Two (insulated) poles phase phase

Voltage transformers VRC3/S1 - VRC3/S2


0

# Max reference voltage for insulation: 24 - 36 kV # Usn secondary rated voltage: see selection table # Upn primary rated voltage: refer to page 37 # rated thermal output: VRC3/S1 = 700 VA VRC3/S2 = 350 350 VA # voltage factor: 1.2 ill.

Selection table
n of secondaries per VT standard types application standard secondary voltage (V) operation 2nd sec. 1st sec. 1 VRC3/S1 measuring or protection 2 VRC3/S2 1 for measuring or protection (1st sec.) 1 for protection (2nd sec.) 100 - 100 or 110 - 110 simultaneous (1) 0,5 or 1 0,5 or 1 25 30 50 100 15 02 0,5 15 25 30 50 100

100 or 110

100 feasability (1) Output with simultaneous operation means that accuracy class of the 1st secondary is guaranteed with the 2 secondary under load and vice versa
nd

accuracy class output accuracy class output

0,2 25 50 50

0,5 75

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and required output indicate a point within the blue area.

Dimensions (mm)
type VRC3/S1-S2 Weight kg 45

DJ 1113

380 320
225 255

282 400

390

GROUPE SCHNEIDER

300 325

N4 holes 11

69

320 445

56
M6 screw type secondary and earthing terminals

AMTED300031EN_050_053. fm/50

Gamme

Schneider Electric

Two (insulated) poles phase phase

Voltage transformers VDC11/S1 - VDC11/S2


0

# Max reference voltage for insulation: 7.2 - 12 kV # Usn secondary rated voltage: see selection table # Upn primary rated voltage: refer to page 37 # rated thermal output: VDC11/S1 = 200 VA VDC11/S2 = 100 100 VA # voltage factor: 1.2 ill.

Selection table
n of secondaries per VT standard types application standard secondary voltage (V) operation 2nd sec. 1st sec. 1 VDC11/S1 measuring or protection 2 VDC11/S2 1 for measuring or protection (1st sec.) 1 for protection (2nd sec.) 100 - 100 or 110 - 110 simultaneous (1) 0,5 or 1 0,5 or 1 25 20 30 50 15 02 0,5 15 25 20 30 50

100 or 110

50 feasability (1) Output with simultaneous operation means that accuracy class of the 1st secondary is guaranteed with the 2 secondary under load and vice versa
nd

accuracy class output accuracy class output

0,2 15 25 25

0,5 40

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and required output indicate a point within the blue area.

Dimensions (mm)
type VDC11/S1-S2 Weight kg 15

100
M 10 DIN 40430 Pg 16
A

110
M8

100

125

148

221

GROUPE SCHNEIDER

31

270

N4 holes 11
M5 screw type secondary and earthing terminals

Schneider Electric

20

168

150

350

Gamme

AMTED300031EN_050_053. fm/51

Two (insulated) poles phase phase

Voltage transformers VDC21/S1 - VDC21/S2


0

# Max reference voltage for insulation: 7.2 - 12 - 17.5 - 24 kV # Usn secondary rated voltage: see selection table # Upn primary rated voltage: refer to page 37 # rated thermal output: VDC21/S1 = 300 VA VDC21/S2 = 150 150 VA # voltage factor: 1.2 ill.

Selection table
n of secondaries per VT standard types application standard secondary voltage (V) operation 2nd sec. 1st sec. 1 VDC21/S1 measuring or protection 2 VDC21/S2 1 for measuring or protection (1st sec.) 1 for protection (2nd sec.) 100 - 100 or 110 - 110 simultaneous (1) 0,5 or 1 0,5 or 1 25 30 50 100 15 02 0,5 15 25 30 50 100

100 or 110

100 feasability (1) Output with simultaneous operation means that accuracy class of the 1st secondary is guaranteed with the 2 secondary under load and vice versa
nd

accuracy class output accuracy class output

0,2 25 50 50

0,5 75

Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and required output indicate a point within the blue area.

Dimensions (mm)
type VDC21/S1-S2 Weight kg 21

165
M 10

130

100

150

178

DIN 40430 Pg 16

M8

280

GROUPE SCHNEIDER

31

280

N4 holes 14
M5 screw type secondary and earthing terminals

20

188

160

370

AMTED300031EN_050_053. fm/52

Gamme

Schneider Electric

Voltage transformers Order form


0

Part 1 Type: Maximum voltage level for insulation (kV): Number of secondaries: Primary rated voltage: Secondary rated voltages: Voltage factor: 1 secondary Output:
st

7.2 1

12 2

17.5 3 kV V

24

36

Class: Class: Class: simultaneous IEC

2 secondary
nd

Output: Output:

3 secondary
rd

Operation Standards:

separate Others

Part 2 - Optional accessories Cover or secondary terminals :

Part 3 - Special versions Frequency: 60 Hz Others

Non standard primary voltage: Non standard secondary voltages: Primary voltage change with secondary tap:
Others:

kV V

Note Apparatus with the following features are defined as standard: # electrical features, max. reference voltage, rated voltages, output and classes strictly as indicated in the table of options from page 38 to page 52 # pickled copper primary holds and secondary terminals # fixtures, if any, are zinc-plated steel.