Transformer sizing for PCC - LF [SS-LC08, =SL_944_901-UHL]

1 Formula used: 1.1 Working load in KVA= [Working load(KW)*L.F]/[D.F*P.F*Eff.] 1.2 System P.F = Total working load(KW)/Total Working Load(KVA) 2 Input data and calculations: Sr.no Item description Rating in KW Efficiency P.F L.F

Client: NMDC Consultant: MECON Project: NMDC BOF Work: VERIFICATION OF VOLTAGE DROP
D.F Connected Load Unit 1 1 FORMULAS 1 1

L.F=Load Factor P.F= Motor PF

Total(KW) 1146 200

Working load Unit Total(KW) 1 1 1146 200

Working load(KVA) [Working load(KW)*L.F]/[D.F*P.F*Eff.] 1432.5 225.6

2.1

Connected Load - Largest Rated Motor

1146 200

1 0.95

0.8 0.84

1 0.9

2.1 Booster Compressor Fan

3 4 5 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 5.10 5.11 5.12 5.13 5.14 5.15 5.16

Considering 20% contingency(KVA): System P.F:

1989.68 0.84 2000 6.25 200 0.433 0.84 0.95 349 225.6 1432.50 1669.17 1015.04 32.00 42.67 32000.00 9.69 7.65

[1.2*Working load(KVA)]

Calculation to check the starting of the largest size motor:


Rating of the transformer assumed(KVA): % Impedance of transformer assumed: Rating of the largest size motor(KW): Supply Voltage(KV): P.F of largest size Motor: Efficiency of largest size Motor: FLC of motor(A): Rating of largest size motor in KVA: Base load on transformer before starting largest motor (KVA): Motor starting KVA with DOL starter: Motor starting KVA with soft starter: Fault level at transformer secondary side (MVA): Fault current for transformer secondary side(Isc) (KA): S.C Capacity of transformer(KVA): Voltage drop at transformer terminal when largest motor is started with Voltage drop at transformer terminal when largest motor is started with Nearest standard size(Config. 6.6/0.433 KV, DYn 11) From IS 2026 From above table System voltage From above table From above table From motor datasheet From above table From above table [7.4*Rating of largest size motor in KVA] [4.5*Rating of largest size motor in KVA] [Rating of transformer in MVA]*100/[Impedance of transformer in %] [Fault level in MVA]/[1.7321*KV] [1.7321*KV*Isc] [Motor starting KVA(DOL)+Base load KVA]*100/[S.C capacity of transformer] [Motor starting KVA(S/D)+Base load KVA]*100/[S.C capacity of transformer]

Prep By : ARUNAVA BASAK

Ckd By

: ABHIJIT MANDAL

KVA Ratings-KVA ratings for 3 phase transformers are given in below table:
Table 1-KVA ratings for 3 phase transformers

KVA
5 6.3 8 10 12.5 16 20 25 31.5 40 50 63 80 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000

IS:2026(Part 1)-1977

TABLE-2: TYPICAL VALUES OF IMPEDANCE VOLTAGE FOR TRANSFORMERS WITH TW CURRENT,GIVEN AS A PERCENTAGE OF THE RATED VOLTAGE OF THE WINDING TO

Rated power(1) KVA


Up to 630 63 to 1250 1251 to 3150 3151 to 6300 6301 to 12500 12501 to 25000 25001 to 200000

R TRANSFORMERS WITH TWO SEPARATE WINDINGS(AT RATED OLTAGE OF THE WINDING TO WHICH THE VOLTAGE IS APPLIED

Impedance voltage(2)(%)
4.5 5 6.25 7.15 8.35 10 12.5