SECTION 10270

ACCESS FLOORING
1. PART 1 - GENERAL
1.01 SECTION INCLUDES
A.

Floor support stringer framing system.

B.

Removable floor panels.

C.

Facia panels and stairs

D.

System electrostatic grounding.

1.02 REFERENCES
A.

ASTM E 84

Test for Surface Burning Characteristics of


Building Materials.

1.03 PERFORMANCE REQUIREMENTS


2

A.

Pedestals: Maximum axial load of 4.5 kN on 25 mm


without permanent deformation. Ultimate Strength shall
not be less than twice design load.

B.

Floor Panels: Conform to the following:


2

1.

Uniformly Distributed Load: 12 kN/m .

2.

Maximum Deflection: 2.4 mm

3.

Concentrated load of 6.9 MPa at any location


with maximum deflection of 2 mm.

4.

Ultimate Strength: Not less than twice design load.

5.

Flame Spread Requirement shall conform to one of


the following:
-

Class 1 in accordance with BS 476; Part 7


Class A in accordance with ASTM E 84
F 30 in accordance with DIN 4102

C.

Lateral Stability: Design system for lateral stability


in all directions, with or without panels in place.

D.

Grounding: Ground resistance for areas provided with


raised access flooring shall be in accordance with the
recommendations of Computer/Equipment manufacturer(s)
and shall be tested in accordance with NFPA 99.

10270-1
Access Flooring

1.04 SUBMITTALS
A.

Submit
shop
drawings
indicating
floor
layout,
interruptions to grid,
special
sized panels,
panels requiring
drilling
or
cut-out for
services,
appurtenances
or
interruptions, edge details, elevation differences and
stairs.

B.

Submit product
accessories.

C.

Submit 2 samples of floor grid and panel illustrating


finishes and color.

D.

Submit manufacturer's certificate showing that products


meet or exceed specified design strength and electrical
resistance requirements.

E.

Submit manufacturer's installation instructions.

F.

Maintenance Data: Submit maintenance data including


recommended cleaning methods, cleaning materials stain
removal methods, and polishes and waxes.

data

for

grid

system,

panels,

and

2. PART 2 - PRODUCTS
2.01 SUPPORT COMPONENTS
A.

Pedestals: Steel with flat bottom base plate, threaded


supporting rod, vibration-proof lock nut to permit
adjustment.
Pedestals
shall
have the
manufacturer's standard finish.

B.

Pedestal
to achieve
indicated on Drawings.

C.

Frame Grid Stringers: Continuous type, prepared for


loose installation; consisting of steel channels, box,
or tee sections.

finished

floor

elevation

as

2.02 PANEL COMPONENTS


A.

Floor Panels: Particle board high density composite


core laminated with galvanized sheet steel structurally
bonded with thermosetting adhesive. Panels shall have
protective edge trim on all edges.

B.

Floor Panel Size: 600 x 600 mm.

C.

Panel Thickness:

D.

Floor Panel Finish: Carpet tiles.

32 mm (Minimum).

10270-2
Access Flooring

E.

Floor
Panel
Finish
Adhesive:
Waterproof,
recommended by floor finish manufacturer.

type

F.

Facia Panels: Provide manufacturer's standard extruded


aluminum facing panels including corner pieces, trims,
reinforcing, and clip angles.

G.

Stairs:
Same materials,
structural
strength,
and
construction as floor panels with flush aluminum cover
plates.

2.03 ACCESSORIES
A.

Provide manufacturer standard electrical sockets, cable


trays, wall connection(s) as indicated on Drawings
and as required for proper installation.

B.

Electrostatic Grounding Connectors: Solid copper.

C.

Cable Cutout Protection: Extruded polyvinyl chloride or


neoprene edging, 3/8 inch thick, self-extinguishing.

D.

Panel Lifting Device: Provide recommended manufacturer


standard type.

E.

Gaskets: Closed cell sponge rubber, preformed to

suit. F.

Edge Trim: Extruded plastic angles or

channels.
G.

Sealant: Conform to the


Section 07900 - SEALANTS.

requirements

specified

in

2.04 FINISHES
A.

Exposed Metal Surfaces: Baked enamel finish,


shall be as selected by Engineer from
manufacturers standard range.

color

B.

Carpet Tiles: Refer to Section 09685 CARPET TILES.

2.05 FABRICATION TOLERANCES


A.

Floor Panel Flatness: Plus or minus 0.02 inch in any


direction.

B.

Floor Panel Width or Length From Specified Size: Plus


or minus 0.02 inch.

C.

Floor Panel Squareness: Plus or minus 0.03


difference between opposite diagonal dimensions.

inch

3. PART 3 - EXECUTION

10270-3

Access Flooring

3.01 EXAMINATION
A.

Verify that surfaces and openings are ready to receive


work.

B.

Verify field measurements are as shown on approved shop


drawings.

C.

Verify
that
required
sub-floor
utilities
available, in proper location, and ready for use.

D.

Beginning of installation
existing conditions.

means

installer

are

accepts

3.02 PREPARATION
A.

Clean substrate surfaces.

B.

Protect elements surrounding the work of this Section


from damage or disfiguration.

3.03 INSTALLATION
A.

Install components
instructions.

B.

Secure pedestal
fasteners.

C.

Install additional pedestals where grid pattern


interrupted by room appurtenances and at cutouts.

is

D.

Install
stringers
pedestals.

on

E.

Where required, install grilles or perforated

panels. F.

in accordance

base

plate

and

to

floor

with manufacturer's
subfloor

panels

with

metal

solidly

Seal field cuts of floor panels with edge

trim.
G.

Cut
holes
in floor
panels
for
installation
of
Owner's equipment as directed. Include cable cutout
protection.

H.

Provide floor, and stairswith


edge trim and end
closures. Provide lateral braces at stair edges and
other locations where a pedestal is not braced.

I.

Provide positive electrical earth grounding of entire


floor assembly.

3.04 FACIA PANELS


A.

Install facia panels at exposed sides and stair risers.


Access Flooring

10270-4

Access Flooring

B.

Secure panels to clip angles attached to subfloor


and edge of floor panels.

C.

Install metal trim at intersection of facia panels and


access floor and at abutting walls and columns.

3.05 ERECTION TOLERANCES


A.

Maximum Out of Level Tolerance: 1/16 inch in 10 ft

3.06 ADJUSTING, CLEANING AND PROTECTION OF FINISHED WORK


A.

Adjust pedestals to achieve a level floor and to assure


adjacent floor panel surfaces are flush.

B.

Clean exposed surfaces of all components in


accordance with manufacturer's instructions and
recommendations.

C.

Protect finished installation as required.

D.

Do not permit traffic over unprotected floor surface.

E.

Advise Engineer if flooring has been overloaded after


completion and prior to Substantial Performance.
END OF SECTION

10270-5