output Kvav 13: motor speed rpm 14: power module temperature 15: braking resistor temperature 16: digital terminal input status 17: PID output command 18: PID feedback 19: the q axis voltage 20: the d axis voltage 21: magnetic flux 22: overload accumulated time
6-1

6
0

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

VFD-V Series

Parameters 00-04

Functions Definitions of the Multi-Function Display

Settings 23: accumulated time of the electronic thermal relay 24: execution time of the multi-step speed 25: quiescence stage 26: over-torque accumulated time 27: DC braking time 28: compensated voltage 29: slip compensated frequency 30: number of the pg operation times 31: pg location 32: remaining points of the location control 33: DC voltage at breakdown 34: the output AC voltage at breakdown 35: the output frequency at breakdown 36: the current value at breakdown 37: the frequency command at breakdown 38: day (power-up time) 39: hour, minute 40: the upper bound frequency value 41: over-torque level 42: stall level limitation 43: torque compensation gain 44: torque limitation 45: the q axis current 46: pg frequency 4 words: 0~3 (decimal) 3~0 words: 40~9999 Read-only 0~9999 0~9999

Factory Customer Setting 0

= = = =

00-05 00-06 00-07 00-08 00- 09

User-Defined Coefficient Setting Software Version Password Input Password Setting

0 0 0

The Frequency Bit0=0: controlled by the up/down Setting and Operation key of PU05 Bit0=1: press the data/prog key and then set the frequency Bit1=0: PU05&RS485 frequency memorized Bit1=1: PU05&RS485 frequency not memorized
6-2

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

VFD-V Series

Parameters 00-09

Functions

Settings

00-10

00-11

= =

00-12

00-13

00-14

= = = =

00-15 00-16 00-17

The Frequency Bit2=0: up/down pin frequency Setting and Operation memorized of PU05 Bit2=1: up/down pin frequency not memorized Bit3=0: FWD/REV memorized Bit3=1: FWD/REV not memorized Bit4=0: parameter memorized Bit4=1: parameter not memorized Control Methods 0: V/F control 1: V/F control + PG 2: vector control 3: vector control + PG 4: torque control 5: torque control + PG V/F Voltage Mode 0: FWD/REV do not skip the start-up frequency 1: FWD/REV skip the start-up frequency 2: V/F1.5 power curve (do not skip) 3: V/F1.5 power curve (skip) 4: 2 power curve (do not skip) 5: 2 power curve (skip) Constant torque 0: OL (100%) constant torque operation selection operation 1: OL (125%) variable torque operation Optimal Accel/Decel 0: Linear accel/decel 1: Auto accel, linear decel Setting: follow the maximum 2: Linear accel, auto decel speed-tracing current 3: Auto accel/decel and the over-voltage 4: Auto accel/decel (Please refer to stall prevention P01-12 ~P01-19) Accel/Decel and the S 0: unit: 0.01 sec 1: unit: 0.1 sec Curve Time Unit Carrier Frequency 0: soft pwm Upper Bound 1~15KHz Carrier Frequency 1~15KHz Lower Bound Center Frequency of 1~7KHz Soft pwm Automatic Voltage Regulation (AVR) 0: AVR function enabled 1: AVR function disabled 2: AVR function disabled when decel
6-3

Factory Customer Setting 0

0 15 10 3

00-18

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

VFD-V Series

Parameters

Functions Auto Energy-Saving Operation

Settings

00-19

00-20

= =

00-21

00-22 00-23

BIT0=0: No auto energy-saving operation BIT0=1: auto energy-saving operation BIT1=0: maximum output voltage will be equal to the input power voltage BIT1=1: maximum output voltage could be greater than the input power voltage (over-modulation available) Source of the 0:Via the digital keypad Frequency Command 1:Via the RS485 communication input 2:Via the external analog input 3:Via the external up/down pin (multi-function input terminal) 4:Via the clock, not including direction command 5:Via RS485/PU05 at the same time 6:Via the clock, direction is set from 10-12 Source of the 0: via the RS485 Operation Command communication/the digital keypad operation 1: via the external terminal/the digital keypad operation 2: via the digital keypad operation Stop Methods 0: ramp to stop 1: coast to stop Reverse Operation 0: REV enabled Inhibited 1: REV disabled 2: FWD disabled

Factory Customer Setting 0

0 0

Basic Parameter 01 Parameters 01-00 01-01 01-02 01-03 01-04

Functions

Settings 50.0~400.00Hz 0.00~400.00Hz 0.0~255.0*V 0.00~400.00Hz 0.0~255.0*V

Maximum Operation Frequency Setting of the 1st Output Frequency Setting of the 1st Output Voltage Setting of the 2nd Output Frequency Setting of the 2nd Output Voltage
6-4

Factory Customer Setting 60.00/ 50.00 60.00/ 50.00 220.0* 0.50 5.0*

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

VFD-V Series

Parameters 01-05 01-06 01-07 01-08 01-09 01-10 01-11 01-12 01-13 01-14 01-15 01-16 01-17 01-18 01-19 01-20 01-21 01-22 01-23 01-24 01-25 01-26 01-27 01-28 01-29 01-30

Functions Setting of the 3rd Output Frequency Setting of the 3 Output Voltage Setting of the 4 Output Frequency Setting of the 4 Output Voltage Startup Frequency Upper Bound Frequency Lower Bound Frequency The 1 Accel Time The 1st Decel Time The 2nd Accel Time The 2nd Decel Time The 3rd Accel Time The 3rd Decel Time The 4th Accel Time The 4th Decel Time JOG Accel Time JOG Decel Time JOG Frequency 1st/4th Accel/Decel Frequency S-Curve in Accel Departure Time S-Curve in Accel Arrival Time S-Curve in Decel Departure Time S-Curve in Decel Arrival Time Inhibit the Frequency Setting Upper Bound 1 Inhibit the Frequency Setting Lower Bound 1 Inhibit the Frequency Setting Upper Bound 2
6-5
st th th rd

Settings 0.00~400.00Hz 0.0~255.0*V 0.00~400.00Hz 0.0~255.0*V 0.00~400.00Hz 0.0~110.0% 0.0~100.0% 0.00~6000.0 Sec 0.00~6000.0 Sec 0.00~6000.0 Sec 0.00~6000.0 Sec 0.00~6000.0 Sec 0.00~6000.0 Sec 0.00~6000.0 Sec 0.00~6000.0 Sec 0.00~6000.0 Sec 0.00~6000.0 Sec 0.00 Hz~400.00Hz 0.00 Hz~400.00Hz 0.00~250.0 Sec 0.00~250.0 Sec 0.00~250.0 Sec 0.00~250.0 Sec 0.00~400.00Hz 0.00~400.00Hz 0.00~400.00Hz

Factory Customer Setting 0.50 5.0* 0.00 0.0* 0.50 100.0 0.0 10.00/ 60.00 10.00/ 60.00 10.00/ 60.00 10.00/ 60.00 10.00/ 60.00 10.00/ 60.00 10.00/ 60.00 10.00/ 60.00 10.00/ 60.00 10.00/ 60.00 6.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

= = = = = = = = = = = = = = = = = = =

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

VFD-V Series

Parameters 01-31 01-32 01-33

Functions Inhibit the Frequency Setting Lower Bound 2 Inhibit the Frequency Setting Upper Bound 3 Inhibit the Frequency Setting Lower Bound 3

Settings 0.00~400.00Hz 0.00~400.00Hz 0.00~400.00Hz

Factory Customer Setting 0.00 0.00 0.00

Digital Output/Input Parameter 02 Parameters Functions 02-00

02-01

02-02

02-03

02-04

Factory Customer Setting 2-Wire/3-Wire 0, 1: 2-wire operation control (1) 0 Operation Control Bit 0 = 1 lock power on 2, 3: 2-wire operation control (2) 4, 5: 3-wire operation control Multi-Function Input 0: no functions 1 Command 1 (of the 1: multi-step speed command 1 STOP-specific terminal 2: multi-step speed command 2 at the 3-wire operation) 3: multi-step speed command 3 (MI1) 4: multi-step speed command 4 5: Reset Multi-Function Input 6: JOG command 2 Command 2 (MI2) 7: accel/decel speed inhibited 8: the 1st, 2nd accel/decel time selection 9: the 3rd, 4th accel/decel time selection 10: EF input Multi-Function Input 12: B.B. traces from the bottom 3 Command 3 (MI3) upward 13: B.B. traces from the top downward 14: cancel the setting of the optimal accel/decel speed 15: switch between drives 1 and 2 16: operation speed command form AVI Multi-Function Input 17: operation speed command 4 Command 4 (MI4) from ACI 18: operation speed command from AUI 19: forced stop 20: UP Command 21: Down Command
6-6
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

Settings

VFD-V Series

Parameters 02-05

Functions Multi-Function Input Command 5 (MI5)

Settings

02-06

22: auto procedural operation function disabled 23: auto procedural operation suspended 24: PID function disabled 25: counter cleared 26: input the counter value (multi-function input command 6) Multi-Function Input 27: FWD JOG command Command 6 28: REV JOG command (TRG-specific terminal) 29: braking module breakdown (MI6) 30: location control UP/DOWN key mode

Factory Customer Setting 5

10

02-07

= = = =

02-08

02-09 02-10 02-11

Bit 0 0:UP/DOWM following the 0 accel/decel time 1:UP following the constant Bit 1 speed, and DOWN following the decel time 0:UP following the accel time, and DOWN following the constant speed 1:UP/DOWN following the constant speed The Accel/Decel Speed 0.01~1.00Hz/msec 0.01 Rate of the UP/DOWN Key with Constant Speed Digital Input 0.001~30.000 Sec 0.005 Responding Time Digital Input Operation 0~255 0 Direction Bit 0~7=1 high active 0 Multi-Function Output 1 1: indication during operation RA, RB, RC (Relay1) 2: operation speed reaches 1 (two-way) 3: operation speed reaches 2 (two-way) 4: pre-set speed reaches 1 (two-way) 5: pre-set speed reaches 1 (one-way) 6: pre-set speed reaches2 (two-way) 7: pre-set speed reaches 2 (one-way)
6-7

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

VFD-V Series

Parameters

Functions

Settings

02-12

02-13

02-14

= = = =

02-15 02-16

02-17 02-18

Multi-Function Output 2 10: zero speed MRA, MRC 11: over-torque(oL2) (Relay2) 12: base block (B.B.) 13: drive ready for use 14: low voltage alarm (LV) 15: error indication 16: drive operation mode 17: auto operation command 18: auto operation suspended Multi-Function Output 3 19: the 1st stage operation (MO1) completed 20: auto operation completed 21: pre-set counter value achieved 22: designated counter value achieved 23: heat sink overheat warning 24: operation frequency reaches 1 (two-way) 25: operation frequency reaches 2 (two-way) 26: pre-set frequency reaches 1 (two-way) Multi-Function Output 4 27: pre-set frequency reaches 2 (MO2) (one-way) 28: pre-set frequency reaches 1 (two-way) 29: pre-set frequency reaches 2 (one-way) 30: software braking output 31: location achieved 32~47: auto operation stage indication 48~63: multi-stage indication 64: PG Fault 69: over-torque(oL3) 0: no functions Multi-Function Output 0~15 (1 high) Direction Counter Values 0~65500 Achieve the Pre-Set Values Designated Counter 0~65500 Value Achieved Digital Output Gain 1~40

Factory Customer Setting 0

0 0

0 1

6-8

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

VFD-V Series

Parameters

Functions Arbitrary Arrival Frequency 1 Arbitrary Arrival Frequency 1 Width Arbitrary Arrival Frequency 2 Arbitrary Arrival Frequency 2 Width

Settings 0.00~400.00HZ 0.00~400.00HZ 0.00~400.00HZ 0.00~400.00HZ

= = = =

02-19 02-20 02-21 02-22

Factory Customer Setting 60.00/ 50.00 2.00 60.00/ 50.00 2.00

Analog Output/Input Parameter 03 Parameters Functions

Settings

= = =

03-00

Analog Input 1 (AVI)

03-01

Analog Input 2 (ACI)

03-02

Analog Input 3 (AUI)

= = = =

03-03 03-04 03-05 03-06

Analog Input Bias Voltage 1 (AVI) Analog Input Bias Voltage 2 (ACI) Analog Input Bias Voltage 3 (AUI) AVI Positive/Negative Bias Voltage Mode

0: no functions 1: frequency/torque command 2: torque limitations 3: accel/decel time gain 4: upper bound frequency 0 5: over-torque current level 6: torque compensation gain 7: over-current stall prevention level during operation 8: torque compensation(Vector) 0 9: AVI auxiliary frequency (multiplication by the ratio of AVI) 10: ACI auxiliary frequency (multiplication by the ratio of ACI) 11: AUI auxiliary frequency (multiplication by the ratio of AUI) -10.00~10.00V 0.00 0.00~20.00mA -10.00~10.00V 0: bias voltage as the center 1: lower than bias voltage = bias voltage 2: greater than bias voltage = bias voltage 3: absolute value of the bias voltage while serving as the center

Factory Customer Setting 1

4.00 0.00 0

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

6-9

VFD-V Series

Parameters

Functions ACI Positive/Negative Bias Voltage Mode

Settings

03-07

03-08

AUI Positive/Negative Bias Voltage Mode

= = = = = = =

03-09 03-10 03-11 03-12

03-13 03-14

03-15

Analog Input 1 Gain (AVI) Analog Input 2 Gain -500.0~+500.0% (ACI) Analog Input 3 Gain -500.0~+500.0% (AUI) Addition Function of the 0: addition disabled (AVI, ACI, Analog Input AUI) 1: addition enabled Wave Filtering Time of 0.00~2.00 Sec the Analog Input Handling the ACI 0: not to deal with it Power-Off Situation 1: operate with the same frequency before the power-off 2: stop 3: E.F. stopped instantly Analog Output Selection 0: output frequency 1: command frequency 2: speed 3: current 4: output voltage 5: DC BUS voltage 6: power factor 7: power 8: torque 9: AVI 10: ACI 11: AUI 12: torque current command
6-10

0: bias voltage as the center 1: lower than bias voltage = bias voltage 2: greater than bias voltage = bias voltage 3: absolute value of the bias voltage while serving as the center 0: bias voltage as the center 0 1: lower than bias voltage = bias voltage 2: greater than bias voltage = bias voltage 3: absolute value of the bias voltage while serving as the center -500.0~+500.0% 100.0 125.0 100.0 0

Factory Customer Setting 1

0.10 0

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

VFD-V Series

Parameters

Functions

Settings

03-15

= = =

03-16 03-17 03-18

Analog Output Selection 13: torque current estimation 14: exciting magnet current command 15: magnetic flux current 16: Q-axis voltage command 17: D-axis voltage command 18: vector-controlled error measures 19: vector-controlled PID overall measures 20: PID error measures 21: PID total measures 22: torque command 23: pg frequency 24: voltage command Analog Output Gain -900.0~900.0% Analog Output Bias -10.00~10.00V Voltage Analog in REV Direction 0: absolute value of the output Enabled voltage 1: output 0V in REV direction 2: output negative voltage in REV direction enabled

Factory Customer Setting 0

100.0 0.00

6
0

Multi-Step Speed and Procedural Operation Parameter 04 Parameters Functions Settings

= = = = = = = = = = = = =

04-00 04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10 04-11 04-12

The 1st Step Speed The 2 Step Speed The 3rd Step Speed The 4 Step Speed The 5 Step Speed The 6 Step Speed The 7 Step Speed The 8th Step Speed The 9 Step Speed The 10 Step Speed The 11 Step Speed The 12 Step Speed The 13th Step Speed
th th th th th th th th nd

0.00~400.00Hz 0.00~400.00Hz 0.00~400.00Hz 0.00~400.00Hz 0.00~400.00Hz 0.00~400.00Hz 0.00~400.00Hz 0.00~400.00Hz 0.00~400.00Hz 0.00~400.00Hz 0.00~400.00Hz 0.00~400.00Hz 0.00~400.00Hz
6-11

Factory Customer Setting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

VFD-V Series

Parameters

Functions The 14th Step Speed The 15 Step Speed


th

Settings 0.00~400.00Hz 0.00~400.00Hz

= =

04-13 04-14 04-15 04-16 04-17 04-18 04-19 04-20 04-21 04-22 04-23 04-24 04-25 04-26 04-27 04-28 04-29 04-30 04-31 04-32 04-33

Factory Customer Setting 0.00 0.00 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 10 0 0

Time Duration of the PLC 0.0~65500 Sec Master Speed Time Duration of PLC Step 1 0.0~65500 Sec Time Duration of PLC Step 2 0.0~65500 Sec Time Duration of PLC Step 3 0.0~65500 Sec Time Duration of PLC Step 4 0.0~65500 Sec Time Duration of PLC Step 5 0.0~65500 Sec Time Duration of PLC Step 6 0.0~65500 Sec Time Duration of PLC Step 7 0.0~65500 Sec Time Duration of PLC Step 8 0.0~65500 Sec Time Duration of PLC Step 9 0.0~65500 Sec Time Duration of PLC Step 10 0.0~65500 Sec Time Duration of PLC Step 11 0.0~65500 Sec Time Duration of PLC Step 12 0.0~65500 Sec Time Duration of PLC Step 13 0.0~65500 Sec Time Duration of PLC Step 14 0.0~65500 Sec Time Duration of PLC Step 15 0.0~65500 Sec The PLC Time Multiple Auto Procedural Operation Mode 1~10 bit0=0: direction determined by 04-32 bit0=1: direction determined by the master speed Bit1=0: auto operation mode continues running Bit1=1: auto operation motion disabled after one operation cycle Bit2=0: no intervals during the auto operation Bit2=1: zero speed intervals during the auto operation Bit3=0: operate at zero speed when HOLD The PLC Operation Direction 0~32767 (0: FWD; 1: REV)

6-12

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

VFD-V Series

Parameters 04-33

Functions Auto Procedural Operation Mode

Settings Bit3=1: operate at a constant step speed when HOLD Bit4=0: PLC disabled Bit4=1: PLC enabled bit0=0: direction determined by 04-32 bit0=1: direction determined by the master speed Bit1=0: multi-step speed continues running Bit1=1: multi-step speed disabled after one step speed cycle Bit2=0: no zero speed intervals during the operation Bit2=1: zero speed intervals during the operation

Factory Customer Setting

04-34

Multi-Step Speed Operation Mode

Motor Modulation Parameter 05 Parameters Functions 05-00

Settings

05-01 05-02

= =

05-03

05-04 05-05 05-06 05-07 05-08

Auto Measures of the Motor 0: no function Parameters 1: measures (R1, R2, Lm, Lc, no-load current) 2: auto measures (R1, R2, Lc) 3: auto measures (R1, R2, Lc, Lm, calculated by the motors no-load current) Full-Load Current of Motor ****A (30~120%) A 1 (100%) No-Load Current of Motor 1 XXXA (5~90%) A (40%) Torque Compensation of 0.0~25.0% 0.0 Motor 1 (for the V/F Mode Only) Slip Compensation of Motor 0.0~10.0% 0.0 1 (for the V/F Mode Only) Pole Number of Motor 1 2~20 4 Parameter R1 of Motor 1 Parameter R2 of Motor 1 Parameter LM of Motor 1

Factory Customer Setting 0

8 m8
m MH

Xx Xx Xx

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

6-13

VFD-V Series

Parameters

Functions Parameter LC of Motor 1 Iron Loss of Motor 1 MH 0.0~10.0%

Settings

= = =

05-09 05-10 05-11 05-12 05-13

Factory Customer Setting Xx 0.0 A (100%) A (40%) 0.0

Full-Load Current of Motor ****A (30~120%) 2 No-Load Current of Motor 2 XXXA 5~90% Torque Compensation of 0.0~25.0% Motor 2 (for the V/F Mode Only) Slip Compensation of Motor 0.0~10.0% 2 (for the V/F Mode Only) Pole Number of Motor 2 2~20 Parameter R1 of Motor 2 Parameter R2 of Motor 2 Parameter LM of Motor 2 Parameter LC of Motor 2 Iron Loss of Motor 2 ASR P Gain 1 Auto Speed Regulation (ASR) Gain (P) 1 ASR I Integration Time 1 Integration (I) Time 1 ASR P Gain 2 ASR I Integration Time 2

05-14 05-15 05-16 05-17 05-18 05-19 05-20 05-21

0.0 4 Xx Xx Xx Xx 1.5 25.0

8 m8
m MH MH

= = = = = = = = = = =

0.0~10.0% 0.0~500.0%

05-22 05-23 05-24 05-25 05-26 05-27 05-28 05-29 05-30

0.000~10.000 Sec 0.000: no integration 0.0~500.0%

0.250 25.0 0.250 7.00 30 50 0.010 100 0

0.000~10.000 Sec 0.000: no integration Frequency Switch between 0.00~400.00Hz ASR1 and 2 Low-Speed Exciting 0~100% Magnet Compensation The Torque Pre-Controlled 0~100% Feedback One-Time Delay of the 0.000~2.000 Sec Pre-Controlled Feedback Vibration Compensation 0~10000 Factor Vector-Controlled R1 0: no R1 detection Detection Activation 1: R1 detection

6-14

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

VFD-V Series

Protection Parameter 06 Parameters Functions

Settings 160~220V* 350.0~450.0V* 0: warning and keep on operating less than 50% 1: warning and ramp to stop 2: warning and coast to stop 20~250% 20~250%

= = = = = = =

06-00 06-01 06-02

Low Voltage Level Over Voltage Stall Prevention Phase-Lacking Protection

Factory Customer Setting 180 380.0* 0

06-03 06-04

06-05 06-06

Over-Current Stall Prevention during Accel Over-Current Stall Prevention during Operation Over-Current Decel Time during Operation Selection on the Over-Torque Detection Function

170 170

0.05~600.00 Sec 0: not to detect 1: over-torque detection during constant speed operation, (oL2) keeps on operating 2: over-torque detection during constant speed operation, (oL2) stopped operating 3: over-torque detection during operation, (oL2) keeps on operating 4: over-torque detection during operation, (oL2) stopped operating 20~250% 0.0~60.0 Sec

3.00 0

= =

06-07 06-08

Over-Torque Detection Level Over-Torque Detection Time

150 0.1

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

6-15

VFD-V Series

Parameters

Functions Over-Torque Detection Selection 2

Settings 0:no detection 1:over-torque detection during constant speed operation, (oL3) keeps on operating 2:over-torque detection during constant speed operation, (oL3) stopped operating 3:over-torque detection during operation, (oL3) keeps on operating 4:over-torque detection during operation, (oL3) stopped operating 10~250%

06-09

Factory Customer Setting 0

= = = = = =

06-10

Over-Torque Detection Level 2

150

06-11

Over-Torque Detection Time 2

0.0~60.0 Sec

0.1

06-12

Electronic Thermal Relay Selection

0: inverter-specific motor 1: standard motor 2: electronic thermal relay not available 30~600 Sec 0.0~110.0 0: no fault 1: oc (over-current) 2: ov (over-voltage) 3: oH1 (IGBT overheat) 4: oL (drive overload) 5: oL1 (electronic thermal relay) 6: EF (external fault) 7: CF3 (hardware circuit fault) 8: HPF (protection circuit fault)

06-13 06-14 06-15

Duration Time of the Electronic Thermal Relay Heat Sink Overheat Warning 1st Most Recent Fault Record

60 85.0 0

6-16

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

VFD-V Series

Parameters

Functions 2nd Most Recent Fault Record

Settings 9: ocA (over-current during accel) 10: ocd (over-current during decel) 11: ocn (over-current during constant speed) 12: GFF (ground fault) 13: pg error 14: Lv (low voltage) 15: CF1 (write-in fault) 16: CF2 (read-out fault) 17: bb (base block) 18: oL2 (motor overload) 19: sc (driving module fault) 20: bF (braking transistor fault) 21: OL3 (motor overload) 22: 0h2 (brake overheat) 23: fuse 24: CT2 (current sensor 2) 25: CT1 (current sensor 1) 26: PWM (upper and lower arms at the same low level) 27: auto tuning (motor parameter) 28: pid err 29: ACI err 31: CC 33: VEC R1 out of range (Pr. 05-30) 34: keypad err 35: RS485 over time 36: FAN fault 37: input phase loss

06-16

Factory Customer Setting 0

06-17

3rd Most Recent Fault Record

06-18

4th Most Recent Fault Record

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

6-17

VFD-V Series

Special Parameter 07 Parameters

Functions

Settings 350.0~450.0VDC* 0~100% 0.00~60.00 Sec 0.00~400.00Hz 1~500

= = = = = = = = = = = = =

07-00 07-01 07-02 07-03 07-04 07-05 07-06

The Software Braking Level DC Braking Current Level Stop the DC Braking Time Start/Stop Frequency of DC Braking Increasing Rate of the DC Voltage Re-activate after Momentary Power Loss Maximum Loss Time B.B. Time for Speed Search

Factory Customer Setting 380.0* 0 0.00 0.00 0.00 30 0

Activate the DC Braking Time 0.00~60.00 Sec

07-07 07-08 07-09 07-10 07-11 07-12

0: invalid 1: traces from top down 2: traces from bottom up Allowable Power 0.1~5.0 Sec 0.1~5.0 Sec

2.0 0.5 150 3.00 0

Maximum Current Level for 20~200% Speed Search Decel Time for Speed Search 0.50~600.00 Sec Auto Restart after Fault Activate the Speed Search 0~10

= = = = = =

07-13 07-14 07-15 07-16 07-17 07-18

0: speed search not 0 activated 1: speed search through the frequency command 2: FWD-speed search 3: REV-speed search 4: FWD/REV speed search 5: REV/FWD speed search Forwardly activate the speed 0.00~400.00Hz 60.00/ search frequency 50.00 Reversely activate the speed 0.00~400.00Hz 60.00/ search frequency 50.00 Gear Gap Accel-Interruption 0.00~400.00 Sec 0.00 Time Gear Gap Accel-Interruption 0.00~400.00Hz 6.00 Frequency Gear Gap Decel-Interruption 0.00~400.00 Sec 0.00 Time Gear Gap Decel-Interruption 0.00~400.00Hz 6.00 Frequency

6-18

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

VFD-V Series

High-Performance Parameter 08 Parameters Functions

Settings

08-00

= = = = = = = = = = = =

PID Feedback Terminal 0: not functioning Selection 1: input through the 0~10V terminals (AVI) 2: input through the 4~20mA terminals (ACI) 3: input through the +/-10V terminals (AUI) 4: input through the clock (Fwd/Rev is decided by master speed) 5: input through the clock (Fwd/Rev is decided by A/B direction) Proportional Gain (P) Integral Time (I) Differential Time (D) 0.0~500.0% 0.00~100.00 Sec 0.00: no integral 0.00~1.00 Sec

Factory Customer Setting 0

08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09

80.0 1.00 0.00 100.0 100.0 0.0 0.000 0.0 0

Upper Bound for the 0.0~100.0% Integral Time Restrictions on the PID 0.0~100.0% Output Command PID Deviation Range -100.0~+100.0% One-Time Delay 0.000~0.005 Sec Detection Time of the 0.0~6000.0 Sec Feedback Error Feedback Signal Fault 0: warning and keep on operating Treatment 1: warning and RAMP to stop 2: warning and COAST to stop Latent Frequency 0.00~400.00Hz Revival Frequency Latent Period 0.00~400.00Hz 0.0~6000.0 Sec

08-10 08-11 08-12

0.00 0.00 0.0

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

6-19

VFD-V Series

Communication Parameter 09 Parameters Functions

Settings 1~254 4.8~115.2 Kbits/Sec

= = = = =

09-00 09-01 09-02

Communication Address Transmission Speed of the Communication Transmission Fault Treatment

Factory Customer Setting 1 9.6 3

09-03 09-04

0: warning and keep on operating 1: warning and RAMP to stop 2: warning and COAST to stop 3: no treatment and no display Overtime Detection 0: disabled 1~100 Sec Communication Protocol 0: 7, N, 1 for ASCII 1: 7, N, 2 for ASCII 2: 7, E, 1 for ASCII 3: 7, O, 1 for ASCII 4: 7, E, 2 for ASCII 5: 7, O, 2 for ASCII 6: 8, N, 1 for ASCII 7: 8, N, 2 for ASCII 8: 8, E, 1 for ASCII 9: 8, O, 1 for ASCII 10: 8, E, 2 for ASCII 11: 8, O, 2 for ASCII 12: 8, N, 1 for RTU 13: 8, N, 2 for RTU 14: 8, E, 1 for RTU 15: 8, O, 1 for RTU 16: 8, E, 2 for RTU 17: 8, O, 2 for RTU Keypad Transmission Fault Treatment 0: warning and keep on operating 1: warning and RAMP to stop 2: warning and COAST to stop

0 0

09-05

6-20

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

VFD-V Series

Speed Feedback Parameter 10 Parameters Functions 10-00 10-01 PG Point PG Input (bit2=1 REV) 1~20000

Settings

Factory Customer Setting 600 0

10-02

PG Feedback Signal Fault Treatment

10-03

10-04 10-05 10-06 10-07 10-08 10-09 10-10 10-11 10-12

PG Feedback Signal Fault Treatment Time Rotation Filtration Time 0.001~1.000 Sec PG Slip Range PG Stall Level PG Electrical Gear A PG Electrical Gear B 0.0~50.0% 0.0~115.0% 1~5000 1~5000

0, 1: A, B edge trigger (*4) 2, 3: A clock B direction 4, 5: A, B clock; following the B, A direction 6, 7: A, B level trigger (*2) 0: warning and keep on operating 1: warning and RAMP to stop 2: warning and COAST to stop 0.00~10.00 Sec

0.10 0.010 10.0 110.0 1 1 600 10 0.003 0

PG Location Control 0~60000 Point PG Location Achieving 0~6000 Range Clock Filter Time 0.001~1.000 second Clock Direction A>B When it is 90, it is forward run. A<B When it is 90, it is reverse run. Settings 0.0~500.0% 0.00~100.00 Sec 0.00: no integral 0.00~1.00 Sec 0.00~400.00 Hz 0~20000 0.00~400.00 Hz 0~20000 1~63

Location Control Parameter Parameters Functions 10-13 10-14 10-15 10-16 10-17 10-18 10-19 10-20 Proportional (P) Gain Integral (I) Time Differential (D) Time Orient Speed Creep point Loop Speed Loop Point Dividing Frequency Card PG-05 Output Setting denominator

Factory Customer Setting 50.0 1.00 0.00 5.00 50 1.00 10 1

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

6-21