Sie sind auf Seite 1von 70

ROI-S04451-056E 030908

P N M T

ASOLINK

ETWORK

Operation Manual
PASOLINK+ (SDH/STM-0) version

ANAGEMENT

ERMINAL

NEC Corporation
Copyright 2003

ROI-S04451

Table of Contents
1. GETTING STARTED................................................................................................................... 1
1.1 INTRODUCTION ................................................................................................................................. 1 1.2 CONVENTIONS USED IN THIS MANUAL ............................................................................................ 1 1.3 PNMT COMMUNICATION INTERFACES ............................................................................................ 2 1.3.1 Communications....................................................................................................................... 2 1.4 HARDWARE CONFIGURATION FOR MOBILE TERMINAL (PNMT) ..................................................... 3 1.5 SOFTWARE CONFIGURATION FOR MOBILE TERMINAL (PNMT)....................................................... 4

2.

SYSTEM OPERATION & MAINTENANCE............................................................................ 5


2.1 THE PNMT SCREEN ......................................................................................................................... 5 2.2 LAUNCHING THE PNMT APPLICATION. ........................................................................................... 7 2.3 LOGIN ............................................................................................................................................... 8 2.3.1 User Level Privilege ................................................................................................................. 9 2.4 LOGOUT .......................................................................................................................................... 10 2.5 SHUTTING DOWN THE PNMT......................................................................................................... 10 2.6 SEARCHING FOR NETWORK ELEMENTS AND CONNECTING TO SELECTED PASOLINK .................... 11 2.7 CHANGE PASSWORD ....................................................................................................................... 11 2.8 ALARM BUZZER SETTING ............................................................................................................... 12 2.9 REFRESH ......................................................................................................................................... 13 2.10 REMOTE VIEWING PNMT (LINK SUMMARY) WINDOW ................................................................. 14 2.11 OVERALL TAB ................................................................................................................................ 15 2.12 ODU TAB ....................................................................................................................................... 17 2.12.1 ODU Tab ................................................................................................................................ 17 2.13 IDU TAB......................................................................................................................................... 19 2.13.1 IDU Tab .................................................................................................................................. 19 2.14 CLK TAB ........................................................................................................................................ 22 2.15 AUXILIARY I/O TAB ....................................................................................................................... 23 2.15.1 Monitored Items ..................................................................................................................... 23 2.15.2 Optocoupler Input Setting ...................................................................................................... 24 2.15.3 Relay Output Setting .............................................................................................................. 25 2.15.4 Relay Configuration ............................................................................................................... 25 2.16 VERSION TAB ................................................................................................................................. 26 2.16.1 Version Monitor...................................................................................................................... 26 2.17 CONTROL (CTRL) TAB .................................................................................................................. 28 2.17.1 The Control Module ............................................................................................................... 28 2.17.2 CPU Reset .............................................................................................................................. 29 2.17.3 Downloading the Configuration Files to the Control Module................................................ 29 2.17.4 Downloading a new Program File to the Control Module...................................................... 31 2.17.5 Uploading Control Module Configuration file to PNMT PC ................................................. 32 2.18 MAINTENANCE ............................................................................................................................... 32 2.18.1 Maintenance Menu ................................................................................................................. 33 2.18.2 Selecting Maintenance Mode ................................................................................................. 34 2.18.3 Switching TX (for 1+1 system only) ...................................................................................... 34 2.18.4 Switching RX (for 1+1 system only)...................................................................................... 34 2.18.5 Main Signal Loopback ........................................................................................................... 34 2.18.6 IF Loopback (local only loopback) ........................................................................................ 35 2.18.7 ALS Restart ............................................................................................................................ 36 2.18.8 Lockout Control...................................................................................................................... 36

-i-

ROI-S04451

2.18.9 Source Select Control ............................................................................................................. 36 2.18.10 Clear WTR Timer.................................................................................................................. 37 2.18.11 Selecting TX Mute Status ..................................................................................................... 37 2.18.12 TX Frequency ....................................................................................................................... 37 2.18.13 RX Frequency ....................................................................................................................... 37 2.18.14 Selecting Carrier Wave Status............................................................................................... 38 2.18.15 ATPC Manual........................................................................................................................ 38 2.19 EQUIPMENT SETUP ......................................................................................................................... 39 2.19.1 Equipment Configuration Window......................................................................................... 39 2.19.2 Setup....................................................................................................................................... 40 2.19.3 Editing the NE Name.............................................................................................................. 41 2.19.4 Editing the Note for CTRL..................................................................................................... 41 2.20 PROVISIONING ................................................................................................................................ 42 2.20.1 Provisioning Window ............................................................................................................. 42 2.20.2 MAIN INTFC......................................................................................................................... 43 2.20.3 Overhead (OH) Assignment ................................................................................................... 48 2.20.4 Manual Transmit Power Control (MTPC) Status ................................................................... 49 2.20.5 Automatic Transmit Power Control (ATPC) Status................................................................ 50 2.20.6 SW priority ............................................................................................................................. 52 2.20.7 TX SW Priority....................................................................................................................... 52 2.20.8 RX SW Priority ...................................................................................................................... 52 2.20.9 Sub INTFC ............................................................................................................................. 53 2.20.10 BER Threshold...................................................................................................................... 54 2.21 LINK PERFORMANCE MONITOR ...................................................................................................... 60 2.21.1 Viewing Summary Link Performance Monitor ...................................................................... 60 2.21.2 Threshold setting .................................................................................................................... 61 2.21.3 Link Performance Monitor (Daily Data) window................................................................... 62 2.21.4 Link Performance Monitor (15 min Data) window ................................................................ 62 2.21.5 Section Trace .......................................................................................................................... 63 2.21.6 Section Trace J0 (MUX)......................................................................................................... 64 2.21.7 Section Trace J0 (DMR) ......................................................................................................... 64 2.21.8 Section Trace J1 (MUX)......................................................................................................... 64 2.21.9 Section Trace J1(DMR) .......................................................................................................... 65 2.21.10 Section Trace J2 .................................................................................................................... 65 2.21.11 Signal Label .......................................................................................................................... 65 2.22 EVENT LOG ..................................................................................................................................... 67 2.22.1 2.21.1 Event log monitor ........................................................................................................ 67

- ii -

ROI-S04451

1. Getting Started
1.1 Introduction
The PNMT is a Pasolink Network Management Terminal developed by NEC for management of NECs Pasolink and Pasolink+ radio transmission network. The PNMT is a scaled down version of Pasolink Network Management System (PNMS) that is designed as a maintenance tool for field engineers to locally and remotely monitor alarms, control points, generate repots, and archive data, all within a familiar graphical user interface, and all in real time. The PNMT is a Mobile laptop computer fitted with NEC PNMT software package that interfaces and controls NEC PASOLINK series short haul radio equipment. This Windows-NT/98 based software package remote monitors and controls the status and configuration of an entire PASOLINK network with associated equipment as well as the performance of the actual microwave links.

1.2

Conventions Used in This Manual


What the Font Represents For manual titles or related document names. Items on the user interface. Items on the computer display.
File and directory names.

Font Italic
Hostname Bold

Example Please refer to Pasolink Operation Manual for details.


The Overall window

[Button]

Buttons on the user interface.

Menu Items

<username>

A menu name followed by a colon (:) means that you must select the menu and then item. When the item is followed by an arrow (-> ), a cascading menu follows. A command variable where the user must enter the appropriate value. This is also commonly used when asking for a password. Keyboard keys.

Click on [OK] button to continue Click on [Execute] button to send command. Select System -> Login/Logout

<password>

Keycap

Press Enter key.

-1-

ROI-S04451

1.3
1.3.1

PNMT Communication Interfaces


Communications Communications between the PNMT and the radio network equipment can be via the PNMT Port of the Pasolink equipment, via the DSC to a remote node in the network.

1.3.1.1

PNMT Port Interface On the Pasolink equipment, the PNMT Port is located on the front of the equipment.

ODU

Fig. 1: Connecting the PNMT to Pasolink+ IDU

IDU PNMT port

Pasolink+ IDU

PNMT Cable PNMT

The PNMT Port consists of an RJ-45 connector and connects to Control Module(CTRL) installed in the IDU via a serial cable to the relevant communications port of the PNMT Computer. The PNMT Port has the following properties: Port Configuration: Connector type: Bit per second rate: Stop bits: Data bit length: Parity: RS-232 RJ-45 modular jack 1200/2400/4800/9600/19200 (default 19200) 1 8 no parity.

-2-

ROI-S04451

The following table is the pin assignment of the connection between the IDU PNMT Port and PNMT PC.

PNMT(PC) to Pasolink+ (PNMT port)

3M

9pin(F)

RJ45

PC (PNMT)
RS-232C 1 2 3 4 5 6 7 8 9 DCD RXD TXD DTR GND DSR RTS CTS RI 1 2 3 4 5 6 7 8 9

Pasolink+ PNMT port


RS-232C 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CD TXD RXD DSR GND DTR CTS RTS

Cabling Diagram between PNMT PC and PNMT Port

1.4

Hardware Configuration for Mobile Terminal (PNMT)


Recommended PNMT mobile PC configuration: Laptop PC with TFT DISPLAY (IBM PC or compatible) CPU: Pentium-400 or higher RAM: 128 MB or more HDD: 2 GB or more FDD: 3.5 x 1 CD-ROM: 8 X or higher Display: 800x600 Screen area (16-bit color) Integrated Sound Card + Speaker

-3-

ROI-S04451

1.5

Software Configuration for Mobile Terminal (PNMT)


All structured and modular programs used in PNMT are resident in the hard disk and RAM of the personal computer. The Windows operating system is employed which is capable of multi-task processing using the Pentium microprocessor. The PNMT software basically consists of two parts, the operating system and the application programs . The operating system -Windows 98 (English Version) or -Windows NT Workstation Ver4.0 (English Version) -Windows 2000 (English Version) The application programs -PNMT software Other applications: -Internet Explorer 5.0 or higher -Acrobat Reader (to read Help File with PDF)

-4-

ROI-S04451

System Operation & Maintenance


This chapter explains the menu structure and procedures for operating of the PNMT. The explanation uses typical PNMT screens to illustrate the hierarchy of menu.

2.1

The PNMT Screen


The PNMT window is comprised of the following main parts (Refer to figure 1). For detailed descriptions, refer to the Users Manual for the Windows NT operating system. o Title bar The title bar of the window is used to indicate the title of the window. Common Menu bar The common menu bar of the window presents the System and Help options, illustrates the commands that can be executed from the various options. The Help function also can display the html version of this operation manual. NE-specific Menu bar This menu is a list of tasks that can be performed to the specific network element (NE) displayed in the PNMT. Configuration, Event Log, and Link Performance Monitor functions can be executed in the NE-specific Menu bar. Block Diagram The block diagram illustrates the equipments of the Pasolink Radio system. Its main purpose in the window is to display the current summary alarm state of the equipment. You can click on a specific block to display the status of equipment in the data window. Data window This window displays in detail the status and alarm items of a specific equipment of the NE. You can select the tab or the block of the specific equipment you want to monitor in the data window. Tabs To view the status and alarms in the Pasolink radio, click on the tab at the bottom of the Data window. Command Button The command button is used to enter the data selected on the pop-up window into the computer. Selectable Field The selectable field is a standard Windows input field where the user can scroll down on a list of values available for that option. Login User This indicates the current user that logged-in in the PNMT.

-5-

ROI-S04451

Title Bar NE-Specific Menu Bar Common Menu Bar Block Diagram

Common Tool Bar

Data Window

Tabs

Login User

Selectable Field

Command Button

Fig. 1: Common Parts of a Window

-6-

ROI-S04451

2.2

Launching the PNMT Application


To start PNMT: 1. Power ON the system. NOTE Connect the RS-232C cable 30seconds after IDU's power is ON make sure that the RS-232C cable is connected between Com 1 of the PNMT PC and the PNMT Port of the IDU. 2. Login to Windows 2000/NT/98 Workstation. Please refer to Windows 2000/NT/98 Manual. 3. Click on Start -> Programs -> Pnmt -> Pnmt then PNMT system logo appears followed by the PNMT (Link summary) window in the PNMT main window (See figure below)

-7-

ROI-S04451

2.3

Login
Users are registered by means of login name and password. To protect the network and network management system from unauthorized access or unauthorized modifications, five levels (refer to the table shown in section 2.3.1 User Level Privilege) of users are defined with different privileges. The functions are available in the window depending on the users access level. Therefore, some of the functions may or may not be carried out. The highest level or administrator level has full access to the network and network management system and has the ability to create and assign privileges to other users. To login: 1. Click on System -> Login/Logout in the Menu bar on main window.

2. Enter the User name. 3. Enter the valid Password for the specific User. 4. Click on the [OK] button.

-8-

ROI-S04451

2.3.1

User Level Privilege User Privilege (STM-0)

Category SYSTEM PROVISIONING

MAINTENANCE

EQUIPMENT SETUP

AUX I/O

PMON

EVENT LOG CTRL

ITEM ALARM BUZZER CONNECT(Remote Login) MTPC MTPC TX POWER RX THRESHOLD LEVEL ADDITIONAL ATT ATPC ATPC MAXIMUM ATPC MINIMUM RX THRESHOLD LEVEL ADDITIONAL ATT TX POWER CONTROL on ODU CPU ALM MODE BER ALM HIGH BER(RADIO) THRESHOLD THRESHLD(RADIO) RX SWITCH(RADIO) THRESHOLD BER ALM B1 E-BER(DMR) THRESHOLD THRESHLD(DMR) B1 SD(DMR) THRESHOLD B2 E-BER(DMR) THRESHOLD B2 SD(DMR) THRESHOLD B3 E-BER(DMR) THRESHOLD BER ALM B1 E-BER(MUX) THRESHOLD THRESHLD(MUX) B1 SD(MUX) THRESHOLD B2 E-BER(MUX) THRESHOLD B2 SD(MUX) THRESHOLD B3 E-BER(MUX) THRESHOLD MAIN INTFC ALS ALS DELAY TIME MAIN CHANNEL ASSIGNMENT CH-? SETTING MAIN CHANNEL USAGE VC12-? AIS ACTIVATION CONDITION MS RDI ACTIVATION CONDITION AIS SEND (LOOPBACK-1) AIS SEND (LOOPBACK-2) CHANNEL USAGE ERROR J0 DETECT MUX/DMR J1 DETECT MUX/DMR CLK PROVISIONING SUB INTFC SUB INTFC WS INTFC WS LINE LENGTH OH ASSIGNMENT ASSIGNMENT CHANNEL USAGE V11-? DIRECTIONAL SETTING SW PRIORITY TX SW PRIORITY RX SW PRIORITY MAINT TX/RX FREQUENCY TX SWITCH TX MUTE IF LOOPBACK MAIN SIGNAL LOOPBACK-1 MAIN SIGNAL LOOPBACK-2 MAIN SIGNAL VC12-? LOOPBACK-1 MAIN SIGNAL VC12-? LOOPBACK-2 CW ALS RESTART ATPC MANUAL CONTROL RX SWITCH CLK LOCKOUT CONTROL CLK SOURCE SELECT CONTROL CLK CLEAR WTR TIMER EQUIPMENT SETUP NE NAME NOTE INPUT OUTPUT RELAY CONFIGURATION PMON PMON Threshold Save to disk SECTION TRACE PATTERN SETTING Save to disk Save to disk CONTROL DATE/TIME DOWNLOAD CONFIGURATION FILE PROGRAM FILE UPLOAD CONFIGURATION FILE CPU RESET RESET

5 4 3 2 1 Monitor User Local Remote Admin O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O

*Admin : Enable to access to the all Network Elements. *Remote : Enable to access to the all Network Elements. (Disable to change network configuration and change program with downloading.) *Local : Enable to access to the Local NE and Opposite NE. (Disable to change network configuration and change program with downloading.) *User : Enable to access to items which doesn't affect to the equipment. *Monitor : Enable to monitor only and disable to control.

-9-

ROI-S04451

2.4

Logout
To logout from PNMT: 1. Click System -> Login/Logout on the Menu bar on the main window.

2. 3.

Select Logout from the Login /Logout window. Click on [OK] button to continue the Logout process.

2.5

Shutting Down the PNMT


To close the PNMT application: 1. Click System -> Exit on the Menu bar on the main window

2.

Click [Yes] to confirm closing the application.

- 10 -

ROI-S04451

2.6

Searching for Network Elements and Connecting to Selected Pasolink


The summary description (Pasolink name, Equipment type, Opposite Pasolink, etc.) of the current station where PNMT is connected can be displayed using this function. Summary description of the opposite station belonging to that link is also displayed. To search for or connect to Pasolink in the network: 1. Click on System -> Connect on Menu bar on main window.

NOTE Initially only the current NE physically connected to the PNMT and its opposite station will be shown on the Network Element List.

2. 3. 4.

Click on [Search for Element] button to display all connected NEs in the network. Select and highlight the NE to be viewed. Click [Connect] button. The PNMT(Link Summary) of the Pasolink selected and its opposite station will be displayed.

2.7

Change Password
To change the password: 1.Click on System -> Change Password on the Menu bar on main window.

Enter the Old password. 2. Enter New Password

- 11 -

ROI-S04451

3. Enter new password on the Confirm New Password to confirm. 4. Click on [OK] button. NOTE For details on initial user name and password, please refer to PNMT Install manual.

2.8

Alarm Buzzer Setting


This function is used to activate and set the Alarm Buzzer. The desired sound scheme can also be set using this function. To set the Alarm Buzzer: 1. Click System |Alarm Buzzer in the main window.

2. 3.

Select the Wave file or Beep box to activate the buzzer. No sound is the factory setting of the PNMT. If you select the Wave file box, Enter the location of the sound file (*.wav) Otherwise; click on [] to locate the desired file. You can also preview the *.wav file by click on the arrow next to the browse button. If you select the Beep box, click on [Edit] to edit the beep with its frequency and duration. You can also preview the Beep by click on the arrow next to the browse button. Click on [OK] button to activate the new setting.

4.

- 12 -

ROI-S04451

2.9

Refresh
This function is supported only by PNMT. This function enables PNMT to acquire all status manually and to update equipment information To Refresh: Click on Refresh Refresh in the main window or click on the refresh icon in the tool bar.

NOTE Metering items such as TX power, RX level, power supply and BER are automatically refreshed every 15 seconds. This function is used when the immediate refreshing of these metering items is necessary or confirmation of all current status is immediately required.

- 13 -

ROI-S04451

2.10 Remote Viewing PNMT (Link Summary) Window


You can view a target link within the one Root NE cluster of the Pasolink network by searching the connected NEs and then connecting to a target NE. Please refer to Section 2.6 Searching for Network Elements and Connecting to Selected Pasolink. This function allows you to connect to any NE in the network remotely. NOTE: For multi-Root NE network, you can only connect to NEs that are being polled by the same RootNE as the local NE where you are directly connected via the PNMT cable.

PNMT (Link Summary) Window (1+0 configuration)

- 14 -

ROI-S04451

2.11 Overall Tab


This tab is displayed on startup. The overall tab provides a snapshot at the most significant monitored items in the NE.

Overall Tab for 1+0 configuration

Overall Tab for 1+1 Twin-Path configuration

Overall Tab for 1+1 Hot-standby configuration

The Overall tab gives a snapshot of the important settings of the NE. This window only displays current settings and there are no control functions associated with this window.

- 15 -

ROI-S04451

The following items are displayed in this tab: o MTPC TX Power the current value (in dB) of the Manual Transmitter Power Control attenuation set in the ODU. The MTPC Attenuation will only have a valid data if the MTPC is enabled. TX Frequency the current transmit frequency used. RX Frequency the current receive frequency used. Frame ID the set frame ID of the NE. TX Power Control shows the current power control mode used by the ODU. The TX Power Control is either Automatic Transmitter Power Control (ATPC) or Manual Transmitter Power Control (MTPC). MAIN INTFC shows the current main interface used by the IDU. The available interfaces are: STM-1(Electrical), STM-1(Optical) and 21CH*2B ALS shows the current setting of the Automatic Laser Shutdown (ALS). It can either be Enable or Disable. The ALS is an IDU function that intermittently turns on/off the laser output when a certain period elapses after STM-1 LOS mode starts. MAINT the current state of the Maintenance status. Selected TX (for Hot-standby configuration only) shows the current system used for signal transmission. Selected RX (for 1+1 system only) shows the current system used for signal reception.

o o o o

o o o

- 16 -

ROI-S04451

2.12 ODU Tab


This function is to display the values and status of the monitored items of the ODU. This window only displays current settings and there are no control functions associated with this window. To set the ODU parameters see the chapters on Equipment Setup and Provisioning. 2.12.1 ODU Tab To view the alarm and status display of the ODU: 1. Click the ODU tab in PNMT (Link Summary) window of the target NE.

ODU Window (1+0 configuration)

ODU Window (1+1 configuration)

- 17 -

ROI-S04451

Monitored Items in the ODU Following items are monitored. TX PORTION Alarm o TX INPUT: alarm occurs when the TX IF input signal from the IDU is lost o TX POWER: TX RF Power decreases 3 to 6 dB from nominal value. Metering TX Power: The transmitted power of the ODU in dBm. MTPC Status (This portion of screen is only active if MTPC is used.) o MTPC TX Power * o RX Threshold Level* o Additional Attenuation* RX PORTION Alarm RX LEVEL: alarm occurs when the input level decreases by preset value from squelch level. (See Provisioning : RX Threshold) Metering RX Level: The received level interpreted in dBm.

ATPC Status (This portion of screen is only active if ATPC is used.) o Control Range* o RX Threshold Level* o Additional Attenuation* o ODU ALM Mode*

COMMON PORTION Alarm o APC this alarm occurs when the Local Oscillator is locked out. o CABLE this alarm occurs when the communication between the ODU and the IDU is lost. Metering Power Supply: Display PS value (V) * For the detailed description of this items see 2.16 Equipment Setup and 2.17 Provisioning.

- 18 -

ROI-S04451

2.13 IDU Tab


This function is to display the values and status of the monitored items of the IDU. This window only displays current settings and there are no control functions associated with this window. To set the ODU parameters see the chapters on Equipment Setup and Provisioning. 2.13.1 IDU Tab To view the alarm and status of the IDU: 1. Select the IDU tab in PNMT (Link Summary) window of the target NE. The figure below illustrates the difference between the IDU tab of a 1+0 and a 1+1 system. Only the TX, RX and Common portion is different for both systems.

Displayed at 2M INTFC only

IDU Window (1+0 configuration)

- 19 -

ROI-S04451

Displayed at 2M INTFC only

IDU Window (1+1 configuration)

- 20 -

ROI-S04451

Monitored Items Following items are monitored: MODULE Alarm o MAIN INTFC - alarm occurs when Main INTFC module fails. o SUB INTFC - alarm occurs when the SUB INTFC fails. o MODEM - alarm occurs if there is a modem failure. o PS - alarm occurs if there is a DC-DC CONV failure. (for 1+1 systems only) TX & RX Alarm MOD - alarm occurs when the TX unit (modem) failed. DEM - alarm occurs when the RX unit (demodulator) fails or the IF signal is lost HIGH BER - alarm when BER is worse than preset value. (for 1+1 systems only) MDCPU - alarm when there is a failure in the communication between modules Sw Status Selected (for 1+1 systems only) SUB INTFC Alarm LOS - loss of signal occurred AIS RCVD - Indicates reception of the AIS code in each 2Mbps data stream from the MUX

COMMON PORTION Metering BER: The current overall value of the Bit-ErrorRate(B1)

MUX & DMR LOP - loss of pointer occurred LOS - loss of signal occurred PLM - detects Payload Mismatch LOF - loss of frame occurred LOM - Loss of Multi-frame occurred TIM - detects Trace Indication Mismatch AIS - Alarm Indication Signal (MUX only) E-BER - BER portion is worse than E-BER threshold. UNEQ - detects Unequipped condition SD - BER is worse than the Signal Degrade RDI receives Remote Defect Indication threshold Table of Displayed Alarm with MUX and DMR
LOS SPI RST MST MSA(AU) HPT HPA PPI C M LOF C TIM C C EBER C C C SD C C LOP C PLM C LOM C AIS M M M UNEQ C RDI C C -

SPI/RST - SDH Physical Interface/Regenerator Section Termination MST - Multiplex Section Termination MSA - Multiplex Section Adaptation HPT - Higher order Path Termination HPA - Higher order Path Adaptation PPI - PDH Physical Interface MUX only C: Common between MUX and DMR M: MUX only

- 21 -

ROI-S04451

2.14 CLK Tab


The function of each control is as follows. CLK Loss of Timing Input Signal Fail (EQUIP) Signal Fail (Line) - alarm occurs when all clock source are lost. - alarm occurs when each clock source is in the failed condition. - alarm occurs when each clock source is in the failed condition. (applies only when an external clock is used and the Selected External Output provisioning item has been set to Line.) - indicates the clock that has been selected for the equipment timing source. - indicates the line clock selected for the external clock output. (applies only when an external clock is used and the selected External Output provisioning item has been set to Line.) - indicates the availability of each applicable clock source. - indicates the quality level of each applicable clock source. - indicates whether the associated clock source that is now back to normal condition is in the wait to restore state. - indicates the reception of the AIS code in the 2 Mbps signal fed to the EXT IN port. (applies only when a 2 Mbps signal is used as an external clock source) - Indicates whether the operating mode of the equipment clock is Freerun state or not.

CLK Selected (EQUIP) CLK Selected (Line)

Signal Available Interpret QL MON Wait To Restore

AIS RCVD

Operation Mode (Freerun)

Operation Mode (Holdover) - Indicates whether the operating mode of the equipment clock is Holdover state or not. Squelched External Output - Indicates the status of the external clock signal supplied by the EXT OUT port. External Command Reject - indicates that the manual clock switching operation performed by the user has been rejected The EXT CLK output is derived from the PLL. The EXT CLK output is derived from a CLK extracted from an STM signal (MUX/DMR CLK)

EQUIP (equipment): Line:

- 22 -

ROI-S04451

2.15 Auxiliary I/O Tab


4-relay output and 6 optocoupler inputs are provided in the PNMT for external control and alarms. The setting for each relay output/optocoupler is available by clicking on the selected device in the Auxiliary I/O Monitor window. To monitor and set the Auxiliary I/O: 1. Select the Aux. I/O tab in the PNMT(Link Summary) window

2.15.1 Monitored Items Following items are monitored in this tab: 1. 2. Six (6) inputs (Input1 - Input6) Four (4)-relay outputs. (Output1 - Output4)

- 23 -

ROI-S04451

2.15.2 Optocoupler Input Setting To set the Optocoupler input: 1. 2. Click on the selected [Input-n] button in Aux. I/O tab. The input properties will be displayed in the ensuing window.

2.15.2.1 Setting the selected Input to Alarm or Status 1. Select the Alarm condition of the Input. You can select the event when the target Input will send the alarm signal to the PNMS/PNMT. Also you can preset the input to just send the Status of the input instead of an alarm signal. The alarm input severity is defined in the X.733 recommendations. Select the Severity of the alarm, its type and probable cause by clicking on the pull-down arrow on the left-hand side of the field. 2. Click on the Name tab. 3. Enter the name of the Input in the Name, Event ON, and Event OFF field. A maximum of 32 characters can be used 4. Click on [Execute] button to activate the selected state of the device. 5. Click on [Close] button when finished.

- 24 -

ROI-S04451

2.15.3 Relay Output Setting To set the relay output: 1. Click [Output-n] button in Aux. I/O window.

2. 3. 4. 5. 6.

To open or close the relays click on the Event ON or Event OFF button respectively. Enter the desired strings for the open and close states of the Relay in the appropriate Even ON and Event OFF fields. A maximum of 32 characters can be used. Enter the desired name on the Name field. A maximum of 32 characters can be used. Click on [Execute] button to carry out the command. Click on [Close] button when finished.

2.15.4 Relay Configuration There are 11 relays in the Pasolink+ IDU. Consequently, 11 parallel alarms can be defined. Relays RL01, RL02 and RL03 have fixed alarms. Maintenance, PS ALM and CPU Alarm are outputted on RL01, RL02 and RL03 respectively. RL04 to RL11 are user-definable relays. If the HK-OUTs are enabled, RL08 to RL11 are allocated for Housekeeping (HK) alarms. The PNMT allows the user to configure the relays in a table format. The columns indicate the relays (RL01 to RL11) and the rows indicate the parallel alarms available in the Pasolink+ IDU. The following indicators are used in the table: Out indicates that the alarm - in the corresponding row, is issued on the corresponding relay. HK Indicates that the corresponding relay is used for House Keeping. Mask Indicates that no alarm is issued in the corresponding relay when the maintenance mode is activated. Blank button not related to the corresponding alarm.

- 25 -

ROI-S04451

To set the relay configuration: 1. Click [Relay Configuration] button in Aux. I/O window.

2.

Select the HK-OUT used in the IDU. There are four (4) available HK-OUTs in the Pasolink+ system. Selecting 1/2/3/4 button means all HK-OUTs will be enable; 1/2/3 means only HK-OUT 1, 2 and 3 will be enabled; and so on. If the HK-OUTs will not be used, select Disable button. Click on the button(s) that corresponds to the target alarm(s) and relay (s). Click on [Execute] button to apply the new relay configuration. Click on [Close] button when finished.

3. 4. 5.

2.16 Version Tab


The inventory information of the ODU and IDU can be viewed using this function. 2.16.1 Version Monitor To display version of ODU and IDU. 1. Select the Version tab in PNMT (Link Summary) window. 2. The version tab shows Code No, the Date of Manufacture, Serial No. Hardware Type, and Software Version of the ODU, IDU.

- 26 -

ROI-S04451

Version Window for (1+0)

Version Window for (1+1)

- 27 -

ROI-S04451

2.17 Control (CTRL) Tab


2.17.1 The Control Module Select the CTRL tab in PNMT (Link Summary) window of the target NE. The following items can be monitored and controlled in the CTRL tab: Calendar Alarm Date/Time CPU Reset Download Configuration File Download Program File Upload Configuration File Setting the Date/Time The Date and Time stored in control module can be displayed and adjusted using this function. To set the Date/Time: 1. Click on the [Date/Time] button in the CTRL tab. NOTE To set the value of the Date and Time field to the same value as that of the PNMT computer, check on the Display PC Time box 1) To check the Date and Time on the Control module: Select Get Date/Time in the Date/Time window. Click on [Execute] button. The current date and time in the control will be displayed in the Date and Time field. 2). To set the Date and Time on the Control module: 2)-1 2)-2 2)-3 Select Set Date/Time in the Date/Time window. Click on [Execute] button. Click on [Close] button when finished. 1)-1 1)-2 1)-3

- 28 -

ROI-S04451

2.17.2 CPU Reset The control module can be reset using this function NOTE Resetting the control module will not affect the traffic. The connection to the selected Pasolink will be lost a few minutes and will be automatically reconnected. To reset the control module: 1. 2. Click on the [CPU Reset] button in CTRL tab. You can select the with ROM(Ctrl Program) Switching option if you want to switch to a newly downloaded control module Program file. Click on [Execute] button to continue the control module reset operation.

3.

2.17.3 Downloading the Configuration Files to the Control Module This function is used to download configuration files from the PNMT to the control module. The configuration file pp_network.cfg, contains the IP address of the CTRL as well as the IP address of the opposite station and the information about the Pasolink network where the CTRL is located. The pp_mib.cfg contains the information about the equipment (i.e. name, pm type, etc.) and housekeeping (AUX I/O) To download new configuration file to the CTRL: 1. Click on [Configuration File] in the button in the CTRL tabs Download (PC>>CTRL) section. Select the type of file to be downloaded in the Type list. Enter the location of the configuration file in the File field, or click on [Browse] to locate the file on the local hard disk or diskette. WARNING!!! Make sure that the correct configuration file is downloaded to the correct Control module. Incorrect configuration file will lead to Control module or network failure. 4. 5. Click on [Execute] button to start the operation. A message window indicating the status of the operation will appear. It will close automatically once the operation is finished.

2. 3.

- 29 -

ROI-S04451

WARNING: Make sure that you have successfully downloaded the configuration file before doing Update. Otherwise the Control module will switch to an empty ROM that may cause Control module failure. 6. 7. Click on [Update] button to activate the new configuration file(s). Select the appropriate box for the type of configuration file that will be updated. One or more configuration file can be updated by checking the box opposite to the configuration file name. Click on [Execute] button to start the operation. The "with ROM (Ctrl Program) Switching" box is for switching to the ROM with the new CTRL Program and has the same function that was previously discussed in section 2.14.5 Downloading a new Program file to the Control Module. NOTE When updating pp_network.cfg file, NE-to-NE communication will be lost when the Control module re-initializes to the new system configuration. This WILL NOT affect the radio link. During this time PNMT connection to the Pasolink will be lost but will automatically be reconnected after the Control module resets. 8. Click on [Yes] button. When below window is opened.

9.

Click on [Close] button when done.

- 30 -

ROI-S04451

2.17.4 Downloading a new Program File to the Control Module This function is used to update the application program on the Control module. This operation affects only the NMS communication but not the radio link, and will not disrupt communication. To download the program file to control module: 1. 2. Click on [Program File] in the button in the CTRL tabs Download (PC>>CTRL) section. Check the CTRL button. If you tick the with Self Reset the control module will be reset automatically after program file download is completed. In this case, you wont need to do steps 5 thru 8. Enter the appropriate location of the program file (*.out) in the File field. Otherwise, click [Browse] to locate the file.

3.

WARNING!!! Make sure that the correct program file is downloaded to the Control module. Incorrect program file will lead to failure. 4. 5. Click on [Execute] button to start the operation. A message window will appear displaying the status of the operation. The message window will close automatically once the download is completed. NOTE This operation may take several minutes depending on the program file size. 6. Click on [CPU Reset] button to switch to the new program file.

7. Check the with ROM(Ctrl Program) Switching box. 8. Click on the [Execute] button to complete the switch to the new program file. NOTE The connection to the selected Pasolink+ will be lost a few minutes and will automatically re-connect.

- 31 -

ROI-S04451

2.17.5 Uploading Control Module Configuration file to PNMT PC This function is used to upload the configuration file from the Control module of the selected Pasolink to the PNMT PC. To upload configuration file from the Control module to the PNMT: 1. Click on [Configuration File] in the button in the CTRL tabs Upload (CTRL>>PC) section.

2. 3. 4. 5. 6. 7.

Select the type of file to be uploaded on the Type field. Enter the desired file name for the uploaded file. And select and the directory where the uploaded file will be saved. Click on the [Execute] button to start the operation. A message window indicating the status of the operation will appear. It will close automatically once the operation is completed. After the upload is finished click on [Close] button. Verify that the file was uploaded on the specified directory.

2.18 Maintenance
The function of each control is as follows. Control MAINT : To switch Maintenance mode to ON Main signal Loopback-1: (Near-end Loopback) Disable for 2MB INTFC Main signal Loopback-2: (Far-end Loopback) Disable for 2MB INTFC Main signal VC12 Loopback-1/2: (Near and far -end Loopback) Available for 2MB INTFC only IF Loopback : (Local only) ALS Restart: To set the time of manual restart Automatic Laser Shutdown (ALS) CW (MOD Carrier): To turn on the Continuous Wave for measurements (Local only) TX Mute : To turn off TX power (Local only) TX Frequency - transmit Frequency RX Frequency - Receive Frequency ATPC Manual - To set TX power during Automatic transmitter Power Control (ATPC) CLK Lockout Control - Set CLK source which is locked out Source Select Control - Set CLK source which is used forcefully Clear WTR Timer - Clear the Waiting timer when CLK restores the normal source.

- 32 -

ROI-S04451

2.18.1 Maintenance Menu To go to maintenance window: 1. Select Configuration -> Maintenance in the NE-specific menu bar. Maintenance Window (1+0 configuration)

Maintenance Window (1+1 configuration)

Displayed at 2M INTFC only

- 33 -

ROI-S04451

2.18.2 Selecting Maintenance Mode To switch the Pasolink to maintenance mode: 1. 2. 3. 4. Click [MAINT] button in Maintenance window. Select on ON/OFF depending on desired state. Click on [Execute] to carry out the command. Click on [Close] button when finished.

2.18.3 Switching TX (for 1+1 system only) To control the TX switch manually: 1. 2. Click [TX Switch] button in Maintenance window. Select the system that you want to use for the TX portion of the radio. The default value is Auto. Click on [Execute] button to switch the TX to the selected system. Click on [Close] button when finished.

3. 4.

2.18.4 Switching RX (for 1+1 system only) To control the RX switch manually: 1. 2. Click [RX Switch] button in Maintenance window. Select the system that you want to use for the RX portion of the radio. The default value is Auto. Click on [Execute] button to switch the RX to the selected system. Click on [Close] button when finished.

3. 4.

2.18.5 Main Signal Loopback Following loopbacks are created at the 150MB INFTC/OPT INTFC of the selected NE where you are currently connected Main Signal Loopback - 1 (near-end loopback) Main Signal Loopback - 2 (far-end loopback) To set the near(or far)-end loopback: 1. 2. Click on the [Main Signal Loopback] button in the Maintenance window. Select Loopback-1(or Loopback-2) tab on the top

- 34 -

ROI-S04451

Loopback-1 Window

Loopback-2 Window

3. 4. 5.

Select ON to activate the loopback. Click on [Execute] button to apply the loopback. Click on [Close] button when finished.

2.18.6 IF Loopback (local only loopback) This type loopback is created at the MODEM module of the local NE. To set the local only loopback: 1. Click on the [IF Loopback] button in the Maintenance window.

2. 3. 4.

Select ON to activate the loopback. Click on [Execute] button to apply the loopback. Click on [Close] button when finished.

- 35 -

ROI-S04451

2.18.7 ALS Restart This function is used to set the time of manual restart of the Automatic Laser Shutdown (ALS). When the optical input signal is off due to ALS, the IDU will emit laser signal from TX to RX at a preset value (2 sec or 90 sec), at this point, if the fault has been recovered then the ALS will be released and operation will return to normal. Otherwise, the laser emission will end immediately. (See Pasolink + Instruction Manual for further details.) To set the ALS restart: 1. 2. 3. 4. Click on [ALS Restart] button in the Maintenance window. Select the timing in seconds of the laser emission for manual restart. Click on [Execute] button to apply the timing of the manual restart. Click on the [Close] button when finished.

2.18.8 Lockout Control It is possible to restrict the use of the CLK source to the INTFC set this function To set the Lockout Control: 1. 2. 3. 4. Click on [Lockout Control] button in the Maintenance window. Select to set the Lockout Control to Four Sources [EXT1, EXT2, MUX, DMR] respectively. Click on [Execute] button to apply the new setting Click on the [Close] button when finished.

2.18.9 Source Select Control To set the Source Select Control 1. 2. Click on [Source Select Control] button in the Maintenance window. Select a source type from following types as below Freerun: operating mode of the equipment clock is free-run. Holdover: operating mode of the equipment clock is hold-over. Auto: operating mode of equipment clock is normal. 3. 4. Click on [Execute] button to apply the new setting Click on the [Close] button when finished.

- 36 -

ROI-S04451

2.18.10 Clear WTR Timer It is possible to clear the waiting timer from setting the new CLK to reset the current CLK. To check the Clear WTR Timer: 1. 2. 3. 4. Click on [Clear WTR Timer] button in the Maintenance window. Select Clear the action of waiting timer to restart when you will switch over the CLK Click on [Execute] button to apply the new setting Click on the [Close] button when finished.

2.18.11 Selecting TX Mute Status TX power of the ODU is switched off when TX Mute is ON. This should be OFF in normal operation. To change the TX Mute status: 1. Click [TX Mute] button in Maintenance window

NOTE Switch ON maintenance mode first before performing TX Mute.

2. 3. 4.

Select ON/OFF depending on the desired state. Click on [Execute] button to carry out the command. Click on [Close] button when finished.

2.18.12 TX Frequency Sets the RF transmitted frequency and consequently its pair receiving frequency. (Proceed to 2.16 Equipment Setup.) NOTE Switch ON maintenance mode first before performing TX Frequency. 2.18.13 RX Frequency Displays the current RF receiving frequency used by the ODU. (Proceed to 2.16 Equipment Setup.) NOTE Switch ON maintenance mode first before performing RX Frequency.

- 37 -

ROI-S04451

2.18.14 Selecting Carrier Wave Status When doing frequency measurements, the CW should be turned ON to have an unmodulated signal. During normal operations this status should be OFF. To change the CW (MOD Carrier) status: 1. Click [CW (MOD Carrier)] button in Maintenance window

NOTE Switch ON maintenance mode first before performing CW.

2. 3. 4.

Click on ON/OFF button depending on desired state. Click on [Execute] button to carry out command. Click on [Close] button when finished.

2.18.15 ATPC Manual Used when an optional transmitting power is required when the ATPC is in operation. To set the ATPC Manual: 1. Click [ATPC Manual] button in Maintenance window

NOTE Switch ON maintenance mode first before performing ATPC Manual.

2. Select the whether to manually turn ON or OFF the ATPC manual and the ATPC manual power that will be transmitted in dB. 3. Click on [Execute] button to activate the new setting. 4. Click on [Close] button when finished.

- 38 -

ROI-S04451

2.19 Equipment Setup


Main signal, ODU and CTRL portion can be monitored and controlled in this window. 2.19.1 Equipment Configuration Window To open the Equipment Configuration Monitor: 1. 2. Select Configuration -> Equipment Setup in the NE-specific menu bar. This window contains the setup information and control for the IDU and the ODU. The Equipment Setup window is shown below.

- 39 -

ROI-S04451

2.19.2 Setup To setup the ODU and IDU parameters: 1. 2. 3. Click on the [Setup] button in the Equipment Setup window. On the Setup window, the configurable items are shown and described in the table below: Click on [Execute] button to apply the new set of values

ODU

IDU

CTRL

Start Frequency - Minimum of Available Frequency Band Stop Frequency - Maximum of available Frequency Band Shift Frequency - TX/RX frequency spacing Upper/Lower - Positional relation of TX frequency TX Frequency - sets the RF transmit frequency and consequently the RF receive frequency of the ODU TX Power Control - method used by the ODU for power control functions can be set here. Either Automatic Transmit Power Control (ATPC) or Manual Transmit Power Control (MTPC) can be selected. Redundancy - This function Is available only for 1+1 systems Hot-Stand-By or Twin-Patch configuration can be set using this function. System - The name of equipment SOH Termination - Section Overhead Termination Main INTFC - the main interface of IDU can be selected here. The available interfaces are STM-1(Optical), STM-1(Electrical) or 21CH X 2MB Modulation - Modulation form Frame ID - used to synchronize the TX and RX frames of opposing NEs in the hop. The frame ID can be set from 1 to 8. NE Name - Name of NE IP Address - IP Address of NE Note - Used to describe the short message

CAUTION: Changing the TX/RX CH will interrupt the traffic.

- 40 -

ROI-S04451

2.19.3 Editing the NE Name To edit the NE name: 1. 2. Click [NE Name] button in Equipment Setup window. Enter new Pasolink name in the NE Name dialog box. A maximum of 32 characters can be used. Click on [Execute] button to change to new name. Click on [Close] button when finished.

3. 4.

2.19.4 Editing the Note for CTRL To put an optional description on the current Pasolink: 1. 2. Click [Note] button in Equipment Setup window. Enter the optional description for the specific Pasolink in the Note dialog box. A maximum of 100 characters can be used in this field Click on [Execute] button when finished. Click on [Close] button when finished.

3. 4.

- 41 -

ROI-S04451

2.20 Provisioning
The main interface (MAIN INTFC), overhead (OH), Threshold SUB INTFC, MTPC and ATPC can be set in this window. 2.20.1 Provisioning Window To open the Equipment Configuration Monitor: 1. 2. Select Configuration -> Provisioning in the NE-specific menu bar. This window contains the setup information of the Main INTFC, OH, Threshold, SUB INTFC, MTPC and ATPC. The Provisioning window is shown below.

Provisioning Window (1+0)

- 42 -

ROI-S04451

Provisioning Window (1+1) 2.20.2 MAIN INTFC 2.20.2.1 Enabling the ALS When the ALS is enabled, the laser emission will be cut off after a certain period have elapsed after the IDU have issued an STM-1 LOS. If the ALS is disabled, the laser emission will be continuously outputted. To enable the ALS: 1. 2. 3. 4. Click on the [ALS] button on the Provisioning window. Select Enable on the ensuing window. Click on [Execute] button to enable the ALS. Click on [Close] button when finished.

- 43 -

ROI-S04451

2.20.2.2 Setting the ALS Delay Time (ALS Restart) This function allows you to set the time in seconds before the ALS will try automatically to release the laser lock-off. After the preset time have elapsed, the IDU will emit laser intermittently and if the fault have been corrected the ALS will be released and continue with the normal operation. Otherwise, the laser will be immediately cut off. To set the ALS delay time: 1. 2. Click on the [ALS Delay Time] button on the Provisioning window. Select the time in seconds when the ALS will try to automatically release the lock-off in laser emission in the ensuing window. Click on [Execute] button to apply the new setting. Click on [Close] button when finished.

3. 4.

2.20.2.3 AIS Activation Condition When E-BER Alarm occurs, this function enable Alarm Indication Signal (or AIS) to be Active

2.20.2.4 MS RDI Activation Condition When E-BER Alarm occurs, this function enable MS RDI to be Active.

2.20.2.5 AIS Send (Loopback-1) This function is used to set whether AIS is sent to the opposite station when Near-end loopback is performed

2.20.2.6 AIS Send (Loopback-2) This sets whether AIS is sent to the MUX when Far-end loopback is performed.

- 44 -

ROI-S04451

2.20.2.7 VC12 Assignment This function is used to assign the virtual container number to the physical channel number. It is possible to assign the VC number to the same physical channel number by selecting [Easy] It is possible to assign the VC number to the desired physical channel number by selecting [Customize]

NOTE: It is essential for Execute to assign all Channels or VC12s. 2.20.2.8 Channel Usage Error This function is used to report the alarms from the main channel.

- 45 -

ROI-S04451

2.20.2.9 CLK Provisioning Provision of clock can be set in this Window External CLK Interface: Kind of external clock interface selected from the following items. Not Used: 2MHz: 2MB: When the External clock is not provided. When the External clock is 2.048MHz When the External clock is 2.048Mbps.

Selected External Output: When an External clock is selected, this defines the source of the CLK signal that is set out to the EXT CLK OUT ports, to be used by external equipment. Select: Equipment: Line: The EXT CLK output is derived from the PLL. The EXT CLK output is derived from a CLK extracted from an STM signal (MUX/DMR CLK)

QL (Quality) Mode: To monitor the SSM. In this mode, the clock source having the highest quality and priority will be selected EXT OUT Priority Level [for line]: This setting is used by the equipment to decide which of the line clock signals will be supplied by the EXT OUT port. NOTE In this priority setting , 1 is the highest priority and 4 is the lowest priority. A CLK source having a priority set to disable will not be considered for CLK selection Equipment Priority Level [Port Usage]: This sets the priority level SSM Supported [Input Port] [STM Input EXT IN/OUT]: This setting defines to supports the SSM or not QL Overwrite: This setting defines whether the quality (QL) value is overwritten with a fixed value. QL Fixed Value: This sets the fixed quality value of each CLK source. SSM Usage for STM Output: This sets whether SSM value sent for STM output. Usually, Enabled is set. At the border of the network, Disabled is set when the SSM value should not be sent to the other network. Wait to Restore [WTR] Timer: When a selected clock source is cut off, another available clock source is automatically selected. If the cut off clock that is restored, a waiting period is required before the equipment judges that the CLK is indeed restored and may now be re-selected. The wait to restore time defines the waiting period. Line Extracted CLK Squelched by MS-AIS: Select yes to squelch the line clock if MS-AIS is detected in the STM signal where the line clock is extracted. QL Minimum Value: QL Minimum Value sets minimum quality of the EXT CLK OUT signal. External SSM Channel [Sax]: this defines which Sax bit is used to convey the SSM when the EXT CLK is set to 2MB. This setting is common for both EXT CLK IN and EXT CLK OUT ports.

- 46 -

ROI-S04451

External CLK Output Control: Continue: To prevent the EXT OUT CLK signal when the internal (free-run, holdover) clock gets selected as the EXT OUT signal. This item is usually set to Auto

2.20.2.10 Section Trace J0 Detect This function sets the Section Trace J0 detectable.

2.20.2.11 Section Trace J1 Detect This function sets Section Trace J1 detectable.

- 47 -

ROI-S04451

2.20.3 Overhead (OH) Assignment 2.20.3.1 OH Assignment Type The OH can be either set at factory default (Easy) or customized (Custom) according to user requirements. To set the OH Assignment type: 1. 2. 3. 4. Click on the [Assignment] button in the Provisioning window. Select the type of OH assignment that will be employed. Click on [Execute] button to apply the setting. Click on [Close] button when finished.

2.20.3.2 Direction To set the direction: 1. 2. 3. 4. Click on the [Direction] button in the OH Assignment table. On the ensuing table, you will be able to select the direction for the V11-1 and V11-2 interface. Click on [Execute] button to apply the new setting. Click on [Close] button when finished.

2.20.3.3 Channel Usage This function allows you to set the interface used on the available user channels (E1, F1, DSC, etc.) in the Pasolink +. The user channels can be set as V11, VF or LAN (Ethernet) using this function. To set the channel usage: 1. 2. Click on the [Channel Usage] button in the OH Assignment table. On the ensuing window, the channel usage table will be displayed. You can assign a target channel to use a specific interface by plotting the channel (column) and the interface (row) on the table and clicking on the button that corresponds to the target channel and interface. Note that for each channel you can set only one interface.

3.

Click on [OK] button to apply the new settings.

- 48 -

ROI-S04451

2.20.4 Manual Transmit Power Control (MTPC) Status When the MTPC is selected over ATPC the buttons on this section will become sensitive and the MTPC parameters can be set. The MTPC has three (3) parameters: MTPC TX Power RX Threshold Additional Attenuation The procedure for setting these parameters will be presented in this section. 2.20.4.1 MTPC TX Power When the MTPC is in operation, the transmission power (dB) can be set using this function. To set the maximum transmission power in MTPC: 1. 2. Click on [MTPC TX Power] button in the Provisioning button. Set the power (dB) in the ensuing window. You can either highlight the input field and enter the dB value using the keypad or use the arrows on the right-hand corner of the field to increase or decrease the value shown in the input field. Click on [Execute] button to apply the maximum MTPC TX power. Click on [Close] button when finished.

3. 4.

2.20.4.2 RX Threshold Sets the threshold value of the receiving level. When the received level converge on the preset value of the threshold the TX power is controlled by sending control signals in the Radio Frame Complementary Overhead (RFCOH). To set the RX threshold: 1. 2. Click on the [RX Threshold] button in the MTPC status section of the Provisioning window. Set the power (dB) in the ensuing window. You can either highlight the input field and enter the dB value using the keypad or use the arrows on the right-hand corner of the field to increase or decrease the value shown in the input field. Click on [Execute] button to apply the new preset value. Click on [Close] button when finished.

3. 4.

- 49 -

ROI-S04451

2.20.4.3 Additional Attenuation If the transmission length of the radio section is short, additional span attenuators can be set in the ODU. The additional attenuation can be set from 0 to 5 dB. To set the additional attenuation: 1. 2. Click on the [Additional Attenuation] button in the MTPC status section of the Provisioning window. Set the attenuation (dB) in the ensuing window. You can either highlight the input field and enter the dB value using the keypad or use the arrows on the right-hand corner of the field to increase or decrease the value shown in the input field Click on [Execute] button to apply the attenuation. Click on [Close] button when finished.

3. 4.

2.20.5 Automatic Transmit Power Control (ATPC) Status When the ATPC is selected over MTPC the buttons on this section will become sensitive and the ATPC parameters can be set. The ATPC has five (5) parameters: TX MAX Power TX MIN Power RX Threshold Additional Attenuation ODU ALM Mode The procedure for setting these parameters will be presented in this section. 2.20.5.1 TX MAX Power When the ATPC is in operation, the maximum transmission power (dB) can be set using this function. To set the maximum transmission power in ATPC: 1. Click on [TX MAX Power] button in the Provisioning button. 2. Set the power (dB) in the ensuing window. You can either highlight the input field and enter the dB value using the keypad or use the arrows on the right-hand corner of the field to increase or decrease the value shown in the input field. 3. Click on [Execute] button to apply the maximum ATPC TX power. 4. Click on [close] button when finished.

- 50 -

ROI-S04451

2.20.5.2 TX MIN Power When the ATPC is in operation, the minimum transmission power (dB) can be set using this function. To set the minimum transmission power in ATPC: 1. 2. Click on [TX MIN Power] button in the Provisioning button. Set the power (dB) in the ensuing window. You can either highlight the input field and enter the dB value using the keypad or use the arrows on the right-hand corner of the field to increase or decrease the value shown in the input field. Click on [Execute] button to apply the minimum ATPC TX power. Click on [Close] button when finished.

3. 4.

2.20.5.3 RX Threshold Sets the threshold value of the receiving level. When the received level converge on the preset value of the threshold the TX power is controlled by sending control signals in the Radio Frame Complementary Overhead (RFCOH). To set the RX threshold: 1. Click on the [RX Threshold] button in the ATPC status section of the Provisioning window. 2. Set the power (dB) in the ensuing window. You can either highlight the input field and enter the dB value using the keypad or use the arrows on the right-hand corner of the field to increase or decrease the value shown in the input field. 3. Click on [Execute] button to apply the new preset value. 4. Click on [Close] button when finished. 2.20.5.4 Additional Attenuation If the transmission length of the radio section is short, additional span attenuators can be set in the ODU. The additional attenuation can be set from 0 to 5 dB. To set the additional attenuation: 1. 2. Click on the [Additional Attenuation] button in the ATPC status section of the Provisioning window. Set the attenuation (dB) in the ensuing window. You can either highlight the input field and enter the dB value using the keypad or use the arrows on the right-hand corner of the field to increase or decrease the value shown in the input field Click on [Execute] button to apply the attenuation. Click on [Close] button when finished.

3. 4.

- 51 -

ROI-S04451

2.20.5.5 ODU ALM Mode In cases wherein the ODU losses communication with the IDU due to failure of some sort, the response of the ODU can be preset using this function. Since the control function of the TX power is in the IDU, the ODU will be cut-off to this control when a failure in the communication between the ODU and the IDU occurs. In this case, the ODU either mutes the TX or Hold the current TX power, depending on the preset ODU ALM mode. To set the ODU ALM mode: 1. 2. Click on the [ODU ALM Mode] button in the ATCP status section of the Provisioning window. Select the action of the ODU in case of IDU communication failure. For ATPC, MAX, MIN or Hold mode is available. Click on [Execute] button to apply the new setting. Click on [Close] button when finished.

3. 4.

2.20.6 SW priority 2.20.7 TX SW Priority The TX SW priority defines the channel that will be selected by the TX switch when both channels are normal. Non-priority : There is no priority. Priority No.1: Priority is given to No.1 channel. To set the TX switch priority : 1. 2. 3. 4. Click on the [TX SW Priority] button in the SW Priority of the Provisioning window. Select the type of TX switch priority. Click on [Execute] button to apply the new setting. Click on [Close] button when finished.

2.20.8 RX SW Priority The RX SW priority defines the channel that will be selected by the RX switch when both channels are normal. Non-priority: There is no priority. Priority No.1: Priority is given to No.1 channel To set the RX switch priority : 1. 2. 3. 4. Click on the [RX SW Priority] button in the SW Priority of the Provisioning window. Select the type of RX switch priority. Click on [Execute] button to apply the new setting. Click on [Close] button when finished.

- 52 -

ROI-S04451

2.20.9 Sub INTFC There are 4 optional sub interfaces available in the Pasolink + system. On this section, these sub-interfaces can be defined and specified accordingly. 2.20.9.1 Defining the SUB INTFC To set the type of sub interface mounted in the IDU: 1. 2. Click on the [SUB INTFC] button in the Provisioning window. Select the type of interface used from the ensuing window. If there is no one of 4 sub interfaces, Not used must be selected.

3. 4.

Click on [Execute] button to apply the newly defined sub interface. Click on [Close] button when finished.

2.20.9.2 Defining the Wayside (WS) Interface To specify the type of WS interface used: 1. 2. Click on the [WS INTFC] button in the Provisioning window. Select the type of WS interface on the ensuing window.

3. 4.

Click on [Execute] button to apply the new setting. Click on [Close] button when finished.

- 53 -

ROI-S04451

2.20.9.3 WS Line Length To specify the WS line length: 1. 2. Click on the [WS Line Length] button in the Provisioning window. Select the line length in meters from the ensuing window. The WS line length can be set from 0 to 199 meters (from 0 to 655 ft).

3. 4.

Click on [Execute] button to apply the newly specified length. Click on [Close] button when finished.

2.20.10 BER Threshold

From MUX

From DMR

MUX

RADIO

(1) Signal Degrade (B1,B2) E-BER (B1, B2, B3)

(3)

(2)

Low BER (RX Switch) High BER

Signal Degrade (B1,B2) E-BER (B1, B2, B3)

- 54 -

ROI-S04451

The BER in the Pasolink+ system is monitored in 3 sections - (1) the MUX section, (2) the DMR section and the (3) Radio section. The Radio section is available 1+1 systems only and is used for switchover function. The figure below illustrates these sections The MUX and DMR section BER is measured in terms of Signal Degrade and E-BER. Signal Degrade is triggered when the BER is worse than the preset threshold (1E-6, 1E-7, etc.). Excessive BER (E-BER) occurs when the BER is worse than the preset threshold (1E-3, 1E-4, or 1E-5). The radio section, on the other hand, monitors the BER for switchover purposes. When the BER becomes worst than the preset value (3E-6,3E-7, etc) of the Low BER (RX Switch) the RX is switched to the other system in a 1+1 configuration. In a similar manner, when the BER becomes worse than the preset value (3E-4,3E-5,3E-6) for High BER, the switched to the other system. The preset value mentioned above is called the BER Threshold. The BER threshold can be set in 6 points: (1) Signal Degrade (MUX), (2) E-BER (MUX), (3) Signal Degrade (DMR), (4) E-BER (MUX), (5) Low BER, and (6) High BER. Low BER and High BER, however, are only available in 1+1 systems. The MUX and DMR are classified with B1, B2 and B3 section respectively. There is EBER only for B3 2.20.10.1 B1 Signal Degrade (MUX) To set the threshold for signal degrade: 1. 2. Click on the [B1 Signal Degrade (MUX)] button in the Provisioning window. Select the preset BER value that will trigger the signal degrade. The factory setting is 1E-6.

3. 4.

Click on [Execute] button to apply the new threshold. Click on [Close] button when finished.

2.20.10.2 B1 E-BER (MUX) To set the E-BER Threshold for the MUX section: 1. 2. Click on the [B1 E-BER (MUX)] button in the Provisioning window. Select the preset value wherein the E-BER will be triggered.

- 55 -

ROI-S04451

3. 4.

Click on [Execute] button to apply the new threshold. Click on the [Close] button when finished.

2.20.10.3 B2 Signal Degrade (MUX) To set the threshold for signal degrade: 1. 2. Click on the [B2 Signal Degrade (MUX)] button in the Provisioning window. Select the preset BER value that will trigger the signal degrade. The factory setting is 1E-6.

3. 4.

Click on [Execute] button to apply the new threshold. Click on [Close] button when finished.

2.20.10.4 B2 E-BER (MUX) To set the E-BER Threshold for the MUX section: 1. Click on the [B2 E-BER (MUX)] button in the Provisioning window. 2. Select the preset value wherein the E-BER will be triggered.

3. Click on [Execute] button to apply the new threshold. 4. Click on the [Close] button when finished. 2.20.10.5 B3 E-BER (MUX) To set the E-BER Threshold for the MUX section: 1. Click on the [B3 E-BER (MUX)] button in the Provisioning window. 2. Select the preset value wherein the E-BER will be triggered.

- 56 -

ROI-S04451

3. Click on [Execute] button to apply the new threshold. 4. Click on the [Close] button when finished. 2.20.10.6 B1 Signal Degrade (DMR) To set the threshold for signal degrade: 1. Click on the [B1 Signal Degrade (DMR)] button in the Provisioning window. 2. Select the preset BER value that will trigger the signal degrade. The factory setting is 1E-6.

3. 4.

Click on [Execute] button to apply the new threshold. Click on [Close] button when finished.

2.20.10.7 B1 E-BER (DMR) To set the E-BER Threshold for the DMR section: 1. 2. Click on the [E-BER (DMR)] button in the Provisioning window. Select the preset value wherein the E-BER will be triggered.

3. 4.

Click on [Execute] button to apply the new threshold. Click on the [Close] button when finished.

- 57 -

ROI-S04451

2.20.10.8 B2 Signal Degrade To set the threshold for signal degrade: 1. Click on the [B2 Signal Degrade (DMR)] button in the Provisioning window. 2. Select the preset BER value that will trigger the signal degrade. The factory setting is 1E-6.

3. Click on [Execute] button to apply the new threshold. 4. Click on [Close] button when finished. 2.20.10.9 B2 E-BER To set the E-BER Threshold for the DMR section: 1. Click on the [B2 E-BER (DMR)] button in the Provisioning window. 2. Select the preset value wherein the E-BER will be triggered.

3. Click on [Execute] button to apply the new threshold. 4. Click on the [Close] button when finished. 2.20.10.10 B3 E-BER

To set the E-BER Threshold for the DMR section: 1. Click on the [B3 E-BER (DMR)] button in the Provisioning window. 2. Select the preset value wherein the E-BER will be triggered.

3. Click on [Execute] button to apply the new threshold. 4. Click on the [Close] button when finished.

- 58 -

ROI-S04451

2.20.10.11

High BER (Radio) [for 1+1 systems only]

To set the threshold for High BER: 1. 2. Click on the [High BER] button in the Provisioning window. Select the preset BER value that will trigger the signal degrade. The factory setting is 3E-4.

3. 4. 2.20.10.12

Click on [Execute] button to apply the new threshold. Click on [Close] button when finished. RX Switch (Radio) [for 1+1 systems only]

To set the Low BER: 1. 2. Click on the [RX Switch] button in the Provisioning window. Select the preset value wherein the E-BER will be triggered.

3. 4.

Click on [Execute] button to apply the new threshold. Click on the [Close] button when finished.

- 59 -

ROI-S04451

2.21 Link Performance Monitor


The following performance items can be monitored according to G.826 recommendation: Out of Frame Second (OFS) - the total number of seconds the out of frame condition is generated in 15 minute-blocks.(OFS is applied to the RST only) Errored Second (ES) the cumulative time in which more than one B1 error pulse per second was detected (ES is not applied to the MSA) Severely Errored Second (SES) the cumulative time in which the BER of onesecond period exceeded 10E-3. (SES is not applied to the MSA) Unavailable Second (UAS) the cumulative time in which the unit remained inoperative (UAS is not applied to the MSA) Background Block Error (BBE) - the sum of the B1 background block error PJE+ (is applied to the MSA only) PJE (is applied to the MSA only) Red color in Performance monitor window indicates the occurrence of performance items exceeding the threshold value. The threshold values can be set in Threshold window. The detailed daily performance data can be seen by clicking on the [Detail] button. 2.21.1 Viewing Summary Link Performance Monitor To view Summary Link Performance Monitor: 1. Click on Link Performance Monitor in the NE-specific menu bar of the target Pasolink the Pasolink that you intend to monitor. And select the item on the ensuing window. AS for [Section Trace] and [signal Label], proceed to chart 2.18.5

Summary Link Performance Monitor Window (ex; RST)

- 60 -

ROI-S04451

Summary Link Performance Monitor Window (ex; LPT) 2.21.2 Threshold setting To set the threshold values: 1. Click on [Threshold] button in the Summary Link Performance Monitor window

This check box is used to set the same value to all VC12s , and this is equipped with the LPT layer window

Threshold Setting Window (ex; RST) 2. Select the performance item that is to be configured on the table shown above. The G.826 measure becomes available for setting when selected. The arrow buttons on the left-hand side of the field indicates this. Set the value when the alarm Occur and when the alarm Recover in the appropriate field. The measure will issue an alarm status when it reaches the alarm occur value or issue an alarm clear status when it reaches the recover value set in the threshold table. Click on [Execute] button to activate the new settings. Click on [Close] button when finished.

3.

4. 5.

- 61 -

ROI-S04451

2.21.3 Link Performance Monitor (Daily Data) window.

This window contains the Link Performance data of the current 8 days. To view the Link Performance Monitor (Daily Data) window:
1. Click [Detail] button in Link Performance Monitor window.

Link Performance Monitor window (ex: RST) 2. On this window a table presents the available data in the CTRL. The table is presented as G.826 measure versus the Date. The date buttons on the right-hand side of the table is selectable. Moreover, the buttons reflect the summary alarm for that specific date. Click on the date buttons to display the detailed 15-min data for that date.

3.

2.21.4 Link Performance Monitor (15 min Data) window To view the 15-min Data: 1. Click button of the target date in Link Performance Monitor (Daily Date) window to display the detailed 15-min performance data.

Refresh 2.

Save

Link Performance Monitor (15-min Data) Window (ex; RST) The data can be saved in text format by clicking on the save icon. Or can be refreshed by clicking on the refresh button.

- 62 -

ROI-S04451

2.21.5 Section Trace This function is used to enter Section Trace of J0 J1 and J2 byte. The following items are displayed Transmitting Pattern: Pattern to transmitted to MUX or DMR Expected Pattern: Expected Pattern to received from MUX or DMR Received Pattern: Actual Pattern to received from MUX or DMR To view the threshold values: 1. Click on Link Performance Monitor in the NE-specific menu bar of the target Pasolink the Pasolink that you intend to monitor. And select [Section Trace] window.

This function is used to remove all check of VC12 This function is used to check all VC12 Check Box: This function is used to appoint someVC12s to be detected J2 byte

- 63 -

ROI-S04451

2.21.6 Section Trace J0 (MUX) To set the threshold values: 1. 2. Click on [MUX] button in the [Section Trace J0] window Enter the transmitting and expected patterns CAUTION: Characters corresponds to the ASCII code 20h to 7Fh are valid for transmitting/expected pattern. Fifteen characters must be entered. If less than fifteen characters are entered, rest that characters has been not entered are recognized as space (ASCII code 20h).

2.21.7 Section Trace J0 (DMR) To set the threshold values: 1. 2. Click on [DMR] button in the [Section Trace J0] window Enter the transmitting and expected patterns CAUTION: Characters corresponds to the ASCII code 20h to 7Fh are valid for transmitting/expected pattern. Fifteen characters must be entered. If less than fifteen characters are entered, rest that characters has been not entered are recognized as space (ASCII code 20h).

2.21.8 Section Trace J1 (MUX) To set the threshold values: 1. 2. Click on [MUX] button in the [Section Trace J1] window Enter the transmitting and expected patterns CAUTION: Characters corresponds to the ASCII code 20h to 7Fh are valid for transmitting/expected pattern. Fifteen characters must be entered. If less than fifteen characters are entered, rest that characters has been not entered are recognized as space (ASCII code 20h).

- 64 -

ROI-S04451

2.21.9 Section Trace J1 (DMR) To set the threshold values: 1. 2. Click on [DMR] button in the [Section Trace J1] window Enter the transmitting and expected patterns CAUTION: Characters corresponds to the ASCII code 20h to 7Fh are valid for transmitting/expected pattern. Fifteen characters must be entered. If less than fifteen characters are entered, rest that characters has been not entered are recognized as space (ASCII code 20h).

2.21.10 Section Trace J2 To set the threshold values: 1. 2. Click on the number of [VC12] button in the [Section Trace J2] window Enter the transmitting and expected patterns CAUTION: Characters corresponds to the ASCII code 20h to 7Fh are valid for transmitting/expected pattern. Fifteen characters must be entered. If less than fifteen characters are entered, rest that characters has been not entered are recognized as space (ASCII code 20h).

2.21.11 Signal Label This function is used to monitor Signal Label To monitor the Signal Label values: 1. Click on Link Performance Monitor in the NE-specific menu bar of the target Pasolink the Pasolink that you intend to monitor. And select [Signal Label] window. As for Signal Label(LPT), Click on VC12 button, and check the desired VC12 Execute Refresh

2. 3.

- 65 -

ROI-S04451

Refresh: Get the current Signal Label value

- 66 -

ROI-S04451

2.22 Event Log


The Event Log Windows displays the date when the event or command was received, the equipment, item, and status. 2.22.1 Event Log Monitor 1. 2. Click on Event Log in the NE-specific menu bar of the target Pasolink the Pasolink that you intend to monitor. A message window showing the progress of the uploading of the Event Log data will appear on the screen. Wait until the PNMT finishes the uploading of the data. The progress window will automatically close once the uploading is completed. The Event Log View will be displayed. The event log is presented in a table form showing the date of the event, the item that triggered the event and the status change. Sorting is possible for every column in EventLog window. The date shown in the Event Log window will be the format set up by OS

3.

4. 5.

- 67 -

Das könnte Ihnen auch gefallen