Sie sind auf Seite 1von 43

Date:

2/26/2014

Gurban Abasov_Galley Refurbishment

Gurban Abasov_Galley Refurbishment

2/26/2014

Gurban Abasov_Galley Refurbishment / Table of contents

Table of contents
Gurban Abasov_Galley Refurbishment
Site 1
Building 1
Storey 1
Room 1
Room summary....................................................................................................................................................................................... 4
Luminaire parts list...................................................................................................................................................................................5
Results summary of surfaces.................................................................................................................................................................. 6
Workplane 1
Value chart/Perpendicular illuminance (adaptive)...............................................................................................................................7
Room 2
Room summary....................................................................................................................................................................................... 8
Workplane 2
Value chart/Perpendicular illuminance (adaptive)...............................................................................................................................9
Room 3
Room summary..................................................................................................................................................................................... 10
Workplane 3
Value chart/Perpendicular illuminance (adaptive).............................................................................................................................11
Room 4
Room summary..................................................................................................................................................................................... 12
Workplane 4
Value chart/Perpendicular illuminance (adaptive).............................................................................................................................13
Room 5
Room summary..................................................................................................................................................................................... 14
Workplane 5
Value chart/Perpendicular illuminance (adaptive).............................................................................................................................16
Room 6
Room summary..................................................................................................................................................................................... 17
Workplane 6
Value chart/Perpendicular illuminance (adaptive).............................................................................................................................19
Room 7
Room summary..................................................................................................................................................................................... 20
Workplane 7
Value chart/Perpendicular illuminance (adaptive).............................................................................................................................22
Room 8
Room summary..................................................................................................................................................................................... 23
Workplane 8
Value chart/Perpendicular illuminance (adaptive).............................................................................................................................25
Room 9
Room summary..................................................................................................................................................................................... 26
Workplane 9
Value chart/Perpendicular illuminance (adaptive).............................................................................................................................28
Room 10
Workplane 10
Value chart/Perpendicular illuminance (adaptive).............................................................................................................................29
Room 11
Room summary..................................................................................................................................................................................... 30
Workplane 11
Value chart/Perpendicular illuminance (adaptive).............................................................................................................................31
Room 3 Working Plane
Room summary..................................................................................................................................................................................... 32
Workplane 12
Results overview............................................................................................................................................................................... 33
Value chart/Perpendicular illuminance (adaptive).............................................................................................................................34
Room-6 Oven Top
Room summary..................................................................................................................................................................................... 35
Workplane 13
Page 2

Gurban Abasov_Galley Refurbishment

2/26/2014

Gurban Abasov_Galley Refurbishment / Table of contents

Results overview............................................................................................................................................................................... 37
Value chart/Perpendicular illuminance (adaptive).............................................................................................................................38
Room-8 Working Plane
Room summary..................................................................................................................................................................................... 39
Room-10 Working Plane
Room summary..................................................................................................................................................................................... 41
Workplane 15
Results overview............................................................................................................................................................................... 42
Value chart/Perpendicular illuminance (adaptive).............................................................................................................................43

Page 3

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 1 / Room summary

Room 1 / Room summary

Scale: 1 : 25

Perpendicular illuminance (adaptive)


Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 1

514

373

619

0.726

0.603

32 x 32 (all)

Height of room: 2.800 m, Reflection factors: Ceiling 61.4%, Walls 81.9%, Floor 27.9%, Light loss factor: 0.80
No.

Quantity

Glamox DLT RS(M)284 218 FR2


Light output ratio: 43.82%

105

105

90

90

75

75

60

60

See our luminaire catalog for


an image of the luminaire.

80

45

45

120

30

15

cd/klm
C0 - C180

15

30

= 44%
C90 - C270

Total luminous flux: 5400 lm, Total Load: 96 W


Specific connection value: 0.00 W/m = 0.00 W/m/100 lx (Ground area 0.00 m)

Page 4

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 1 / Luminaire parts list

Room 1 / Luminaire parts list


1.) 2 x Glamox DLT RS(M)284 218 FR2

See our luminaire catalog


for an image of the
luminaire.

105

105

90

90

75

75

60

Luminous emittance 1
Fitting: 2xT8 18 W
Light output ratio: 43.82%

60
80

45

45

120

30

15

cd/klm
C0 - C180

15

30

= 44%
C90 - C270

Total luminous flux: 5400 lm, Total Load: 96 W

Page 5

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 1 / Results summary of surfaces

Room 1 / Results summary of surfaces


Perpendicular illuminance (adaptive)
Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 1

514

373

619

0.726

0.603

32 x 32 (all)

Height of room: 2.800 m, Reflection factors: Ceiling 61.4%, Walls 81.9%, Floor 27.9%, Light loss factor: 0.80
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 6

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 1 / Workplane 1 / Value chart/Perpendicular illuminance (adaptive)

Workplane 1 / Value chart/Perpendicular illuminance (adaptive)

Scale: 1 : 25
Perpendicular illuminance (Surface)
Average: 514 lx, Min: 373 lx, Max: 619 lx, Min/average: 0.726, Min/max: 0.603, Points: 32 x 32 (Relevant: all)
Height of working plane: 1.000 m, Wall zone: 0.000 m
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 7

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 2 / Room summary

Room 2 / Room summary

Scale: 1 : 25

Perpendicular illuminance (adaptive)


Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 2

443

267

551

0.603

0.485

32 x 32 (1021)

Height of room: 2.800 m, Reflection factors: Ceiling 61.4%, Walls 77.1%, Floor 27.9%, Light loss factor: 0.80
No.

Quantity

Glamox DLT RS(M)284 218 FR2


Light output ratio: 43.82%

105

105

90

90

75

75

60

60

See our luminaire catalog for


an image of the luminaire.

80

45

45

120

30

15

cd/klm
C0 - C180

15

30

= 44%
C90 - C270

Total luminous flux: 5400 lm, Total Load: 96 W


Specific connection value: 0.00 W/m = 0.00 W/m/100 lx (Ground area 0.00 m)

Page 8

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 2 / Workplane 2 / Value chart/Perpendicular illuminance (adaptive)

Workplane 2 / Value chart/Perpendicular illuminance (adaptive)

Scale: 1 : 25
Perpendicular illuminance (Surface)
Average: 443 lx, Min: 267 lx, Max: 551 lx, Min/average: 0.603, Min/max: 0.485, Points: 32 x 32 (Relevant: 1021)
Height of working plane: 1.000 m, Wall zone: 0.000 m
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 9

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 3 / Room summary

Room 3 / Room summary

Scale: 1 : 25

Perpendicular illuminance (adaptive)


Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 12

312

80

502

0.257

0.159

64 x 32 (1866)

Workplane 3

237

0.37

444

0.002

0.001

32 x 64 (2046)

Summary

0.37

502

Height of room: 2.800 m, Reflection factors: Ceiling 61.4%, Walls 65.8%, Floor 27.6%, Light loss factor: 0.80
No.

Quantity

Glamox DLT RS(M)284 218 FR2


Light output ratio: 43.82%

105

105

90

90

75

75

60

60

See our luminaire catalog for


an image of the luminaire.

80

45

45

120

30

15

cd/klm
C0 - C180

15

30

= 44%
C90 - C270

Total luminous flux: 13500 lm, Total Load: 240 W


Specific connection value: 0.00 W/m = 0.00 W/m/100 lx (Ground area 0.00 m)

Page 10

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 3 / Workplane 3 / Value chart/Perpendicular illuminance (adaptive)

Workplane 3 / Value chart/Perpendicular illuminance (adaptive)

Scale: 1 : 25
Perpendicular illuminance (Surface)
Average: 237 lx, Min: 0.37 lx, Max: 444 lx, Min/average: 0.002, Min/max: 0.001, Points: 32 x 64 (Relevant: 2046)
Height of working plane: 0.800 m, Wall zone: 0.000 m
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 11

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 4 / Room summary

Room 4 / Room summary

Scale: 1 : 25

Perpendicular illuminance (adaptive)


Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 4

425

278

549

0.654

0.506

128 x 64 (8123)

Height of room: 2.800 m, Reflection factors: Ceiling 61.4%, Walls 69.3%, Floor 27.8%, Light loss factor: 0.80
No.

Quantity

Glamox DLT RS(M)284 218 FR2


Light output ratio: 43.82%

105

105

90

90

75

75

60

60

See our luminaire catalog for


an image of the luminaire.

80

45

45

120

30

15

cd/klm
C0 - C180

15

30

= 44%
C90 - C270

Total luminous flux: 10800 lm, Total Load: 192 W


Specific connection value: 0.00 W/m = 0.00 W/m/100 lx (Ground area 0.00 m)

Page 12

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 4 / Workplane 4 / Value chart/Perpendicular illuminance (adaptive)

Workplane 4 / Value chart/Perpendicular illuminance (adaptive)

Scale: 1 : 25
Perpendicular illuminance (Surface)
Average: 425 lx, Min: 278 lx, Max: 549 lx, Min/average: 0.654, Min/max: 0.506, Points: 128 x 64 (Relevant: 8123)
Height of working plane: 1.000 m, Wall zone: 0.000 m
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 13

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 5 / Room summary

Room 5 / Room summary

Scale: 1 : 25

Perpendicular illuminance (adaptive)


Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 5

398

374

423

0.941

0.885

8 x 1 (all)

Height of room: 2.800 m, Reflection factors: Ceiling 61.4%, Walls 77.5%, Floor 27.6%, Light loss factor: 0.80

Page 14

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 5 / Room summary

No.

Quantity

Glamox DLT RS(M)284 218 FR2


Light output ratio: 43.82%

105

105

90

90

75

75

60

60

See our luminaire catalog for


an image of the luminaire.

80

45

45

120

30

15

cd/klm
C0 - C180

15

30

= 44%
C90 - C270

Total luminous flux: 10800 lm, Total Load: 192 W


Specific connection value: 0.00 W/m = 0.00 W/m/100 lx (Ground area 0.00 m)

Page 15

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 5 / Workplane 5 / Value chart/Perpendicular illuminance (adaptive)

Workplane 5 / Value chart/Perpendicular illuminance (adaptive)

Scale: 1 : 25
Perpendicular illuminance (Surface)
Average: 512 lx, Min: 185 lx, Max: 702 lx, Min/average: 0.360, Min/max: 0.263, Points: 128 x 256 (Relevant: 31339)
Height of working plane: 1.000 m, Wall zone: 0.000 m
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 16

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 6 / Room summary

Room 6 / Room summary

Scale: 1 : 25

Perpendicular illuminance (adaptive)


Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 6

266

37

449

0.141

0.083

64 x 64 (4070)

Workplane 13

107

38

264

0.354

0.144

32 x 32 (all)

Summary

37

449

Height of room: 2.800 m, Reflection factors: Ceiling 61.4%, Walls 83.8%, Floor 27.5%, Light loss factor: 0.80
No.

Quantity

Glamox DLT RS(M)284 218 FR2


Light output ratio: 43.82%

105

105

90

90

75

75

60

60

See our luminaire catalog for


an image of the luminaire.

80

45

45

120

30

15

cd/klm
C0 - C180

15

30

= 44%
C90 - C270

Page 17

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 6 / Room summary

No.

Quantity

Glamox MIRZ54 236 PC


Light output ratio: 71.50%

135

150

165

180

165

150

135

160

120

120

120

80

See our luminaire catalog for


an image of the luminaire.

105

105

90

90

75

75

60

60

45

30

15

cd/klm
C0 - C180

15

30

45

= 72%
C90 - C270

Total luminous flux: 12100 lm, Total Load: 166 W


Specific connection value: 0.00 W/m = 0.00 W/m/100 lx (Ground area 0.00 m)

Page 18

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 6 / Workplane 6 / Value chart/Perpendicular illuminance (adaptive)

Workplane 6 / Value chart/Perpendicular illuminance (adaptive)

Scale: 1 : 25
Perpendicular illuminance (Surface)
Average: 311 lx, Min: 306 lx, Max: 315 lx, Min/average: 0.984, Min/max: 0.969, Points: 2 x 1 (Relevant: all)
Height of working plane: 1.000 m, Wall zone: 0.000 m
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 19

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 7 / Room summary

Room 7 / Room summary

Scale: 1 : 25

Perpendicular illuminance (adaptive)


Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 7

523

220

663

0.421

0.332

64 x 64 (3979)

Height of room: 2.800 m, Reflection factors: Ceiling 61.4%, Walls 83.6%, Floor 27.4%, Light loss factor: 0.80

Page 20

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 7 / Room summary

No.

Quantity

Glamox DLT RS(M)284 218 FR2


Light output ratio: 43.82%

105

105

90

90

75

75

60

60

See our luminaire catalog for


an image of the luminaire.

80

45

45

120

30

15

cd/klm
C0 - C180

15

30

= 44%
C90 - C270

Total luminous flux: 16200 lm, Total Load: 288 W


Specific connection value: 0.00 W/m = 0.00 W/m/100 lx (Ground area 0.00 m)

Page 21

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 7 / Workplane 7 / Value chart/Perpendicular illuminance (adaptive)

Workplane 7 / Value chart/Perpendicular illuminance (adaptive)

Scale: 1 : 25
Perpendicular illuminance (Surface)
Average: 523 lx, Min: 220 lx, Max: 663 lx, Min/average: 0.421, Min/max: 0.332, Points: 64 x 64 (Relevant: 3979)
Height of working plane: 1.000 m, Wall zone: 0.000 m
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 22

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 8 / Room summary

Room 8 / Room summary

Scale: 1 : 50

Perpendicular illuminance (adaptive)


Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 8

422

0.52

977

0.001

0.001

64 x 128 (6370)

Workplane 14

553

216

1077

0.391

0.201

512 x 256 (90697)

Summary

0.52

1077

Height of room: 2.800 m, Reflection factors: Ceiling 61.4%, Walls 65.4%, Floor 27.5%, Light loss factor: 0.80
No.

Quantity

Glamox DLT RS(M)284 218 FR2


Light output ratio: 43.82%

105

105

90

90

75

75

60

60

See our luminaire catalog for


an image of the luminaire.

80

45

45

120

30

15

cd/klm
C0 - C180

15

30

= 44%
C90 - C270

Page 23

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 8 / Room summary

Total luminous flux: 16200 lm, Total Load: 288 W


Specific connection value: 15.91 W/m = 3.77 W/m/100 lx (Ground area 18.10 m)

Page 24

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 8 / Workplane 8 / Value chart/Perpendicular illuminance (adaptive)

Workplane 8 / Value chart/Perpendicular illuminance (adaptive)

Scale: 1 : 50
Perpendicular illuminance (Surface)
Average: 422 lx, Min: 0.52 lx, Max: 977 lx, Min/average: 0.001, Min/max: 0.001, Points: 64 x 128 (Relevant: 6370)
Height of working plane: 0.800 m, Wall zone: 0.000 m
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 25

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 9 / Room summary

Room 9 / Room summary

Scale: 1 : 25

Perpendicular illuminance (adaptive)


Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 9

390

218

505

0.558

0.431

128 x 128 (16290)

Height of room: 2.800 m, Reflection factors: Ceiling 61.4%, Walls 83.9%, Floor 27.5%, Light loss factor: 0.80
No.

Quantity

Glamox DLT RS(M)284 218 FR2


Light output ratio: 43.82%

105

105

90

90

75

75

60

60

See our luminaire catalog for


an image of the luminaire.

80

45

45

120

30

15

cd/klm
C0 - C180

15

30

= 44%
C90 - C270

Page 26

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 9 / Room summary

Total luminous flux: 10800 lm, Total Load: 192 W


Specific connection value: 0.00 W/m = 0.00 W/m/100 lx (Ground area 0.00 m)

Page 27

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 9 / Workplane 9 / Value chart/Perpendicular illuminance (adaptive)

Workplane 9 / Value chart/Perpendicular illuminance (adaptive)

Scale: 1 : 25
Perpendicular illuminance (Surface)
Average: 390 lx, Min: 218 lx, Max: 505 lx, Min/average: 0.558, Min/max: 0.431, Points: 128 x 128 (Relevant: 16290)
Height of working plane: 1.000 m, Wall zone: 0.000 m
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 28

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 10 / Workplane 10 / Value chart/Perpendicular illuminance (adaptive)

Workplane 10 / Value chart/Perpendicular illuminance (adaptive)

Scale: 1 : 50
Perpendicular illuminance (Surface)
Average: 236 lx, Min: 0.36 lx, Max: 462 lx, Min/average: 0.002, Min/max: 0.001, Points: 512 x 256 (Relevant: 93514)
Height of working plane: 0.800 m, Wall zone: 0.000 m
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 29

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 11 / Room summary

Room 11 / Room summary

Scale: 1 : 50

Perpendicular illuminance (adaptive)


Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 11

1218

758

1451

0.623

0.522

16 x 64 (all)

Height of room: 2.800 m, Reflection factors: Ceiling 56.8%, Walls 57.3%, Floor 20.0%, Light loss factor: 0.80
No.

Quantity

Glamox MIRZ54 236 PC


Light output ratio: 71.50%

135

150

165

180

165

150

135

160

120

120

120

80

See our luminaire catalog for


an image of the luminaire.

105

105

90

90

75

75

60

60

45

30

15

cd/klm
C0 - C180

15

30

45

= 72%
C90 - C270

Total luminous flux: 20100 lm, Total Load: 210 W


Specific connection value: 0.00 W/m = 0.00 W/m/100 lx (Ground area 0.00 m)

Page 30

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 11 / Workplane 11 / Value chart/Perpendicular illuminance (adaptive)

Workplane 11 / Value chart/Perpendicular illuminance (adaptive)

Scale: 1 : 50
Perpendicular illuminance (Surface)
Average: 1218 lx, Min: 758 lx, Max: 1451 lx, Min/average: 0.623, Min/max: 0.522, Points: 16 x 64 (Relevant: all)
Height of working plane: 1.000 m, Wall zone: 0.000 m
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 31

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 3 Working Plane / Room summary

Room 3 Working Plane / Room summary

Scale: 1 : 25

Perpendicular illuminance (adaptive)


Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 12

312

80

502

0.257

0.159

64 x 32 (1866)

Workplane 3

237

0.37

444

0.002

0.001

32 x 64 (2046)

Summary

0.37

502

Height of room: 2.800 m, Reflection factors: Ceiling 61.4%, Walls 65.8%, Floor 27.6%, Light loss factor: 0.70
No.

Quantity

Glamox DLT RS(M)284 218 FR2


Light output ratio: 43.82%

105

105

90

90

75

75

60

60

See our luminaire catalog for


an image of the luminaire.

80

45

45

120

30

15

cd/klm
C0 - C180

15

30

= 44%
C90 - C270

Total luminous flux: 13500 lm, Total Load: 240 W


Specific connection value: 0.00 W/m = 0.00 W/m/100 lx (Ground area 0.00 m)

Page 32

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 3 Working Plane / Workplane 12 / Results overview

Workplane 12 / Results overview


Results overview (Surface)
Result type

Average

Min

Max

Min/average

Min/max

Points (Relevant)

Perpendicular illuminance [lx]

312

80

502

0.257

0.159

64 x 32 (1866)

Height of working plane: 1.000 m, Wall zone: 0.000 m


Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 33

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room 3 Working Plane / Workplane 12 / Value chart/Perpendicular illuminance (adaptive)

Workplane 12 / Value chart/Perpendicular illuminance (adaptive)

Scale: 1 : 25
Perpendicular illuminance (Surface)
Average: 312 lx, Min: 80 lx, Max: 502 lx, Min/average: 0.257, Min/max: 0.159, Points: 64 x 32 (Relevant: 1866)
Height of working plane: 1.000 m, Wall zone: 0.000 m
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 34

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room-6 Oven Top / Room summary

Room-6 Oven Top / Room summary

Scale: 1 : 10

Perpendicular illuminance (adaptive)


Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 13

107

38

264

0.354

0.144

32 x 32 (all)

Height of room: 2.800 m, Reflection factors: Ceiling 65.2%, Walls 57.4%, Floor 26.6%, Light loss factor: 0.70

Page 35

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room-6 Oven Top / Room summary

No.

Quantity

Glamox MIRZ54 236 PC


Light output ratio: 71.50%

135

150

165

180

165

150

135

160

120

120

120

80

See our luminaire catalog for


an image of the luminaire.

105

105

90

90

75

75

60

60

45

30

15

cd/klm
C0 - C180

15

30

45

= 72%
C90 - C270

Total luminous flux: 6700 lm, Total Load: 70 W


Specific connection value: 0.00 W/m = 0.00 W/m/100 lx (Ground area 0.00 m)

Page 36

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room-6 Oven Top / Workplane 13 / Results overview

Workplane 13 / Results overview


Results overview (Surface)
Result type

Average

Min

Max

Min/average

Min/max

Points (Relevant)

Perpendicular illuminance [lx]

107

38

264

0.354

0.144

32 x 32 (all)

Height of working plane: 1.000 m, Wall zone: 0.000 m


Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 37

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room-6 Oven Top / Workplane 13 / Value chart/Perpendicular illuminance (adaptive)

Workplane 13 / Value chart/Perpendicular illuminance (adaptive)

Scale: 1 : 10
Perpendicular illuminance (Surface)
Average: 107 lx, Min: 38 lx, Max: 264 lx, Min/average: 0.354, Min/max: 0.144, Points: 32 x 32 (Relevant: all)
Height of working plane: 1.000 m, Wall zone: 0.000 m
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 38

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room-8 Working Plane / Room summary

Room-8 Working Plane / Room summary

Scale: 1 : 50

Perpendicular illuminance (adaptive)


Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 8

422

0.52

977

0.001

0.001

64 x 128 (6370)

Workplane 14

553

216

1077

0.391

0.201

512 x 256 (90697)

Summary

0.52

1077

Height of room: 2.800 m, Reflection factors: Ceiling 63.6%, Walls 56.3%, Floor 27.5%, Light loss factor: 0.70
No.

Quantity

Glamox DLT RS(M)284 218 FR2


Light output ratio: 43.82%

105

105

90

90

75

75

60

60

See our luminaire catalog for


an image of the luminaire.

80

45

45

120

30

15

cd/klm
C0 - C180

15

30

= 44%
C90 - C270

Total luminous flux: 16200 lm, Total Load: 288 W


Page 39

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room-8 Working Plane / Room summary

Specific connection value: 15.91 W/m = 2.88 W/m/100 lx (Ground area 18.10 m)

Page 40

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room-10 Working Plane / Room summary

Room-10 Working Plane / Room summary

Scale: 1 : 50

Perpendicular illuminance (adaptive)


Name

Average [lx]

Min [lx]

Max [lx]

Min/average

Min/max

Points (Relevant)

Workplane 15

347

118

511

0.341

0.232

512 x 256 (92904)

Workplane 10

236

0.36

462

0.002

0.001

512 x 256 (93514)

Summary

0.36

511

Height of room: 2.800 m, Reflection factors: Ceiling 61.4%, Walls 78.2%, Floor 25.7%, Light loss factor: 0.70
No.

Quantity

Glamox DLT RS(M)284 218 FR2


Light output ratio: 43.82%

105

105

90

90

75

75

60

60

See our luminaire catalog for


an image of the luminaire.

80

45

45

120

30

15

cd/klm
C0 - C180

15

30

= 44%
C90 - C270

Total luminous flux: 21600 lm, Total Load: 384 W


Specific connection value: 0.00 W/m = 0.00 W/m/100 lx (Ground area 0.00 m)

Page 41

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room-10 Working Plane / Workplane 15 / Results overview

Workplane 15 / Results overview


Results overview (Surface)
Result type

Average

Min

Max

Min/average

Min/max

Points (Relevant)

Perpendicular illuminance [lx]

347

118

511

0.341

0.232

512 x 256 (92904)

Height of working plane: 1.000 m, Wall zone: 0.000 m


Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 42

Gurban Abasov_Galley Refurbishment

2/26/2014

Site 1 / Building 1 / Storey 1 / Room-10 Working Plane / Workplane 15 / Value chart/Perpendicular illuminance (adaptive)

Workplane 15 / Value chart/Perpendicular illuminance (adaptive)

Scale: 1 : 50
Perpendicular illuminance (Surface)
Average: 347 lx, Min: 118 lx, Max: 511 lx, Min/average: 0.341, Min/max: 0.232, Points: 512 x 256 (Relevant: 92904)
Height of working plane: 1.000 m, Wall zone: 0.000 m
Relevant points are points that are within the respective surface and are not covered by furniture or other elements. The summarized results are based
exclusively on these points, as all other points would falsify the results, in some cases significantly.

Page 43