Medium Voltage Distribution

Vacuum
Type VA, VAA, VAH, VXA, VXB, VXC

circuit-breaker

Selection List

VA Auswahlliste EN 030709.indd 1

5/12/2011 10:48:31 AM

Delivery conditions The General Conditions of Delivery as amended shall apply. Illustrations The illustrations are not bin-

VA Auswahlliste EN 030709.indd 2

5/12/2011 10:48:32 AM

VA

Table of contents

Introduction........................................................................................... 4 Mechanical design................................................................................ 5 Optional equipment.............................................................................. 7 Vacuum circuit-breaker with reclosing facility (auto-reclosure)...... 8 Specifications and tests. ...................................................................... 9 Specifications, Tests, Environmental and operating conditions........ 9 Numbers of breaking operations up to the summation current limit........... 10 Vacuum tester VT. ............................................................................11 Selection tables. .................................................................................. 12 Vacuum circuit-breakers VA, VAA 12 kV. ...........................................12 Vacuum circuit-breakers VA, VAA 17.5 kV. ........................................14 Vacuum circuit-breakers VA, VAA 24 kV. ...........................................16 Vacuum circuit-breakers VA 36 kV.....................................................18 Vacuum circuit-breakers for railway applications VXA, B, 17.5 / 25 / 27.5 kV...20 Vacuum circuit-breakers for high numbers of switching operations VXC, 24 / 36 / 38 kV. .............................................................................22 Vacuum circuit-breakers for high currents VAH.................................24 Electric circuit diagrams ................................................................... 26 Vacuum circuit-breaker dimensions. ................................................................32 Transport............................................................................................. 50

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 3

5/12/2011 10:48:32 AM

VA

Introduction

General Description
VA and VAA vacuum circuitbreakers are front-mounted switches for application in medium-voltage indoor switchgear. They can be fixed installations in switchgear or can be mounted on a switchgear truck, a drawing-unit truck or a drawing unit. In railway applications, vacuum circuitbreakers VXA or VXB (single-/ two-pole units respectively) are used. VXC circuit-breakers which are designed for an especially high number of mechanical and electrical switching operations are suitable to operate electric melting furnaces. Vacuum circuit-breakers are capable of performing all switching operations and tasks encountered in industrial plants and distribution networks or in railway applications, especially for operation of: short-circuit currents underground and overhead lines motors transformers generators
VXA vacuum circuit-breaker Rated voltage 17.5 kV Rated short-circuit breaking current 31.5 kA

capacitors

Essential Features
High number of mechanical and electrical switching operations No critical current range Long service life High switching capacity reserve Minimum maintenance

VAA vacuum circuit-breakers Rated voltage 12 kV Rated short-circuit breaking current 25 kA

VA vacuum circuit-breakers Rated voltage 12 kV Rated short-circuit breaking current 50 kA

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 4

5/12/2011 10:48:34 AM

VA

Mechanical design

Application
Vacuum circuit-breakers are designed as front switches. The three-pole VA and VAA vacuum circuit-breakers master all switching cases occurring in medium-voltage systems. The VXA and VXB vacuum types satisfy specific circuit-breaker requirements. VXA vacuum circuit-breakers are single-pole, VXB types feature two poles, both types being mainly suited for railway applications. Threepole vacuum circuit-breakers VXC are used for extremely high operating frequencies, as are required e.g. for furnaces. Vacuum circuit-breakers can be fixed installations in switchgear or can be mounted on a drawing unit, a drawing-unit truck or a switchgear truck.

Design and method of operation


VA 12 kV - View: Operating and drive side

Each of the switch poles with 1 interrupter chamber per phase is fastened to a common base frame with 2 cast-resin post insulators. All drive components, auxiliary and release devices are located in the base frame which is designed as a closed housing. Vacuum circuit- breakers can be equipped with control switches, auxiliary releases, secondary releases and undervoltage releases, as required. Vacuum circuit-breakers are equipped with a snap-action mechanism with manually or electrically operated spring charging motor and can be equipped at choice with a reclosing facility (auto-reclosure). Power transmission between the energy-storing device and the switch poles which is required for switching ON and OFF is effected by means of an operating rod made of highquality glass-fibre reinforced insulating material which is largely free of constraints while the vacuum circuitbreaker is ON.

VA 12 kV - View: Pole sections with vacuum interrupter chambers

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 5

5/12/2011 10:48:36 AM

VA

Mechanical design (contd.)

Pole Section
The pole section is of extremely robust design. The solid support provides for a suspension free of external forces for the interrupter chamber. Due to this statically closed support system, the axial forces produced on closing and opening only act on the contact system, whereas the vacuum interrupter chamber remains free of constraints. The power transmission acts from the contact spring onto the moving contact via a lever system with pendulum rod to make sure the closing and opening forces are applied in precisely axial direction.

Drive Mechanism
The drive mechanism has been designed as a making/breaking spring mechanism. The closing spring of the making storedenergy mechanism is charged either via an electric motor installed in the drive housing or by hand using an insertable crank. If the electric motors power supply fails, the spring can still be charged at any time via the crank. The opening spring is charged during the closing operation (ON). Once closing is concluded, the closing spring - now discharged - can be charged again by the spring-charging motor automatically or by hand. In this state, the drive mechanism is ready to perform the operating sequence OtCO. The chargedclosing spring can eitherbe released by hand, by actuation of the ON pushbutton, or by a shunt closingrelease installed in the drive box. The opening procedure is initiated by actuation of the OFF pushbutton or via a shunt opening release, an undervoltage release or a secondary release.

VA pole section

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 6

5/12/2011 10:48:38 AM

VA

Optional equipment

Releases
Auxiliary release
(Shunt releases) The coil of the auxiliary release is supplied with exciter voltage from an auxiliary supply source via a release contact. Pulsing can be initiated by hand, via control switches, overcurrent releases or undervoltage releases. If AC voltage is supplied, a rectifier located in the switch housing is installed upstream of the coil. As the coil is designed for short-term excitation only, the exciter circuit is routed via an auxiliary switch contact controlled by the circuit- breaker shaft, thus - once released - interrupting the current circuit.

Secondary release
(Transformer-operated release) Secondary releases are used for automatic release of switching devices in case of short-circuits and overcurrent. Once the protector has reacted, the release is excited by the transformer current, thus causing the switch to be tripped. These releases are supplied for transformer secondary currents of 0.5 A and 5 A.

Undervoltage release
Undervoltage releases are suppliedby the auxiliary sourcepermanently. Whenever the auxiliary current is interrupted or its voltage drops essentially, the switching device is tripped straight away. If the undervoltage release is supplied by a voltage transformer located downstream of the switch, a holding device can be installed which prevents the switch from being released, when it is not yet closed completely.

Control Switches
Auxiliary switch
Auxiliary switches are always actuated directly by the switch shaft via an intermediate linkage, their position always corresponding to that of the main contacts. The circuitbreakers are equipped with an auxiliary switch with 12 contact elements on principle; 8 contact elements have been assigned to the internal switching operation (see circuit diagrams). For additional current circuits, up to 8 contact elements can be arranged additionally. Moreover, the switching device can be equipped with a mechanically time-delayed contact element (1-pole pulse contact, T 50 ms).

Push switches
The push switches are snapaction switches mounted to the drive mechanism. Unlike auxiliary switches, push switches are not necessarily dependent on the switching devices position, but are actuated e.g. via cams or via various elements attached to the switch. The control switches are wired to the terminal strip; on request, a plug-andsocket connection (with connector and connector base) is also available.

Chassis Frames
Chassis frames for circuitbreakers are manufactured of folded sheet metal or sectional steel, and are equipped with castors. Binding dimension drawings are available on request.

Surge Arresters
Surge arresters must be used to protect the high-voltage motor circuits against overvoltage. The following data are required to determine the surge arrester: motor rated voltage max. ambient temperature transformer neutral point earth fault duration
VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 7

5/12/2011 10:48:38 AM

VA

Vacuum circuit-breaker

with reclosing facility (auto-reclosure)

All vacuum circuit-breakers can be supplied with reclosing facility (KU).

Method of operation
If a short-circuit occurs, an overcurrent relay issues a pulse to the shunt opening release, after expiry of the preset instantaneous zone, switching the circuit-breaker OFF. Once the preset dead time has expired, an ON command is issued to the shunt closing release via a NO contact of the auto-reclosing relay. If the short-circuit is still present, another OFF command is issued by the overcurrent relay, and the circuit-breaker is switched off for good. The auto-reclosing relay does not issue another ON command. The vacuum circuit-breakers economic efficiency is based on its excellent maintenance characteristics. The interrupter chamber need not normally be replaced during the switching devices service life. The admissible numbers of switching operations at different breaking currents are indicated in the diagrams. The high value of the service life is considered in comparisons of economic efficiency with other switch principles, especially in applications requiring high operating frequencies. In other cases, maintenance of the drive mechanism and the expense required to this effect for electric isolation decisively affect availability and maintenance costs. The requirement of having a single inspection of the drive mechanism after 10,000 operating cycles or 20 years of operation means that maintenance expense is reduced to a minimum. The VXC vacuum circuit-breakers can be used for extremely high numbers of operating cycles, e.g. as furnace-type switches. After 25,000 switching operations, the drive mechanism should be checked and the vacuum interrupter chambers replaced at the same time. The mechanical service life of the VXC vacuum circuit-breaker is 75,000 operating cycles.

Rated operating sequences


Rated operating sequence
03 min CO 3 min CO 00,3s CO 3 min CO

Designation

Specifications Remarks
see Selection Tables see Selection Tables see Selection IEC Tables, column ANSI - Standard "with reclosing C37 facility"

without reclosing IEC 62271-100 facility with reclosing IEC 62271-100 facility

CO 15s CO 0-0,3s CO 15s - CO bis 0-0,3s CO 15s - CO 15s CO 15s CO 0-15s CO 15s CO - 15s CO 15s CO 0-15s CO 15s CO - 15s CO 15s CO reclosing cycles Thunderstorm cycle

ANSI - Standard on request C37 Customer specification on request

Thunderstorm Customer specification 15s - CO 15s CO - 15s cycle CO 15s - CO 15 CO C Switching ON at rated short-circuit making current C' Switching ON at rated current O Switching OFF at rated short-circuit breaking current

on request

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 8

5/12/2011 10:48:41 AM

VA

Specifications
and tests

Specifications

The three-pole vacuum circuit- breakers VA, VAA, VXC, VAH meet the specifications for AC switchgear for voltages above 1 kV in acc. with IEC 62271-100, and also comply to a large extent, regarding their switching and insulating level, with the requirements of ANSI C37... 1) The single-pole vacuum circuit-breaker VXA/VXB complies with the requirements regarding AC switching devices for voltages above 1 kV in acc. with IEC 62271-100 as well as with the railway standard EN 50152-1.

Tests

Vacuum circuit-breakers have proved their suitability in type tests and in comprehensive test series during the development phase. The tests were performed in the companys own high-performance test laboratories and in neutral institutes such as FGH and KEMA. The tests not only covered compliance with the specified type tests, but also various special requirements, the determination of service life characteristics for the interrupter chambers and the suitability in type-tested switchgear; moreover, complex tests in power supply systems were performed. Reliability, operating safety and the mechanical function of the switching devices were checked in endurance tests. 1) on request

Environmental and operating conditions

Circuit-breakers VA, VAA, VAH, VXA, VXB and VXC may only be operated under normal operating conditions according to IEC 60694. Operation under conditions deviating from these is only admissible upon consultation and with the approval of the manufacturer.

Rated voltage, insulating level, specifications


Voltage designation and insulating ability within the
Type designation

Rated voltage

kV

Rated lightning impulse withstand voltage


kV

Rated power frequency withstand voltage


kV

12

17 VA VAA VXC 24

4.76 7.2 12 13.8 15 17.5 15.4 24 25.8 27.6 36 38 38 17.5 25 27.5

60 60 75 95 95 95 110 125 150 125 170 150 200 170 170 250

19 20 28 38 38 38 50 50 60 60 70 80 80 70 70 105

36 38 17 25 27

VXA VXB

Ambient conditions
Ambient conditions
Temperature class: Minus 5 indoors optional: minus 25 indoors) Min./max. ambient temperature Average value over 24 hours (max.) Maximum installation altitude above sea-level higher installation altitudes possible on request) -5 / 40 C 35 C 1000 m

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 9

5/12/2011 10:48:41 AM

VA

Specifications
and tests (contd.)

Numbers of Breaking operations up to the summation current limit


The diagrams define exclusively the admissible summation current limit. They indicate whether the vacuum interrupter chambers need to be replaced. Depending on the rated normal voltage, not all the combinations shown may be possible. The data for the rated normal current and short-circuit opening current are indicated in the Selection Tables as of page 12. Depending on the rated normal
Rated normal current Ir 630 A, 1250 A, 1600 A, 2000 A, 2500 A 30 000 10 000 Number of breaking operations n 5000 1000 500 100 50 10

Vacuum circuit-breakers VA, VAA, VXA, VXB

Ir
Breaking current log Ia

ISC

Rated normal current Ir 1250 A, 2500 A 30 000 25 000 10 000 Number of breaking operations n 5000 1000 500 100 50 10

Vacuum circuit-breaker VXC

Vacuum circuit-breaker Typ VA


Ir
Breaking current log Ia

ISC

Ir [A]
25 31.5

Isc [kA]
40 50

Ir = Rated (normal) current [A] Isc = Rated short-circuit breaking current [kA]

630 1250 1600 2000 2500

Vacuum circuit-breaker Typ VAA


Ir [A]
16

Isc [kA]
20 25

630 1250

Vacuum circuit-breaker Typ VXC


Ir [A]
25

Isc [kA]
31.5

1250 2500

VA Auswahlliste EN

10

VA Auswahlliste EN 030709.indd 10

5/12/2011 10:48:41 AM

VA

Specifications
and tests (contd.)

Vacuum tester VT 60 (Optional)


The vacuum tester VT 60 can be used to verify the dielectric strength of the contact gap of the vacuum circuit-breakers. This test is also used to determine indirectly whether the vacuum interrupter chambers are subject to an inside pressure of 10 -2 mbar. This unit enables the operator to determine easily and quickly, without disassembling the switching device, without extensive testing with a sufficient precision whether the vacuum level in the interrupter chamber still satisfies the requirements.

Special features
Straightforward handling Compact design (unit incl. case approx. in the size of a briefcase) Rugged design Low weight (approx. 8 kg) Low cost of investment

Physical bases of the test method


The dielectric strength of the vacuum contact gap depends on the chamber pressure P. Thus, the vacuum can be checked indirectly by means of voltage measurement. The test point A has been arranged conveniently so that it features a sufficient distance from point B (state with the chamber filledwith air), but so that the vacuum interrupter chamber is not subjected to an unnecessarily high load.

Performance of the audit


After connecting the vacuum tester VT 60 to the circuitbreaker to be checked, the test can be performed easily and quickly: Select the test voltage (40 or 60 kV) Switch on power supply; the red warning lamp Attention high voltage lights up. At the same time, turn knobs Test with your left and right hands to their stop in the direction of the arrow and wait for a few seconds for the lamps not faulty or faulty to light up. If the green lamp (not faulty) goes on, the test is completed, the vacuum chamber can be considered to be functional. If the red lamp goes on, the test is repeated twice. If the green lamp does not go on even after the 3rd attempt, the vacuum interrupter chamber is considered to be faulty. The vacuum tester VT 60 thus permits straightforward, quick and reliable testing of highquality switching devices.

Technical data of vacuum tester VT 60


System voltage Dielectric strength depending on the chamber pressure PChamber pressure Po Atmospheric pressure Pp Chamber pressure on passing the voltage test Ud Disruptive discharge voltage Up Test voltage Frequency of mains voltage Output voltage (0 10%) Ripple content of DC voltage Short circuit current Discharge time of high-voltage circuit LV fuse Weight incl. case Dimensions of case switchable 220 V WS, 120/130 V WS 50/60 Hz switchable 40 kV DC voltage 60 kV DC voltage 3% 33 mA 0.3 sec. Micro-fuse 0.5 A slow-blowing approx. 8 kg 350 x 315 x 175 mm

VA Auswahlliste EN

11

VA Auswahlliste EN 030709.indd 11

5/12/2011 10:48:41 AM

VA

Selection tables

Vacuum circuit-breakers VA, VAA 12 kV


Rated insulation level Rated short-time current Rated lightning impulse withstand voltage Rated power frequency withstand voltage Rated short-circuit breaking current Breaking current under out-of-phase conditions kA
5 6,3 8 8 10 12,5
5/12/2011 10:48:41 AM

Percentage value of the DC component

Rated short-circuit current at rated voltage in kV

mm
VAA VAA VAA VAA VAA VAA VAA VAA VA VA VA VA VA VA VA VA VA VA VA VA VA VA VA VA VA VA VA VA VA VA VA VA
*) 1)

kV
12

kV
28

kV
75

Hz
50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50 60 50/60 50/60 50/60 50/60

A
630 *) 630 *) 1250 1250 630 *) 630 *) 1250 1250 630 *) 1250 630 *) 1250 1600 2000 2500 3000 2900 3150 1250 1600 2000 2500 3000 2900 3150 1250 1600 2000 2500 3000 2900 3150

kA
50/52

3s kA
20

7.2 12 kA kA
20 20

%
40

A
25

506/12 506/12 5012/12 5012/12 636/12 636/12 6312/12 6312/12 806/12 8012/12 806/12 8012/12 8016/12 8020/12 8025/12 8031/12 8031/12 8031/12 10012/12 10016/12 10020/12 10025/12 10031/12 10031/12 10031/12 12512/12 12516/12 12520/12 12525/12 12531/12 12531/12 12531/12

160 210 160 210 160 210 160 210 160 160 210 210 210 210 210 210 210 275 210 210 210 210 210 210 275 210 210 210 210 210 210 275 12 28 75 12 28 75 12 28 75 12 28 75 12 28 75

63/65

25

25

25

40

25

80/82

31,5

31,5 31,5

38

25

80/85

31,5/34

34

31,5

41

25

10 A for transformers in no-load state

50/60 50 60 50/60 50/60 50/60 50/60 50/60 50 60 50/60

100/104

40

40

40

41

25

125/130

50

50

50

40

25

promised also for 800 A in case of class minus 25 indoors: extend closing time and opening time by 3 ms 2) admissible tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report

12

VA Auswahlliste EN 030709.indd 12

Low ind. currents A

Rated frequency

Type

Cable breaking current

Rated (normal) current

Rated peak withstand current at 50/60 Hz

Pole center spacing

Rated voltage

VA Auswahlliste EN

VA

Selection tables (contd.)

Rated operating sequence O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO

Switching operations without inspection with rated (normal) current mechanical electrical

Operating times with release 25 W 160 W 160 W Min./max. opening time2) Min./max. closing time2) Min./max. opening time

Command times with release 25 W160 W160 W Charging time for motor drive mechanism

O - 0.3 s - CO - 15 s - CO

with rated short-circuit current

Interrupter chamber

CO - 15 s - CO

Arc duration

Partitions

ms
10000 30000 10000 100 45/65

ms
31/50

ms
35/70

ms
6 bis 12

ms
50

ms
20

ms
20

s
5

10000

30000

10000

100

45/65

31/50

35/70

6 bis 12

50

20

20

10000

30000

10000

100

45/65

31/50

35/70

6 bis 12

50

20

20

9 9 9 9 9 12 12 12 12 12 9 9 12

10000

30000

10000

100

45/65

30/50

35/70

6 bis 12

50

20

20

10000

30000

10000

100

45/65

30/50

35/70

6 bis 12

50

20

20

12 12 12 12 12 12 12

10000

30000

10000

100

45/65

30/50

35/70

6 bis 12

50

20

20

12 12 12 12

Weight kg
105 105 115 115 115 115 115 125 125 140 140 140 115 115 125 125 140 140 140 125 125 125 125 140 140 140

Drive

OFF

OFF

ON

VA Auswahlliste EN

13

VA Auswahlliste EN 030709.indd 13

5/12/2011 10:48:42 AM

VA

Selection tables (contd.)

Vacuum circuit-breakers VA, VAA 17.5 kV


Rated insulation level Rated lightning impulse withstand voltage Rated power frequency withstand voltage
Rated shortcircuit breaking current

Rated peak withstand current at 50/60 Hz

Rated short-circuit current at rated voltage in kV

Percentage value of the DC component

Rated short-time current

mm
VAA VAA VAA VAA VAA VAA VAA VAA VAA VAA VAA VAA VA VA VA VA VA VA VA VA VA VA VA VA VA VA
*) 1)

kV

kV

kV

Hz
50/60 50/60

A
630 *) 630 *) 630 *) 1250 1250 1250 630 *) 630 *) 630 *) 1250 1250 1250 2000 1250 1250 1600 1600 2000 2000 2500 2500 3000 2900 3150 2000 2500

kA

3s kA

15 17.5 kA kA

Low ind. currents A


10 A for transformers in noload state

Rated frequency

Type

506/17 506/17 506/17 5012/17 5012/17 5012/17 636/17 636/17 636/17 6312/17 6312/17 6312/17 6320/17 8012/17 8012/17 8016/17 8016/17 8020/17 8020/17 8025/17 8025/17 8031/17 8031/17 8031/17 10020/17 10025/17

160 210 275 160 210 275 160 210 275 160 210 275 210 210 275 210 275 210 275 210 275 210 210 275 210 210 17 38 95 17 38 95 17 38 95 17 38 95

50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50 60 50/60 50/60 50/60

50/52

20

20

40

31.5

63/65

25

25

40

31.5

80/82

31.5

31.5

41

31.5

80/82

31.5

31.5

42

31.5

100/104

40

40

41

31.5

promised also for 800 A in case of class minus 25 indoors: extend closing time and opening time by 3 ms 2) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report

14

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 14

Breaking current under out-of-phase conditions kA


5 6,3 8 8 10
5/12/2011 10:48:42 AM

Cable breaking current

Rated (normal) current

Pole center spacing

Rated voltage

VA

Selection tables (contd.)

Rated operating Number of operating Operating times sequence cycles without overhaul with release mechanical electrical 25 W 160 W 160 W O - 3 min - CO - 3 min - CO with rated (normal) current O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO with rated short-circuit current

Command times with release 25 W 160 W 160 W Charging time for motor drive mechanism

Interrupter chamber

Drive mechanism

Min./Max. opening time 2)

Min./Max. opening time 2)

Min./Max. closing time 2)

CO - 15 s - CO

Arc duration

Partitions

ms

ms

ms

ms

ms

ms

ms

10000

30000

10000

100

45/65

31/50

35/70

6 to 14

50

20

20

10000

30000

10000

100

45/65

31/50

35/70

6 to 14

50

20

20

12 9 9 9 10000 30000 10000 100 45/65 30/50 35/70 6 to 14 50 20 20 9 12 12 12 12 12 10000 30000 10000 100 45/65 30/50 35/70 6 to 14 50 20 20 12 12 10000 30000 10000 100 45/65 30/50 35/70 6 to 14 50 20 20 12 12

VA Auswahlliste EN

15

VA Auswahlliste EN 030709.indd 15

5/12/2011 10:48:42 AM

Weight kg
105 105 130 115 115 115 115 125 125 125 125 140 140 140 125 125

OFF

OFF

ON

VA

Selection tables (contd.)

Vacuum circuit-breakers VA, VAA 24 kV


Rated peak withstand current at 50/60 Hz Rated insulation level Rated lightning impulse withstand voltage Rated power frequency withstand voltage Rated (normal) current
Rated shortcircuit breaking current

Rated short-circuit current at rated voltage in kV

Percentage value of the DC component

Rated short-time current

mm
VAA VAA VAA VAA VAA VAA VAA VAA VAA VAA VA VA VA VA VA VA VA VA
*) 1)

kV
24

kV
50

kV
125

Hz
50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60

A
630 *) 630 *) 1250 1250 630 *) 630 *) 1250 1250 1250 1250 1600 1600 2000 2000 2500 2000 2000 2500

kA
40/42

3s kA
16

24 kA kA
16

%
33

A
31.5

Low ind. currents A


10 A for transformers in noload state

Rated frequency

Type

406/24 406/24 4012/24 4012/24 506/24 506/24 5012/24 5012/24 6312/24 6312/24 6316/24 6316/24 6320/24 6320/24 6325/24 6325/24 8020/24 8025/24

210 275 210 275 210 275 210 275 210 275 210 275 210 275 275 210 275 275 24 50 125 24 50 125 24 50 125

50/52

20

20

33

31.5

50/60 50/60 50/60 50/60 50/60 50/60 50/60

63/65

25

25

41

31.5

80/82

31.5

31.5

41

31.5

promised also for 800 A adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report 2) Partitions required for installation of circuit-breaker in WBA

16

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 16

Breaking current under out-of-phase conditions kA



5/12/2011 10:48:42 AM

Cable breaking current

Pole center spacing

Rated voltage

VA

Selection tables (contd.)

with rated (normal) current

Rated operating Number of operating Operating times sequence cycles without overhaul with release mechanical electrical 25 W 160 W 160 W O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO Min./Max. closing time1) O - 0.3 s - CO - 15 s - CO Min./Max. opening time Min./Max. opening time with rated short-circuit current

Command times with release 25 W160 W160 W Charging time for motor drive mechanism

Interrupter chamber

Drive mechanism

CO - 15 s - CO

Arc duration

Partitions
-2) -2) -2) -2) 2)

ms
10000 30000 10000 100 45/65

ms
30/50

ms
35/65

ms
6 to 14

ms
50

ms

ms
20

s
5

10000

30000

10000

100

45/65

30/50

35/65

6 to 14

50

20

5 5 9 10000 30000 10000 100 45/65 30/50 35/65 6 to 14 50 20 20 9 12 12 12 12 10000 30000 10000 100 45/65 30/50 35/65 6 to 14 50 20 20 12 12 -2)

Weight kg
105 105 105 105 122 122 130 130 130 130

OFF

OFF

ON

VA Auswahlliste EN

17

VA Auswahlliste EN 030709.indd 17

5/12/2011 10:48:42 AM

VA

Selection tables (contd.)

Vacuum circuit-breakers VA 36 kV
Rated peak withstand current at 50/60 Hz Rated short-circuit current at rated voltage in kV Rated insulation level Rated lightning impulse withstand voltage Rated power frequency withstand voltage
Rated short-circuit breaking current

Per centage value of the DC component

Rated short-time current

mm
VA VA VA VA VA VA VA VA VA VA
1) 2)

kV
36

kV
70

kV
170

Hz
50//60 50/60 50/60 50/60

A
1250 1250 1250 1250 20003) 2000 2500 20003) 2000 2500

kA
65

3s kA
25

36 kA kA
25

%
33

A
50

Low ind. currents A


10 A for transformers in no-load state

Rated frequency

Type

6312/36 6312/36 8012/36 8012/36 8020/36 8020/36 8025/36 10020/36 10020/36 10025/36

275 400 275 400 275 400 400 275 400 400

36

70

170

50/60 50/60 50/60 50/60

82

31.5

31.5

40

50

36

70

170

50/60 50/60

104

40

40

40

50

in case of class minus 25 indoors: extend closing time and opening time by 3 ms adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report 3) at 60 Hz 2000 A only possible at max. ambient temperatures of 38 C

18

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 18

Breaking current under out-of-phase conditions kA


6.3 6.3 6.3
5/12/2011 10:48:42 AM

Cable breaking current

Rated (normal) current

Pole center spacing

Rated voltage

VA

Selection tables (contd.)

with rated short-circuit current

Interrupter chamber

Charging time for motor drive mechanism

Rated operating Number of operating Operating times sequence cycles without overhaul with release mechanical electrical 25 W 160 W 160 W O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO
2)

Command times with release 25 W 160 W 160 W

Min. Max. opening time 2)

O - 0.3 s - CO - 15 s - CO

Min. Max. opening time

Rated (normal) current

Min. Max. closing time

Drive mechanism

CO - 15 s - CO

2)

Arc duration

Partitions

ms
10000 30000 10000 100 45/65

ms

ms
40/70

ms
8 to 14

ms
50

ms
20

ms
20

s
9

10000

30000

10000

100

45/65

31/45

40/70

8 to 14

50

20

20

12

10000

30000

10000

100

45/65

31/45

40/70

8 to 14

50

20

20

12

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 19

5/12/2011 10:48:42 AM

on demand

Weight kg
19

OFF

OFF

ON

VA

Selection tables (contd.)

Vacuum circuit-breakers for railway applications VXA, B, 17.5 / 25 / 27.5 kV


Rated peak withstand current at 50/60 Hz Rated short-circuit current at rated voltage in kV Rated insulation level Rated lightning impulse withstand voltage Rated power frequency withstand voltage
Rated shortcircuit breaking current

Rated operating sequence O - 0.3 s - CO - 1 min - CO

Rated short-time current

Percentage value of the DC component

Rated frequency

Type

mm
VXA VXA VXA VXA VXA VXA VXA VXA VXA VXA VXA 5016/17 6316/17 6320/17 8020/17 8025/17 10020/17 10025/17 6316/27 8016/27 8020/27 8025/27 550 550

kV
17.5

kV
70

kV
170

Hz
16 2/3 or 25 16 2/3 or 25

A
1600 1600 2000 2000 2500 2000 2500 1600 1600 2000 2000 2000 1250 2000 1250 2000

kA
50 63 63 80 80 100 100 63 80 80 80 63 63 80 63 80

3s kA
20 25 25 31.5 31.5 40 40 25 31.5 31.5 31.5 25 25 31.5 25 31.5

kA
20 25 25 31.5 31.5 40 40 25 31.5 31.5 31.5 25 25 31.5 25 31.5

%
51 51 51 51 51 51 51 51 51 51 51 51 41 41 41 41

A kA

4)

17.5

70

170

6.3 6.3 6.3 6.3 12.5 12.5 12.5 12.5

27.5

70

170

50/60

VXA 6320/17-125 VXA 6312/27-250 VXA 8020/27-250 VXB 6312/27-250 VXB78020/27-250


1) 2)

17.5 25/ 27.5 25/ 27.5

50 95/ (105) 95/ (105)

125 250 250

16 2/3 50/60 50/60

in case of class minus 25 indoors: extend closing time and opening time by 3 ms adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report 3) on request 4) Test operating sequence cannot be tested directly under certain conditions on 16 2/3 or 25 Hz test equipment

20

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 20

O - 0.3 s - CO - 15 s - CO 3)
5/12/2011 10:48:43 AM

Low ind. currents Breaking current under out-of-phase conditions

Rated (normal) current

Pole center spacing

CO - 15 s - CO

Rated voltage

O - 5 s - CO

VA

Selection tables (contd.)

with rated short-circuit curent

Number of operating cycles without overhaul mechanical electrical with rated (normal) current

Operating times instantaneous trippin Opening time with instantaneous tripping with without Opening time without instantaneous tripping

Command times instantaneous trippi Charging time for motor drive mechanism
with without

Interrupter chamber

Drive mechanism

Opening time 2)

Opening time 2)

Closing time 2)

Partitions

ms
100 10000 30000 10000 50 10000 30000 10000 50 10 to 17 10 to 17

ms

ms

ms

ms

ms

ms

20 to 40

40 to 55

15 to 82

25 to 105

20

20

12

20 10000 30000 10000 100 20 to 40 40 to 55 25 to 58 20 20 20 20000 10000 10000 30000 30000 30000 20000 10000 10000 100 100 100 20 to 40 30 to 45 30 to 45 40 to 55 40 to 55 40 to 55 25 to 105 35 to 58 35 to 58 20 20 20 20 20

20 20 20 20 20 20 20 20 20

12 12 12 12 12 12 12 12 12

on demand

20 to 40

40 to 55

10 to 82

25 to 105

20

20

12

Weight kg
21
5/12/2011 10:48:43 AM

OFF

OFF

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 21

ON

VA

Selection tables (contd.)

Vacuum circuit-breakers for high numbers of switching operations VXC, 24 / 36 / 38 kV


Insulating level
Rated Rated transient short-circuit breaking recovery voltage current

Rated short-circuit current at rated voltage in kV

Percentage value of the DC component

Peak value (first-pole-toclear factor 1.5)

Rated short-time current

mm kV
VXC VXC VXC VXC VXC VXC VXC VXC VXC 6312/24 210 6312/24 275 6325/24 275 6312/36 275 6312/36 400 6325/36 400 8012/36 275 8012/36 400 8025/36 400 400 400 400 400 38 36 24

kV
50

kV
125

Hz
50/60

A
1250 1250 2500 1250 1250

kA
63/65

3s kA
25 25

kA
25 25 25 25 31.5 31.5 31.5 25 25 31.5 31.5 40 40

%
40

kA

Uc kV kV/s A
41 41 41 62 62 62 62 62 62

Low ind. currents A


Rated frequency

Type

0.47 31.5

63/65

25 25 31.5

70

170

50/60

2500 1250 1250 2500 1250 2500 1250 2500 63/65 63/65 80/82 80/82 80/82

40

0.57

50

31.5 31.5 25 25 31.5 31.5 40 40

VXC 6312/38-200 VXC 6325/38-200 VXC 8012/38-200 VXC 8025/38-200

71.7 71.7 40 71.7 71.7 71.7 71.7 1.32 50

95

200

50/60

VXC 10012/38-200 400 VXC 10025/38-200 400


1) 2)

1250 100/104 2500 100/104

in case of class minus 25 indoors: extend closing time and opening time by 3 ms adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report

22

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 22

Breaking current under out-of-phase conditions kA


6.3 6.3 6.3 6.3 6.3 6.3 7.9 7.9 7.9 6.3 6.3 7.9 7.9
5/12/2011 10:48:43 AM

Rated lightning impulse withstand voltage

Rated power frequency withstand voltage

Rated (normal) current

Rated peak withstand current

Rated cable-charging breaking current

at rated voltage in kV

Pole center spacing

Rated voltage

Rate of rise

VA

Selection tables (contd.)

Rated operating Switching operations sequence without inspection mechanical electrical with rated (normal) current O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO with rated short-circuit current

Operating times with release 25 W 160 W

Command tims with release 160 W 25 W160 W 160 W Charging time for motor drive mechanism s

TrennwPartitionsnde

Interrupter chamber

Opening time 2)

Opening time 2)

Closing time 2)

CO - 15 s - CO

ms

ms
31-45

ms
40-70

ms
50

ms
20

ms
20

25000 30000 25000 100

45-65

12

25000 30000 25000 100

45-65

31-45

40-70

50

20

20

12

25000 30000 25000 100

45-65

31-45

40-70

50

20

20

12

Weight kg
122 140 140 130 160 160 130 160 160 160 160 160 160 160 160

Drive

OFF

OFF

ON

VA Auswahlliste EN

23

VA Auswahlliste EN 030709.indd 23

5/12/2011 10:48:43 AM

VA

Selection tables (contd.)

High-capacity vacuum circuit-breakers for high currents VAH 12 kv, 13.8 kv (15.8), 17.5 kV
Rated insulation level

Percentage value of the DC component

Rated short-circuit current at rated voltage in kV

Rated Rated short-circuit transient breaking recovery current voltage

Peak value (first-pole-toclear factor 1.5) at rated Voltage

Rated short-time current

mm kV
VAH 12-50-40-27 **) VAH 12-50-50-27 **) VAH 12-50-50-27 **) VAH 12-63-12-27 VAH 12-63-25-27 VAH 12-63-31-27 VAH 12-63-40-27 VAH 12-63-50-27 VAH 12-63-50-27 VAH 12-63-80-27 *) VAH 12-63-80-27 *) VAH 13,8-63-12-27 VAH 13,8-63-25-27 VAH 13,8-63-31-27 VAH 13,8-63-40-27 VAH 13,8-63-50-27 VAH 13,8-63-50-27 VAH 13,8-63-80-27 *) VAH 13.8-63-80-27 *) VAH 17,5-50-12-27 **) VAH 17,5-50-25-27 **) VAH 17,5-50-31-27 **) VAH 17,5-50-31-27 **) VAH 17,5-50-40-27 **) VAH 17,5-50-50-27 **) VAH 17,5-50-50-27 **) 275 275 275 275 275 275 275 275 275 275 275 275 275 275 275 275 275 275 275 275 275 275 275 275 275 275 17.5 13.8 12

kV

kV

Hz
50/60 50 60 50 50

A
4000 5000 2) 4750 4) 1250 2500 3150 4000 5000 2) 4750 4) 8000 3) 7700 5) 1250 2500 3150 4000 5000 2) 4750 4) 8000 3) 7700 5) 1250 2500 3150 3000 4000 5000
2)

kA
125

3s kA
50

kA
50

%
50 15

kV kV/s
20.6 23.7 20.6 0.34 4.0 0.34

A
25

Low ind. currents A

Rated frequency

Type

63

15

28 (42)

75

50 50/60 50 60 50 60 50 50 50

160

63

63 50

15 15

20.6 23.7

0.34 4.0

25

also possible

63 63

15 15

23.7 0.39 (27.1) (0.40) 23.7 0.39

38

95

50 50 60 50 60 50/60 50/60 50

(15.8) (42)

160

63

(27.1) (0.40) also possible 50 on 13.8 kV 15 27.1 4.0

on re31.5 quest

38 (42)

95

60 50/60 50 60 50 60

125

50

50

15

30

0.42

31.5

4750 4) 8000 3) 7700 5)

VAH 17,5-50-80-27*)**) 275 VAH 17,5-50-80-27*)**) 275


*) **)

with motor-actuated fans checked in accordance with generator current ANSI C37.013 1) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report 2) max. ambient temperature 38 C (4900 A at 40C), terminal bars 4000 mm2 Cu 3) max. ambient temperature 39 C (7950 A at 40C), terminal bars 8000 mm2 Cu 4) Terminal bars 4000 mm2 Cu 5) Terminal bars 8000 mm2 Cu

24

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 24

Breaking current under out-of-phase conditions kA


5/12/2011 10:48:43 AM

Rated power frequency withstand voltage Rated lightning impulse withstand voltage

Cable breaking current

Rated (normal) current

Rated peak withstand current at 50/60 Hz

Pole center spacing

Rated voltage

Rate of rise

VA

Selection tables (contd.)

Rated operat- Switching operations ing sequence without inspection with rated (normal) current mechanical electrical O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO with rated short-circuit current

Operating times with release 25 W 160W 160 W

Command times with release 25 W160W 160W

Charging time for motor drive mechanism s

Interrupter chamber

Non-simultaneity (between poles)

Opening time1)

Opening time1)

CO - 15 s - CO

Closing time1)

Arc duration

Partitions

ms

ms

ms
35 to 55

ms
6 to 12

ms
2

ms 50

ms

ms
20

10000 10000 10000

30 70 to 110

12

10000 10000 10000

20 70 to 110

35 to 55

6 to 12

50

20

12

10000 10000 10000

20 70 to 110

35 to 55

6 to 12

50

20

12

10000 10000 10000

30 70 to 110

35 to 55

6 to 14

50

20

12

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 25

5/12/2011 10:48:43 AM

Weight kg
500 500 500 200 200 380 500 500 500 500 500 200 200 380 500 500 500 500 500 200 200 200 380 500 500 500 500 500

Drive

OFF

OFF

ON

25

VA

Electric circuit diagrams

Vacuum circuit-breakers without reclosing facility (Auto-Reclosure) Basic design


This circuit diagram shows the max. possible secondary equipment. Depending on the order volume, components shown may not be included. with terminal strip with anti-pumping relay

Devices which may be installed in the circuit-breaker depending on order specification F 11 Shunt opening release (shunt release) F 2 Shunt closing release (shunt release) M 1 Motor to charge the energy-storing device S 1 Auxiliary switch S 21S 25 Push switch actuated by energy storing device S 41 Push switch actuated by the buttons ON / OFF S 43 Push button actuated by the button OFF S 6 Push-button actuated by the switchgear truck V 1 Diode V 2 Rectifier X 1 Terminal strip

Charging the energy-storingdevice


As the switch (F 101) is closed, the motor (M) is energized and the energy-storing device is charged. Once charging is finished, the push switches (S 22 and S 23) are actuated by a shaft, and the motor switchedoff.

Switching ON (Closing)
Closing can be effected mechanically via the button ON electrically via the contact element ON (SOE), which excites the shunt closing release (F 2). As soon as closing operation (ON) is terminated, the motor charges the energy-storing device, as the push switches (S 22 and S 23) are closed with the energy-storing device discharged.

Switching OFF (Opening)


Opening can be effected mechanically via the button OFF electrically via the contact element OFF (SOA), which excites the shunt opening release (F 11). electrically via an overcurrent relay (F 321) which excites the shunt opening release (F 11).

Message
In closed state (ON), the pilot lamp ON (HOE) is lit, in open state (OFF), the pilot lamp OFF (HOA) is lit. The malfunction signalling relay (KOS) only receives a switching pulse via the passing contact (239/230) from the auxiliary switch of the circuitbreaker (S 1) if tripping is effected by the overcurrent relay (F 321), as in case of manual operation, either the NC contact of the push switch (S 41) of the button OFF opens, or, in case of electrical operation, the NC contact of the contact element OFF (SOA). The malfunction signalling relay features a self-holding contact, but can be de-excited via its shut-down element (SOR). The malfunction pilot lamp (HOS) is energized via the malfunction signalling relay.

26

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 26

5/12/2011 10:48:44 AM

VA

Electric circuit diagrams (contd.)

Vacuum circuit-breakers without reclosing facility (Auto-Reclosure) Basic design


This circuit diagram shows the max. possible secondary equipment. Depending on the order volume, components shown may not be included. with terminal strip without anti-pumping relay

Devices which may be installed in the circuitbreaker depending on order specification F 11 Shunt opening release (shunt release) F 2 Shunt closing release (shunt release) KO1 Anti-pumping relay M 1 Motor to charge the energy-storing device S 1 Auxiliary switch S 21S 25 Push switch actuated by energy storingdevice S 41 Push switch actuated by the buttons ON / OFF S 43 Push button actuated by the button OFF S 6 Push-button actuated by the switchgear truck V 1 Diode V 2 Rectifier X 1 Terminal strip

The operations charging the energy-storing device, switching ON, switching OFF and signalling are effected as in case of vacuum circuit-breakers without reclosing facility.

Reclosing facility (auto-reclosure)


If a short-circuit occurs, the overcurrent relay (F 321) issues a pulse to the shunt opening release (F 11 ), after expiry of the preset instantaneous zone, switching the circuit-breaker OFF. Once the preset dead time has expired, a ON command is issued to the shunt closing release (F 2) via a NO contact of the auto-reclosing relay (F 371). If the short-circuit is still present, another OFF command is issued by the overcurrent relay, and the circuit- breaker is switched off for good. The auto-reclosing relay does not issue another ON command.

VA Auswahlliste EN

27

VA Auswahlliste EN 030709.indd 27

5/12/2011 10:48:44 AM

VA

Electric circuit diagrams (contd.)

Electric circuit diagrams for circuit-breakers


This circuit diagram shows the max. possible secondary equipment. Depending on the order volume, components shown may not be included. with connector, 24-pole with anti-pumping relay

Devices which may be installed in the circuit-breaker depending on order specification F 11 Shunt opening release (shunt release) F 2 Shunt closing release (shunt release) M 1 Motor to charge the energy-storing device S 1 Auxiliary switch S 21S 25 Push switch actuated by energy storing device S 41 Push switch actuated by the buttons ON / OFF S 43 Push button actuated by the button OFF S 6 Push-button actuated by the switchgear truck V 1 Diode V 2 Rectifier X 1 Terminal strip

This circuit diagram shows the max. possible secondary equipment. Depending on the order volume, components shown may not be included. with connector, 24-pole without anti-pumping relay

28

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 28

5/12/2011 10:48:44 AM

VA

Electric circuit diagrams (contd.)

Electric circuit diagrams for circuit-breakers


This circuit diagram shows the max. possible secondary equipment. Depending on the order volume, components shown may not be included. with connector, 64-pole with anti-pumping relay

Devices which may be installed in the circuit-breaker depending on order specification F 11 Shunt opening release (shunt release) F 2 Shunt closing release (shunt release) M 1 Motor to charge the energy-storing device S 1 Auxiliary switch S 21S 25 Push switch actuated by energy storing device S 41 Push switch actuated by the buttons ON / OFF S 43 Push button actuated by the button OFF S 6 Push-button actuated by the switchgear truck V 1 Diode V 2 Rectifier X 1 Terminal strip

This circuit diagram shows the max. possible secondary equipment. Depending on the order volume, components shown may not be included. with connector, 64-pole without anti-pumping relay

VA Auswahlliste EN

29

VA Auswahlliste EN 030709.indd 29

5/12/2011 10:48:45 AM

VA

Electric circuit diagrams (contd.)

Vacuum circuit-breaker VXA with instantaneous tripping 60 V DC

A1 A3 C 1, 2,3, 4, 5 F2 F 4 F 11 F 12 F 31, 32 K2 M1 R 1, 2 R3 R7 R 11, 12 S 1 S 2126 S 4143 V 1, 3, 4, 5, 6 V 2 X 0 X 1 T

Thyristor module Capacitor diode module Surge discharge capacitor 1000 F/100 V Shunt closing release ON Undervoltage release Shunt tripping release OFF EMERGENCY OFF auxiliary release Secondary release Timing relay 1.5 sec Motor Charging resistor 39 Charging resistor 68 Protection resistor 68 Discharge resistor 56 Auxiliary switch Push switch actuated by energy storing device Push switch, actuated by mechanical ON / OFF switch Diode Rectifier Connector erminal strip in circuit-breaker

Charging the energy-storingdevice


The motor (M) is energized via L+ and L-, the energy storing device is charged. Once charging is finished, the push switches (S 22 and S 23) are actuated by a shaft, and the motor switched off.

Switching ON (Closing)
Closing can be effected mechanically via the button ON electrically via the contact element ON, which excites the shunt closing release (F 2). As soon as closing operation (ON) is terminated, the motor charges the energy-storing device, as the push switches (S 22 and S 23) are closed with the energy-storing device discharged.

Switching OFF (Opening)


Opening can be effected mechanically via the button OFF electrically via the contact element OFF, which excitesthe shunt opening release (F 11). electrically via the contact element Emergency OFF, which excites the shunt opening release (F 12).

30

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 30

5/12/2011 10:48:49 AM

VA

Electric circuit diagrams (contd.)

Vacuum circuit-breaker VXA with instantaneous tripping 220 V DC

A 1, 2 A3 C 1, 2, 3, 4, 5 F2 F4 F 11 F 12 F 31, 32 K1 K 2, 3 M1 R 1, 3, 5, 6 R 2, 4 R 7 R8 R 11, 12, 13 S1 S 2126 S 4143 V 1, 3, 4, 5, 6 V2 X0 X1 X2

Thyristor module Capacitor diode module Surge discharge capacitor 1000 F/100 V Shunt closing release ON Undervoltage release Shunt tripping release OFF EMERGENCY OFF auxiliary release Secondary release Anti-pumping relay Timing relay 1.5 sec Motor Charging resistor 39 Charging resistor 14 Protection resistor 14 Series resistor 68 Discharge resistor 56 Auxiliary switch Push switch actuated by energy storing device Push switch, actuated by mechanical ON / OFF switch Diode Rectifier Connector Terminal strip in circuit-breaker Terminal strip on truck

Charging the energy-storingdevice


The motor (M) is energized via L+ and L-, the energy storing device is charged. Once charging is finished, the push switches (S 22 and S 23) are actuated by a shaft, and the motor switched off.

Switching ON (Closing)
Closing can be effected mechanically via the button ON electrically via the contact element ON, which excites the shunt closing release (F 2). As soon as closing operation (ON) is terminated, the motor charges the energy-storing device, as the push switches (S 22 and S 23) are closed with the energy-storing device discharged.

Switching OFF (Opening)


Opening can be effected mechanically via the button OFF electrically via the contact element OFF, which excitesthe shunt opening release (F 11). electrically via the contact element Emergency OFF, which excites the shunt opening release (F 12).

VA Auswahlliste EN

31

VA Auswahlliste EN 030709.indd 31

5/12/2011 10:48:53 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request)


Vacuum circuit-breakers VAA 12 / 17.5 / 24 kV
N G 185 M12 40 30 30 live spannungsfhrend B A A 60
12.5 12,5

20

40

20

580

30 107 E 86 O 212 120 23 95 C D 120 M12


Rated voltage: Rated short-time current: Rated (normal) current: 12 kV 20 kA; 25 kA; 630 A; 1250 A 17.5 kV 20 kA; 25 kA 630 A; 1250 A 24 kV 16 kA; 25 kA 630 A; 1250 A

*) with A *) bei 1250 A

Vacuum circuit-breaker

Type/ Rated voltage


VAA VAA VAA VAA 506/12 636/12 506/17 636/17

Pole center spacing


A B 505 415 515 635 635 415 515 645 510 640 526 656 C 560 460 560 690 690 460 560 690 560 690 560 690 D 210 160 210 275 275 160 210 275

Installation dimensions
E 215 215 215 215 215 215 215 215 155 155 155 155 F 260 260 260 260 260 260 260 260 342 342 342 342 G 517 517 517 562 562 562 562 562 597 597 597 597 J 149 149 149 149 149 149 149 149 90 90 90 90 K 394 394 394 394 394 394 394 394 476 476 476 476 M 100 100 100 100 100 100 100 100 100 100 100 100 H 700 700 780 780 -

Partitions
L 72 72 132 132 N 50 50 60 60 O 280 280 310 310 -

VAA 5012/12 VAA 6312/12 VAA 5012/17 VAA 6312/17 VAA VAA 406/24 506/24

600 500 600 730 730 500 600 730 600 730 600 730

210 275 210 275

VAA 5012/24 VAA 6312/24 Dimensions in mm

32

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 32

F
5/12/2011 10:48:54 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Vacuum circuit-breakers VAA 12 / 17.5 / 24 kV
Zusatzadapter fr for Additional adapter beidseitigen busbar connection on Schienenanschluss both sides available on auf besondere special request Bestellung 40

G 185 M12 30 30
12.5 12,5

live spannungsfhrend B
A A 60

78

40

20

40

580

30 107 E 23 86 O 212 120 95 C D 120 M12


Rated voltage: Rated short-time current: Rated (normal) current: 12 kV 31.5 kA; 40 kA; 630 A; 1250 A; 1250 A; 1600 A 17.5 kV 31.5 kA 1600 A

40 78

Vacuum circuit-breaker

Type/ Rated voltage


VA VA VA VA VA VA VA 806/12 8012/12 806/12 8012/12 8016/12 8016/12 8012/17

20

Pole center spacing


A 160 160 B 443 443 C 460 460 D

M 20

Installation dimensions
E 215 215 F 260 260 G 517 517 J 149 149 K 394 394 M 142 142 H 700 700

Partitions
L 72 72 N 50 50 O 280 280

500 500

210

533

560

600

215

260

517

149

394

142

F
443 533 683 533 460 560 690 560 500 600 730 600 215 215 215 215 260 260 260 260 562 562 562 517 149 149 149 149 394 394 394 394 142 142 142 142 700 700 72 72 50 50 280 280

VA 10016/12 160 210 275 VA 8016/17 210

Dimensions in mm

VA Auswahlliste EN

33

VA Auswahlliste EN 030709.indd 33

5/12/2011 10:48:54 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Vacuum circuit-breakers VA 12 / 17 kV
50 40 20 M12 40 20 N G 185 * 30 30 12.5 A B live A

100

40

580

30 107 E

100

20 40

Zusatzadapter fr for Additional adapter beidseitigen busbar connection Schienenanschluss on both sides available on auf besondere Bestellung special request

86 212 120

23

* O

95

115 C D 120

*) 2500 A Khlkrper *)bei with 2500 A heat sink

Vacuum circuit-breaker

Rated voltage: Rated short-time current: Rated (normal) current:

12 kV 31.5 kA; 40 kA; 2000 A; 2500 A

17.5 kV 31.5 kA; 50 kA 2000 A; 2500 A

Type/ Rated voltage


VA VA 8020/12 8025/12

Pole center spacing


A 210 210 210 210 210 210 210 275 210 275 B 553 580 553 580 553 553 580 580 553 580 C 560 560 560 560 560 560 560 690 560 690 D

Installation dimensions
E 219 219 219 219 219 219 219 219 219 219 F 277 277 277 277 277 277 277 277 277 277 G 520 520 520 520 565 565 565 565 565 565 J 145 145 145 145 145 145 145 145 145 145 K 430 430 430 430 430 430 430 430 430 430 M 169 169 169 169 169 169 169 169 169 169 H 838 838 838 838 838 838

Partitions
L 73 73 73 73 73 73 N 100 100 100 100 100 100 O 353 353 353 353 353 353

600 600 600 600 600 600 600 730 600 730

VA 10020/12 VA 10025/12 VA VA VA VA 6320/17 8020/17 8025/17 8025/17

VA 10020/17 VA 10025/17 Dimensions in mm

34

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 34

5/12/2011 10:48:54 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Vacuum circuit-breakers VA 12 / 17 kV
50 40 20 M12 40 N G 185 30 30 12.5 B spannungsfhrend live A A

100

H K

580

100

40

30 107 E

40

20

Zusatzadapter fr for Additional adapter beidseitigen busbar connection on Schienenanschluss both sides available on auf besondere Bestellung special request

86 O 212 120

23

95

115 C D 120

Vacuum circuit-breaker

Rated voltage: Rated short-time current: Rated (normal) current:

12 kV 31.5 kA; 40 kA; 3000 A; 3150 A

17.5 kV 31.5 kA 3000 A; 3150 A

Type/ Rated voltage


VA VA VA VA 8031/12 8031/12 8031/17 8031/17

Pole center spacing


A 210 210 275 275 210 275 B 574 574 740 740 553 740 C 560 560 690 690 560 690 D

Installation dimensions
E 219 219 219 219 219 219 F 277 277 277 277 277 277 G 520 520 520 520 565 565 J 145 145 145 145 145 145 K 430 430 430 430 430 430 M 169 169 169 169 169 169 H 890 890 874 874 960 874

Partitions
L 116 116 91 91 124 91 N 61 61 56 56 210 56 O 315 315 290 290 555 290

600 600 730 730 600 730

VA 10031/12 VA 10031/12

Dimensions in mm

VA Auswahlliste EN

35

VA Auswahlliste EN 030709.indd 35

5/12/2011 10:48:54 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Vacuum circuit-breakers VA 12 kV
50 40 20 M12 40 N G 185 30 12.5 spannungsfhrend live B A A

Additional adapter Zusatzadapter fr for busbar connecbeidseitigen Schienenanschluss tion on both sides auf besondere available on special Bestellung request 78

78

580

30 107 E

20 40

40

86 15 O 212 120

23

95

115 C D 120

20

P 50

G M12 185 30 12.5

spannungsfhrend live B A A

100

40

580

30 100 40 20 J * 15 O *) with 2500 A heat sink *) bei 2500 A Khlkrper 86 212 120 107 M E

23

95

115 C D

M12

120

Vacuum circuit-breaker

Rated voltage: Rated short-time current: Rated (normal) current:

12 kV; 50 kA; 1250 A; 1600 A; 2000 A; 2500 A

Type/ Rated voltage


VA 12512/12 VA 12516/12 VA 12520/12 VA 12525/12 Dimensions in mm

Pole center spacing


A 210 210 210 210 B 590 590 590 590 C 560 560 560 560 D

Installation dimensions
E 219 219 219 219 F 277 277 277 277 G 520 520 520 520 J 145 145 145 145 K 430 430 430 430 M 169 169 169 169 H 700 700 700 700

Partitions
L 56 56 56 56 N 27 27 27 27 O 280 280 280 280

600 600 600 600

36

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 36

5/12/2011 10:48:54 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Vacuum circuit-breakers VA 12 kV
spannungsfhrend live B N 50 M12 G 185 30 30 12,5 40 A A 40

100

40

20

580

30 100 20 J 107 M E 23 86 15 O 212 120


Vacuum circuit-breaker Rated voltage: Rated short-time current: Rated (normal) current: 12 kV 50 kA 3150 A

40

M12 95 115 C D 120

Type/ Rated voltage


VA 12531/12 Dimensions in mm

Pole center spacing


A 210 275 B 590 720 C 560 690 D

Installation dimensions
E 219 219 F 277 277 G 520 520 J 145 145 K 430 430 M 169 169 H 800 700

Partitions
L 55 55 N 62 27 O 315 280

600 730

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 37

5/12/2011 10:48:54 AM

37

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Vacuum circuit-breakers VA, VXC 24 kV
N G 185 40 20 20 50 40 M12 30 30
12.5 12,5

live spannungsfhrend B
A A 60

78

20

580

78

40

30 107 E 23 95 C D 120 120

40 20

15 O 212

86

Zusatzadapter fr Additional adapter beidseitigen for busbar connecSchienenanschluss tion on both sides auf besondere available on special Bestellung request

Vacuum circuit-breaker

Rated voltage: Rated short-time current: Rated (normal) current:

VA 24 kV 25 kA 1250 A; 1600 A

VXC 24 kV 25 kA 1250 A

Type/ Rated voltage


VA 6316/24

Pole center spacing


A 210 275 210 275 B 533 663 533 663 C 560 690 560 690 D

Installation dimensions
E 155 155 155 155 F 342 342 342 342 G 597 597 597 597 J 90 90 90 90 K 476 476 476 476 M 142 142 142 142 H 780 780 -

Partitions
L 132 132 N 60 60 O 310 310 -

600 730 600 730

VXC 6312/24 Dimensions in mm

38

VA Auswahlliste EN 030709.indd 38

VA Auswahlliste EN

5/12/2011 10:48:55 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Vacuum circuit-breakers VA, VXC 24 kV
live spannungsfhrend B
50 N G 185 M12 20 * 30 30 A A 40
12.5 12,5

100 40

20

40

580

40

30 * 107 E 23 95 C O 120 D 120 M12 115

40 100

20

86 212

20

15

Additional adapter Zusatzadapter fr beidseitigen for busbar connecSchienenanschluss tion on both sides auf besondere available on special Bestellung request Vacuum circuit-breaker

*) 2500 AA Khlkrper *) bei with 2500 heat sink

Rated voltage: Rated short-time current: Rated (normal) current:

VA 24 kV 25 kA; 31.5 kA; 50 kA 2000 A; 2500 A

VXC 24 kV 25 kA 2500 A

Type/ Rated voltage


VA VA 6320/24 8020/24

Pole center spacing


A 210 275 210 275 210 275 210 275 210 275 210 275 B 533 683 533 683 533 693 580 710 580 710 580 710 C 560 690 560 690 560 690 560 690 560 690 560 690 D

Installation dimensions
E 149 149 149 149 149 149 149 149 149 149 149 149 F 347 347 347 347 347 347 347 347 347 347 347 347 G 600 600 600 600 600 600 600 600 600 600 600 600 J 75 75 75 75 75 75 75 75 75 75 75 75 K 500 500 500 500 500 500 500 500 500 500 500 500 M 169 169 169 169 169 169 169 169 169 169 169 169 H 995 995 995 980 995 995 -

Partitions
L 173 173 173 110 110 110 N 107 107 107 110 110 110 O 360 360 360 390 360 360 -

600 730 600 730 600 730 600 730 600 730 600 730

VA 10020/24

VXC 6325/24 VA 8025/24

VA 10025/24 Dimensions in mm

VA Auswahlliste EN

39

VA Auswahlliste EN 030709.indd 39

5/12/2011 10:48:55 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Vacuum circuit-breakers VA, VXC 36 kV
N 50 G 221 20 M12 * 40 185 30 30 spannungsfhrend B live B A A 40

100

12.5 12,5

40

580

30 107 E 23 M12 95 C O *)with Bei 2500 A Khlkrper *) 2500 A heat sink 120 D 120

100

* 20 212 15

40

86

N M12 20

G 221 185 30 30

live B spannungsfhrend B A A

12.5 12,5

40

580

40

30 107 E 23 M12 95 C 120 D 120

20

86 212 O

Vacuum circuit-breaker

Rated voltage: Rated short-time current: Rated (normal) current:

VA 36 kV 31.5 kA; 40 kA 2000 A; 2500 A

40

40

VXC 36 kV 25 kA; 31.5 kA 1250 A; 2500 A

Type/ Rated voltage


VA 8020/36

Pole center spacing


A 275 400 275 400 400 400 400 400 275 400 275 400 B 686 936 686 936 936 936 936 936 686 936 686 936 C 690 940 690 940 940 940 940 940 690 940 690 940 D

Installation dimensions
E 82 82 82 82 82 82 82 82 82 82 82 82 F 476 476 476 476 476 476 476 476 476 476 476 476 G 703 703 703 703 703 703 703 703 703 703 703 703 J 30 30 30 30 30 30 30 30 30 30 30 30 K 587 587 587 587 587 587 587 587 587 587 587 587 M 169 169 169 169 169 169 169 169 169 169 169 169 H 1100 1100 1100 1100 1100 1100 980 1100 980 1100

Partitions
L 213 213 213 213 213 213 213 213 213 213 N 160 160 160 160 160 160 110 160 110 160 O 420 420 420 420 420 420 390 420 390 420

730 980 730 980 980 980 980 980 730 980 730 980

VA 10020/36

VA

8025/36

VA 10025/36 VXC 6325/36 VXC 8025/36 VXC 8012/36 VXC 6312/36 Dimensions in mm

40

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 40

5/12/2011 10:48:55 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Vacuum circuit-breakers VXC 38 kV
N M12 20 G 221 185 30 30 spannungsfhrend B live B A A

12.5 12,5
40 580 30 107 E 23 M12 95 C 120 D 120

40

40

20

86 212 O

50 20

G 221

live B B spannungsfhrend B
A A 40

100

20

M12

185 30 30

40

12.5 12,5
40 580 30 107 23

Additional adapter Zusatzadapter fr for busbar conbeidseitigen Schienenanschluss nection on both auf besondere sides available on Bestellung special request

40

40

100

20

20 40

86 212

M12 95 C 120 D 120

15

O *) with 2500A A heat sink *) Bei 2500 Khlkrper

Vacuum circuit-breaker

Rated voltage: Rated short-time current: Rated (normal) current:

38 kV 25 kA; 31.5 kA 1250 A; 2500 A

Type/Rated voltage

Pole center spacing


A B 936 936 936 936 936 936 C 940 940 940 940 940 940 D 400 400 400 400 400 400

Installation dimensions
E 82 82 82 82 82 82 F 501 501 501 501 501 501 G 903 903 903 903 903 903 J 30 30 30 30 30 30 K 587 587 587 587 587 587 M 169 169 169 169 169 169 H 980 980 980 1100 1100 1100

Partitions
L 213 213 213 213 213 213 N 110 110 110 160 160 160 O 390 390 390 420 420 420

VXC VXC VXC VXC

6312/38 8012/38 6325/38 8025/38

980 980 980 980 980 980

VXC 10012/38

VXC 10025/38 Dimensions in mm

VA Auswahlliste EN

41

VA Auswahlliste EN 030709.indd 41

5/12/2011 10:48:55 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Vacuum circuit-breakers VAH 12 kV
N M12 20 G 185 30 12.5

live spannungsfhrend B
A A

40

40

580

30 107 E

86 O 212 120

23

95

115 C D

M12

120

50 20 M12 20

G 185 30 12.5

live spannungsfhrend B
A A

100

40

40

Additional adapter Zusatzadapter fr for beidseitigen busbar connection on both sides Schienenanschluss auf besondere available on special Bestellung request
100

40

580

30 * 86 107 E

20 40

J 20

23

95

115 C

M12

15 *) 2500 A Khlkrper *) bei with 2500 A heat sink

212 120

120

Vacuum circuit-breaker

Rated voltage: Rated short-time current: Rated (normal) current:

12 kV 63 kA 1250 A; 2500 A

Type/ Rated voltage

Pole center spacing


A B 720 720 720 720 720 720 C 795 795 795 795 795 795 D 275 275 275 275 275 275

Installation dimensions
E 180 180 180 180 180 180 F 338 338 338 338 338 338 G 565 565 565 565 565 565 J 127 127 127 127 127 127 K 450 450 450 450 450 450 M 169 169 169 169 169 169 H 745 745 745 745 745 745

Partitions
L 50 50 50 50 50 50 N 50 50 50 50 50 50 O 372 372 372 372 372 372

VAH VAH

12-63-12-27 12-63-25-27

835 835 835 835 835 835

VAH 13.8-63-12-27 VAH 13.8-63-12-27 VAH 17.5-50-12-27 VAH 17.5-50-25-27 Dimensions in mm

42

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 42

5/12/2011 10:48:56 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Vacuum circuit-breakers VAH 12 / 13.8 / 17.5 kV
Center of gravity

Control and auxiliary lines

Center of gravity

Connection to earth M12

Vacuum circuit-breaker

Rated voltage: Rated short-time current: Rated (normal) current:

12 kV 63 kA 3150 A

13.8 kV 63 kA 3150 A

17.5 kV 63 kA 3150 A

Type/ Rated voltage

Pole center spacing


A B 700 700 700 C 795 795 795 D 275 275 275

Installation dimensions
E 180 180 180 F 338 338 338 G 565 565 565 J 127 127 127 K 450 450 450 M 169 169 169 H -

Partitions
L 50 50 50 N O 372 372 372

VAH

12-63-31-27

835 835 835

VAH 13.8-63-31-27 VAH 17.5-50-31-27 Dimensions in mm

VA Auswahlliste EN

43

VA Auswahlliste EN 030709.indd 43

5/12/2011 10:48:56 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Vacuum circuit-breakers VAH 12 / 15.8 / 17.5 kV
N live spannungsfhrend B 185 30 30 276 A A

40

40

580

40

107

86 212 O M12 95 115 C D

Vacuum circuit-breaker

Rated voltage: Rated short-time current: Rated (normal) current:

12 kV 50/63 kA 4000/5000/8000 A

13.8 (15.8) kV 63 kA 4000/5000/8000 A

17.5 kV 40/50 kA 4000/5000/8000 A

Type/ Rated voltage

Pole center spacing


A B 790 790 790 790 790 790 790 790 790 790 790 C 795 795 795 795 795 795 795 795 795 795 795 D 275 275 275 275 275 275 275 275 275 275 275

Installation dimensions
E 140 140 140 140 140 140 140 140 140 140 140 F 378 378 378 378 378 378 378 378 378 378 378 G 693 693 693 693 693 693 693 693 693 693 693 J 115 115 115 115 115 115 115 115 115 115 115 K 344 344 344 344 344 344 344 344 344 344 344 M 205 205 205 205 205 205 205 205 205 205 205 H 1025 1025 1025 1025 1025 1025 1025 1025 1025 1025 1025

Partitions
L 190 190 190 190 190 190 190 190 190 190 190 N 40 40 40 40 40 40 40 40 40 40 40 O 490 490 490 490 490 490 490 490 490 490 490

VAH VAH VAH VAH VAH

12-50-40-27 12-63-40-27 12-50-50-27 12-63-50-27 12-63-80-27

835 835 835 835 835 835 835 835 835 835 835

VAH 13.8-63-40-27 VAH 13.8-63-50-27 VAH 13.8-63-80-27 VAH 17.5-50-40-27 VAH 17.5-50-50-27 VAH 17.5-50-80-27 Dimensions in mm

44

23 VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 44

40

40

5/12/2011 10:48:56 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Vacuum circuit-breakers VXA 27 kV - for railway applications
Terminal 2000 A

Terminal 1250 A

Controland auxiliary lines

Earth screw M12 M12

Securing bolt 10

VXA 6312/27-250 Vacuum circuit-breaker Rated voltage: Rated short-time current: Rated (normal) current: 27 kV 25 kA 1250 A

VXA 8012/27-250 27 kV 31.5 kA 1250 A

VXA 8020/27-250 27 kV 31.5 kA 2000 A

VA Auswahlliste EN

45

VA Auswahlliste EN 030709.indd 45

5/12/2011 10:48:56 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Vacuum circuit-breakers VXB 27 kV - for railway applications
Terminal 1250 A Terminal 2000 A

Controland auxiliary lines

Earth screw M12

VXB 6312/25-250 Vacuum circuit-breaker Rated voltage: Rated short-time current: Rated (normal) current: 27 kV 25 kA 1250 A

VXB 8020/25-250 27 kV 31.5 kA 2000 A

46

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 46

5/12/2011 10:48:57 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Chassis frame for VAA 12 kV up to 24 kV
PMA PMA

1035 842 Connection to earth M12 Erdungsanschluss 223 100* Pipe 60x40 Rohr i* 100* e f d b c

*) Fastening bore-hole Befestigungsbohrung 18

Rated voltage
kV 12 12 17.5 24 24 Dimensions in mm

Pole center spacing


PMA 160 210 210 210 275 b 671 771 971 971 1101 c 729 829 1029 1029 1159 d

Main dimensions
e 564 564 564 564 564 f 660 660 660 660 660 h 1285 1285 1285 1285 1285 i 675 775 975 975 1105 620 720 920 920 1050

VA Auswahlliste EN

47

VA Auswahlliste EN 030709.indd 47

5/12/2011 10:48:57 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Chassis frame for VA, VXC, VAH and VAA 36 kV

g PMA PMA

97

1315

ErdungsConnection to earth M12 anschluss M12 500 100 147 100*

842

i*

e f

d b c

*) Fastening bore-hole 18 *) Befestigungsbohrung 18

Rated voltage
kV 12 12 12 (VAH) 17.5 17.5 (VAH) 24 24 36 36 Double pole 8012/36 8025/36 Dimensions in mm

Pole center spacing


PMA 160 210 275 210 275 210 275 275 400 400 400 b 671 771 1101 971 1101 971 1101 1321 1571 1571 1571 c 729 829 1159 1029 1159 1029 1159 1379 1629 1629 1629 d 620 720 1050 920 1050 920 1050 1270 1520 1520 1520

Main dimensions
e 564 564 674 564 674 564 564 674 674 674 674 f 660 660 770 660 770 660 660 770 770 770 770 g 660 760 1090 960 1090 960 1000 1315 1566 1566 1566 h 1355 1355 1355 1355 1355 1355 1355 1355 1355 1438 1480 i 660 760 1090 960 1090 960 1090 1310 1560 1560 1560

48

1035

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 48

5/12/2011 10:48:57 AM

VA

Vacuum circuit-breaker dimensions

(Dimensions specified on request) (contd.)


Chassis frame for DB model
588

97 917 500 ErdungsEarth screw schraube M12 M12

97 917 136* 510*

147

684 780

40

458 510 568

*) Befestigungs*) Fastening bore-hole 18 bohrung 18

1420

VA Auswahlliste EN

49

VA Auswahlliste EN 030709.indd 49

5/12/2011 10:48:57 AM

VA

Transport

Transport
The vacuum circuit-breakers are shipped with packaging. The circuit-breakers weight corresponds to the selection tables. On delivery, the circuitbreakers are fully assembled and adjusted. The vacuum circuit-breakers must be lifted in accordance with the illustration. A rope with a diameter of 12 to 15 mm or a strap is required.

Example for a shipping unit, type VA, VAA, VXC, VAH

90

Transport VA, VAA, VXC

min. 0,5 m

Transport VAH

Transport VXA

50

VA Auswahlliste EN

VA Auswahlliste EN 030709.indd 50

5/12/2011 10:48:58 AM

Appendices

Notes

VA Auswahlliste EN

51

VA Auswahlliste EN 030709.indd 51

5/12/2011 10:48:58 AM

Schneider Electric 35, rue Joseph Monier CS 30323 92506 Rueil-Malmaison Cedex, France RCS Nanterre 954 503 439 Capital social 896 313 776 www.schneider-electric.com VA Auswahlliste EN

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Publishing: Schneider Electric Design: Schneider Electric Printing:

02-2011

VA Auswahlliste EN 030709.indd 52

5/12/2011 10:48:58 AM

2011 Schneider Electric - All rights reserved