FFU Series

FAN FILTER UNITS


The FFU Series of fan filter units are specifically designed to provide clean, unidirectional supply air at controlled discharge velocities for cleanroom, pharmacy and laboratory applications. These units come standard with many useful features and can be customized with standard or special options to suit virtually any project.

Fan powered diffusers with integrated high efficiency filters for critical applications requiring additional static pressure boost.

Quiet, low heat, energy efcient ECM motor programmed for constant ow

Deluxe speed controllers with digital display feedback

LED kits for convenient roomside visual of lter condition and motor status

High capacity or room-side replaceable lter modules available

www.price-hvac.com for additional product information, including product videos and brochures.

Fan Filter Units FFU Series


Return to product page

Product Information
Price FFU Series modules consist of a fan/ motor assembly and high efficiency HEPA/ ULPA filter. The modules are designed to provide filtered, unidirectional vertical air flow over a cleanroom space. Price fan filter units are recommended for use in all types of cleanroom environments semiconductor and microelectronics manufacturing facilities, as well as pharmaceutical and medical labs. The product is designed for use in Class 10 through Class 100,000 cleanroom spaces. High capacity (FFU-HC) units offer the largest active filter area and the highest air flow capacity of all Price fan filter units. Removable filters allow for periodic filter changes (filter removal and replacement requires access to the ceiling plenum), and an expanded metal mesh screen protects the filter media from inadvertent damage during installation. Filter face is PSL tested post-assembly. Room-Side-Removable (FFU/FFUSS) units offer the convenience and flexibility to periodically replace filters from the roomside of installed modules. All RSR units are PAO tested to ensure the knife-edge frame is completely sealed. Filters are latched in place such that the continuously welded knife-edge is embedded into the filter gel seal, creating a leak-proof barrier. Additional benefits include optional roomside removable motors and 3/8 in. NPT aerosol injection ports. Once installed, the filter is protected by a perforated face that is secured to the main assembly using quarterturn fasteners. ECM motor technology is an available option on all Price fan filter units. Key benefits of these motors include: Lower energy use. Lower operating temperatures. Programmed to deliver constant air volume, independent of filter condition. Features Quiet operation - High efficiency soundabsorbing foam liners and Motors mounted with vibration isolators. Non-ducted modules are ETL certified to UL507 standard. Ducted modules are ETL certified to UL1995 standard (with optional plenum rated polymer foam insulation). FFU - Room-Side Replaceable Construction FFU-HC - High Capacity Construction

Filter Retainers

Four (4) thumb wheel retaining latches hold the filter in place and allow for easy filter replacement without the need for tools. Unique adjustable latch design does not penetrate the knife-edge, further reducing the risk of leaks.

Copyright Price Industries Limited 2011.

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.

E-141

CRITICAL ENVIRONMENTS

Fan Filter Units FFU Series


Return to product page

Product Information
Standard Features (all FFU types) UL900 certified filters. Integral fan/motor assembly. Blower wheel is directly driven by PSC thermally protected motor. Blower wheel is encased in an engineered enclosure to optimize capacity and reduce noise. 25-30% efficient washable prefilter (MERV4). Lined with foam insulation to reduce sound levels. Solid state speed control. Eyebolts at each plenum corner for support from above. FFU-HC Unit Features Replaceable HEPA (99.99% efficiency on 0.3 um particles) filter requires access above ceiling. Expanded metal mesh screen protects filter media. Largest active filter area. Filter face is PSL Tested post-assembly. FFU Room-Side Replaceable Features Room-side replaceable HEPA filter (minimum 99.99% efficiency on 0.3 m particles). Knife-edge frame for gel filter seal. Perforated laminar flow face with easy access turn fasteners. All units factory PAO tested to ensure casing leakage is consistent with the filter. Walkable Plenum (up to 250lbs) aluminum FFU. Static pressure port. 3/8 in. NPT aerosol injection port (optional). Washable Pre-Filter (non-ducted units). Options (FFU and FFU-HC) 1/3 HP ECM - energy efficient motor programmed for constant flow. ULPA filter (minimum 99.9995% efficiency on 0.12 m particles) recommended with ECM motor. 115V, 208V, 240V and 277V supply voltages (115, 240, 277 for ECM). 10 in. or 12 in. diameter inlet collar for direct connection to conditioned air. 8 ft power cord (115V, 277V (nonducted)). Ion bar for neutralizing static charges (optional). Washable Pre-Filter (ducted units). Construction / Finish Plenum 14 gauge mill finish aluminum (optional powder coat finishes available. 20 gauge stainless steel (2B polished finish) RSR units only. FFU-HC

G L W

Dimensional Data - FFU (Standard Filter) - Imperial, in. (Metric, mm)


Unit Size 2x4 2x2 Inlet Collar F 16 (406) G 20 (508) W 23 5/8 (600) L 47 5/8 (1210) 23 5/8 (600) H PSC 12 1/2 (318) 12 1/2 (318) ECM 14 3/4 (375) 14 3/4 (375)

FFU Room-Side Replaceable

CRITICAL ENVIRONMENTS

G H L W

Dimensional Data - FFU (RSR Filter) - Imperial, in. (Metric, mm)


Unit Size 2x4 2x3 2x2 Inlet Collar F 16 (406) G 20 (508) W 23 /4 (603)
3

L 47 3/4 (1213) 35 3/4 (908) 23 3/4 (603)

H PSC 14 1/4 (362) 15 1/4 (387)* ECM 16 1/2 (419) 17 1/2 (445)*

* 3 lter media.

Face - HC Units Aluminum frame w/expanded mesh screen protecting filter media. Face - RSR Units Aluminum perforated face 16 gauge mill finish aluminum (optional powder coat or anodized finishes available). Stainless steel perforated face 20 gauge stainless steel (#4 brushed finish).

PSL Tested - FFU-HC PAO Tested - FFU/FFUSS


ETL certified to: UL507 - open inlet UL1995 - ducted inlet
Copyright Price Industries Limited 2011.

E-142

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.

Fan Filter Units FFU Series


Return to product page

FFU Room-Side Replaceable Filters Performance Data


Standard PSC Motor Operating* Motor Range Amps @ HP Voltage FPM 90FPM 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/3 1/3 1/3 1/3 115 208 240 277 115 208 240 277 115 208 240 277 115 208 240 277 115 208 204 277 60 - 120 60 - 120 60 - 120 60 - 120 60 - 120 60 - 120 60 - 120 60 - 120 90 - 140 90 - 140 90 - 140 90 - 140 90 - 140 90 - 140 90 - 140 90 - 140 90 - 130 90 - 130 90 - 130 90 - 130 4.5 1.4 1.5 1.6 4.9 1.7 1.9 1.8 3.9 1.6 1.7 1.6 3.7 1.6 1.6 1.5 3.0 1.4 1.5 1.3 Sensible Heat Watts @ (BTU/HR) 90FPM @ 90FPM 400 400 350 350 350 290 300 360 190 170 190 230 180 170 180 220 110 120 120 120 957 1128 854 1051 784 513 507 692 507 439 405 462 490 473 434 404 336 275 270 245 Total Unit Weight Max (approx) Static Lb (kg) Pressure 75 (34) 75 (34) 75 (34) 75 (34) 80 (36) 80 (36) 80 (36) 80 (36) 53 (24) 53 (24) 53 (24) 53 (24) 53 (24) 53 (24) 53 (24) 53 (24) 55 (25) 55 (25) 55 (25) 55 (25) 0.9 0.9 0.9 0.9 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.2 1.3 1.3 1.1 0.6 0.6 0.6 0.6 Sound Level dBA 54 54 54 54 55 55 55 55 45 45 45 45 47 47 47 47 54 54 54 54

Unit Size 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x4 2x3 2x3 2x3 2x3 2x3 2x3 2x3 2x3 2x2 2x2 2x2 2x2

Filter Type HEPA HEPA HEPA HEPA ULPA ULPA ULPA ULPA HEPA HEPA HEPA HEPA ULPA ULPA ULPA ULPA HEPA HEPA HEPA HEPA

Max Amps 4.7 1.6 1.7 1.8 4.9 1.7 1.9 1.8 3.9 1.7 1.8 1.7 3.9 1.7 1.8 1.7 3.0 1.4 1.5 1.3

ECM Motor Operating* Motor Range Amps @ HP Voltage FPM 90FPM 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 115 240 277 115 204 277 115 240 277 115 240 277 115 240 277 115 240 277 60 - 140 60 - 140 60 - 140 60 - 115 60 - 115 60 - 115 60 - 140 60 - 140 60 - 140 60 - 140 60 - 140 60 - 140 60 - 140 60 - 140 60 - 140 60 - 140 60 - 140 60 - 140 1.8 0.8 0.8 2.4 1.1 1.1 0.8 0.3 0.3 1.0 0.4 0.4 1.3 0.6 0.4 1.5 0.7 0.6 Sensible Heat Watts @ (BTU/HR) 90FPM @ 90FPM 140 120 140 180 180 200 48 42 48 60 60 58 90 80 70 100 110 100 400 400 400 461 461 461 304 304 304 304 304 304 160 160 160 160 160 160 Total Unit Weight Max (approx) Static Lb (kg) Pressure 75 (34) 75 (34) 75 (34) 75 (34) 75 (34) 75 (34) 53 (24) 53 (24) 53 (24) 53 (24) 53 (24) 53 (24) 55 (25) 55 (25) 55 (25) 55 (25) 55 (25) 55 (25) 1.0 1.0 1.0 1.1 1.1 1.1 1.4 1.4 1.5 1.8 1.8 1.8 0.9 0.9 0.9 1.0 1.0 1.0 Sound Level dBA 52 52 52 54 54 54 44 44 44 45 45 45 52 52 52 52 52 52

Unit Size 2x4 2x4 2x4 2x4 2x4 2x4 2x3 2x3 2x3 2x3 2x3 2x3 2x2 2x2 2x2 2x2 2x2 2x2

Filter Type HEPA HEPA HEPA ULPA ULPA ULPA HEPA HEPA HEPA ULPA ULPA ULPA HEPA HEPA HEPA ULPA ULPA ULPA

Max Amps 4.7 2.5 2.1 5.0 2.2 1.9 5.9 2.4 2.1 5.5 2.3 2.1 3.5 1.6 1.4 3.3 1.4 1.3

* To determine Air Flowrate in CFM, multiply operating range velocity (fpm) by the lter face area, (2x4 = 5.04ft2, 2x3 = 4.31ft2, 2x3 = 3.59ft2, 2x2 = 2.13ft2) do not select at high velocity end as it is rated with clean lter only. It is not recommended to have a lter face velocity exceeding 140 fpm. Above this point lter efciency decreases.

Copyright Price Industries Limited 2011.

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.

E-139

CRITICAL ENVIRONMENTS

Fan Filter Units FFU Series


Return to product page

FFU-HC Performance Data


HEPA Filter Active Filter Area (Sq. Ft) 7.2 7.2 7.2 3.5 3.5 3.5 7.2 7.2 7.2 3.5 3.5 3.5 Capacity Operating Watts @ @ 90FPM Range 90FPM (CFM) (FPM) (Watts) 650 650 650 315 315 315 650 650 650 315 315 315 60 - 95 50 - 95 50 - 95 65 - 135 65 - 135 65 - 135 55-110 55-110 55-105 45-140 45-140 40-135 275 255 265 130 115 120 215 215 210 65 60 65 Amps @ 90FPM (Amps) 2.9 1.2 1.0 2.5 0.9 0.9 3.2 1.6 1.4 1.0 0.5 0.5 Sensible Heat Sound @ @ 90 FPM 90FPM (BTU) (dBA) 940 870 905 445 395 410 735 735 720 225 205 225 54.5 54.5 54.5 52.5 52.5 52.5 54.5 54.5 54.5 49.5 49.5 49.5

Nominal Unit Size 2x4 2x4 2x4 2x2 2x2 2x2 2x4 2x4 2x4 2x2 2x2 2x2
CRITICAL ENVIRONMENTS

Motor Type PSC PSC PSC PSC PSC PSC ECM ECM ECM ECM ECM ECM

Voltage (Volts) 115 240 277 115 240 277 115 240 277 115 240 277

Weight (lbs) 65 65 65 42 42 42 65 65 65 42 42 42

* To determine Flowrate (Capacity) in CFM, multiply lter face velocity (FPM) by the lter face area. ** Sensible Heat: BTU = Watts X 3.413 It is not recommended to have a lter face velocity exceeding 140 FPM. Above this point, lter efciency decreases.

Performance
Average velocity The unit will provide ltered air at an average velocity of 90 FPM (+/-15 FPM). FFU Performance notes: 1. Units are tested in accordance with IEST RP-CC002.2, Recommended Practice for Unidirectional Flow Clean-Air Devices. 2. Sound levels were measured with unit installed in a T-Bar ceiling, with gasket, in a standard room. Sound levels in dBA were measured at a distance of 30 inches from the lter face, with the unit set to produce 90 fpm average face velocity. (Note that data is for a clean lter only. If fan speed is increased to compensate for lter loading the noise level will increase.) 3. Amp and Watt ratings are based on a unit with a clean lter. 4. Max Static Pressure - The maximum static pressure drop in inches w.g. produced across the unit while maintaining a face velocity of 90 fpm at maximum motor speed. FFU-HC Performance notes: 1. Units are tested in accordance with IEST RP-CC002.2, Recommended Practice for Unidirectional Flow Clean-Air Devices. 2. Airow measured in accordance with the (ANSI/AMCA 210-07), (ANSI/ASHRAE 51-07) test standards for Certied Aerodynamic Performance Rating. 3. Sound levels were measured with unit installed in a T-Bar ceiling, with gasket, in a standard room. Sound levels in dBA were measured at a distance of 30 inches from the lter face, with the unit set to produce 90 fpm average face velocity. (Note that data is for a clean lter only. If fan speed is increased to compensate for lter loading the noise level will increase.) 4. Amp and Watt ratings are based on a unit with a clean lter.

E-140

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.

Copyright Price Industries Limited 2011.

Fan Filter Units FFU Series


Return to product page

Fan Performance Curves


FFU-HC 2x2 ECM
Filter Loading Additional Static Pressure, inches w.g. Filter Loading Additional Static Pressure, inches w.g. Filter Loading Additional Static Pressure, inches w.g. Filter Loading Additional Static Pressure, inches w.g.
0.50

FFU-HC 2x2 PSC


90 FPM Max.

Min.
0.45 0.40 0.35 0.30

Filter Loading Additional Static Pressure, inches w.g. Filter Loading Additional Static Pressure, inches w.g. Filter Loading Additional Static Pressure, inches w.g. Filter Loading Additional Static Pressure, inches w.g.

0.50

Min.
0.45 0.40 0.35 0.30

90 FPM

Max.

FFU-HC 2x2 ECM 0.25


0.50 0.20 0.45 0.15 0.40 0.10 0.35 0.05 0.30 0.00 0.25 0 0.20 50 100 150 200 250

FFU-HC 2x2 PSC 0.25


0.50 0.20 0.45 0.15 0.40 0.10 0.35 0.05 0.30 0.00 0.25 0 0.20 50 100 150 200 250

Min.

90 FPM

Max.

Min.

90 FPM

Max.

150

ilt %F

er L

oad

50%

Fil

ter

Lo

ad

Constant Air Flow

Air Flow Rate, cfm


ilte r Lo ad

300

350

400

450

500

r Air Flow Rate, cfm ilte % 150 F

300

Lo

ad

350

400

450

500

0.15 FFU-HC 2x4 ECM 0.50 0.10 0.45 0.05 0.40 0.00 0 0.35 0.30

150
Min.

%F

0.15 FFU-HC 2x4 PSC 0.50 0.10 0.45 0.05 0.40 0.00 0 0.35 0.30

90 FPM
Constant Air Flow

Max.

Min.

90 FPM

Max.

50

100

150

Air Flow Rate, cfm

200

250

300

350

400

450

500

50

100

150

Air Flow Rate, cfm

200

250

300

350

400

450

500

FFU-HC 2x4 ECM 0.25


0.50 0.20 0.45 0.15 0.40 0.10 0.35 0.05 0.30 0.00 0.25 200 0.20 300 400 500

FFU-HC 2x4 PSC 0.25


Min.

150%

o 90 ter L ilFPM F

ad

0.50 0.20 0.45 0.15 0.40 0.10 0.35 0.05 0.30 0.00 0.25 200 0.20 0.15 0.10 0.05 0.00 200 300 400 500 600 700 800

Max.

Min.

90 FPM

Max.

150

%F

ilte

r Lo

ad

Constant Air Flow

Air Flow Rate,ocfm ad


150% rL Filte

600

700

800

900

Air Flow Rate, cfm


150 %F ilte r Lo ad

FFU-HC 2x2 0.15


0.10

FFU-HC 2x4
450 400 350
300 400

Energy Consumption Comparison Charts


0.05 400 0.00 350 200 300 400 Constant Air Flow

450

300

Air Flow Rate, cfm

500

600

700

800

900

300

Air Flow Rate, cfm

500

600

700

800

Power (W)

450 400 350 300 250 200 150 100 50 0

200 150 100 50 0

Power (W)

FFU-HC 2x2

250

PS

FFU-HC 2x4
450 400 350 300 200 150 100 50 0

250

PS

EC

EC

Power (W)

Air Flow Rate, cfm


M

Power (W)

50

100

150

200

250

300

PS

C
350 400 450 500 250 200 150 100 50 0

100

200

300

400

500

PS

C
600 700 800 900

Air Flow Rate, cfm


M

EC

EC

50

100

150

200

250

300

350

400

450

500

100

200

300

400

500

600

700

800

900

Air Flow Rate, cfm

Air Flow Rate, cfm

Copyright Price Industries Limited 2011.

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.

E-141

CRITICAL ENVIRONMENTS

Fan Filter Units FFU Series


Return to product page

ECM Technology
Electronically Commutated Motors (ECM) are optional on all FFU Series modules. These brushless DC motors include a built-in inverter and microprocessor-based motor control. The ECM motor includes several features that make them superior to conventional electric motors: Factory set fan flow Energy efficient operation Long motor and filter life Programmable Wide operating range Low heat generation Quiet operation As lter pressure increases with use, the ECM motor automatically compensates with increased speed to maintain a constant ow of supply air. ECM

Options
Ion Bar Option Ion bars are easily fastened to the FFU perforated face and provide ionization to help statically neutralize the air and work surfaces serviced by the FFU. Many industries use ion bars as a portion of their defense against electrostatic discharge damage to sensitive electronic components. 24 VAC input power Silicon emitters Steady-DC ion emission Available in 11 , 22 and 44 lengths. Note: * 60 FPM airflow velocity required at ion bar for proper operation. ** Not available for FFU-HC. FFU with Ion Bar

CRITICAL ENVIRONMENTS

E-142

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.

Copyright Price Industries Limited 2011.

Fan Filter Units FFU Series


Return to product page

Product Options
FFU Series modules are supplied with a motor/blower assembly that is easily accessible and removable from the top of the unit (left-hand image). RSR lter modules are also available with a roomside-removable motor/blower option (right-hand image). Standard Construction REM Option

LED Filter Indicator Option (FL)* LED indicator light turns from green to yellow when the pressure drop over the lter exceeds the specied limit. Yellow light indicates that filter is still functional but should be replaced as soon as possible. LED operation is unaffected by room pressure changes.
CRITICAL ENVIRONMENTS

LED Motor Indicator Option (ML)* LED indicator turns from green to red if the motor stops running. Motor BAS Signal Option (MBAS) Motor signal is wired directly to the building automation system to provide a signal for the motor status. The signal originates from a differential pressure switch that switches when the motor/blower is moving air. General LED, are visible from occupied area, so there is no need to open the unit in order to determine the lter or motor status. LED kit requires 24 VAC power supply, which is to be provided by others. (PSC motor units). LED kit is available factory installed or shipped loose for eld installation. Factory installed LED kit comes with factory pre-calibrated switch. Switches can be eld adjusted if required. Max available pressure setting is 1.0 in. w.g. Field installed kit may comes with switch that requires eld calibration to suit specic job conditions instructions are included in Installation Manual. Note: * Not available for FFU-HC.

LED Pressure Switch

LED Controls Enclosure

Face Mounted LED Indicator Light

Copyright Price Industries Limited 2011.

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.

E-143

Fan Filter Units FFU Series


Return to product page

Universal Speed Controller (USC)


Description The Price Universal Speed Controller provides variable speed control of permanent split capacitor (PSC) motors used in Price fan lter units. The USC is a solid state device with integral heat sink/mounting plate. This results in a long life component that is easy to install. Wiring The connection is 2-wire (no-polarity). The USC is connected in series with one of the motor lines. (Typically the hot). Setup The USC is factory calibrated for the fan lter unit it is installed on. This means the minimum adjust dial has been set to a specied voltage. The user adjust dial can then adjust the motor speed between minimum and maximum speed. Notes When measuring the voltage output from the speed controller you must use a TRUERMS volt-meter. A non TRUE-RMS voltmeter will give inaccurate readings due to the shape of the AC waveform coming from the electronic speed controller. It is not recommended to change the minimum adjust dial since running the motor at lower speed may reduce its life due to overheating the windings and stressing the shaft bearings. (Low RPM prevents lubrication of the bearings). USC label with UR mark and model number. USC model 277-08 shown User Adjust Dial Minimum Adjust Dial

CRITICAL ENVIRONMENTS

Certication All USC models are UR (Underwriters Laboratories) Recognized components.

E-144

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.

Copyright Price Industries Limited 2011.

Fan Filter Units FFU Series


Return to product page

Price Standard ECM Speed Controller


Description The Price ECM speed controller is specically engineered to interface with a high-efficiency ECM motor. This low voltage speed controller offers either full manual control (VIA an on-board dial), or BAS (building automation system) control of the ECM motor. Switching between the two modes is easy: just apply the BAS signal and the controller will automatically switch over from manual (dial) mode to BAS mode. Features Low supply voltage (24 VAC). Dual outputs to control up to 2 ECM motors. Front facing Green Diagnostic LED for easy troubleshooting. On-board manual adjustment dial with front facing voltage taps for voltmeter hookup (no need to open electrical enclosure). Building Automation System (BAS 2 to 10 VDC) input for variable speed remote control. Diagnostic LED The Diagnostic LED blinks out the current status of the board. This information is used to determine if the speed controller is operating in Manual (Dial) or BAS (Building automation system) mode and if the current setting is OFF or CONTROL. Note: The Diagnostic LED repeatedly blinks out the sequential status code followed by a pause. 1 Blink Manual Off Mode 2 Blinks Manual Control Mode 3 Blinks BAS Off Mode 4 Blinks BAS Control Mode Building Automation System (BAS) Interface The BAS interface accepts an industry standard 2-10 VDC signal from a controller or computer to vary the speed of the ECM motor. This allows remote control/shutdown of the ECM motor based on air requirements and/or occupancy modes. Note: turning off 24 VAC power to the ECM speed controller will turn off ECM motor. 0-1 VDC BAS input Manual Mode 1-2 VDC BAS input BAS Off Mode (recommend sending 1.5 VDC to turn off motor) 2-10 VDC BAS input Modulating control (0 100%)

Operating Conditions: Storage Conditions: Processor: Inputs: Outputs: Connections: Dimensions: Shipping Weight:

24 VAC 10% @ 50/60Hz (2VA) 32 F to 122 F [0 C to 50 C] 0% 95% R.H. non-condensing -22 F to 122 F [-30 C to 50 C] 0% 95% R.H. non-condensing 8-bit standard ash microcontroller 2 Analog (Dial input and BAS input) 3 Digital (GO signal to ECM, Vspd PWM signal @ 80.0 Hz, Green Status LED) in. Spade Terminals Recommend 18-22AWG copper wire 2.5 in. by 3.8 in. [64 mm by 96 mm] (includes mounting plate) 0.100 lbs [46 grams]

Copyright Price Industries Limited 2011.

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.

E-145

CRITICAL ENVIRONMENTS

Specications Power:

Fan Filter Units FFU Series


Return to product page

Deluxe ECM Speed Controller


Description The Price Deluxe ECM speed controller works with a high efciency ECM motor. This low voltage (24 VAC) speed control allows full manual (push button adjust) or BAS (2-10 VDC signal) control of the ECM motor. Features: Dual outputs for controlling 2 ECM motors (Note: Both motors will receive the same signal.) Red three-digit digital display for reading out: a) Speed 0-100% b) Motor RPM (for motor number 1 only) c) BAS input voltage (Digital readout of incoming BAS voltage signal.) Building Automation System input (2-10 VDC) for remote control LED Digital Display The Digital Display shows the user several modes of operation. This allows for easier and more precise eld adjustment and troubleshooting. By pressing both the UP and DOWN push buttons at the same time the user can cycle between the following modes: 1) Speed Adjustment is easier and more precise with the digital display and push buttons than with a standard dial. 2) Motor RPM displays the real time motor speed to aid in troubleshooting. 3) BAS input voltage displays the input voltage signal from the building automation system (BAS). Note: any BAS voltage signal above 1 VDC overrides local speed control.

CRITICAL ENVIRONMENTS

Display Mode Spd Manual Speed Adjust Mode rPn Shows current RPM of ECM motor #1 bAS BAS Mode Voltage Signal

Range 0-100 % 0-1350 RPM 2-10 VDC

Specications Power:

Important Information Regarding the ECM Motor


Do not switch 120/208/240/277 VAC power to turn ECM motor on and off. Instead control the 24 VAC signal or BAS signal to turn the ECM motor on and off. The ECM motor has large capacitors that charge quickly on mains power up. Switching on several motors frequently could reduce building power quality and is not recommended.

Operating Conditions: Storage Conditions: Processor: Inputs: Outputs: Connections: Dimensions: Shipping Weight:

24 VAC 10% @ 50/60Hz (2VA) 32 F to 122 F [0 C to 50 C] 0% 95% R.H. non-condensing -22 F to 122 F [-30 C to 50 C] 0% 95% R.H. non-condensing 8-bit enhanced ash microcontroller 1 Analog and 3 digital inputs 2 Digital (GO signal to ECM and Vspd PWM signal @ 80.0 Hz) in. Spade Terminals Recommend 18-22AWG copper wire 2.8 in. by 3.8 in. [71 mm by 96 mm] (includes mounting plate) 0.220 lbs, 100 grams

E-146

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.

Copyright Price Industries Limited 2011.

Fan Filter Units FFU Series


Return to product page

Product Options
Wall Mounted Speed Control Kit Option - WK
The Wall Mounted Speed Control Kit is provided for customer convenience when air ow adjustment is required from the occupied zone without the use of any tools. When WK is provided there is no need to access the FFU unit directly. The WK kit can be easily installed in the eld by a qualied electrician instructions are included in the installation manual. The WK kit will be provided in 3 different styles to match motor selection: PSC Wall Mounted Control

WK kit for PSC Motor is high voltage and, as such, requires field supplied conduit and junction box. It is supplied loose for field installation in place of a speed controller usually located on the FFU unit. As opposed to standard speed controller, it is easily accessible and comes with a knob that can be adjusted without the use of a screw driver.

WK kit for ECM motor and Price Deluxe Speed Controller uses 24 VAC and comes supplied with approximately 2 ft of cable connected to the speed controller, to be field installed in a field supplied junction box. This WK kit also comes with a 2 ft cable with connector to attach to the ECM motor, and must be eld wired by a qualified electrician. In total, 8 wires should be run in the conduit; 6 for motor control, and 2 for 24 VAC. The WK kit is supplied loose in place of a speed controller usually mounted on the FFU unit. This option will also display motor RPM, giving the user an indication of how the FFU is responding to control.

ECMDX Wall Control

Copyright Price Industries Limited 2011.

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.

E-147

CRITICAL ENVIRONMENTS

WK kit for ECM motor uses 24 VAC and comes supplied with approximately 1 ft of cable soldered to the controller and to the wall-mount for eld installation in a eld supplied junction box. The wall-mounted potentiometer is supplied loose in addition to a standard ECM speed controller mounted on the FFU unit. This potentiometer has to be wired to the speed controller by matching the coordinated wire colors. As opposed to a standard speed controller, the WK kit is easily accessible and can be adjusted by a user without a screw driver.

ECM Wall Mounted Control

Critical Environments Suggested Specication


Return to product page

Fan Filter Units


FFU-HC High Capacity Fan Filter Unit General Module shall be furnished with a bench-top replaceable, UL900 certified HEPA (minimum 99.99% efficiency on 0.3m particle size) or ULPA (minimum 99.9995% efficiency on 0.12m particle size) high efficiency filter. Module sizes, power requirements, efficiencies, capacities and options shall be as scheduled. Performance The discharge sound level shall be less than 55dBA when measured at 30 in. from lter face at 90 fpm (average face velocity). The filter shall be PAO scan tested post assembly to assure leakage is consistent with an uncompromised lter. Construction Filters shall be framed in an aluminum housing which is integral to the plenum. Modules to be provided with an expanded-metal perforated face protecting the downstream side of the lter. Plenum construction shall be mill finish, 0.063 aluminum. Inlet shall include a 25 30% MERV 4 washable pre-filter. Unit shall be provided with eyebolts at each plenum corner for support from above. Plenum shall be walkable up to 250lbs. Motor/blower to be direct drive with thermally protected PSC or constant ow programmed ECM style motor and manufactured in North America. Motor/blower assembly shall be accessible and removable from the top of the unit. Solid state speed control shall be provided. o Units specified with ECM style motor shall have BAS Interface to accept industry standard 2 10VDC signal for variable speed remote control. Unit shall be ETL Certified to: o UL 507, unit shall be lined with urethane foam for additional noise attenuation. o UL 1995, unit shall be lined with plenum-rated elastomeric insulation tested to ASTM E84, having a flame spread index of less than 25 and a smoke developed index of less than 50. Options (If Specied) Ducted units shall be provided with either a 10 or 12 round inlet, and an optional 25-30% MERV 4 washable pre lter Unit shall provide operation status signal to a BAS through factory mounted contacts. Unit shall be provided with wall mounted speed control potentiometer shipped loose for eld installation. Unit shall be provided with wall mounted speed control with digital display capable of reading out Speed (0-100%), Motor RPM and BAS Input Voltage Signal. Unit shall be provided with LED Filter Indicator light that turns from green to yellow when the pressure drop across the lter becomes 1.5 times the pressure drop of a clean filter. LED operation shall be unaffected by room pressure changes. Unit shall be provided with LED Motor Indicator light that turns from green to red if the motor stops running. Unit shall provide motor operation status signal to a BAS through factory mounted contacts. Unit shall be provided with wall mounted speed control potentiometer shipped loose for eld installation. Unit shall be provided with wall mounted speed control with digital display capable of reading out Speed (0-100%), Motor RPM and BAS Input Voltage Signal. Motor/blower assembly shall be accessible and removable from the room side. Unit shall be provided with a Simco-Ion model 5685 ion bar , 304 stainless steel. Unit construction shall be 0.035

CRITICAL ENVIRONMENTS

E-202

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.

Copyright Price Industries Limited 2011.

Critical Environments Suggested Specication


Return to product page

Fan Filter Units


FFU/FFUSS - Room-Side Replaceable Fan Filter Unit General Module shall be furnished with room side replaceable, UL900 certified HEPA (minimum 99.99% efficiency on 0.3m particle size) or ULPA (minimum 99.9995% efficiency on 0.12m particle size) high efciency lter with gel seal frame. Module sizes, power characteristics, efficiencies, capacities and options shall be as scheduled on the drawings. Performance The discharge sound level shall be less than 55dBA when measured at 30 in. from lter face at 90 fpm (average face velocity). The unit is to be factory sealed and PAO tested to assure leakage is consistent with the lter. Construction Filters shall be framed in extruded aluminum and provided with a gel knife-edge seal. Modules to be provided with aluminum perforated laminar ow face with quarter-turn fasteners. Plenum shall be constructed with 0.063in aluminum and have a powder coat pain finish tested to ASTM D1654, ASTM D610 and ASTM D714. Inlet includes a 25 30% MERV 4 washable pre-filter Unit shall be provided with static pressure / aerosol sample port in the knife-edge frame. Unit shall be provided with eyebolts at each plenum corner for support from above. Aluminum plenums shall be walkable up to 250lbs Motor/blower to be direct drive with thermally protected PSC or constant ow programmed ECM style motor, and manufactured in North America. Motor/blower assembly shall be accessible and removable from the top of the unit. Solid state speed control shall be provided. o Units specified with ECM style motor shall have BAS Interface to accept industry standard 2 10VDC signal for variable speed remote control. Unit shall be ETL Certified to: o UL 507, unit shall be lined with urethane foam for additional noise attenuation. o UL 1995, unit shall be lined with plenum-rated elastomeric insulation tested to ASTM E84, having a flame spread index of less than 25 and a smoke developed index of less than 50. Options (If Specied) Ducted units shall be provided with either a 10 or 12 round inlet, and an optional 25-30% MERV 4 washable pre lter Unit shall be provided with LED Filter Indicator light that turns from green to yellow when the pressure drop across the lter becomes 1.5 times the pressure drop of a clean filter. LED operation shall be unaffected by room pressure changes. Unit shall be provided with LED Motor Indicator light that turns from green to red if the motor stops running. Unit shall provide motor operation status signal to a BAS through factory mounted contacts. Unit shall be provided with wall mounted speed control potentiometer shipped loose for eld installation. Unit shall be provided with wall mounted speed control with digital display capable of reading out Speed (0-100%), Motor RPM and BAS Input Voltage Signal. Motor/blower assembly shall be accessible and removable from the room side. Unit shall be provided with a Simco-Ion model 5685 ion bar Unit construction shall be 0.035 , 304 stainless steel.

Copyright Price Industries Limited 2011.

All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimeter.

E-203

CRITICAL ENVIRONMENTS