Lighting Radial sockets (13amp) Shower(17m) Lighting: Location Terrance Bath Master Bath Bedroom 1 Bedroom 2 Master Bedroom Dining Room Staircase
Cable Length 4 3 4 11 15 15 13 2
Watts 60 60 60 60 60 60 60 58
Switches and sockets 1.2m from finishes floor level. Sockets and switches height is : H=2.7-1.2 =1.5m
Remarks - For max. 50m2 floor area 21m cable Master Bedroom - For max. 20m2 floor area 17m cable Terrance, Bath, Master Bath, Bedroom 1, Bedroom 2, Dining Room and Staircase
Calculation Part: For 58 watts lighting: Amps = Watts Volts = 58 240 = 0.24 From table, select 1 mm2 c.s.a. Staircase: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.24 x 2.0) 1000 = 0.021 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory. For 60 watts lighting: Amps = Watts Volts = 60 240 = 0.25 From table, select 1 mm2 c.s.a. Terrance: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.25 x 4.0) 1000 = 0.044 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory. Bath: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.25 x 3.0) 1000 = 0.033 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory. Master Bath: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.25 x 4.0) 1000 = 0.044 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory.
Bedroom 1: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.25 x 11.0) 1000 = 0.121 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory. Bedroom 2: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.25 x 15.0) 1000 = 0.165 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory. Master Bedroom: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.25 x 15.0) 1000 = 0.165 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory. Dining Room: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.25 x 2.0) 1000 = 0.022 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory.
Shower Shower specification For Master Bath: Shower rating (kW) = 8.4 Cable length (m) = 5.0m Fuse of MCB rating (amps) = 40 Amps = Watts Volts = 8400 240 = 35 From table, select 10 mm2 c.s.a. (52 amps) Voltage drop = (mV x Current flowing x Cable length) 1000 = ( 4.4 x 35 x 5.0 ) 1000 = 0.77 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 10 mm2 c.s.a. cable is satisfactory. For Bath: Shower rating (kW) = 8.4 Cable length (m) = 3.0m Fuse of MCB rating (amps) = 40 Amps = Watts Volts = 8400 240 = 35 From table, select 10 mm2 c.s.a. (52 amps) Voltage drop = (mV x Current flowing x Cable length) 1000 = ( 4.4 x 35 x 3.0 ) 1000 = 0.462 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 10 mm2 c.s.a. cable is satisfactory. Lighting Radial sockets Shower 14 15 1 1 4 10 13 30 52 44 11 4.4
Diversity Standard of Diversity Factor Appliance / Circuit Lighting Radial sockets Shower Diversity for Domestic Installation Appliance / Circuit Lighting Double insulated shaver sockets Radial sockets 2 - 15 Shower Number of appliance / Circuit 8 2 22 2 Current Demand (amps) 13 30 30 52 Total = Diversity Allowance (amps) 8 x 13 x 66% = 84.48 2 x 30 x 100% = 60 22 x 30 x 40% = 264 2 x 52 x 100% = 104 512.48 amps Diversity factor 66% of the total current demand 100% of the largest circuit full load current + 40% of the remainder 100% of highest rated + 100% of second highest + 25% of any remaining