Series PM130 PLUS Powermeters

SATEC ASCII Communications


Protocol

Reference Guide

BG0426 Rev. A1

Every effort has been made to ensure that the material herein is complete and accurate.
However, the manufacturer is not responsible for any mistakes in printing or faulty instructions
contained in this book. Notification of any errors or misprints will be received with
appreciation.
For further information regarding a particular installation, operation or maintenance of
equipment, contact the manufacturer or your local representative or distributor.

Table of Contents
1 GENERAL ..........................................................................................................6
2 ASCII PROTOCOL DESCRIPTION....................................................................7
2.1

ASCII FRAMING....................................................................................................................7

2.1.1 ASCII MESSAGE FRAME .........................................................................................................................7

2.2
2.3

EXCEPTION RESPONSES ..........................................................................................................8


PROTOCOL IMPLEMENTATION .........................................................................................8

2.3.1 ASCII SPECIFIC AND DIRECT REQUESTS ..................................................................................................8


2.3.2 DATA FORMATS ......................................................................................................................................9

2.4

DIRECT READ/WRITE REQUESTS.....................................................................................9

2.4.1
2.4.2
2.4.3
2.4.4

GENERAL ...............................................................................................................................................9
LONG-SIZE DIRECT READ/WRITE .............................................................................................................9
VARIABLE-SIZE DIRECT READ/WRITE .....................................................................................................10
USER ASSIGNABLE REGISTERS ..............................................................................................................10

2.5

PASSWORD PROTECTION .......................................................................................................11

3 SPECIFIC ASCII REQUESTS ..........................................................................12


3.1
3.2

BASIC DATA SET ....................................................................................................................12


DEVICE CONTROL AND STATUS ..............................................................................................13
Reset/Clear .......................................................................................................................................... 13
Warm Restart....................................................................................................................................... 14
Firmware Version ................................................................................................................................. 14
Device Status....................................................................................................................................... 14

3.3

DEVICE SETUP.......................................................................................................................14
Read Basic Setup ................................................................................................................................ 14
Write Basic Setup ................................................................................................................................ 14
Read Analog Output Setup .................................................................................................................. 14
Write Analog Output Setup .................................................................................................................. 15
Read Pulse Counter Setup .................................................................................................................. 15
Write Pulse Counter Setup................................................................................................................... 15
Read Clock Indication .......................................................................................................................... 15
Write Clock Setup ................................................................................................................................ 16

4 DIRECT READ/WRITE REQUESTS ................................................................17


4.1

PROTOCOL SETUP REGISTERS ...............................................................................................17


Assignable Registers ........................................................................................................................... 17
Assignable Registers Map ................................................................................................................... 17
Device Data Scales.............................................................................................................................. 17

4.2

ANALOG REGISTERS, BINARY REGISTERS AND COUNTERS ......................................................17


Special Inputs ...................................................................................................................................... 17
Digital Inputs DI1-DI4 (bitmap) ............................................................................................................. 17
Relay Outputs RO1-RO2 (bitmap) ....................................................................................................... 17
Counters .............................................................................................................................................. 17
1-Cycle Phase Values.......................................................................................................................... 17
1-Cycle Total Values ............................................................................................................................ 18
1-Cycle Auxiliary Values....................................................................................................................... 18
Phasor.................................................................................................................................................. 19
1-Second Phase Values....................................................................................................................... 19
1-Second Total Values......................................................................................................................... 20
1-Second Auxiliary Values ................................................................................................................... 20
Present Volt, Ampere and Power Demands......................................................................................... 20
Total Energies EH.................................................................................................................................. 21
Summary Energy Registers EH ............................................................................................................. 21
Phase Energies EH ............................................................................................................................... 21
V1/V12 Harmonic Distortion EH............................................................................................................. 22
V2/V23 Harmonic Distortion EH............................................................................................................. 22

V3/V31 Harmonic Distortion EH............................................................................................................. 22


I1 Harmonic Distortion EH ..................................................................................................................... 22
I2 Harmonic Distortion EH ..................................................................................................................... 22
I3 Harmonic Distortion EH ..................................................................................................................... 22
Fundamental Phase Values EH ............................................................................................................. 22
Fundamental Total Values EH ............................................................................................................... 23
Minimum 1-Cycle Phase Values .......................................................................................................... 23
Minimum 1-Cycle Total Values............................................................................................................. 23
Minimum 1-Cycle Auxiliary Values ....................................................................................................... 23
Maximum 1-Cycle Phase Values ......................................................................................................... 23
Maximum 1-Cycle Total Values............................................................................................................ 24
Maximum 1-Cycle Auxiliary Values ...................................................................................................... 24
Maximum Demands ............................................................................................................................. 24
TOU Parameters EH.............................................................................................................................. 24
Scaled Analog Outputs ........................................................................................................................ 24
TOU Energy Register #1 EH.................................................................................................................. 25
TOU Energy Register #2 EH.................................................................................................................. 25
TOU Energy Register #3 EH.................................................................................................................. 25
TOU Energy Register #4 EH.................................................................................................................. 25
Summary Energy Accumulated Demands EH ....................................................................................... 25
Summary Energy Block Demands EH ................................................................................................... 25
Summary Energy Sliding Window Demands EH.................................................................................... 25
Summary Energy Maximum Demands EH ............................................................................................ 25
TOU Maximum Demand Register #1 EH ............................................................................................... 26
TOU Maximum Demand Register #2 EH ............................................................................................... 26
TOU Maximum Demand Register #3 EH ............................................................................................... 26
TOU Maximum Demand Register #4 EH ............................................................................................... 26
V1/V12 Harmonic Angles EH ................................................................................................................. 26
V2/V23 Harmonic Angles EH ................................................................................................................. 26
V1/V31 Harmonic Angles EH ................................................................................................................. 26
I1 Harmonic Angles EH ......................................................................................................................... 26
I2 Harmonic Angles EH ......................................................................................................................... 27
I3 Harmonic Angles EH ......................................................................................................................... 27
Setpoint Status SP1-SP16 (bitmap) ..................................................................................................... 27

4.3

MINIMUM/MAXIMUM LOG REGISTERS ......................................................................................27


Minimum Phase Values ....................................................................................................................... 27
Minimum Total Values.......................................................................................................................... 27
Minimum Auxiliary Values .................................................................................................................... 28
Maximum Phase Values ...................................................................................................................... 28
Maximum Auxiliary Values ................................................................................................................... 28
Summary Energy Maximum Demands EH ............................................................................................ 28
Maximum Demands ............................................................................................................................. 28
TOU Maximum Demand Register #1 EH ............................................................................................... 30
TOU Maximum Demand Register #2 EH ............................................................................................... 30
TOU Maximum Demand Register #3 EH ............................................................................................... 30
TOU Maximum Demand Register #4 EH ............................................................................................... 30

4.4

DEVICE CONTROL AND STATUS REGISTERS ............................................................................31


Device Authorization Register .............................................................................................................. 31
Remote Relay Control.......................................................................................................................... 31
Device Reset/Clear Registers .............................................................................................................. 31
Device Status Registers....................................................................................................................... 31
Alarm Notification Registers ................................................................................................................. 31

4.5

DEVICE SETUP REGISTERS ....................................................................................................33


Device Identification ............................................................................................................................. 33
Factory Device Settings ....................................................................................................................... 33
Communication Ports Setup ................................................................................................................ 33
Basic Setup.......................................................................................................................................... 34
Device Options Setup .......................................................................................................................... 34
Digital Inputs Setup .............................................................................................................................. 34
Alarm/Event Setpoints Setup ............................................................................................................... 34
Local Settings ...................................................................................................................................... 35
TOU Daily Profile Setup EH ................................................................................................................... 35
TOU Calendar Setup EH ....................................................................................................................... 36

Summary Energy/TOU Registers Setup EH .......................................................................................... 37


Summary Energy/TOU Registers Source Setup EH .............................................................................. 37
Digital Inputs Setup .............................................................................................................................. 37
Relay Outputs Setup ............................................................................................................................ 37

4.6

ANALOG AND DIGITAL I/O CONFIGURATION .............................................................................39


I/O Slots Configuration Info .................................................................................................................. 39
I/O Type Info ........................................................................................................................................ 39

5 DATA SCALES AND UNITS ............................................................................40


Data Scales.......................................................................................................................................... 40
Data Units Low Resolution Option .................................................................................................... 40
Data Units High Resolution Option.................................................................................................... 40

6 DATA FORMATS .............................................................................................41


Timestamp ........................................................................................................................................... 41
Wiring Mode......................................................................................................................................... 41
TOU Tariff Change Time...................................................................................................................... 41
Summary/TOU Energy Register Source ID.......................................................................................... 41
Setpoint Trigger Parameters ID ........................................................................................................... 41
Relays .................................................................................................................................................. 41
Setpoint Action ID ................................................................................................................................ 42
Counter Source ID ............................................................................................................................... 42
Relay Output Pulse Source ID ............................................................................................................. 42
AO Output Parameters ID .................................................................................................................... 43
Device Diagnostics............................................................................................................................... 43
Instrument Options............................................................................................................................... 44
I/O Slot Types ...................................................................................................................................... 44
Reset/Clear Function ........................................................................................................................... 44
Basic Setup Parameters ID.................................................................................................................. 44

1 General
This document specifies the SATEC ASCII serial communications protocol used to transfer data
between a master computer station and the PM130. The document provides the complete information
necessary to develop third-party communications software capable of communication with the Series
PM130 instruments. Additional information concerning operating the device, configuring the
communication parameters, and communication connections may be found in "Series PM130 PLUS
Powermeters, Installation and Operation Manual".
The document is applicable to the PM130P and PM130EH devices.
IMPORTANT
1.

In 3-wire connection schemes, the unbalanced current and phase readings for power factor, active power,
and reactive power will be zeros, because they have no meaning. Only the total three-phase power values
are provided.

2.

Most of the advanced features are configured using multiple setup parameters that can be accessed in a
number of contiguous registers. When writing the setup registers, it is recommended to write all the registers
at once using a single request, or to clear (zero) the setup before writing into separate registers.

Designations used in the guide:


EH - available in the PM130EH

2 ASCII Protocol Description


2.1 ASCII FRAMING
2.1.1 ASCII Message Frame
The following specifies the ASCII message frame:
Field No.
Contents
Length, char

1
SYNC
(!)
1

2
Message
length
3

3
Slave
address
2

4
Message
type
1

5
Message body

6
Checksum

0 to 246

7
Trailer
(CR LF)
2

SYNC

Synchronization character: one character '!' (ASCII 33), used for starting synchronization.
Message length

The length of the message including only number of bytes in fields #2, #3, #4 and #5. Contains three
characters between '006' and '252'.
Slave address

Contains two characters from '00' to '99'. The instrument with address '00' responds to requests with
any incoming address. For RS-422/RS-485 communications (multi-drop mode), this field must
NEVER be zero.
Message type

Consists of one character representing the type of a host request. A list of the message types is shown
in Tables 2-1 and 2-2. Note that they are case-sensitive.
Message body

Contains the message parameters in ASCII representation. All parameter fields have a fixed format.
The data fields vary in length depending on the data type. Unless otherwise indicated, the parameters
should be right justified and left-padded with zeros. Most parameters are represented in ASCII
hexadecimal notation, and in some cases (to provide compatibility with old devices) a decimal
representation is preserved. For data formats, see Section 3.2.
Checksum

Arithmetic sum, calculated in a 2-byte word over fields #2, #3, #4 and #5 to produce a one-byte
check sum in the range of 0x22 to 0x7E (hexadecimal) as follows: [(each byte 0x22)] mod 0x5C +
0x22
Trailer

The message termination consisting of two ASCII characters CR (ASCII 13) and LF (ASCII 10).
NOTE

Fields #3 and #4 of the instrument response are always the same as those in the host request.

Table 2-1 Specific ASCII Requests


Message type
ASCII Char
ASCII Hex
0
0x30
1
0x31
2
0x32
4
0x34
8
0x38
9
0x39
?
0x3F
B
0x42
b
0x62
J
0x4A
j
0x6A
S
0x53
T
0x54

Description
Read basic data registers
Read basic setup
Write basic setup
Reset/clear functions
Reset the instrument
Read version number
Read extended status
Read analog output setup
Write analog output setup
Read pulse counter setup
Write pulse counter setup
Read Real Time Clock
Write Real Time Clock

Table 2-2 Direct Read/Write ASCII Requests


Message type
ASCII Char
ASCII Hex
A
0x41
a
0x61
X
0x58
x
0x78

Description
Long-size direct read
Long-size direct write
Variable-size direct read
Variable-size direct write

2.2 Exception Responses


The instrument will send the following error codes in the message body in response to incorrect host
requests:
XK
XM
XP

the meter is in programming mode


invalid request type or illegal operation
invalid data address or data value, or data is not available

NOTE

When a check or framing error is detected, the meter will not act on or respond to the master's request.

2.3 PROTOCOL IMPLEMENTATION


2.3.1 ASCII Specific and Direct Requests
The ASCII protocol provides two different types of messages to transfer data between a master
application and the meter: specific requests and direct read/write requests.
Specific ASCII requests use different formats for accessing different data locations. The message body
differs depending on the request type. Each data field has a fixed position in the ASCII string. Section
3 describes specific ASCII requests and their message body formats.
Direct read/write requests use a universal message body format, described in Section 2.4. These
requests allow a master application to access different data locations (registers) in the instrument by
specifying a direct register index. A number of consequent registers can be read or written by a single
request by specifying an arbitrary start register and the number of registers to be accessed. Section 4
gives a register map for direct read/write requests and their contents.
All measurement data in your instrument can be accessed using direct read requests, and some data can
be read via specific ASCII requests. In all cases, a direct register read offers you more precise data with
extended resolution. Setup data can be partially accessed using both specific and direct requests, and
partially via either specific or direct requests.

2.3.2 Data Formats


Specific ASCII requests use both decimal and hexadecimal notation. Direct requests transfer ASCII
data only in a hexadecimal format.
Using a decimal notation, data is transmitted in a decimal representation as is, i.e., no conversion is
needed. Negative numbers are transmitted with a sign at the left. Fractional numbers are represented
with a decimal point. When the value exceeds the field width, it is truncated to the right.
In a hexadecimal notation, each data byte is transferred by two hexadecimal characters in ASCII
representation (i.e., ASCII printable characters 0-9, A-F are used to represent hexadecimal digits 0x000x09, 0x0a-0x0f). All data is transferred as 2-character (8-bit unsigned byte), 4-character (16-bit
unsigned or signed integer) or 8-character (32-bit unsigned or signed long integer) whole numbers.
Negative numbers are transmitted in 2-complement code. Each data byte is transmitted high order
digit first. Each integer or long integer register is transmitted high order bytes first.
Fractional numbers are transmitted being scaled by 10 in power N, where N is the number of digits in
the fractional part. For example, the frequency reading of 50.01 Hz is transmitted as 5001 being premultiplied by 100. Whenever a data register contains a fractional number, the register measurement
unit is given with a multiplier 0.1, 0.01 or 0.001, showing an actual register resolution (the weight
of the least significant decimal digit). To get an actual fractional number with specified precision, scale
the register value with the given multiplier. To write a fractional number into the register, divide the
number by the given multiplier.

2.4 DIRECT READ/WRITE REQUESTS


2.4.1 General
In direct read/write requests, data registers are addressed by point IDs that are given in a 4-digit
hexadecimal format. All data is transmitted in ASCII hexadecimal notation as 2-character (UINT8, 8bit unsigned byte), 4-character (16-bit unsigned UINT16 or signed INT16 integer) or 8-character (32bit unsigned UINT32 or signed INT32 long integer) numbers. Negative numbers are transmitted in 2complement code. Register type in the tables below shows an actual data size for data accessed using
variable-size direct read/write requests. When long-size direct read/write request is used, an actual data
size is ignored and all registers are transmitted in an 8-character format as long signed (INT32) or
unsigned (UINT32) integers.
2.4.2 Long-Size Direct Read/Write
In long-size direct read/write messages, all data items are read and written as long unsigned (UINT32)
or signed (INT32) integers, which are represented in messages by 8-digit hexadecimal numbers,
regardless of the actual data size. Up to 30 contiguous points can be read in one message once. A write
request allows for writing only one data location at a time.
Table 2-3 Read Request
Offset

+0
+4
+0
+2
+10
...
+234

Description
Message type
Request body:
Start point ID
The number of points to read
Response body:
Number of points read
Point #1 value
Point #2 value
...
Point #30 value

Range

Type

A
0x0000-0xFFFF
1-30 (0x01-0x1E)

UINT16
UINT8

1-30 (0x01-0x1E)
0x00000000-0xFFFFFFFF
0x00000000-0xFFFFFFFF

UINT8
INT32
INT32
...
INT32

0x00000000-0xFFFFFFFF

Table 2-4 Write Request


Offset

+0
+4
+0
+4

Description
Message type
Request body:
Point ID
Point value to write
Response body:
Point ID
Written value

Range

Type

a
0x0000-0xFFFF
0x00000000-0xFFFFFFFF

UINT16
INT32

0x0000-0xFFFF
0x00000000-0xFFFFFFFF

UINT16
INT32

2.4.3 Variable-Size Direct Read/Write


With variable-size direct read/write messages, data points are read and written as 2, 4 or 8-character
hexadecimal numbers. The actual data size is indicated for each data location. When written, the data
type should be exactly the same as indicated.
The number of parameters that can be read or written by a single read/write request depends on the
size of each data item. The total length of all parameters should not exceed 240 characters.
Table 2-5 Read Request
Offset

+0
+4
+0
+2

Description
Message type
Request body:
Start point ID
The number of points to read
Response body:
Number of points read
Point #1 value
Point #2 value
...
Point #60 value

Range

Type

X
0x0000-0xFFFF
1-60 (0x01-0x3C)

UINT16
UINT8

1-60 (0x01-0x3C)

UINT8
INT8/16/32
INT8/16/32
...
INT8/16/32

Table 2-6 Write Request


Offset

+0
+4
+6

+0
+4

Description
Message type
Request body:
Start point ID
The number of points to write
Point #1 value
Point #2 value
...
Point #60 value
Response body:
Start point ID
Number of points written

Range

Type

x
0x0000-0xFFFF
1-60 (0x01-0x3C)

UINT16
UINT8
INT8/16/32
INT8/16/32
...
INT8/16/32

0x0000-0xFFFF
1-60 (0x01-0x3C)

UINT16
UINT8

2.4.4 User Assignable Registers


The PM130 contains 120 user assignable registers designated by points 0x8000 through 0x8077, any of
which you can map to any point accessible in the instrument through direct read/write requests. Points
that reside in different locations may be accessed by a single request by re-mapping them to adjacent
points in the user assignable registers area.
The actual point IDs of the assignable registers, which are accessed via addresses 0x8000 through
0x8077, are specified in the register map through points 0x8100-0x8177, where point 0x8100 contains
the actual point ID of the register accessed via point 0x8000, point 0x8101 contains the actual point ID
of the register accessed via point 0x8001, and so on. The assignable registers and the map registers
themselves may not be re-mapped.
To build your own register map, write to map registers (points 0x8100-0x8177) the actual point IDs of
the registers you want to read from or write to via the assignable points 0x8000-0x8077. For example,

10

if you want to read points 0x0C00 (real-time voltage of phase A) and 0x1700 (kWh import) through
points 0x8000-0x8001, do the following:
- write 0x0C00 to point 0x8100
- write 0x1700 to point 0x8101
Reading from points 0x8000-0x8001 will return the voltage reading through point 0x8000, and the
kWh reading through point 0x8001.

2.5 Password Protection


The PM130 has a password protection option allowing you to protect your setups, cumulative registers
and logs from being changed or cleared through communications. You can disable or enable password
protection through communications or via the front display. For details, refer to your instrument
Installation and Operation Manual. When password protection is enabled, the user password you set in
your instrument should be written into the device authorization register (point 0xFF00) before another
write request is issued. If the correct password is not supplied while password protection is enabled,
the instrument will respond to all write requests with the exception code XM (illegal operation). It is
recommended to clear the password register after you have completed your changes in order to
activate password protection.

11

3 Specific ASCII Requests


3.1 Basic Data Set
Offset

Length

Description

Range

Units

Type

R/W

Notes

Basic Data Set

+0
+4
+8
+12
+17
+22
+27
+33
+39
+45
+49
+53
+57
+63
+67
+73
+78
+82
+88
+94
+100
+106
+112
+118
+124
+130
+136
+142
+148
+153
+158
+163
+165

4
4
4
5
5
5
6
6
6
4
4
4
6
4
6
5
4
6
6
6
6
6
6
6
6
6
6
6
5
5
5
2
6

Message Type
Request Body
Response Body (decimal)
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
kW L1
kW L2
kW L3
Power factor L1
Power factor L2
Power factor L3
kW total
Power factor total
kWh import
Neutral (unbalanced) current
Frequency
kvar L1
kvar L2
kvar L3
kVA L1
kVA L2
kVA L3
kvarh net
kvar total
kVA total
Maximum sliding window kW import demand
Accumulated kW import demand
I1 Max. ampere demand
I2 Max. ampere demand
I3 Max. ampere demand
Status inputs (bitmap - hex)
kWh export

0
No

0 to Vmax
0 to Vmax
0 to Vmax
0 to Imax
0 to Imax
0 to Imax
-Pmax to Pmax
-Pmax to Pmax
-Pmax to Pmax
-.99 to 1.00 4
-.99 to 1.00 4
-.99 to 1.00 4
-Pmax to Pmax
-.99 to 1.00 4
0 to 99999.
0 to Imax
25.0 to 400.
-Pmax to Pmax
-Pmax to Pmax
-Pmax to Pmax
0 to Pmax
0 to Pmax
0 to Pmax
-9999. to 99999.
-Pmax to Pmax
0 to Pmax
0 to Pmax
0 to Pmax
0 to Imax
0 to Imax
0 to Imax
0x00-0x03
0 to 99999.

U1
U1
U1
U2
U2
U2
U3
U3
U3

1
1
1

U3
MWh
A
Hz
U3
U3
U3
U3
U3
U3
Mvarh
U3
U3
U3
U3
U2
U2
U2

MWh

12

Offset

Length

+171
+177
+181
+185
+189
+193
+197
+201
+209
+215
+221
+225
+229
+233

Description
6
4
4
4
4
4
4
8
6
6
4
4
4
4

Maximum sliding window kVA demand 5


V1/V12 Voltage THD
V2/V23 Voltage THD
V3/V31 Voltage THD
I1 Current THD
I2 Current THD
I3 Current THD
kVAh total
Present sliding window kW import demand
Present sliding window kVA demand 5
PF (import) at maximum KVA demand
I1 Current TDD
I2 Current TDD
I3 Current TDD

Range

0 to Pmax
0.0 to 999.
0.0 to 999.
0.0 to 999.
0.0 to 999.
0.0 to 999.
0.0 to 999.
0 to 99999.99
0 to Pmax
0 to Pmax
0 to 1.00
0.0 to 99.9
0.0 to 99.9
0.0 to 99.9

Units
U3
%
%
%
%
%
%
MVAh
U3
U3

Type

R/W

Notes
1

3-sec value
3-sec value
1 3-sec value
3-sec value
3-sec value
3-sec value
1

%
%
%

3-sec value
3-sec value
3-sec value

NOTES:
Energy, power demand and harmonics readings are only available in the PM130EH meters.
1

Voltage and voltage harmonics readings: when the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line
voltages.

All analog registers except of harmonics are 1-second average values. For volts, amps and power scales and units, refer to Section 5 Data Scales and Units.
When ASCII compatibility mode is disabled (see Section 5.5), voltages, currents and powers are transmitted with a decimal point in units defined in the table. When the value is greater than
the field width, the right most digits of the fractional part are truncated.
When ASCII compatibility mode is enabled, the meter provides a fully downward-compatible response using a lower resolution for voltages, currents and powers - the value is transmitted as
a whole number until the field is filled up, and then it is converted to higher units and transmitted with a decimal point. If the value is greater than the field width, the right most digits of the
fractional part are truncated. Voltages are transmitted in volts as whole numbers or in kilovolts with a decimal point, currents in amperes as whole numbers, and powers in kilowatts as
whole numbers or in megawatts with a decimal point.

Energy readings are transmitted in MWh, Mvarh and MVAh units with a decimal point. If the energy value exceeds the field width, the right-most digits are truncated. If you use these
request for energy readings, then, to avoid overflow, limit the energy roll value (see Device Options Setup) to 7 digits if you use kvarh net reading or to 8 digits if you
do not use it.

For negative power factor, the minus sign is transmitted before a decimal point as shown in the table.

3.2 Device Control and Status


Offset
Reset/Clear

+0
+1

Length

Description
Message Type
Request Body (hexadecimal):
1 Reset function
2 Target
Response the same as request

Range

Units

Type

R/W

Notes

4
F30
F30

13

Offset
Length
Warm Restart

Description
Message Type
Request Body
Response Body

Range

Units

Type

R/W

Notes

8
No
No

Firmware Version

+0
+4
Device Status

+0
+4
+8
+12
+16

Message Type
Request Body
Response Body
4 Firmware version number

9
No

2 Firmware build number

1-99

4
4
4
4
40

Message Type
Request Body
Response Body
Relay status (bitmap)
Not used
Digital (status) inputs (bitmap)
Setpoints status (bitmap)
Not used

1100-1199

Two higher decimal digits = major


version number, two lower decimal
digits = minor version number

?
No
0x0000-0x0003
0x0000
0x0000-0x0003
0x0000-0xFFFF
0x0000

3.3 Device Setup


Offset
Length
Read Basic Setup

+0
+0
+3
+7
Write Basic Setup

Description

3
3
4
6

Message Type
Request Body (decimal):
Parameter ID
Response Body (decimal)
Parameter ID
Not used
Parameter value

Message Type
Request Body (decimal):
+0
3 Parameter ID
+3
4 Not used
+7
6 Parameter value
Response the same as request
Read Analog Output Setup
Message Type

Range

Units

Type

R/W

Notes

1
F31
F31
00.0
See Basic Setup in Section 4.5
1
F31
00.0
See Basic Setup in Section 4.5

14

Offset

Length

Description
Request Body
+0
2 Analog channel number
Response Body (hexadecimal)
+0
2 Analog channel number
+2
4 Output parameter point ID
+6
8 Zero scale (0/4 mA)
+14
8 Full scale (20/1 mA)
Write Analog Output Setup
Message Type
Request Body (hexadecimal)
+0
2 Analog channel number
+2
4 Output parameter point ID
+6
8 Zero scale (0/4 mA)
+14
8 Full scale (20/1 mA)
Response Body the same as request
Read Pulse Counter Setup
Message Type
Request Body
+0
2 Counter ID
Response Body (hexadecimal)
+0
2 Counter ID
+2
2 Source ID
+4
4 Multiplier
Write Pulse Counter Setup
Message Type
Request Body (hexadecimal)
+0
2 Counter ID
+2
2 Source ID
+4
4 Multiplier
+2
4 Timer interval
Response Body the same as request
Read Clock Indication
Message Type
Request Body
Response Body (decimal)
+0
2 Second
+2
2 Minute
+4
2 Hour
+6
2 Day
+8
2 Month
+10
2 Year
+12
2 Day of week

Range

Units

Type

R/W

Notes

0-1=channel AO1-AO2
0-1=channel AO1-AO2
F18
See Section 4.2
See Section 4.2
b
0-1=channel AO1-AO2
F18
See Section 4.2
See Section 4.2

J
0-3=counter #1-#4
0-3=counter #1-#4
0=not assigned, 1-4=DI1-DI4
1-9999
j
0-3=counter #1-#4
0=not assigned, 1-2=DI1-DI2
1-9999
1-9999, 0=timer disabled

S
No
0-59
0-59
0-23
1-31
1-12
0-99
1-7 (1=Sunday)

15

Offset
Length
Write Clock Setup

+0
+2
+4
+6
+8
+10
+12

Description

2
2
2
2
2
2
2

Message Type
Request Body (decimal)
Second
Minute
Hour
Day
Month
Year
Day of week
Response Body the same as request

Range

Units

Type

R/W

Notes

T
0-59
0-59
0-23
1-31
1-12
0-99
1-7 (1=Sunday)

Ignored when written

16

4 Direct Read/Write Requests


4.1 Protocol Setup Registers
Point ID Description
Assignable Registers
0x8000 Register 0 contents
0x8001 Register 1 contents
...
0x8077 Register 119 contents
Assignable Registers Map
0x8100 Mapped point for register 0x8000
0x8101 Mapped point for register 0x8001
...
0x8177 Mapped point for register 0x8077
Device Data Scales
0x81F2 Voltage scale, secondary volts
0x81F3 Current scale, secondary amps

Options/Range

Units

Type

R/W

0-65535
0-65535

UINT16
UINT16

R/W
R/W

0-65535

UINT16

R/W

0x0000 - 0xFFFF
0x0000 - 0xFFFF

UINT16
UINT16

R/W
R/W

0x0000 - 0xFFFF

UINT16

R/W

UINT16
UINT16

R/W
R/W

60-828
10-100

1V
0.1A

Notes

Default 144V
Default 2CT secondary

4.2 Analog Registers, Binary Registers and Counters


Point ID

Description

0x0000 None
Special Inputs
0x0101 Phase rotation order
0x0600 Digital Inputs DI1-DI4 (bitmap)
0x0800 Relay Outputs RO1-RO2 (bitmap)
Counters
0x0A00 Counter #1
0x0A01 Counter #2
0x0A02 Counter #3
0x0A03 Counter #4
1-Cycle Phase Values
0x0C00 V1/V12 Voltage
0x0C01 V2/V23 Voltage
0x0C02 V3/V31 Voltage
0x0C03 I1 Current
0x0C04 I2 Current
0x0C05 I3 Current

Options/Range

Units

Type

R/W

UINT16

0=error, 1=positive (ABC),


2=negative (CBA)
0x0000-0x000F
0x0000-0x0003

UINT16

UINT16
UINT16

R
R

0-99,999
0-99,999
0-99,999
0-99,999

UINT32
UINT32
UINT32
UINT32

R/W
R/W
R/W
R/W

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax

U1
U1
U1
U2
U2
U2

Notes

1
1
1

17

Point ID
0x0C06
0x0C07
0x0C08
0x0C09
0x0C0A
0x0C0B
0x0C0C
0x0C0D
0x0C0E
0x0C0F
0x0C10
0x0C11
0x0C12
0x0C13
0x0C14
0x0C15
0x0C16
0x0C17
0x0C18
0x0C19
0x0C1A
0x0C1B
0x0C1C
0x0C1D
0x0C1E
0x0C1F
0x0C20
0x0F00
0x0F01
0x0F02
0x0F03
0x0F04
0x0F05
0x0F06
0x0F07
0x0F08
0x0F09
0x0F0A
0x0F0B
0x0F0C
0x1000

Description
kW L1
kW L2
kW L3
kvar L1
kvar L2
kvar L3
kVA L1
kVA L2
kVA L3
Power factor L1
Power factor L2
Power factor L3
V1/V12 Voltage THD
V2/V23 Voltage THD
V3/V31 Voltage THD
I1 Current THD
I2 Current THD
I3 Current THD
I1 K-Factor
I2 K-Factor
I3 K-Factor
I1 Current TDD
I2 Current TDD
I3 Current TDD
V12 Voltage
V23 Voltage
V31 Voltage
1-Cycle Total Values
Total kW
Total kvar
Total kVA
Total PF
Total PF lag
Total PF lead
Total kW import
Total kW export
Total kvar import
Total kvar export
3-phase average L-N/L-L voltage
3-phase average L-L voltage
3-phase average current
1-Cycle Auxiliary Values
Not used

Options/Range
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
0-Pmax
0-Pmax
0-Pmax
-1000-1000
-1000-1000
-1000-1000
0-9999
0-9999
0-9999
0-9999
0-9999
0-9999
10-9999
10-9999
10-9999
0-1000
0-1000
0-1000
0-Vmax
0-Vmax
0-Vmax
-Pmax-Pmax
-Pmax-Pmax
0-Pmax
-1000-1000
0-1000
0-1000
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Vmax
0-Vmax
0-Imax

Type

R/W

Units
U3
U3
U3
U3
U3
U3
U3
U3
U3
0.001
0.001
0.001
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1
0.1
0.1
0.1%
0.1%
0.1%
U1
U1
U1

INT32
INT32
INT32
INT32
INT32
INT32
UINT32
UINT32
UINT32
INT16
INT16
INT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

U3
U3
U3
0.001
0.001
0.001
U3
U3
U3
U3
U1
U1
U2

INT32
INT32
UINT32
INT16
UINT16
UINT16
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R
R

UINT32

Notes

2-cycle value
2-cycle value
1 2-cycle value
2-cycle value
2-cycle value
2-cycle value
2-cycle value
2-cycle value
2-cycle value
2-cycle value
2-cycle value
2-cycle value
1

18

Point ID
0x1001
0x1002
0x1003
0x1004
0x1080
0x1081
0x1082
0x1083
0x1084
0x1085
0x1086
0x1087
0x1088
0x1089
0x108A
0x108B
0x108C
0x108D
0x108E
0x108F
0x1100
0x1101
0x1102
0x1103
0x1104
0x1105
0x1106
0x1107
0x1108
0x1109
0x110A
0x110B
0x110C
0x110D
0x110E
0x110F
0x1110
0x1111
0x1112
0x1113
0x1114

Description
In (neutral) Current
Frequency
Voltage unbalance
Current unbalance
Phasor
V1/V12 Voltage magnitude
V2/V23 Voltage magnitude
V3/V31 Voltage magnitude
Not used
I1 Current magnitude
I2 Current magnitude
I3 Current magnitude
Not used
V1/V12 Voltage angle
V2/V23 Voltage angle
V3/V31 Voltage angle
Not used
I1 Current angle
I2 Current angle
I3 Current angle
Not used
1-Second Phase Values
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
kW L1
kW L2
kW L3
kvar L1
kvar L2
kvar L3
kVA L1
kVA L2
kVA L3
Power factor L1
Power factor L2
Power factor L3
V1/V12 Voltage THD
V2/V23 Voltage THD
V3/V31 Voltage THD

Options/Range

0-Imax
0-Fmax
0-3000
0-3000

Units
U2
0.01Hz
0.1%
0.1%

0-Vmax
0-Vmax
0-Vmax

U1
U1
U1

0-Imax
0-Imax
0-Imax

U2
U2
U2

-1800-1800
-1800-1800
-1800-1800

0.1
0.1
0.1

-1800-1800
-1800-1800
-1800-1800

0.1
0.1
0.1

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
0-Pmax
0-Pmax
0-Pmax
-1000-1000
-1000-1000
-1000-1000
0-9999
0-9999
0-9999

U1
U1
U1
U2
U2
U2
U3
U3
U3
U3
U3
U3
U3
U3
U3
0.001
0.001
0.001
0.1%
0.1%
0.1%

Type

R/W

Notes

UINT32
UINT16
UINT16
UINT16

R
R
R
R

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
INT16
INT16
INT16
INT16
INT16
INT16
INT16
INT16

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
INT32
INT32
INT32
INT32
INT32
INT32
UINT32
UINT32
UINT32
INT16
INT16
INT16
UINT16
UINT16
UINT16

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

1
1

1
1
1

1
1

3-sec value
3-sec value
1 3-sec value
1

19

Point ID
0x1115
0x1116
0x1117
0x1118
0x1119
0x111A
0x111B
0x111C
0x111D
0x111E
0x111F
0x1120
0x1400
0x1401
0x1402
0x1403
0x1404
0x1405
0x1406
0x1407
0x1408
0x1409
0x140A
0x140B
0x140C
0x1500
0x1501
0x1502
0x1503
0x1504
0x1600
0x1601
0x1602
0x1603
0x1604
0x1605
0x1606
0x1607
0x1608
0x1609

Description
I1 Current THD
I2 Current THD
I3 Current THD
I1 K-Factor
I2 K-Factor
I3 K-Factor
I1 Current TDD
I2 Current TDD
I3 Current TDD
V12 Voltage
V23 Voltage
V31 Voltage
1-Second Total Values
Total kW
Total kvar
Total kVA
Total PF
Total PF lag
Total PF lead
Total kW import
Total kW export
Total kvar import
Total kvar export
3-phase average L-N/L-L voltage
3-phase average L-L voltage
3-phase average current
1-Second Auxiliary Values
Not used
In (neutral) Current
Frequency
Voltage unbalance
Current unbalance
Present Volt, Ampere and Power Demands
V1/V12 Volt demand
V2/V23 Volt demand
V3/V31 Volt demand
I1 Ampere demand
I2 Ampere demand
I3 Ampere demand
kW import block demand
kvar import block demand
kVA block demand
kW import sliding window demand

Options/Range

Type

R/W

0-9999
0-9999
0-9999
10-9999
10-9999
10-9999
0-1000
0-1000
0-1000
0-Vmax
0-Vmax
0-Vmax

Units
0.1%
0.1%
0.1%
0.1
0.1
0.1
0.1%
0.1%
0.1%
U1
U1
U1

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R
R
R
R
R
R
R
R
R
R
R
R

-Pmax-Pmax
-Pmax-Pmax
0-Pmax
-1000-1000
0-1000
0-1000
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Vmax
0-Vmax
0-Imax

U3
U3
U3
0.001
0.001
0.001
U3
U3
U3
U3
U1
U1
U2

INT32
INT32
UINT32
INT16
UINT16
UINT16
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R
R

0-Imax
0-Fmax
0-3000
0-3000

U2
0.01Hz
0.1%
0.1%

UINT32
UINT32
UINT16
UINT16
UINT16

R
R
R
R
R

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax
0-Pmax
0-Pmax
0-Pmax
0-Pmax

U1
U1
U1
U2
U2
U2
U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R

Notes
3-sec
3-sec
3-sec
3-sec
3-sec
3-sec
3-sec
3-sec
3-sec

value
value
value
value
value
value
value
value
value

1
1
1

20

Point ID
0x160A
0x160B
0x160C
0x160D
0x160E
0x160F
0x1610
0x1611
0x1612
0x1613
0x1614
0x1615
0x1616
0x1617
0x1618
0x1619
0x161A
0x161B
0x161C
0x161D
0x161E
0x161F
0x1620
0x1621
0x1622
0x1700
0x1701
0x1702
0x1703
0x1704
0x1705
0x1706
0x1707
0x1708
0x1780
0x1781
0x1782
0x1783
0x1800

Description
kvar import sliding window demand
kVA sliding window demand
Not used
Not used
Not used
kW import accumulated demand
kvar import accumulated demand
kVA accumulated demand
kW import predicted sliding window demand
kvar import predicted sliding window demand
kVA predicted sliding window demand
PF (import) at Max. kVA sliding window demand
kW export block demand
kvar export block demand
kW export sliding window demand
kvar export sliding window demand
kW export accumulated demand
kvar export accumulated demand
kW export predicted sliding window demand
kvar export predicted sliding window demand
Not used
Not used
Not used
Not used
In Ampere demand
Total Energies EH
kWh import
kWh export
Not used
Not used
kvarh import
kvarh export
Not used
Not used
kVAh total
Summary Energy Registers EH
Summary energy register #1
Summary energy register #2
Summary energy register #3
Summary energy register #4
Phase Energies EH
kWh import L1

Options/Range

Units
U3
U3

0-Pmax
0-Pmax
0
0
0
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-1000
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0-Pmax
0
0
0
0
0-Imax

U3
U3
U3
U3
U3
U3
0.001
U3
U3
U3
U3
U3
U3
U3
U3

0-109-1
0-109-1

1 kWh
1 kWh

0-109-1
0-109-1

1 kvarh
1 kvarh

0-109-1

Type

R/W

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT16
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

1 kVAh

UINT32
UINT32
INT32
UINT32
UINT32
UINT32
INT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R

0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1

kWh
kWh
kWh
kWh

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-109-1

1 kWh

UINT32

U2

Notes

21

Point ID
0x1801
0x1802
0x1803
0x1804
0x1805
0x1806
0x1807
0x1808
0x1900
0x1901
0x1927
0x1A00
0x1A01
0x1A27
0x1B00
0x1B01
0x1B27
0x1C00
0x1C01
0x1C27
0x1D00
0x1D01
0x1D27
0x1E00
0x1E01
0x1E27
0x2900

Description
kWh import L2
kWh import L3
kvarh import L1
kvarh import L2
kvarh import L3
kVAh total L1
kVAh total L2
kVAh total L3
V1/V12 Harmonic Distortion EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
V2/V23 Harmonic Distortion EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
V3/V31 Harmonic Distortion EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
I1 Harmonic Distortion EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
I2 Harmonic Distortion EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
I3 Harmonic Distortion EH
H01 Harmonic distortion
H02 Harmonic distortion
...
H40 Harmonic distortion
Fundamental Phase Values EH
V1/V12 Voltage

Options/Range
0-109-1

Units
kWh
kWh
kvarh
kvarh
kvarh
kVAh
kVAh
kVAh

Type

R/W

0-109-1
0-109-1
0-109-1
0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1
1
1
1
1

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R

0-10000
0-10000

0.01%
0.01%

UINT16
UINT16

R
R

0-10000

0.01%

UINT16

0-10000
0-10000

0.01%
0.01%

UINT16
UINT16

R
R

0-10000

0.01%

UINT16

0-10000
0-10000

0.01%
0.01%

UINT16
UINT16

R
R

0-10000

0.01%

UINT16

0-10000
0-10000

0.01%
0.01%

UINT16
UINT16

R
R

0-10000

0.01%

UINT16

0-10000
0-10000

0.01%
0.01%

UINT16
UINT16

R
R

0-10000

0.01%

UINT16

0-10000
0-10000

0.01%
0.01%

UINT16
UINT16

R
R

0-10000

0.01%

UINT16

0-Vmax

U1

UINT32

Notes

2-cycle values
1

22

Point ID
0x2901
0x2902
0x2903
0x2904
0x2905
0x2906
0x2907
0x2908
0x2909
0x290A
0x290B
0x290C
0x290D
0x290E
0x290F
0x2910
0x2911
0x2A00
0x2A01
0x2A02
0x2A03
0x2C00
0x2C01
0x2C02
0x2C03
0x2C04
0x2C05
0x2D00
0x2D01
0x2D02
0x2D03
0x2E00
0x2E01
0x2E02
0x3400
0x3401
0x3402
0x3403

Description
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
kW L1
kW L2
kW L3
kvar L1
kvar L2
kvar L3
kVA L1
kVA L2
kVA L3
Power factor L1
Power factor L2
Power factor L3
Fundamental Total Values EH
Total fundamental kW
Total fundamental kvar
Total fundamental kVA
Total fundamental PF
Minimum 1-Cycle Phase Values
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
Minimum 1-Cycle Total Values
Total kW
Total kvar
Total kVA
Total PF
Minimum 1-Cycle Auxiliary Values
Not used
In Current
Frequency
Maximum 1-Cycle Phase Values
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current

Options/Range
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
-Pmax-Pmax
0-Pmax
0-Pmax
0-Pmax
-1000-1000
-1000-1000
-1000-1000

Type

R/W

Units
U1
U1
U2
U2
U2
U3
U3
U3
U3
U3
U3
U3
U3
U3
0.001
0.001
0.001

UINT32
UINT32
UINT32
UINT32
UINT32
INT32
INT32
INT32
INT32
INT32
INT32
UINT32
UINT32
UINT32
INT16
INT16
INT16

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

-Pmax-Pmax
-Pmax-Pmax
0-Pmax
-1000-1000

U3
U3
U3
0.001

INT32
INT32
UINT32
INT16

R
R
R
R

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax

U1
U1
U1
U2
U2
U2

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R

-Pmax-Pmax
-Pmax-Pmax
0-Pmax
0-1000

U3
U3
U3
0.001

INT32
INT32
UINT32
UINT32

R
R
R
R

0-Imax
0-Fmax

U2
0.01Hz

UINT32
UINT32
UINT32

R
R
R

0-Vmax
0-Vmax
0-Vmax
0-Imax

U1
U1
U1
U2

UINT32
UINT32
UINT32
UINT32

R
R
R
R

Notes
1
1

2-cycle values

1
1
1

Absolute value

1
1
1

23

Point ID

Description

0x3404 I2 Current
0x3405 I3 Current
Maximum 1-Cycle Total Values
0x3500 Total kW
0x3501 Total kvar
0x3502 Total kVA
0x3503 Total PF
Maximum 1-Cycle Auxiliary Values
0x3600 Not used
0x3601 In Current
0x3602 Frequency
Maximum Demands
0x3700 V1/V12 Maximum volt demand
0x3701 V2/V23 Maximum volt demand
0x3702 V3/V31 Maximum volt demand
0x3703 I1 Maximum ampere demand
0x3704 I2 Maximum ampere demand
0x3705 I3 Maximum ampere demand
0x3706 Not used
0x3707 Not used
0x3708 Not used
0x3709 Maximum kW import sliding window demand
0x370A Maximum kvar import sliding window demand
0x370B Maximum kVA sliding window demand
0x3737 Not used
0x370D Not used
0x370E Not used
0x370F Maximum kW export sliding window demand
0x3710 Maximum kvar export sliding window demand
0x3711 Not used
0x3712 Not used
0x3713 Not used
0x3714 Not used
0x3715 In Maximum ampere demand
TOU Parameters EH
0x3C00 Active tariff
0x3C01 Active profile

Scaled Analog Outputs


0x3C80 Analog output AO1

Options/Range

Type

R/W

0-Imax
0-Imax

Units
U2
U2

UINT32
UINT32

R
R

-Pmax-Pmax
-Pmax-Pmax
0-Pmax
0-1000

U3
U3
U3
0.001

INT32
INT32
UINT32
UINT32

R
R
R
R

0-Imax
0-Fmax

U2
0.01Hz

UINT32
UINT32
UINT32

R
R
R

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax

U1
U1
U1
U2
U2
U2

0-Pmax
0-Pmax
0-Pmax

U3
U3
U3

0-Pmax
0-Pmax

U3
U3

0-Imax

U2

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

0-7
0-15:
0-3 = Season 1 Profile #1-4,
4-7 = Season 2 Profile #1-4,
8-11 = Season 3 Profile #1-4,
12-15 = Season 4 Profile #1-4

UINT32
UINT32

R
R

0-4095

UINT32

R/W

Notes

Absolute value

1
1
1

24

Point ID

Description

0x3C81 Analog output AO2


TOU Energy Register #1 EH
0x3D00 Tariff #1 register
0x3D01 Tariff #2 register
0x3D02 Tariff #3 register
0x3D03 Tariff #4 register
TOU Energy Register #2 EH
0x3E00 Tariff #1 register
0x3E01 Tariff #2 register
0x3E02 Tariff #3 register
0x3E03 Tariff #4 register
TOU Energy Register #3 EH
0x3F00 Tariff #1 register
0x3F01 Tariff #2 register
0x3F02 Tariff #3 register
0x3F03 Tariff #4 register
TOU Energy Register #4 EH
0x4000 Tariff #1 register
0x4001 Tariff #2 register
0x4002 Tariff #3 register
0x4003 Tariff #4 register
Summary Energy Accumulated Demands EH
0x4500 Summary register #1 demand
0x4501 Summary register #2 demand
0x4502 Summary register #3 demand
0x4503 Summary register #4 demand
Summary Energy Block Demands EH
0x4580 Summary register #1 demand
0x4581 Summary register #2 demand
0x4582 Summary register #3 demand
0x4583 Summary register #4 demand
Summary Energy Sliding Window Demands

Options/Range

Units

0-4095

Type

R/W

UINT32

R/W

0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1

kWh
kWh
kWh
kWh

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1

kWh
kWh
kWh
kWh

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1

kWh
kWh
kWh
kWh

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-109-1
0-109-1
0-109-1
0-109-1

1
1
1
1

kWh
kWh
kWh
kWh

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax

U3
U3

UINT32
UINT32

R
R

Notes

EH

0x4600
0x4601
0x4602
0x4603

Summary register #1 demand


Summary register #2 demand
Summary register #3 demand
Summary register #4 demand
Summary Energy Maximum Demands EH
0x4780 Summary register #1 maximum demand
0x4781 Summary register #2 maximum demand

25

Point ID

Description

0x4782 Summary register #3 maximum demand


0x4783 Summary register #4 maximum demand
TOU Maximum Demand Register #1 EH
0x4800 Tariff #1 maximum demand
0x4801 Tariff #2 maximum demand
0x4802 Tariff #3 maximum demand
0x4803 Tariff #4 maximum demand
TOU Maximum Demand Register #2 EH
0x4900 Tariff #1 maximum demand
0x4901 Tariff #2 maximum demand
0x4902 Tariff #3 maximum demand
0x4903 Tariff #4 maximum demand
TOU Maximum Demand Register #3 EH
0x4A00 Tariff #1 maximum demand
0x4A01 Tariff #2 maximum demand
0x4A02 Tariff #3 maximum demand
0x4A03 Tariff #4 maximum demand
TOU Maximum Demand Register #4 EH
0x4880 Tariff #1 maximum demand
0x4881 Tariff #2 maximum demand
0x4882 Tariff #3 maximum demand
0x4883 Tariff #4 maximum demand
V1/V12 Harmonic Angles EH
0x6400 H01 Harmonic angle
0x6400 H02 Harmonic angle
...
0x6427 H40 Harmonic angle
V2/V23 Harmonic Angles EH
0x6500 H01 Harmonic angle
0x6500 H02 Harmonic angle
...
0x6527 H40 Harmonic angle
V1/V31 Harmonic Angles EH
0x6600 H01 Harmonic angle
0x6600 H02 Harmonic angle
...
0x6627 H40 Harmonic angle
I1 Harmonic Angles EH
0x6700 H01 Harmonic angle
0x6700 H02 Harmonic angle

Options/Range

Type

R/W

0-Pmax
0-Pmax

Units
U3
U3

UINT32
UINT32

R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

0-Pmax
0-Pmax
0-Pmax
0-Pmax

U3
U3
U3
U3

UINT32
UINT32
UINT32
UINT32

R
R
R
R

-1800-1800
-1800-1800

0.1
0.1

INT16
INT16

R
R

-1800-1800

0.1

INT16

-1800-1800
-1800-1800

0.1
0.1

INT16
INT16

R
R

-1800-1800

0.1

INT16

-1800-1800
-1800-1800

0.1
0.1

INT16
INT16

R
R

-1800-1800

0.1

INT16

-1800-1800
-1800-1800

0.1
0.1

INT16
INT16

R
R

Notes

1, 3

1, 3

1, 3

26

Point ID
0x6727
0x6800
0x6800
0x6827
0x6900
0x6900
0x6927
0x7C00

Description
...
H40 Harmonic angle
I2 Harmonic Angles EH
H01 Harmonic angle
H02 Harmonic angle
...
H40 Harmonic angle
I3 Harmonic Angles EH
H01 Harmonic angle
H02 Harmonic angle
...
H40 Harmonic angle
Setpoint Status SP1-SP16 (bitmap)

Options/Range

Type

Units

R/W

-1800-1800

0.1

INT16

-1800-1800
-1800-1800

0.1
0.1

INT16
INT16

R
R

-1800-1800

0.1

INT16

-1800-1800
-1800-1800

0.1
0.1

INT16
INT16

R
R

-1800-1800
0x00000000-0x0000FFFF

0.1

INT16
UINT32

R
R

Notes

NOTES:
Energy, power demand and harmonics readings are only available in the PM130EH meters.
1

Voltage and voltage harmonics readings: when the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line
voltages.

For volts, amps, power and frequency scales and units, refer to Section 5 Data Scales and Units.

Harmonic angles are referenced to the fundamental voltage harmonic H01 on phase L1.

4.3 Minimum/Maximum Log Registers


Point ID
0xB000
0xB001
0xB002
0xB003
0xB004
0xB005
0xB006
0xB007
0xB008
0xB009
0xB00A
0xB00B
0xB080
0xB081

Description
Minimum Phase Values
Min. V1/V12 Voltage
Timestamp
Min. V2/V23 Voltage
Timestamp
Min. V3/V31 Voltage
Timestamp
Min. I1 Current
Timestamp
Min. I2 Current
Timestamp
Min. I3 Current
Timestamp
Minimum Total Values
Min. Total kW
Timestamp

Options/Range/Format
0-Vmax
F1
0-Vmax
F1
0-Vmax
F1
0-Imax
F1
0-Imax
0-Imax

-Pmax-Pmax

Units

Type

R/W

U1
sec
U1
sec
U1
sec
U2
sec
U2
sec
U2
sec

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R

U3
sec

INT32
UINT32

R
R

Notes
1
1
1

27

Point ID
0xB082
0xB083
0xB084
0xB085
0xB086
0xB087

Description

Min. Total kvar


Timestamp
Min. Total kVA
Timestamp
Min. Total PF
Timestamp
Minimum Auxiliary Values
0xB100 Not used
0xB101
0xB102 Min. In Current
0xB103 Timestamp
0xB104 Min. Frequency
0xB105 Timestamp
Maximum Phase Values
0xB200 Max. V1/V12 Voltage
0xB201 Timestamp
0xB202 Max. V2/V23 Voltage
0xB203 Timestamp
0xB204 Max. V3/V31 Voltage
0xB205 Timestamp
0xB206 Max. I1 Current
0xB207 Timestamp
0xB208 Max. I2 Current
0xB209 Timestamp
0xB20A Max. I3 Current
0xB20B Timestamp
Maximum Auxiliary Values
0xB300 Not used
0xB301
0xB302 Max. In Current
0xB303 Timestamp
0xB304 Max. Frequency
0xB305 Timestamp
Summary Energy Maximum Demands EH
0xB340 Summary register #1 Maximum Demand
0xB341 Timestamp
0xB342 Summary register #2 Maximum Demand
0xB343 Timestamp
0xB344 Summary register #3 Maximum Demand
0xB345 Timestamp
0xB346 Summary register #4 Maximum Demand
0xB347 Timestamp
Maximum Demands
0xB380 V1/V12 Maximum volt demand

Options/Range/Format
-Pmax-Pmax

Type

R/W

Units
U3
sec
U3
sec
0.001
sec

INT32
UINT32
UINT32
UINT32
INT32
UINT32

R
R
R
R
R
R

U2
sec
0.01Hz
sec

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R

U1
sec
U1
sec
U1
sec
U2
sec
U2
sec
U2
sec

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R
R
R
R
R

U2
sec
0.01Hz
sec

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R

0-Pmax

U3

UINT32

0-Pmax

U3

UINT32

0-Pmax

U3

UINT32

0-Pmax

U3

UINT32

0-Vmax

U1

UINT32

0-Pmax
-1000-1000

0
0-Imax
0-Fmax

0-Vmax
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax

0
0-Imax
0-Fmax

Notes

1
1
1

28

Point ID
0xB381
0xB382
0xB383
0xB384
0xB385
0xB386
0xB387
0xB388
0xB389
0xB38A
0xB38B
0xB38C
0xB38D
0xB38E
0xB38F
0xB390
0xB391
0xB392
0xB393
0xB394
0xB395
0xB396
0xB397
0xB398
0xB399
0xB39A
0xB39B
0xB39C
0xB39D
0xB39E
0xB39F
0xB3A0
0xB3A1
0xB3A2
0xB3A3
0xB3A4
0xB3A5
0xB3A6
0xB3A7
0xB3A8
0xB3A9
0xB3AA
0xB3AB

Description
Timestamp
V2/V23 Maximum volt demand
Timestamp
V3/V31 Maximum volt demand
Timestamp
I1 Maximum ampere demand
Timestamp
I2 Maximum ampere demand
Timestamp
I3 Maximum ampere demand
Timestamp
Not used

Options/Range/Format
0-Vmax
0-Vmax
0-Imax
0-Imax
0-Imax

Units
sec
U1
sec
U1
sec
U2
sec
U2
sec
U2
sec

Not used

Not used

Maximum kW import sliding window demand


Timestamp
Maximum kvar import sliding window demand
Timestamp
Maximum kVA sliding window demand
Timestamp
Not used

0-Pmax

Not used

Not used

Maximum kW export sliding window demand


Timestamp
Maximum kvar export sliding window demand
Timestamp
Not used

0-Pmax

Not used

Not used

Not used

In Maximum ampere demand


Timestamp

0-Imax

0-Pmax
0-Pmax

U3
sec
U3
sec
U3
sec

0-Pmax

U3
sec
U3
sec

U2
sec

Type
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

Notes
1
1

29

Point ID
0xB480
0xB481
0xB482
0xB483
0xB484
0xB485
0xB486
0xB487
0xB500
0xB501
0xB502
0xB503
0xB504
0xB505
0xB506
0xB507
0xB580
0xB581
0xB582
0xB583
0xB584
0xB585
0xB586
0xB587
0xB4C0
0xB4C1
0xB4C2
0xB4C3
0xB4C4
0xB4C5
0xB4C6
0xB4C7

Description
TOU Maximum Demand Register #1 EH
Tariff #1 maximum demand
Timestamp
Tariff #2 maximum demand
Timestamp
Tariff #3 maximum demand
Timestamp
Tariff #4 maximum demand
Timestamp
TOU Maximum Demand Register #2 EH
Tariff #1 maximum demand
Timestamp
Tariff #2 maximum demand
Timestamp
Tariff #3 maximum demand
Timestamp
Tariff #4 maximum demand
Timestamp
TOU Maximum Demand Register #3 EH
Tariff #1 maximum demand
Timestamp
Tariff #2 maximum demand
Timestamp
Tariff #3 maximum demand
Timestamp
Tariff #4 maximum demand
Timestamp
TOU Maximum Demand Register #4 EH
Tariff #1 maximum demand
Timestamp
Tariff #2 maximum demand
Timestamp
Tariff #3 maximum demand
Timestamp
Tariff #4 maximum demand
Timestamp

Options/Range/Format
0-Pmax
0-Pmax
0-Pmax
0-Pmax

0-Pmax
0-Pmax
0-Pmax
0-Pmax

0-Pmax
0-Pmax
0-Pmax
0-Pmax

0-Pmax
0-Pmax
0-Pmax
0-Pmax

Units

Type

R/W

U3
sec
U3
sec
U3
sec
U3
sec

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R

U3
sec
U3
sec
U3
sec
U3
sec

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R

U3
sec
U3
sec
U3
sec
U3
sec

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R

U3
sec
U3
sec
U3
sec
U3
sec

UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32

R
R
R
R
R
R
R
R

Notes

NOTES:
Power demand readings are only available in the PM130EH meters.
1

Voltage readings: when the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages.

For volts, amps, power and frequency scales and units, refer to Section 5 Data Scales and Units.

30

4.4 Device Control and Status Registers


Point ID
Description
Options/Range
Device Authorization Register
0xFF00 When write: 4-digit password. When read: 0 = access 0-9999 (write)
permitted, -1 = authorization required.
0/-1 (read)
Remote Relay Control
0x8400-0x8401
Remote relay command
0 = remove a remote command
1 = operate relay
2 = remove a remote command and
release a locally latched relay
+0 RO1 Control
+1 RO2 Control
Device Reset/Clear Registers
0xA000 Clear total energy registers
0
0xA001 Clear total maximum demand registers
0 = Clear all maximum demands
1 = Clear power demands EH
2 = Clear volt, ampere and
harmonic demands
0xA002 Clear TOU energy registers EH
0
0xA003 Clear TOU maximum demand registers EH
0
0xA004 Clear pulse counters
0 = Clear all counters
1-4 = Clear counter #1-#4
0xA005 Clear Min/Max log
0
Device Status Registers
0x7D00 Relay status RO1-RO2 (bitmap)
0x0000-0x0003
0x7D01 Event flags (bitmap) EH
0x0000-0x00FF
0x7D02 Digital (status) inputs DI1-DI2
0x0000-0x0003
0x7D03 Present setpoint status SP1-SP16 (bitmap)
0x0000-0xFFFF
0x7D06 Current serial port number
Alarm Notification Registers
0x7E00 Setpoint alarm status SP1-SP16 (bitmap). Nonvolatile
register that keeps the status of the operated
setpoints.

0x7E01 Self-check alarm status (device diagnostics).


Nonvolatile register that keeps the status of the
internal device diagnostics.

Units

Type

R/W

INT16

R/W

UINT16

UINT16
UINT16

W
W

UINT16
UINT16
UINT16

W
W
W

UINT16

UINT16
UINT16
UINT16
UINT16

R
R
R
R

0=COM1, 1=COM2

UINT16

0x0000-0xFFFF

UINT16

R/W

F23

UINT16

R/W

Notes

Bits set to 1 indicate closed relay contacts.


Bits set to 1 indicate closed input contacts.
Bits set to 1 indicate operated (activated)
setpoints.

When read: Bits set to 1 indicate that the


designated setpoint have been operated at
least once since the alarm bits were reset.
When written: Bits preset to 0 clear
corresponding alarms, Bits set to 1 have no
effect.
When read: Bits set to 1 indicate that the
designated diagnostics failed at least once
since the alarm bits were reset.
When written: Bits preset to 0 clear
corresponding alarms; bits set to 1 have no

31

Point ID

Description

Options/Range

Units

Type

R/W

Notes
effect.

32

4.5 Device Setup Registers


Address
Description
Device Identification
0x7F00-0x7F01 Instrument options
0xFF43 Device model ID
Factory Device Settings
0xFF40-0xFF42
+0 I1-I3 input overload
+1 I1-I3 input range
+2 V1-V3 input range
Communication Ports Setup
0x8500-0x851F
+0 Communication protocol

+1 Interface
+2 Device address

+3 Baud rate

+4 Data format
+5 Flow control
+6 RTS mode

+7
+8-15
0x8500-0x850F
0x8510-0x851F

ASCII compatibility mode


Reserved
COM1 Setup
COM2 Setup

Options/Range

Units

F28
17210=PM130P, 17230=PM130EH

200
1, 5
690, 120 (option U)

COM1: 0=SATEC ASCII, 1=Modbus


RTU, 2=DNP3.0, 4=DTE,
COM2: 0=SATEC ASCII, 1=Modbus
RTU, 2=DNP3.0, 5=Profibus DP
COM1: 2=RS-485,
COM2: 0=RS-232, 1=RS-422,
2=RS-485, 6=Ethernet, 7=Profibus
SATEC ASCII: 0-99
Modbus RTU: 1-247
DNP3.0: 065532
Profibus DP: 0-126
1=300 bps, 2=600 bps, 3=1200
bps, 4=2400 bps, 5=4800 bps,
6=9600 bps, 7=19200 bps,
8=38400 bps, 9=57600 bps,
10=115200 bps
0=7 bits/even parity,
1=8 bits/no parity,
2=8 bits/even parity
0=no flow control
1=software (XON/XOFF)
2=hardware (CTS)
0=not used,
1=RTS is permanently asserted
2=RTS is asserted during the
transmission
0=disabled, 1=enabled

%
A
V

Type

R/W

Notes

UINT16
UINT16

R
R

UINT16
UINT16
UINT16

R
R
R

UINT16

R/W

UINT16

R/W

UINT16

R/W

UINT16

R/W

UINT16

R/W

UINT16

R/W

N/A for COM1 (read as 65535)

UINT16

R/W

N/A for COM1 (read as 65535)

UINT16
UINT16

R/W
R

Does not limit the 690V input range

33

Address
Basic Setup
0x8600-0x8614
+0
+1
+2
+3

+4
+5-7
+8
+9-10
+11
+12

Description

Options/Range

Units

Type

R/W

Wiring mode
PT ratio
CT primary current
Power block demand period

F2
10 to 65000
1 to 50,000
1,2,3,5,10,15,20,30,60 min,
255 = external synchronization

0.1
A
min

UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W

0 to 1800

sec

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W
R/W
R/W

UINT16
UINT16

R/W
R/W

UINT16

R/W

UINT16

R/W

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W
R/W
R/W

EH

Volt/ampere demand period


Reserved
Number of blocks in a sliding window
Reserved
Nominal line frequency
Maximum demand load current

EH

+13-19 Reserved
+20 PT ratio multiplication factor
Device Options Setup
0x8700-0x870A
+0 Power calculation mode
+1 Energy roll value
+2
+3-9
+10
+11
+12-13
+14

EH

Phase energy calculation mode EH


Reserved
Energy LED test mode EH
Starting voltage, percent of FS voltage
Reserved
Device resolution (see Section 5 for details)

1 to 15
25, 50, 60, 400
0 to 50,000 (0 = CT primary
current)

Hz
A

1, 10

0=using reactive power: S=f(P,Q),


1=using non-active power:
Q=f(S,P)
0=1104, 1=1105, 2=1106,
3=1107, 4=1108, 5=1x109
0=disabled, 1=enabled
0=disabled, 1=Wh test, 2=varh test
15-50
0.1%
0 = Low resolution, 1 = High
resolution

Digital Inputs Setup


0x8900-0x8904
+0
+1
+2
+3
+4

Status inputs (bitmap)


Pulse inputs (bitmap)
Not used
External demand synchronization input (bitmap)
Time synchronization input (bitmap)

0x0003
0x0003
0
0x0001=DI1
0x0001=DI1, 0x0002=DI2,
0x0004=DI3, 0x0008=DI4

UINT16
UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W
R/W

Notes

If the external synchronization is selected, the


DI1 input is considered a pulse or KYZ input.
The pulse edge restarts the power demand
block accumulation interval. E
Read as 65535
E

Read as 65535

Read as 65535

Read as 65535
LED pulse rate is 10,000 pulses/kWh
Default 1.5%
Read as 65535
Default 0

Obsolete registers. Refer to Digital Inputs


setup registers 0X9600-0X9607
Ignored when written
Ignored when written
Ignored when written

Alarm/Event Setpoints Setup


0x8200-0x825F

34

Address
+0
+1
+2
+3
+4,5
+6,7
0x8200-0x8205
0x8206-0x820B
0x820C-0x8211
0x8212-0x8217
0x8218-0x821D
0x821E-0x8223
0x8224-0x8229
0x822A-0x822F
0x8230-0x8235
0x8236-0x820B
0x823C-0x8241
0x8242-0x8247
0x8248-0x824D
0x824E-0x8253
0x8254-0x8259
0x825A-0x825F
Local Settings
0x8C00-0x8C0A
+0

Description
Trigger parameter ID
Action ID
Operate delay
Release delay
Operate limit
Release limit
Setpoint #1
Setpoint #2
Setpoint #3
Setpoint #4
Setpoint #5
Setpoint #6
Setpoint #7
Setpoint #8
Setpoint #9
Setpoint #10
Setpoint #11
Setpoint #12
Setpoint #13
Setpoint #14
Setpoint #15
Setpoint #16

Options/Range
F12
F14
0-9999
0-9999
See Section 4.2
See Section 4.2

Daylight savings time (DST) option

+1 DST start month


+2 DST start week of the month
+3 DST start weekday
+4 DST end month
+5 DST end week of the month
+6 DST end weekday
+7 Clock synchronization source
+8 Country code
+9 DST start hour
+10 DST end hour
TOU Daily Profile Setup EH
0x9000-0x907F
+0 1st tariff change

Units

Type
UINT16
UINT16
UINT16
UINT16
UINT32
UINT32

R/W
R/W
R/W
R/W
R/W
R/W
R/W

0 = DST disabled (standard time


only), 1 = DST enabled
1-12
1-4 = 1st, 2nd, 3rd and 4th week,
5=the last week of the month
1-7 (1=Sun, 7=Sat)
1-12
1-4=1st, 2nd, 3rd and 4th week,
5=the last week of the month
1-7 (1=Sun, 7=Sat)
1-4 = DI1-DI4, 32767 = meter
clock

UINT16

R/W

UINT16
UINT16

R/W
R/W

UINT16
UINT16
UINT16

R/W
R/W
R/W

UINT16
UINT16

R/W
R/W

ITU calling number


1-6
1-6

UINT16
UINT16
UINT16

R/W
R/W
R/W

F10

UINT16

R/W

0.1 sec
0.1 sec

Notes

Scaled value
Scaled value

A DI input is considered a pulse or KYZ input.


The pulse edge adjusts the clock at the
nearest whole minute.

35

Address

Description
+1 2nd tariff change
+2 3rd tariff change
+3 4th tariff change
+4 5th tariff change
+5 6th tariff change
+6 7th tariff change
+7 8th tariff change
0x9000-0x9007 Daily profile #1: Season 1, Day type 1
0x9008-0x900F Daily profile #2: Season 1, Day type 2
0x9010-0x9017 Daily profile #3: Season 1, Day type 3
0x9018-0x901F Daily profile #4: Season 1, Day type 4
0x9020-0x9027 Daily profile #5: Season 2, Day type 1
0x9028-0x902F Daily profile #6: Season 2, Day type 2
0x9030-0x9037 Daily profile #7: Season 2, Day type 3
0x9038-0x903F Daily profile #8: Season 2, Day type 4
0x9040-0x9047 Daily profile #9: Season 3, Day type 1
0x9048-0x904F Daily profile #10: Season 3, Day type 2
0x9050-0x9057 Daily profile #11: Season 3, Day type 3
0x9058-0x905F Daily profile #12: Season 3, Day type 4
0x9060-0x9067 Daily profile #13: Season 4, Day type 1
0x9068-0x906F Daily profile #14: Season 4, Day type 2
0x9070-0x9077 Daily profile #15: Season 4, Day type 3
0x9078-0x907F Daily profile #16: Season 4, Day type 4
TOU Calendar Setup EH
0x9100-0x923F
+0-9 Calendar entry record
+0 Daily profile

+1 Week of month
+2
+3
+4
+5
+6
+7
+8-9
0x9100-0x9109
0x910A-0x9113
0x9114-0x911D

Weekday
Till Weekday
Month
Day of month
Till Month
Till Day of month
Reserved
Calendar entry #1
Calendar entry #2
Calendar entry #3

Options/Range
F10
F10
F10
F10
F10
F10
F10

0-3 = Season 1, Day types 0-3


4-7 = Season 2, Day types 0-3
8-11 = Season 3, Day types 0-3
12-15 = Season 4, Day types 0-3
0=all, 1=1st, 2=2nd, 3=3rd, 4=4th,
5=last week of the month
0=all, 1-7 (Sun=1, Sat=7)
0=all, 1-7 (Sun=1, Sat=7)
0=all, 1-12=January - December
0=all, 1-31=day 1-31
0=all, 1-12=January - December
0=all, 1-31=day 1-31

Units

Type
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

UINT16

R/W
R/W

UINT16

R/W

UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W
R/W
R/W
R/W

Notes

36

Address
Description
0x9236-0X923F Calendar entry #32
Summary Energy/TOU Registers Setup EH
0X9400-0X941F
+0 Not used
+1 Units of measurement

+2 Flags (bitmap)

+3 Not used
0X9400-0X9403 Register #1 Setup
0X9404-0X9407 Register #2 Setup
0X9408-0X940B Register #3 Setup
0X940C-0X940F Register #4 Setup
Summary Energy/TOU Registers Source Setup EH
0X9500-0X9517
+0 Energy source ID
+1 Target summary register number
+2 Multiplier
0X9500-0X9502 Energy Source #1
0X9503-0X9505 Energy Source #2
0X9506-0X9508 Energy Source #3
0X9509-0X950B Energy Source #4
Digital Inputs Setup
0X9600-0X960F
+0 Pulse mode
+1 Polarity
+2 De-bounce time, ms
+3 Reserved
0X9600-0X9603 DI1 Setup
0X9604-0X9607 DI2 Setup
0X9608-0X960B DI3 Setup
0X960C-0X960F DI4 Setup
Relay Outputs Setup
0X9700-0X970B
+0 Operation Mode
+1 Polarity

Options/Range

Units

0=none, 1=kWh, 2=kvarh, 3=kVAh,


4=m3, 5=CF (cubic feet), 6=CCF
(hundred cubic feet)
Bit 0=1 - TOU enabled
Bit 1=1 - Use profile enabled
Bit 2=1 - Max. Demand profile
enabled
Bit 3=1 - Summary (total) profile
enabled
0

F11
0-7 = register #1-#8
0-1000000

0 = pulse, 1 = KYZ
0 = normal, 1 = inverting
1-100

0=latched, 1=unlatched,
2=pulse, 3=KYZ
Bit 0 Polarity:

0.001

Type

R/W

UINT16
UINT16

R/W
R/W

UINT16

R/W

UINT16

R/W

UINT16
UINT16
INT32

R/W
R/W
R/W

UINT16
UINT16
UINT16

R/W
R/W
R/W

UINT16

R/W

UINT16

R/W

UINT16

R/W

Notes

Debounce time will be the same for both


inputs

37

Address

+2
+3
+4
+5
0X9700-0X9705
0X9706-0X970B

Description

Pulse width, ms
Pulse source ID EH
Units per pulse
Reserved
RO1 Setup
RO2 Setup

Options/Range
0=normal, 1=inverting,
Bit 1 - Retentive mode:
0=disabled, 1=enabled
1-1000
F17
1-10000

Units

x0.1

Type

R/W

UINT16
UINT16
UINT16
UINT16

R/W
R/W
R/W
R/W

Notes

38

4.6 Analog and Digital I/O Configuration


Address
Description
I/O Slots Configuration Info
0xF100-0xF12F
+0 I/O type
+1 Number of I/Os on the slot
+2 First I/O number on the slot
+3 Last I/O number on the slot
0xF100-0xF103 DI Slot Configuration
0xF104-0xF107 RO Slot Configuration
0xF108-0xF10B AI/AO Slot Configuration
0xF10C-0xF12F Reserved
I/O Type Info
0xF200-0xF23F
+0 Number of I/O slots of this type
+1 Total number of I/O's of this type
+2 Number of I/O's in the slot
+3 Not used
0xF200-0xF203 DI Type Info
0xF204-0xF207 RO Type Info
0xF208-0xF20B AI Type Info
0xF20C-0xF20F AO Type Info
0xF210-0xF23F Reserved

Options/Range

Units

Type

R/W

F29
0-2
0
0-1

UINT16
UINT16
UINT16
UINT16

R
R
R
R

0-1
0-4
0-4
0

UINT16
UINT16
UINT16
UINT16

R
R
R
R

Notes

39

5 Data Scales and Units


Code
Data Scales
Vmax
Imax
Pmax

Condition

Wiring 4LN3, 3LN3, 3BLN3


Wiring 4LL3, 3LL3, 3BLL3,
3OP2, 3OP3, 3DIR2
Fmax
Nominal frequency 25, 50
or 60 Hz
Nominal frequency 400Hz
Data Units Low Resolution Option
U1
U2
U3
Data Units High Resolution Option
U1
PT Ratio = 1
PT Ratio > 1
U2
U3
PT Ratio = 1
PT Ratio > 1

Value/Range
Voltage scale PT Ratio, V
Current scale CT Ratio, A
Vmax Imax 3, W
Vmax Imax 2, W

Notes
2
1, 3
4

100 Hz
500 Hz
1V
1A
1kW/kvar/kVA
0.1V
1V
0.01A
1W/Var/VA
1kW/kvar/kVA

See Device Options Setup for information on selecting the device resolution option.
1 CT Ratio = CT primary current/CT secondary current
2 The default Voltage scale is 144V (120V + 20%). You can change it via the Device Data Scale setup (see Section 4.1) or via

the Device Options setup in PAS.


3 The default Current scale is 2 CT secondary current (2.0A with 1A secondaries, 10.A with 5A secondaries). You can change

it via the Device Data Scale setup (see Section 4.1) or via the Device Options setup in PAS.

4 Pmax is rounded to whole kilowatts. With PT=1.0, if Pmax is greater than 9,999,000 W, it is truncated to 9,999,000 W.

40

6 Data Formats
Format Code
Timestamp
F1
Wiring Mode
F2

Value

Description

Notes

Local time in a UNIX-style format. Represents the number


of seconds since midnight (00:00:00), January 1, 1970.
The time is valid after January 1, 2000.
0
1
2
3
4
5
6
8
9

3OP2 - 3-wire open delta using 2 CTs (2 element)


4LN3 - 4-wire WYE using 3 PTs (3 element), line-toneutral voltage readings
3DIR2 - 3-wire direct connection using 2 CTs (2 element)
4LL3 - 4-wire WYE using 3 PTs (3 element), line-to-line
voltage readings
3OP3 - 3-wire open delta using 3 CTs (2 1/2 element)
3LN3 - 4-wire WYE using 2 PTs (2 1/2 element), line-toneutral voltage readings
3LL3 - 4-wire WYE using 2 PTs (2 1/2 element), line-toline voltage readings
3BLN3 - 3-wire broken delta using 2 PTs (2 1/2 element),
line-to-neutral voltage readings
3BLL3 - 3-wire broken delta using 2 PTs (2 1/2 element),
line-to-line voltage readings

TOU Tariff Change Time


F10
Bits 8:15 = 0-7
Tariff number #1-#8
Bits 2:7 = 0-23
Tariff start hour
Bits 0:1 = 0-3
Tariff start quarter of an hour
Summary/TOU Energy Register Source ID
F11
0x0000
None
0x0700-0x0703
Pulse input DI1-DI4
0x1700
kWh import
0x1701
kWh export
0x1704
kvarh import
0x1705
kvarh export
0x1708
kVAh total
Setpoint Trigger Parameters ID
F12
0x0000
None (condition is not active)
Status Inputs
0x0600
Status input #1 ON
0x0601
Status input #2 ON
0x0602
Status input #3 ON
0x0603
Status input #4 ON
0x8600
Status input #1 OFF
0x8601
Status input #2 OFF
0x8602
Status input #3 OFF
0x8603
Status input #4 OFF
0x0701
Pulse input #2
Relays
0x0800
Relay #1 ON
0x0801
Relay #2 ON
0x8800
Relay #1 OFF
0x8801
Relay #2 OFF
Phase Reversal
0x8901
0x8902
0x0A00
0x0A01
0x0A02
0x0A03
0x0E00
0x8D00
0x0E01
0x8D01
0x0E07
0x0E08

Positive phase rotation reversal


Negative phase rotation reversal
Pulse Counters
High pulse counter #1
High pulse counter #2
High pulse counter #3
High pulse counter #4
1-Cycle Values on any Phase
High voltage
Low voltage
High current
Low current
High voltage THD EH
High current THD EH

41

Format Code

Value
0x0E09
0x0E0A
0x1002
0x9002
0x1003
0x1004
0x1103
0x1104
0x1105
0x9103
0x9104
0x9105
0x1300
0x9200
0x1301
0x9201
0x1406
0x1407
0x1408
0x1409
0x1402
0x9404
0x9405
0x1501
0x1502
0x9502

0x1600
0x1601
0x1602
0x1603
0x1604
0x1605
0x1606
0x1608
0x1609
0x160B
0x160F
0x1611
0x1612
0x1614
Setpoint Action ID
F14
0x0000
0x3000
0x3001
0x3100
0x3101
0x4000
0x4001
0x4002
0x4003
0x4400
0x4401
0x4402
0x4403
Counter Source ID
F16
0x0000
0x0001-0x0002
Relay Output Pulse Source ID
F17
0x0000
0x0400
0x0401

Description
High K-Factor EH
High current TDD EH
1-Cycle Auxiliary Values
High frequency
Low frequency
High voltage unbalance
High current unbalance
1-Sec Phase Values
High I1 current
High I2 current
High I3 current
Low I1 current
Low I2 current
Low I3 current
1-Sec Values on any Phase
High voltage
Low voltage
High current
Low current
1-Sec Total Values
High total kW import
High total kW export
High total kvar import
High total kvar export
High total kVA
Low total PF Lag
Low total PF Lead
1-Sec Auxiliary Values
High neutral current
High frequency
Low frequency
Present Demands
High V1/V12 Volt demand
High V2/V23 Volt demand
High V3/V31 Volt demand
High I1 Ampere demand
High I2 Ampere demand
High I3 Ampere demand
High block kW import demand EH
High block kVA demand EH
High sliding window kW import demand EH
High sliding window kVA demand EH
High accumulated kW import demand EH
High accumulated kVA demand EH
High predicted kW import demand EH
High predicted kVA demand EH
No action
Operate Relay #1
Operate Relay #2
Release latched Relay #1
Release latched Relay #2
Increment counter #1
Increment counter #2
Increment counter #3
Increment counter #4
Count operating time using
Count operating time using
Count operating time using
Count operating time using

counter
counter
counter
counter

Notes

#1
#2
#3
#4

None
Pulse input DI1-DI2
None
kWh import pulse EH
kWh export pulse EH

42

Format Code

Value
0x0403
0x0404
0x0405
0x0406
AO Output Parameters ID
F18
0x0000
0x0C00
0x0C01
0x0C02
0x0C03
0x0C04
0x0C05
0x0C1E
0x0C1F
0x0C20
0x0F00
0x0F01
0x0F02
0x0F03
0x0F04
0x0F05
0x1001
0x1002
0x1100
0x1101
0x1102
0x1103
0x1104
0x1105
0x111E
0x111F
0x1120
0x1400
0x1401
0x1402
0x1403
0x1404
0x1405
0x1501
0x1502
0x160F
0x1610
0x1611
0x161A
0x161B
Device Diagnostics
F23
Bit 0
Bit 1
Bit 2 = 1
Bit 3 = 1
Bit 4 = 1
Bit 5 = 1
Bit 6
Bit 7 = 1
Bit 8 = 1
Bit 9 = 1
Bit 10 = 1
Bit 11 = 1
Bit 12
Bit 13

Description

Notes

kvarh import pulse EH


kvarh export pulse EH
kvarh total pulse EH
kVAh pulse EH
None (output disabled)
1-Cycle Phase Values
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
V12 Voltage
V23 Voltage
V31 Voltage
1-Cycle Total Values
Total kW
Total kvar
Total kVA
Total PF
Total PF Lag
Total PF Lead
1-Cycle Auxiliary Values
In Current
Frequency
1-Sec Phase Values
V1/V12 Voltage
V2/V23 Voltage
V3/V31 Voltage
I1 Current
I2 Current
I3 Current
V12 Voltage
V23 Voltage
V31 Voltage
1-Sec Total Values
Total kW
Total kvar
Total kVA
Total PF
Total PF Lag
Total PF Lead
1-Sec Auxiliary Values
In Current
Frequency
Present Demands EH
Accumulated kW import demand
Accumulated kvar import demand
Accumulated kVA demand
Accumulated kW export demand
Accumulated kvar export demand

Reserved
Reserved
RAM/Data error
CPU watchdog reset
Sampling fault
CPU exception
Reserved
Software watchdog reset
Power down
Device reset
Configuration reset
RTC fault
Reserved
Reserved

43

Format Code

Value
Bit 14
Bit 15 = 1
Instrument Options
F28
Bit 0=1
Bit 1=1
Bits 2-5
Bit 6=1
Bit 7=1
Bit 8=1
Bit 9=1
Bit 10=1
Bit 11=1
Bit 12=1
Bit 13=1
Bit 14=1
Bit 15
Bits 16-18
Bits 19-22
Bits 23-24
Bits 25-29
Bits 30-31
I/O Slot Types
F29
DI
DRY
RO
AI
1 mA
AI
0-20 mA
AI
4-20 mA
AI
0-1 mA
AO
1 mA
AO
0-20 mA
AO
4-20 mA
AO
0-1 mA
Empty slot
Reset/Clear Function
F30
Function Target
1
0
2
0=all maximum
demands
1=power
demands EH
2=volt, ampere
demands
3
0
4
0
5
0=all counters
1-4=counter
#1-#4
6
0
Basic Setup Parameters ID
F31
W40
U14
I17
D11
F47
C12
Q51
Q52
Q60

Description

Notes

Reserved
EEPROM fault
120V Option
690V Option
Reserved
Analog output 0/4 or 4/20mA
Analog output 0-1mA
Analog output 1mA
RO option
DI option
Reserved
Setup is secured by a password (authorization required)
Reserved
Reserved
Reserved
Number of RO - 1
Number of DI 1
Number of AO - 1
Reserved
Reserved
00000000B
00100000B
01010000B
01010001B
01010010B
01010011B
01100000B
01100001B
01100010B
01100011B
11111111B

Clear total energy registers EH


Clear total maximum demand registers

Clear TOU energy registers EH


Clear TOU demand registers EH
Clear pulse counters
Clear Min/Max log
Wiring mode
PT ratio
CT primary current
Power block demand period EH
The number of blocks in a sliding window
Volt/ampere demand period
Nominal frequency
Maximum demand load current
PT ratio multiplication factor

EH

NOTES:
1

Analog Outputs

1) For bi-directional analog output (1 mA), the zero scale setup corresponds to the center (0 mA) of the scale range, and the
direction of the current matches the sign of the output parameter. Unsigned parameters are output within the current range 0
to +1 mA and can be scaled as in the case of single-ended analog output (0-1 mA).
For signed values, such as powers and signed power factor, the scale is always symmetrical with regard to 0 mA, and the full
scale corresponds to +1 mA output for positive readings and to -1 mA output for negative readings. The zero scale (0 mA

44

output) is permanently set in the instrument to zero for all parameters except the signed power factor for which it is set to
1.000 (see Note 2). In write requests, the zero scale is ignored.
2) Except for the signed power factor, the setup scale is continuous within the entire value range. For signed power factor, the
setup scale is broken at +1.000 in order to provide continuous output current when the power factor changes close to 1.000.
The setup scale is symmetrical in the range of -0 to +0 with a center at 1.000 (-1.000 is assumed to be equal to +1.000).
Negative power factor is output as -1.000 minus measured value, and non-negative power factor is output as +1.000 minus
measured value. To set the entire range for power factor from-0 to +0, the scales would be specified as -0 to 0. Because of the
fact that negative zero may not be transmitted through communications, the value of -0.001 is used to specify the scale of -0,
and both +0.001 and 0.000 are used to specify the scale of +0.
2

Phase Reversal Trigger

The setpoint is operated when the actual phase sequence does not match the designated phase rotation order.