Modbus Communications Protocol

Reference Guide

BG0427 Rev. A1

Every effort has been made to ensure that the material herein is complete and accurate.
However, the manufacturer is not responsible for any mistakes in printing or faulty instructions
contained in this book. Notification of any errors or misprints will be received with
appreciation.
For further information regarding a particular installation, operation or maintenance of
equipment, contact the manufacturer or your local representative or distributor.

Modbus is a trademark of Schneider Electric.

Table of Contents
1 GENERAL ..........................................................................................................7
2 MODBUS PROTOCOL IMPLEMENTATION......................................................8
2.1
2.2
2.3
2.4
2.5
2.6
2.7

TRANSMISSION MODES ............................................................................................................8


ADDRESS FIELD .......................................................................................................................8
FUNCTION FIELD ......................................................................................................................8
EXCEPTION RESPONSES ..........................................................................................................8
TRANSACTION TIMING ..............................................................................................................8
MODBUS REGISTER ADDRESSES ..............................................................................................9
DATA FORMATS .......................................................................................................................9

2.7.1
2.7.2
2.7.3
2.7.4

16-BIT SCALED INTEGER FORMAT ............................................................................................................9


32-BIT LONG INTEGER FORMAT ..............................................................................................................10
32-BIT FLOATING POINT FORMAT ...........................................................................................................11
32-BIT MODULO-10000 FORMAT ...........................................................................................................11

2.8
2.9

USER ASSIGNABLE REGISTERS...............................................................................................11


PASSWORD PROTECTION .......................................................................................................12

3 MODBUS REGISTER MAP ..............................................................................13


3.1

MODBUS SETUP REGISTERS ..................................................................................................13


Assignable Modbus Registers.............................................................................................................. 13
Assignable Registers Map ................................................................................................................... 13
Modbus Conversion Scales ................................................................................................................. 13
Device Data Scales.............................................................................................................................. 13
32-bit Register Type............................................................................................................................. 13

3.2
3.3

16-BIT SCALED ANALOG REGISTERS AND ENERGY COUNTERS - BASIC REGISTER SET .............14
16-BIT SCALED ANALOG REGISTERS, BINARY REGISTERS AND COUNTERS ...............................16
None .................................................................................................................................................... 16
Special Inputs ...................................................................................................................................... 16
Digital Inputs (bitmap) .......................................................................................................................... 16
Relay Outputs (bitmap) ........................................................................................................................ 16
Counters .............................................................................................................................................. 16
1-Cycle Phase Values.......................................................................................................................... 16
1-Cycle Total Values ............................................................................................................................ 17
1-Cycle Auxiliary Values....................................................................................................................... 17
Phasor.................................................................................................................................................. 17
1-Second Phase Values....................................................................................................................... 18
1-Second Total Values......................................................................................................................... 18
1-Second Auxiliary Values ................................................................................................................... 19
Present Volt, Ampere and Power Demands......................................................................................... 19
Total Energies EH.................................................................................................................................. 19
Phase Energies EH ............................................................................................................................... 20
V1/V12 Harmonic Distortion EH............................................................................................................. 20
V2/V23 Harmonic Distortion EH............................................................................................................. 20
V3/V31 Harmonic Distortion EH............................................................................................................. 20
I1 Harmonic Distortion EH ..................................................................................................................... 20
I2 Harmonic Distortion EH ..................................................................................................................... 20
I3 Harmonic Distortion EH ..................................................................................................................... 21
Fundamental Phase Values EH ............................................................................................................. 21
Fundamental Total Values EH ............................................................................................................... 21
Minimum 1-Cycle Phase Values .......................................................................................................... 21
Minimum 1-Cycle Total Values............................................................................................................. 21
Minimum 1-Cycle Auxiliary Values ....................................................................................................... 22
Maximum 1-Cycle Phase Values ......................................................................................................... 22
Maximum 1-Cycle Total Values............................................................................................................ 22
Maximum 1-Cycle Auxiliary Values ...................................................................................................... 22
Maximum Demands ............................................................................................................................. 22

TOU Parameters EH.............................................................................................................................. 22


Scaled Analog Outputs ........................................................................................................................ 23
TOU Energy Register #1 EH.................................................................................................................. 23
TOU Energy Register #2 EH.................................................................................................................. 23
TOU Energy Register #3 EH.................................................................................................................. 23
TOU Energy Register #4 EH.................................................................................................................. 23
Summary Energy Accumulated Demands EH ....................................................................................... 23
Summary Energy Block Demands EH ................................................................................................... 23
Summary Energy Sliding Window Demands EH.................................................................................... 23
Summary Energy Maximum Demands EH ............................................................................................ 24
TOU Maximum Demand Register #1 EH ............................................................................................... 24
TOU Maximum Demand Register #2 EH ............................................................................................... 24
TOU Maximum Demand Register #3 EH ............................................................................................... 24
TOU Maximum Demand Register #4 EH ............................................................................................... 24
V1/V12 Harmonic Angles EH ................................................................................................................. 24
V2/V23 Harmonic Angles EH ................................................................................................................. 24
V1/V31 Harmonic Angles EH ................................................................................................................. 25
I1 Harmonic Angles EH ......................................................................................................................... 25
I2 Harmonic Angles EH ......................................................................................................................... 25
I3 Harmonic Angles EH ......................................................................................................................... 25
Setpoint Status (bitmap)....................................................................................................................... 25

3.4

32-BIT ANALOG REGISTERS, BINARY REGISTERS AND COUNTERS ............................................26


Special Inputs ...................................................................................................................................... 26
Digital Inputs DI1-DI4 (bitmap) ............................................................................................................. 26
Relay Outputs RO1-RO2 (bitmap) ....................................................................................................... 26
Counters .............................................................................................................................................. 26
1-Cycle Phase Values.......................................................................................................................... 26
1-Cycle Total Values ............................................................................................................................ 27
1-Cycle Auxiliary Values....................................................................................................................... 27
Phasor.................................................................................................................................................. 27
1-Second Phase Values....................................................................................................................... 28
1-Second Total Values......................................................................................................................... 28
1-Second Auxiliary Values ................................................................................................................... 29
Present Volt, Ampere and Power Demands......................................................................................... 29
Total Energies EH.................................................................................................................................. 29
Summary Energy Registers EH ............................................................................................................. 30
Phase Energies EH ............................................................................................................................... 30
V1/V12 Harmonic Distortions EH ........................................................................................................... 30
V2/V23 Harmonic Distortions EH ........................................................................................................... 30
V3/V31 Harmonic Distortions EH ........................................................................................................... 30
I1 Harmonic Distortions EH ................................................................................................................... 30
I2 Harmonic Distortions EH ................................................................................................................... 31
I3 Harmonic Distortions EH ................................................................................................................... 31
Fundamental (H01) Phase Values EH ................................................................................................... 31
Harmonic Total Values EH .................................................................................................................... 31
Minimum 1-Cycle Phase Values .......................................................................................................... 31
Minimum 1-Cycle Total Values............................................................................................................. 32
Minimum 1-Cycle Auxiliary Values ....................................................................................................... 32
Maximum 1-Cycle Phase Values ......................................................................................................... 32
Maximum 1-Cycle Total Values............................................................................................................ 32
Maximum 1-Cycle Auxiliary Values ...................................................................................................... 32
Maximum Demands ............................................................................................................................. 32
TOU Parameters EH.............................................................................................................................. 33
Scaled Analog Outputs ........................................................................................................................ 33
TOU Energy Register #1 EH.................................................................................................................. 33
TOU Energy Register #2 EH.................................................................................................................. 33
TOU Energy Register #3 EH.................................................................................................................. 33
TOU Energy Register #4 EH.................................................................................................................. 33
Summary Energy Accumulated Demands EH ....................................................................................... 33
Summary Energy Block Demands EH ................................................................................................... 34
Summary Energy Sliding Window Demands EH.................................................................................... 34
Summary Energy Maximum Demands EH ............................................................................................ 34
TOU Maximum Demand Register #1 EH ............................................................................................... 34

TOU Maximum Demand Register #2 EH ............................................................................................... 34


TOU Maximum Demand Register #3 EH ............................................................................................... 34
TOU Maximum Demand Register #4 EH ............................................................................................... 34
V1/V12 Harmonic Angles EH ................................................................................................................. 34
V2/V23 Harmonic Angles EH ................................................................................................................. 35
V1/V31 Harmonic Angles EH ................................................................................................................. 35
I1 Harmonic Angles EH ......................................................................................................................... 35
I2 Harmonic Angles EH ......................................................................................................................... 35
I3 Harmonic Angles EH ......................................................................................................................... 35
Setpoint Status SP1-SP16 (bitmap) ..................................................................................................... 35

3.5

MINIMUM/MAXIMUM LOG REGISTERS ......................................................................................36


Minimum Phase Values ....................................................................................................................... 36
Minimum Total Values.......................................................................................................................... 36
Minimum Auxiliary Values .................................................................................................................... 36
Maximum Phase Values ...................................................................................................................... 36
Maximum Total Values......................................................................................................................... 37
Maximum Auxiliary Values ................................................................................................................... 37
Summary Energy Maximum Demands EH ............................................................................................ 37
Maximum Demands ............................................................................................................................. 37
TOU Maximum Demand Register #1 EH ............................................................................................... 38
TOU Maximum Demand Register #2 EH ............................................................................................... 38
TOU Maximum Demand Register #3 EH ............................................................................................... 38
TOU Maximum Demand Register #4 EH ............................................................................................... 39

3.6

DEVICE CONTROL AND STATUS REGISTERS ............................................................................40


Device Restart Register ....................................................................................................................... 40
Device Authorization Registers ............................................................................................................ 40
Remote Relay Control.......................................................................................................................... 40
Device Reset/Clear Registers .............................................................................................................. 40
Device Identification ............................................................................................................................. 40
Device Status Registers....................................................................................................................... 40
Alarm Notification Registers ................................................................................................................. 41

3.7

DEVICE SETUP REGISTERS ....................................................................................................42


Device Identification ............................................................................................................................. 42
Factory Device Settings ....................................................................................................................... 42
Basic Setup.......................................................................................................................................... 42
Communication Ports Setup ................................................................................................................ 43
Device Options Setup .......................................................................................................................... 43
Local Settings ...................................................................................................................................... 44
Clock Indication and Setup .................................................................................................................. 44
Alarm/Event Setpoints Setup ............................................................................................................... 44
Pulse Counters Setup .......................................................................................................................... 45
Analog Outputs Setup .......................................................................................................................... 45
Digital Inputs Setup .............................................................................................................................. 45
Network Setup...................................................................................................................................... 45
Password Setup ................................................................................................................................... 46
Expert Power Service Setup ................................................................................................................ 46
Internet Service Provider (ISP) accounts ............................................................................................. 46
DNP Options Setup.............................................................................................................................. 46
DNP Class 0 Point Assignments .......................................................................................................... 47
TOU Daily Profile Setup EH ................................................................................................................... 47
TOU Calendar Setup EH ....................................................................................................................... 48
Summary Energy/TOU Registers Setup EH .......................................................................................... 48
Summary Energy/TOU Registers Source Setup EH .............................................................................. 48
Digital Inputs Setup .............................................................................................................................. 49
Relay Outputs Setup ............................................................................................................................ 49
Analog Outputs Setup .......................................................................................................................... 49

3.8

ANALOG AND DIGITAL I/O CONFIGURATION .............................................................................50


I/O Slots Configuration Info .................................................................................................................. 50
I/O Type Info ........................................................................................................................................ 50

4 DATA SCALES AND UNITS ............................................................................51


Data Scales.......................................................................................................................................... 51

Data Units Low Resolution Option .................................................................................................... 51


Data Units High Resolution Option.................................................................................................... 51

5 DATA FORMATS .............................................................................................52


Timestamp ........................................................................................................................................... 52
Wiring Mode......................................................................................................................................... 52
TOU Tariff Change Time...................................................................................................................... 52
Summary/TOU Energy Register Source ID.......................................................................................... 52
Setpoint Trigger Parameters ID ........................................................................................................... 52
Relays .................................................................................................................................................. 52
Setpoint Action ID ................................................................................................................................ 53
Counter Source ID ............................................................................................................................... 53
Relay Output Pulse Source ID ............................................................................................................. 53
AO Parameters ID................................................................................................................................ 54
Device Diagnostics............................................................................................................................... 54
DNP Object Types ............................................................................................................................... 54
DNP Class 0 Objects ........................................................................................................................... 55
Instrument Options............................................................................................................................... 55
I/O Slot Types ...................................................................................................................................... 55

1 General
This document specifies a subset of the Modbus serial communications protocol used to transfer data
between a master computer station and the PM130. The document provides the complete information
necessary to develop third-party communications software capable of communication with the Series
PM130 instruments. Additional information concerning operating the device, configuring the
communication parameters, and communication connections may be found in the "Series PM130
PLUS Powermeters, Installation and Operation Manual".
The document is applicable to the PM130P and PM130EH devices.
IMPORTANT
1.

In 3-wire connection schemes, the unbalanced current and phase readings for power factor, active power,
and reactive power will be zeros, because they have no meaning. Only the total three-phase power values
are provided.

2.

Most of the advanced features are configured using multiple setup parameters that can be accessed in a
number of contiguous registers. When writing the setup registers, it is recommended to write all the registers
at once using a single request, or to clear (zero) the setup before writing into separate registers.

Designations used in the guide:


EH - available in the PM130EH

2 Modbus Protocol Implementation


For detailed information about Modbus protocol, Modbus message framing and error checking, refer
to the "Modicon Modbus Protocol Reference Guide". It can be downloaded from the
www.modbus.org Website. The following paragraphs outline some issues concerning the
implementation of the Modbus protocol in the PM130.

2.1 Transmission Modes


The PM130 can be set up to communicate on a Modbus network using RTU transmission mode. Refer
to the "Series PM130 PLUS Powermeters, Installation and Operation Manual" on how to select the
transmission mode in your meter.

2.2 Address Field


The address field contains a user assigned address of the instrument (1-247) on a Modbus network.
Broadcast mode using address 0 is not supported.

2.3 Function Field


The Modbus functions implemented in the PM130 are shown in Table 2-1. Function 04 can be used in
the same context as function 03.
Table 2-2 Modbus Function Codes
Code (decimal)
03
04
06
16
08
1

Meaning in Modbus
Read holding registers
Read input registers
Preset single register
Preset multiple registers
Loop-back test

Action
Read multiple registers
Read multiple registers
Write single register
Write multiple registers
Communications test

The PM130 supports only diagnostic code 0 - return query data.

2.4 Exception Responses


The instrument sends an exception response when an error is detected in the received message. To
indicate that the response is notification of an error, the high order bit of the function code is set to 1.
Implemented exception response codes:
01
02
03
04

Illegal function
Illegal data address
Illegal data value
Device failure

When the character framing, parity, or redundancy check detects a communication error, processing of
the master's request stops. The instrument will not act on or respond to the message.

2.5 Transaction Timing


The PM130 response time to master requests is indicated in Table 2-2.
Table 2-2 Response Time
Baud Rate, bps
9600
19200
57600
115200

Min
13
11
9
9

Response Time, ms
Max
15
12
10
10

Typical
13
11
9
9

2.6 Modbus Register Addresses


The PM130 Modbus registers are numbered in the range of 0 to 65535. From the Modbus
applications, the PM130 Modbus registers can be accessed by simulating holding registers of the
Modicon 584, 884 or 984 Programmable Controller, using a 5-digit 4XXXX or 6-digit 4XXXXX
addressing scheme. To map the PM130 register address to the range of the Modbus holding registers,
add a value of 40001 to the PM130 register address. When a register address exceeds 9999, use a 6-digit
addressing scheme by adding 400001 to the PM130 register address.

2.7 Data Formats


The PM130 uses four data formats to pass data between a master application and the instrument: 16bit short integer, 32-bit long integer, 32-bit floating point and 32-bit modulo-10000 formats. Binary
values and counters are always transmitted in 32-bit registers, while analog values can be read both in
32-bit and in 16-bit scaled registers.
32-bit analog and energy registers and counters can be read either in long integer or in single precision
floating point format. The register type can be selected in the meter separately for analog registers,
binary counters and energy registers via Modbus register 246 (see Section 3.1, Modbus Setup
Registers). Refer to the "PM130 PLUS Powermeters, Installation and Operation Manual, Device
Options Setup" for information on how to setup the type of 32-bit registers in your meter.
Analog registers 256 through 308 and 6656 through 10935 contain scaled 16-bit data.
2.7.1 16-bit Scaled Integer Format
16-bit scaled analog data is transmitted in a single 16-bit Modbus register being scaled to the range of 0
to 9999. To get a true reading, a reverse conversion should be done using the following formula:
Y=

X (HI LO)
+ LO
9999

where:
Y
X
LO and HI -

True reading in engineering units


Raw input data in the range of 0 to 9999
Data low and high scales in engineering units

The engineering scales are indicated for every scaled 16-bit register. Refer to Section 4 Data Scales
and Units for applicable data scales and measurement units. The default voltage scale in the device is
144V (120V+20%). It can be changed through register 242 (see Section 3.1, Device Data Scales), or via
the supplemental PAS software. The recommended voltage scale is 120V+20% = 144V for using with
external PTs, and 690V+20% = 828V for a direct connection to power line.
CONVERSION EXAMPLES
1. Voltage readings

a) Assume device settings (direct wiring): PT ratio = 1; Voltage scale = 828V (690V + 20%).
Voltage engineering scales (see Section 4):
HI_ENG = Vmax = 828.0 PT ratio = 828.0 1 = 828.0V
LO_ENG = 0V
If the raw data reading is 1449 then the voltage reading in engineering units will be as follows:
Volts reading = 1449 (828.0 - 0)/(9999 - 0) + 0 = 120.0V
b) Assume device settings (wiring via PT): PT ratio = 14,400V : 120V = 120; Voltage scale = 144V.
Voltage engineering scales (see Section 4):
HI_ENG = Vmax = 144.0 PT ratio = 144 120 = 17,280V
LO_ENG = 0V
If the raw data reading is 8314 then the voltage reading in engineering units will be as follows:

Volts reading = 8314 (17,280 - 0)/9999 + 0 = 14,368V


2. Current readings

Assume device settings: CT primary current = 200A.


Current engineering scales (see Section 4):
HI_ENG = Imax = CT primary current 2 = 200.00 2 = 400.00A
LO_ENG = 0A
If the raw data reading is 250 then the current reading in engineering units will be as follows:
Amps reading = 250 (400.00 - 0)/(9999 - 0) + 0 = 10.00A
3. Power readings

a) Assume device settings (direct wiring): Wiring 4LL3; PT = 1; CT primary current = 200A; Voltage scale = 828V.
Active Power engineering scales (see Section 4):
HI_ENG = Pmax = Vmax Imax 2 = (828.0 1) (200.00 2) 2 = 662,400W = 662.400kW
LO_ENG = -Pmax = -662.400kW
If the raw data reading is 5500 then the power reading in engineering units will be as follows:
Watts reading = 5500 (662.400 - (-662.400))/(9999 - 0) + (-662.400) = 66.313kW
If the raw data reading is 500 then the power reading in engineering units will be as follows:
Watts reading = 500 (662.400 - (-662.400))/(9999 - 0) + (-662.400) = -596.153kW
b) Assume device settings (wiring via PT): Wiring 4LN3; PT = 120; CT primary current = 200A.
Active Power engineering scales (see Section 4):
HI_ENG = Pmax = Vmax Imax 3 = (828 120) (200.00 2) 3/1000 = 119,232kW
LO_ENG = -Pmax = -119,232kW
If the raw data reading is 5500 then the power reading in engineering units will be as follows:
Watts reading = 5500 (119,232 - (-119,232))/(9999 - 0) + (-119,232) = 11,936kW
If the raw data reading is 500 then the power reading in engineering units will be as follows:
Watts reading = 500 (119,232 - (-119,232))/(9999 - 0) + (-119,232) = -107,307kW
4. Power Factor readings

Power factor engineering scales (see Section 3.3):


HI_ENG = 1.000.
LO_ENG = -1.000.
If the raw data reading is 8900 then the power factor in engineering units will be as follows:
Power factor reading = 8900 (1.000 - (-1.000))/(9999 - 0) + (-1.000) = 0.78

2.7.2 32-bit Long Integer Format


32-bit long integer data is transmitted in two adjacent 16-bit Modbus registers as unsigned (UINT32)
or signed (INT32) whole numbers. The first register contains the low-order word (lower 16 bits) and
the second register contains the high order word (higher 16 bits). The low-order word always starts at
an even Modbus address. The value range for unsigned data is 0 to 4,294,967,295; for signed data the
range is -2,147,483,648 to 2,147,483,647.
If your Modbus driver does not support a 32-bit long integer format, you can read the two 16-bit
registers separately, and then convert them into a 32-bit value as follows (using C notation):
32-bit value = (signed short)high_order_register 65536L + (unsigned short)low_order_register

10

Examples
1. Unsigned 32-bit Values

If you read unsigned Voltage V1 of 69,000V from registers 13952-13953, then the register readings will be as follows:
(13952) = 3464
(13953) = 1
The 32-bit value is (1 x 65536 + 3464) = 69000V.
2. Signed 32-bit Values

If you read signed kW of -789kW from registers 14336-14337, then the register readings will be:
(14336) = 64747 (unsigned)
(14337) = 65535 (unsigned) or -1(signed value).
To take the high order register as a signed value, compare it with 32767. If the value is less or equal to 32767, use it as is.
If it is greater than 32767, then this is a negative number in a two's complement code (like in our example) - just subtract it
from 65536 to get the original negative value.
The 32-bit reading is (-1 x 65536 + 64747) = -789kW.

Fractional 32-bit data is transmitted using a decimal pre-multiplier to pass fractional numbers in an
integer format. Fractional numbers are pre-multiplied by 10 to the power N, where N is the number of
digits in the fractional part. For example, the frequency reading of 50.01 Hz is transmitted as 5001,
having been pre-multiplied by 100. Whenever a data register contains a fractional number, the register
measurement unit is given with a multiplier 0.1, 0.01 or 0.001, showing the weight of the least
significant decimal digit. To get an actual fractional number with specified precision, multiply the
register value by the given multiplier. To write a fractional number into the register, divide the number
by the given multiplier.
2.7.3 32-bit Floating Point Format
32-bit analog registers, energy registers and binary counters, and 32-bit Min/Max registers (see Sections
3.3-3.5) can be read in IEEE single precision floating point format in two adjacent 16-bit Modbus
registers, the low order register first.
The low-order register always starts at an even Modbus address.
2.7.4 32-bit Modulo-10000 Format
Energy counters 287-294 and 301-302 are read in two contiguous 16-bit registers in a modulo-10000
format. The first (low order) register contains the value mod 10000, and the second (high order)
register contains the value/10000. To get the true energy reading, the high order register value should
be multiplied by 10,000 and added to the low order register.

2.8 User Assignable Registers


The PM130 provides 120 user assignable registers in the address range of 0 to 119. You can re-map
any register available in the meter to any assignable register so that Modbus registers that reside at
different locations may be simply accessed using a single request by re-mapping them to adjacent
addresses. Refer to Configuring Modbus in the PM130 PLUS Installation and Operation Manual for
information on how to configure the assignable registers via PAS.
The actual addresses of the assignable registers, which are accessed via addresses 0 through 119, are
specified in the register map (registers 120 through 239), where register 120 contains the actual address
of the register accessed via register 0, register 121 contains the actual address of the register accessed
via register 1, and so on. The assignable registers and the map registers themselves may not be remapped.
Initially these registers are reserved and none of them points to an actual register address. To build
your own register map, write to map registers 120 to 239 the actual addresses you want to read from or
write to via the assignable area (registers 0 to 119). 32-bit long registers should always be aligned at

11

even addresses. For example, if you want to read registers 7136 (1-second V1 voltage, scaled short
integer) and 14720-14721 (kWh Import, long integer) via registers 0-2, do the following:
- write 14720 to register 120
- write 14721 to register 121
- write 7136 to register 122
Reading from registers 0-2 will return the kWh reading in registers 0 (low 16 bits) and 1 (high 16 bits),
and the voltage reading in register 2.

2.9 Password Protection


The PM130 has a password protection option allowing you to protect your setups, cumulative registers
and logs from being changed or cleared through communications. You can disable or enable password
protection through communications or via the front display. For details, refer to your instrument
Installation and Operation Manual. When password protection is enabled, the user password you set in
your instrument should be written into the device authorization register (2575) before another write
request is issued. If the correct password is not supplied while password protection is enabled, the
instrument will respond to all write requests with the exception code 01 (illegal operation). It is
recommended to clear the password register after you have completed your changes in order to activate
password protection.

12

3 Modbus Register Map


3.1 Modbus Setup Registers
Address
Point ID Description
Assignable Modbus Registers
0-119
+0
Register 0 contents
+1
Register 1 contents
...
+119
Register 119 contents
Assignable Registers Map
120-239
+0
Mapped register 0 address
+1
Mapped register 1 address

Options/Range

+119
Mapped register 119 address
Modbus Conversion Scales
240
Low raw scale
241
High raw scale
Device Data Scales
242
Voltage scale, secondary volts
243
Current scale, secondary amps
244-245
Reserved
32-bit Register Type
246
Type of 32-bit registers

Type

R/W

0-65535
0-65535

UINT16
UINT16

R/W
R/W

0-65535

UINT16

R/W

0-65535
0-65535

UINT16
UINT16

R/W
R/W

0-65535

UINT16

R/W

0
9999

UINT16
UINT16

R
R

UINT16
UINT16
UINT16

R/W
R/W
R

Default 144V
Default 2CT secondary

UINT16

R/W

Default 0

60-828
10-100
0
Bits 0-1 - analog values:
0 = 32-bit integer
1 = 32-bit floating point
Bits 2-3 - binary counters:
0 = 32-bit integer
1 = 32-bit floating point
Bit 4-5 - energy counters:
0 = 32-bit integer
1 = 32-bit floating point

Units

1V
0.1A

Notes

13

3.2 16-bit Scaled Analog Registers and Energy Counters - Basic Register Set
Address

256-308
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
+17
+18
+19
+20
+21
+22
+23
+24
+25
+26
+27
+28
+29
+30
+31
+32
+33
+34
+35
+36
+37

Point ID

Description

Low and High Scales

Units

Type

R/W

Notes

0x1100
0x1101
0x1102
0x1103
0x1104
0x1105
0x1106
0x1107
0x1108
0x1109
0x110A
0x110B
0x110C
0x110D
0x110E
0x110F
0x1110
0x1111
0x1403
0x1400
0x1401
0x1402
0x1501
0x1502
0x3709
0x160F
0x370B
0x1611
0x3703
0x3704
0x3705

V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
kW L1
kW L2
kW L3
kvar L1
kvar L2
kvar L3
kVA L1
kVA L2
kVA L3
Power factor L1
Power factor L2
Power factor L3
Total PF
Total kW
Total kvar
Total kVA
In (neutral) Current
Frequency
Maximum kW import sliding window demand
kW import accumulated demand
Maximum kVA sliding window demand
kVA accumulated demand
I1 Maximum ampere demand
I2 Maximum ampere demand
I3 Maximum ampere demand
kWh import (low)
kWh import (high)
kWh export (low)
kWh export (high)
+kvarh net (low)
+kvarh net (high)
-kvarh net (low)

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-1.000-1.000
-1.000-1.000
-1.000-1.000
-1.000-1.000
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
0-Imax
45.00-65.00
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
0-Imax
0-Imax
0-Imax
0-9999
0-9999
0-9999
0-9999
0-9999
0-9999
0-9999

U1
U1
U1
U2
U2
U2
U3
U3
U3
U3
U3
U3
U3
U3
U3
0.001
0.001
0.001
0.001
U3
U3
U3
U2
0.01Hz
U3
U3
U3
U3
U2
U2
U2
1kWh
10MWh
1kWh
10MWh
1kvarh
10Mvarh
1kvarh

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
INT16
INT16
INT16
INT16
INT16
INT16
UINT16
UINT16
UINT16
INT16
INT16
INT16
INT16
INT16
INT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

1
1
1

5
5
5
5
3, 5
3, 5
4, 5

14

Address

Point ID

+38
+39
+40
+41
+42
+43
+44
+45
+46
+47
+48
+49
+50
+51
+52

0x1112
0x1113
0x1114
0x1115
0x1116
0x1117

0x1609
0x160B
0x1615
0x111B
0x111C
0x111D

Description

-kvarh net (high)


V1/V12 Voltage THD
V2/V23 Voltage THD
V3/V31 Voltage THD
I1 Current THD
I2 Current THD
I3 Current THD
kVAh (low)
kVAh (high)
Present kW import sliding window demand
Present kVA sliding window demand
PF (import) at Max. kVA sliding window demand
I1 Current TDD
I2 Current TDD
I3 Current TDD

Low and High Scales


0-9999
0-999.9
0-999.9
0-999.9
0-999.9
0-999.9
0-999.9
0-9999
0-9999
-Pmax-Pmax
-Pmax-Pmax
0-1.000
0-100.0
0-100.0
0-100.0

Units
10Mvarh
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
1kVAh
10MVAh
U3
U3
0.001
0.1%
0.1%
0.1%

Type

R/W

Notes

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

4, 5

3-sec value
3-sec value
1 3-sec value
3-sec value
3-sec value
3-sec value
1
1

5
5

3-sec value
3-sec value
3-sec value

NOTES:

Energy, power demand and total harmonics readings are only available in the PM130EH meters.
1

Voltage and Voltage Harmonics Readings:


When the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages.

All analog registers except of harmonics are 1-second average values. For volts, amps and power scales and units, refer to Section 4 Data Scales and Units. For analog data scaling
formulas and examples, see Section 2.7.1, 16-bit Scaled Integer Format.

Positive readings of kvarh net

Negative readings of kvarh net

If you use these energy registers instead of 32-bit registers, limit the energy roll value to 8 digits to avoid overflow (see Device Options Setup).

15

3.3 16-bit Scaled Analog Registers, Binary Registers and Counters


Address

Point ID

6656 0x0000
6697 0x0101
6896
6976
7056-7063
+0,1
+2,3
+4,5
+6,7
7136-7168
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
+17
+18
+19
+20
+21
+22
+23
+24
+25
+26

0x0600
0x0800
0x0A00
0x0A01
0x0A02
0x0A03
0x0C00
0x0C01
0x0C02
0x0C03
0x0C04
0x0C05
0x0C06
0x0C07
0x0C08
0x0C09
0x0C0A
0x0C0B
0x0C0C
0x0C0D
0x0C0E
0x0C0F
0x0C10
0x0C11
0x0C12
0x0C13
0x0C14
0x0C15
0x0C16
0x0C17
0x0C18
0x0C19
0x0C1A

Description
None
Special Inputs
Phase rotation order
Digital Inputs (bitmap)
Relay Outputs (bitmap)
Counters
Counter #1
Counter #2
Counter #3
Counter #4
1-Cycle Phase Values
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
kW L1
kW L2
kW L3
kvar L1
kvar L2
kvar L3
kVA L1
kVA L2
kVA L3
Power factor L1
Power factor L2
Power factor L3
V1/V12 Voltage THD
V2/V23 Voltage THD
V3/V31 Voltage THD
I1 Current THD
I2 Current THD
I3 Current THD
I1 K-Factor
I2 K-Factor
I3 K-Factor

Low and High Scales


0

2, 4

Units

Type

R/W

UINT16

0=error, 1=positive (ABC),


2=negative (CBA)
0x0000-0x000F
0x0000-0x0003

UINT16

UINT16
UINT16

R
R

0-99,999
0-99,999
0-99,999
0-99,999

UINT32
UINT32
UINT32
UINT32

R/W
R/W
R/W
R/W

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
INT16
INT16
INT16
INT16
INT16
INT16
UINT16
UINT16
UINT16
INT16
INT16
INT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
0-Pmax
0-Pmax
0-Pmax
-1.000-1.000
-1.000-1.000
-1.000-1.000
0-999.9
0-999.9
0-999.9
0-999.9
0-999.9
0-999.9
1.0-999.9
1.0-999.9
1.0-999.9

U1
U1
U1
U2
U2
U2
U3
U3
U3
U3
U3
U3
U3
U3
U3
0.001
0.001
0.001
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1
0.1
0.1

Notes

1
1
1

2-cycle value
2-cycle value
1 2-cycle value
2-cycle value
2-cycle value
2-cycle value
2-cycle value
2-cycle value
2-cycle value
1
1

16

Address

+27
+28
+29
+30
+31
+32
7256-7359
+0
+1
+2
+3
+4
+5
+5
+7
+8
+9
+10
+11
+12
7296-7300
+0
+1
+2
+3
+4
7316-7331
+0
+1
+2
+3
+4
+5
+5
+7
+8
+9
+10
+11
+12
+13
+14
+15

Point ID

Description

0x0C1B
0x0C1C
0x0C1D
0x0C1E
0x0C1F
0x0C20

I1 Current TDD
I2 Current TDD
I3 Current TDD
V12 Voltage
V23 Voltage
V31 Voltage
1-Cycle Total Values
Total kW
Total kvar
Total kVA
Total PF
Total PF lag
Total PF lead
Total kW import
Total kW export
Total kvar import
Total kvar export
3-phase average L-N/L-L voltage
3-phase average L-L voltage
3-phase average current
1-Cycle Auxiliary Values
Not used
In (neutral) Current
Frequency
Voltage unbalance
Current unbalance
Phasor
V1/V12 Voltage magnitude
V2/V23 Voltage magnitude
V3/V31 Voltage magnitude
Not used
I1 Current magnitude
I2 Current magnitude
I3 Current magnitude
Not used
V1/V12 Voltage angle
V2/V23 Voltage angle
V3/V31 Voltage angle
Not used
I1 Current angle
I2 Current angle
I3 Current angle
Not used

0x0F00
0x0F01
0x0F02
0x0F03
0x0F04
0x0F05
0x0F06
0x0F07
0x0F08
0x0F09
0x0F0A
0x0F0B
0x0F0C
0x1000
0x1001
0x1002
0x1003
0x1004
0x1080
0x1081
0x1082
0x1083
0x1084
0x1085
0x1086
0x1087
0x1088
0x1089
0x108A
0x108B
0x108C
0x108D
0x108E
0x108F

2, 4

Low and High Scales


0-100.0
0-100.0
0-100.0
0-Vmax
0-Vmax
0-Vmax

Units
0.1%
0.1%
0.1%
U1
U1
U1

Type

R/W

Notes

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R
R
R
R
R
R

2-cycle value
2-cycle value
2-cycle value

-Pmax-Pmax
-Pmax-Pmax
0-Pmax
-1.000-1.000
0-1.000
0-1.000
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Vmax
0-Vmax
0-Imax

U3
U3
U3
0.001
0.001
0.001
U3
U3
U3
U3
U1
U1
U2

INT16
INT16
UINT16
INT16
UINT16
UINT16
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R
R

0-Imax
0-Fmax
0-300
0-300

U2
0.01Hz
%
%

UINT16
UINT16
UINT16
UINT16
UINT16

R
R
R
R
R

0-Vmax
0-Vmax
0-Vmax

U1
U1
U1

0-Imax
0-Imax
0-Imax

U2
U2
U2

-180.0-180.0
-180.0-180.0
-180.0-180.0

0.1
0.1
0.1

-180.0-180.0
-180.0-180.0
-180.0-180.0

0.1
0.1
0.1

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
INT16
INT16
INT16
INT16
INT16
INT16
INT16
INT16

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

1
1
1

1
1
1

17

Address

7336-7368
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
+17
+18
+19
+20
+21
+22
+23
+24
+25
+26
+27
+28
+29
+30
+31
+32
7456-7459
+0
+1
+2
+3
+4
+5
+5
+7

Point ID

0x1100
0x1101
0x1102
0x1103
0x1104
0x1105
0x1106
0x1107
0x1108
0x1109
0x110A
0x110B
0x110C
0x110D
0x110E
0x110F
0x1110
0x1111
0x1112
0x1113
0x1114
0x1115
0x1116
0x1117
0x1118
0x1119
0x111A
0x111B
0x111C
0x111D
0x111E
0x111F
0x1120
0x1400
0x1401
0x1402
0x1403
0x1404
0x1405
0x1406
0x1407

Description
1-Second Phase Values
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
kW L1
kW L2
kW L3
kvar L1
kvar L2
kvar L3
kVA L1
kVA L2
kVA L3
Power factor L1
Power factor L2
Power factor L3
V1/V12 Voltage THD
V2/V23 Voltage THD
V3/V31 Voltage THD
I1 Current THD
I2 Current THD
I3 Current THD
I1 K-Factor
I2 K-Factor
I3 K-Factor
I1 Current TDD
I2 Current TDD
I3 Current TDD
V12 Voltage
V23 Voltage
V31 Voltage
1-Second Total Values
Total kW
Total kvar
Total kVA
Total PF
Total PF lag
Total PF lead
Total kW import
Total kW export

2, 4

Low and High Scales

Units

Type

R/W

Notes

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
0-Pmax
0-Pmax
0-Pmax
-1.000-1.000
-1.000-1.000
-1.000-1.000
0-999.9
0-999.9
0-999.9
0-999.9
0-999.9
0-999.9
1.0-999.9
1.0-999.9
1.0-999.9
0-100.0
0-100.0
0-100.0
0-Vmax
0-Vmax
0-Vmax

U1
U1
U1
U2
U2
U2
U3
U3
U3
U3
U3
U3
U3
U3
U3
0.001
0.001
0.001
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1
0.1
0.1
0.1%
0.1%
0.1%
U1
U1
U1

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
INT16
INT16
INT16
INT16
INT16
INT16
UINT16
UINT16
UINT16
INT16
INT16
INT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

-Pmax-Pmax
-Pmax-Pmax
0-Pmax
-1.000-1.000
0-1.000
0-1.000
0-Pmax
0-Pmax

U3
U3
U3
0.001
0.001
0.001
U3
U3

INT16
INT16
UINT16
INT16
UINT16
UINT16
UINT32
UINT32

R
R
R
R
R
R
R
R

1
1

3-sec value
3-sec value
1 3-sec value
3-sec value
3-sec value
3-sec value
3-sec value
3-sec value
3-sec value
3-sec value
3-sec value
3-sec value
1
1

18

Address

+8
+9
+10
+11
+12
7496-7500
+0
+1
+2
+3
+4
7536-7565
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
+17
+18
+19
+20
+21
+22
+23
+24
+25
+26
+27
+28
+29
7576-7611

Point ID

Description

0x1408
0x1409
0x140A
0x140B
0x140C

Total kvar import


Total kvar export
3-phase average L-N/L-L voltage
3-phase average L-L voltage
3-phase average current
1-Second Auxiliary Values
Not used
In (neutral) Current
Frequency
Voltage unbalance
Current unbalance
Present Volt, Ampere and Power Demands
V1/V12 Volt demand
V2/V23 Volt demand
V3/V31 Volt demand
I1 Ampere demand
I2 Ampere demand
I3 Ampere demand
kW import block demand
kvar import block demand
kVA block demand
kW import sliding window demand
kvar import sliding window demand
kVA sliding window demand
Not used
Not used
Not used
kW import accumulated demand
kvar import accumulated demand
kVA accumulated demand
kW import predicted sliding window demand
kvar import predicted sliding window demand
kVA predicted sliding window demand
PF (import) at Max. kVA sliding window demand
kW export block demand
kvar export block demand
kW export sliding window demand
kvar export sliding window demand
kW export accumulated demand
kvar export accumulated demand
kW export predicted sliding window demand
kvar export predicted sliding window demand
Total Energies EH

0x1500
0x1501
0x1502
0x1503
0x1504
0x1600
0x1601
0x1602
0x1603
0x1604
0x1605
0x1606
0x1607
0x1608
0x1609
0x160A
0x160B
0x160C
0x160D
0x160E
0x160F
0x1610
0x1611
0x1612
0x1613
0x1614
0x1615
0x1616
0x1617
0x1618
0x1619
0x161A
0x161B
0x161C
0x161D

2, 4

Low and High Scales


0-Pmax
0-Pmax
0-Vmax
0-Vmax
0-Imax

Units
U3
U3
U1
U1
U2

0-Imax
0-Fmax
0-300
0-300

U2
0.01Hz
%
%

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax

U1
U1
U1
U2
U2
U2
U3
U3
U3
U3
U3
U3

0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-1.000
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3
U3
U3
0.001
U3
U3
U3
U3
U3
U3
U3
U3

Type

R/W

Notes

UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R

UINT16
UINT16
UINT16
UINT16
UINT16

R
R
R
R
R

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

1
1
1

19

Address

+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
+16,17
7616-7633
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
+16,17
7656-7695
+0
+1

Point ID

0x1700
0x1701

0x1704
0x1705

0x1708
0x1800
0x1801
0x1802
0x1803
0x1804
0x1805
0x1806
0x1807
0x1808
0x1900
0x1901

+39 0x1927
7696-7735
+0 0x1A00
+1 0x1A01
+39 0x1A27
7736-7775
+0 0x1B00
+1 0x1B01
+39 0x1B27
7776-7815
+0 0x1C00
+1 0x1C01
+39 0x1C27
7816-7855

Description

kWh import
kWh export
Not used
Not used
kvarh import
kvarh export
Not used
Not used
kVAh total
Phase Energies EH
kWh import L1
kWh import L2
kWh import L3
kvarh import L1
kvarh import L2
kvarh import L3
kVAh total L1
kVAh total L2
kVAh total L3
V1/V12 Harmonic Distortion EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
V2/V23 Harmonic Distortion EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
V3/V31 Harmonic Distortion EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
I1 Harmonic Distortion EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
I2 Harmonic Distortion EH

2, 4

Type

R/W

1 kVAh

UINT32
UINT32
INT32
UINT32
UINT32
UINT32
INT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R

0-109-1
0-109-1
0-109-1
0-109-1
0-109-1
0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1
1
1
1
1
1

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R

0-100.00
0-100.00

0.01%
0.01%

UINT16
UINT16

R
R

0-100.00

0.01%

UINT16

0-100.00
0-100.00

0.01%
0.01%

UINT16
UINT16

R
R

0-100.00

0.01%

UINT16

0-100.00
0-100.00

0.01%
0.01%

UINT16
UINT16

R
R

0-100.00

0.01%

UINT16

0-100.00
0-100.00

0.01%
0.01%

UINT16
UINT16

R
R

0-100.00

0.01%

UINT16

Low and High Scales


0-109-1
0-109-1

Units
1 kWh
1 kWh

0-109-1
0-109-1

1 kvarh
1 kvarh

0-109-1

kWh
kWh
kWh
kvarh
kvarh
kvarh
kVAh
kVAh
kVAh

Notes

20

Address

Point ID

+0 0x1D00
+1 0x1D01
+39 0x1D27
7856-7895
+0 0x1E00
+1 0x1E01
+39
8296-8313
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
+17
8336-8343
+0
+1
+2
+3
8416-8445
+0
+1
+2
+3
+4
+5
8456-8459
+0

0x1E27
0x2900
0x2901
0x2902
0x2903
0x2904
0x2905
0x2906
0x2907
0x2908
0x2909
0x290A
0x290B
0x290C
0x290D
0x290E
0x290F
0x2910
0x2911
0x2A00
0x2A01
0x2A02
0x2A03
0x2C00
0x2C01
0x2C02
0x2C03
0x2C04
0x2C05
0x2D00

Description

H01 Harmonic distortion


H02 Harmonic distortion
...
H40 Harmonic distortion
I3 Harmonic Distortion EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
Fundamental Phase Values EH
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
kW L1
kW L2
kW L3
kvar L1
kvar L2
kvar L3
kVA L1
kVA L2
kVA L3
Power factor L1
Power factor L2
Power factor L3
Fundamental Total Values EH
Total fundamental kW
Total fundamental kvar
Total fundamental kVA
Total fundamental PF
Minimum 1-Cycle Phase Values
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
Minimum 1-Cycle Total Values
Total kW

2, 4

Low and High Scales


0-100.00
0-100.00

Units
0.01%
0.01%

Type

R/W

UINT16
UINT16

R
R

0-100.00

0.01%

UINT16

0-100.00
0-100.00

0.01%
0.01%

UINT16
UINT16

R
R

0-100.00

0.01%

UINT16

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
0-Pmax
0-Pmax
0-Pmax
-1.000-1.000
-1.000-1.000
-1.000-1.000

U1
U1
U1
U2
U2
U2
U3
U3
U3
U3
U3
U3
U3
U3
U3
0.001
0.001
0.001

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
INT16
INT16
INT16
INT16
INT16
INT16
UINT16
UINT16
UINT16
INT16
INT16
INT16

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

-Pmax-Pmax
-Pmax-Pmax
0-Pmax
-1.000-1.000

U3
U3
U3
0.001

INT16
INT16
UINT16
INT16

R
R
R
R

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax

U1
U1
U1
U2
U2
U2

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R
R
R
R
R
R

-Pmax-Pmax

U3

INT16

Notes

2-cycle values
1
1
1

2-cycle values

1
1
1

21

Address

+1
+2
+3
8496-8498
+0
+1
+2
8736-8765
+0
+1
+2
+3
+4
+5
8776-8779
+0
+1
+2
+3
881608818
+0
+1
+2
8856-8872
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
9056-9057
+0

Point ID

Description

0x2D01
0x2D02
0x2D03

Total kvar
Total kVA
Total PF
Minimum 1-Cycle Auxiliary Values
Not used
In Current
Frequency
Maximum 1-Cycle Phase Values
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
Maximum 1-Cycle Total Values
Total kW
Total kvar
Total kVA
Total PF
Maximum 1-Cycle Auxiliary Values
Not used
In Current
Frequency
Maximum Demands
V1/V12 Maximum volt demand
V2/V23 Maximum volt demand
V3/V31 Maximum volt demand
I1 Maximum ampere demand
I2 Maximum ampere demand
I3 Maximum ampere demand
Not used
Not used
Not used
Maximum kW import sliding window demand
Maximum kvar import sliding window demand
Maximum kVA sliding window demand
Not used
Not used
Not used
Maximum kW export sliding window demand
Maximum kvar export sliding window demand
TOU Parameters EH
Active tariff

0x2E00
0x2E01
0x2E02
0x3400
0x3401
0x3402
0x3403
0x3404
0x3405
0x3500
0x3501
0x3502
0x3503
0x3600
0x3601
0x3602
0x3700
0x3701
0x3702
0x3703
0x3704
0x3705
0x3706
0x3707
0x3708
0x3709
0x370A
0x370B
0x370C
0x370D
0x370E
0x370F
0x3710
0x3C00

2, 4

Low and High Scales


-Pmax-Pmax
0-Pmax
0-1.000

Units
U3
U3
0.001

Type

R/W

Notes

INT16
UINT16
UINT16

R
R
R

Absolute value

0-Imax
0-Fmax

U2
U2
0.01Hz

UINT16
UINT16
UINT16

R
R
R

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax

U1
U1
U1
U2
U2
U2

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R
R
R
R
R
R

-Pmax-Pmax
-Pmax-Pmax
0-Pmax
0-1.000

U3
U3
U3
0.001

INT16
INT16
UINT16
UINT16

R
R
R
R

0-Imax
0-Fmax

U2
U2
0.01Hz

UINT16
UINT16
UINT16

R
R
R

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax

U1
U1
U1
U2
U2
U2

0-Pmax
0-Pmax
0-Pmax

U3
U3
U3

0-Pmax
0-Pmax

U3
U3

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

UINT16

R/W

0-7

1
1
1

Absolute value

1
1
1

22

Address

Point ID

+1 0x3C01

9076-9079
+0
+1
+2
+3
9096-9103
+0,1
+2,3
+4,5
+6,7
9136-9143
+0,1
+2,3
+4,5
+6,7
9176-9183
+0,1
+2,3
+4,5
+6,7
9216-9223
+0,1
+2,3
+4,5
+6,7
9416-9419
+0
+1
+2
+3
9436-9439
+0
+1
+2
+3
9456-9459

0x3C80
0x3C81
0x3C82
0x3C83
0x3D00
0x3D01
0x3D02
0x3D03
0x3E00
0x3E01
0x3E02
0x3E03
0x3F00
0x3F01
0x3F02
0x3F03
0x4000
0x4001
0x4002
0x4003
0x4500
0x4501
0x4502
0x4503
0x4580
0x4581
0x4582
0x4583

Description

Active profile

Scaled Analog Outputs


Analog output AO1
Analog output AO2
Analog output AO3
Analog output AO4
TOU Energy Register #1 EH
Tariff #1 register
Tariff #2 register
Tariff #3 register
Tariff #4 register
TOU Energy Register #2 EH
Tariff #1 register
Tariff #2 register
Tariff #3 register
Tariff #4 register
TOU Energy Register #3 EH
Tariff #1 register
Tariff #2 register
Tariff #3 register
Tariff #4 register
TOU Energy Register #4 EH
Tariff #1 register
Tariff #2 register
Tariff #3 register
Tariff #4 register
Summary Energy Accumulated Demands EH
Summary register #1 demand
Summary register #2 demand
Summary register #3 demand
Summary register #4 demand
Summary Energy Block Demands EH
Summary register #1 demand
Summary register #2 demand
Summary register #3 demand
Summary register #4 demand
Summary Energy Sliding Window Demands EH

Low and High Scales


0-15:
0-3 = Season 1 Profile #1-4,
4-7 = Season 2 Profile #1-4,
8-11 = Season 3 Profile #1-4,
12-15 = Season 4 Profile #1-4

2, 4

Units

0-4095
0-4095
0-4095
0-4095

Type

R/W

UINT16

R/W

UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W

0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1

kWh
kWh
kWh
kWh

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1

kWh
kWh
kWh
kWh

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1

kWh
kWh
kWh
kWh

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1

kWh
kWh
kWh
kWh

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT16
UINT16
UINT16
UINT16

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT16
UINT16
UINT16
UINT16

R
R
R
R

Notes

23

Address

Point ID

+0
+1
+2
+3
9516-9519
+0
+1
+2
+3
9536-9539
+0
+1
+2
+3
9576-9579
+0
+1
+2
+3
9616-9619
+0
+1
+2
+3
9556-9559
+0
+1
+2
+3
10656-10695
+0
+1

0x4600
0x4601
0x4602
0x4603
0x4780
0x4781
0x4782
0x4783
0x4800
0x4801
0x4802
0x4803
0x4900
0x4901
0x4902
0x4903
0x4A00
0x4A01
0x4A02
0x4A03
0x4880
0x4881
0x4882
0x4883
0x6400
0x6400

+39 0x6427
10696-10735
+0 0x6500
+1 0x6500
+39 0x6527

Description

Summary register #1 demand


Summary register #2 demand
Summary register #3 demand
Summary register #4 demand
Summary Energy Maximum Demands EH
Summary register #1 maximum demand
Summary register #2 maximum demand
Summary register #3 maximum demand
Summary register #4 maximum demand
TOU Maximum Demand Register #1 EH
Tariff #1 maximum demand
Tariff #2 maximum demand
Tariff #3 maximum demand
Tariff #4 maximum demand
TOU Maximum Demand Register #2 EH
Tariff #1 maximum demand
Tariff #2 maximum demand
Tariff #3 maximum demand
Tariff #4 maximum demand
TOU Maximum Demand Register #3 EH
Tariff #1 maximum demand
Tariff #2 maximum demand
Tariff #3 maximum demand
Tariff #4 maximum demand
TOU Maximum Demand Register #4 EH
Tariff #1 maximum demand
Tariff #2 maximum demand
Tariff #3 maximum demand
Tariff #4 maximum demand
V1/V12 Harmonic Angles EH
H01 Harmonic angle
H02 Harmonic angle
...
H40 Harmonic angle
V2/V23 Harmonic Angles EH
H01 Harmonic angle
H02 Harmonic angle
...
H40 Harmonic angle

2, 4

Low and High Scales


0-Pmax
0-Pmax
0-Pmax
0-Pmax

Units
U3
U3
U3
U3

Type

R/W

UINT16
UINT16
UINT16
UINT16

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT16
UINT16
UINT16
UINT16

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT16
UINT16
UINT16
UINT16

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT16
UINT16
UINT16
UINT16

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT16
UINT16
UINT16
UINT16

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT16
UINT16
UINT16
UINT16

R
R
R
R

-180.0-180.0
-180.0-180.0

0.1
0.1

INT16
INT16

R
R

-180.0-180.0

0.1

INT16

-180.0-180.0
-180.0-180.0

0.1
0.1

INT16
INT16

R
R

-180.0-180.0

0.1

INT16

Notes

1, 3

1, 3

24

Address

Point ID

10736-10775
+0 0x6600
+1 0x6600
+39 0x6627
10816-10855
+0 0x6700
+1 0x6700
+39 0x6727
10856-10895
+0 0x6800
+1 0x6800
+39 0x6827
10896-10935
+0 0x6900
+1 0x6900
+39 0x6927
11616 0x7C00

Description
V1/V31 Harmonic Angles EH
H01 Harmonic angle
H02 Harmonic angle
...
H40 Harmonic angle
I1 Harmonic Angles EH
H01 Harmonic angle
H02 Harmonic angle
...
H40 Harmonic angle
I2 Harmonic Angles EH
H01 Harmonic angle
H02 Harmonic angle
...
H40 Harmonic angle
I3 Harmonic Angles EH
H01 Harmonic angle
H02 Harmonic angle
...
H40 Harmonic angle
Setpoint Status (bitmap)

2, 4

Low and High Scales

Units

Type

R/W

-180.0-180.0
-180.0-180.0

0.1
0.1

INT16
INT16

R
R

-180.0-180.0

0.1

INT16

-180.0-180.0
-180.0-180.0

0.1
0.1

INT16
INT16

R
R

-180.0-180.0

0.1

INT16

-180.0-180.0
-180.0-180.0

0.1
0.1

INT16
INT16

R
R

-180.0-180.0

0.1

INT16

-180.0-180.0
-180.0-180.0

0.1
0.1

INT16
INT16

R
R

-180.0-180.0
0x0000-0xFFFF

0.1

INT16
UINT16

R
R

Notes
1, 3

NOTES:

Energy, power demand and harmonics readings are only available in the PM130EH meters.
1

Voltage and voltage harmonics readings:


When the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages.

For volts, amps, power and frequency scales and units refer to Section 4 Data Scales and Units. For analog data scaling formulas and examples, see Section 2.7.1, 16-bit Scaled Integer
Format.

Harmonic angles are referenced to the fundamental voltage harmonic H01 on phase L1.

The binary counters and energy registers can be read either as 32-bit integer, or 32-bit floating-point values. Refer to Section 2.7 for details.

25

3.4 32-bit Analog Registers, Binary Registers and Counters


Address

Point ID

11776-11777 0x0000

Description

11904-11905 0x0101

None
Special Inputs
Phase rotation order

12544-12545
12800-12801
13056-13063
+0,1
+2,3
+4,5
+6,7
13312-13377
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
+16,17
+18,19
+20,21
+22,23
+24,25
+26,27
+28,29
+30,31
+32,33
+34,35
+36,37
+38,39
+40,41
+42,43
+44,45
+46,47
+48,49
+50,51
+52,53

Digital Inputs DI1-DI4 (bitmap)


Relay Outputs RO1-RO2 (bitmap)
Counters
Counter #1
Counter #2
Counter #3
Counter #4
1-Cycle Phase Values
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
kW L1
kW L2
kW L3
kvar L1
kvar L2
kvar L3
kVA L1
kVA L2
kVA L3
Power factor L1
Power factor L2
Power factor L3
V1/V12 Voltage THD
V2/V23 Voltage THD
V3/V31 Voltage THD
I1 Current THD
I2 Current THD
I3 Current THD
I1 K-Factor
I2 K-Factor
I3 K-Factor

0x0600
0x0800
0x0A00
0x0A01
0x0A02
0x0A03
0x0C00
0x0C01
0x0C02
0x0C03
0x0C04
0x0C05
0x0C06
0x0C07
0x0C08
0x0C09
0x0C0A
0x0C0B
0x0C0C
0x0C0D
0x0C0E
0x0C0F
0x0C10
0x0C11
0x0C12
0x0C13
0x0C14
0x0C15
0x0C16
0x0C17
0x0C18
0x0C19
0x0C1A

Options/Range
0

2, 4

Units

Type
UINT32

R/W

0=error, 1=positive (ABC),


2=negative (CBA)
0x00000000-0x0000000F
0x00000000-0x00000003

UINT32

UINT32
UINT32

R
R

0-99,999
0-99,999
0-99,999
0-99,999

UINT32
UINT32
UINT32
UINT32

R/W
R/W
R/W
R/W

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
INT32
INT32
INT32
INT32
INT32
INT32
UINT32
UINT32
UINT32
INT32
INT32
INT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
0-Pmax
0-Pmax
0-Pmax
-1000-1000
-1000-1000
-1000-1000
0-9999
0-9999
0-9999
0-9999
0-9999
0-9999
10-9999
10-9999
10-9999

U1
U1
U1
U2
U2
U2
U3
U3
U3
U3
U3
U3
U3
U3
U3
0.001
0.001
0.001
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1
0.1
0.1

Notes

1
1
1

2-cycle value
2-cycle value
1 2-cycle value
2-cycle value
2-cycle value
2-cycle value
2-cycle value
2-cycle value
2-cycle value
1
1

26

Address

+54,55
+56,57
+58,59
+60,61
+62,63
+64,65
13696-13721
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
+16,17
+18,19
+20,21
+22,23
+24,25
13824-13833
+0,1
+2,3
+4,5
+6,7
+8,9
13864-13895
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
+16,17
+18,19
+20,21
+22,23
+24,25
+26,27
+28,29
+30,31

Point ID

Description

0x0C1B
0x0C1C
0x0C1D
0x0C1E
0x0C1F
0x0C20

I1 Current TDD
I2 Current TDD
I3 Current TDD
V12 Voltage
V23 Voltage
V31 Voltage
1-Cycle Total Values
Total kW
Total kvar
Total kVA
Total PF
Total PF lag
Total PF lead
Total kW import
Total kW export
Total kvar import
Total kvar export
3-phase average L-N/L-L voltage
3-phase average L-L voltage
3-phase average current
1-Cycle Auxiliary Values
Not used
In (neutral) Current
Frequency
Voltage unbalance
Current unbalance
Phasor
V1/V12 Voltage magnitude
V2/V23 Voltage magnitude
V3/V31 Voltage magnitude
Not used
I1 Current magnitude
I2 Current magnitude
I3 Current magnitude
Not used
V1/V12 Voltage angle
V2/V23 Voltage angle
V3/V31 Voltage angle
Not used
I1 Current angle
I2 Current angle
I3 Current angle
Not used

0x0F00
0x0F01
0x0F02
0x0F03
0x0F04
0x0F05
0x0F06
0x0F07
0x0F08
0x0F09
0x0F0A
0x0F0B
0x0F0C
0x1000
0x1001
0x1002
0x1003
0x1004
0x1080
0x1081
0x1082
0x1083
0x1084
0x1085
0x1086
0x1087
0x1088
0x1089
0x108A
0x108B
0x108C
0x108D
0x108E
0x108F

2, 4

Units
0.1%
0.1%
0.1%
U1
U1
U1

Type
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R/W

Notes

R
R
R
R
R
R

2-cycle value
2-cycle value
2-cycle value

-Pmax-Pmax
-Pmax-Pmax
0-Pmax
-1000-1000
0-1000
0-1000
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Vmax
0-Vmax
0-Imax

U3
U3
U3
0.001
0.001
0.001
U3
U3
U3
U3
U1
U1
U2

INT32
INT32
UINT32
INT32
UINT16
UINT16
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R
R

0-Imax
0-Fmax
0-300
0-300

U2
0.01Hz
%
%

UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R

0-Vmax
0-Vmax
0-Vmax

U1
U1
U1

0-Imax
0-Imax
0-Imax

U2
U2
U2

-1800-1800
-1800-1800
-1800-1800

0.1
0.1
0.1

-1800-1800
-1800-1800
-1800-1800

0.1
0.1
0.1

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
INT32
INT32
INT32
INT32
INT32
INT32
INT32
INT32

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

Options/Range
0-1000
0-1000
0-1000
0-Vmax
0-Vmax
0-Vmax

1
1
1

1
1
1

27

Address

13952-14017
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
+16,17
+18,19
+20,21
+22,23
+24,25
+26,27
+28,29
+30,31
+32,33
+34,35
+36,37
+38,39
+40,41
+42,43
+44,45
+46,47
+48,49
+50,51
+52,53
+54,55
+56,57
+58,59
+60,61
+62,63
+64,65
14336-14361
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15

Point ID

0x1100
0x1101
0x1102
0x1103
0x1104
0x1105
0x1106
0x1107
0x1108
0x1109
0x110A
0x110B
0x110C
0x110D
0x110E
0x110F
0x1110
0x1111
0x1112
0x1113
0x1114
0x1115
0x1116
0x1117
0x1118
0x1119
0x111A
0x111B
0x111C
0x111D
0x111E
0x111F
0x1120
0x1400
0x1401
0x1402
0x1403
0x1404
0x1405
0x1406
0x1407

Description
1-Second Phase Values
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
kW L1
kW L2
kW L3
kvar L1
kvar L2
kvar L3
kVA L1
kVA L2
kVA L3
Power factor L1
Power factor L2
Power factor L3
V1/V12 Voltage THD
V2/V23 Voltage THD
V3/V31 Voltage THD
I1 Current THD
I2 Current THD
I3 Current THD
I1 K-Factor
I2 K-Factor
I3 K-Factor
I1 Current TDD
I2 Current TDD
I3 Current TDD
V12 Voltage
V23 Voltage
V31 Voltage
1-Second Total Values
Total kW
Total kvar
Total kVA
Total PF
Total PF lag
Total PF lead
Total kW import
Total kW export

Options/Range

2, 4

R/W

Notes

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
INT32
INT32
INT32
INT32
INT32
INT32
UINT32
UINT32
UINT32
INT32
INT32
INT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

INT32
INT32
UINT32
INT32
UINT16
UINT16
UINT32
UINT32

R
R
R
R
R
R
R
R

Units

Type

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
0-Pmax
0-Pmax
0-Pmax
-1000-1000
-1000-1000
-1000-1000
0-9999
0-9999
0-9999
0-9999
0-9999
0-9999
10-9999
10-9999
10-9999
0-1000
0-1000
0-1000
0-Vmax
0-Vmax
0-Vmax

U1
U1
U1
U2
U2
U2
U3
U3
U3
U3
U3
U3
U3
U3
U3
0.001
0.001
0.001
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1
0.1
0.1
0.1%
0.1%
0.1%
U1
U1
U1

-Pmax-Pmax
-Pmax-Pmax
0-Pmax
-1000-1000
0-1000
0-1000
0-Pmax
0-Pmax

U3
U3
U3
0.001
0.001
0.001
U3
U3

1
1

3-sec value
3-sec value
1 3-sec value
3-sec value
3-sec value
3-sec value
3-sec value
3-sec value
3-sec value
3-sec value
3-sec value
3-sec value
1
1

28

Address

+16,17
+18,19
+20,21
+22,23
+24,25
14464-14473
+0,1
+2,3
+4,5
+6,7
+8,9
14592-14651
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
+16,17
+18,19
+20,21
+22,23
+24,25
+26,27
+28,29
+30,31
+32,33
+34,35
+36,37
+38,39
+40,41
+42,43
+44,45
+46,47
+48,49
+50,51
+52,53
+54,55
+56,57
+58,59
14720-14755

Point ID

Description

0x1408
0x1409
0x140A
0x140B
0x140C

Total kvar import


Total kvar export
3-phase average L-N/L-L voltage
3-phase average L-L voltage
3-phase average current
1-Second Auxiliary Values
Not used
In (neutral) Current
Frequency
Voltage unbalance
Current unbalance
Present Volt, Ampere and Power Demands
V1/V12 Volt demand
V2/V23 Volt demand
V3/V31 Volt demand
I1 Ampere demand
I2 Ampere demand
I3 Ampere demand
kW import block demand
kvar import block demand
kVA block demand
kW import sliding window demand
kvar import sliding window demand
kVA sliding window demand
Not used
Not used
Not used
kW import accumulated demand
kvar import accumulated demand
kVA accumulated demand
kW import predicted sliding window demand
kvar import predicted sliding window demand
kVA predicted sliding window demand
PF (import) at Max. kVA sliding window demand
kW export block demand
kvar export block demand
kW export sliding window demand
kvar export sliding window demand
kW export accumulated demand
kvar export accumulated demand
kW export predicted sliding window demand
kvar export predicted sliding window demand
Total Energies EH

0x1500
0x1501
0x1502
0x1503
0x1504
0x1600
0x1601
0x1602
0x1603
0x1604
0x1605
0x1606
0x1607
0x1608
0x1609
0x160A
0x160B
0x160C
0x160D
0x160E
0x160F
0x1610
0x1611
0x1612
0x1613
0x1614
0x1615
0x1616
0x1617
0x1618
0x1619
0x161A
0x161B
0x161C
0x161D

2, 4

Units
U3
U3
U1
U1
U2

Type
UINT32
UINT32
UINT32
UINT32
UINT32

R/W

Notes

R
R
R
R
R

0-Imax
0-Fmax
0-300
0-300

U2
0.01Hz
%
%

UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax

U1
U1
U1
U2
U2
U2
U3
U3
U3
U3
U3
U3

0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-1000
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3
U3
U3
0.001
U3
U3
U3
U3
U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

Options/Range
0-Pmax
0-Pmax
0-Vmax
0-Vmax
0-Imax

1
1
1

29

Address

+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
+16,17
14760-14767
+0,1
+2,3
+4,5
+6,7
14848-14865
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
+16,17
14976-15055
+0,1
+2,3

Point ID

0x1700
0x1701
0x1702
0x1703
0x1704
0x1705
0x1706
0x1707
0x1708
0x1780
0x1781
0x1782
0x1783
0x1800
0x1801
0x1802
0x1803
0x1804
0x1805
0x1806
0x1807
0x1808
0x1900
0x1901

+78,79 0x1927
15104-15183
+0,1 0x1A00
+2,3 0x1A01
+78,79 0x1A27
15232-15311
+0,1 0x1B00
+2,3 0x1B01
+78,79 0x1B27
15360-15439

Description

kWh import
kWh export
Not used
Not used
kvarh import
kvarh export
Not used
Not used
kVAh total
Summary Energy Registers EH
Summary energy register #1
Summary energy register #2
Summary energy register #3
Summary energy register #4
Phase Energies EH
kWh import L1
kWh import L2
kWh import L3
kvarh import L1
kvarh import L2
kvarh import L3
kVAh total L1
kVAh total L2
kVAh total L3
V1/V12 Harmonic Distortions EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
V2/V23 Harmonic Distortions EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
V3/V31 Harmonic Distortions EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
I1 Harmonic Distortions EH

Options/Range
0-109-1
0-109-1

2, 4

Units
1 kWh
1 kWh

R/W

0-109-1
0-109-1

1 kvarh
1 kvarh

0-109-1

1 kVAh

Type
UINT32
UINT32
INT32
UINT32
UINT32
UINT32
INT32
UINT32
UINT32

0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1

kWh
kWh
kWh
kWh

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-109-1
0-109-1
0-109-1
0-109-1
0-109-1
0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1
1
1
1
1
1

kWh
kWh
kWh
kvarh
kvarh
kvarh
kVAh
kVAh
kVAh

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R

0-10000
0-10000

0.01%
0.01%

UINT32
UINT32

R
R

0-10000

0.01%

UINT32

0-10000
0-10000

0.01%
0.01%

UINT32
UINT32

R
R

0-10000

0.01%

UINT32

0-10000
0-10000

0.01%
0.01%

UINT32
UINT32

R
R

0-10000

0.01%

UINT32

Notes

R
R
R
R
R
R
R
R
R

30

Address

Point ID

+0,1 0x1C00
+2,3 0x1C01
+78,79 0x1C27
15488-15567
+0,1 0x1D00
+2,3 0x1D01
+78,79 0x1D27
15616-15695
+0,1 0x1E00
+2,3 0x1E01
+78,79
17024-17059
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
+16,17
+18,19
+20,21
+22,23
+24,25
+26,27
+28,29
+30,31
+32,33
+34,35
17152-17164
+0,1
+2,3
+4,5
+6,7
17408-17467
+0,1
+2,3
+4,5

0x1E27
0x2900
0x2901
0x2902
0x2903
0x2904
0x2905
0x2906
0x2907
0x2908
0x2909
0x290A
0x290B
0x290C
0x290D
0x290E
0x290F
0x2910
0x2911
0x2A00
0x2A01
0x2A02
0x2A03
0x2C00
0x2C01
0x2C02

Description

H01 Harmonic distortion


H02 Harmonic distortion
...
H40 Harmonic distortion
I2 Harmonic Distortions EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
I3 Harmonic Distortions EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
Fundamental (H01) Phase Values EH
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
kW L1
kW L2
kW L3
kvar L1
kvar L2
kvar L3
kVA L1
kVA L2
kVA L3
Power factor L1
Power factor L2
Power factor L3
Harmonic Total Values EH
Total fundamental kW
Total fundamental kvar
Total fundamental kVA
Total fundamental PF
Minimum 1-Cycle Phase Values
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage

2, 4

Units
0.01%
0.01%

Type
UINT32
UINT32

R/W

0-10000

0.01%

UINT32

0-10000
0-10000

0.01%
0.01%

UINT32
UINT32

R
R

0-10000

0.01%

UINT32

0-10000
0-10000

0.01%
0.01%

UINT32
UINT32

R
R

0-10000

0.01%

UINT32

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
0-Pmax
0-Pmax
0-Pmax
-1000-1000
-1000-1000
-1000-1000

U1
U1
U1
U2
U2
U2
U3
U3
U3
U3
U3
U3
U3
U3
U3
0.001
0.001
0.001

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
INT32
INT32
INT32
INT32
INT32
INT32
UINT32
UINT32
UINT32
INT32
INT32
INT32

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

-Pmax-Pmax
-Pmax-Pmax
0-Pmax
-1000-1000

U3
U3
U3
0.001

INT32
INT32
UINT32
INT32

R
R
R
R

0-Vmax
0-Vmax
0-Vmax

U1
U1
U1

UINT32
UINT32
UINT32

R
R
R

Options/Range
0-10000
0-10000

Notes

R
R

2-cycle values
1
1
1

2-cycle values

1
1
1

31

Address

+6,7
+8,9
+10,11
17536-17543
+0,1
+2,3
+4,5
+6,7
17664-17669
+0,1
+2,3
+4,5
18432-18491
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
18560-18567
+0,1
+2,3
+4,5
+6,7
18688-18693
+0,1
+2,3
+4,5
18816-18849
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
+16,17
+18,19
+20,21
+22,23
+24,25
+26,27

Point ID

Description

0x2C03
0x2C04
0x2C05

I1 Current
I2 Current
I3 Current
Minimum 1-Cycle Total Values
Total kW
Total kvar
Total kVA
Total PF
Minimum 1-Cycle Auxiliary Values
Not used
In Current
Frequency
Maximum 1-Cycle Phase Values
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
Maximum 1-Cycle Total Values
Total kW
Total kvar
Total kVA
Total PF
Maximum 1-Cycle Auxiliary Values
Not used
In Current
Frequency
Maximum Demands
V1/V12 Maximum volt demand
V2/V23 Maximum volt demand
V3/V31 Maximum volt demand
I1 Maximum ampere demand
I2 Maximum ampere demand
I3 Maximum ampere demand
Not used
Not used
Not used
Maximum kW import sliding window demand
Maximum kvar import sliding window demand
Maximum kVA sliding window demand
Not used
Not used

0x2D00
0x2D01
0x2D02
0x2D03
0x2E00
0x2E01
0x2E02
0x3400
0x3401
0x3402
0x3403
0x3404
0x3405
0x3500
0x3501
0x3502
0x3503
0x3600
0x3601
0x3602
0x3700
0x3701
0x3702
0x3703
0x3704
0x3705
0x3706
0x3707
0x3708
0x3709
0x370A
0x370B
0x3737
0x370D

2, 4

Units
U2
U2
U2

Type
UINT32
UINT32
UINT32

R/W

-Pmax-Pmax
-Pmax-Pmax
0-Pmax
0-1000

U3
U3
U3
0.001

INT32
INT32
UINT32
UINT32

R
R
R
R

0-Imax
0-Fmax

U2
0.01Hz

UINT32
UINT32
UINT32

R
R
R

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax

U1
U1
U1
U2
U2
U2

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R

-Pmax-Pmax
-Pmax-Pmax
0-Pmax
0-1000

U3
U3
U3
0.001

INT32
INT32
UINT32
UINT32

R
R
R
R

0-Imax
0-Fmax

U2
0.01Hz

UINT32
UINT32
UINT32

R
R
R

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax

U1
U1
U1
U2
U2
U2

0-Pmax
0-Pmax
0-Pmax

U3
U3
U3

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R
R
R

Options/Range
0-Imax
0-Imax
0-Imax

Notes

R
R
R

Absolute value

1
1
1

Absolute value

1
1
1

32

Address

+28,29
+30,31
+32,33
19456-19459
+0,1
+2,3

19496-19503
+0,1
+2,3
+4,5
+6,7
19584-19591
+0,1
+2,3
+4,5
+6,7
19712-19719
+0,1
+2,3
+4,5
+6,7
19840-19847
+0,1
+2,3
+4,5
+6,7
19968-19975
+0,1
+2,3
+4,5
+6,7
20608-20615
+0,1
+2,3
+4,5
+6,7

Point ID

Description

0x370E
0x370F
0x3710

Not used
Maximum kW export sliding window demand
Maximum kvar export sliding window demand
TOU Parameters EH
Active tariff
Active profile

0x3C00
0x3C01

0x3C80
0x3C81
0x3C82
0x3C83
0x3D00
0x3D01
0x3D02
0x3D03
0x3E00
0x3E01
0x3E02
0x3E03
0x3F00
0x3F01
0x3F02
0x3F03
0x4000
0x4001
0x4002
0x4003
0x4500
0x4501
0x4502
0x4503

Scaled Analog Outputs


Analog output AO1
Analog output AO2
Analog output AO3
Analog output AO4
TOU Energy Register #1 EH
Tariff #1 register
Tariff #2 register
Tariff #3 register
Tariff #4 register
TOU Energy Register #2 EH
Tariff #1 register
Tariff #2 register
Tariff #3 register
Tariff #4 register
TOU Energy Register #3 EH
Tariff #1 register
Tariff #2 register
Tariff #3 register
Tariff #4 register
TOU Energy Register #4 EH
Tariff #1 register
Tariff #2 register
Tariff #3 register
Tariff #4 register
Summary Energy Accumulated Demands EH
Summary register #1 demand
Summary register #2 demand
Summary register #3 demand
Summary register #4 demand

2, 4

Type
UINT32
UINT32
UINT32

R/W

0-7
0-15:
1-3 = Season 1 Profile #1-4,
4-7 = Season 2 Profile #1-4,
8-11 = Season 3 Profile #1-4,
12-15 = Season 4 Profile #1-4

UINT32
UINT32

R
R

0-4095
0-4095
0-4095
0-4095

UINT32
UINT32
UINT32
UINT32

R/W
R/W
R/W
R/W

Options/Range

0-Pmax
0-Pmax

Units

U3
U3

Notes

R
R
R

0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1

kWh
kWh
kWh
kWh

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1

kWh
kWh
kWh
kWh

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1

kWh
kWh
kWh
kWh

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1

kWh
kWh
kWh
kWh

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

33

Address

20648-20655
+0,1
+2,3
+4,5
+6,7
20736-20743
+0,1
+2,3
+4,5
+6,7
20904-20911
+0,1
+2,3
+4,5
+6,7
20992-20999
+0,1
+2,3
+4,5
+6,7
21120-21127
+0,1
+2,3
+4,5
+6,7
21248-21255
+0,1
+2,3
+4,5
+6,7
21032-21039
+0,1
+2,3
+4,5
+6,7
24576-24655
+0,1
+2,3

Point ID

0x4580
0x4581
0x4582
0x4583
0x4600
0x4601
0x4602
0x4603
0x4780
0x4781
0x4782
0x4783
0x4800
0x4801
0x4802
0x4803
0x4900
0x4901
0x4902
0x4903
0x4A00
0x4A01
0x4A02
0x4A03
0x4880
0x4881
0x4882
0x4883
0x6400
0x6400

+78,79 0x6427

Description
Summary Energy Block Demands EH
Summary register #1 demand
Summary register #2 demand
Summary register #3 demand
Summary register #4 demand
Summary Energy Sliding Window Demands EH
Summary register #1 demand
Summary register #2 demand
Summary register #3 demand
Summary register #4 demand
Summary Energy Maximum Demands EH
Summary register #1 maximum demand
Summary register #2 maximum demand
Summary register #3 maximum demand
Summary register #4 maximum demand
TOU Maximum Demand Register #1 EH
Tariff #1 maximum demand
Tariff #2 maximum demand
Tariff #3 maximum demand
Tariff #4 maximum demand
TOU Maximum Demand Register #2 EH
Tariff #1 maximum demand
Tariff #2 maximum demand
Tariff #3 maximum demand
Tariff #4 maximum demand
TOU Maximum Demand Register #3 EH
Tariff #1 maximum demand
Tariff #2 maximum demand
Tariff #3 maximum demand
Tariff #4 maximum demand
TOU Maximum Demand Register #4 EH
Tariff #1 maximum demand
Tariff #2 maximum demand
Tariff #3 maximum demand
Tariff #4 maximum demand
V1/V12 Harmonic Angles EH
H01 Harmonic angle
H02 Harmonic angle
...
H40 Harmonic angle

Options/Range

2, 4

R/W

Units

Type

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

-1800-1800
-1800-1800

0.1
0.1

INT32
INT32

R
R

-1800-1800

0.1

INT32

Notes

1, 3

34

Address

Point ID

24704-24783
+0,1 0x6500
+2,3 0x6500
+78,79 0x6527
24832-24911
+0,1 0x6600
+2,3 0x6600
+78,79 0x6627
25088-25167
+0,1 0x6700
+2,3 0x6700
+78,79 0x6727
25216-25295
+0,1 0x6800
+2,3 0x6800
+78,79 0x6827
25344-25423
+0,1 0x6900
+2,3 0x6900
+78,79 0x6927
27648-27649 0x7C00

Description
V2/V23 Harmonic Angles EH
H01 Harmonic angle
H02 Harmonic angle
...
H40 Harmonic angle
V1/V31 Harmonic Angles EH
H01 Harmonic angle
H02 Harmonic angle
...
H40 Harmonic angle
I1 Harmonic Angles EH
H01 Harmonic angle
H02 Harmonic angle
...
H40 Harmonic angle
I2 Harmonic Angles EH
H01 Harmonic angle
H02 Harmonic angle
...
H40 Harmonic angle
I3 Harmonic Angles EH
H01 Harmonic angle
H02 Harmonic angle
...
H40 Harmonic angle
Setpoint Status SP1-SP16 (bitmap)

Options/Range

2, 4

R/W

Units

Type

-1800-1800
-1800-1800

0.1
0.1

INT32
INT32

R
R

-1800-1800

0.1

INT32

-1800-1800
-1800-1800

0.1
0.1

INT32
INT32

R
R

-1800-1800

0.1

INT32

-1800-1800
-1800-1800

0.1
0.1

INT32
INT32

R
R

-1800-1800

0.1

INT32

-1800-1800
-1800-1800

0.1
0.1

INT32
INT32

R
R

-1800-1800

0.1

INT32

-1800-1800
-1800-1800

0.1
0.1

INT32
INT32

R
R

-1800-1800
0x00000000-0x0000FFFF

0.1

INT32
UINT32

R
R

Notes
1, 3

1, 3

NOTES:

Energy, power demand and harmonics readings are only available in the PM130EH meters.
1

Voltage and voltage harmonics readings:


When the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages.

For volts, amps, power and frequency scales and units, refer to Section 4 Data Scales and Units.

Harmonic angles are referenced to the fundamental voltage harmonic H01 on phase L1.

The registers can be read as 32-bit integer or 32-bit floating-point values. Refer to Section 2.7 for details.

35

3.5 Minimum/Maximum Log Registers


Address

35840-35959
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
+16,17
+18,19
+20,21
+22,23
36096-36111
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
36352-36362
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
36864-36983
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
+16,17
+18,19

Point ID

0x2C00
0x2C01
0x2C02
0x2C03
0x2C04
0x2C05

0x2D00
0x2D01
0x2D02
0x2D03

0x2E00
0x2E01
0x2E02

0x3400
0x3401
0x3402
0x3403
0x3404

Description
Minimum Phase Values
Min. V1/V12 Voltage
Timestamp
Min. V2/V23 Voltage
Timestamp
Min. V3/V31 Voltage
Timestamp
Min. I1 Current
Timestamp
Min. I2 Current
Timestamp
Min. I3 Current
Timestamp
Minimum Total Values
Min. Total kW
Timestamp
Min. Total kvar
Timestamp
Min. Total kVA
Timestamp
Min. Total PF
Timestamp
Minimum Auxiliary Values
Not used

Min. In Current
Timestamp
Min. Frequency
Timestamp
Maximum Phase Values
Max. V1/V12 Voltage
Timestamp
Max. V2/V23 Voltage
Timestamp
Max. V3/V31 Voltage
Timestamp
Max. I1 Current
Timestamp
Max. I2 Current
Timestamp

Options/Range/Format

0-Vmax
F1
0-Vmax
F1
0-Vmax
F1
0-Imax
F1
0-Imax
0-Imax

-Pmax-Pmax
-Pmax-Pmax
0-Pmax
-1000-1000

0-Imax
0-Fmax

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax

2, 3

Units

Type

R/W

U1
sec
U1
sec
U1
sec
U2
sec
U2
sec
U2
sec

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R

U3
sec
U3
sec
U3
sec
0.001
sec

INT32
UINT32
INT32
UINT32
UINT32
UINT32
INT32
UINT32

R
R
R
R
R
R
R
R

U2
sec
0.01Hz
sec

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R

U1
sec
U1
sec
U1
sec
U2
sec
U2
sec

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R

Notes
1
1
1

1
1
1

36

Address

+20,21
+22,23
37120-37135
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
37376-37387
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
37504-37535
+0,1
+2,3
+4,5
+6,7
+12,13
+14,15
37632-37695
+0,1
+2,3
+4,5
+6,7
+8,9
+10,11
+12,13
+14,15
+16,17
+18,19
+20,21
+22,23
+24,25
+26,27
+28,29
+30,31

Point ID

0x3405

0x3500
0x3501
0x3502
0x3503

0x3600
0x3601
0x3602

0x4780
0x4781

0x4783

0x3700
0x3701
0x3702
0x3703
0x3704
0x3705
0x3706
0x3707

Description

Max. I3 Current
Timestamp
Maximum Total Values
Max. Total kW
Timestamp
Max. Total kvar
Timestamp
Max. Total kVA
Timestamp
Max. Total PF
Timestamp
Maximum Auxiliary Values
Not used
Max. In Current
Timestamp
Max. Frequency
Timestamp
Summary Energy Maximum Demands EH
Summary register #1 Maximum Demand
Timestamp
Summary register #2 Maximum Demand
Timestamp

Summary register #4 Maximum Demand


Timestamp
Maximum Demands
V1/V12 Maximum volt demand
Timestamp
V2/V23 Maximum volt demand
Timestamp
V3/V31 Maximum volt demand
Timestamp
I1 Maximum ampere demand
Timestamp
I2 Maximum ampere demand
Timestamp
I3 Maximum ampere demand
Timestamp
Not used
Timestamp
Not used
Timestamp

2, 3

Type

R/W

Options/Range/Format
0-Imax

Units
U2
sec

UINT32
UINT32

R
R

-Pmax-Pmax

U3
sec
U3
sec
U3
sec
0.001
sec

INT32
UINT32
INT32
UINT32
UINT32
UINT32
INT32
UINT32

R
R
R
R
R
R
R
R

U2
sec
0.01Hz
sec

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R

0-Pmax

U3

UINT32

0-Pmax

U3

UINT32

0-Pmax

U3

UINT32

0-Vmax

U1
sec
U1
sec
U1
sec
U2
sec
U2
sec
U2
sec

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

-Pmax-Pmax
0-Pmax
-1000-1000

0-Imax
0-Fmax

0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax

Notes

1
1
1

37

Address

+32,33
+34,35
+36,37
+38,39
+40,41
+42,43
+44,45
+46,47
+48,49
+50,51
+52,53
+54,55
+56,57
+58,59
+60,61
+62,63
+64,65
+66,67
38144-38159
+0,1
+2,3
+4,5
+6,7

Point ID

0x3708
0x3709
0x370A
0x370B
0x3737
0x370D
0x370E
0x370F
0x3710

0x4800
0x4801

+12,13 0x4803
+14,15
38400-38415
+0,1 0x4900
+2,3
+4,5 0x4901
+6,7
+12,13 0x4903
+14,15
38656-38671
+0,1 0x4A00
+2,3
+4,5 0x4A01
+6,7
+12,13 0x4A03
+14,15

Description

Not used
Timestamp
Maximum kW import sliding window demand
Timestamp
Maximum kvar import sliding window demand
Timestamp
Maximum kVA sliding window demand
Timestamp
Not used
Timestamp
Not used
Timestamp
Not used
Timestamp
Maximum kW export sliding window demand
Timestamp
Maximum kvar export sliding window demand
Timestamp
TOU Maximum Demand Register #1 EH
Tariff #1 maximum demand
Timestamp
Tariff #2 maximum demand
Timestamp

Tariff #4 maximum demand


Timestamp
TOU Maximum Demand Register #2 EH
Tariff #1 maximum demand
Timestamp
Tariff #2 maximum demand
Timestamp

Tariff #4 maximum demand


Timestamp
TOU Maximum Demand Register #3 EH
Tariff #1 maximum demand
Timestamp
Tariff #2 maximum demand
Timestamp

Tariff #4 maximum demand


Timestamp

Options/Range/Format

2, 3

Units

Type

R/W

U3
sec
U3
sec

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

U3
sec
U3
sec

UINT32
UINT32
UINT32
UINT32

0-Pmax

U3
sec

UINT32
UINT32

R
R
R
R
R
R
R

0-Pmax

U3
sec
U3
sec

UINT32
UINT32
UINT32
UINT32

0-Pmax

U3
sec

UINT32
UINT32

0-Pmax

U3
sec
U3
sec

UINT32
UINT32
UINT32
UINT32

U3
sec

UINT32
UINT32

0-Pmax
0-Pmax
0-Pmax

0-Pmax
0-Pmax

0-Pmax
0-Pmax

0-Pmax

0-Pmax

0-Pmax

U3
sec
U3
sec
U3
sec

Notes

R
R
R
R
R
R
R
R
R
R
R
R
R
R

38

Address

Point ID

38272-38287
+0,1 0x4880
+2,3
+4,5 0x4881
+6,7
+12,13 0x4883
+14,15

Description
TOU Maximum Demand Register #4 EH
Tariff #1 maximum demand
Timestamp
Tariff #2 maximum demand
Timestamp

Tariff #4 maximum demand


Timestamp

Options/Range/Format

0-Pmax
0-Pmax

0-Pmax

2, 3

Units

Type

U3
sec
U3
sec

UINT32
UINT32
UINT32
UINT32

U3
sec

UINT32
UINT32

R/W

Notes

R
R
R
R
R
R
R

NOTES:

Power demand readings are only available in the PM130EH meters.


1

Voltage and Voltage Harmonics readings:


When the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages.

For volts, amps, power and frequency scales and units, refer to Section 4 Data Scales and Units.

The Min/Max register values can be read as 32-bit integer or 32-bit floating-point values. Refer to Section 2.7 for details.

39

3.6 Device Control and Status Registers


Address
Point ID Description
Device Restart Register
2560
Warm restart of the device

Options/Range

Type

R/W

UINT16

R/W

INT16

R/W

INT32

R/W

UINT16

UINT16
UINT16

W
W

UINT16
UINT16
UINT16

W
W
W

UINT16

UINT16
UINT16
UINT16
UINT16

R
R
R
R

F28
0=COM1, 1=COM2

UINT32
UINT16

R
R

0x0000-0x0003

UINT16

0 when read,
0xFFFF when written = restart the
device

Device Authorization Registers


2575
When write: 4-digit password. When read: 0 = access 0-9999 (write)
permitted, -1 = authorization required.
0/-1 (read)
44378-44379
When write: 8-digit password. When read: 0 = access 0 - 99999999 (write)
permitted, -1 = authorization required.
0/-1 (read)
Remote Relay Control
3244-3245
+0
Remote relay command
0 = remove a remote command
1 = operate relay
2 = remove a remote command and
release a locally latched relay
3244
RO1 Control
3245
RO2 Control
Device Reset/Clear Registers
3404
Clear total energy registers
0
3405
Clear total maximum demand registers
0 = Clear all maximum demands
1 = Clear power demands EH
2 = Clear volt, ampere and
harmonic demands
3406
Clear TOU energy registers EH
0
3407
Clear TOU maximum demand registers EH
0
3408
Clear pulse counters
0 = Clear all counters
1-4 = Clear counter #1-#4
3409
Clear Min/Max log
0
Device Identification
2561-2562
Reserved
0
2563
Firmware build number
1-99
2564
Reserved
0
2565
Firmware version number
1300-1399,1500-1599(PM130P/E),
1400-1499,1600-1699 (PM130EH)

2566,2567
Instrument options
3484
Current serial port number
Device Status Registers
3452
Relay status RO1-RO2 (bitmap)

Units

Notes

Two higher decimal digits = major


version number, two lower decimal
digits = minor version number

Bits set to 1 indicate closed relay


contacts.

40

Address

3453
3454

Point ID

Description
Reserved
Digital (status) inputs DI1-DI4

Options/Range
0
0x0000-0x000F

3455

Present setpoint status SP1-SP16 (bitmap)

Alarm Notification Registers


3474
Setpoint alarm status SP1-SP16 (bitmap). Nonvolatile
register that keeps the status of the operated
setpoints.

3475

Self-check alarm status (device diagnostics).


Nonvolatile register that keeps the status of the
internal device diagnostics.

Units

Type
UINT16
UINT16

R/W
R
R

0x0000-0xFFFF

UINT16

0x0000-0xFFFF

UINT16

R/W

F23

UINT16

R/W

Notes

Bits set to 1 indicate closed input


contacts.
Bits set to 1 indicate operated
(activated) setpoints.
When read: Bits set to 1 indicate
that the designated setpoint have
been operated at least once since
the alarm bits were reset.
When written: Bits preset to 0 clear
corresponding alarms, Bits set to 1
have no effect.
When read: Bits set to 1 indicate
that the designated diagnostics
failed at least once since the alarm
bits were reset.
When written: Bits preset to 0 clear
corresponding alarms; bits set to 1
have no effect.

41

3.7 Device Setup Registers


Address
Point ID
Device Identification
46080-46111
+0,1
+2,3
+4-11
+12-13
+14-19
+20

+21
+22,23
+24
+25
+26-31
Factory Device Settings
46112-46125
+0
+1
+2,3
+4
+5
+6-13
Basic Setup
2304-2324
+0
+1
+2
+3

+4
+5-7
+8
+9,10

Description

Options/Range

Device serial number


Device model ID
Device model name
Device options (bitmap)
Reserved
Device firmware version number

0-999999
13010=PM130P, 13030=PM130EH
PM130P, PM130EH
0

Device firmware build number


Reserved
Boot loader version number

1-99

Boot loader build number


Reserved

1-99

V1-V3 input range


V1-V3 input overload
Reserved
I1-I3 input range
I1-I3 input overload
Reserved

690, 120 (option U)


120

V
%

1, 5
200

A
%

Wiring mode
PT ratio
CT primary current
Power block demand period

F2
10 to 65000
1 to 50,000
1,2,5,10,15,20,30,60 min,
255 = external synchronization

0.1
A
min

0 to 1800

sec

1100-1199 (PM130P/EH)

0101-0199

EH

Volt/ampere demand period


Reserved
Number of blocks in a sliding window
Reserved

Units

EH

1 to 15

Type

R/W

UINT32
UINT32
CHAR16
UINT32
UINT16
UINT16

R
R
R
R
R
R

UINT16
UINT16
UINT16

R
R
R

UINT16
UINT16

R
R

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R
R
R
R
R
R

UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W

UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W

Notes

Null-terminated string

Two higher decimal digits = major


version number, two lower decimal
digits = minor version number

Two higher decimal digits = major


version number, two lower decimal
digits = minor version number

Does not limit the 690V input range

If the external synchronization is


selected, the DI1 input is
considered a pulse or KYZ input.
The pulse edge restarts the power
demand block accumulation
interval. E
Read as 65535
E

Read as 65535

42

Address

Point ID Description
+11
Nominal line frequency
+12
Maximum demand load current
+13-19
Reserved
+20
PT ratio multiplication factor
Communication Ports Setup
2344-2359
+0
Communication protocol

+1

Interface

+2

Device address

+3

Baud rate

+4

Data format

+5

Flow control

+6

RTS mode

+7
2344-2351
2352-2359
Device Options Setup
2376-2386
+0
+1
+2
+3-9

Options/Range
25, 50, 60, 400
0 to 50,000 (0=CT primary current)

ASCII compatibility mode


COM1 Setup
COM2 Setup

Power calculation mode


Energy roll value

EH

Phase energy calculation mode


Reserved

Type
UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W
R/W

COM1: 0=SATEC ASCII, 1=Modbus


RTU, 2=DNP3.0
COM2: 0=SATEC ASCII, 1=Modbus
RTU, 2=DNP3.0, 5=Profibus DP
COM1: 2=RS-485
COM1: 0=RS-232, 1=RS-422,
2=RS-485, 6=Ethernet, 7=Profibus
SATEC ASCII: 0-99
Modbus RTU: 1-247
DNP3.0: 065532
Profibus DP: 0-126
1=300 bps, 2=600 bps, 3=1200
bps, 4=2400 bps, 5=4800 bps,
6=9600 bps, 7=19200 bps,
8=38400 bps, 9=57600 bps,
10=115200 bps
0=7 bits/even parity,
1=8 bits/no parity,
2=8 bits/even parity
0=no flow control
1=software (XON/XOFF)
2=hardware (CTS)
0=not used,
1=RTS is permanently asserted
2=RTS is asserted during the
transmission
0=disabled, 1=enabled

UINT16

R/W

UINT16

R/W

UINT16

R/W

UINT16

R/W

UINT16

R/W

UINT16

R/W

N/A for COM1 (read as 65535)

UINT16

R/W

N/A for COM1 (read as 65535)

UINT16

R/W

0=using reactive power: S=f(P,Q),


1=using non-active power:
Q=f(S,P)
0=1104, 1=1105, 2=1106,
3=1107, 4=1108, 5=1109
0=disabled, 1=enabled

UINT16

R/W

UINT16

R/W

Default 1108

UINT16
UINT16

R/W
R/W

Read as 65535

1, 10

EH

Units
Hz
A

Notes

Read as 65535

43

Address

Point ID

+10
+11
+12-13
+14
Local Settings
4320-4328
+0

Description
Energy LED test mode

EH

Starting voltage, percent of FS voltage


Reserved
Device resolution (see Section 4 for details)

Daylight savings time (DST) option

+1
+2

DST start month


DST start week of the month

+3
+4
+5

DST start weekday


DST end month
DST end week of the month

+6
+7

DST end weekday


Clock synchronization source

+8
Country code
Clock Indication and Setup
4352-4358
+0
Seconds
+1
Minutes
+2
Hour
+3
Day of month
+4
Month
+5
Year (calendar year minus 2000)
+6
Weekday
Alarm/Event Setpoints Setup
2576-2703
+0
Trigger parameter ID
+1
Action
+2
Operate delay
+3
Release delay
+4,5
Operate limit
+6,7
Release limit
2576-2583
Setpoint #1
2584-2591
Setpoint #2
2592-2599
Setpoint #3

Options/Range
Units
0=disabled, 1=Wh test, 2=varh test

Type
UINT16

R/W
R/W

15-50

UINT16
UINT16
UINT16

R/W
R/W
R/W

UINT16

R/W

UINT16
UINT16

R/W
R/W

UINT16
UINT16
UINT16

R/W
R/W
R/W

UINT16
UINT16

R/W
R/W

ITU calling number

UINT16

R/W

0-59
0-59
0-23
1-31
1-12
0-99
1-7 (1=Sun, 7=Sat)

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W
R/W
R/W
R/W

Ignored when written

F12
F14
0-9999
0-9999
See Section 3.3
See Section 3.3

UINT16
UINT16
UINT16
UINT16
UINT32
UINT32

R/W
R/W
R/W
R/W
R/W
R/W

Scaled value
Scaled value

0.1%

0 = Low resolution, 1 = High


resolution

0 = DST disabled (standard time


only), 1 = DST enabled
1-12
1-4 = 1st, 2nd, 3rd and 4th week,
5=the last week of the month
1-7 (1=Sun, 7=Sat)
1-12
1-4=1st, 2nd, 3rd and 4th week,
5=the last week of the month
1-7 (1=Sun, 7=Sat)
1-4 = DI1-DI4, 32767 = meter
clock

0.1 sec
0.1 sec

Notes
LED pulse rate is 10,000
pulses/kWh
Default 1.5%
Read as 65535
Default 0

A DI input is considered a pulse or


KYZ input. The pulse edge adjusts
the clock at the nearest whole
minute.

44

Address
Point ID
2600-2607
2608-2615
2616-2623
2624-2631
2632-2639
2640-2647
2648-2655
2656-2663
2664-2671
2672-2679
2680-2687
2688-2695
2696-2703
Pulse Counters Setup
2940-2947
+0

Description
Setpoint #4
Setpoint #5
Setpoint #6
Setpoint #7
Setpoint #8
Setpoint #9
Setpoint #10
Setpoint #11
Setpoint #12
Setpoint #13
Setpoint #14
Setpoint #15
Setpoint #16

Options/Range

Source digital input ID

+1
2940-2941
2942-2943
2944-2945
2946-2947
Analog Outputs Setup
3148-3153
+0
+1
+2
3148-3150
3151-3153
Digital Inputs Setup
3292-3296

Multiplier
Counter #1 Setup
Counter #2 Setup
Counter #3 Setup
Counter #4 Setup

+0
+1
+2
+3
+4
Network Setup
46576-46703
+0,1
+2,3

Output parameter ID
Zero scale value (0/4 mA)
Full scale value (1/20 mA)
AO1 Setup
AO2 Setup

Units

Type

R/W

0=not assigned, 1=DI1, 2=DI2,


3=DI3, 4=DI4
0-9999

UINT16

R/W

UINT16

R/W

F18
See Section 3.3
See Section 3.3

UINT16
UINT16
UINT16

R/W
R/W
R/W

Status inputs (bitmap)


Pulse inputs (bitmap)
Not used
External demand synchronization input (bitmap)
Time synchronization input (bitmap)

0x0003
0x0003
0
0x0001=DI1
0x0001=DI1, 0x0002=DI2,
0x0004=DI3, 0x0008=DI4

UINT16
UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W
R/W

Device IP Address
Network subnet mask

0x01000000-0xFFFFFFFF
0x00000001-0xFFFFFFFF

UINT32
UINT32

R/W
R/W

Notes

Scaled value
Scaled value

Obsolete registers. Refer to Digital


Inputs setup registers 61728-61735
Ignored when written
Ignored when written
Ignored when written

Network byte order


Network byte order

45

Address

Point ID

+4,5
+6,7
+8,9

Description
Network default gateway
Use DHCP
TCP service port

+10-127
Reserved
Password Setup
46704-46707
+0,1
Communications password (4 digits)
+2
Password protection enabled
+3
Reserved
Expert Power Service Setup
46768-46783
+0,1
Expert Power server IP Address
+2,3
Expert Power server TCP service port
+4,5
Expert Power client enabled
+6,7
Time to next session
Time to next session
+8,9
+10-15
Reserved
Internet Service Provider (ISP) accounts
46784-46879
+0-15
ISP telephone number
+16-31
Login name
+32-47
Login password
46784-46831
Account No.1
46832-46879
Account No.2
DNP Options Setup
51158-51183
+0
Binary Input Static Objects
+1
Reserved
+2
Binary Counter Objects
+3-5
Reserved
+6
Analog Input Objects
+7-10
Reserved
+11
16-bit BC Scaling
+12
+13-5
+16
+17
+18-21
+22,23

16-bit AI Scaling
Reserved
Select/Operate Timeout
Multi Fragment Interval
Reserved
Time Sync Period

Options/Range
0x00000000-0xFFFFFFFF
0 = NO, 1 = YES
502 = Modbus/TCP,
20000 = DNP3.0/TCP

Units

Type
UINT32
UINT32
UINT32

R/W
R/W
R/W
R/W

Notes
Network byte order

R/W

0-9999
0 = disabled, 1 = enabled

UINT32
UINT16
UINT16

R/W
R/W
R/W

Read as 0

0x01000000-0xFFFFFFFF
0-65535
0 = client disabled, 1 = client
enabled
1-99999
1-99999

UINT32
UINT32
UINT32

R/W
R/W
R/W

Default = 207.232.60.18
Default = 5001

UINT32
UINT32

R/W
R

CHAR32
CHAR32
CHAR32

R/W
R/W
R/W

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W
R/W
R/W
R/W

UINT16
UINT16
UINT16
UINT16
UINT16
UINT32

R/W
R/W
R/W
R/W
R/W
R/W

F24 (default 0)
F24 (default 3)
F24 (default 3)
0=1 (default), 1=10, 2=100,
3=1000
0 scaling OFF, 1-scaling ON
2 to 30 seconds (default 10 sec)
50 to 500 ms (default 50 ms)
Read as 65535
0 to 86400 seconds (default 86400

min
min

Same as previous

46

Address

Point ID

Description

+24
Voltage scale, secondary volts
+25
Current scale, secondary amps
51184-51189
Reserved
DNP Class 0 Point Assignments
51702-51797
+0
DNP object and variation
+1
DNP point number
+2
Number of points
DNP Class 0 Points Range 1
51702-51704
DNP Class 0 Points Range 2
51705-51707

51795-51797
DNP Class 0 Points Range 32
51798-51893
Reserved
TOU Daily Profile Setup EH
55574-55701
+0
1st tariff change
+1
2nd tariff change
+2
3rd tariff change
+3
4th tariff change
+4
5th tariff change
+5
6th tariff change
+6
7th tariff change
+7
8th tariff change
55574-55581
Daily profile #1: Season 1, Day type 1
55582-55589
Daily profile #2: Season 1, Day type 2
55590-55597
Daily profile #3: Season 1, Day type 3
55598-55605
Daily profile #4: Season 1, Day type 4
55606-55613
Daily profile #5: Season 2, Day type 1
55614-55621
Daily profile #6: Season 2, Day type 2
55622-55629
Daily profile #7: Season 2, Day type 3
55630-55637
Daily profile #8: Season 2, Day type 4
55638-55645
Daily profile #9: Season 3, Day type 1
55646-55653
Daily profile #10: Season 3, Day type 2
55654-55661
Daily profile #11: Season 3, Day type 3
55662-55669
Daily profile #12: Season 3, Day type 4
55670-55677
Daily profile #13: Season 4, Day type 1
55678-55685
Daily profile #14: Season 4, Day type 2
55686-55693
Daily profile #15: Season 4, Day type 3
55694-55701
Daily profile #16: Season 4, Day type 4
Reserved
55702-55711

Options/Range
sec)
60-828
10-100

Units

Type

R/W

V
0.1A

UINT16
UINT16

R/W
R/W

F25
Point number for the selected object
0-128

UINT16
UINT16
UINT16

R/W
R/W
R/W

F10
F10
F10
F10
F10
F10
F10
F10

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

Notes

47

Address
Point ID
TOU Calendar Setup EH
55712-56031
+0-9
+0

+1

Description

Calendar entry record


Daily profile

Week of month

+2
Weekday
+3
Till Weekday
+4
Month
+5
Day of month
+6
Till Month
+7
Till Day of month
+8-9
Reserved
55712-55721
Calendar entry #1
55722-55731
Calendar entry #2
55732-55741
Calendar entry #3

56022-56031
Calendar entry #32
56032-56191
Reserved
Summary Energy/TOU Registers Setup EH
56672-56703
+0
Not used
+1
Units of measurement

+2
Flags (bitmap)
+3
Not used
56672-56675
Register #1 Setup
56676-56679
Register #2 Setup
56680-56683
Register #3 Setup
56684-56687
Register #4 Setup
Summary Energy/TOU Registers Source Setup EH
56928-57183
+0
Energy source ID
+1
Target summary register number
+2,3
Multiplier
56928-56931
Energy Source #1
56932-56935
Energy Source #2
56936-56939
Energy Source #3
56940-56943
Energy Source #4

Options/Range

Units

0-3 = Season 1, Day types 0-3


4-7 = Season 2, Day types 0-3
8-11 = Season 3, Day types 0-3
12-15 = Season 4, Day types 0-3
0=all, 1=1st, 2=2nd, 3=3rd, 4=4th,
5=last week of the month
0=all, 1-7 (Sun=1, Sat=7)
0=all, 1-7 (Sun=1, Sat=7)
0=all, 1-12=January - December
0=all, 1-31=day 1-31
0=all, 1-12=January - December
0=all, 1-31=day 1-31

0=none, 1=kWh, 2=kvarh, 3=kVAh,


4=m3, 5=CF (cubic feet), 6=CCF
(hundred cubic feet)
Bit 0=1 - TOU enabled
0

F11
0-7 = register #1-#8
0-1000000

0.001

Type

R/W

UINT16

R/W
R/W

UINT16

R/W

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W
R/W
R/W
R/W

UINT16
UINT16

R/W
R/W

UINT16
UINT16

R/W
R/W

UINT16
UINT16
INT32

R/W
R/W
R/W

Notes

48

Address
Point ID
Digital Inputs Setup
61728-61743
+0
+1
+2

+3
61728-61731
61732-61735
61736-61739
61740-61743
Relay Outputs Setup
61984-61995
+0
+1
+2
+3
+4
+5
61984-61989
61990-61995
Analog Outputs Setup
62560-62571
+0
+1
+2,3
+4,5
62560-62565
62566-62571

Description

Options/Range

Pulse mode
Polarity
De-bounce time, ms

0 = pulse, 1 = KYZ
0 = normal, 1 = inverting
1-100

Units

Reserved
DI1 Setup
DI2 Setup
DI3 Setup
DI4 Setup

Operation Mode
Polarity
Pulse width, ms
Pulse source ID EH
Units per pulse
Reserved
RO1 Setup
RO2 Setup

Output parameter ID
Not used
Zero scale value (0/4 mA)
Full scale value (20/1 mA)
AO1 Setup
AO2 Setup

0=unlatched, 1=latched,
2=pulse, 3=KYZ
Bit 0 Polarity:
0=normal, 1=inverting
1-1000
F17
1-10000

F18
0
See Section 3.4
See Section 3.4

x0.1

Type

R/W

UINT16
UINT16
UINT16

R/W
R/W
R/W

UINT16

R/W

UINT16

R/W

UINT16

R/W

UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W

UINT16
UINT16
INT32
INT32

R/W
R/W
R/W
R/W

Notes

Debounce time will be the same for


both inputs

49

3.8 Analog and Digital I/O Configuration


Address
Point ID Description
I/O Slots Configuration Info
63008-63055
+0
I/O type
+1
Number of I/Os on the slot
+2
First I/O number on the slot
+3
Last I/O number on the slot
63008-63011
DI Slot Configuration
63012-63015
RO Slot Configuration
63016-63019
AI/AO Slot Configuration
63020-63055
Reserved
I/O Type Info
63056-63119
+0
Number of I/O slots of this type
+1
Total number of I/O's of this type
+2
Number of I/O's in the slot
+3
Not used
63056-63059
DI Type Info
63060-63063
RO Type Info
63064-63067
AI Type Info
63068-63071
AO Type Info
63076-63119
Reserved

Options/Range

Units

Type

R/W

F29
0-2
0
0-1

UINT16
UINT16
UINT16
UINT16

R
R
R
R

0-1
0-4
0-4
0

UINT16
UINT16
UINT16
UINT16

R
R
R
R

Notes

50

4 Data Scales and Units


Code
Data Scales
Vmax
Imax
Pmax

Condition

Wiring 4LN3, 3LN3, 3BLN3


Wiring 4LL3, 3LL3, 3BLL3,
3OP2, 3OP3, 3DIR2
Fmax
Nominal frequency 25, 50
or 60 Hz
Nominal frequency 400Hz
Data Units Low Resolution Option
U1
U2
U3
Data Units High Resolution Option
U1
PT Ratio = 1
PT Ratio > 1
U2
U3
PT Ratio = 1
PT Ratio > 1

Value/Range

Voltage scale PT Ratio, V


Current scale CT Ratio, A
Vmax Imax 3, W
Vmax Imax 2, W

Notes
2
1, 3
4

100 Hz
500 Hz
1V
1A
1kW/kvar/kVA
0.1V
1V
0.01A
1W/Var/VA
1kW/kvar/kVA

See Device Options Setup for information on selecting the device resolution option.
1 CT Ratio = CT primary current/CT secondary current
2 The default Voltage scale is 144V (120V +20%). You can change it via the Device Data Scale setup (see Section 3.1) or via

the Device Options setup in PAS.


3 The default Current scale is 2 CT secondary current (2.0A with 1A secondaries, 10.A with 5A secondaries). You can change

it via the Device Data Scale setup (see Section 3.1) or via the Device Options setup in PAS.

4 Pmax is rounded to whole kilowatts. With PT=1.0, if Pmax is greater than 9,999,000 W, it is truncated to 9,999,000 W.

51

5 Data Formats
Format Code
Timestamp
F1
Wiring Mode
F2

Value

Description

Notes

Local time in a UNIX-style format. Represents the number


of seconds since midnight (00:00:00), January 1, 1970.
The time is valid after January 1, 2000.
0
1
2
3
4
5
6
8
9

3OP2 - 3-wire open delta using 2 CTs (2 element)


4LN3 - 4-wire WYE using 3 PTs (3 element), line-toneutral voltage readings
3DIR2 - 3-wire direct connection using 2 CTs (2 element)
4LL3 - 4-wire WYE using 3 PTs (3 element), line-to-line
voltage readings
3OP3 - 3-wire open delta using 3 CTs (2 1/2 element)
3LN3 - 4-wire WYE using 2 PTs (2 1/2 element), line-toneutral voltage readings
3LL3 - 4-wire WYE using 2 PTs (2 1/2 element), line-toline voltage readings
3BLN3 - 3-wire broken delta using 2 PTs (2 1/2 element),
line-to-neutral voltage readings
3BLL3 - 3-wire broken delta using 2 PTs (2 1/2 element),
line-to-line voltage readings

TOU Tariff Change Time


F10
Bits 8:15 = 0-3
Tariff number #1-#4
Bits 2:7 = 0-23
Tariff start hour
Bits 0:1 = 0-3
Tariff start quarter of an hour
Summary/TOU Energy Register Source ID
F11
0x0000
None
0x0700-0x0703
Pulse input DI1-DI4
0x1700
kWh import
0x1701
kWh export
0x1704
kvarh import
0x1705
kvarh export
0x1708
kVAh total
Setpoint Trigger Parameters ID
F12
0x0000
None (condition is not active)
Status Inputs
0x0600
Status input #1 ON
0x0601
Status input #2 ON
0x0602
Status input #3 ON
0x0603
Status input #4 ON
0x8600
Status input #1 OFF
0x8601
Status input #2 OFF
0x8602
Status input #3 OFF
0x8603
Status input #4 OFF
Relays
0x0800
Relay #1 ON
0x0801
Relay #2 ON
0x8800
Relay #1 OFF
0x8801
Relay #2 OFF
Phase Reversal

0x8901
0x8902
0x0E00
0x8D00
0x0E01
0x8D01
0x0E07
0x0E08
0x0E09
0x0E0A
0x1002
0x9002
0x1003

Positive phase rotation reversal


Negative phase rotation reversal
1-Cycle Values on any Phase
High voltage
Low voltage
High current
Low current
High voltage THD EH
High current THD EH
High K-Factor EH
High current TDD EH
1-Cycle Auxiliary Values
High frequency
Low frequency
High voltage unbalance

2-cycle response
2-cycle response

2-cycle
2-cycle
2-cycle
2-cycle

values
values
values
values

52

Format Code

Value

0x1004
0x1103
0x1104
0x1105
0x9103
0x9104
0x9105
0x1300
0x9200
0x1301
0x9201
0x1406
0x1407
0x1408
0x1409
0x1402
0x9404
0x9405
0x1501
0x1502
0x9502
0x1600
0x1601
0x1602
0x1603
0x1604
0x1605
0x1606
0x1608
0x1609
0x160B
0x160F
0x1611
0x1612
0x1614
Setpoint Action ID
F14
Action type Target
0x00
0x00
0x30
0x00
0x30
0x01
0x31
0x00
0x31
0x01
0x40
0x00
0x40
0x01
0x40
0x02
0x40
0x03
0x44
0x00
0x44
0x01
0x44
0x02
0x44
0x03
Counter Source ID
F16
0x0000
0x0001-0x0004
Relay Output Pulse Source ID
F17
0x0000
0x0400
0x0401
0x0403
0x0404
0x0405
0x0406

Description
High current balance
1-Sec Phase Values
High I1 current
High I2 current
High I3 current
Low I1 current
Low I2 current
Low I3 current
1-Sec Values on any Phase
High voltage
Low voltage
High current
Low current
1-Sec Total Values
High total kW import
High total kW export
High total kvar import
High total kvar export
High total kVA
Low total PF Lag
Low total PF Lead
1-Sec Auxiliary Values
High neutral current
High frequency
Low frequency
Present Demands
High V1/V12 Volt demand
High V2/V23 Volt demand
High V3/V31 Volt demand
High I1 Ampere demand
High I2 Ampere demand
High I3 Ampere demand
High block kW import demand EH
High block kVA demand EH
High sliding window kW import demand EH
High sliding window kVA demand EH
High accumulated kW import demand EH
High accumulated kVA demand EH
High predicted kW import demand EH
High predicted kVA demand EH

No action
Operate Relay #1
Operate Relay #2
Release latched Relay #1
Release latched Relay #2
Increment counter #1
Increment counter #2
Increment counter #3
Increment counter #4
Count operating time using
Count operating time using
Count operating time using
Count operating time using

counter
counter
counter
counter

Notes

#1
#2
#3
#4

None
Pulse input DI1-DI4
None
kWh import pulse EH
kWh export pulse EH
kvarh import pulse EH
kvarh export pulse EH
kvarh total pulse EH
kVAh pulse EH

53

Format Code
Value
AO Parameters ID
F18
0x0000

0x0C00
0x0C01
0x0C02
0x0C03
0x0C04
0x0C05
0x0C1E
0x0C1F
0x0C20
0x0F00
0x0F01
0x0F02
0x0F03
0x0F04
0x0F05
0x1001
0x1002
0x1100
0x1101
0x1102
0x1103
0x1104
0x1105
0x111E
0x111F
0x1120
0x1400
0x1401
0x1402
0x1403
0x1404
0x1405
0x1501
0x1502
0x160F
0x1610
0x1611
0x161A
0x161B
Device Diagnostics
F23
Bit 0
Bit 1
Bit 2 = 1
Bit 3 = 1
Bit 4 = 1
Bit 5 = 1
Bit 6
Bit 7 = 1
Bit 8 = 1
Bit 9 = 1
Bit 10 = 1
Bit 11 = 1
Bit 12
Bit 13 = 1
Bit 14
Bit 15 = 1
DNP Object Types
F24

Description

None (output disabled)

Notes
2

1-Cycle Phase Values


V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
V12 Voltage
V23 Voltage
V31 Voltage
1-Cycle Total Values
Total kW
Total kvar
Total kVA
Total PF
Total PF Lag
Total PF Lead
1-Cycle Auxiliary Values
In Current
Frequency
1-Sec Phase Values
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
V12 Voltage
V23 Voltage
V31 Voltage
1-Sec Total Values
Total kW
Total kvar
Total kVA
Total PF
Total PF Lag
Total PF Lead
1-Sec Auxiliary Values
In Current
Frequency
Present Demands EH
Accumulated kW import demand
Accumulated kvar import demand
Accumulated kVA demand
Accumulated kW export demand
Accumulated kvar export demand

Reserved
Reserved
RAM/Data error
CPU watchdog reset
Sampling fault
CPU exception
Reserved
Software watchdog reset
Power down
Device reset
Configuration reset
RTC fault
Reserved
Low battery
Reserved
EEPROM fault
Static Binary Input Objects

54

Format Code

Value

0
1
0
1
2
3
0
1
2
3
DNP Class 0 Objects
F25
0x1E01
0x1E02
0x1E03
0x1E04
0x2801
0x2802
0x0101
0x0102
0x1401
0x1402
0x1405
0x1406
Instrument Options
F28
Bit 0=1
Bit 1=1
Bits 2-5
Bit 6=1
Bit 7=1
Bit 8=1
Bit 9=1
Bit 10=1
Bit 11=1
Bit 12=1
Bits 13-15
Bits 16-18
Bits 19-22
Bits 23-24
Bits 25-31
I/O Slot Types
F29
DI
RO
AI
AI
AI
AI
AO
AO
AO
AO
Empty slot

Description
Single-Bit Binary Input
Binary Input With Status
Static Binary Counters
32-bit Binary Counter
32-bit Binary Counter Without Flag
16-bit Binary Counter
16-bit Binary Counter Without Flag
Static Analog Input Objects
32-bit Analog Input
32-bit Analog Input Without Flag
16-bit Analog Input
16-bit Analog Input Without Flag

Notes

Analog Input 30:01


Analog Input 30:02
Analog Input 30:03
Analog Input 30:04
Analog Output 40:01
Analog Output 40:02
Binary Input 01:01
Binary Input 01:02
Binary Counter 20:01
Binary Counter 20:02
Binary Counter 20:05
Binary Counter 20:06
120V Option
690V Option
Reserved
Analog output 0/4 or 4/20mA
Analog output 0-1mA
Analog output 1mA
RO option
DI option
Reserved
Setup is secured by a password (authorization required)
Reserved
Number of RO - 1
Number of DI 1
Number of AO - 1
Reserved
DRY
1 mA
0-20 mA
4-20 mA
0-1 mA
1 mA
0-20 mA
4-20 mA
0-1 mA

00000000B
00100000B
01010000B
01010001B
01010010B
01010011B
01100000B
01100001B
01100010B
01100011B
11111111B

NOTES:
1

Analog Outputs

1) For bi-directional analog output (1 mA), the zero scale setup corresponds to the center (0 mA) of the scale range, and the
direction of the current matches the sign of the output parameter. Unsigned parameters are output within the current range 0
to +1 mA and can be scaled as in the case of single-ended analog output (0-1 mA).
For signed values, such as powers and signed power factor, the scale is always symmetrical with regard to 0 mA, and the full
scale corresponds to +1 mA output for positive readings and to -1 mA output for negative readings. The zero scale (0 mA
output) is permanently set in the instrument to zero for all parameters except the signed power factor for which it is set to
1.000 (see Note 2). In write requests, the zero scale is ignored.
2) Except for the signed power factor, the setup scale is continuous within the entire value range. For signed power factor, the
setup scale is broken at +1.000 in order to provide continuous output current when the power factor changes close to 1.000.

55

The setup scale is symmetrical in the range of -0 to +0 with a center at 1.000 (-1.000 is assumed to be equal to +1.000).
Negative power factor is output as -1.000 minus measured value, and non-negative power factor is output as +1.000 minus
measured value. To set the entire range for power factor from-0 to +0, the scales would be specified as -0 to 0. Because of the
fact that negative zero may not be transmitted through communications, the value of -0.001 is used to specify the scale of -0,
and both +0.001 and 0.000 are used to specify the scale of +0.
2

Phase Reversal Trigger

The setpoint is operated when the actual phase sequence does not match the designated phase rotation order.