Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV) Issue AJ, January 18, 2011

SYSTEM OVERVIEW
Preface:

Home

This document provides power data and system application information on the following equipment used in a NETSURE Power System. MODEL PSS4850-23GV R48-3200 R48-3200e R48-3500e SPEC. NO. 588705000 1R483200 1R483200e 1R483500e DESCRIPTION Rectifier Module Mounting Shelf Rectifier Module (PCU, 3200 watts) Rectifier Module (PCU, 3200 watts), HighEfficiency Rectifier Module (PCU, 3500 watts), HighEfficiency

Description:

The Rectifier Module Mounting Shelf and Rectifier Modules (PCUs), when used in a NETSURE Power System equipped with a Meter-Control-Alarm (MCA) Assembly, comprise a -48V DC Power System designed to power a load while charging a positive grounded battery. This system is capable of operating in a battery-less installation or off battery for maintenance purposes. The system is designed for operation with the positive output grounded. The NETSURE Power System utilizing this equipment is a complete integrated power system containing rectifiers (PCUs), intelligent control, metering, monitoring, and distribution. A NETSURE Power System, utilizing this equipment, typically consists of... Rectifier Module Mounting Shelf The system contains one or more Rectifier Module Mounting Shelves, each of which houses up to six (6) Rectifier Modules (PCUs). Rectifier Modules (PCUs) The system contains Rectifier Modules (PCUs), which provide load power, battery float current, and battery recharge current during normal operating conditions. The Rectifier Modules (PCUs) are a constant power design. This means that, within the normal operating ambient temperature range, the maximum output power available is a constant 3200W or 3500W. Within this ambient temperature range, the Rectifier Modules (PCUs) will operate in one of three modes, depending upon load demands. Transition between modes is completely automatic. Constant Voltage Mode: For any initial output voltage setting from 47 to 58 volts, output voltage remains constant regardless of load. This is the normal operating condition, in which loads are being supplied and batteries are float charged. Rectifier Modules (PCUs) will operate in the Constant Voltage Mode unless load increases to the point where the product of load current and output voltage is approximately 3200W or 3500W. Constant Power Mode: As load increases above approximately 3200W or 3500W (non-adjustable), output current continues to increase, but output voltage decreases as required to maintain constant output power. Rectifier Modules (PCUs) will operate in the Constant Power Mode unless load continues to increase to the point where the current limit setting is reached.

Page 1 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV) Constant Current Mode: If load increases above the current limit setting, output voltage decreases linearly to maintain output current at current limit. Home

Rectifier Modules (PCUs) continue to operate in higher ambient temperatures, but at reduced power. Refer also to Paragraph 1.4.6 under SPECIFICATIONS. Meter-Control-Alarm (MCA) Assembly The system contains one MCA. The MCA controls the operation of the Rectifier Modules (PCUs). The MCA also provides power system control, metering, monitoring, and alarm functions. Note: This document does not describe the MCA. Refer to the Power System SAG (System Application Guide) for MCA information. NETSURE Distribution Provides DC distribution through fuses and/or circuit breakers. Note: This document does not describe NETSURE Distribution. Refer to the Power System SAG (System Application Guide) for distribution information.

Family: Spec. No.: Model: Rectifier Input Voltage

NETSURE 588705000 PSS4850-23GV Nominal 208/240 volts AC, single phase, 50/60 Hz, with an operating range of 176 to 264 volts. Acceptable input frequency range is 45 to 65 Hz. -48 Volts DC

Rectifier Output Voltage:

Rectifier Output Capacity: Shelf: 437.5 Amperes, 21000 Watts (maximum) Rectifier Module (PCU, R48-3200 or R48-3200e): 55.2A @ -58.0VDC to 66.6A @ -48.0VDC, 3200 Watts (max) Rectifier Module (PCU, R48-3500e): 60.3A @ -58.0VDC to 72.9A @ -48.0VDC, 3500 Watts (max) Agency Approval: Framework Type: Mounting Width: Mounting Depth: Mounting Height Access: Control: Color: Options: UL 60950 Recognized; CAN/CSA 22.2, No. 60950-00 For Mounting in a 23 Inch Wide Relay Rack 23 Inch (Relay Rack Mounting) 18 Inches 6 Inches (3U) Front and Rear for Installation and Maintenance, Front for Operation Microprocessor Bright Zinc Plating (Spec. M500-53) Body, Textured Gray (Spec. M500-147) Faceplates Rectifier Module Mounting Shelf, Single Phase Input, AC Input Terminal Blocks, Rectifier Module Mounting Shelf, Three Phase Input, AC Input Terminal Blocks, Rectifier Module Mounting Shelf, Single Phase Input, AC Input Line Cords Rectifiers, Wiring Components, Rectifier Module Mounting Position Blank Cover Panel, Battery Charge Temperature Compensation Probe for Single Probe Digital Compensation, Battery Charge Temperature Compensation Probe Concentrator for Multiple Probe

Accessories:

Page 2 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

PD588705000 Issue AJ, January 18, 2011

Use (TXM), Adding Additional Shelf in Field Output Busbar Kit, Replacement Cables, Replacement Components Environment: -40C to +65C (-40F to +149F). Refer also to Paragraph 1.4.6.

Page 3 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV) Home

588705000

Rectifier Module Mounting Shelf (List 1, 3, 11)

Rectifier Module P/N 1R483200, P/N 1R483200e, or P/N 1R483500e

See Also System Overview Table of Contents Ordering Information List Descriptions Accessory Descriptions Specifications Physical Size Information Related Documentation

Page 4 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

PD588705000 Issue AJ, January 18, 2011

TABLE OF CONTENTS
Ordering Information System Overview Picture List Descriptions Accessory Descriptions Specifications Physical Size Information Related Documentation

SYSTEM OVERVIEW.................................................................................................................................................1 TABLE OF CONTENTS.............................................................................................................................................5 ORDERING INFORMATION......................................................................................................................................6 List Options..........................................................................................................................................................6 Accessory Options..............................................................................................................................................6 LIST DESCRIPTIONS ................................................................................................................................................7 588705000 List 1: Rectifier Module Mounting Shelf, Single-Phase Input, AC Input Terminal Blocks............7 588705000 List 3: Rectifier Module Mounting Shelf, Three-Phase Input, AC Input Terminal Blocks ............7 588705000 List 11: Rectifier Module Mounting Shelf, Single-Phase Input, AC Input Line Cords ..................8 ACCESSORY DESCRIPTIONS.................................................................................................................................9 P/N 1R483500E: High-Efficiency Rectifier Module (PCU)..............................................................................9 P/N 1R483200E: High-Efficiency Rectifier Module (PCU)..............................................................................9 P/N 1R483200: Rectifier Module (PCU) .........................................................................................................9 Wiring Components ..........................................................................................................................................10 AC Input Branch Circuit Protection and Wire Size Selection.........................................................................10 DC Output Connections .................................................................................................................................12 Frame Ground Wire Size Selection................................................................................................................12 External Alarms Wire Size Selection..............................................................................................................12 Rectifier Module Mounting Position Blank Cover Panel ...............................................................................13 Battery Charge Temperature Compensation Probe for Single Probe Digital Compensation ...................13 Battery Charge Temperature Compensation Probe Concentrator for Multiple Probe Use (TXM) ............14 Battery Temperature Probe Concentrator Kit (P/N 524570)..........................................................................14 Analog Battery Temperature Probe (P/N 521262).........................................................................................14 TXM Extension Cable (P/N 514153) ..............................................................................................................14 Adding Additional Shelf in Field Output Busbar Kit......................................................................................15 Replacement Cables .........................................................................................................................................16 Replacement Components ...............................................................................................................................16 SPECIFICATIONS....................................................................................................................................................17 1.1 Output Ratings ............................................................................................................................................17 1.2 Input Ratings ...............................................................................................................................................19 1.3 Environmental Ratings...............................................................................................................................26 1.4 Standard Features ......................................................................................................................................28 PHYSICAL SIZE INFORMATION ............................................................................................................................34 Overall Dimensions ...........................................................................................................................................34 Rectifier Module Mounting Shelf ....................................................................................................................34 Digital Battery Charge Temperature Compensation Probe (P/N 107021 and 106824).................................35 Analog Battery Temperature Probe (P/N 521262).........................................................................................35 Connection Locations.......................................................................................................................................36 List 1 AC Input and Frame Ground (Single-Phase Input) ..............................................................................36 List 3 AC Input and Frame Ground (Three-Phase Input)...............................................................................37 List 11 AC Input (Single-Phase Input)............................................................................................................38 DC Output and Alarm/Control to MCA ...........................................................................................................39 RELATED DOCUMENTATION................................................................................................................................40

Page 5 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

Home REVISION RECORD ................................................................................................................................................41

ORDERING INFORMATION List Options


This equipment is used in a NETSURE Power System. Refer also to the Power System's documentation. Order the following by the items Part Number as specified in the following table. When viewing electronically, click on the List # to jump to the detailed description page. Mounting Positions (1U = 1-3/4) 58870500001 Rectifier Module Mounting Shelf, Single-Phase Input, AC Input Terminal Blocks (Individual Rectifier Module AC Input Feeds; One AC Input Branch Circuit per Rectifier Module, Six AC Input Branch Circuits per Shelf) Rectifier Module Mounting Shelf, Two (2) Three-Phase Inputs, AC Input Terminal Blocks (Each input supplies three (3) single-phase rectifier modules.) Rectifier Module Mounting Shelf, Single-Phase Input, AC Input Line Cords (Individual Rectifier Module AC Input Feeds; One AC Input Branch Circuit per Rectifier Module, Six AC Input Branch Circuits per Shelf) 3U --

List #

Part Number

Description

Notes

58870500003

3U

--

11

58870500011

3U

--

Accessory Options
Order the following by the items Part Number as specified in the ACCESSORY DESCRIPTIONS section. When viewing electronically, click on the link to jump to the detailed description page. Description 1R483200 3200W Rectifier Module (PCU) 1R483200e 3200W eSure Rectifier Module (PCU) 1R483500e 3500W Rectifier Module (PCU) Wiring Components Rectifier Module Mounting Position Blank Cover Panel Battery Charge Temperature Compensation Probe for Single Probe Digital Compensation Battery Charge Temperature Compensation Probe Concentrator for Multiple Probe Use (TXM) Adding Additional Shelf in Field Output Busbar Kit Replacement Cables Replacement Components See ACCESSORY DESCRIPTIONS Section Part Number

Page 6 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

PD588705000 Issue AJ, January 18, 2011 Home

LIST DESCRIPTIONS
588705000 List 1: Rectifier Module Mounting Shelf, Single-Phase Input, AC Input Terminal Blocks Features Provides one (1) Model PSS4850-23GV (-48V, 330A/400A), Spec. No. 588705000 Rectifier Module Mounting Shelf. Each Rectifier Module Mounting Shelf holds up to six (6) Rectifier Modules. Each Mounting Shelf is equipped with individual Rectifier Module single-phase AC input feeds (one AC input branch circuit per Rectifier Module, six AC input branch circuits per Rectifier Module Mounting Shelf). Terminal blocks provided for AC input connections.

Restrictions None. Ordering Notes 1) Order Rectifier Modules as required per P/N 1R483200, or P/N 1R483200e. 2) Order a Rectifier Module Mounting Position Blank Cover Panel, P/N 21140440, for each empty rectifier module mounting position in the system. 3) Refer also to ACCESSORY DESCRIPTIONS.

588705000 List 3: Rectifier Module Mounting Shelf, Three-Phase Input, AC Input Terminal Blocks Features Provides one (1) Model PSS4850-23GV (-48V, 330A/400A), Spec. No. 588705000 Rectifier Module Mounting Shelf. Each Mounting Shelf holds up to six (6) Rectifier Modules. Each Mounting Shelf is equipped with two (2) three-phase AC input circuits. Each input circuit powers three (3) single-phase Rectifier Modules. Terminal blocks provided for AC input connections.

Restrictions To maintain phase balance, Rectifier Modules should be installed in groups of three (all three on left and/or all three on right). Ordering Notes 1) Order Rectifier Modules in groups of three per P/N 1R483200, P/N 1R483200e or P/N 1R483500e. 2) Order a Rectifier Module Mounting Position Blank Cover Panel, P/N 21140440, for each empty rectifier module mounting position in the system. 3) Refer also to ACCESSORY DESCRIPTIONS.

Page 7 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011 588705000 List 11: Rectifier Module Mounting Shelf, Single-Phase Input, AC Input Line Cords Features

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

Provides one (1) Model PSS4850-23GV (-48V, 330A/400A), Spec. No. 588705000 Rectifier Module Mounting Shelf. Each Rectifier Module Mounting Shelf holds up to six (6) Rectifier Modules. Each Mounting Shelf is equipped with individual Rectifier Module single-phase AC input feeds (one AC input branch circuit per Rectifier Module, six AC input branch circuits per Rectifier Module Mounting Shelf). Factory wired AC input line cords equipped with NEMA L6-30P twist-lock plugs provided. (Six per shelf, each 7.5 long, 12/3 AWG.)

Restrictions Line cord option can only be used up to 40C ambient. Ordering Notes 1) Order Rectifier Modules as required per P/N 1R483200, P/N 1R483200e, or P/N 1R483500e. 2) Order a Rectifier Module Mounting Position Blank Cover Panel, P/N 21140440, for each empty rectifier module mounting position in the system. 3) Refer also to ACCESSORY DESCRIPTIONS.

Page 8 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

PD588705000 Issue AJ, January 18, 2011 Home

ACCESSORY DESCRIPTIONS
P/N 1R483500E: High-Efficiency Rectifier Module (PCU) Features Provides one (1) Model R48-3500e (-48V, 3500W), Spec. No. 1R483500E, eSure Rectifier Module, High Efficiency.

Ordering Notes 1) Order as required. Each shelf holds up to six (6) Rectifier Modules.

P/N 1R483200E: High-Efficiency Rectifier Module (PCU) Features Provides one (1) Model R48-3200e (-48V, 3200W), Spec. No. 1R483200E, eSure Rectifier Module, High Efficiency.

Ordering Notes 1) Order as required. Each shelf holds up to six (6) Rectifier Modules.

P/N 1R483200: Rectifier Module (PCU) Features Provides one (1) Model R48-3200 (-48V, 3200W), Spec. No. 1R483200, Rectifier Module.

Ordering Notes 1) Order as required. Each shelf holds up to six (6) Rectifier Modules.

Page 9 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

Wiring Components
AC Input Branch Circuit Protection and Wire Size Selection List 1 Mounting Shelf (Single Phase Input) See Connections Locations, AC Input and Frame Ground under PHYSICAL SIZE INFORMATION for illustration. LIST 1 AC INPUT (TB1 and TB2) Connection Points for Individual Rectifier Module AC Input Branch Circuits are Provided (One AC Input Branch Circuit per Rectifier Module, Six AC Input Branch Circuits per Shelf) Operating Ambient 1 Temperature 30C 40C 65C
1

Recm Branch Circuit 2, 3 Protection

TB1 and TB2 Terminals Recm 90C 1 Wire Size Capacity Type

25 Amperes

10 AWG

10 to 24 AWG

Screw Compression Tubular Contact

Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire at 90C conductor temperature, operating in ambient of 30C, 40C, and 65C was used. For operation in other ambients, apply derating factors listed in Table 310-16 of the NEC. For operation in countries where the NEC is not recognized, follow applicable codes. The AC input branch circuit protective device should be of the time-delay or high inrush type. Recommendations based on Nominal Line Full Load Input Current of 18 Amperes.

2 3

Page 10 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV) List 3 Mounting Shelf (Three Phase Input)

PD588705000 Issue AJ, January 18, 2011 Home

See Connections Locations, AC Input and Frame Ground under PHYSICAL SIZE INFORMATION for illustration. LIST 3 AC INPUT (TB1 and TB2) Connection Points for Two 3-Phase AC Input Feeds are Provided Operating Ambient 1 Temperature 30C 40C 65C
1

Recm Branch Circuit 2, 3 Protection

TB1 and TB2 Terminals Recm 90C 1 Wire Size Capacity Type

40 Amperes, 3-Pole

8 AWG

6 to 14 AWG

Screw Compression Tubular Contact

Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire at 90C conductor temperature, operating in ambient of 30C, 40C, and 65C was used. For operation in other ambients, apply derating factors listed in Table 310-16 of the NEC. For operation in countries where the NEC is not recognized, follow applicable codes. The AC input branch circuit protective device should be of the time-delay or high inrush type. Recommendations based on Nominal Line Full Load Input Current of 29.3 Amperes.

2 3

List 11 Mounting Shelf (Single Phase Input) See Connections Locations, AC Input and Frame Ground under PHYSICAL SIZE INFORMATION for illustration. LIST 11 AC INPUT (Line Cords) Line Cords for Individual Rectifier Module AC Input Branch Circuits are Factory Connected (One AC Input Branch Circuit per Rectifier Module, Six AC Input Branch Circuits per Shelf) Operating Ambient Temperature 30C 25 Amperes 40C
1 2 3 3

Recm Branch Circuit 1, 2 Protection

The AC input branch circuit protective device should be of the time-delay or high inrush type. Recommendations based on Nominal Line Full Load Input Current of 18 Amperes. Line cord option can only be used up to 40C ambient.

Page 11 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011 DC Output Connections

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV) Home

See Connections Locations, DC Output and Alarm/Control to MCA under PHYSICAL SIZE INFORMATION for illustration. No wire size or lug recommendations provided here. Shelf DC output is connected via busbars to a NETSURE Power System.

Frame Ground Wire Size Selection See Connections Locations, AC Input and Frame Ground under PHYSICAL SIZE INFORMATION for illustration. FRAME GROUND (FR GND) Terminals Two 10-32 X 3/4" Studs and Hardware
1 1

Recm Wire Size 10 AWG

This terminal must be connected to earth ground, not power system neutral. Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper wire. If aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for increased conductor size. For operation in countries where the NEC is not recognized, follow applicable codes. For relay rack grounding requirements, refer to the NEC, applicable local codes, and your specific site requirements.

External Alarms Wire Size Selection See Connections Locations, DC Output and Alarm/Control to MCA under PHYSICAL SIZE INFORMATION for illustration. No wire size recommendations provided here. Shelf external alarms are provided via the MCA of an associated NETSURE Power System.

Page 12 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

PD588705000 Issue AJ, January 18, 2011 Home

Rectifier Module Mounting Position Blank Cover Panel


Features Covers one (1) unused Rectifier Module mounting position.

Ordering Notes 1) Order a Rectifier Module Mounting Position Blank Cover Panel, P/N 21140440, for each empty rectifier module mounting position in the system.

Battery Charge Temperature Compensation Probe for Single Probe Digital Compensation
Features This system can be used with a Battery Charge Temperature Compensation Probe. This probe must be mounted near the battery to sense battery ambient temperature. The probe connects to and allows the MCA to automatically increase or decrease the output voltage of the system to maintain battery float current as battery ambient temperature decreases or increases, respectively. Battery life can be extended when an optimum charge voltage to the battery with respect to temperature is maintained. Two probes are available. Part No. 107021 has a 25-foot long cord. Part No. 106824 has a 100 foot-long cord. See Overall Dimensions, Digital Battery Charge Temperature Compensation Probe (P/N 107021 and 106824) under PHYSICAL SIZE INFORMATION for a dimensional drawing. Allows Rectifier Module Battery Charge Temperature Compensation. For more features, see the SPECIFICATIONS section. Temperature Curve: Refer to Figure 1.

Ordering Notes 1) Order one Battery Charge Temperature Compensation Probe per power system, as required.
MAX W/T Adjustable from Float to 58.0V max.*
Increasing

SLOPE Adjustable from 0.0 V / C to 0.2 V / C FLOAT Determines Float Mode Output Voltage at 25C. Adjustable from 46.0V to 57.0V max.*

Voltage

Decreasing

MIN W/T Adjustable from Float to 44V

* Maximum setting is automatically limited to 1.0 volt less than HVSD setting.

Decreasing

Temperature +25C (+77F)

Increasing

Figure 1 Typical Float Charge Thermal Characteristics Using Optional Battery Charge Digital Temperature Compensation Probe (Indicated parameters are user-adjustable via the associated MCA.)

Page 13 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV) Home

Battery Charge Temperature Compensation Probe Concentrator for Multiple Probe Use (TXM)
Battery Temperature Probe Concentrator Kit (P/N 524570) Features The Battery Temperature Probe Concentrator (TXM) expands battery temperature monitoring capabilities by providing a means of monitoring up to eight (8) analog battery temperature probes. The TXM provides a digital output for connection to the MCAs battery temperature probe connector. The MCA can be programmed to compensate for the hottest probe reading, the average temperature of all connected probes, or the probe connected to the lowest numbered connector. The kit includes one TXM (P/N 521211) and one 25 ft. interface cable (P/N 521228) for connecting the TXM to the MCA. Restrictions

521211

Requires P/N 521262 analog probes. Cannot be used with digital probes (P/Ns 106824 and 107021). Ordering Notes 1) Order one Battery Charge Temperature Compensation Probe Concentrator Kit, P/N 524570, per power system, and up to eight (8) P/N 521262 probes, as required. Can also be ordered from the System Application Guide (SAG) of the Power System in which these shelves are used.

521228

Analog Battery Temperature Probe (P/N 521262) Features An analog probe designed to sense internal battery temperature. Mounts on the negative terminal of the battery; mounting hole clears 5/16 hardware. Includes 15 ft. cable with connector. See Overall Dimensions, Analog Battery Temperature Probe (P/N 521262) under PHYSICAL SIZE INFORMATION for a dimensional drawing.

Ordering Notes 1) See above Ordering Notes.

TXM Extension Cable (P/N 514153) Features 25 ft. long cable. Can be used between a P/N 521262 Analog Battery Temperature Probe and the TXM; or to extend a P/N 521228 interface cable between the TXM and MCA.
514153

Ordering Notes 1) See above Ordering Notes.

Page 14 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

PD588705000 Issue AJ, January 18, 2011 Home

Adding Additional Shelf in Field Output Busbar Kit


Features Kit to tie the DC output busbars in a field installed Rectifier Module Mounting Shelf to the DC busbars in a Spec. No. 582126000 NETSURE Power System.

Ordering Notes 1) Order kit P/N 529139 for each Rectifier Module Mounting Shelf to be added in the field.

Shelf Mounting Hardware

Interconnecting Busbars and Hardware

Page 15 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)


Home

Replacement Cables
Ordering Notes

1) Refer to the Power System "System Application Guide" (SAG) for part numbers.

Replacement Components
Ordering Notes

1) Rectifier Module (PCU): Order via P/N 1R483200, P/N 1R483200e, or 1R483500e. 2) Rectifier Module Fan: P/N P7001111.

Page 16 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

PD588705000 Issue AJ, January 18, 2011 Home

SPECIFICATIONS

Note: All MCA references pertain to the Meter-Control-Alarm assembly located in the associated Power System. Refer to the separate System Application Guide (SAG) of the associated Power System for the following: 1.1 MCA specifications and factory default settings. All external alarms. All external controls. Local status and alarm indicators other than those provided on the Rectifier Modules (PCUs) and DC-DC Converter Modules.

Output Ratings 1.1.1 Voltage: Nominal -48 volts DC, Positive Ground. (A) Without Battery Charge Temperature Compensation: Float voltage is adjustable from 47.00 to 58.00 volts DC. Test/equalize voltage is adjustable from 44.00 to 58.00 volts DC. The output voltage temperature coefficient does not exceed 0.01% per degree centigrade from -40C to +75C. Adjustment is made via the associated MCA. Refer to the separate Power System documentation for the factory setting. (B) With Battery Charge Digital Temperature Compensation Probe or TXM (multiple probe concentrator module): With an optional battery charge digital temperature compensation probe or TXM installed, the MCA automatically increases or decreases the output voltage as battery ambient temperature decreases or increases, respectively. The float and test/equalize voltage range is the same as without battery charge temperature compensation. Refer to the separate Power System documentation for the factory setting. Using battery and equipment manufacturers recommendations, the user selects the following temperature compensation curve parameters via the MCA. Refer to the Temperature Compensation Probe Curve (Figure 1). (1) The temperature compensation slope in volts/C. Adjustable from zero to 200 millivolts/C. Adjustment is made via the associated MCA. Refer to the separate Power System documentation for the factory setting. (2) The maximum voltage limit in volts DC. Adjustable from float up to 58.00 volts DC, but automatically limited to 1.0 volt below the High Voltage Shutdown setting. Adjustment is made via the associated MCA. Refer to the separate Power System documentation for the factory setting. (3) The minimum voltage limit in volts DC. Adjustable from float down to 44.00 volts DC, but automatically limited to 1.0 volt above the Low Voltage Disconnect Reconnect setting. Adjustment is made via the associated MCA. Refer to the separate Power System documentation for the factory setting.

Page 17 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011 1.1.2 Current:

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

(A) Full Load Rated Current: Refer to the following table. Full Load Rated Current (Amps) 3200W At 58.0 VDC At 48.0 VDC Full Load Rated Current (Amps) 3500W At 58.0 VDC At 48.0 VDC

Number of Rectifier Modules

1 2 3 4 5 6

55.2A 110.4A 165.6A 220.8A 276.0A 331.2A

66.6A 133.2A 199.8A 266.4A 333.0A 399.6A

60.3A 120.7A 181.0A 241.4A 301.7A 362.1A

72.9A 145.8A 218.8A 291.7A 364.6A 437.5A

Output Voltage vs. Output Current: Refer to the following illustration.

Output voltage vs. output current 3200W unit


70 Output voltage (V) 60 50 40 30 20 10 0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 Output current (A)

Output voltage v.s. Output current 3500W unit


60 Output Voltage (V) 50 40 30 20 10 0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75

Output Current (A)

Page 18 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)


1.1.3

PD588705000 Issue AJ, January 18, 2011 Home

Regulation: Static regulation will give other voltage depending on load. (A) Output Voltage Tolerance:

Output voltage tolerance: < 0.2% < 0.5% 25A load 25A load +15C - +35C -5C - +55C

Static regulation, including input voltage variation and temperature variation: < 0.5% < 1% 5-100% load 5-100% load +15C - +35C -5C - +55C

Uin = 85-290 Vac, f = 45 Hz - 65 Hz Output voltage decreases with increased output current. Overshot of output voltage at startup 1%.
(B) Dynamic Response Characteristic (at rated input and output voltage):

Response time 200us and overshot 5% for load changes at 50% - 25% - 50% and 50% - 75% - 50%. Overshot or undershot 5% and within 1% of regulation band 4ms at 50us for load changes at 10% - 90% and 90% - 10%. (Telcordia GR-947.)
1.1.4 Filtering (with or without battery): (A) Voice Band Noise: Complies with Telcordia GR-947-CORE. (1) Output noise according to Telcordia GR-947-CORE: < 32dBrnC between180V~290Vac input and 10 - 100% load (output voltage > 42V, for any application with > 1 rectifier). (2) Psophometric noise is 1mV between 180V~290Vac input and 10 -100% load (output voltage > 42V) and 16.66-6000Hz. (for any application with > 1 rectifier). (B) Wide Band Noise: Complies with Telcordia GR-947-CORE. (1) Typically 130 millivolt peak-to-peak. Does not exceed 250 millivolt peak-to-peak. (2) Typically 13 millivolts rms. Does not exceed 30 millivolt rms. 1.1.5 1.1.6 Output Discharge: The output capacitors automatically discharge when the rectifier is disconnected from the batteries and AC is turned OFF. Time constant is less than 1 minute. Power Interruption: The rectifier starts when connected to a fully discharged battery or capacitor bank (bus voltage > 15V) without operating protective devices or requiring the shedding of load or needing any manual intervention. The rectifier starts under all line and environmental conditions, when the output terminals are connected to an impedance of less than 15 milliohms. Stability Criteria: Complies with GR947 Core R3-20. Stability criteria: > 30 deg. of phase margin when gain is unity (0 dB) and gain down to < - 6 dB when phase is 180 deg.

1.1.7 1.2

Input Ratings 1.2.1 Voltage: (A) Normal: Nominal 208/240 volts AC, single phase, 50/60 Hz, with an operating range of 176 to 264 volts. Acceptable input frequency range is 45 to 65 Hz. (B) Safe Voltage: The system can tolerate 415 volts AC without damage. 1.2.2 Harmonic Content: < 5% THD at 50% - 100% load. The voltage source must have a voltage THD of < 1.1%. The range of input voltage is 200~250Vac.

Page 19 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

The rectifier is designed to comply with EN61000-3-2.


1.2.3 Inrush Current: Peak does not exceed 1.5 times the steady state peak value of the input current at full load, nominal input voltage, and for any duration of AC input interrupts. Under the above conditions, standard AC distribution circuit breakers will not trip. Typical Input Data (1R483200): 50 Hz input. (A) System output is initially adjusted to 54.48 volts DC as measured at the system sense point at 50% of full load and nominal input. Percent of Full Load refers to percent of 55 Amperes. Number of Rectifier Modules Installed Nominal Input Voltage Percent of Full Load Input Current (Amperes) Input VA Input Watts Power Factor % Heat Efficiency Dissipation % BTU/Hr*

1.2.4

0 25 50 208 75 100 110 1 120 0 25 50 240 75 100 110 120

0.51 3.55 7.90 12.02 15.90 17.30 17.25 0.51 3.11 6.81 10.33 13.69 14.82 14.86

109 734 1644 2491 3312 3594 3582 123 748 1637 2485 3300 3566 3557

82 726 1639 2486 3308 3589 3572 82 735 1631 2481 3296 3560 3550

76.0 98.9 99.7 99.8 99.8 99.8 99.8 66.9 98.3 99.5 99.8 99.8 99.8 99.8

-82.5 91.4 90.3 90.5 90.5 91.1 -81.5 88.5 90.5 90.9 91.0 91.7

279 460 621 815 1063 1159 1075 279 463 453 798 1023 1083 998

* - Heat dissipation is the same for a List 3 shelf (three phase input).
(B) Typical Power Factor: Greater than or equal to 98% for any load greater than or equal to 50% of rated full load at nominal line. Meets IEC 1000-3-2. (C) Typical Operating Efficiency:

92% at best point, 91% at 50A / 53.5V between 215Vac-250Vac input, 90.5% at 50A / 53.5V between 200Vac-215Vac. 90.5% at 55A / 53.5V between 215Vac-250Vac input, 90% at 55A / 53.5V between 200Vac-215Vac.

(D) Maximum Input Current: at 100% of full load with output adjusted to 58 volts DC as measured at the shelf output terminals. Nominal Input Voltage Input Voltage Number of Rectifier Modules Installed Input Current (Amperes)

208/240

176

20.35

Page 20 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)


1.2.5 Typical Input Data (1R483200e): 50 Hz input.

PD588705000 Issue AJ, January 18, 2011 Home

(A) System output is initially adjusted to 54.48 volts DC as measured at the system sense point at 50% of full load and nominal input. Percent of Full Load refers to percent of 55 Amperes. Number of Rectifier Modules Installed Nominal Input Voltage Percent of Full Load Input Current (Amperes) Input VA Input Watts Power Factor % Heat Efficiency Dissipation % BTU/Hr*

0 25 50 208 75 100 110 1 120 0 25 50 240 75 100 110 120

0.3547 3.779 7.41 11.178 14.911 16.363 16.314 0.4207 3.303 6.41 9.663 12.868 14.08 14.099

74.6 793.5 1551.5 2335 3107 3411 3429 102.02 799.1 1547.7 2330 3095 3384 3407

10.751 782.1 1546.8 2332 3105 3405 3427 10.697 780.5 1537.9 2324 3092 3382 3404

14.8 98.5 99.6 99.8 99.9 99.9 99.9 10.5 97.6 99.3 99.7 99.8 99.8 99.8

0 95.697 96.613 96.274 95.707 95.7 94.995 0 95.86 96.806 96.609 96.094 95.957 95.446

36.693 114.86 178.812 296.537 454.909 499.718 585.448 36.509 110.279 167.669 268.985 412.202 466.723 529.079

* - Heat dissipation is the same for a List 3 shelf (three phase input).
(B) Typical Power Factor: Greater than or equal to 98% for any load greater than or equal to 50% of rated full load at nominal line. Meets IEC 1000-3-2. (C) Typical Operating Efficiency:

97% at best point, 96.2% at 50A / 53.5V between 215Vac-250Vac input, 96.6% at 50A / 53.5V between 200Vac-215Vac. 95.8% at 55A / 53.5V between 215Vac-250Vac input, 95.6% at 55A / 53.5V between 200Vac-215Vac.

(D) Maximum Input Current: at 100% of full load with output adjusted to 58 volts DC as measured at the shelf output terminals. Nominal Input Voltage Input Voltage Number of Rectifier Modules Installed Input Current (Amperes)

208/240

176

19.6

Page 21 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011 1.2.6 Typical Input Data (1R483500e): 50 Hz input.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)


Home

(A) System output is initially adjusted to 54.48 volts DC as measured at the system sense point at 50% of full load and nominal input. Percent of Full Load refers to percent of 60 Amperes. Number of Rectifier Modules Installed Nominal Input Voltage Percent of Full Load Input Current (Amperes) Input VA Input Watts Power Factor % Heat Efficiency Dissipation % BTU/Hr*

0 25 50 208 75 100 110 1 120 0 25 50 240 75 100 110 120

0.3486 4.182 8.182 12.298 16.556 18.123 18.038 0.4109 3.647 7.096 10.623 14.259 15.598 15.537

72.58 869.44 1699.40 2550.61 3430.40 3753.27 3735.67 98.70 875.28 1701.62 2545.27 3413.60 3732.60 3718.00

11.56 853.6 1691.6 2546 3425 3749 3731 11.173 581.2 1686.4 2536 3406 3725 3710

0.157 0.981 0.995 0.998 0.998 0.999 0.998 0.113 0.972 0.991 0.996 0.997 0.998 0.998

0.000 95.31 96.50 96.19 95.27 94.82 94.46 0.00 95.42 96.72 96.53 95.77 95.46 95.14

39.45 136.69 202.15 331.13 552.36 663.18 705.02 38.12 113.18 188.53 300.58 491.16 577.14 615.09

* - Heat dissipation is the same for a List 3 shelf (three phase input).
(B) Typical Power Factor: Greater than or equal to 98% for any load greater than or equal to 50% of rated full load at nominal line. Meets IEC 1000-3-2. (C) Typical Operating Efficiency:

97% at best point, 96.2% at 50A / 53.5V between 215Vac-250Vac input, 96.6% at 50A / 53.5V between 200Vac-215Vac. 95.8% at 55A / 53.5V between 215Vac-250Vac input, 95.6% at 55A / 53.5V between 200Vac-215Vac.

(D) Maximum Input Current: at 100% of full load with output adjusted to 58 volts DC as measured at the shelf output terminals. Nominal Input Voltage Input Voltage Number of Rectifier Modules Installed Input Current (Amperes)

208/240

176

18.5

Page 22 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)


1.2.7 Typical Input Data (1R483200): 60 Hz input.

PD588705000 Issue AJ, January 18, 2011 Home

(A) System output is initially adjusted to 54.48 volts DC as measured at the system sense points at 50% of full load and nominal input. Percent of Full Load refers to percent of 55 Amperes. Number of Rectifier Modules Installed Nominal Input Voltage Percent of Full Load Input Current (Amperes) Power Factor % Heat Efficiency Dissipation % BTU/Hr*

Input VA

Input Watts

0 25 50 208 75 100 110 1 120 0 25 50 240 75 100 110 120

0.62 4.13 7.92 11.87 16.02 17.28 16.88 0.68 3.65 6.89 10.23 13.68 14.84 14.46

127 856 1644 2457 3298 3561 3478 163 865 1648 2445 3269 3538 3455

69 842 1639 2453 3297 3558 3477 66 846 1633 2441 3265 3534 3454

54.2 98.8 99.7 99.8 99.8 99.8 99.8 61.2 97.7 99.4 99.8 99.8 99.8 99.8

-88.9 91.4 91.6 90.9 90.5 89.9 -88.7 91.9 92.1 91.8 91.3 90.5

235.25 319.31 479.51 701.88 1020.09 1156.27 1208.42 225.31 325.42 453.62 654.78 917.81 1050.24 1118.21

* - Heat dissipation is the same for a List 3 shelf (three phase input).
(B) Typical Power Factor: Greater than or equal to 98% for any load greater than or equal to 50% of rated full load at nominal line. Meets IEC 1000-3-2. (C) Typical Operating Efficiency:

92% at best point, 91% at 50A / 53.5V between 215Vac-250Vac input, 90.5% at 50A / 53.5V between 200Vac-215Vac. 90.5% at 55A / 53.5V between 215Vac-250Vac input, 90% at 55A / 53.5V between 200Vac-215Vac.

(D) Maximum Input Current: at 100% of full load with output adjusted to 58 volts DC as measured at the shelf output terminals. Nominal Input Voltage Input Voltage Number of Rectifier Modules Installed Input Current (Amperes)

208/240

176

20.33

Page 23 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011 1.2.8 Typical Input Data (1R483200e): 60 Hz input.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)


Home

(A) System output is initially adjusted to 54.48 volts DC as measured at the system sense points at 50% of full load and nominal input. Percent of Full Load refers to percent of 55 Amperes. Number of Rectifier Modules Installed Nominal Input Voltage Percent of Full Load Input Current (Amperes) Power Factor % Heat Efficiency Dissipation % BTU/Hr*

Input VA

Input Watts

0 25 50 208 75 100 110 1 120 0 25 50 240 75 100 110 120

0.4228 3.8 7.417 11.176 15.202 16.361 16.279 0.4978 3.331 6.443 9.773 12.856 14.081 14.06

88.91 797.6 1552.8 2334 3166 3406 3424 120.6 806.2 1556.4 2356 3094 3395 3398

10.702 782.2 1546.7 2331 3164 3406 3422 10.451 780.4 1543.2 2349 3089 3386 3394

12.2 98.0 99.6 99.8 99.9 99.9 99.9 8.8 96.8 99.1 99.7 99.8 99.8 99.8

0.000 95.706 96.621 96.315 95.637 95.539 95.003 0.000 95.900 96.840 96.629 96.191 96.050 95.346

36.526 114.644 178.380 293.163 471.097 518.523 583.642 35.669 109.194 166.429 270.249 401.595 456.467 539.139

* - Heat dissipation is the same for a List 3 shelf (three phase input).
(B) Typical Power Factor: Greater than or equal to 98% for any load greater than or equal to 50% of rated full load at nominal line. Meets IEC 1000-3-2. (C) Typical Operating Efficiency:

97% at best point, 96.2% at 50A / 53.5V between 215Vac-250Vac input, 96.0% at 50A / 53.5V between 200Vac-215Vac. 95.8% at 55A / 53.5V between 215Vac-250Vac input, 95.6% at 55A / 53.5V between 200Vac-215Vac.

(D) Maximum Input Current: at 100% of full load with output adjusted to 58 volts DC as measured at the shelf output terminals. Nominal Input Voltage Input Voltage Number of Rectifier Modules Installed Input Current (Amperes)

208/240

176

19.6

Page 24 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)


1.2.9 Typical Input Data (1R483500e): 60 Hz input.

PD588705000 Issue AJ, January 18, 2011 Home

(A) System output is initially adjusted to 54.48 volts DC as measured at the system sense points at 50% of full load and nominal input. Percent of Full Load refers to percent of 60 Amperes. Number of Rectifier Modules Installed Nominal Input Voltage Percent of Full Load Input Current (Amperes) Power Factor % Heat Efficiency Dissipation % BTU/Hr*

Input VA

Input Watts

0 25 50 208 75 100 110 1 120 0 25 50 240 75 100 110 120

0.4173 4.211 8.192 12.299 16.548 18.151 18.022 0.4886 3.686 7.121 10.635 14.26 15.605 15.519

86.88 875.47 1701.48 2552.04 3428.75 3759.07 3732.36 117.41 884.64 1707.62 2548.15 3413.84 3734.28 3713.70

11.388 853.5 1691.1 2545 3424 3752 3727 11.276 851.4 1686.7 2535 3404 3725 3705

0.131 0.974 0.993 0.997 0.998 0.998 0.998 0.095 0.962 0.987 0.995 0.997 0.997 0.997

0.00 95.29 96.50 96.20 95.31 94.84 94.63 0.00 95.57 96.76 96.55 95.84 95.43 95.18

38.87 137.10 201.98 330.11 547.82 661.03 683.11 38.50 128.87 186.55 298.43 483.21 580.82 609.15

* - Heat dissipation is the same for a List 3 shelf (three phase input).
(B) Typical Power Factor: Greater than or equal to 98% for any load greater than or equal to 50% of rated full load at nominal line. Meets IEC 1000-3-2. (C) Typical Operating Efficiency:

97% at best point, 96.2% at 50A / 53.5V between 215Vac-250Vac input, 96.0% at 50A / 53.5V between 200Vac-215Vac. 95.8% at 55A / 53.5V between 215Vac-250Vac input, 95.6% at 55A / 53.5V between 200Vac-215Vac.

(D) Maximum Input Current: at 100% of full load with output adjusted to 58 volts DC as measured at the shelf output terminals. Nominal Input Voltage Input Voltage Number of Rectifier Modules Installed Input Current (Amperes)

208/240

176

18.5

Page 25 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011 1.3 Environmental Ratings 1.3.1

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)


Home

Climatic and Mechanical Environment: Meets Telcordia GR-63 Transportation.

According to ETS 300 019-1-2, class 2.3. Storage and handling: According to ETS 300 019-1-1, class 1.2. Operation: According to ETS 300 019-1-3, class 3.2. Transportation, storage and handling, operation: According to Telcordia GR-63-Core, chapter 4. Earthquake according to Eq (Z4). The rectifier operates in an extended temperature with output derating according to Figure 2. Relative Humidity: 95% (no condensation).

(A) Temperature: (1) Temperature:

-40 to +75 degrees C, operating temperature range -40 to +45 degrees C with 3200W output, +45 to +75 degrees C with derating output. -20 to +45 degrees C with full performance. Max. output at 65C is 2320W.

(2) Temperature Coefficient: 0.01% per degrees Celsius.

Rectifier starts at -40 degrees C, and continuously operates. At fan failure the rectifier shuts down. Does not rely on the temperature sensors.

(B) Dust Filter: No dust filter is used. (C) Airborne Contaminant: Erosion-proof paint is used on PCB boards. (1) Gas Contaminant Test (Corrosion Air): The rectifier works normally in corrosion air condition according to Telcordia, GR63 ch. 4.5 and 5.5.3. Also complies with NEBS requirement of gas contaminant. (2) Hygroscopic Dust: Complies with NEBS requirement of hygroscopic dust. (D) Altitude (Air Pressure): (1) The maximum operating ambient temperature should be derated above altitude of 2000m. (2) Meets NEBS requirement of altitude. (E) Office Vibration: Meets NEBS requirement of office vibration. (F) Illumination: Meets NEBS requirement of illumination. 1.3.2 Ventilation Requirements (A) Ventilation: The Rectifier Modules are fan cooled and utilize front to back forced ventilation. A Rectifier Module Mounting Shelf must be mounted so ventilating openings are not blocked and temperature of the air entering the cabinet does not exceed the Operating Ambient Temperature Range stated above.

The distance from the rear of a Rectifier Module Mounting Shelf to a wall or other solid structure must not be less than two inches. This will assure proper airflow through the Rectifier Modules. (See also Paragraph 1.3.7 [Mounting].)

Page 26 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

PD588705000 Issue AJ, January 18, 2011

Home (B) Stacking Considerations: This system is designed for front to back ventilation to facilitate stacking of Rectifier Module Mounting Shelves, one above the other, in a relay rack. There is no spacing requirement between stacked Rectifier Module Mounting Shelves of a single system. 1.3.3 Single Rectifier Audible Noise: (A) At 25C 53dB(A) with fan in high speed; Measurement made at 0.6m distance in front of rectifier and at same horizontal line of the middle of rectifier. (B) At 25C 45dB(A) with fan in low speed; Measurement made at 1m distance in front of rectifier and at same horizontal line of the middle of rectifier. 1.3.4 EMI/RFI Suppression: (A) Rectifier Modules operating in a Rectifier Module Mounting Shelf conform to the requirements of FCC rules Part 15, Subpart B, Class B for Radiated and Conducted emissions limits. (B) Rectifier Modules operating in a Rectifier Module Mounting Shelf conform to the requirements of European Norm, EN55022, Class B for Radiated and Conducted emissions limits. 1.3.5 Surge Protection: Compliance with EN61000-4-5 Installation Class 4, and capable of withstanding surges per ANSI/IEEE C 62.41 1980 Category B3 across the input terminals. Note: This level of protection is a widely used standard for telecommunications power equipment. As with all such equipment, it is the end user's responsibility to provide an adequately sized Surge Suppression Device at the commercial power service entrance of the building that reduces all incoming surges to levels below the classes/categories stated for the equipment. 1.3.6 Compliance Information: (A) Safety Compliance: This unit meets the requirements of UL 60950-1, Standard for Information Technology Equipment, and is UL Recognized as a power supply for use in Telephone, Electronic Data Processing or Information Processing Equipment. This unit meets the requirements of CAN/CSA 22.2, No. 60950-00 and is tested and Certified by UL ("c UR") as a Component Type Power Supply. (B) The rectifiers are RoHS compliant. 1.3.7 Mounting: This unit intended only for installation in a Restricted Access Location on or above a non-combustible surface. Clearance requirements are: (A) Recommended minimum aisle space clearance for the front of the unit is 2' 6". (B) When unit is shipped loose, recommended minimum aisle space clearance behind the unit is 2' 0 for access to installers connections. When unit is factory-installed in a NETSURE Power System, refer to the System Application Guide (SAG) for rear aisle space clearance recommendations. See Ventilation Requirements (Para. 1.3.2) in this document for minimum spacing requirements in all cases. 1.3.8 ESD Protection: Meets EN 61000-4-2.

Requirements are 6kV contact and 8kV air for criteria B and 8kV/15kV for criteria C. According Telcordia GR-1089-CORE R2-1, R2-2, R2-3, O2-4.

Page 27 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011 Contact 2kV 4kV 6kV 8kV 1.3.9 Electrical Fast Transient / Burst Immunity (A) Meets EN 61000-4-4: 1.4 Air

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)


Home 2kV 4kV 8kV 15kV

Burst will be fulfilled for AC and DC terminals at 4kV with criteria B. Burst will be fulfilled CAN-bus signals at 1kV with criteria B.

(B) Meets GR-1089 O2-8:

Burst (EFT) will be fulfilled for AC and DC terminals at 0.5kV. Burst will be fulfilled CAN-bus signals at 0.25kV.

Standard Features 1.4.1 1.4.2 Type of Power Conversion Circuit: High frequency. Float Charging Output Mode: In this mode of operation, system output voltage is constant and output current does not exceed the current limit setting. During normal operation, the battery is not required to furnish load current and remains in a fully charged condition.

The float voltage setting can be checked and/or adjusted without removing a Rectifier Module or affecting the load. One adjustment changes the output of all Rectifier Modules.
Note: If the current demanded by the load exceeds the current limit setting of the system, the battery is required to furnish the difference in load current and begins discharging. Note: If the system is used with a digital battery charge temperature compensation probe or TXM, the MCA automatically adjusts system output. This ensures proper voltage to the battery as battery ambient temperature fluctuates. 1.4.3 Test/Equalize Charging Output Mode: This mode of operation is used if higher output voltage is required for equalizing the charge on all battery cells of a conventional flooded cell battery, or for recharging the battery following a commercial power failure.

If the installation site does not require system equalize mode of operation, the equalize feature can be used as a test feature. System equalize voltage can be adjusted to a test voltage value. Placing the system into the test/equalize mode causes system output voltage to increase or decrease to this test voltage value. The test/equalize voltage setting can be checked and/or adjusted without removing a Rectifier Module or affecting the load. One adjustment changes the output of all Rectifier Modules.
Note: If the system is used with a battery charge digital temperature compensation probe or TXM, typical equalize mode of operation is not used. 1.4.4 Output Mode of Operation Selection: There are four methods of placing the system from the float mode to the test/equalize mode. (A) Method 1 (Manual Test/Equalize): A user manually places the system into the test/equalize mode via the MCA interface. A user must manually return the system to the float mode via the MCA interface.

Page 28 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

PD588705000 Issue AJ, January 18, 2011

Home (B) Method 2 (Manually Initiated Timed Test/Equalize): A user manually places the system into the test/equalize mode via the MCA interface. The system automatically returns to the float mode after a preset programmable time period (1-99 hours, in increments of one hour). (C) Method 3 (Automatic Test/Equalize):

THE AUTOMATIC EQUALIZE FEATURE IS INTENDED FOR USE ONLY WITH WET CELL BATTERIES. USING THIS FEATURE WITH VALVE REGULATED BATTERIES IS NOT RECOMMENDED. This feature can be enabled or disabled by a user via the MCA. The default state is disabled. The Automatic Equalize feature is a time based function that is controlled by a customer selectable multiplier and by the Battery On Discharge (BOD) alarm setpoint. The MCAs default setting is for a multiplier of zero, which disables the Automatic Equalize feature. When the Automatic Equalize feature is enabled, if system voltage drops to less than the BOD alarm setpoint, the MCA initiates a timing cycle to measure the discharge time period. The MCA requires at least 15 minutes of continuous BOD alarm in order to prevent nuisance equalization cycles. When system voltage rises to above the BOD alarm setpoint, the MCA ends the discharge timing cycle and (assuming a minimum of 15 minutes has elapsed) places the Rectifier Modules into the equalize mode for a customer selectable multiple of the discharge time period (the discharge time period includes the initial 15 minutes). The equalize time period can be set for 0 to 15 times the discharge time period, up to a maximum of 300 hours. A zero (0) setting disables the feature.
(D) Method 4 (External Test/Equalize): A user (or external equipment) places the system into the test/equalize mode by applying an external signal to the system. The system returns to the float mode when the external signal is removed. This method overrides the other three methods. 1.4.5 Input Protection: (A) Fuse: On the input two UL recognized fuses are used. (B) Input Voltage Protection: Requirement of operating range is 85-290Vac. Derating from 176Vac and 50% at 120Vac. Withstanding 415Vac input w/o damage.

To fulfill these, the following actions will be taken. 1) The rectifier will shut down at low or high voltage input; The protecting voltages are: Low voltage disable point: 80V3V; Hysteresis at least 15 VAC for restart. High voltage disable point: 295V5V; Hysteresis at least 10 VAC for restart. 2) Between 85V and 176V the output power will be derated linearly according input voltage as following. For R48-3200 and R48-3200e, Output power (not less than) Vs input voltage and temperature. Input voltage 85Vac 120Vac 176Vac 45C 700 1750 3200 55C 635 1586 2900 65C 508 1269 2320 70C 318 793 1450 75C 0 0 0

Page 29 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)


Home

For R48-3500e, Output power (not less than) Vs input voltage and temperature. Input voltage 85Vac 120Vac 176Vac 45C 700 1750 3500 50C 640 1600 3200 55C 580 1450 2900 65C 464 1160 2320 70C 290 725 1450 75C 0 0 0

For the stabilization, the output power can sluggishly change when input voltage fluctuate in a narrow range which not more than 3V. 3) Over voltage isolation The rectifier will be disconnected from the mains when a preset non-adjustable value is reached.
(C) AC Fail Alarm: The rectifier issues an "AC Fail Alarm" when AC input voltage drops to 164Vac. This alarm clears when AC input voltage recovers to 169Vac. 1.4.6 Output Protection: (A) Current Limiting: The maximum current delivered by the system can be programmed from 10% to 121% of total system capacity at maximum rated output voltage. The associated MCA automatically adjusts the current limit circuit on each Rectifier Module so that this value is not exceeded. If a Rectifier Module fails, the MCA automatically resets each remaining Rectifier Module's current limit point to maintain this value. The MCA also insures that the current limit circuit on any Rectifier Module is not set above 121% of its capacity. The default current limit setting is the sum of each installed Rectifier Modules output rating. If an additional Rectifier Module is added to the system, the system current limit is automatically increased by the rating of the new Rectifier Module and the new current limit value is displayed.

The current limiting point can be adjusted (via the MCA) without removing a Rectifier Module. One adjustment changes the setting of all Rectifier Modules. The current limit is factory set at 100% of rated full load, unless otherwise specified. Output Current Limit Error: 1.5A (at 42-58.5V), 3A (at 30-42V), 5A (20 < at < 30V).
(B) Thermal Current Limiting: Each Rectifier Module continuously monitors the ambient temperature surrounding the power conversion circuit. If this temperature for any reason (such as a high ambient temperature) increases above approximately +45C (+113F), the Rectifier Module will not shut down. Rather, the Rectifier Module will limit its maximum output power to maintain the temperature of the power conversion circuit within design parameters. Operation between +45C (+113F) and +65C (149F) will result in the output power being decreased. Full power capability is restored when the temperature decreases to below approximately +45C (+113F). Refer to the following curve (Figure 2) illustrating typical operating parameters. Warning: The module is rated for continuous operation at full output power up to +45C (+113F). Operation between +45C (+113F) and +65C (149F) will result in output power decrease. Operation above +65C (+149F) is 1 considered abnormal and should be used on a temporary basis only.

Temporary Operation at Abnormal Temperature: Temporary operation refers to a period of not more than eight consecutive hours per day, and a total of not more than 15 days in a year. (This refers to a total of 120 hours in any given year, but no more than 15 occurrences in that one year period.)

Page 30 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

PD588705000 Issue AJ, January 18, 2011 Home

Output power vs. Temperature at Uin > 176 VAC


120 % of output power 100 80 60 40 20 0 -40 -20 0 20 40 60 80 100 Temperature (C)

Figure 2 Typical Thermal Power Limit Curve


(C) High Temperature Alarm: Each Rectifier Module continuously monitors the ambient temperature surrounding the power conversion circuit. If this temperature exceeds a preset non-adjustable value, local and extended Rectifier Module Fail alarms are activated. The alarms will automatically be removed when the ambient temperature surrounding the power conversion circuit decreases to below a preset non-adjustable value. (D) High Voltage Shutdown: (1) Internal: If Rectifier Module output voltage exceeds an adjustable preset value and it is delivering more than 10% of its rated current, the Rectifier Module shuts down.

After approximately 6 seconds, the Rectifier Module automatically restarts. If Rectifier Module output voltage again exceeds the high voltage shutdown value within 5 minutes, the Rectifier Module shuts down and locks out. Manual restart is then required (by turning AC power to the Rectifier Module off or by removing the Rectifier Module, waiting 19 seconds or more, then turning AC power to the Rectifier Module on or reinserting the Rectifier Module). If the Rectifier Module does not experience a high voltage condition within the 5-minute time-period, the restart circuit is reset. If two or more Rectifier Modules are installed in a shelf, or if the shelf is paralleled with other Rectifier Mounting Shelves, only the Rectifier Module causing the high voltage condition shuts down. The high voltage shutdown point can be checked and/or adjusted without removing a Rectifier Module. One adjustment changes the setting of all Rectifier Modules. Adjustable from 48.00 to 59.00 volts DC. Refer to the separate Power System documentation for the factory setting.
(2) Remote: See associated Power System documentation. (3) Backup: If Rectifier Module output voltage exceeds a second (non-adjustable) value, the Rectifier Module shuts down and locks out regardless of load. Manual restart is then required (by turning AC power to the Rectifier Modules off then on, or by removing and re-inserting the Rectifier Modules). (E) Overload / Reverse Current: An output fuse is provided on each Rectifier Module. This fuse is not customer replaceable. The Rectifier Module can be plugged into or pulled out of a shelf while operating, without damage or opening the fuse.

Page 31 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011 1.4.7 1.4.8

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)


Home

Paralleling: This system may be connected in parallel with any rectifier of the same polarity and adjusted to the same output voltage. Load Sharing:

(A) Rectifier Module Load Sharing (per Bay): The requirement is < 1.5A difference of average current of rectifiers at 10%~100% load for rectifiers in one cabinet (max 1320A).

The internal processors of rectifiers will control load sharing. The maximum number of parallel rectifiers is 36.
(B) MCA Load Sharing (between two Bays): The MCA load sharing feature automatically balances the load to within 1% of the Bays' rated output currents. If the MCA's load sharing feature is disabled for any reason, pre-programmed slope control in each Rectifier Module balances the load in each bay as stated above. The MCA will balance a system of up to 72 Rectifier Modules within 5 minutes. The MCA's load sharing feature is disabled whenever the system is in current limit, the system is delivering more than 100% capacity, or the system is delivering less than 1% capacity. MCA Load Share Alarm: The MCA balances the load by monitoring the output current of each Rectifier Module, and raising or lowering the output voltage of each Rectifier Module individually to reduce the output current differences between the Rectifier Modules. If one Rectifier Module is delivering less (or more) current than the others, the MCA slowly continues to increase (or decrease) that Rectifier Module's output voltage in an attempt to get its output current to equal the others. If, after about 15 minutes of trying, the MCA is unable to balance the output currents, the MCA turns on the Load Share Alarm and identifies the Rectifier Module that is the furthest out of balance. The MCA Load Share Alarm can be enabled or disabled by the customer. The factory default setting is to have the MCA Load Share Alarm 'enabled'. 1.4.9 Output Current Walk-In: (A) Normal Start:

Start up time, defined as beginning at AC switch on and ending when full output power has been reached, consists of two time intervals, the delay period and the output voltage ramp up period. During the delay period the output voltage will be zero volt. Start up time (AC on, till full power): 5 seconds. Output voltage ramp up period, t: 50 t 150 ms. (10% to 90% of full power) The rectifier will not suffer any damage, when subjected to repetitive AC switch on / switch off operations.

(B) Current Walk-In:

90% load in > 8S 100% load max 124s with < 10% time tolerances. According to Telcordia GR-947-CORE, R3-19.

1.4.10 Cooling: Adopting front-to-back force air-cooling.

Thirty-six rectifiers are able to operate in a 400 mm deep cabinet without door, with back panel, 2200 mm high. The output air from the rectifiers is less than 80C at 55C ambient temperature and 186Vac input 54.5V / 2700W output; and less than 85C at 65C ambient temperature 186Vac input and 54.5V / 2320W output. [EMEA requirement]. The distance is 5mm from the test point to the back panel of the rectifier. Page 32 of 41

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

PD588705000 Issue AJ, January 18, 2011 Home

Thirty-six rectifiers are able to operate in a 600 mm deep cabinet without door, with back panel, 2200 mm high.

Fan Control

When input voltage is at normal range, the fans speed is adjusted by the built-in processor according the rectifier's internal temperature. The fan is turned off when input voltage is abnormal such as very low or high input voltage. The fan starts at half of full speed when the rectifier starts up. The fan failure is detected and reported to MCA. Full fan speed is customer selectable from the MCA.
1.4.11 Rectifier Module Local Status and Alarm Indicators: Refer to the "Operating Procedures" chapter in the Power System User Instructions (Section 5975) for a complete description. (A) Power (Green) (B) Protection (Yellow) (C) Alarm (Red) 1.4.12 External Control Circuits: Provided via the associated MCA. Refer to the separate Power System documentation for a complete description of available external control circuits. 1.4.13 External Alarm Circuits: Provided via the associated MCA. Refer to the separate Power System documentation for a description of available external alarms. 1.4.14 Mounting: The Rectifier Mounting Shelves are designed for mounting in a 23 inch wide relay rack with 1 inch or 1-3/4 inch multiple drilling. Mounting angles can be positioned from 'FlushFront' mounting to '6-inch front projection' mounting, in 1-inch increments. Refer to "Overall Dimensions, Rectifier Module Mounting Shelf" for dimensional illustration.

Page 33 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)


Home

PHYSICAL SIZE INFORMATION Overall Dimensions


Rectifier Module Mounting Shelf
Notes: 1. All dimensions are in inches, unless otherwise specified. 2. Weight in LBS. Shelf Net: 17 Shipping: 18 Rectifier Module Net: 7 Shipping : 8 3. Finish: Shelf and Rectifier Module Bodies: Bright Zinc Plating (M500-53) Rectifier Module Face Plates: Textured Gray (M500-147)

1.484

2.250

1.484

4. Mounting angles may be positioned from flush front mounting to 6-inch front projection mounting, in 1-inch increments.

Top View 0.688

Mounting Angle Detail

See Mounting Angle Detail

17.510

5.217

20.638 22.312 23.000 Front View

5.970 Right Side View Hole for 3/4 Conduit Filling (AC Input)

Hole for 3/4 Conduit Filling (AC Input)

Rear View

Hole for 3/4 Conduit Filling (AC Input)

Hole for 3/4 Conduit Filling (AC Input)

Left Side View

Page 34 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

PD588705000 Issue AJ, January 18, 2011

Digital Battery Charge Temperature Compensation Probe (P/N 107021 and 106824)

Home

0.25 (6.35) DIA.

0.75 (19.05)

3.00 (76.2)

0.75 (19.05)

2.25 (57.15)

0.35 (8.89)

300 (7,620) or 1200 (30,480) Part No. 107021 (25 foot) Part No. 106824 (100 foot)

Note: All dimensions are in inches and (millimeters).

Analog Battery Temperature Probe (P/N 521262)

PROBE ATTACH TO NEGATIVE BATTERY TERMINAL (CLEARANCE FOR 5/16 (7.94) HARDWARE)

180 3.00 (4,572 76)

NOTE: All dimensions are in inches and (millimeters).

Page 35 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV) Home

Connection Locations
List 1 AC Input and Frame Ground (Single-Phase Input)

Hole for 3/4" Conduit Fitting (AC Input)

Rear View Hole for 3/4" Conduit Fitting (AC Input)

Rear View

Rectifier Module 4 AC IN

1 2 Rectifier 1 Module 5 2 Rectifier 1 Module 6 2

PCU 4 PCU 5 PCU 6

1 2 1 2 1 2

FRAME GROUND CONNECTION ONE 10-32 X 3/4" STUD AND HARDWARE, PER SIDE

1 PCU 1 2 1 PCU 2 2 1 PCU 3 2

1 2 1 2 1 2

Rectifier Module 1 Rectifier Module 2 Rectifier Module 3 AC IN

Note: Rectifier Module mounting positions are numbered left to right as viewed from front of shelf.

Page 36 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV) List 3 AC Input and Frame Ground (Three-Phase Input)

PD588705000 Issue AJ, January 18, 2011 Home

Hole for 3/4" Conduit Fitting (AC Input) Rear View

Hole for 3/4" Conduit Fitting (AC Input)

Rear View

AC IN Feed 2 (Rectifier Modules 4-6)

(A) (B) (C)

TB2 A 1 B 2 C 3

TB1 1 A 2 B 3 C

(A) (B) (C)

AC IN Feed 1 (Rectifier Modules 1-3)

FRAME GROUND CONNECTIONS One 10-32 X 3/4" stud and hardware per side

FRAME GROUND CONNECTIONS One 10-32 X 3/4" stud and hardware per side

CONNECTIONS WITHIN THE SHELF Mounting Position TB1, Terminal 1 (A) L1 L1 L1 2 (B) L2 L2 L2 L1 L1 L1 L2 L2 L2 3 (C) TB2, Terminal 1 (A) 2 (B) 3 (C)

NOTE Rectifier Module mounting positions are numbered left to right as viewed from front of shelf.

Rect 1 Rect 2 Rect 3 Rect 4 Rect 5 Rect 6

Page 37 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011 List 11 AC Input (Single-Phase Input)

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV) Home

Rectifier Module 4

Rectifier Module 5 Rectifier Module 6

Rear View

Rectifier Module 1 Rectifier Module 2 Rectifier Module 3

Note: Rectifier Module mounting positions are numbered left to right as viewed from front of shelf.

Page 38 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

PD588705000 Issue AJ, January 18, 2011 Home

DC Output and Alarm/Control to MCA

Rear View

Alarm & Control Connections Between Shelves and MCA to MCA if Top Shelf or to Shelf Mounted Above 1/4-20 Captive Fastener (4 Places, 2 per Polarity) 1.00" 1.00"

to Shelf Mounted Below Alarm & Control Connections Between Shelves and MCA

Negative Output (-)

Positive Output (+)

Rear View

Page 39 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

PD588705000 Issue AJ, January 18, 2011

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV)

RELATED DOCUMENTATION
Spec. No. 588705000 Rectifier Mounting Shelf Schematic Diagram: Wiring Diagram:
SD588705000 T588705000

Home

Spec. No. 582126000 NETSURE Power System System Application Guide: System Installation Instructions: System User Instructions: Color MCA Menu Tree:
SAG582126000 Section 5974 Section 5975 Section 6022

Spec. No. 582126100 NETSURE Power System System Application Guide: System Installation Instructions: System User Instructions: Color MCA Menu Tree:
SAG582126100 Section 6027 Section 6028 Section 5886

Page 40 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Power Data Sheet Spec. No. 588705000 (Model PSS4850-23GV) REVISION RECORD Issue AA AB AC AD AE AF AG AH AJ Change Number (ECO) LLP205300 LLP207736 LLP207874 LLP208864 LLP210447 LLP211072 LLP213309 LLP213967 LLP214969 New Miscellaneous updates per marketing. AC input terminal block changed. Wire size capacity updated. Revised aisle space clearance requirements in Specifications section. Corrected heat dissipation data in Para. 1.2.4 and 1.2.5. Added List 3. Corrected input data. Removed input data for multiple rectifier modules. List 11 (Shelf with AC Line Cords) added. 1R483200e Rectifier Module added as option. Physical Dimension labeling updated. Added 1R483500e rectifier to the existing power system of 582126000. Added and updated charts for rectifier specifications. Description of Change

PD588705000 Issue AJ, January 18, 2011


Home

Date 05/17/06 01/11/07 05/04/07 07/30/07 05/16/08 07/23/08 01/20/10 05/06/10 01/04/11

Approved John Jasko John Jasko John Jasko J. Kirkpatrick J. Kirkpatrick John Jasko Shanon Ravacio Shanon Ravacio Khristebelle Ilagan

Mike Smith Jan 21, 2011 Bruce Walsh Jan 23, 2011

Emerson Network Power, Energy Systems, North America, Inc. 4350 Weaver Parkway, Warrenville, IL 60555

Toll Free: 800-800-1280 (USA and Canada) Telephone: 440-246-6999 Fax: 440-246-4876 Web: EmersonNetworkPower.com/EnergySystems EnergyNet: Secure.EmersonNetworkPower.com Page 41 of 41
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.