Project: Location: Contract: Engineer:

Earthing Grid _ Golden Finger Dubai , UAE +91 22 33221207 Shrikant Wahane

ETAP
6.0.0

Page: Date: SN:

1 02-17-2014 12345678 golden finger

Study Case: MainGrid_GF

Filename:

Main Earthing grid calculations for Golden Finger project

Electrical Transient Analyzer Program

Ground Grid Systems

IEEE Std 80-2000

Number of Ground Conductors: Number of Ground Rods:

33 50

Total Length of Ground Conductors: Total Length of Ground Rods:

4730.00 m 500.00 m

Frequency: Unit System: Project Filename:

50.0 Metric golden finger

Output Filename:

C:\ETAP 600\golden finger\Grid1_MainEGRID.GR1

Project: Location: Contract: Engineer:

Earthing Grid _ Golden Finger Dubai , UAE +91 22 33221207 Shrikant Wahane

ETAP
6.0.0

Page: Date: SN:

2 02-17-2014 12345678 golden finger

Study Case: MainGrid_GF

Filename:

Main Earthing grid calculations for Golden Finger project

Ground Grid Input Data System Data:


Short-Circuit Current Ambient Temp. C
35.00

Fault Duration (Seconds) Cp Projection Factor %


100.0

Freq. Hz
50.0

Weight kg
70

Total Fault Current kA


36.000

X/R
12.00

Sf Division Factor %
100.0

Tf for Total Fault Duration


0.50

Tc for Sizing Ground Conductors


0.50

Ts for Available Body Current


0.50

Soil Data:
Surface Material Material Type
Gravel

Upper Layer Soil Depth m


0.750

Lower Layer Soil Depth m


2.00

Resistivity W.m
8534.4

Material Type
Moist soil

Resistivity W.m
250.0

MaterialType
Moist soil

Resistivity W.m
100.0

Material Constants:
ar Factor

Conductivity Conductor/Rod
Conductor & Rod

@ 20 C 1/C
0.00393

K0 @ 0 C
234.0

Fusing Temperature C
1083.0

Resistivity of Ground Conductor @ 20C


mW.cm
1.72

Thermal Capacity Per Unit Volume J/(cm.C)


3.42

Type
Copper, annealed soft-drawn

%
100.0

Rod Data:
Diameter cm
2.000

Length m
10.00

No. of Rods
50

Arrangement
Rods along Grid Perimeter

Cost $/Rod
100.00

Grid Configuration:
Grid Length m Depth m
0.60

Conductor Size mm
300

Number of Conductors in X Direction


11

Separation m in X Direction
10.0

Lx
210.00

Ly
110.00

in Y Direction
22

in Y Direction
11.0

Cost $/m
10.00 Shape: Rectangular

Cost:
Conductor Total No.
33

Rod Cost $
47300.00

Total Length m
4730.00

Total No.
50

Total Length m
500.00

Cost $
5000.00

Total Cost $
52300.00

Project: Location: Contract: Engineer:

Earthing Grid _ Golden Finger Dubai , UAE +91 22 33221207 Shrikant Wahane

ETAP
6.0.0

Page: Date: SN:

3 02-17-2014 12345678 golden finger

Study Case: MainGrid_GF

Filename:

Main Earthing grid calculations for Golden Finger project

Ground Grid Summary Report


Rg Ground Resistance Ohm
0.439

GPR Ground Potential Rise Volts


16399.3

Touch Potential Tolerable Volts


2908.2

Step Potential Calculated %


121.8

Calculated Volts
3543.2

Tolerable Volts
10966.8

Calculated Volts
2201.5

Calculated %
20.1

Total Fault Current: Maximum Grid Current:

36.000 kA 37.350 kA

Reflection Factor (K): Surface Layer Derating Factor (Cs): Decrement Factor (Df):

-0.943 0.945 1.037

Warnings:
The maximum Touch Voltage exceeds the tolerable limits Grid area is smaller than 6.25 m or greater than 10,000 m

Report of Intermediate Constants for IEEE 80 Methods


- Correction factor for grid geometry regarding touch voltage (Kim):

2.889 2.889

- Correction factor for grid geometry regarding step voltage (Kis): - Spacing factor for touch voltage (Km): - Spacing factor for step voltage (Ks): 0.727 0.324

- Corrective weighting factor that adjusts for the effects of inner conductors on the corner mesh (Kii): - Constants 1 related to the geometry of system (K1): - Constants 2 related to the geometry of system (K2): 1.334 5.660

1.000