FIRST FLOOR Cable Rating: Standard applications Number Cable specification (mm2 c.s.a.

) 14 15 1 1 4 10 Current carrying in conduit 13 30 52 Voltage drop (mV/amp/m) 44 11 4.4

Lighting Radial sockets (13amp) Shower(17m) Lighting: Location Terrance Bath Master Bath Bedroom 1 Bedroom 2 Master Bedroom Dining Room Staircase

Cable Length 4 3 4 11 15 15 13 2

Watts 60 60 60 60 60 60 60 58

Switches and sockets 1.2m from finishes floor level. Sockets and switches height is : H=2.7-1.2 =1.5m

Remarks - For max. 50m2 floor area 21m cable Master Bedroom - For max. 20m2 floor area 17m cable Terrance, Bath, Master Bath, Bedroom 1, Bedroom 2, Dining Room and Staircase

Cable c.s.a (mm2) 2..5 4.0

Minimum overload protection (amps) 20 30

Calculation Part: For 58 watts lighting: Amps = Watts Volts = 58 240 = 0.24 From table, select 1 mm2 c.s.a. Staircase: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.24 x 2.0) 1000 = 0.021 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory. For 60 watts lighting: Amps = Watts Volts = 60 240 = 0.25 From table, select 1 mm2 c.s.a. Terrance: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.25 x 4.0) 1000 = 0.044 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory. Bath: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.25 x 3.0) 1000 = 0.033 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory. Master Bath: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.25 x 4.0) 1000 = 0.044 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory.

Bedroom 1: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.25 x 11.0) 1000 = 0.121 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory. Bedroom 2: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.25 x 15.0) 1000 = 0.165 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory. Master Bedroom: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.25 x 15.0) 1000 = 0.165 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory. Dining Room: Voltage drop = (mV x Current flowing x Cable length) 1000 = (44 x 0.25 x 2.0) 1000 = 0.022 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 1 mm2 c.s.a. cable is satisfactory.

Shower Shower specification For Master Bath: Shower rating (kW) = 8.4 Cable length (m) = 5.0m Fuse of MCB rating (amps) = 40 Amps = Watts Volts = 8400 240 = 35 From table, select 10 mm2 c.s.a. (52 amps) Voltage drop = (mV x Current flowing x Cable length) 1000 = ( 4.4 x 35 x 5.0 ) 1000 = 0.77 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 10 mm2 c.s.a. cable is satisfactory. For Bath: Shower rating (kW) = 8.4 Cable length (m) = 3.0m Fuse of MCB rating (amps) = 40 Amps = Watts Volts = 8400 240 = 35 From table, select 10 mm2 c.s.a. (52 amps) Voltage drop = (mV x Current flowing x Cable length) 1000 = ( 4.4 x 35 x 3.0 ) 1000 = 0.462 volts Maximum voltage drop = 240 x 4% = 9.6 volts. Therefore, 10 mm2 c.s.a. cable is satisfactory. Lighting Radial sockets Shower 14 15 1 1 4 10 13 30 52 44 11 4.4

Diversity Standard of Diversity Factor Appliance / Circuit Lighting Radial sockets Shower Diversity for Domestic Installation Appliance / Circuit Lighting Double insulated shaver sockets Radial sockets 2 - 15 Shower Number of appliance / Circuit 8 2 22 2 Current Demand (amps) 13 30 30 52 Total = Diversity Allowance (amps) 8 x 13 x 66% = 84.48 2 x 30 x 100% = 60 22 x 30 x 40% = 264 2 x 52 x 100% = 104 512.48 amps Diversity factor 66% of the total current demand 100% of the largest circuit full load current + 40% of the remainder 100% of highest rated + 100% of second highest + 25% of any remaining