DESIGN BASIS FOR ELECTRICAL ITEMS S.No. 1.0 1.

1 GENERAL Standards Description 110kV Chayadevi S/S

Relevant IS / IEC / IEEE / CBIP standards & manuals Outdoor 110 123 230 550 25

1.2 1.3 1.4 1.5 1.6 1.7 2.0 2.1 2.2 2.3 2.4 3.0 3.1 3.2 4.0 4.1

Service System Voltage (kV rms) Highest system voltage (kV rms) Power frequency withstand capability (kV rms) Basic insulation level (kV peak) Creepage distance for insulators (mm/kV) MINIMUM CLEARANCES Between Phase and earth (mm) Between phases (mm) Sectional clearance (mm) Ground clearance (mm) FAULT LEVEL PARAMETERS Magnitude of Three Line fault current in kA Duration of fault current (Sec.) BUS BAR ARRANGEMENTS Type of Bus

: : : : : :

: : : :

1100 1100 4000 4600

: :

31.5 3

2.5" IPS AL Tube (As per schedule 40) Lynx

4.2 5.0 5.1 5.2

ACSR Conductor EARTHING SYSTEM Type Magnitude of earth fault current to be considered for earth mat sizing (kA) Time duration for calculation of step & touch potentials (Sec.) Fault time duration for sizing the earthing conductor (Sec.)

: :

Solidly earthed system 31.5 kA

5.3

0.5

5.4

5.5 5.6 5.7 5.8

Type of joint for earth mats Depth of buried conductor (mm) Average soil resistivity (Ohm-m) Area to be covered for laying earthmat

: : : :

Welded joints 600 Refer soil resistivity report Complete fenced area.However fence shall be isolated from main earthing mate

5.9 5.10

Type of conductor & size Material for treated earth electrodes

: :

75 X 8 GI 3M long, 40 mm dia, GI Pipe electrode with treated for transformer neutral and Lightning arrestor 3M long, 40 mm dia, MS Rod electrode for others.

5.11

Material for un-treated earth electrodes

6.0

LIGHTNING PROTECTION SYSTEM

1 OF 11

S.No. 6.1 6.2 6.3 System type Angle of coverage

Description : : :

110kV Chayadevi S/S Lightning masts As per Razevig method 25 x 3 GI flats

Earthing down conductors for Lightning Arrestors and Lightning Protection GENERAL Details of relays and meters Colour & finish of panels Height of all panels with base channels Control cabling philosophy AVAILABLE AUXILIARY SUPPLIES DC supply (V) AC supply (V) CIRCUIT BREAKER Voltage One Minute Power Frequency Voltage Lightning Impulse withstand voltage Normal current SC breaking current Short time withstand current and duration Operating sequence Operating Mechanism Closing and opening device supply voltage Motor supply voltage Auxiliary supply voltage Frequency ISOLATOR Voltage Maximum operating voltage Power frequency with stand voltage Lightning Impulse withstand voltage Normal current Short time current rating Operating voltage of main switch motor Switch type Creepage distance of insulator

7.0 7.1 7.2 7.3 7.4 8.0 8.1 8.2 9.0 9.1 9.2 9.3 9.4 9.5 9.6 9.7 9.8 9.9 9.10 9.11 9.12 10.0 10.1 10.2 10.3 10.4 10.5 10.6 10.7 10.8 10.9

: : : :

As in cable philosophy diagram

: :

110 V, -15% to +10% 230 / 415 +/- 10% at 50 Hz +/- 5%

: : : : : : : : : : : : : : : : : : : : : :

123 kV 230 kV (rms) 550 kVP 1250 A 31.5 kA 31.5 kA for 3 secs O-0.3S-CO-3 min-CO Standalone spring charged. 110 V DC 230 V AC 230 V AC 50 Hz

110 kV 123 kV 230 kV 550 kVP 1250 A 31.5 kA for 3 secs 230 V AC Double break center rotating type 25 mm/kV

2 OF 11

S.No. 10.0 10.11

Description Pole to Pole distance Mechanical interlock : :

110kV Chayadevi S/S 2.7 metre To be provided between main switch and earth switch and respective CB

11.0 11.1 11.2 11.3 11.4 11.5 11.6

CURRENT TRANSFORMER Normal operating voltage Highest system voltage Basic insulation level Power frequency high voltage Short time current rating & duration Normal current

: : : : : : : 110 kV 123 kV 550 kVP 230 kV 31.5 kA for 3 secs 175A for both line CTs and trafo side CTs 50 Hz Refer single line diagram

11.7 11.8 12.0 12.1 12.2 12.3 12.4 12.5 12.6 12.7

Operating frequency CT ratio, No. of cores & accuracy classes POTENTIAL TRANSFORMER Normal operating voltage Highest system voltage Basic insulation level Power frequency high voltage Voltage factor Operating frequency PT Ratio, No. of Cores & accuracy classes for 132kV side LIGHTNING ARRESTOR Rated voltage Nominal discharge current Frequency Discharge current class

: :

: : : : : : :

110 kV 123 kV 550 kVP 230 kV 1.2 continuous & 1.5 for 30 sec 50 Hz Refer single line diagram

13.0 13.1 13.2 13.3 13.4

: 96 kV : : : 10 kA, heavy duty 50 Hz 3

14.0 14.1 14.2 14.3 14.4 14.5 15.0 15.1 15.1.1 15.1.2 15.1.3 15.1.4

Control and relay panel Auxiliary supply for instruments & relays Auxiliary supply for space heaters and illumination Metering, relays & other devices Type of construction Painting Power and control cables Power cable Voltage grade Conductor Insulation Innersheath material

: : : : : : -

: : : :

1100V Aluminium strands PVC Extruded PVC

3 OF 11

S.No. 15.1.5

Description Armouring :

110kV Chayadevi S/S a) Galvanized round MS wire / strips for multi core cables

15.1.6 15.2 15.2.1 15.2.2 15.2.3 15.2.4 15.2.5

Outer Sheath of insulation Control cable Voltage grade Conductor Insulation Innersheath material Armouring

PVC

: : : : :

1100V Copper strands. PVC Extruded PVC Galvanized round MS wire / strips for multi core cables

15.2.6 16.0 16.1

Outer Sheath of insulation Bay marshalling kiosk Construction

PVC

Sheet steel enclosure with minimum thickness of 2 mm.

16.2 16.3 16.4 16.5

Mounting arrangement Enclosure protection AC distribution Paint shade

: :

Free standing type IP-65 with canopy arrangement

:Shall be planned for switchyard equipment. : Bhoruka to indicate

17.0 17.1 17.1.1 17.1.2 17.1.3 17.1.4 17.1.5

Insulators, Hardwares and Connectors Post Insulator Type Nominal Voltage Highest System Voltage Creepage Distance Cantilever Strength : : : : : Solid Core 110 kV 123 kV 25 mm/kV 800 kg for Bus Support 600 kg for Isolator 230 kV 550 kVP

17.1.6 17.1.7 17.2 17.2.1

One (1) minute power frequency voltage Impulse Voltage Clamps and Connectors Sizes

: :

Suitable for 2.5" IPS and Lynx ACSR Conductor Aluminium Smooth Polished and Corona free

17.2.2 17.2.3

Material Finishes

: :

4 OF 11

DESIGN BASIS FOR ELECTRICAL ITEMS 110kV KPTCL S/S

Relevant IS / IEC / IEEE / CBIP standards & manuals Outdoor 110 123 230 550 25

1100 1100 4000 4600

31.5 3

2.5" IPS AL Tube (As per schedule 40)

Lynx

Solidly earthed system 31.5 kA

0.5

Welded joints 600 Refer soil resistivity report Complete fenced area.However fence shall be isolated from main earthing mate

75 X 8 GI 3M long, 40 mm dia, GI Pipe electrode with treated for transformer neutral and Lightning arrestor 3M long, 40 mm dia, MS Rod electrode for others.

5 OF 11

110kV KPTCL S/S Lightning masts As per Razevig method 25 x 3 GI flats

As in the SLDs Bhoruka to indicate Bhoruka to indicate As in cable philosophy diagram

220 V, -15% to +10% 230 / 415 +/- 10% at 50 Hz +/- 5%

123 kV 230 kV (rms) 550 kVP 1250 A 31.5 kA 31.5 kA for 3 secs O-0.3S-CO-3 min-CO Standalone spring charged. 220 V DC 230 V AC 230 V AC 50 Hz

110 kV 123 kV 230 kV 550 kVP 1250 A 31.5 kA for 3 secs NA Double break center rotating type 25 mm/kV

6 OF 11

110kV KPTCL S/S 2 metre To be provided between main switch and earth switch and respective CB

110 kV 123 kV 550 kVP 230 kV 31.5 kA for 3 secs 400A for both line CTs and trafo side CTs

50 Hz Refer single line diagram

110 kV 123 kV 550 kVP 230 kV 1.2 continuous & 1.5 for 30 sec 50 Hz Refer single line diagram

96 kV 10 kA, heavy duty 50 Hz 3

220 V DC 230 V AC As per SLD Simplex Type Bhoruka to indicate

1100V Aluminium strands PVC Extruded PVC

7 OF 11

110kV KPTCL S/S a) Galvanized round MS wire / strips for multi core cables

PVC

1100V Copper strands. PVC Extruded PVC Galvanized round MS wire / strips for multi core cables

PVC

Sheet steel enclosure with minimum thickness of 2 mm.

Free standing type IP-65 with canopy arrangement Shall be planned for switchyard equipment. Bhoruka to indicate

Suitable for 2.5" IPS and Lynx ACSR Conductor Aluminium Smooth Polished and Corona free

8 OF 11

DESIGN BASIS FOR ELECTRICAL ITEMS S.No. 1.0 1.1 GENERAL Standards Description 11kV borad

Relevant IS / IEC / IEEE / CBIP standards & manuals Outdoor 11 28 28 70 25

1.2 1.3 1.4 1.5 1.6 1.7 2.0 3.1 3.2 3.0 3.1 4.0 4.1 4.2

Service System Voltage (kV rms) Highest system voltage (kV rms) Power frequency withstand capability (kV rms) Basic insulation level (kV peak) Creepage distance for insulators (mm/kV) FAULT LEVEL PARAMETERS Magnitude of Three Line fault current in kA Duration of fault current (Sec.) BUS BAR ARRANGEMENTS Type of Bus EARTHING SYSTEM Type Magnitude of earth fault current to be considered for earth mat sizing (kA) Fault time duration for sizing the earthing conductor (Sec.) AVAILABLE AUXILIARY SUPPLIES DC supply (V) AC supply (V) CIRCUIT BREAKER Type Voltage

: : : : : :

: :

40 3

Aluminium busbar rated for 2500 A

: :

Non-effectively earthed 40 kA

4.3

5.0 5.1 5.2 6.0 6.1 6.2

: :

110 V, -15% to +10% 230 / 415 +/- 10% at 50 Hz +/- 5%

: :

SF6/ VCB 12 kV

9 of 11

6.3 6.4 6.5 6.6 6.7 6.8 6.9 6.10 6.11 6.12 6.13 7.0 7.1 7.2 7.3 7.4 7.5 7.6 7.7 8.0 8.1 8.2 8.3 8.4 8.5

One Minute Power Frequency Voltage Lightning Impulse withstand voltage Normal current SC breaking current Short time withstand current and duration Operating sequence Operating Mechanism Closing and opening device supply voltage Motor supply voltage Auxiliary supply voltage Frequency LOAD BREAK SWITCH Voltage Maximum operating voltage Power frequency with stand voltage Lightning Impulse withstand voltage Normal current Short time current rating Operating mechanism CURRENT TRANSFORMER Normal operating voltage Highest system voltage Basic insulation level Power frequency high voltage Short time current rating & duration

: : : : : : : : : : : : : : : : : : : : : : : : :

28 kV (rms) 70 kVP 2500 A 40 kA 40 kA for 3 secs O-0.3S-CO-3 min-CO Standalone spring charged. 110 V DC 240 V AC 240 V AC 50 Hz

11 kV 12 kV 28 kV 70 kVP 200 A 40 kA for 3 secs Manual

11 kV 12 kV 70 kVP 7028 40 kA for 1 sec

10 of 11

8.6

Normal current

1800A for trafo CTs and 40 A for UAT CTs 50 Hz Refer single line diagram

8.7 8.8 9.0 9.1 9.2 9.3 9.4 9.5 9.6 9.7

Operating frequency CT ratio, No. of cores & accuracy classes for 132kV side POTENTIAL TRANSFORMER Normal operating voltage Highest system voltage Basic insulation level Power frequency high voltage Voltage factor Operating frequency PT Ratio, No. of Cores & accuracy classes for 132kV side

: :

: : : : : : :

11 kV 12 kV 70 kVP 28 kV 1.2 continuous & 1.5 for 30 sec 50 Hz Refer single line diagram

11 of 11