Malfunction Handbook
May 1, 2008
Service Target: 100% Customer Satisfaction Service Standard: 100% Earnestness Service Tenet: Customer First Forever
Contents I . E r r o r Indication o f M D V I n d o o r U n i t s 6 II. Error Indication of MDV Digital Scroll Central Air Conditioner8 1. Error Indication of Digital Scroll Unit D3 (D4)8 2. MDV-D540 (560, 580, 820, 840, 860) W/S-820.....................12 3. MDV-D280 (220) W/S-810....................15 III. Error Indica tion of Intellige nt Variable Frequency Ce ntral Air Co n di t i o ne r 1 8 1. Error Indication of V3 (V4, Vi) Intelligent Variable Frequency Unit18
2. MDV-J280W/S-810(811) 23 3. MDV-280W/BS................26 IV. Error Indication of MDV Home Central Air Conditioner32 1. MDV(H)-J140(120)W-510(511), MDV(H)-J160(180)W(/S)-720...32 2. MDV-D100 (120) (/S) ..35 3. Error Code List for Novel M-home Series Digital Indoor Unit. 38 4. Error Code List for Novel Home Digital Water Unit.41 5. MDVJ110 ~ MDVJ160 AC Inverter44 6. Home Central Air Conditioner with Water System Based on Frequency Conversion. .52
7. KFR-61T2W/BP or KFR-402W/BP-510T2.59 V. Error Indication of Unitary Central Air Conditioner...70 1. Error Code List of Ordinary One-to-One ...70 2. Error Code List of Novel Four-way cassette ...74
3. Error Code List of 10HP Air Cooled Cabinet Unit78 4. Error Indication of 20HP Medium Static Pressure Fan Coil Unit...79 VI. Error Indication of Digital Scroll Air Cooled Module ...92 1. Display List of Error and Protection for 60Kw Modular Air Cooled Heat Pump Unit..92 2. Display List of Error and Protection for 200KW Large Modular Air Cooled
Heat Pump Unit.96 3. Code List of Error and Protection for Wire Controller on Modular Unit.97 VII. Error Indication of Water Cooled Cabinet Unit.100 VIII. Error Indication of Screw Unit105 IX. Error Indication of Network Air Conditioner.113
I. Error Indication of MDV Indoor Units LED Flash RUN Indicator Flash, Slowly RUN Indicator Constantly On Pre-heating/Defrosting Indicator Constantly On Timing Indicator Constantly On RUN Indicator Flash, Quickly Definition of Error or Protection Standby Operation Anti-cooling or Defrosting Start up Timing Function Error in Any Temperature Sensor in Indoor Unit
Timing Indicator Flash, Quickly Pre-heating/Defrosting Indicator Flash, Quickly Alarm Indicator Flash, Quickly Alarm Indicator Flash, Slowly
Communication Error between Indoor Units and Outdoor Unit Mode Conflict Water Level Alarm Outdoor Unit Error
II. Error Indication of Midea Digital Scroll A/C 1. Error Indication of Digital Scroll Unit D3 (D4) Display Content E0 E1 E2 Definition of Error or Protection Communication Error between Outdoor Units Phase-sequence Protection Communication Error between Indoor Units and Outdoor Unit Remark Only Displayed on Principal Unit
E3 E4
T3 Tube Temperature Sensor Error T4 Ambient Temperature Sensor Error Digital Discharge Temperature Sensor Error Outdoor Address Error Mode Conflict Error (D3 R410a) Communication Error between Chips Reduction in the Number of Outdoors Only Displayed on
E5 E8 H0 H1 H2
Units H3 P1 P2 P3 Increase in the Number of Outdoor Units High-voltage Protection Low-voltage Protection Over-current Protection of Digital Scroll Compressor
10
P4
Over-high Discharge Temperature Protection of Compressor High Tube Temperature Protection of Outdoor Condenser Current Protection of NO.1 Fixed Compressor Current Protection of NO. 2 Fixed Compressor
P5
P7
P8
11
2. MDV-D540 (560, 580, 820, 840, 860) W/S-820 Error Indication of Outdoor Main Control Board DSP1 (Digital Tube) Display Content of Digital Tube Quantity of Indoor Unit Capability Demand of Indoor Units dF Normal Operation Defrosting Definition of Error or Protection Standby
12
P1 P2 P3 P4 P5
High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection of Compressor High Temperature Protection of Outdoor Condenser Communication Error between Outdoor Units
E0
13
E1 E2 E3 E4 E5 E6 E7
Phase-sequence Error Communication Error between Indoor Units and Outdoor Unit Outdoor Tube Temperature Sensor Error Outdoor Ambient Temperature Sensor Error Discharge Temperature Sensor Error Water Level Alarm Error Inlet Temperature Sensor Error of Condenser for Master Unit
14
3. MDV-D280220W/S-810 Error Indication of Outdoor Main Control Board DSP1 (Digital Tube) Display Content of Digital Tube Capability Demand of Indoor Unit dF Definition of Error or Protection Standby Operation Defrosting
15
P1 P2 P3 P4 P5 E1
High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection of Compressor High Temperature Protection of Outdoor Condenser Phase-sequence Error
16
E2 E3 E4 E5 E6
Communication Error between Indoor Units and Outdoor Unit Outdoor Tube Temperature Sensor Error Outdoor Ambient Temperature Sensor Error Discharge Temperature Sensor Error Water Level Alarm Error
17
IIIError Indication of Intelligent Variable Frequency Central Air Conditioner 1. Error Indication of V3 (V4) Intelligent Variable Frequency Unit Display Content E0 E1 E2 Definition of Error or Protection Communication Error between Outdoor Units Phase-sequence Error Communication Error between Indoor Remark Only Displayed on Master Unit
18
Units and Master Unit E3 or E4 E8 E9 H0 H1 Ambient Temperature or Tube Temperature Sensor Error Outdoor Unit Address Error
Voltage Error Communication Error between DSP and 780034 Communication Error between 9177
19
and 780034 H2 Reduction in the Number of Outdoor Units Increase in the Number of Outdoor Units Temperature Protection of Top Part of Inverter Compressor High-voltage Protection Only Displayed on Master Unit Only Displayed on Master Unit
H3
P0 P1
20
P2 P3
Low-voltage Protection Over Current Protection of Inverter Compressor Over-high DischargeTemperature Protection High Tube Temperature Protection Module Protection Current Protection of NO.1 Fixed
P4 P5 P6 P7
21
22
2. MDV-J280W/S-810(811) Display Content Operating Frequency of Compressor dF P1 Definition of Error or Protection Standby Normal Operation Defrosting High-voltage Protection
23
P2 P3 P4 P5 P6 E1
Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection of Compressor High Temperature Protection of Outdoor Condenser Module Protection Phase-sequence Error
24
E2 E3 E4 E5 E6
Communication Error between Indoor Units and Outdoor Unit Communication Error between outdoor PCB and Inverter Module Ambient Temperature Sensor Error Voltage Protection Water Level Alarm Error
25
3. MDV-280W/BS Spot Inspection Error Information Code 99 A0 A1 A2 18 Error Content Terminal Blocks of Wire Controller Loop of Outlet Temperature Sensor (TD1) Loop of Outlet Temperature Sensor (TD2) Loop of Inlet Temperature Sensor (TS) Loop of Outdoor Heat Exchanger Sensor (TE) Spot Inspection
26
AA B4 1C 22 E6 95 96 A6
Loop of High Pressure Sensor (Pd) Loop of Low Pressure Sensor (Ps) Interface Substrate Loop High Voltage Protection Action (Sensor Pd) Phase-sequence Error of Power Supply Communication Loop of Indoor and Outdoor Inconsistency Detection of Indoor and Outdoor Address Protection Action of Outlet Temperature (TD1)
27
bb AE A7 Ab 89
Protection Action of Outlet Temperature (TD2) Protection Action of Discharge Temperature (TD1) during Low Frequency Protection Action of Inlet Temperature Wiring Error of Pressure Sensor (Pd, Ps) The capability of indoor unit connected is transfinite.
28
0b 0c 11 12 93 94 95
Spot Inspection Error Information of Indoor Unit Drainage System of Suction Pump Loop of Room Temperature Sensor (TA) Motor Loop Loop of Indoor Substrate Loop of Indoor Heat Exchanger (Tc1) Loop of Indoor Heat Exchanger (Tc2) Outdoor Unit Communication Loop
29
97 98 9A b5 b6 b9
Communication Loop of Centralized Management Address Setting of Centralized Management Wiring Error of Indoor Equipment, Connection Error
30
Spot Inspection Error Information of Frequency Converter Plate Spot Inspection Information Over-current Protection of Frequency Converter Compressor System Loop Current Detection Loop High-voltage Switch Loop of Frequency Converter Side Current Transformer Loop
Error Content 14 1d 1F 21 17
31
IV. Error Indication of MDV Home Central Air Conditioner 1. MDV (H)-J140(120, 80)W-510(511) and Free Frequency Converter Error Indication of Outdoor Main Control Board DSP1 (Digital Tube) MDV(H)-J160 (180)W(/S)-720
32
LED Display E1 E2 E3 E4 E5 H0 P1 P2
Content Phase-sequence Error Communication Error between Indoor Unit and Outdoor Unit Communication Error between PCB and inverter module Outdoor Temperature Sensor Error Voltage Protection Error Mismatching Error of Indoor Units High-voltage Protection Low-voltage Protection
33
P3 P4 P5 P6
Current Protection of Compressor Discharge Temperature Protection High-temperature Protection of Condenser Module Protection
34
2. MDV (H) -D100 (120) (/S)-510 Error Code Display of Outdoor Unit LED Display Quantity of Indoor Units Capability Demand of Indoor Unit dF E1 Content Standby Normal Operation Period of Defrosting Phase-sequence Protection (only 5HP unit has)
35
E2 E3 E4 E5 H0 P1
Communication Error between Indoor Units and Outdoor Unit Outdoor Tube Temperature Error Outdoor Ambient Temperature Sensor Error Discharge Temperature Sensor Error of Compressor Mismatching Error of Indoor Units High-voltage Protection
36
P2 P3 P4 P5
Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection High-temperature protection of Condenser
37
3. Error Code List of Novel M-home Series Digital Indoor Unit Display (LED) Timing Indicator LED2 Flash, Quickly RUN Indicator LED1 Flash, Quickly RUN Indicator LED1 Flash, Quickly RUN Indicator LED1 Flash, Display E1 Definition of Error Communication Error between Indoor Units and Outdoor Unit Room Temperrature Sensor Error
E2
E3 E4
38
Quickly Alarm Indicator LED4 Flash, Quickly RUN Indicator LED1 Flash, Slowly Defrosting Indicator LED3 Flash, Quickly Alarm Indicator LED4 Flash, Slowly EE Water Level Alarm Error
E7
EEPROM Error
E0
Ed
39
Ed
40
4. Error Code List of Novel Home Digital Water Chiller Display E0 E1 E2 E3 E4 E5 Definition of Error Detection Error of Water Flow Pahse-sequence Error Communication Error between Indoor Units and Outdoor Unit Backwater Temperature Sensor Error Outdoor Ambient Temperature Sensor Error Outlet Water Temperature Sensor Error
41
E6 E7 E8 E9 P0 P1 P2 P3
Tube Temperature Sensor Error of Condenser Temperature Sensor Error 1of Plate Exchanger Temperature Sensor Error 2 of Plate Exchanger Digital Compressor Discharge ( Dispaly E4 on Wire Controller) Current Protection of System High-voltage Protection Low-voltage Protection Discharge Temperature Protection
42
P4 P5 P6 Pb
Temperature Difference Protection of Inlet and Outlet Water High-temperature Protection of System Condenser Low-temperature Protection of Plate Exchanger Anti-Freezing Protection of System Temperature Difference Protection of Inlet and Outlet Water (3 times
P8
43
5. MDV-J110 ~MDV-J160 AC Inverter Error Indication of Outdoor Unit LED4 X LED3 X LED2 X LED1 X LED0 O Definition of Error or Protection Normal Status (Compressor is shut down) Normal Status (Compressor is operating) Module Error Temperature Protection of Top
O X X
O X X
X X O
X O X
44
part of Compressor X O X X Room Temperature or Inner Tube Temperature Sensor Error Outdoor Temperature Sensor Error Discharge Temperature Protection High-temperature Protection of Indoor Heat Exchanger
45
X O O
O X O
O O X
X X X
Over-voltage or Short-voltage Error Current Protection Low-temperature Protection of Indoor Heat Exchanger (Freezing Prevention Protection) Communication Error between Outdoor Plate and Frequency Converter Plate Communication Error between Indoor Plate and Outdoor Plate High-temperature Protection of Outdoor Heat Exchanger
O O X
O O X
X O X
O X X
46
O X
O X
O O
O O
Protection for the Disconnection of Temperature Fuse Over-low or Over-high Outdoor Ambient Temperature (Cancelled)
47
Error Indication of Display Board for Indoor Unit Anti-cold fan Mode Conflict Room Temperature
Defrosting and Preheating Indicator Flash at 0.2Hz Timing Indicator and Defrosting Indicator Flash at 5Hz, Simultaneously Timing Indicator Flash at 5Hz
48
Defrosting Indicator Flash at 5Hz RUN Indicator LED1, Timing Indicator LED2, Automatic Indicator LED3 and Defrosting and Preheating Indicator LED4 Flash at 0.2 Hz, Simultaneously
Outdoor Error
49
Unit
with
Variable-frequency
LED Display RUN Indicator Flash, Slowly RUN Indicator On RUN Indicator of Principal Unit Flash, Slowly Preheating/Defrosting Indicator On
50
Timing Indicator On
Timing Setting Room Temperature Sensor is Abnormal Evaporator Sensor is Abnormal Communication Error Outdoor Unit Error
Automatic Indicator Flash Preheating/Defrosting Indicator Flash Four Indicators Flash, Simultaneously
51
6. Variable- Frequency Water System Home Central Air Conditioner What displayed on the integrated controller (KJR-07B) of Midea variable frequency water chiller is only simple code, but not the real error code. The real error code is shown on the signaling transfer board of outdoor unit. Error Codes of Wire Controller LED Display E0 E1 E2 Parameter Error Communication Error of Outdoor Unit Outlet Water Temperature Sensor Error Content
52
E3
Outdoor Fixed-frequency System Heat Exchanger Sensor Error Refrigerant Inlet Sensor Error of Plate-type Heat Exchanger Side by Variable Frequency System Refrigerant Inlet Sensor Error of Plate-type Heat Exchanger Side by Fixed Frequency System Outdoor Heat Exchanger Sensor or Temperature Sensor (T4) Error of Variable Frequency System Communication Error of Wire Controller
E4
E5
E6 E7
53
P0 P1 P2 P3 P4 P5 P6 P7
Temperature Protection of Top Part of Compressor Pump Mode (Prevent pump being frozen) Hydraulic Pressure Protection of Inlet Water Module Protection Current Protection Voltage Protection Freezing Prevention Protection of Fixed-frequency System High-temperature Protection of Fixed-frequency Compressor and Condenser
54
P8 P9 PA PB
Over-high Discharge Temperature Protection Freezing Prevention Protection of Variable-frequency System High-temperature Protection of Heat Exchanger (None) High-temperature Protection of Variable-frequency Compressor and Condenser
As for the variable frequency water chiller being produced after 2005, signaling transfer board is cancelled in outdoor unit, while LED digital tube is added. Error Codes for Integrated Controller of Variable Frequency Water Chiller or Digital Tube of Outdoor Unit:
55
LED Display P0 P1 P2 P3 P4 P5 P6
Content Current Protection Temperature Protection of Top Part of Compressor Discharge Temperature Protection of Compressor Module Protection Voltage Protection High-temperature Protection of Frequency Converter Tube High-temperature Protection of Fixed Frequency Tube
56
Pb E0 E1 E2
Freezing Prevention Protection Detection Error of Water Flow EEPROM Error Communication Error between Integrated Controller Outdoor Unit and
E3 E4 E5 E6
Communication Error of Outdoor Frequency Converter T4 or T3BP Error Temperature Sensor Error of Outlet Water T3DP Error
57
E7 E8 E9 H0 H1 H2
Temperature Sensor 1 Error of Plate Exchanger Temperature Sensor 2 Error of Plate Exchanger Error Codes of Integrated Controller EEPROM Error Error of Room Temperature T1 Communication Error between Integrated Controller and Outdoor Unit
H3
58
7. KFR-61T2W/BP or KFR-402W/BP-510T2 LED Display Timing Indicator and Defrosting Indicator Off, RUN Indicator Flash Timing Indicator and Defrosting Indicator Flash, RUN Indicator Flash, Alternate Flash Timing Indicator, RUN Indicator and Defrosting Indicator Flash Content Indoor Tube Temperature Error
Communication Error between Indoor Units and Outdoor Unit Overloading Protection of Compressor (Temperature of top part
59
exceeds 120) Defrosting Indicator, RUN Indicator and Timing Indicator Flash Timing Indicator On, RUN Indicator and Defrosting Indicator Flash Defrosting Indicator On, RUN Indicator and Timing Indicator Flash Timing Indicator Off, Defrosting Indicator On, RUN Indicator Flash Module Protection
Defrosting
60
at 1.5Hz Timing Indicator On, Defrosting Indicator Unknown, RUN Indicator Flash at 1.5Hz Plasma Dedusting Mark
61
Direct-Current Variable-Frequency One-to-Any Air Conditioner with One Group of Tube Display Content E0 E2 EEPROM Error Communication Error between Indoor Chips and Outdoor Chip E3 E4 Communication Error between Outdoor Chip and DSP Ambient Temperature Sensor Error Definition of Error or Protection
62
E5
P0 P1 P2 P3 P4 P5 P6
Temperature Protection of Top Part High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection High-temperature Protection of Outdoor Condenser Module Protection
63
DC Inverter "One-to-Two" or "One-to-Three" Air Conditioner with Several Groups of Tube Display Content E0 E1 E2 E3 E4 Definition of Error or Protection EEPROM Parameter Error Temperature Sensor Error of 1# Indoor Evaporator Outlet Temperature Sensor Error of 2# Indoor Evaporator Outlet Temperature Sensor Error of 3# Indoor Evaporator Outlet Ambient Temperature Sensor Error
64
E5 E6 E7 P0 P1 P2 P3 P4
Voltage Protection of Compressor Pre-reserved Communication Error of Outdoor Frequency Converter Temperature Protection of Top Part High-voltage Protection (Pre-reserved) Low-voltage Protection (Pre-reserved) Current Protection of Compressor Module Protection
65
P5 P6 P7
66
DC Variable-Frequency "One-to-Four" Air Conditioner with Several Groups of Tube Display Content E0 E1 E2 E3 Definition of Error or Protection EEPROM Parameter Error Temperature Sensor Error of 1# Indoor Evaporator Outlet Temperature Sensor Error of 2# Indoor Evaporator Outlet Temperature Sensor Error of 3# Indoor Evaporator Outlet
67
E4 E5 E6 E7 P0 P1 P2
Ambient Temperature and Tube Temperature Sensor Error Voltage Protection Temperature Sensor Error of 4# Indoor Evaporator Outlet Communication Error between DSP and 780034 Temperature Protection for Top of Inverter Compressor High-voltage Protection Low-voltage Protection
68
P3 P4 P5 P6 P7 P8
Current Protection of Frequency Converter Module Protection Ambient Low-Temperature Protection High-temperature Protection of Outdoor Condenser Pre-reserved Pre-reserved
69
V. Error Indication of Unitary Central Air Conditioner 1. Error Code List for Ordinary One-to-One Error Code Indication of Indoor Unit LED Flash All indicators flash at 5Hz Timing indicator flashes at 5Hz Definition of Error or Protection Neutral line has not been connected to the PRO port on indoor electric control panel, or optical coupler on circuit wafer has been damaged. Room Temperature Sensor Error
70
Run indicator flashes at 5Hz Defrosting indicator flashes at 5Hz Warning indicator flashes at 5Hz
71
1) LED Error List for 3HP Detection Panel of Outdoor Phase-sequence Symptom LED1 Off On Off On On LED2 Off Off On On On LED3 On On On On On Normal Phase-sequence is reversed. Over Current Phase-loss Pressure Protection Definition of Error or Protection
72
2) LED Error List for 5HP Outdoor Main Control Panel Symptom LED1 Flash Flash Off Off Off Flash LED2 Off Flash Off Flash Flash Flash LED3 Off Off Flash Flash Off Flash Phase-loss, or Phase-sequence is reversed. High/Low Pressure Protection Over Current T3 Open Circuit or Short circuit Error T4 Open Circuit or Short circuit Error High Temperature Protection of Condenser Definition of Error or Protection
73
2. Error Code List for Novel Four-way Cassette Symptom Operating On Timing On Defrosting On Full-water On Error Code Definition of Error or Protection Room X X X E2 Temperature Sensor Error X X X E3 Temperature Sensor Error of
74
Evaporator Temperature X X X E4 Sensor Error of Condenser Temperature X X E5 Sensor Error of Water Pump E6 Outdoor Error Unit
75
X X
E7 E8
(X indicates that the indicator is Off, indicates that the indicator flashes at 5Hz.) (X indicates that the indicator is Off, indicates that the indicator flashes at 5Hz.)
76
3. Error Code List for 10HP Cabinet Unit Display Content Error Icon E1 On Error Icon E2 On Error Icon P1 On Error Icon P2 On Definition of Error or Protection T1 Open Circuit or Short Circuit Error T2 Open Circuit or Short Circuit Error T2 Low Temperature Protection under Cooling Model T2 High Temperature Protection under Heating Model
77
4. Error Indication of 20HP Medium Static-pressure (Outdoor Unit) Symptom Definition of Error or Protection LED1 Flash Flash Off Off LED2 Off Flash Off Flash LED3 Off Off Flash Flash Communication Error Low-pressure Protection Open Circuit or Short Circuit Error of Room Temperature High Temperature Protection of Condenser
78
79
53/71 DC Inverter "One-toOne Air Conditioner Display Content E0 E2 E3 E4 Definition of Error or Protection EEPROM Error Communication Error between Indoor Chip and Outdoor Chip Communication Error between Outdoor Chip and DSP Ambient Temperature Sensor Error
80
E5 P0 P1 P2 P3 P4 P5 P6
Voltage Protection of Compressor Temperature Protection of Top Part High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection High Temperature Protection for Outdoor Condenser Module Protection
81
90/105/140 Single-Phase Direct-Current Variable-Frequency "One-toOne Air Conditioner Display Content E0 E2 E3 Definition of Error or Protection EEPROM Error Communication Error between Indoor Chip and Outdoor Chip Communication Error between Outdoor Chip and DSP
82
E4 E5 E6 P0 P1 P2 P3 P4
Ambient Temperature Sensor Error Voltage Protection of Compressor PFC Module Protection Temperature Protection of Top Part High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection
83
P5 P6
84
105/140/160 Three-Phase DC Inverter "One-toOne Air Conditioner Display Content E0 E2 E3 E4 E5 Definition of Error or Protection EEPROM Error Communication Error between Indoor Chip and Outdoor Chip Communication Error between Outdoor Chip and DSP Ambient Temperature Sensor Error Voltage Protection of Compressor
85
P0 P1 P2 P3 P4 P5 P6
Temperature Protection of Top Part High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection High Temperature Protection for Outdoor Condenser Module Protection
86
87
Indication List for LED Display No. 1 LED1 LED2 LED3 Description Heating Mode (after the Startup of Compressor) Cooling Mode (after the Startup of Compressor) Defrosting Heating Mode, Indoor T2 High-temperature Protection, Shut down Fan as Required.
2 3 4
88
5 6 7 8 9 10 11
Standby Ambient Temperature Sensor Error Outdoor Tube Temperature Sensor Error Phase-sequence Protection T3 High Temperature Protection Low-voltage Protection 1 High-voltage Protection, Discharge Protection 1
89
12 13 14 15 16 17
Current Protection 1 Current Protection 2 Current Protection 3 Current Protection 4 Discharge Protection 2, 3 Discharge Protection 4
90
DIP switch setting: J2: Double Fan / Single Fan (Connected / Unconnected) J1: Three-phase / Single-phase (Connected / Unconnected)
ON
91
VI. Error Indication of Digital Scroll Air Cooling Module 1. Error Protection Display for 60KW Modular Air-Cooling Heat-Pump Unit E0 E1 E2 E3 E4 E5 Detection Error of Water Flow (Third Time) Phase-sequence Error of Power Supply Communication Error Temperature Sensor Error of Master Outlet Water (Principal Unit is in Effect) Temperature Sensor Error of Outlet Water for Plate Exchanger Tube Temperature Sensor Error of Condenser A
92
E6 E7 E8 E9 Eb EF EA
Tube Temperature Sensor Error of Condenser B Ambient Temperature Sensor Error Discharge Temperature Sensor Error of Digital Compressor for System A Detection Error of Water Flow (First and Second Time) Error of Plate Exchanger Low-temperature Freezing-prevention Protection Sensor T61 Error of Plate Exchanger Low-temperature Freezing-prevention Protection Sensor T62 Communication Protection of Subordinate Module (Display of Wire Controller)
93
P0 P1 P2 P3 P4 P5 P6 P7
High-voltage or Discharge Temperature Protection of System A Low-voltage Protection of System A High-voltage or Discharge Temperature Protection of System B Low-voltage Protection of System B Current Protection of System A Current Protection of System B High-temperature Protection of Condenser of System A High-temperature Protection of Condenser of System B
94
P8 Pb PE
Discharge Temperature Protection of Digital Compressor for System A System Freezing-prevention Protection Low-temperature Protection of Plate Exchanger
95
2. Error Protection Display for 200KW Large Modular Air-Cooling Heat-Pump Unit E0 E1 E2 E3 E4 E5 E7 E9 EA Eb P0 Detection Error of Water Flow (Third Time) Phase-sequence Error of Power Supply Communication Error Temperature Sensor Error of Master Outlet Water Temperature Sensor Error of System Inlet Water Tube Temperature Sensor Error of Condenser Ambient Temperature Sensor Error Detection Error of Water Flow (First Time) Communication Protection of Subordinate Module Error of Sensor T6 High-voltage or Discharge Temperature Protection
96
P1 P4 P6 Pb
Low-voltage Protection Current Protection of Compressor High-temperature Protection of Condenser of System System Freezing-prevention Protection
3. List of Display Code for Modular Wire Controller Error Protection E0 E1 E2 E3 E4 Detection Error of Water Flow (Third Time) Phase-sequence Error of Power Supply Communication Error Temperature Sensor Error of Master Outlet Water (Principal Unit is in Effect) Temperature Sensor Error of Outlet Water for Plate Exchanger
97
E5 E6 E7 E8 E9 EA Eb EC ED EE
Tube Temperature Sensor Error of Condenser A Tube Temperature Sensor Error of Condenser B Ambient Temperature Sensor Error Discharge Temperature Sensor Error of Digital Compressor for System A Detection Error of Water Flow (First and Second Time) Reduction in the Number of Subordinate Unit Detected by Principal Unit Freezing-prevention Temperature Sensor Error of Plate Exchanger A Online module unit could not be found on Wire Controller. Communication Data Error for Wire Controller and Module Communication Error between Wire Controller and Computer
98
EF P0 P1 P2 P3 P4 P5 P6 P7 P8 Pb
Freezing-prevention Temperature Sensor Error of Plate Exchanger High-voltage or Exhaust Temperature Protection of System A Low-voltage Protection of System A High-voltage or Exhaust Temperature Protection of System B Low-voltage Protection of System B Current Protection of System A Current Protection of System B High-temperature Protection of Condenser of System A High-temperature Protection of Condenser of System B Discharge Temperature Protection of Digital Compressor for System A System Freezing-prevention Protection
99
PC PE
Protection for Digital Discharge Temperature above 125 Low-temperature Protection of Plate Exchanger
VII Error Indication of Water Cooled Cabinet Unit Error Display Content Error Icon E0 On Error Icon E1 On Error Icon E2 and No. 1 On Definition of Error or Protection T1 Open Circuit or Short Circuit Error Phase-sequence Error T2 Open Circuit or Short Circuit Error of System 1 (T2A)
100
Error Icon E2 and No. 2 On Error Icon E2 and No. 3 On Error Icon E5 and No. 1 On Error Icon E5 and No. 2 On Error Icon E5 and No. 3
T2 Open Circuit or Short Circuit Error of System 2 (T2B) T2 Open Circuit or Short Circuit Error of System 3 (T2C) Three errors in System 1 within 30 minutes
Three errors in System 2 within 30 minutes Three errors in System 3 within 30 minutes
101
On Error Icon P0 and No. 1 On Error Icon P0 and No. 2 On Error Icon P0 and No. 3 On Error Icon P1 and No. 1 On T2 Low-temperature Protection of System 1 (T2A) T2 Low-temperature Protection of System 2 (T2B) T2 Low-temperature Protection of System 3 (T2C) Current Protection of Compressor 1
102
Error Icon P2 and No. 1 On Error Icon P3 and No. 2 On Error Icon P4 and No. 2 On Error Icon P5 and No. 3 On Error Icon P6 and No. 3
103
On Error Icon P7 On Error Icon P9 and No. 1 On Error Icon P9 and No. 2 On Error Icon P9 and No. 3 On Protection of Indoor Blower Motor Discharge Temperature and High/Low Voltage Protection Discharget Temperature and High/Low Voltage Protection Discharge Temperature and High/Low Voltage Protection
104
VIII. Error Indication of Screw Unit Error Indication of Screw Unit with 100 (200) USRT LED2 Off On Off Flash LED3 Off Off Off On EP E1 Display N/A Standby Operation Voltage Protection and Phase-sequence Error Flash Inlet Sensor Protection of Chilled Water Error Content
LED1 On On Flash
105
On On On On Off Flash
E2 E3 E4 E5 E6 E7
Outlet Sensor Protection of Chilled Water Inlet Sensor Protection of Cooling Water Outlet Sensor Protection of Cooling Water Protection of Discharge Temperature Sensor Low-voltage Protection Communication Error
106
P0 P1 P2 P3 P4 P5
Switch Protection of Chilled Water Flow Switch Protection of Cooling Water Flow High-voltage Protection Internal Compressor Protection Overload of Compressor Protection of Oil Pressure Difference
107
Off On
Flash On
Off Flash
P6 P7
108
Error Indication of Screw Unit with 400 USRT LED1 On On LED2 Off On LED3 Off Off Display N/A Error Content Standby Operation Voltage Protection Flash Off Off EP and Phase-sequence Error Inlet Sensor Flash Flash On E1 Protection of Chilled Water
109
Outlet Sensor Flash Off On E2 Protection of Chilled Water Inlet Sensor On Flash On E3 Protection of Cooling Water Outlet Sensor Off Flash On E4 Protection of Cooling Water Protection of Flash On On E5 Discharge Temperature Sensor
110
E6 E7 P0 P1 P2 P3
Low-voltage Protection Communication Error Switch Protection of Chilled Water Flow Switch Protection of Cooling Water Flow High-voltage Protection Internal Compressor Protection
111
On On Flash
P4 P5 P6
Overload of Compressor Protection of Oil Pressure Difference Protection of Oil Level Protection of
On
On
Flash
P7
112
IX. Error Indication of Network Air Conditioner Error Code Error Content Protection Code Content of Protection
Error and Protection of Air Conditioner EF EE Other Error Error of Water Level Detection ED EC Protection of Outdoor Unit Error Fresh Error (Reserved) PC Reserved PD Reserved PF PE Other Protection Reserved
113
Protection of Variable EB Frequency Module (Reserved) EA Over Current of Compressor (Four Times) Communication Error of E9 Main Board and Display Board E8 Wind-speed detection is out of control (Reserved) P8 Over Current of Compressor P9 Reserved PA Reserved PB Reserved
114
E7
P7
E6
P6
E5
P5
115
E4
P4
E3
P3
E2
P2
Temperature Protection of Vent Tube Temperature Protection of Compressor High Temperature Protection of Condenser Protection of Preventing Cold Air or Defrosting
E1
P1
116
(Reserved) E0 Phase-sequence Error or Phase-loss (Reserved) Network Error Communication Error 03# between Centralized 01# Monitor and Computer (Gateway) Monitor and Network Interface Module Communication Error between Centralized P0 Temperature Protection of Evaporator
117
Communication Error 02# between Centralized 00# Monitor and Function Module
Communication Error between Network Interface Module and Main Control Board