Beruflich Dokumente
Kultur Dokumente
Todays Agenda
Why the Concern over Ground Faults?
Electrical Grounding Options Upgrading from Ungrounded to High Resistance Grounded
The Concerns with Solidly Grounded Systems Controlling Time and Current to Minimize Hazard
5
0 0-99 100-199 200-299 300-399 400-499 500-599 1m - 1.9m over 2m
All figures correspond to losses associated with electrical ground faults that occurred over a seven year period and were reported by one leading US based Insurance Company .
Most Effective
Webinar Focus
Awareness
Hazard Category Labels
Todays Agenda
Why the Concern over Ground Faults?
The Concerns with Solidly Grounded Systems Controlling Time and Current to Minimize Hazard
Feeders must be de-energized to locate ground fault Susceptible to voltage buildup 6-9 times above ground on intermittent arcing faults
GND
C A
C A
B No Ground Fault
B C 3 IC0 3 IC0
IF = 3IC0
Va
Vcb = Vcg
Vab = Vag
60 Vb Vca
Ic=3Ico
Vbc
GND
Protection
Personal Protection Wearing of PPE Administration
Prevention
Engineering Controls Arc Resistant Switchgear
Substitution Reduction of Time or Fault Current Available
Grounding
System grounding the connection of earth ground to the neutral points of current carrying conductors such as the neutral point of a circuit, a transformer, rotating machinery, or a system, either solidly or with a current limiting device. Equipment grounding the connection of earth ground to non current carrying conductive materials such as conduit, cable trays, junction boxes, enclosures and motor frames.
Todays Agenda
Why the Concern over Ground Faults? Electrical Grounding Options
The Concerns with Solidly Grounded Systems Controlling Time and Current to Minimize Hazard
IEE Std 242-1986 Recommended Practice for the Protection and Coordination of Industrial and Commercial Power Systems
7.2.5 Ungrounded systems offer no advantage over high-resistance grounded systems in terms of continuity of service and have the disadvantages of transient overvoltages, locating the first fault and burndowns from a second ground fault. For these reasons, they are being used less frequently today than high-resistance grounded systems
Faulted feeder remains in service Ground fault pulse locating provides valuable troubleshooting tool To prevent voltage escalation on the phase-to-ground capacitance during intermittent arcing ground faults, the resistor current must exceed system charging current, IR 3IC0
The resistor must be built with a low coefficient of resistance/Temperature to ensure that it carries the rated current during a ground fault condition
2. 2. Experience
4. 4. Measurement
I G 3I C 0
VA EI G
C
VA
R NG R
B
E 3IG X C0 3
R NG R
IG 3IC 0
N ZIG-ZAG Transformer RNGR
2 W NG R I G R NG R
Todays Agenda
Why the Concern over Ground Faults? Electrical Grounding Options
The Concerns with Solidly Grounded Systems Controlling Time and Current to Minimize Hazard
To avoid ground fault escalation into a phase-to-phase fault, system charging current should be 5.5A (J.R. Dunki-Jacobs) 5A-10A resistor typical (IR 3IC0)
Alarm pick-up level typically 50% resistor let-through current Optional individual motor feeder alarm relays set at 10% prealarm setting (monitor winding insulation)
32.34
5A 1 min
51G
5A 1 min
51G
5A 1 min
G
87GD
G
87GD
G
87GD
87G 52
87G 52
87G 52
51N
40A
52
51G
40A 1 Sec
100A 10 sec
600V
To DCS 15-20A, 3P 100 kAIC
VOLTAGE SE NSING
To DCS
5A
Todays Agenda
Why the Concern over Ground Faults? Electrical Grounding Options Upgrading from Ungrounded to High Resistance Grounded
Arc Flash hazard when opening the main switchboard to trace the fault
Second ground fault resulting in destructive phase-to-phase faults Loss of the Neutral Path resulting in loss of protection Closing a main-tie onto a ground fault Intermittent Faults
TRIP ZSCT
Motor
Motor
TRIP ZSCT
Motor
Motor
Motor
Motor
TRIP ZSCT
Motor
Motor
Motor
Motor
Tie into Internet Monitor plant anywhere in world Notify maintenance or local qualified electrical contractor to locate ground fault
Motor
Motor
Todays Agenda
Why the Concern over Ground Faults? Electrical Grounding Options
277V
Potential for severe damage at point of fault due to intense heat energy of the arc Arcing ground faults are more common than bolted faults
Switchboard of a solidly grounded system at an amusement park in Ontario Canada
B)
Protection
Personal Protection Wearing of PPE Administration
Prevention
Engineering Controls Arc Resistant Switchgear
Substitution Reduction of Time or Fault Current Available
Todays Agenda
Why the Concern over Ground Faults? Electrical Grounding Options
Ground fault relays trip breakers and limit how long a fault lasts
1.
2.
3.
4.
5.
to reduce burning and melting effects in faulted electric equipment, such as switchgear, transformers, cables and rotating machines to reduce mechanical stresses in circuits and apparatus carrying fault currents to reduce electric-shock hazards to personnel caused by stray ground fault currents in the ground return path to reduce arc blast or flash hazard to personnel who may have accidentally caused or who happen to be in close proximity to the fault current to reduce the momentary line-voltage dip occasioned by the occurrence and clearing of a ground fault
Resistors rated for : Line-to-neutral voltage, let-thru current, allowable on time Grounding transformers rated for : Line-to-line voltage, let-thru current, allowable on time
Todays Agenda
Why the Concern over Ground Faults? Electrical Grounding Options
Protection
Personal Protection Wearing of PPE Administration
Prevention
Engineering Controls Arc Resistant Switchgear
Substitution Reduction of Time or Fault Current Available
-35 ms:
no significant damage to persons or Switchgear, which can often be returned to use after checking the insulation resistances
small damage, requires cleaning and possibly some minor repair likely large damage both for persons and the switchgear, which must be partly replaced.
- 100ms:
3.23 Cal/cm2
- 500ms:
18.1 Cal/cm2
The arc burning time is the sum of the time to detect the arc and the time to open the correct breaker.
*Based on 50kA maximum bolted fault current on a 480 volt solidly grounded system.
An arc is developed within milliseconds and leads to the discharge of enormous amounts of destructive energy. The energy in the arc is directly proportional to the square of the short-circuit current and the time the arc takes to develop. Reduce the Time, Reduce the Damage,
RELAY
175 A
400 A
OVERLOAD
GROUND FAULT
40 A 1 sec
13.8 kV
51G
100 A 10 sec
200 A 10 sec
80 A 1 sec
52 51N 40 A 1 sec
52 51N 80 A 1 sec
To avoid erroneous trips, it is normal to use a short-circuit current detector along with one of the aforementioned arc indicators. The most common pairing in North America is current and light.
80%
Productivity Impact
Ungrounded System
Severe Unknown High Possible but not recommended
Overvoltages
Equipment Damage
Overcurrent-Damage at fault point Maintenance Costs Continuous Operation with Ground Fault
Downtime
Relay Co-ordination (Appropriate equipment Tripped, Ease of Fault Location Safety to Personnel
Difficult
Difficult
Good
Excellent
Personnel
Poor
Poor
Good
Excellent
Resistance Grounded
Eliminate Risk
Upgrade to HRG with first fault time delay, second fault trip and feeder identification
THANK YOU